Report (52) , SAS. ao/1-1-46 .06/ 7, C) I s(2 04 72_, RECEIVED ti,tti JAN 0 2 2014 Worldwide Contacts www.tyco-fire.com CITY OF TIGARD RtuI1 IIINC EliVICIfIN Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers - — - Description described herein must be installed and maintained in compliance with this doc- The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable f Upright(TY313)and Pendent(TY323) standards of the National Fire Protec- Sprinklers described in this data sheet tion Association,in addition to the stan- ...1•-, , are quick response,standard coverage, dards of any other authorities having ' - decorative 3 mmglass bulb-type spray jurisdiction.Failure to do so impair :x• , 1 Yp p Ymay Y sprinklers designed for use in light or the performance of these devices. —_�it _. `. -� , iliktifer.r ordinary hazard,commercial occupan- The owner is responsible for maintain- _ i ¢ cies such as banks, hotels,and shop- ing their fire protection system and = '` ping malls. devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent , t sprinkler uses one of the following: v Sprinkler c_.4,.......,:--;t:...75:1-, • A two-piece Style 15 Recessed - - - 1 Escutcheon with recessed adjust- Identification ,a 8 : ment up to 5/8 inch (15,9 mm)from the flush pendent position. Number (SIN) ,t -= '' • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT r ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT the flush pendent position. _ '; The adjustment provided by the Technical Recessed Escutcheon reduces the Finishes accuracy to which the fixed pipe drops Data Sprinkler: Natural Brass,Chrome to the sprinklers must be cut. Plated,Pure White(RAL 9010)and Intermediate level versions of Series Approvals Signal White(RAL 9003). TY-FRB Sprinklers are n described is UL and C-UL Listed Recessed Escutcheon:White Coated, Technical Data Sheet TFP357. Sprin- FM and VdS Approved Chrome Plated,or Brass Plated kler guards and shields are described CE Certified Physical Characteristics in Technical Data Sheet TFP780. Maximum Working Pressure Frame Bronze 175 psi(12.1 bar) Button Brass/Copper 250 psi(17.2 bar)* Sealing Assembly Stainless The maximum working pressure of 250 psi Steel w/TEFLON (17.2 bar)only applies to the listing by Un- Bulb Glass derwriters Laboratories,Inc.(UL). Compression Screw Bronze Deflector Bronze IMPORTANT Discharge Coefficient K=5.6 GPM/ps1112(80,6 LPM/barlI2) Always refer to Technical Data Sheet TFP700 for the "INSTALLER Temperature Rating WARNING" that provides cautions 135°F(57°C) with respect to handling and 155°F(68°C) installation of sprinkler systems and 175°F(79°C) components. Improper handling and 200°F(93°C) installation can permanently damage 286°F(141°C) a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 JANUARY 2013 TFP172 4 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* ��....., — \ __„_- ._—_-- i .I.i,f,Iri q\. iirrri-i,�_����m 5 =I 7/16" Y -= (11,1 mm) t fur 4 NOMINAL 2" I) (I R i MAKE-IN .4 (50,8 mm) 1 1 �, 3 1 W rr (50,8 mm) 1 ___ (34,9/mm) I ��� WRENCH G ! / 1 FLATS 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. — CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE L. Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, WRENCH RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached,the Sprinklers must be installed in accor- END"A") fluid expands sufficiently to shatter the dance with this section. glass bulb, allowing the sprinkler to General Instructions - FIGURE 2 activate and water to flow. Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally,a small air WRENCH bub- Criteria ble should be present. The diameter of the air bubble is approximately 1/16 RECESS The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) �,yr Sprinklers are intended for fire protec- temperature ratings. s tion systems designed in accordance with the standard installation rules rec- ognized by the applicable Listing or should be obtained by applying a min- Approval agency(such as, UL Listing imum to maximum torque of 7 to 14 Sr is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels II �.�� 13, and FM Approval is based on the of torque can distort the sprinkler Inlet PUSH WRENCH requirements of FM's Loss Prevention with consequent leakage or impairment IN TO ENSURE Data Sheets).Only the Style 15 or Style of the sprinkler. ENGAGEMENT 20 Recessed Escutcheon is to be used Do not attempt to compensate for WITH SPRINKLER for recessed pendent installations. insufficient adjustment in the Escutch- WRENCHING AREA eon Plate by under-or over-tightening the sprinkler. Re-adjust the position of FIGURE 3 the sprinkler fitting to suit. W--TYPE 7 RECESSED Upright and Pendent Sprinklers SPRINKLER WRENCH The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. ., TFP172 Page 3 of 4 Step 3.Tighten the sprinkler into the 2-7/8"DIA. sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench(Figure 2).With ref- . erence to Figure 1, apply the W-Type 6 2-1/4"DIA. Sprinkler Wrench to the wrench flats. FACE OF ~ (57,2 mm) — Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers i \ on FLUSH The Series TY-FRB Recessed Pendent --_- ------1 I I Sprinklers must be installed in accor- 3/±7,9 m" P (9,517,9 mm) 1 � Iv dance with the following instructions. } / il Step A.After installing the Style 15 or MOUNTING ' 1/8" j I Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread - -_ - — I sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE 3/4"(19,1 mm) sprinkler fitting. Step B.Tighten the sprinkler into the FIGURE 4 sprinkler fitting using only the W-Type SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) 7 Recessed Sprinkler Wrench(Figure WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 3).With reference to Figure 1,apply the RECESSED ESCUTCHEON W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8"DIA. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER 2-1/4"DIA. ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- kler and push the Closure over the 5/16±1/4" 1/2"(12,7 mm) Mounting Plate until its flange comes in (7,9±6,4 mm) contact with the ceiling. I FLUSH Care and f I Maintenance MOUNTING IN 3,2 mm) SURFACE The TYCO Series TY-FRB,5.6 K-factor, ---_--- I Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE viced in accordance with this section. 