SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:269-818-1680 Email:techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Quick Response Dry Horizontal Sidewall Sprinklers are thermosensitive � I �_
spray sprinklers suitable for use in areas subject to freezing. The sprinklers are II j I C
designed for dry systems and preaction systems where it is necessary to prevent I E_
water or condensation from entering the drop nipple before sprinkler operation.
They may also be installed in spaces subject to freezing and supplied from a wet
system in an adjacent heated area.
Viking Quick Response Dry HSW Sprinklers are available in various finishes '1' E .4.--
and
temperature ratings to meet design requirements. The special Polyester and
Electroless Nickel PTFE (ENT) coatings have been investigated for installation
in corrosive atmospheres and are listed/approved as corrosion resistant as indi-
cated in the Approval Charts. (Note: FM Global has no approval classification for
Polyester coatings as corrosion resistant.) it
NOTE: When installed in some corrosive environments, the Polyester finish
may change color.This natural discoloration over time is not in itself an indi-
cation of corrosion and should not be treated as such.All sprinklers installed For Light Hazard Occupancies Only
in corrosive environments should be replaced or tested as described in NFPA 25
on a more frequent basis.
2. LISTINGS AND APPROVALS
OcULus Listed: Category VNIV
O e FM Approved: Classes 2013 and 2015
<> NYC Approved: MEA 89-92-E,Volume 15
— Refer to Approval Chart 1 and Design Criteria on page 106c for cULus Listing requirements, and refer to Approval Chart 2
and Design Criteria on page 106d for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 1993.
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: 175 psi(12 bar).
Factory tested pneumatically to 100 psi (6.89 bar)
Thread size: 1"NPT or 25 mm BSP
Nominal K-Factor:5.6 U.S. (80.6 metric*)for all listed and approved lengths.
*Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
Glass-bulb fluid temperature rated to-65°F (-55°C)
Covered by the following U.S. Patent numbers: 8,636,075 and 8,376,060 Viking Technical Data may be found on
Material Standards: The Viking Corporation's Web site at
Frame Casting: Brass UNS-C84400 http://www.vikinggroupinc.com.
Deflector: Phosphor Bronze UNS-C51000 The Web site may include a more recent
Bulb: Glass, nominal 3 mm diameter edition of this Technical Data Page.
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with
PTFE Tape
Compression Screw: Brass UNS-C36000
Pip Cap: Brass UNS-C31400 or UNS-C31600
Pip Cap Adapter: Brass UNS-C36000
Orifice: Copper UNS-C22000 or UNS-C11000
Tube: ERW Hydraulic Steel Tube
Support(Internal): Stainless Steel UNS-530400
Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish
Barrel End and Threads: QM Brass
Sleeve(for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800
Escutcheon Materials:
Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800
Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080
ENT Coated Adjustable and Recessed Escutcheons: Stainless Steel UNS-S30400
Ordering Information: (Also refer to the current Viking price list.)
Order QR Dry HSW Sprinklers by first adding the appropriate suffix for the sprinkler finish,the appropriate suffix for the temperature rating,
and then the suffix for the length("A"dimension)to sprinkler base part number.Order in a specific length noted as the"A"dimension.The
"A"dimension is the distance from the face of the fitting(tee)to the desired finished surface of the wall in which it is to be installed.
Form No. F_031993 Rev 15.1
Page 2 of 8
NIKING® QUICK RESPONSE
TECHNICAL DATA DRY HORIZONTAL
SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
These sprinklers are listed and approved in lengths from 1-1/2"to 45-1/2"(38.1 mm to 1,156 mm)for the adjustable standard style,3"to
47"(76.2 mm to 1,194 mm)for the plain barrel style,and 3-1/4"to 47-1/2"(82.5 mm to 1,207 mm)for the adjustable recessed style.
