Report (2) Project: Brittany Homes-Oak Street Adult Foster Care Keithpage A Kudrna Location: Beam Nr.02-Header at Hallway net to Great Room F Suntel Design Roof Beam L 16865 Boones Ferry Rd of • [2012 International Building Code(2012 NDS)] - ! Lake Oswego,Oregon 97035 3.5 IN x 9.0 IN x 6.5 FT 24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.2.5 2/3/2016 12:15:12 PM Section Adequate By:57.0% Controlling Factor:Shear DEFLECTIONS Center LOADING DIAGRAM Live Load 0.09 IN U901 Dead Load 0.05 in Total Load 0.13 IN 0593 Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: 11180 REACTIONS A D Live Load 2681 lb 2681 lb Dead Load 1395 lb 1395 lb Total Load 4076 lb 4076 lb Bearing Length 1.79 in 1.79 in w DEAM DATA Span Length 6.5 ft Unbraced Length-Top 0 ft Unbraced Length-Bottom 0 ft Roof Pitch 0 :12 Roof Duration Factor 1.15 ROOF LOADING MATERIAL PROPERTIES Side One: 24F-V4-Visually Graded Western Species Roof Live Load: LL= 30 psf Base Values Adjusted Roof Dead Load: DL= 15 psf Bending Stress: Fb= 2400 psi Controlled by: Tributary Width: TW= 18 ft Fb cmpr= 1850 psi Fb'= 2760 psi Side Two: Cd=1.15 Roof Live Load: LL= 30 psf Shear Stress: Fv= 265 psi Fv'= 305 psi Roof Dead Load: DL= 15 psf Cd=1.15 Tributary Width: TW= 9.5 ft Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi Comp.1 to Grain: Fc- = 650 psi Fc-1'= 650 psi Wall Load: WALL= 10 plf Controlling Moment: 6624 ft-lb SLOPE/PITCH ADJUSTED LENGTHS AND LOADS 3.25 ft from left support Adjusted Beam Length: Ladj= 6.5 ft Created by combining all dead and live loads. Beam Self Weight: BSW= 7 plf Controlling Shear: 4077 lb Beam Uniform Live Load: wL= 825 plf At support. Beam Uniform Dead Load: wD_adj= 429 plf Created by combining all dead and live loads. Total Uniform Load: wT= 1254 plf Comparisons with required sections: Req'd provided Section Modulus: 28.8 in3 47.25 in3 Area(Shear): 20.07 in2 31.5 in2 Moment of Inertia(deflection): 64.58 in4 212.63 in4 Moment: 6624 ft-lb 10868 ft-lb Shear: 4077 lb 6400 lb NOTES Project: Brittany Homes-Oak Street Adult Foster Carel ►/ 41 page w Keith A Kudrna Location: Beam Nr.03-Dining Room Header to Rear Patio Suntel Design / Roof Beam " 16865 Boones Ferry Rd of [2012 International Building Code(2012 NDS)] y :Lake Oswego,Oregon 97035 5.5 IN x 12.0 IN x 12.5 FT 24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.2.5 2/3/2016 12:15:13 PM Section Adequate By:26.4% Controlling Factor: Moment DEFLECTIONS Center LOADING DIAGRAM Live Load 0.31 IN U481 Dead Load 0.16 in Total Load 0.47 IN U317 Live Load Deflection Criteria:U240 Total Load Deflection Criteria: U180 REACTIONS A )� Live Load 5063 lb 5063 lb Dead Load 2621 lb 2621 lb Total Load 7684 lb 7684 lb Bearing Length 2.15 in 2.15 in BEAM DATA Span Length 12.5 ft Unbraced Length-Top 0 ft Unbraced Length-Bottom 0 ft Roof Pitch 0 :12 Roof Duration Factor 1.15 ROOF LOADING MATERIAL PROPERTIES Side One: 24F-V4-Visually Graded Western Species Roof Live Load: LL= 30 psf Base Values Adjusted Roof Dead Load: DL= 15 psf Bending Stress: Fb= 2400 psi Controlled by: Tributary Width: TW= 17.8 ft Fb_cmpr= 1850 psi Fb'= 2760 psi Side Two: Cd=1.15 Roof Live Load: LL= 30 psf Shear Stress: Fv= 265 psi Fv'= 305 