7/8"(22,2 mm) Before closing a fire protection system FIGURE 5 main control valve for maintenance SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) work on the fire protection system WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 that it controls, obtain permission to RECESSED ESCUTCHEON shut down the affected fire protection systems from the proper authorities Modified sprinklers must be replaced. of the National Fire Protection Associa- and notify all personnel who may be Sprinklers that have been exposed to tion (e.g., NFPA 25), in addition to the affected by this action. corrosive products of combustion, but standards of any other authorities hav- Absence of the outer piece of an have not operated,should be replaced ing jurisdiction. Contact the installing escutcheon, which is used to cover if they cannot be completely cleaned contractor or sprinkler manufacturer a clearance hole, can delay sprinkler by wiping the sprinkler with a cloth or regarding any questions. operation in a fire situation, by brushing it with a soft bristle brush. Automatic sprinkler systems are rec- The owner must assure that the sprin- Care must be exercised to avoid dam- ommended to be inspected, tested, klers are not used for hanging any age to the sprinklers- before, during, and maintained by a qualified Inspec- objects and that the sprinklers are only and after installation.Sprinklers dam- tion Service in accordance with local cleaned by means of gently dusting aged by dropping, striking, wrench requirements and/or national codes. with a feather duster;otherwise, non- twist/slippage, or the like, must be operation in the event of a fire or inad- replaced. Also, replace any sprinkler vertent operation may result. that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Sprinklers which are found to be leak- Section.) . ing or exhibiting visible signs of corro- sion must be replaced. The owner is responsible for the Automatic sprinklers must never be inspection,testing,and maintenance of P their fire protection system and devices painted, plated, coated, or other- in compliance with this document,as wise altered after leaving the factory. well as with the applicable standards TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(112"NPT) TY313 4 SIGNAL WHITE(RAL 9003) 155 155`F(68°C) 371 5.6K PENDENT(112"NPT) TY323 3 PURE WHITE(RAL 9010)°° 175 175°F(79°C) Use suffix 1"for ISO 7-1 connection; 9 CHROME PLATED 200 200'F(93°C) for example,77-370-4-175-I Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS —PART NUMBER SELECTION- Ordering Procedure Contact your local distributor for avail- ability.When placing an order,indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (SIN), K=5.6, (Upright or Pendent) Sprinkler Quick Response, (specify) temperature rat- ing,(specify)finish, P/N(Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish, P/N(specify") Specify: Style 20 Recessed Escutch- eon with(specify")finish,P/N(specify") "Refer to Technical Data Sheet TFP770. Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 Copyright®2013 Tyco Fire Products,LP. All rights reserved. two TEFLON is trademark of The DuPont Corporation. 'f ti. ci Worldwide Contacts www.tyco-fire.com Series TY-B — 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General be consulted with respect to the suit- ability of these coatings for any given - Description corrosive environment.The effects of - "~M ambient temperature,concentration of :.,r ;�# The TYCO Series TY-B, 2.8, 5.6, and chemicals,and gas/chemical velocity, " 8.0 K-factor, Upright and Pendent should be considered,as a minimum, I Sprinklers described in this data sheet along with the corrosive nature of the are standard response - standard chemical to which the sprinklers will be i coverage,decorative 5 mm glass bulb exposed. a type spray sprinklers designed for use An intermediate level version of the in light,ordinary,or extra hazard,corn- Series TY-B Pendent Sprinkler can be 1` 1 " : mercial occupancies such as banks, obtained by utilizing the Series TY-B hotels, shopping malls, factories, Pendent Sprinkler in combination with refineries,and chemical plants. the Model S2 Shield. ( ' The recessed version of the Series TY-B Pendent Sprinkler,where appli- NOTICE � � cable, is intended for use in areas with The TYCO Series TY-B Sprinklers a finished ceiling. It uses a two-piece described herein must be installed „ Style 10(1/2 inch NPT)or Style 40(3/4 and maintained in compliance with h inch NPT)Recessed Escutcheon.The this document, as well as with the of 1 ; Recessed Escutcheon provides 1/2 applicable standards of the National inch(12,7 mm)of recessed adjustment Fire Protection Association,in addition or up to 3/4 inch (19,1 mm) of total to the standards of any other authori- ' , adjustment from the flush pendent ties having jurisdiction.Failure to do so position.The adjustment provided by may impair the performance of these , the Recessed Escutcheon reduces the devices. - ...- accuracy to which the fixed pipe drops to the sprinklers must be cut. The owner is responsible for maintain- ing ` their fire protection system and Corrosion resistant coatings, where devices in proper operating condition. applicable, are utilized to extend the The installing contractor or sprinkler life of copper alloy sprinklers beyond manufacturer should be contacted with that which would otherwise be obtained any questions. when exposed to corrosive atmo- spheres.Although corrosion resistant coated sprinklers have passed the Sprinkler standard corrosion tests of the appli- cable approval agencies, the testing Identification is not representative of all possible corrosive atmospheres.Consequently, Numbers it is recommended that the end user TY1151 Upright 2.8K,1/2""NPT TY1251 .... Pendent 2.8K,1/2"NPT TY3151 Upright 5.6K,1/2"NPT IMPORTANT TY3251 .... Pendent 5.6K,1/2"NPT Always refer to Technical Data TY4151 Upright 8.0K,3/4"NPT Sheet TFP700 for the "INSTALLER TY4251 .... Pendent 8.0K,3/4""NPT WARNING" that provides cautions TY4851 Upright 8.0K,1/2""NPT with respect to handling and TY4951 .... Pendent 8.0K,1/2"NPT installation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 MARCH 2013 TFP151 TFP151 , Page 2 of 8 CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 7 3 - Sealing 6 - Deflector* • ❑i - —— -�-� Assembly 7 - Bushing lijiY 1 ,t¢ 1 4 - Bulb 7/16" 2-1/4" NOMINAL I (57,2 mm) �' . MAKE IN 1 r r 2e rating is r__ 2-3/16" 1-9/16" 4 indicated on Deflector. I (55,6 mm) 1 I (39,7 mm) C' 5 ** Pipe thread connections \ + II 1.i 6* per ISO 7-1 can be 1 /�l! �� ��� provided on special 1/2"NPT** I WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 1 SERIES TY-B UPRIGHT(TY1151)AND PENDENT(TY1251)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT,STANDARD RESPONSE * ti - Temperature rating Pipe thread connections per 1 - Frame 3 - Sealing 5Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE ,//7TOh) 7��CCOk, - �i 1 7/16" ___ i / I ' 3(11,1mm) 40 ANOMINAL 2 3/16" �� -" 2 _ } -rGMAKE-IN I (55,6 mm) I , j (55,6/mm) I ' 1-1/2" 1�F 4 (38,1 mm) - \ -__,���--- _,ate _1�_—5 6* 1/2"NPT** t WRENCHSTYLE 10 Imo---2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 SERIES TY-B UPRIGHT(TY3151)AND PENDENT(TY3251)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT,STANDARD RESPONSE TFP151 Page 3 of 8 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* • SURFACE Y 1 1/2.. '� 3 ' (12,7 mm) .111111-41 ' krd NOMINAL N f0 2-5/16" !