Lengths exceeding the standard lengths are available,with no approvals,on a"made-to-order"basis:Recessed Dry HSW up to 65-
1/2"(1,664 mm).Adjustable Standard Dry HSW up to 63-1/2"(1,613 mm).Plain Barrel Dry HSW up to 65"(1,651 mm).Contact
the manufacturer for more information.
Finish Suffix: Brass=A, Chrome= F,White Polyester= M-/W,and ENT=JN
Temperature Suffix: 155°F(68°C)= B, 175°F(79°C)= D,200 °F(93 °C)= E,286°F(141 °C)=G
Escutcheon Suffix=Y for the adj.recessed sprinkler with the Model G-1 Escutcheon(no iveeded for me oriel -1, scutcheon).
For example, sprinkler VK182 with 1" NPT Threads, a Chrome finish, a 155 °F �r corr er } t Durres l G-1
Escutcheon, and "A"length of 10"= Part No. 08386UFBY10. for correct deflector orientation.)
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the"Sprinkler Accessories"section.) Protective
Sprinkler
Sprinkler Wrenches: Shield
A. Standard Wrench: Part No. 07297W/B(available since 1991)
B. Wrench for recessed sprinklers:Part No.07565W/B**(available since 1991) A.!',e �� •
**AY."ratchet is required(not available from Viking). i
Dry Sprinkler Protective Cover: Part No. 15610
Replacement Escutcheons: ��` �. r
A.Adjustable Standard Dry Escutcheon: Base Part No.08086F
B. Model E-1 Recessed Dry Escutcheon Cup: Base Part No.05459A Wrench
4. INSTALLATION Flat
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, VIKING 0)29) a))
causing the glass to shatter, releasing the internal parts to open the water-
way.Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire. Figure 1:
6. INSPECTIONS, TESTS AND MAINTENANCE Standard Sprinkler Wrench 07297W/B
Refer to NFPA 25 for Inspection,Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Quick Response Dry Horizontal Sidewall Sprinkler is available through a network of domestic and international distribu-
tors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Ordinary 155°F(68°C) 100°F(38°C) Red
Intermediate 175°F(79°C) 150°F(65°C) Yellow
Intermediate 200 °F(93°C) 150°F(65°C) Green
High 286°F(141 °C) 225°F(107°C) Blue
Sprinkler Finishes: Brass, Chrome,White Polyester, and ENT
Corrosion-Resistant Coating'':White Polyester and ENT in all temperature ratings
Footnotes
The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
The corrosion-resistant Polyester and ENT coatings have passed the standard corrosion test required by the approving agencies indi-
cated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Note: These coatings are
NOT corrosion proof.Prior to installation,verify through the end-user that the coatings are compatible with or suitable for the proposed
environment.Polyester and ENT coatings are applied to the exposed exterior surfaces only.Note that the spring is exposed on sprinklers
with Polyester and ENT coatings.
'When installed in some corrosive environments,the Polyester finish may change color.This natural discoloration over time is not in itself
an indication of corrosion and should not be treated as such.All sprinklers Installed in corrosive environments should be replaced or
tested as described in NFPA 25 on a more frequent basis.
Form No. F_031993 Rev 15.1
Page 3 of 8
NIKING® QUICK RESPONSE
TECHNICAL DATA DRY HORIZONTAL
SIDEWALL SPRINKLERS
The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464- Fax:269-818-1680 Email:t^e--chsvcs@vikingcorp.com
. ■*Note: A 1/2' ratchet Is required.
Sprinkler Wrench Part (Not available from Viking).
No. 07565W/B** for
installing recessed
dry sprinklers.
I L 1 I- •L _ i
�� is ■ { .�� ----t'. II
- ''r-gIEMI 1 III N
w- I 4 t= _�
,' :�..-� w 1, ---
" r la '1 r F ♦ .
1` 1 .I :
1_
Step 1i Carefully slide the Step 2: Press the wrench onto
wrench sideways around the the sprinkler wrench flats and
deflector and protective -turn slightly to ensure engage-
shield as shown. ment with the wrench flats.