psi Roof Dead Load: DL= 15 psf Cd=1.15 Tributary Width: TW= 9.3 ft Modulus of Elasticity: E= 1800 ksi E= 1800 ksi Comp.1 to Grain: Fc-1= 650 psi Fc- = 650 psi Wall Load: WALL= 0 plf Controlling Moment: 24010 ft Ib SLOPE/PITCH ADJUSTED LENGTHS AND LOADS 6.25 ft from left support Adjusted Beam Length: Ladj= 12.5 ft Created by combining all dead and live loads. Beam Self Weight: BSW= 14 plf Controlling Shear: -7683 lb Beam Uniform Live Load: wL= 810 plf At support. Beam Uniform Dead Load: wD_adj= 419 plf Created by combining all dead and live loads. Total Uniform Load: wT= 1229 plf Comparisons with required sections: Read Provided Section Modulus: 104.39 in3 132 in3 Area(Shear): 37.82 in2 66 in2 Moment of Inertia(deflection): 450.11 in4 792 in4 Moment: 24010 ft-lb 30360 ft-lb Shear: -7683 lb 13409 lb NOTES Project: Brittany Homes-Oak Street Adult Foster Care NV,/ page • Keith A Kudrna Location: Beam Nr.04-Rear Patio Roof Beam i Suntel Design / Roof Beam L " 16865 Boones Ferry Rd of [2012 International Building Code(2012 NDS)] -*'!' Lake Oswego,Oregon 97035 5.5 IN x 11.5 IN x 9.0 FT #1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 2/3/2016 12:15:13 PM Section Adequate By: 193.4% Controlling Factor:Moment DEFLECTIONS Center LOADING DIAGRAM Live Load 0.04 IN 112473 Dead Load 0.02 in Total Load 0.07 IN 111605 Live Load Deflection Criteria: 11240 Total Load Deflection Criteria: U180 REACTIONS A B Live Load 1485 lb 1485 lb Dead Load 803 lb 803 lb Total Load 2288 lb 2288 lb Bearing Length 0.67 in 0.67 in BEAM DATA Span Length 9 ft Unbraced Length-Top 0 ft 9ft Unbraced Length-Bottom 0 ft Roof Pitch 0 :12 Roof Duration Factor 1.15 ROOF LOADING MATERIAL PROPERTIES Side One: #1 -Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf Base Values Adjusted Roof Dead Load: DL= 15 psf Bending Stress: Fb= 1300 psi Fb'= 1495 psi Tributary Width: TW= 9.5 ft Cd=1.15 CF=1.00 Side Two: Shear Stress: Fv= 170 psi Fv'= 196 psi Roof Live Load: LL= 30 psf Cd=1.15 Roof Dead Load: DL= 15 psf Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 1.5 ft Comp.1 to Grain: Fc- = 625 psi Fc-1'= 625 psi Wall Load: WALL= 0 Controlling Moment: 5148 ft-lb plf 4.5 ft from left support SLOPE/PITCH ADJUSTED LENGTHS AND LOADS Created by combining all dead and live loads. Adjusted Beam Length: Ladj= 9 ft Controlling Shear: 2288 lb Beam Self Weight: BSW= 13 plf At support. Beam Uniform Live Load: wL= 330 plf Created by combining all dead and live loads. Beam Uniform Dead Load: wD_adj= 178 plf Total Uniform Load: wT= 508 plf Comparisons with required sections: Req'd provided Section Modulus: 41.32 in3 121.23 in3 Area(Shear): 17.55 in2 63.25 in2 Moment of Inertia(deflection): 78.17 in4 697.07 in4 Moment: 5148 ft-lb 15103 ft-lb Shear: 2288 lb 8244 lb NOTES Project:Brittany Homes-Oak Street Adult Foster Care "'Keith A Kudrna page Location:Beam Nr.05-Rear Patio Roof Beam Fr. • Suntel Design• / Roof Beam "� 16865 Boones Ferry Rd of [2012 International Building Code(2012 NDS)] Lake Oswego,Oregon 97035 5.5 INx11.5INx11.5FT _ g , g #1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 2/3/2016 12:15:14 PM Section Adequate By:79.7% Controlling Factor:Moment DEFLECTIONS Center