� 2 j 'W =� MAKE IN I (58,7 mm) —i (57,2/mm) ' 1-9/16" 4 (39,7 mm) A �. � 6* 3/4"NPT** f WRENCH STYLE 40 I 2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 SERIES TY-B UPRIGHT(TY4151)AND PENDENT(TY4251)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT,STANDARD RESPONSE CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 1 3 - Sealing 6 - Deflector* 11 i,17�7TYT-T , t Assembly y 3 4 - Bulb ' 7/16" ,t (11,1 mm) 2-1/4" ,s f* NOMINAL i I t (57,2 mm) ,� iJ 2 MAKE-IN A I *Temperature rating is I I 2-3/16" I 1-9/16" 4 indicated on Deflector. (55,6 mm) (39,7 mm) \ ■ I �_ �—5 ** Pipe thread connections 11 ,q+ per ISO 7-1 can be 6* provided on special 1/2"NPT** t WRENCH r request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 4 SERIES TY-B UPRIGHT(TY4851)AND PENDENT(TY4951)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT,STANDARD RESPONSE TFP151 Page 4 of 8 SPRINKLER FINISH(See Note 8) • K TYPE TEMP. BULB LIQUID NATURAL CHROME WHITE*** LEAD WAX WAX OVER BRASS PLATED POLYESTER COATED COATED LEAD COATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red 2.8 (Tand 1) 175°F(79°C) Yellow 1,2,3 1/2" PENDENT N/A NPT (TY7251) 200°F(93°C) Green Figure 1 286'F(141°C) Blue 360°F(182°C) Mauve 1,2 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY3151) 1,2,3,5 1,2,3,5 and 175°F(79°C) Yellow PENDENT 1,2,3,4,5,6,7 1,2,3,5 (TN325 DE 200°F(93°C) Green 5.6 Figure 2 286°F(141°C) Blue 1**,2**,3**,5** 1**,2**,3**,5"* 1/2" 360°F(182°C) Mauve N/A NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT1,2,3,4,5 (TY3251)* 175°F(79°C) Yellow N/A Figure 5 200°F(93°C) Green 286°F(141°C) Blue 1,2 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY4151) 1,2,3,5 1,2,5 and 175°F(79°C) Yellow PENDENT 200'F(93°C) Green 1,2,3,4,5,6,7 1,2,5 (TY4251) 8.0 Figure 3 286°F(141°C) Blue 1** 2** 3** 5** 1** 2** 5** 3/4" 360°F(182°C) Mauve N/A NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT1,2,3,4,5 175°F(79°C) Yellow N/A (TY4251)* Figure 6 200°F(93°C) Green 286°F(141°C) Blue 1,2 135°F(57`C) Orange UPRIGHT 155°F(68°C) Red 8.0 ( and PENDENT 175°F(79°C) Yellow 1/2 PENDENT 1,2,3,4,5,6 N/A NPT (TY4951) 200°F(93°C) Green Figure 4 286°F(141°C) Blue 360°F(182°C) Mauve NOTES 1. Listed by Underwriters Laboratories,Inc.(UL) 2. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL) 3. Approved by Factory Mutual Research Corporation(FM) 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/03) 5. Approved by the City of New York under MEA 354-01-E 6. VdS Approved(For details contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05) 8. Where Polyester Coated,Lead Coated,Wax Coated,and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.Where Lead Coated,Wax Coated,and Wax over Lead Coated Sprinklers are noted to be FM Ap- proved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. * Installed with Style 10(1/2-NPT)or Style 40(3/4-NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable 150°F(66°C)Maximum Ceiling Temperature **' Frame and deflector only.Listings and approvals apply to color(Special Order) TABLE A SERIES TV-B UPRIGHT AND PENDENT SPRINKLERS LABORATORY LISTINGS AND APPROVALS TFP151 Page 5 of 8 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD WAX WAX OVER LEAD • BRASS PLATED POLYESTER COATED COATED COATED 2.8 UPRIGHT(TY1151) 1/2" and 175 PSI(12,1 BAR) N/A NPT PENDENT(TY1251) UPRIGHT(TY3151) and 175 PSI(12,1 BAR) 5.6 PENDENT(TY3251) 250 PSI(17,2 BAR) OR 1/2" NPT 175 PSI(12,1 BAR) RECESSED PENDENT (SEE NOTE 1) (TY3251) N/A UPRIGHT(TY4151) and 175 PSI(12,1 BAR) 8.0 PENDENT(TY4251) 3/4" NPT RECESSED PENDENT 175 PSI(12,1 BAR) N/A (TY4251) 8.0 UPRIGHT(TY4851) 1/2" and 175 PSI(12,1 BAR) NPT PENDENT(TY4951) NOTE 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories,Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York TABLE B SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS MAXIMUM WORKING PRESSURE Technical Physical Characteristics Design Frame Bronze Data Button Brass/Copper Criteria Sealing Assembly.. . Beryllium Nickel Approvals w/TEFLON The TYCO Series TY-B, 2.8, 5.6, UL and C-UL Listed Bulb Glass and 8.0 K-factor, Upright and Pen- FM, LPCB, VdS, and NYC Approved Compression Screw Bronze dent Sprinklers are intended for (Refer to Table A for complete approval Deflector Copper fire protection systems designed information including corrosion resis- Bushing(K=2.8) Bronze in accordance with the standard tant status.) installation rules recognized by the applicable Listing or Approval Maximum Working Pressure Operation agency (for example, UL Listing is Refer to Table B Theglass bulb contains a fluid which based on the requirements of NFPA 13, and FM Approval is based on the Discharge Coefficient expands when exposed to heat.When requirements of the FM Loss Prevention K = 2.8 GPM/psi1/2 (40,3 LPM/bar112) the rated temperature is reached,the Data Sheets). Only the Style 10 or 40 K = 5.6 GPM/psi112 (80,6 LPM/barli2) fluid expands sufficiently to shatter the Recessed Escutcheon, as applicable, K= 8.0 GPM/psiv2(115,2 LPM/barl12) glass bulb, allowing the sprinkler to is to be used for recessed pendent activate and water to flow. installations. Temperature Ratings Refer to Table A Finishes Sprinkler:Refer to Table A Recessed Escutcheon:Signal or Pure White, Jet Black, Chrome Plated, or Natural Brass TFP151 Page 6 of 8 2-7/8"DIA. �1 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) - (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) WRENCH RECESS FACE OF (57,2 mm) MOUNTING (END"A"USED FOR SPRINKLER PLATE ^� 1/2"NPT MODELS) FITTING / 1/8" (3,2 mm) WRENCH RECESS '1 �' (END"B"USED FOR I j % j 3/4"NPT MODELS) ��� � FIGURE 7 MOUNTING W-TYPE 6 SURFACE �. I SPRINKLER WRENCH CLOSURE SERIES 1-1/4"(31,8 mm) TY-B 3/4"(19,1 mm) WRENCH RECESS FIGURE 5 SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY s�'� WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT • 11 2-7/8"DIA. - 5/8±1/4" (73,0 mm) -� 3/4"(19,1 mm) PUSH WRENCH (15,9±6,4 mm) IN TO ENSURE 2-1/4"DIA. 1/4"(6,4 mm) (57,2 mm) ENGAGEMENT FACE OF MOUNTING WITH SPRINKLER SPRINKLER PLATE WRENCHING AREA FITTING 1/8 FIGURE 8 / (3,2 mm) W-TYPE 7 RECESSED r■ ' SPRINKLER WRENCH - 1\ „71_ vii, IInstallation MOUNTIN �. T8.0 he TYCO Series TV-B, 2.8and Pendent, 5.6, and SURFACE - ----- factor CLOSURE SERIES 1-5/16”(33,3 mm) Sprinklers must be installed in accor- TY B dance with this section. 13/16"(20,6 mm) NOTICE FIGURE 6 Do not install any bulb type sprinkler if SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY the bulb is cracked or there is a loss of WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT liquid from the bulb. With the sprinkler STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F(57°C) to 3/32 inch (2,4 mm) for the 360°F (182°C) temperature ratings. A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Obtain a leak-tight 3/4 inch NPT sprinkler joint by applying a minimum to maximum torque of 10 to 20 ft.