Figure 2: Wrench 07565W/B for Adjustable Recessed Dry Horizontal Sidewall Sprinklers
For 'A' Dimension:
1. Determine the distance from the face of IIIIIIIIIIIIIIIIIIIII11111111111111111111ENOTE:
Deflector at
the tee to the finished face of the wall. Minimum Distance To locate the deflector
2. Round to the nearest 1/2' (12.7 mm) between Finished Ceiling , From veli at the minimum distance
from the wall, with no
1-1/2' (38.1 mm) and 45-1/2' (1,156 mm). adjustment available,
NOTE: The deflector will extend approximately Finished Wall order the standard dr
4-1/8' (104.8 mm) from the wall pwith 2' +1- 4' (102 mm) Minimum �•gg,i horizontal sidewall sprink-
1' (25.4 mm) horizontal adjustment available. 6' (152 mm) Maximum* , ler 1' (25.4 mm) shorter
EI 3-1/e' than the 'A' Dimension.
<79.4 mm)
�••���\\��N Deflector at NOTE:
,� I ■ 3-1/16' Maximum Distance To locate the deflector
I (77.8 mm) From wall at the maximum distance
�`O •
' ,' from the wall, with no
\�--i�p�� ■ } adjustment available,
� 111111
\ I J 1a '.i order the standard dry
5/8' (15.9 mm) horizontal sidewall sprink-
ler 1' (25.4 mm) longer
Minimum wall openingII 5-1/e' than the 'A' Dimension.
mm)
diameter: 1-3/4' (44.5 mm). I—Sleeve diameter: (13-1 8'
Maximum wall opening 1-1/2' (38.1 mm).
diameter: 2-1/4' (57 mm). 13/16' Sleeve finish matches w May be allowed up to 18' (457 mm) for certain
(20.6 mm) finish of escutcheon, FM installations. Refer to the appropriate installation
standards, including NFPA 13 and/or FM Loss
Prevention Data Sheet 2-0.
Figure 3: Adjustable Standard Dry Horizontal Sidewall Sprinkler
11111111111111111111111011111111111111.
lot—
Deflector
lot—Deflector -.-- 1110111111111111111111/11111111111111111I
-.- 1110111111111111111111111111111111111111I
Push and Rotate Slot
- D,/ .1116 - 01/h. _
08 11 ' 0/11 01'
011 Orpli '
_ . 111011!
111
Sleeve '!
STEP 1: Align the slot In STEP 2, Push the rounded STEP 3: Pull the escutcheon STEP 4. Push and rotate STEP 5, To minimize
the escutcheon with the end of the slot against the away from the near edge the escutcheon onto the visibility of the slot
horizontal surface of near edge of the deflector, of the deflector. Move the sleeve. In the escutcheon,
the deflector as shown. Push the far side of the near side of the escut- position the slot
escutcheon past the deflec- cheon over the deflector. at the top of the
tor, toward the sleeve, sprinkler sleeve.
Figure 4: Adjustable Standard Escutcheon Installation
Form No. F_031993 Rev 15.1
Page 4 of 8
NIKING) QUICK RESPONSE
TECHNICAL DATA DRY HORIZONTAL
SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:269-818-1680 Email:techsvcs@vikingcorp.com
Sprinkler Base Thread Size Nominal Order Length Listings and Approvals'
Part No.' SIN Style K-Factor2 Increment (Refer also to Design Criteria on page 106e.)