LOADING DIAGRAM Live Load 0.12 IN 01185 Dead Load 0.06 in Total Load 0.18 IN U769 Live Load Deflection Criteria: U240 Total Load Deflection Criteria: U180 REACTIONS A ]� Live Load 1898 lb 1898 lb Dead Load 1026 lb 1026 lb Total Load 2924 lb 2924 lb Bearing Length 0.85 in 0.85 in DEAM DATA Span Length 11.5 ft Unbraced Length-Top 0 ft 11.5 ft Unbraced Length-Bottom 0 ft Roof Pitch 0 :12 Roof Duration Factor 1.15 ROOF LOADING MATERIAL PROPERTIES Side One: #1 -Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf Base Values Adjusted Roof Dead Load: DL= 15 psf Bending Stress: Fb= 1300 psi Fb'= 1495 psi Tributary Width: TW= 9.5 ft Cd=1.15 CF=1.00 Side Two: Shear Stress: Fv= 170 psi Fv'= 196 psi Roof Live Load: LL= 30 psf Cd=1.15 Roof Dead Load: DL= 15 psf Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 1.5 ft Comp.1 to Grain: Fc-1= 625 psi Fc-1'= 625 psi Wall Load: WALL= 0 Controlling Moment: 8405 ft-lb plf 5.75 ft from left support SLOPE/PITCH ADJUSTED LENGTHS AND LOADS Created by combining all dead and live loads. Adjusted Beam Length: Ladj= 11.5 ft Controlling Shear: -2924 lb Beam Self Weight: BSW= 13 plf At support. Beam Uniform Live Load: wL= 330 plf Created by combining all dead and live loads. Beam Uniform Dead Load: wD_adj= 178 plf Comparisons with required sections: Read Provided Total Uniform Load: wT= 508 plf Section Modulus: 67.47 in3 121.23 in3 Area(Shear): 22.43 in2 63.25 in2 Moment of Inertia(deflection): 163.09 in4 697.07 in4 Moment: 8405 ft-lb 15103 ft-lb Shear: -2924 lb 8244 lb NOTES Project: Brittany Homes-Oak Street Adult Foster Care page Keith A Kudrna Location: Beam Nr.06-Front Porch Roof Beam Suntel Design / Multi-Loaded Multi-Span Beam 16865 Boones Ferry Rd of [2012 International Building Code(2012 NDS)] Lake Oswego,Oregon 97035 5.5 IN x 11.5 IN x 10.0 FT #1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 2/3/2016 12:15:14 PM Section Adequate By:85.5% Controlling Factor:Moment DEFLECTIONS Center LOADING DIAGRAM Live Load 0.07 IN 01827 Dead Load 0.05 in Total Load 0.11 IN U1070 Live Load Deflection Criteria:L/360 Total Load Deflection Criteria: L/240 REACTIONS A 1� Live Load 1342 lb 1783 lb Dead Load 961 lb 1254 lb Total Load 2303 lb 3037 lb TRf TR2 Bearing Length 0.67 in 0.88 in w BEAM DATA Center Span Length 10 ft Unbraced Length-Top 0 ft to n Unbraced Length-Bottom 10 ft Live Load Duration Factor 1.00 Notch Depth 0.00 UNIFORM LOADS Center MATERIAL PROPERTIES Uniform Live Load 45 plf #1 -Douglas-Fir-Larch(North) Uniform Dead Load 30 plf Base Values Adjusted Beam Self Weight 13 plf Bending Stress: Fb= 1300 psi Fb'= 1300 psi Total Uniform Load 88 plf Cd=1.00 CF=1.00 TRAPEZOIDAL LOADS-CENTER SPAN Shear Stress: Fv= 170 psi Fv'= 170 psi Load Number One Two Cd=1.00 Left Live Load 150 plf 338 plf Modulus of Elasticity: E= 1600 ksi E= 1600 ksi Left Dead Load 100 plf 225 plf Comp.1 to Grain: Fc-1= 625 psi Fc-1'= 625 psi Right Live Load 150 plf 338 plf Controlling Moment: 7079 ft-lb Right Dead Load 100 plf 225 plf Load Start 0 ft 3.75 ft 5.3 Ft from left support of span 2(Center Span) Load End 3.75 ft 10 ft Created by combining all dead loads and live loads on span(s)2 Load Length 3.75 ft 6.25 ft Controlling