-lbs. (13,4 to 26,8 Nm).Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. TFP151 Page 7 of 8 Do not attempt to make-up for insuf- Recessed Pendent Sprinklers replaced. Also, replace any sprinkler • ficient adjustment in the escutcheon The Series TY-B Recessed Pendent that has a cracked bulb or that has lost plate by under-or over-tightening the Sprinklers must be installed in accor- liquid from its bulb. (Ref. Installation sprinkler. Readjust the position of the dance with the following instructions. Section.) sprinkler fitting to suit. Step A. After installing the Style 10 The owner is responsible for the Upright and Pendent Sprinklers or 40 Mounting Plate, as applicable, inspection,testing,and maintenance of The Series TY-B Upright and Pendent over the sprinkler threads and with their fire protection system and devices Sprinklers must be installed in accor- pipe-thread sealant applied to the pipe in compliance with this document, as dance with the following instructions. threads,hand-tighten the sprinkler into well as with the applicable standards of the sprinkler fitting. the National Fire Protection Association Step 1. Install pendent sprinklers in (for example, NFPA 25), in addition to the pendent position; install upright Step B.Tighten the sprinkler into the the standards of any other authorities sprinklers in the upright position. sprinkler fitting using only the W-Type having jurisdiction.Contact the install- 7 Recessed Sprinkler Wrench (Figure contractor or sprinkler manufacturer Step 2. With pipe-thread sealant 8).With reference to Figure 3 or 4,the ing p applied to the pipe threads, hand- W-Type 7 Recessed Sprinkler Wrench regarding any questions. tighten the sprinkler into the sprinkler , to the sprinkler wrench flats. Automatic sprinklers are recommended fitting. to be inspected,tested,and maintained Step C.After the ceiling is installed or bya qualified Inspection Service in Step 3.Tighten the sprinkler into the the finish coat is applied,slide on the accordance with localnrequirements i sprinkler fitting using only the W-Type Style 10 or 40 Closure over the Series and/or national codes. 6 Sprinkler Wrench (Figure 7). For TY-B Sprinkler and push the Closure wax-coated sprinklers, use an.8 or over the Mounting Plate until its flange 10 inch adjustable Crescent wrench. contacts the ceiling. With reference to Figures 1 through 4, apply the W-Type 7 Sprinkler Wrench or the adjustable Crescent wrench, Care and as applicable is to be applied to the wrench flats. Maintenance When installing wax-coated sprinklers The TYCO Series TY-B, 2.8, 5.6, and with the adjustable Crescent wrench, 8.0 K-factor, Upright and Pendent exercise care to prevent damage to the Sprinklers must be maintained and ser- wax coating on the sprinkler wrench viced in accordance with this section. flats or frame arms and,consequently, Before closingafireprotection system exposure of bare metal to the corrosiveys environment. Open the jaws of the main control valve for maintenance wrench sufficiently wide to pass over work on the fire protection system the wrench flats without damaging the that it controls, obtain permission to wax coating.Before wrench tightening shut down the affected fire protection the sprinkler, adjust the jaws of the system from the proper authorities wrench to contact only the sprinkler and notify all personnel who may be wrench flats. After wrench tightening affected by this action. the sprinkler, loosen the wrench jaws Owners must ensure that sprinklers before removing the wrench. are not used for hanging any objects. After installation, inspect the sprinkler Otherwise, non-operation in the event wrench flats and frame arms and of a fire or inadvertent operation may retouch(repair)the wax coating when- result. ever the coating has been damaged Absence of an escutcheon, which is and bare metal is exposed. Retouch used to cover a clearance, may delay the wax coating on the wrench flats the time to sprinkler operation in a fire by gently applying a heated 1/8 inch situation. diameter steel rod to the damaged areas of wax,to smooth it back over Sprinklers which are found to be leak- areas where bare metal is exposed. ing or exhibiting visible signs of corro- sion must be replaced. NOTICE Automatic sprinklers must never be Only retouching of the wax coating painted, plated, coated, or otherwise applied to the wrench flats and frame altered after leaving the factory. arms is permitted,and the retouching Modified sprinklers must be replaced. is to be performed only at the time of Sprinklers that have been exposed to the initial sprinkler installation. corrosive products of combustion, but have not operated,should be replaced . The steel rod should be heated only to if they cannot be completely cleaned the point at which it can begin to melt by wiping the sprinkler with a cloth or the wax,and appropriate precautions by brushing it with a soft bristle brush. ' need to be taken when handling the Care must be exercised to avoid dam- installerheated rod in order prevent the age to the sprinklers- before, during, from being burned. and after installation.Sprinklers dam- aged by dropping, striking, wrench twist/slippage, or the like, must be TFP151 Page 8 of 8 P/N 57 - XXX - X - XXX i 1 SIN SPRINKLER TEMPERATURE FINISH RATINGS 530 2.8K UPRIGHT(1/2"NPT) TY1151 1 1 NATURAL BRASS 135 135°F(57°C) 531 2.8K PENDENT(1/2"NPT) TY1251 3 PURE WHITE(RAL9010)* 155 155°F(68°C) 570 5.6K UPRIGHT(1/2"NPT) TY3151 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) 571 5.6K PENDENT(1/2"NPT) TY3251 X JET BLACK(RAL9005)** 200 200°F(93°C) 590 8.0K UPRIGHT(3/4"NPT) TY4151 6 WAX COATED 286 286°F(141°C) 286°F(141°C)MAX 591 8.0K PENDENT(3/4"NPT) TY4251 7 LEAD COATED 360 360°F(182°C) 560 8.0K UPRIGHT(1/2"NPT) TY4851 8 WAX OVER LEAD 286°F(141°C)MAX 561 8.OK PENDENT(1/2"NPT) TY4951 9 CHROME PLATED *Eastern Hemisphere sales only. **Available in only 8.0K,155°F(68°C) _ or 200°F(93°C);requires lead time to manufacture. TABLE C SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-B (specify SIN), (specify K-factor), (specify Upright or Pendent) Sprinkler with (specify) temperature rating, (specify) finish or coating,P/N(Refer to Table C). Recessed Escutcheon Specify: Style (10 or 40) Recessed Escutcheon with(specify)finish,P/N*. *Refer to Technical Data Sheet TFP770. Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, , P/N 56-000-6-387. - Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 Copyright®2013 Tyco Fire Products,LP. All rights reserved. TEFLON is trademark of The DuPont Corporation. Dyna-Thread® - M-COAT® Submittal Data Sheet ® Full Line Sch-40 Replacement Dyna-Thread—M-COAT Specifications Dyna-Thread'—M-Coar`sprinkler pipe repiesents an engineering NPS Nominal I.D. Wt. Wt.