NPT BSP U.S. metric' Inches mm cULus5 NYC" VdS LPCB ((
08384U VK178 Adjustable 1" – 5.6 80.6 1/2' 12.7 Al,A5 Al – – –
16458U Standard -- 25 mm -- 80.6 1/2" 12.7 Al,A5 – – -- MEI
–
08386U VK182 Adjustable 1" – 5.6 80.6 1/4" 6.35 B2, B6 B2 -- -- — —
16454U Recessed -- 25 mm – 80.6 1/4" 6.35 B2,B6 – – -- — —
08388U VK174 Plain Barrel 1" – 5.6 80.6 1/2" 12.7 A3 A4
16456U -- 25 mm -- 80.6 1/2" 12.7 A3 -- -- -- –
Approved Finishes and"A"Dimensions
1* - Chrome, or White Polyester' sprinkler with a Chrome, Brass, or White Polyester Sleeve and
Escutcheon with"A"dimensions 1-1/2"to 45-1/2"(38.1 mm to 1,156 mm)
Approved Temperature Ratings 2* - Chrome, or White Polyester' with "A" dimensions 3-1/4" to 47-1/2" (82.5 mm to 1,207
A- 155 °F(68 °C), 175°F (79°C), 200°F mm)
(93°C), and 286°F(141 °C) 3-Chrome,Brass,White Polyester',or ENT'with"A"dimensions 3"to 47"(76.2 mm to 1,194 mm)
B- 155 °F (68 °C), 175 °F (79 °C), and 4-Chrome or Brass with"A"dimensions 3"to 47"(76.2 mm to 1,194 mm)
200°F(93°C) 5-ENT'sprinkler with an ENT'Sleeve and Escutcheon with"A"dimensions 1-1/2"to 45-1/2"(38.1
mm to 1,156 mm)
6-ENT'with "A"dimensions 3-1/4"to 47-1/2"(82.5 mm to 1,207 mm)
'Brass Finish is listed and approved but not standard offering,lead times of 6-8 weeks required.
(Matching Brass escutcheons are not available.)
Footnotes
' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 K-Factor applies for standard lengths("A"Dimensions indicated above).
3 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
4 This chart shows the listings and approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer
for any additional approvals.
5 Listed by Underwriter's Laboratories for use in the U.S.and Canada for Light Hazard occupancies only.
6 Accepted for use,City of New York Department of Buildings,MEA Number 89-92-E,Vol. 15.
'cULus Listed as corrosion resistant.
NOTE:When using CPVC fittings with Viking dry sprinklers,use only new Nibco Model 5012-S-Bl tees.When selecting other CPVC fittings,
contact Viking Technical Services.
cULus Listing Requirements;
Quick Response Dry Horizontal Sidewall Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edi-
tion of NFPA 13 for standard spray sprinklers.
• Limited to Light Hazard occupancies only.
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.
• Minimum spacing allowed is 6 ft.(1.8 m).
• Deflector must be positioned between 4"and 6"(102 mm and 152 mm)below the ceiling. Keep the top of the deflector oriented parallel with
the ceiling.
• Locate no less than 4"(102 mm)from end walls.
• Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers.The distance shall be measured
perpendicular to the wall.
• The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed.
IMPORTANT:Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers.Also refer to page DRY1-3 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data,the appropriate standards of NFPA, LPCB,APSAD,VdS or other similar organizations, and
also with the provisions of governmental codes,ordinances,and standards,whenever applicable.
Form No. F_031993 Rev 15.1
Page 5 of 8
NIKING QUICK RESPONSE
TECHNICAL DATA DRY HORIZONTAL
SIDEWALL SPRINKLERS
The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:269-818-1680 Email:techsvcs@vikingcorp.com
Sprinkler Base SINS le Thread Size Nominal K-Factor' Order Length Increment FM Approvals'
Part No.' ty BSP U.S. metric' Inches mm (Refer also to Design Criteria below.)