Shear: -3037 lb At right support of span 2(Center Span) Created by combining all dead loads and live loads on span(s)2 Comparisons with required sections: Read Provided Section Modulus: 65.34 in3 121.23 in3 Area(Shear): 26.8 in2 63.25 in2 Moment of Inertia(deflection): 156.33 in4 697.07 in4 Moment: 7079 ft-lb 13133 ft-lb Shear: -3037 lb 7168 lb NOTES • •• Project: Brittany Homes-Oak Street Adult Foster Care lk VW, Page Keith A Kudrna Location: Beam Nr.07-Garage Door Header , Suntel Design Roof Beam th; " 16865 Boones Ferry Rd of [2012 International Building Code(2012 NDS)] ...- - '.Lake Oswego,Oregon 97035 3.5 IN x 11.25 IN x 16.5 FT #2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 2/3/2016 12:15:14 PM Section Adequate By:97.6% Controlling Factor:Moment DEFLECTIONS Center LOADING DIAGRAM Live Load 0.15 IN U1315 Dead Load 0.10 in Total Load 0.25 IN U802 Live Load Deflection Criteria:U240 Total Load Deflection Criteria: L/180 REACTIONS A Live Load 495 lb 495 lb Dead Load 317 lb 317 lb Total Load 812 lb 812 lb Bearing Length 0.37 in 0.37 in BEAM DATA Span Length 16.5 ft Unbraced Length-Top 0 ft 16.5 ft Unbraced Length-Bottom 0 ft Roof Pitch 0 :12 Roof Duration Factor 1.15 ROOF LOADING MATERIAL PROPERTIES Side One: #2-Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf Base Values Adjusted Roof Dead Load: DL= 15 psf Bending Stress: Fb= 850 psi Fb'= 1075 psi Tributary Width: TW= 1 ft Cd=1.15 CF=1.10 Side Two: Shear Stress: Fv= 180 psi Fv'= 207 psi Roof Live Load: LL= 30 psf Cd=1.15 Roof Dead Load: DL= 15 psf Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 1 ft Comp. L to Grain: Fc--L= 625 psi Fc--- = 625 psi Wall Load: WALL= 0 Controlling Moment: 3347 ft-lb plf 8.25 ft from left support SLOPE/PITCH ADJUSTED LENGTHS AND LOADS Created by combining all dead and live loads. Adjusted Beam Length: Ladj= 16.5 ft Controlling Shear: 812 lb Beam Self Weight: BSW= 8 plf At support. Beam Uniform Live Load: wL= 60 plf Created by combining all dead and live loads. Beam Uniform Dead Load: wD_adj= 38 plf Comparisons with required sections: Read provided Total Uniform Load: wT= 98 plf Section Modulus: 37.36 in3 73.83 in3 Area(Shear): 5.88 in2 39.38 in2 Moment of Inertia(deflection): 93.19 in4 415.28 in4 Moment: 3347 ft-lb 6615 ft-lb Shear: 812 lb 5434 lb NOTES Qroject Brittany Homes-Oak Street Adult Foster Care \NW page Keith A Kudrna Location: Beam Nr.08-Storage Room Header Suntel Design / Multi-Loaded Multi-Span Beam `_ • 16865 Boones Ferry Rd of [2012 International Building Code(2012 NDS)] ---- "" Lake Oswego, Oregon 97035 3.5 IN x 11.25 IN x 4.5 FT #2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 2/3/2016 12:15:15 PM Section Adequate By:283.8% Controlling Factor:Shear DEFLECTIONS Center LOADING DIAGRAM Live Load 0.00 IN UMAX Dead Load 0.00 in Total Load 0.01 IN U8560 Live Load Deflection Criteria: U360 Total Load Deflection Criteria: U240 1 REACTIONS A a Live Load 798 lb 399 lb Dead Load 433 lb 236 lb ;t Total Load 1231 lb 635 lb TR1 Bearing Length 0.56 in 0.29 in w BEAM DATA Center Span Length 4.5 ft Unbraced Length-Top 0 ft Unbraced Length-Bottom 4.5 ft Live Load Duration Factor 1.00 Notch Depth 0.00 UNIFORM LOADS Center