(H20 Filled) CRR CRR advancement for the sprinkles pipe industry.It combines the satety In;mm In;rem Lbs/Ft kg/m Lbs/Ft;kg/m Unthreaded Threaded and longevity of traditional Sch-40 pipe with quality and superior 1" 1.080 1.330 1.75 11.39 1.00 hydraulic advantages. 25 27.4 2.0 2.60 — — 11/4" 1.408 1.870 2.54 9.50 1.00 O Comparison to Schedule 40 32 35.8 2.8 3.18 — — 1yz" 1.639 2.290 3.22 9.14 1.00 Dyna-Thread'—M-Coat inside diameter is up to 3.6%larger than Sch-40 40 41.6 3.4 4.79 — giving it superior hydraulics.Also,when used in combination with Dyna- 2" 2.104 3.050 4.57 8.41 1.00 Flow—M-Coat pipe,down sizing often occurs.Dyna-Thread is fully listed and 50 53.4 4.5 6.80 — — approved UL, ULC,and FM for fire sprinkler applications.The life expectancy of Dyna-Thread—M-Coat and Sch-40 are equal based on the calculated wall COa® i thicknesses per UL.The consistent quality of steel used to make Dyna-Thread— RPPRGY[G M-Coat facilitates smooth threading and lower maintenance costs.The exterior - of Dyna-Thread—M-Coat is protected by a clean,durable mill coating for O American Made extended shelf life and easy paint application.With its increased strength Manufactured at one of 3 U.S.Facilities and is available and lighter weight, Dyna-Thread—M-Coat reduces installation fatigue and through distributors in the USA,Canada,Mexico,and - is ideal for retro-fit applications.Corrosion Resistance Ratio(CRR)is a UL Latin America. (Underwriters Laboratory)term for the estimated life expectancy of a pipe joint. This is based on the calculated wall thickness at the base of the first exposed ,p Specifications &Approvals thread, assumed to be the weakest point of the pipe length.Dyna-Thread— M-Coat and Sch-40 have the same calculated wall thicknesses at this point Dyna-Thread—M-Coat pipe is manufactured to meet:ASTM A and are both assigned the same CPR of 1.00. 135,Type E Grade A,and is in compliance with NFPA-13.All sizes of Dyna-Thread—M-Coat are rated at 300 psi working O Comparison to L.W.T. Pipe pressure.Dyna-Thread—M-Coat is UL and ULC Listed for wet, More wall thickness at the thread(CRR-=1.00)gives Dyna-Thread—M-Coat dry and pre action sprinkler systems and FM Approved for better life expectancy than lightwall threadable pipe joints.Dyna-Thread— use in wet systems. Dyna Thread—M-Coat is approved for all M-Coat is approved for standard hanger spacing(15 ft.0.C.),can be used as threaded couplings and welded outlets and is suitable for all earthquake sway bracing,and is safe to use as drops.Dyna-Thread—M-Coat roll-grooved,and plain end fittings.(See listing information). is safer to weld on than many zinc coated lightwall threadable pipe products. Dyna-Thread—M-Coat is more widely accepted than lightwall threadable where Sch-40 is specified. Project: Sprinkler Contractor: Date: �,. Engineer: Specification Reference: System Type: Locations: Comments: Jhe� Customer Service:(800)882-5543 Fax:(800)659-7730 www.alliedtube-sprinkler.com 9 • 16100 S Lathrop Ave • 11350 Norcom Rd. • 2525 N 27th Ave. TUBE&CONDUIT° Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009 APART Of�att;COr@ 02013 Atkore International,Inc.All Rights Reserved.STP-S3-4M-1301 INSTALLATION INSTRUCTIONS I-AQUAFLEX AquaFlex® Stainless Steel Sprinkler Fittings • Read and understand all instructions • These installation instructions are intended for an experienced, before attempting to install any Victaulic AquaFlex°products. trained installer. • Wear safety glasses,hardhat,and foot • The user must understand the purpose of these products, common industry standards for safety,and the potential protection during installation. consequences of improper product installation. ® ® 0 Failure to follow these instructions could cause improper sprinkler operation,resulting Failure to follow these instructions could cause improper sprinkler in serious personal injury and/or property operation,resulting in serious personal injury and/or property damage. damage. INTRODUCTION IMPORTANT INSTALLATION INFORMATION AquaFlex Stainless Steel Sprinkler Fittings connect the branch line • Victaulic AquaFlex products must be Installed according to to the sprinkler using a flexible stainless steel hose and reducer. current,applicable National Fire Protection Association(NFPA The flexible stainless steel hose and fittings are intended for direct 13,13D, 13R,etc.)standards or equivalent standards for wet or connection to the sprinkler and are particularly suited for use in dry systems.Deviations from these standards or alterations to suspended ceiling applications.Each drop assembly comes with one AquaFlex products or sprinklers will void any Victaulic warranty.In stainless steel flexible hose,one branch line connection nipple,one addition,installations must meet provisions of the local authority sprinkler reducing nipple,and the 1BEE2 One-Piece Bracket or the Hat having jurisdiction and local codes,as applicable. Channel Bracket. • If intended for use with drop ceilings,reference must be made to Victaulic AquaFlex unbraided flexible stainless steel hoses are cULus specific ceiling constructions,such as intermediate and heavy- Listed,City of Los Angeles(RR5659)Approved,and accepted for use duty ceilings as described in the Standard Specification for the by the City of New York Department of Buildings(MEA 60-05-E). Manufacture, Performance,and Testing of Metal Suspension Victaulic AquaFlex braided flexible stainless steel hoses are FM Systems for Acoustical Tile and Lay In Panel Ceilings(ASTM Approved,City of Los Angeles(RR5659)Approved,and accepted for C635)when installed in accordance with the Standard Practice for use by the City of New York Department of Buildings(MEA 60-05-E). Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels(ASTM C636). Flexible stainless steel hoses are available in lengths from 31-72 • Victaulic AquaFlex StainlessSteel Sprinkler Fittingsand/or the inches/787-1829 mm with either 12-inch or 3/4-inch NPT threaded quap outlets. 1BEE2 One-Piece Bracket or Hat Channel Bracket must not be intermixed with other manufacturer's products. TECHNICAL DATA • Refer to the specific product submittal for applications and Maximum Working Pressure: listing information.These submittals are located in Sections 200 psi/1375 kPa(FM Approval for Braided System) 10 and 40 of the Victaulic G-100 Catalog or on the Victaulic 175 psi/1206 kPa(UL Listing for Unbraided System) website at www.victaulic.com.In addition,when installing Maximum Ambient Temperature:225°F/107°C Victaulic FireLock®Automatic Sprinklers with Victaulic AquaFlex Stainless Steel Sprinkler Fittings,refer to the 1-40 Connection to Branch Line: 1-Inch NPT/BSPT Installation and Maintenance Instructions for details on sprinkler Minimum Bend Radius of Flexible Stainless Steel Hose: installation requirements. 