083841J ® -- 5.6 80.6 1/2" 12.7 Al
VK178 Adjustable Standard
16458U lin 25 mm -- 80.6 1/2" 12.7 Al
08386U El — 5.6 80.6 1/4" 6.35 B2
VK182 Adjustable Recessed
16454U 25 mm -- 80.6 1/4" 6.35 B2
08388U Ell — 5.6 80.6 1/2" 12.7 A3
VK174 Plain Barrel
16456U 25 mm -- 80.6 1/2" 12.7 A3
Approved Finishes and"A"Dimensions
1*- Bright Brass,Chrome,White Polyester,or ENT5 with"A"dimensions 1-1/2"to 45-1/2" (38.1
Approved Temperature Ratings mm to 1,156 mm)
A- 155°F(68°C), 175°F(79°C),200°F(93°C),and 2*-Bright Brass,Chrome,White Polyester,or ENT5 with"A"dimensions 3-1/4"to 47-1/2" (82.5
286°F(141 °C) mm to 1,207 mm)
B-155°F(68°C), 175°F(79°C),and 200°F(93°C) 3 - Brass,Bright Brass,Chrome,White Polyester,or ENT'"A"dimensions 3"to 47"(76.2 mm to
1,194 mm)
'Brass Finish is listed and approved but not standard offering,lead times of 6-8 weeks required.
(Matching Brass escutcheons are not available.)
Footnotes
' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 K-Factor applies for standard lengths("A"Dimensions indicated above).
3 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
4 This chart shows the FM Approvals available at the time of printing.Other approvals may be in process. Check with the manufacturer for
any additional approvals.
5 FM approved as corrosion resistant.
NOTE:When using CPVC fittings with Viking dry sprinklers,use only new Nibco Model 5012-S-BI tees.When selecting other CPVC fittings,
contact Viking Technical Services.
FM Aooroval Reauirementsz
The Dry HSW Sprinklers in the Approval Chart above are FM Approved as quick response Non-storage standard spray sprinklers as indicated in the
FM Approval Guide.For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including
2-0)and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to,but not
limited to:minimum water supply requirements,hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflec-
tor distance below the ceiling.
NOTE:The FM Installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT:Always refer to Bulletin Form No.F_091699-Care and Handling of Sprinklers.Also refer to page DRY1-3
for general care, installation,and maintenance information.Viking sprinklers are to be installed in accordance with the
latest edition of Viking technical data,the appropriate standards of NFPA,FM Global,LPCB,APSAD,VdS or other simi-
lar organizations,and also with the provisions of governmental codes,ordinances,and standards,whenever applicable.
Form No. F_031993 Rev 15.1
•
Page 6 of 8
NIKING® QUICK RESPONSE
TECHNICAL DATA DRY HORIZONTAL
SIDEWALL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services:877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
For 'A' Dimension:
1. Determine the distance from the face of
the tee to the face of the finished wall. 11111111111111111E
2. Round to the nearest 1/4' (6,35 rim)
between 3-1/4' (83 mm) and 47-1/2' (1,207 rim), Ceiling
NOTE: The sprinkler will be recessed approximately Wall
5/16' (7.9 mm) with 5/8' (16 mm) horizontal
adjustment available. 4' (102 mm) Minimum
6' (152 mm) Maximums
A
_I
�! 5/8' (16 mm)
I
�\ t ill
I I � 3-1/16'
(77.8 mm)
I
Minimum wall opening: I
2-1/8' (54 mm) diameter. I7'11
Maximum wall opening: "ii"
2-1/2' (63.5 mm) diameter. Available
Adjustment
1-23/32' (43.7 mm) Minimum
* May be allowed up to 18' (457 mm) for certain 2-11/32' (59.5 mm) Maximum
FM installations. Refer to the appropriate installation
standards, including NFPA 13 and/or FM Loss 5/16' (7.9 rim) Outward Adjustment
Prevention Data Sheet 2-0. 5/16' (7.9 mm) Inward Adjustment
Figure 5: Adjustable Recessed Dry Horizontal Sidewall Sprinkler with the Model E-1 Escutcheon
Side outlet of u
Tee turned to VII \,�.\ For 'A' Dimensions
req'd angle for 'i ', 1a 1
slope of ceiling 1 / tV 1. Measure B Dimension from centerline of the
1
face of the tee to the horizontal centerline
111 '/ of the wall opening.
Adopter ,try �/ 2. Measure C Dimension from the centerline of
Ring the Face of the tee to the finished wall
q 3. Calculate 'A' Dimension using: A = VB2+ C 2
rnmig......
NOTE.A Dimension will provide opproolmotely 1/4'
of (adjustment In either direction.
Depth:
1-1/16'
(27 mm)
1/8'
3.2
Ad ustuble �(� mm> //// Ceiling
Outer Lu
Ii ..
//////I//c
p� /
Deflector distance
�`,I■ 4-6' (102 to 152 mm)
2-5/8' 4• /__\11-_ below the ceiling.■
(6 I"") (102^") Minimum wall opening: When measuring for
L 2-5/8' (66 mm) diameter. the 'A' Dimension,
Maximum wall openings the exact deflector
3 3/4' (95 mm) diameter. Wall distance below the
ceiling must be known.
C 8 May be allowed up to 18' (457 mm)
1-1/16'I for certain FM Installations. Refer to
(27 mm>I the appropriate installation standards,
including NFPA 13 and/or FM Loss
Prevention Data Sheet 2-0.
Figure 6: Adjustable Recessed Dry Horizontal Sidewall Sprinkler with the Model G-1 Escutcheon
Form No. F_031993 Rev 15.1
Page 7 of 8
NIKING® QUICK RESPONSE
TECHNICAL DATA DRY HORIZONTAL
SIDEWALL SPRINKLERS
The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
For 'A' Dimension. IIIIIuIIIIIIIIuIIIIII'
1. Determine the distance from the face of
the tee to the base of the sprinkler. Ceiling
2. Round to next highest 1/2' (12.7 mm)
increment, between 3' (76.2 mm) and Wall
47' (1,194 mm). 4' (102 mm) Minimum
6' (152 mm) Maximum*
A 2-3/16'
(51 mm)1
•
`'1111
I �\ I 5/8' (16 mm)
111
Outside diameter: 1-5/16'
(33.4 mm). (Same as 1' Do not exceed 6' (152 rim).
(25 mm) Schedule 40 pipe. Do not recess wrench boss.
* May be allowed up to 18' (457 mm) for certain
FM installations, Refer to the appropriate installation
standards, including NFPA 13 and/or FM Loss
Prevention Data Sheet 2-0.
Figure 7: Quick Response Plain Barrel Dry Horizontal Sidewall Sprinkler
Top View-Dry HSW Sprinkler
Side View-Sprinkler Cover 15610
NOTE: Shown with an Adjustable Standard
Dry HSW Sprinkler.The protective cover may
also be used with the Adjustable Recessed Press the cover together
or Plain Barrel style Dry HSW Sprinkler. until it snaps closed.
--- •i\\tel - ---
I Til m
/ Ego
After the sprinkler is installed, / ♦ /
carefully place the cover over J J
the dry sprinkler as shown. NOTE: Remove the sprinkler clip and cover
before placing the system in service!
Figure 8: Dry Horizontal Sidewall Sprinkler Cover Part Number 15610(shown with an Adjustable Standard Dry HSW Sprinkler)
(Optional for temporary use with Viking Dry HSW Sprinklers until finish work is completed around the sprinkler.)
Form No. F_031993 Rev 15.1
•
Page 8 of 8
1
II(II1E ®
QUICK RESPONSE
TECHNICAL DATA DRY HORIZONTAL
SIDEWALL SPRINKLERS
The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:269-818-1680 Email:techsvcs@vikingcorp.com
5 1/B'
(130.2
Seal the clearance space around the sprinkler barrel to avoid Maximum
leakage of air Into the protected area and consequent formation
•
of condensate around the sprinkler frame, which could inhibit
operation or cause premature operation. Refer to Figure 10. ,M -1
i
If humidity and temperature „I„, - � NOTE To locate the
differential causes condensation IIII = Deflector at deflector at the
> Maximum Distance
on the exposed dry sprinkler IIII - maximum distance from
barrel, consider wrapping the ilii From Wall
pp g l it the wall, with no
exposed barrel with insulation, Ilii 13/16' \ adjustment available,
foam insulating tape, or equivalent. illi (206 mm) Ceiling order the standard
lid dry horizontal side-
Install the 1' NPT threaded illi 4' (102 mm) Minimum wall sprinkler 1'
end of the dry sidewall sprink- liii 6' (152 mm) Maximums longer than the 'A'
ler into the 1' NPT outlet of ::i::: 1 Sleeve finish dimension.
a malleable Iron tee fitting per ;l: ,��, matches
ANSI B 16.3 (Class 150> or ast — 'y;D;li- escutcheon Up to 2' (50.8 mm)
iron threaded tee fittingper \,�N
ANSI 16.4 (Class 125) only. \\II �(7781mm) adjustment is available.
��...!I•\Nir' — 01111/1145:
'
Minimum wall opening' n. (15.9 mm) 3-1/8'
ill
diameters 1-3/4' (44.5 mm) (79.4 mm)
Maximum wall opening (Exposed ; Minimum
diameter, 2-1/4' (57 mm). Barrel) 1 1/2' NOTE, To locate the
(38.1 mm) deflector at the
diameter minimum distance from
Exposed Barr
Ambient Outer ,�- thejwall, available,vai n
Mil
Ambient Temperature
Temperature 40'F/4'Cl50'F/10'C�60'F/16•C Surface 1 - adjustment
of Protected of the Wall order the standard
Areas at the Exposed Minimum Barrel FIN , dry horizontal side-
Discharge End Lengthwss Face of the wall sprinkler 1'
of the Sprinkler Tee to the Outer Deflector at shorter than the
Surface of the Vnll Minimum Distance •A' dimension.
In.(M) In.(mm) In.(rm) From Wall
40'F (4'C) 0 0 0
301- (-1'C) 0 0 0 (May be allowed up to 18' (457 mm) for certain FM
20'F (-7'C) 4 (100) 0 0 Installations, Refer to the appropriate installation standards,
10•F (-12•C) 8 (203) 1 C25.4) 0 including NFPA 13 and/or FM Loss Prevention Data Sheet 2-0.
0•F (-18'C) 12 (305) 3 (76) 0 ww(The protected area refers to the area below the ceiling,
-10'F (-23'014 (356) 4 (102) 1 (25.4) The ambient temperature is the temperature at the discharge end of the sprinkler.
-20•F (-29•C)14 (356)6 (152) 3 (76) For protected area temperatures that occur between the
-30'F (-34'C)16 (406)8 (203)4 (102) values listed, use the next cooler temperature.
-40•F (-40'C)18(457)8 (203)4 (102) ***The minimum required barrel length is not the same as the 'A' dimension.
-50'F (-46'C)20(508)10 (254)6 (152) Refer to Figures 3, 5, and 7 for the 'A' dimension.
-60'F (-51'C)20(508)10 (254)6 (152) Exposed minimum barrel lengths are inclusive up to 30 mph wind velocities.
Figure 9: Dry Horizontal Sidwall Sprinkler Required Minimum Barrel Length Based on Ambient Temperature In the Protected Area
(Adjustable Standard Dry HSW Sprinkler Is Shown)
Seal I Seal
<or equivalent q s. k
method)
III IUB �� \ I� II!
1! ��
,, 1 1
Clearance
Opening Z
Insulated § § Insulated
Wall Wall
Dry Sprinkler Seal on the Exterior of the Wall Dry Sprinkler Seal Within the Wall
Figure 10: Dry Sprinkler Seal(Adjustable Standard Dry HSW Sprinkler is Shown)
Form No. F_031993 Rev 15.1