MATERIAL PROPERTIES Uniform Live Load 45 plf #2-Douglas-Fir-Larch(North) Uniform Dead Load 30 plf Base Values Adjusted Beam Self Weight 8 plf Bending Stress: Fb= 850 psi Fb'= 935 psi Total Uniform Load 83 plf Cd=1.00 CF=1.10 Shear Stress: Fv= 180 psi Fv'= 180 psi POINT LOADS-CENTER SPAN Load Number One Cd=1.00 Live Load 700 Ib Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 300 lb Comp.1 to Grain: Fc-1= 625 psi Fc--- = 625 psi Location 1.33 ft Controlling Moment: 1338 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN 1.35 Ft from left support of span 2(Center Span) Load Number ung Two Created by combining all dead loads and live loads on span(s)2 Left Live Load 150 plf 30 plf Controlling Shear: 1231 lb Left Dead Load 100 plf 20 plf At left support of span 2(Center Span) Right Live Load 150 plf 30 plf Created by combining all dead loads and live loads on span(s)2 Right Dead Load 100 plf 20 plf Load Start 0 ft 1.33 ft Comparisons with required sections: Read Provided Load End 1.33 ft 4.5 ft Section Modulus: 17.18 in3 73.83 in3 Load Length 1.33 ft 3.17 ft Area(Shear): 10.26 in2 39.38 in2 Moment of Inertia(deflection): 11.64 in4 415.28 in4 Moment: 1338 ft-lb 5752 ft-lb Shear: 1231 lb 4725 lb NOTES eroject Brittany Homes-Oak Street Adult Foster Care Ilk VW, page Keith A Kudrna Location:Beam Nr.09-Patio Roof Beam at Rear Living Area ,r'. Suntel Design / Roof Beam "" 16865 Boones Ferry Rd of [2012 International Building Code(2012 NDS)] ' - Lake Oswego,Oregon 97035 3.5 IN x 7.25 IN x 6.0 FT #2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 2/3/2016 12:15:15 PM Section Adequate By:51.0% Controlling Factor:Moment DEFLECTIONS Center LOADING DIAGRAM Live Load 0.05 IN U1394 Dead Load 0.03 in Total Load 0.08 IN L/919 Live Load Deflection Criteria: 11240 Total Load Deflection Criteria: U180 REACTIONS 9 Live Load 945 lb 945 lb Dead Load 489 lb 489 lb Total Load 1434 lb 1434 lb Bearing Length 0.66 in 0.66 in BEAM DATA Span Length 6 ft Unbraced Length-Top 0 ft Eft Unbraced Length-Bottom 0 ft Roof Pitch 0 :12 Roof Duration Factor 1.15 ROOF LOADING MATERIAL PROPERTIES Side One: #2-Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf Base Values Adjusted Roof Dead Load: DL= 15 psf Bending Stress: Fb= 850 psi Fb'= 1271 psi Tributary Width: TW= 9 ft Cd=1.15 CF=1.30 Side Two: Shear Stress: Fv= 180 psi Fv'= 207 psi Roof Live Load: LL= 30 psf Cd=1.15 Roof Dead Load: DL= 15 psf Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Tributary Width: TW= 1.5 ft Comp.±to Grain: Fc- L= 625 psi Fc- = 625 psi Wall Load: WALL= 0 Controlling Moment: 2151 ft-lb plf 3.0 ft from left support SLOPE/PITCH ADJUSTED LENGTHS AND LOADS Created by combining all dead and live loads. Adjusted Beam Length: Ladj= 6 ft Controlling Shear: -1434 lb Beam Self Weight: BSW= 5 plf At support. Beam Uniform Live Load: wL= 315 plf Created by combining all dead and live loads. Beam Uniform Dead Load: wD_adj= 163 plf Comparisons with required sections: Read Provided Total Uniform Load: wT= 478 plf Section Modulus: 20.31 in3 30.66 in3 Area(Shear): 10.39 in2 25.38 in2 Moment of Inertia(deflection): 21.77 in4 111.15 in4 Moment: 2151 ft-lb 3247 ft-lb Shear: -1434 lb 3502 lb NOTES