7 inches/178 mm(FM Approval for Braided System) • Size the piping system to provide the minimum required flow rate 4 inches/102 mm(UL Listing for Unbraided System) for the sprinkler system. Maximum Number of 90°Bends Per Flexible Stainless Steel Hose: • Flush the system to remove foreign material.Continue to flush the Refer to the"Friction Loss Data"section on page 2.NOTE:The system until water runs clear. flexible stainless steel hose should not be bent within • DO NOT install sprinkler system piping through heating ducts. 2'k inches/64 mm of the connection nut at both ends. DO NOT connect sprinkler system piping to domestic hot water Maximum K-Factor of Sprinkler to be Connected to Sprinkler systems.DO NOT install sprinklers where they will be exposed Reducing Nipple for Unbraided System: to temperatures that exceed the maximum ambient temperature 5.6 for 1/-inch rating for the sprinkler. 8.0 for 3-inch • The flexible stainless steel hose should not be bent or fluctuated Maximum K-Factor of Sprinkler to be Connected to Sprinkler up-and-down or side-to-side when it is pressurized for test. Reducing Nipple for Braided System: 5.6 for 1/2-inch • The flexible stainless steel hose should not be bent within 14.0 for 3/4-inch 21/2 inches/64 mm of the connection nut at both ends. • Flexible stainless steel hose and fittings have limited flexibility and are Intended only to be installed with bends at their respective minimum bend radii. • Protect wet piping systems from freezing temperatures. 'Important Installation Information"continued on the following page www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. jctaut .- - _ . I-AQUAFLEX . 11 AquaFlex® Stainless Steel Sprinkler Fittings • If construction is altered,refer to applicable standards to determine STAINLESS STEEL FLEXIBLE HOSE BEND If additional sprinklers are required. CHARACTERISTICS • The owner Is responsible for maintaining the fire protection system in proper operating condition. -- • For minimum maintenance and inspection requirements,refer x /Allk • to NFPA 25 and the NFPA pamphlet that describes the care Minirrwn bend radius :y and maintenance of sprinkler systems.In addition,the authority i Minimbm I Minimum `'� � having jurisdiction may have additional maintenance,testing,and , bend radlu! b"dra='u inspection requirements that must be followed. 1 : .il OR _. 7l • Re-location of AquaFlex products MUST be performed by /''\ qualified personnel familiar with the system's original design criteria,sprinkler listings/approvals,and state and local codes 2Y (including NFPA 13 standards). Minimum bend radius I 'I Failure to re-locate this AquaFlex product properly could affect its Mammon bend radius rA°Inum performance during a fire,resulting in serious personal injury and rend raclLs property damage. OR •_. herd radius M,n,n l,m _ bend radius Mlnlnum bend radius NOTE:For out-of-plane(three-dimensional)bends,care must be taken to avoid imparting torque on the flexible stainless steel hose. FRICTION LOSS DATA I Equivalent Length of 1-i rich/33.7-mm Mazlrnum N.,mber Length of Stamlesr Steel Actual Length of Stoinless Steel Flexible Hnte Schedule 40 Pipe of 50Bends at Flexible Hose incheshnm Outlet Size fet.t/iueters y 4-inch/102-mm inches FM i UL_ inches FM* I .: UL# _... .7 Bend R°di us h /z N/A 18 28 5.5 24 N/A 70.0 3/4 N/A 32 2 9.8 96 27 1/2 31 31 2.9 8.2 31 790 780 8.2 3334 2 2.5 10.1 z 11.0 44 36 40 3.4 13.4 36 915 1000 Ye 9.9 48 3 3.0 14.6 17.1 53 48 48 /z 5.2 16.2 48 1220 1220 A 16.5 55 3 5.0 16.8 21.4 68 60 61 6.5 20.7 60 1525 1540 /a 20.1 63 3 6.t 19.2 27.3 73 1/2 72 72 8.3 22.3 72 1830 1830 Y. 26.2 76 3 7.• '1 #Series AQU at 4-inch/102-mm minimum bend radius and straight reducers Series AQB at 7-inch/178-mm minimum bend radius and straight reducers . §A higher number of bends may be permitted,provided the sum of degrees is equal to or less than the total maximum allowable degrees of bend(e.g.Two 90°bends equal 180°.Three 90°bends equal 270°). For friction loss data for elbows,refer to Victaulic submittal 10.85. EXAMPLE:A 48-inch Series AQU hose installed with two 30°bends and two 90'bends at a 4-inch bend radius is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. NOTE:Differences in equivalent lengths are due to varying test methods,per UL 2443 and FM 1637 standards.Refer to these standards for additional information regarding friction loss test methods. www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. jctaulid I-AQUAFLEX AquaFlex® Stainless Steel Sprinkler Fittings . . ASSEMBLY DRAWINGS - 1BEE2 ONE-PIECE BRACKET Stainless Steel Flexible Tube Branch Line Off g. Connection = Nut r 1 BEE One-Piece Branch Line I ! Bracket Assembly Connection NO c ti Nipple -- Connection �U� Sprinkler Nut 1a/► 'Reducing Nipple Alit-el �,• 101111111 , V IrIJ �.4-41.-----,1 ��,iI / Center Gate ASTM C635 �� Ceiling/Rail Wing Nut Assembly with Assembly Wing Nut #8 x grinch Sprinkler © 0 Self-Drilling Screw O Item Description 0 1 24-inch/610-mm or 48-inch/1219-mm Long Square Bar , 2 Center Gate Assembly with Wing Nut 3 End Bracket Assembly with Wing Nut 4 Sheet Metal Screw ASSEMBLY DRAWINGS - HAT CHANNEL BRACKET v:, t'� iL\ -m„ .: 1 y 2 Item Description 1 24-inch/610-mm or 48-inch/1219-mw dip Long Square Bar `l' 4 - 2 Center Gate Assembly with Wing Nut F E rte" 3 Wing Nut Bolt with Cup Point \� 4 Hat Channel End Bracket 5Wing Nut Bolt with Cone Point A\ 6 Self-DrIllIng Screw(410-16 x1/2-inch) `- I. L 1 www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ictauluc ct. 1 _ =E LE I-AQUAFLEX . AquaFlex® Stainless Steel Sprinkler Fittings INSTALLATION FOR ASTM C635 METAL CEILING SUSPENSION SYSTEMS INSTALLED IN ACCORDANCE WITH ASTM C636 STANDARDS ''' iii • The flexible stainless steel hose should not be bent or fluctuated up-and-down or side-to-side when it is pressurized , : 11. : .. . for test. • The flexible stainless steel hose should not be bent within 2' inches/64 mm of the connection nut at both ends. Failure to follow these instructions could cause improper sprinkler f , operation,resulting in serious personal injury and/or property damage. i —• -,,-.:. 3. Connect the nut of the flexible stainless steel hose to the sprinkler riv,ii reducing nipple.DO NOT use pipe joint compound or Teflon* tape on the fine threads of the sprinkler reducing nipple,since the kflat gasket on the end of the flexible stainless steel hose provides ' the leak-proof connection.Tighten the connection to a maximum torque of 15 ft-lbs/20 Nem.NOTE:To prevent damage to the seal, "` DO NOT exceed the specified torque on the nut. 1. Apply pipe joint compound or Teflon*tape to the tapered threads of the branch line connection nipple.NOTE:DO NOT use a combination of pipe joint compound and tape.Using a pipe •' wrench,tighten the branch line connection nipple into the branch line. ." 111 t • '' ''. °Ir: . ''' .., ":' t 1 V •i K 2. Connect the nut of the flexible stainless steel hose to the branch I. line connection nipple,as shown above.DO NOT use pipe joint - 1 compound or Teflon'tape on the threads of the branch line connection nipple,since the flat gasket on the end of the flexible ""'— stainless steel hose provides the leak-proof connection.Tighten 4. Attach the end brackets of the 1BEE2 One-Piece Bracket to the the connection to a maximum torque of 15 ft-lbs/20 N•m.NOTE: rails of an ASTM C635 metal ceiling suspension system installed To prevent damage to the seal,DO NOT exceed the specified in accordance with ASTM C636 standards.Make sure the ends of torque on the nut. the 1BEE2 One-Piece Bracket engage the rails,as shown above. Tighten the wing nuts to a torque of 3 ft-lbs/4 N•m to secure the ends to the rails. •Teflon Is a registered trademark of the DuPont Company www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.O 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. rataulic 1-".. .1:1 ':F:t' • -------,1% ,,---.,c7,,,, I-AQUAFLEX . AquaFlex® Stainless Steel Sprinkler Fittings mill .11 7- ejiiiiiiiii i r,. , , . • - •,—- i . � i_._4.i_....._iI , 0 ''- f1 j 5. For Installations that must meet cULus Listing requirements,or for ' added tamper resistance,tighten a#8 x 1/2-inch self-drilling screw 7. Apply pipe joint compound or Teflon*tape to the male threads of through the 1BEE2 One-Piece Bracket and ceiling grid at the two the sprinkler.Install the sprinkler Into the sprinkler reducing nipple locations on the bracket.NOTE:A tamper-evident label is available by following the sprinkler manufacturer's installation instructions. and can be applied to one or both of the end brackets. 8. After installation is complete,test the system for leaks in . : 7. _i MMI accordance with NFPA guidelines. 10-- ... ;:-_---........---° t uiliN 6. Move the center gate assembly of the 1BEE2 One-Piece Bracket to the desired location,then slide the sprinkler reducing nipple into the center gate assembly. 6a. Close the gate around the sprinkler reducing nipple.Swing the pivot screw into the slot on the gate,and tighten the wing nut to a torque of 3 ft-lbs/4 Nom to secure the sprinkler reducing nipple in the desired location.NOTE:The pivot screw is staked to prevent the wing nut from being backed off/removed completely. •Teflon is a registered trademark of the DuPont Company www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ict.'alUI11C PLV ,F' . 1-AQUAFLEX AquaFlex® Stainless Steel Sprinkler Fittings 2 X 4 WOOD JOIST/STUD INSTALLATION 2 X 4 METAL JOIST/STUD INSTALLATION (FM ONLY) (FM ONLY) 1. Perform steps 1-3 of the"Installation for ASTM C635 Metal 1. Perform steps 1-3 of the"Installation for ASTM C635 Metal Ceiling Suspension Systems Installed in Accordance with ASTM Ceiling Suspension Systems Installed In Accordance with ASTM C636 Standards"section. C636 Standards"section. - —_ ---�— —. ti _ 1 ,, 2. Remove the sheet metal screw from only one end bracket 2. Remove the sheet metal screw from only one end bracket assembly of the 1BEE2 One-Piece Bracket. assembly of the 1BEE2 One-Piece Bracket.Slide the end bracket 2a. Remove the wing nut from each of the end bracket assemblies. assembly toward the center of the square bar. 3. Place the end bracket assembly(with the sheet metal screw still 2a. Remove the wing nut from each of the end bracket assemblies. installed)up against the outside surface of the wood joist/stud with 3. Place the end bracket assembly(with the sheet metal screw still the square bar resting on top of the wood joists/studs. installed)up against the outside surface of the metal joist/stud with 3a. Slide the end bracket assembly(with the sheet metal screw the square bar resting on top of the metal joists/studs. removed in step 2)toward the outside surface of the opposite 3a. Slide the end bracket assembly(with the sheet metal screw wood joist/stud,as shown in the graphic below- removed in step 2)toward the inside,flat surface of the opposite metal joist/stud,as shown in the graphic below. 1'/4-inch/32-mm Long#10 11h-inch/38-mm Long Self-Drilling #10 Wood Screw Sheet Metal (4 Total) Screws (4 Total) ws: *:.R 4. Install the modified 1BEE'One-Piece Bracket assembly to the wood joists/studs by using four,11/-inch/38-mm long#10 wood 4. Install the modified 1BEE2 One-Piece Bracket assembly to the screws in the locations noted in the graphic shown above. metal joists/studs by using four, 11/4-inch/32-mm long#10 self- 5. Using an Ye-inch/3-mm drill bit,drill a hole down through the end drilling sheet metal screws in the locations noted in the graphic bracket assembly(with the sheet metal screw removed in step shown above. 2)and into the square bar to accommodate re-installation of the 5. Using an Ya-inch/3-mm drill bit,drill a hole down through the end sheet metal screw. bracket assembly(with the sheet metal screw removed In step 6. Re install the sheet metal screw into the end bracket assembly/ 2)and into the square bar to accommodate re-Installation of the square bar. sheet metal screw. 7. Perform steps 6 8 of the"Installation for ASTM C635 Metal 6. Re-install the sheet metal screw into the end bracket assembly/ Ceiling Suspension Systems Installed in Accordance with ASTM square bar. C636 for ASTM C635 Metal Standards"section to complete the installation. 7. Perform steps 6 8 of the"Installation o P P • NOTE:For wood joists/studs larger than 2 x 4,longer sprinkler reducing Ceiling Suspension Systems Installed in Accordance with ASTM • nipples should be used. C636 Standards"section to complete the installation. NOTE:For metal joists/studs larger than 2 x 4,longer sprinkler reducing nipples should be used. www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.O 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ictaulic 'i-. _ I-AQUAFLEX AquaFlex® Stainless Steel Sprinkler Fittings ALTERNATIVE WOOD JOIST/STUD INSTALLATION ALTERNATIVE METAL JOIST/STUD INSTALLATION (FM ONLY) (FM ONLY) 1. Perform steps 1-3 of the`Installation for ASTM C635 Metal 1. Perform steps 1-3 of the"Installation for ASTM C635 Metal Ceiling Suspension Systems Installed in Accordance with ASTM Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards"section. C636 Standards"section. - - . , 1042. Remove the sheet metal screw from only one end bracket 2. Remove the sheet metal screw from only one end bracket assembly of the 1BEE2 One-Piece Bracket.Remove the end assembly of the 1BEE2 One-Piece Bracket.Remove the end bracket assembly from the square bar. bracket assembly from the square bar. 2a. Remove the wing nut from each of the end bracket assemblies. 2a. Remove the wing nut from each of the end bracket assemblies. 3. Measure the distance between the wood joists/studs. 3. Measure the distance between the metal joists/studs. 3a. Cut the square bar to the length needed to fit between the two 3a. Cut the square bar to the length needed to fit between the two wood joists/studs.This length must be measured from the outside metal joists/studs.This length must be measured from the outside of the end bracket assembly(with the wing nut removed)to the of the end bracket assembly(with the wing nut removed)to the point on the square bar that will butt up against the other wood point on the square bar that will butt up against the other metal joist/stud. joist/stud. 4. Place the end bracket assembly,removed in step 2,onto the end 4. Place the end bracket assembly,removed in step 2,onto the end of the square bar so that the square bar is flush with the outside of the square bar so that the square bar is flush with the outside of the end bracket assembly.Mark the new location where the of the end bracket assembly.Mark the new location where the sheet metal screw will be re-Installed.Drill an 1/4-inch/3-mm hole at sheet metal screw will be re-installed.Drill an' -Inch/3-mm hole at the mark on the square bar to accommodate re-installation of the the mark on the square bar to accommodate re-installation of the sheet metal screw. sheet metal screw. 5. Re-Install the end bracket assembly to the square bar with the 5. Re-install the end bracket assembly to the square bar with the sheet metal screw removed in step 2. sheet metal screw removed in step 2. 11/:-inch/38-mm Long ' -4111, PA-inch/32-mm114 11 #10 Wood Screw Long#10 (4 Total) Self-Drilling Sheet Metal Screws ' (4 Total) OOP 6. Install the modified 1BEE2 One-Piece Bracket assembly between 6. Install the modified 1BEE2 One-Piece Bracket assembly between the wood joists/studs by using four, 11/2-inch/38-mm long#10 the metal joists/studs by using four, 1'A-inch/32-mm long#10 self- wood screws in the locations noted in the graphic shown above. drilling sheet metal screws in the locations noted in the graphic 7. Perform steps 6-8 of the"Installation for ASTM C635 Metal shown above. Ceiling Suspension Systems Installed in Accordance with ASTM 7. Perform steps 6-8 of the"Installation for ASTM C635 Metal • C636 Standards"section to complete the Installation. Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards"section to complete the installation. • www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. jictaulid EEJC I _.• .: LE' 7 r.. I-AQUAFLEX AquaFlex® Stainless Steel Sprinkler Fittings INSTALLATION FOR ASTM C645 HAT FURRING CHANNEL CEILING SYSTEMS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS (FM ONLY) • $ajsil'(ti • The flexible stainless steel hose should not be bent or fluctuated up-and-down or side-to-side when it is pressurized for test. • The flexible stainless steel hose should not be bent within 21 inches/64 mm of the connection nut at both ends. Failure to follow these instructions could cause improper sprinkler operation,resulting in serious personal injury and/or property 3. Connect the nut of the flexible stainless steel hose to the sprinkler damage. reducing nipple.DO NOT use pipe joint compound or Teflon* tape on the fine threads of the sprinkler reducing nipple,since the flat gasket on the end of the flexible stainless steel hose provides the leak-proof connection.Tighten the connection to a maximum ltj * torque of 15 ft-lbs/20 Nom.NOTE:To prevent damage to the seal, 4u DO NOT exceed the specified torque on the nut. ♦s - I 1. Apply pipe joint compound or Teflon'tape to the tapered threads '^" of the branch Ilne connection nipple.NOTE:DO NOT use a combination of pipe joint compound and tape.Using a pipe wrench,tighten the branch line connection nipple into the branch -. line. • 1IIIird , 2. Connect the nut of the flexible stainless steel hose to the branch line connection nipple,as shown above.DO NOT use pipe joint compound or Teflon*tape on the threads of the branch line 4. Attach the end brackets to the ASTM C645 hat furring channel connection nipple,since the flat gasket on the end of the flexible ceiling system installed in accordance with ASTM C754 standards. stainless steel hose provides the leak-proof connection.Tighten Make sure the end brackets engage the hat furring channels, the connection to a maximum torqueof 15 ft-lbs/20 Nm.• NOTE: as shown above.Tighten the wing nuts loosely to maintain • To prevent damage to the seal,DO NOT exceed the specified engagement with the hat furring channels.The wing nuts will be torque on the nut. tightened completely in later steps. •Teflon Is a registered trademark of the DuPont Company www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.c 2010 VICTAULIC COMPANY,ALL RIGHTS RESERVED.PRINTED IN THE USA. jctaulid I-AQUAFLEX AquaFlex® Stainless Steel Sprinkler Fittings 4\ ni, y: • tit 5. Place the center gate assembly onto the square bar,as shown 7. Adjust the bracket assembly to the appropriate location on the hat above. furring channel. I • • 8. Tighten the wing nut on the side of each end bracket to a torque of 3 ft-lbs/4 N•m to secure the end brackets to the hat furring channels. r =ti •• •• e • 6. Insert the square bar/center gate assembly into each end bracket, as shown above. 9. Tighten the wing nut on the top of each end bracket to a torque of 3 ft-lbs/4 Nem to secure the end brackets to the square bar. www.victaulic.com VICTAULIC AND AOUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. jotaulid - I-AQUAFLEX AquaFlex® Stainless Steel Sprinkler Fittings , qs r Ay i a� ern „s .i , • I l , 10. Tighten a 4t10-16 x' -inch self-drilling screw through the two locations on each end bracket and Into the hat furring channels. lla. Close the gate around the sprinkler reducing nipple.Swing the pivot screw into the slot on the gate,and tighten the wing nut to a torque of 3 ft-lbs/4 N•m to secure the sprinkler reducing nipple in the desired location.NOTE:The pivot screw is staked to prevent the wing nut from being backed off/removed completely. 12. Apply pipe joint compound or Teflon*tape to the male threads of the sprinkler.Install the sprinkler into the sprinkler reducing nipple a_1 by following the sprinkler manufacturer's installation instructions. 13. After installation is complete,test the system for leaks in accordance with NFPA guidelines. 1 ,ter"4.11r. 11. Move the center gate assembly to the desired location,then slide the sprinkler reducing nipple into the center gate assembly. • •Teflon Is a registered trademark of the DuPont Company • www.victaulic.com /•ctaulid VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. V INSTALLATION INSTRUCTIONS '-AQUAFLEX AquaFlex® Stainless Steel Sprinkler Fittings For complete contact information,visit www.vlctaulic.com 1-AQUAFLEX 5878 REV C UPDATED 07/2010 Z000AQUFLX ictauluc° VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA.