Loading...
Specifications 7D U t-vz/ um/ CORBIN MAR-HY Distributors Calculations for HVAC Unit Restraints Sheets Included: R-1 thru R-2 Reference Sheet S-1 thru S-2 Calculation Summary MORE C-1 thru C-12 Restraint Calculations ,sc�,o� . HINOQ Appendix !t-it tar . 5f0st4' t/3 o// . Prepared by: Tuan Tygart, EIT. EO PR 8/. Reviewed by: Dan Morell, P.E., S.E. Project number: CC12001 OREGON For: MAR-HY Distributors, Milwaukie, OR 4 -'o, 2 l0\ \, , R Date: January 16, 2012 Ft MO �� 11,01, EX CORBIN CONSULTING ENGINEERS,INC. PIRES: 12/31/20 (2- 1905 NW 169th Place Suite 121,Beaverton,OR 97006 Tel:503/645-0176 Fax:503/645-0415 • MAR-HY HVAC Unit Restraint Calculations Project#12001 Calculation Summary: The following calculations are to check the wind and seismic actions on the restraint clips for the following RUUD HVAC units. They apply only in the states of Oregon and Washington and only under the conditions as stated in the General Notes of the MAR-HY RUUD HVAC UNIT RESTRAINTS details. Small Units Size Dimensions Wt (lbs) RQNL-B, RQPL-B, RRNL, RRRL, 2—5 Tons 50 13/16 x 47 19/32 x 44/50 381-583 RRPL Medium Units(3 to 6 Ton Large Footprint) RKNL-A, RKPL-A,C, RLPL-A,C, 3—6 Tons 75%x 46'/2 x 35 500-635 RJPL-A, C,RLNL-A, C, RJNL-A, C 92 11/16 x 58 7/32 x 44/50 RKKL-B, RJNL-B,C, RLKL-B, RLNL- B,C, RKNL-B Large Units (7 to 25 Ton Large Footprint) RKKL-B, RJNL-B,C, RLKL-B, RLNL- 7.5 to 12.5 92 11/16 x 58 7/32 x 44/50 910-1311 B,C, RKNL-B Tons RLKL-B, RLNL-B,C, RKNL-B,C 15 to 25 Tons 124 18/32 x 85 19/32 x 57 1797-2433 RJNL-B 15 to 25 Tons 152 1/16 x 85 29/32 x 57 1797-2433 Seismic Conditions Seismic checks were performed using ASCE 7-05,Chapter 13 and ASD load combinations in Chapter 2. The mapped spectral response acceleration,short period, S5= 1.50g. An Importance Factor, Ip=1.0 was used. ASCE 7-05 defines ap=2.5 and Rp=6.0 as the worst case condition for HVAC units in Chapter 13.A site class of D was assumed as the worst case condition. In addition, the following assumptions were used regarding the placement of clips in order to meet the minimum spacing requirements for perforations at the HVAC unit base when calculating the resulting seismic stresses on the tie downs: A) Small units were assumed to have tie downs at the ends of the units B) Medium units tie downs along the long direction were assumed to be 8 inches from the ends and at the ends along the short direction C) Large units were assumed to be evenly spaced in the long direction of the unit starting at the end and ending 16"'from the front of the unit, and at the ends along the short side of the unit. Refer to sections C-1 and C-3 thru C-8 for results regarding the seismic evaluation of the restraint clips. rio CORBI� CONS[1LTT�G ENGT�EERS,[\C, , Pe_ PROJECT NO: /poi �� 1905 NW 169th Place, Suite 121 PROJECT /��AR. 1I'! EIv.,, '✓_f;,r,,�` , REVlikamil J Beaverton,Oregon 97006 TITLE �nkt � r: ,IJIA Sore ,-,A.1" DATE 1/).7. CORRIN Tel: 503/645-0176 Fax: 503/645-0415 ORIGINATOR !i�h^� YC,A4-1 _ CHK J • Wind Conditions Wind calculations were performed using ASCE 7-05,Section 6.5.15 and ASD load combinations in Chapter 2.The following assumptions were used in the calculations: A) Exposure Class=C F) K = Z 1.13 3 B) Velocity= 110 mph G) K2 = 1 C) Category II building, I =1 H) Cf= 1.3 D) G=0.85 I) Force Increase Factor= 1.9(Sect. E) Kd=0.90 6.5.15.1),worst case In addition, a maximum height of 60 feet is assumed and the building is away from hills, ridges and escarpments that can result in increased wind velocities. Areas in the Columbia River Gorge, along the coast or in area with hills,ridges and escarpments that would result in changes to the above assumptions should result in a reevaluation of the clip designs to meet the location conditions. Refer to sections C-2 and C-9 thru C-12 for results regarding the wind evaluation of the restraint clips. Results Wind pressure was the controlling condition for restraint clip checks. Overturning moments calculated for the various configurations are summarized on C-2. The clips are shown to be adequate for overturning due to wind events that fall within the parameters given above. HVAC curb was assumed to resist shear loads.Strength checks were not made for the base rails, roof curbs,etc.as these items are designed by others. AP "ii CORP CONSULTI'G ENGNEERS -\C. PROJECT NO: )10b of e 1905 NW 169th Place, Suite 121 PROJECT �, i_ 0414. l;:`,T; , r, REV _ Beaverton,Oregon 97006 TITLE {'1< < <.�� �, ;,�, ����.�.., • DATE )//2- CORBIN Tel: 503/645-0176 Fax: 503/645-0415 ORIGINATOR ''' )'; t CHK Coccy Cs = L5c1. As4-r scc-7-025- _ re, Op. t.44 site CLA /1.> 22-2 r&5: - I E4 1, ) Sos Spc 1, SD&[ TIO 3 - /A5Sueri6" /, ) s•r• too mitce HT A,,. • (.• r , AS,„of (t A A C c,-7> 17:5 tt, 14' T71.:e L,416-; ,1; f! iS r 141" );r4jt., ./,\) , ro 4 C-Jr> re? A Li ' T, 4,7 c6 s rc,p,(1.2q • •• L P /-1 i 1.1,1 I V- 1 Ta. t--:; ; ArC.:A-) c Cv(?... Lot', CA 3—r,-0 r.) / re,et PAr"'"' CORBIN CONSULTING ENGINEERS, INC. PROJECT NO: — 111111 1905 NW 169t1) Place, Suite 121 PROJECT /11/ / '4L,etde, 4mo-spa REV Beaverton,Oregon 97006TITLE kii,c DATE I ji z CORBIN Tel: 503/645-0176 Fax: 503/645-0415 ORIGINATOR A,..) i ,47 CHK 111.1111.111111111 Corbin Consulting Engineers,Inc. Project No: 12001 Page_of 1905 NW 169th Place,Suite 121 Protect Fan Clip Check Rev: Beaverton,Oregon 97005 Title Center of Gravity/Wind Check Date CORBL"7 Tel:503/645-0176 Far 503/645.0415 Originator Tuan Tygart CHK: Center of Gravity Calculations (Refer to Reference material for unit dimensions and corner weight percentages) Small Footprint (1.5 to 5 ton) Max Size weight Corner% CG Model x y h lbs. 1 2 3 4 x v z RQNL/RQPL 50.8125 47.594 41 510 29% 30% 21% 20% 20.83 24,27 22.55 2-4 TON RQPW/RSPL/RSNL 50.8125 47.594 41 2255 No Info.,Assume similar to RRNL Series RRNL/RRPL/RRRL 50.8125 47.594 41 583 29% 30% 21% 20% 20.83 24.27 22.55 1.5 to 5 ton Worst Case Loading Med Footprint (3 to 6 ton large footprint) RKNL/RKPL 75.5 46.5 35 597 38,25 25.75 19-25 3-5 TON RJNL/RJPL 75.5 46.5 35 620 38.25 25.75 19.25 3-5 ton RKKL 81.5 46.5 35 689 3825 25.75 19.25 6Ton 0iN1/R1PL 81.5313 48.0625 35 620 39 26.125 1.9.25 6 ton RKNL-B 93.6875 58.75 44 1274 23% 33% 27% 17% 41.22 35.25 24.2 6 to 125 tons Worst Case loading and most surface area Large Footprint (7.5 to 25 ton large footprint) RKKL 92.6875 58.75 44 1274 21% 30% 35% 14% 45.42 33.19 24.2 7ton RKKL 92.6875 58.75 44 1274 23% 33% 27% 17% 40.78 35.25 24.2 10 ton RKKL 92.6875 58.75 44 1274 14% 44% 30% 12% 38.93 43.43 24.212 ton RiNL 92.6875 58.219 44 1193 22% 32% 26% 20% 42.64 33.77 24.2 75 TON RJNL 92.6875 58.219 Sc 1193 22% 32% 26% 20% 42.64 33.77 27.5 10 TON 36141-8 93.6875 58.75 44 1274 23% 33% 27% 17% 41.22 35.25 24.26 to 12.5 tons RKKL-13 124.094 85.594 57 2093 24% 32% 27% 16% 53.36 5050 31.35 15-20 TON RKNL 152.063 85.906 57 2433 24% 32% 27% 16% 65.39 50.68 31.3515-20705 Worst Case loading 3 1 4 Ki vpLuFc V“''J 1.,.If7 ✓ •": // � SEE (� G c Wtnd Overturning Moment Check �- N 01-is _rG.:4 r t..__ f'F, ,sr. ' _ _r y.: _-i;E,r� Ur E:i(.') te r_ T-0 t _C.r'i i .., Perpendicular to Lon Anis Cong trds /i� Refer to C-12 thru C-IS for Wind Force Calculations r--,,2 S =f-^ ' •'U i 5 min unit Unit Wt.(Lbs) 0.6'Wt F(lbs) h(ft) width y(ft) CGy(ft) OM(ft'Lb) RM(ft'Ib) Total M T=C(lbs) No Legs T/C T/Leg Max C/leg Small 380 228 95a 3.42 3.97 1.94 1636.6 443.10 1193.48 300.92 2 150.46' 352.07 Med 500 300 2152 2.92 4.01 1.83 3138.3 548.44 2589.90 646.63 4 161.66 355.14 Large 1797 10782 3981 4.75 7.16 2.94 9454.9 3164.65 6290.23 878.67 5 175.73-. 507.45 n 1• rJ GL/fes CG y=Shortest dist to CGy from reference "'- 5 G f" �. ���� (OM)Overturning Moment=F'h/2 _ O ('� (PM)Resisting Moment=0.6'W'CGy f. �-1-F UJ F� r .- Cr,f�J \ t (T)Tension 7 7 ✓ � (C)Compression p'7l� C (:' 4 K6.!:.: L 1 Max C/Leg=(Max wt!No tot.legs)+(OM/y/No.legs in C) i) , C, Corbin Consulting Engineers, Inc. Project No: 12001 Page 1 of z 1905 NW 169th Place, Suite 121 Project RRNL, Etc, Small Ftpri Rev: Beaverton, Oregon 97006 Title Fan Clip Check Date : CORBIN Tel: 503/645-0176 Fax: 503/645.0415 Originator Tuan Tygart CHK Seismic Anchorage Design: input items in grey cells Seismic Inputs Per ASCE 7-05§ 13.3.1 ap= 2.5 Component amplification factor Is tool on RMF? N R = 6 Component response modification factor Sos= 1 Short period component amplification factor 1p= 1 Component importance factor z= 60 ft Height in structure of point of attachement h = 60 ft Average roof hieght Wp= 583 # Componet operating weight Horizontal Seismic Force: Fp = 292 # Fp=(0.4 a n Sos W P)/(R pd p)(1 +2 z/h) ASCE 7-05 EQ 13.3-1 Fp max = 933 # F p mox =1.6 Sos I, Wp ASCE 7-05 EQ 13.3-2 Fp min = 175 # Fmin =0.3Sas 1p Wp ASCE7-05EQ13.3-3 Fp des = 291.50 # Strength Design Fp ASD= 204.05 # Allowable Stress Design Fp ASD=Fp Des *0.7 IBC EQ 16-15 Vertical Seismic Force: Fp vert= 117 # Fp vert=0.2 5 os W p ASCE 7-05§13.3.1 Fp v asd = 82 # Fp v asd=0.7 Fp vert IBC EQ 16-15 Tool Geometry: Height(H) 41 inches distance to c.g. (z)= 22.55 inches Length (X) 50.8125 inches distance of supports(x) = 46.81 inches Width (Y) 47.594 inches distance of supports (y)= 45.47 inches distance of c.g. to support x1 = 18.83 inches distance of c.g. to support yl = 23.21 inches . No. of legs in ten.(x)= 2 No. of legs in com.(x): 2 No. of legs in ten.(y)= 2 No. of legs in com.(y): 2 No. legs in shear= 4 I i I_i_i ,' i1iI. { 'I I1 it • 1 111 1 Corbin Consulting Engineers, Inc. Project No: 12001 Page Z of Z 1905 NW 169th Place, Suite 121 Project RRNL, Etc, Small Ftpr1 Rev: Beaverton, Oregon 97006 Title Fan Clip Check Date : CORBIN Tel: 503/645-0176 Fax: 503/645.0415 Originator Tuan Tygart CHK : Check Tool for overturning: in x direction Mot= 4,601 #-in Mot=(Fp AO)*(z) Mres(x)= 5,051 #-in Mres=((.6*Wp]-(Fp v asd]) *x1 .6 Wp per IBC EQ 16-15 Check if Mres(x)> Mot No net overturning Check Compressive Force on support(x): C = 496 # C=[Mot+(distance of supports(x)-x1)*(Wp+Fp v asd)]/distance of supports(x) c per leg= O g 248 #max/leg N/A Not on RMF Anchorage Design: x Strength Design values: Mot sd = 6,573 #--ft Mot sd=Fp des(z) Mres (x)s= 7,686 #-ft Mres(x)s=(.9Wp-Fp vert)(x1) 0.9Wp per IBC EQ 16-7 T= -24 # Tension force on legs=T=(Mot sd-Mres(x)s)/x . Tension per leg = 0 #Tension per Ieq Tension per leg =T/[No. of legs in ten.(x)] Check Tool for overturning: in y direction Mres (y) = 6,225 #-in Mres(y)=(.6*Wp-Fp v asd)*yl .6 Wp per IBC EQ 16-15 Check if Mres (y)> Mot No net overturning Check Compressive Force on support(y): C= 427 # C=[Mot+(distance of supports(y)-y1)*(Wp+Fp v asd)]/distance of supports(y) c per leg= 213 #max/leg N/A Not on RMF Anchorage Design:y Strength Design values: Mres (y)s= 9,472 #-ft Mres(y)s=(.9Wp-Fp vert)(y1) 0.9Wp per IBC EQ 16-7 T= -64 # Tension force on legs=T=(Mot sd-Mres(y)s)/y Tension per leg = 0 #Tension per leg Tension per leg=T/(No.of legs in ten.(y)] Anchorage Requirements: Max shear on leg = 73 # Max shear on leg=Fp des/(No.legs in shear) Max tension on leg = 0 # CCorbin Consulting Engineers, Inc. Project No: 12001 Page I of x 1905 NW 169th Place, Suite 121 Project Med Ftprt Rev: Beaverton, Oregon 97006 Title Fan Clip Check Date : CORBIN Tel: 503/645-0176 Fax: 503/645.0415 Originator Tuan Tygart CHK : Seismic Anchorage Design:9n: input items in grey cells Seismic Inputs Per ASCE 7-05§ 13.3.1 ap = 2.5 Component amplification factor Is tool on RMF ? N Rp = 6 Component response modification factor SDS= 1 Short period component amplification factor Ip— 1 Component importance factor z = 60 ft Height in structure of point of attachement h = 60 ft Average roof hieght WP= 1,274 # Componet operating weight Horizontal Seismic Force: Fp = 637 # Fp=(0.4 a p SDs W p)/(R p/I p)(1 +2 z/h) ASCE 7-05 EQ 13.3-1 Fp max = 2038 # Fpmax =l.6Sps Ip Wp ASCE 7-05 EQ 13.3-2 Fp min = 382 # F min =0.3 S os l W P p ASCE 7-05 EQ 13.3-3 Fp des = 637.00 # Strength Design Fp ASD= 445.90 # Allowable Stress Design Fp ASD=Fp Des *0.7 IBC EQ 16-15 Vertical Seismic Force: Fp vert= 255 # Fp vert=0.2 S os W Fpvasd = 178 # P ASCE 7-05§13.3.1 Fpvasd=0.7 Fp vert IBC EQ 16-15 Tool Geometry: Height(H) 50 inches distance to c.g. (z — ) 27.50 inches Length (X) 93.6875 inches distance of supports(x) = 73.69 inches Width (Y) 58.75 inches distance of supports Pp (y)= 54.75 inches distance of c.g. to support x1 = 31.22 inches distance of c.g. to support yl = 33.25 inches No. of legs in ten.(x)= 4 No. of legs in com.(x): 4 No. of legs in ten.(y)= 4 No. of legs in com.(y): 4 No. legs in shear= 8 i I I 1 : 1 I I I •I • g i I I 1 I'i ,"`1 CCorbin Consulting Engineers, Inc. Project No: 12001 Page Z of 2. 1905 NW 169th Place, Suite 121 Project Med Ftprt Rev: Beaverton, Oregon 97006 Title Fan Clip Check Date : CORBIN Tel: 503/645-0176 Fax: 503/645.0415 Originator Tuan Tygart CHK: Check Tool for overturning: in x direction Mot= 12,262 #-in Mot=(Fp ASD)*(z) Mres(x)= 18,296 #-in Mres=([.6*Wp]-[Fp v ascii) *x1 .6 Wp per IBC EQ 16-15 Check if Mres(x)>Mot No net overturning Check Compressive Force on support upport(x): C = 1,003 # C=(Mot+(distance of supports(x)-x1)*(Wp+Fp v asd)]/distance of supports(x) c per leg= 251 #max/leg N/A Not on RMF Anchorage Design: x Strength Design values: Mot sd= 17,518 #--ft Mot sd=Fp des(z) Mres (x)s= 27,842 #-ft Mres(x)s=(.9Wp-Fp vert)(x1) 0.9Wp per IBC EQ 16-7 T= -140 # Tension force on legs=T=(Mot sd-Mres(x)s)/x - Tension per leg = 0 #Tension per leg Tension per leg =T/[No. of legs in ten.(x)] Check Tool for overturning: in y direction Mres (y) = 19,486 #-in Mres(y)=(.6*Wp-Fp v osd) *y1 .6 Wp per IBC EQ 16-15 Check if Mres (y)> Mot No net overturning Check Compressive Force on support(y): C = 794 # C=[Mot+(distance of supports(y)-y1)*(Wp+Fp v asd)]/distance of supports(y) c per leg= 199 #max/leg N/A Not on RMF Anchorage Design: y Strength Design values: Mres (y)s= 29,652 #-ft Mres(y)s=(.9Wp-Fp vert)(y1) 0.9Wp per IBC EQ 16-7 T= -222 # Tension force on legs=T=(Mot sd-Mres(y)s)/y Tension per leg = 0 #Tension per leg Tension per leg=T/[No. of legs in ten.(y)] Anchorage Requirements: Max shear on leg = 80 # Max shear on leg=Fp des/(No. legs in shear) Max tension on leg = 0 # ,,G <)5 Corbin Consulting Engineers, Inc. Project No: 12001 Page I of Z. 1905 NW 169th Place, Suite 121 Project RJNL, Etc, Lrg Ftprt Rev: Beaverton, Oregon 97006 Title Fan Clip Check Date : CORBIN Tel: 503/645-0176 Fax: 503/645.0415 Originator Tuan Tygart CHK : Seismic Anchorage Design: input items in grey cells Seismic Inputs Per ASCE 7-05§ 13.3.1 ap= 2.5 Component amplification factor Is tool on RMF? N Rp= 6 Component response modification factor SDS = 1 Short period component amplification factor Ip = 1 Component importance factor Z = 60 ft Height in structure of point of attachement h = 60 ft Average roof hieght Wp = 2,433 # Componet operating weight Horizontal Seismic Force: Fp = 1217 # Fp=(0.4 a p Sos W )/(R // )(1 +2 z/h) ASCE 7-05 EQ 13.3-1 Fp max= 3893 # F p max=1.6 S os /p Wp ASCE 7-05 EQ 13.3-2 Fp min = 730 # F min =0.3 S ps /p Wp ASCE 7-05 EQ 13.3-3 Fp des= 1216.50 # Strength Design Fp ASD= 851.55 # Allowable Stress Design Fp ASD=Fp Des *0.7 IBC EQ 16-15 Vertical Seismic Force: Fp vert= 487 # Fp vert=0.2 Sas Wp ASCE 7-05§13.3.1 Fpvasd = 341 # Fpvasd=0.7 Fp vert IBC EQ 16-15 • Tool Geometry: Height(H) 57 inches distance to c.g. (z)= 31.35 inches Length (X) 152.063 inches distance of supports (x) = 67.03 inches Width (Y) 85.906 inches distance of supports (y)= 81.91 inches distance of c.g. to support x1 = 63.39 inches distance of c.g. to support yl = 48.69 inches 1 No. of legs in ten.(x)= 5 No. of legs in com.(x): 3 No. of legs in ten.(y)= 5 No. of legs in com.(y): 2 No. legs in shear= 10 • r T • x. CCorbin Consulting Engineers, Inc. Project No: 12001 Page sof I _ 1905 NW 169th Place, Suite 121 Project RJNL, Etc, Lrg Ftprt Rev: Beaverton, Oregon 97006 Title Fan Clip Check Date : CORBIN Tel: 503/645-0176 Fax: 503/645.0415 Originator Tuan Tygart CHK : Check Tool for overturning: in x direction Mot= 26,696 #-in Mot=(Fp ASD)*(z) Mres(x)= 70,941 #-in Mres=(1.6*Wp]-[Fp v asd)) *x1 .6 Wp per IBC EQ 16-15 Check if Mres (x)> Mot No net overturning Check Compressive Force on support(x): C = 549 # C=[Mot+(distance of supports(x)-x1)*(Wp+Fp v asd)]/distance of supports(x) c per leg= 183 #max/leg N/A Not on RMF Anchorage Design: x Strength Design values: Mot sd = 38,137 #--ft Mot sd=Fp des(z) Mres (x)s= 107,954 #-ft Mres(x)s=(.9Wp-Fp vert)(x1) 0.9Wp per IBC EQ 16-7 T= -1042 # Tension force on legs=T=(Mot sd-Mres(x)s)/x Tension per leg = 0 #Tension per leg Tension per leg =T/[No. of legs in ten.(x)] Check Tool for overturning: in y direction Mres (y) = 54,487 #-in Mres(y)=(.6*Wp-Fp v asd) *yl .6 Wp Check if Mres (y)> Mot No net overturning Check Compressive Force on support(y): C= 1,451 # C=(Mot+(distance of supports(y)-y1)*(Wp+Fp v asd)]/distance of supports(y) c per leg= 725 #max/leg N/A Not on RMF Anchorage Design: y Strength Design values: Mres (y)s= 82,915 #-ft Mres(y)s=(.9Wp-Fp vert)(y1) 0.9Wp per IBC EQ 16-7 T= -547 # Tension force on legs=T=(Mot sd-Mres(y)s)/y Tension per leg = 0 #Tension per leg Tension per leg=T/(No.of legs in ten.(y)] Anchorage Requirements: Max shear on leg = 122 # Max shear on leg=Fp des/(No.legs in shear) Max tension on leg = 0 # , L o vco 05, 71 I le r r«r V' 110 wt° nu ix 4- 4.),4'\> Ate—7-0S ee) (),/b (46,44“; ��z�L -) TA6 b-y� 1 1.0 (alve-) Ci-r- • -776.1 4- ►<z = 1.13 , Euh C C4sc / a- 7 G-3 ►�Zt r I i�a Cuw,Plvicwi SrrArb-ri 2c carr pkn,...),.v1-7s Gam. D:SS 5Gc= Tacrc %Q C-lZ %rrf2el C- Th w,A) C4 s, 0/i)-r -2_2(t yr 2 to �- z I.i,c E7v1.:a ,0. ft,(-.7,- -r c00.!? e!1 i' Ct7A.V . Sine`) i N CtK CORBII` CONSULTING ENCT\EERSPROJECT NO: ,INC. Page: -9 i y,.' o! ]905 NW 169th Place, Suite 121 PROJECT f�?/j2-tl y f/✓a [�,p�4�0C r-1. REV Beaverton,Oregon 97006 TITLE /,,),w,> c DATE CORBIN Tel: 503/645-0176 Fax:503/645-0415 -777a—Ana ORIGINATOR %Y�,��'^' CHK • Corbin Consulting Engineers, Inc. Project No: - 1zoa I Page i of I 1905 NW 169th Place, Suite 121 Project 1 - /r»n-yi i-+vac. fuE' Rev Beaverton, Oregon 97006 Title - S;1tiLA-rl-Pg-r(r. -s?,A j3ate : I - S . coRBIN Tel: 503/645-0176 :Fax: 503/645.0415 Originator - -j,., 75 6A,,.. CHK : Wind Loads on Rooftop Structures and Equipment ' Based on the 2009 International Building Code and ASCE 7-05, 6.5.15.1 TYPICAL SCREEN WALL ...._..,,,,.. ..,- 1\0_,H___.3,----;/,�/ OV TYPICAL MECHANICAL UNIT ,, , \ , h H DV rO F r H V Input Exposure = C exposure category [6.5.6.3] KZt = 1.00 topographic factor [Figure 6-4] I = 1.00 importance factor [Table 6-1] V = 110 (mph) basic wind speed (3-second gust) B = 100 (ft) horizontal dimension of building measured normal to the wind direction h = 60 (ft) mean roof height of a building (eave height if roof angle <10°) H = 60 (ft) height to top of stucture or equipment Dv = 3.42 (ft) height of rooftop structure or equipment DH = 4.23 (ft) width of rooftop structure or equipment Analysis z = 56.58 (ft) height above ground level Kz = 1.130 velocity pressure exposure coefficient [Table 6-3] Kd = 0.90 wind directionality factor [Table 6-4] qz = 0.00256KZKZfKdV2I [Equation 6-15] qz = 31.5 (lb/ft2) velocity pressure [Equation 6-15] G = 0.85 gust effect factor [6.5.8.1] Cf = 1.3 force coefficient [Figure 6-21] Af = 14.5 (ft2) area of structure normal to the wind direction Bh = 6000.0 (ft2) building area normal to the wind direction x = 1.9 force increase factor [6.5.15.1] Results F= xgZGCfA f [Equation 6-28 and 6.5.15.1] P = 66.1 (Ib/ft2) design wind pressure, P = xqZ GC f F = 958 (Ib) design wind force 6 f yr r{ CCorbin Consulting Engineers, Inc. Project No: - j 2..pp 1 Page 1 of 1905 NW 169th Place, Suite 121 Project - 1 a 11'' )1J4< („v Rev Beaverton, Oregon 97006 Title 6� ; Ur], r 63_�T,,,S)Date : ! - •c • CORBIN Tel: 503/645-0176 Fax: 503/645.0415 Originator �;',�,;., - nr r CHK Wind Loads on Rooftop Structures and Equipment Based on the 2009 International Building Code and ASCE 7-05, 6.5.15.1 TYPICAL SCREEN WALL DH00\ DVDVTYPICAL MECHANICAL UNIT , F DH h DV� '�% V Input Exposure = C exposure category [6.5.6.3] Kzt = 1.00 topographic factor [Figure 6-4] I = 1.00 importance factor [Table 6-1] V = 110 (mph) basic wind speed (3-second gust) B = 100 (ft) horizontal dimension of building measured normal to the wind direction h = 60 (ft) mean roof height of a building (eave height if roof angle <10°) H = 60 (ft) height to top of stucture or equipment Dv = 4.17 (ft) height of rooftop structure or equipment DH = 7.81 (ft) width of rooftop structure or equipment Analysis z = 55.83 (ft) height above ground level Kz = 1.130 velocity pressure exposure coefficient [Table 6-3] Kd = 0.90 wind directionality factor [Table 6-4] qZ = 0.00256KZKZtKdV2I [Equation 6-15] qz = 31.5 (Ib/ft2) velocity pressure [Equation 6-15] G = 0.85 gust effect factor [6.5.8.1] Cf = 1.3 force coefficient [Figure 6-21] At = 32.5 (ft2) area of structure normal to the wind direction Bh = 6000.0 (ft2) building area normal to the wind direction x = 1.9 force increase factor [6.5.15.1] Results F= xgZGCfAf [Equation 6-28 and 6.5.15.1] • P = 66.1 (Ib/ft2) design wind pressure, P = xq,GC f F = 2152 (Ib) design wind force ' Corbin Consulting Engineers, Inc. R-oject No: - J zcz>l: Page 1 of 1 1905 NW 169th Place, Suite 121 Project - i,tfz-f!/ y� cop Rev Beaverton, Oregon 97006 Title - tvc,,X,,;(-r.pi-..z„;) Date : I - 1 CORBI.N Tel: 503/645-0176 Fax: 503/645.0415 Originator - �,,,A,_, ;�(:Vk( CHK : Wind Loads on Rooftop Structures and Equipment Based on the 2009 International Building Code and ASCE 7-05, 6.5.15.1 TYPICAL SCREEN WALL 01 DH ;,\ Typ1ALkECHANICAUNIT CL rs'"4/1 /' F OH \ ,--1. H h DV I - F i H V Input Exposure = C exposure category [6.5.6.3] Kzt = 1.00 topographic factor [Figure 6-4] I = 1.00 importance factor [Table 6-1] V = 110 (mph) basic wind speed (3-second gust) B = 100 (ft) horizontal dimension of building measured normal to the wind direction= 60 ( ) mean roof height g t of a building (eave height if roof angle <10°) H = 60 (ft) height to top of stucture or equipment Dv = 4.75 (ft) height of rooftop structure or equipment DH = 12.67 (ft) width of rooftop structure or equipment Analysis z = 55.25 (ft) height above ground level Kz = 1.130 velocity pressure exposure coefficient [Table 6-3] Kd = 0.90 wind directionality factor [Table 6-4] qZ = 0.00256KZKZtKdV2I [Equation 6-15] qz = 31.5 (Ib/ft2) velocity pressure [Equation 6-15] G = 0.85 gust effect factor [6.5.8.1] Cf = 1.3 force co efficient - [Figure 6-21] Af = 60.2 (ft2) area of structure normal to the wind direction Bh = 6000.0 (ft2) building area normal to the wind direction x = 1.9 force increase factor [6.5.15.1] Results F= xqZ GC fA f [Equation 6-28 and 6.5.15.1] P = 66.1 (Ib/ft2) design wind pressure, P = xgZGC f F = 3981 (Ib) design wind force II Analysis of Stresses on Anchor Clips for Residential HVAC Units Application in Areas of 110 mph Wind Speed and 80 ft Height or Less 4 Brackets per Unit Simplify Stresses on Bracket by Assuming: Point of bending Is about corner due to tension load • Point of application of tension load is top of bracket Load on screws based on distance between screws Tension Load L la.v�c R j ---- (�,��' 1;1157 A�'c height :ill screw spacing base Attachment to HVAC unit consists of four#12 screws into base rail All four screws resist shear,two screws resist bending from tension Shear load on bracket not applicable,as HVAC unit is continuous around curb and is assumed to provide lateral stability in all directions. Input: Max tension load on bracket(maximum of seismic and wind) 151 lbs F r 0,) S r'I.4 I,1_ t'f,. r Number of attachment screws 4 Y { / )� r Prying distance from bottom screw to top Bent plate 1.25 in Base of bracket 2.13 in Height of bracket 3.38 in Width of bracket 4.00 in Thickness of bracket 0.188 in Distance between screws(vertical) 0.75 in Bending moment at corner 321 in-lbs (tension load per restraint*base dimension) Output: Cross section area of bracket(width*thickness) 0.75 Section modulus of bracket 0.023 inA3 Bending stress on one-half of bracket 13,691 psi (bending moment/section modulus) Max allowable stress of steel(2/3 Fy,Fy=32 ksi) 32 21,333 psi Allowable stress/bending stress 1.56 >1.0 OK Clip is adequate Tension force in screws from tension load 257 lbs (tension load*base/prying distance) Shear force per screw from tension load 38 lbs (tension load/#of screws) Allowable tension load on#12-14 HILTI self drilling screws 132 lbs (Per ICC report ESR 2196 Table 2 into 18 ga i.e.0.048") Allowable shear load on#12-14 HILTI self drilling screws 308 lbs (Per ICC Report ESR 2198 Table 4) Allowable tension load/(total tension load/(#of screws/2) 1.03 >1.0 OK Screw is adequate Allowable shear load/shear per screw 8.16 >1.0 OK Screw is adequate Individual allowable loads>individual applied loads Sufficient margin exists for slight differences in loading. Proposed angle brackets are therefore acceptable for the stated use with #12 Hilti Kwik Self drilling screws,when installed per manufacturer guidelines,according to attached installation drawings. Limitations are Indicated on the installation drawing. INCPage: CORBII\ CONSULT NG ENGINEERS, N , PROJECT NO: I� O(2 J ��3 e 1905 NW 169th Place, Suite 121 PROJECTH�'�L U '7 /21"57R4'"1 REV Beaverton,Oregon 97006 TITLE G L I r' Df,/G DATE I iIf3b CORBIN Tel: 503/645-0176 Fax: 503/645-0415 ORIGINATOR _i) CHK • • Analysis of Stresses on Anchor Clips for Residential HVAC Units Application in Areas of 110 mph Wind Speed and 80 ft Height or Less 5 *BracketsperUnit w► rD// r Simplify Stresses on Bracket by Assuming: Point of bending is about corner due to tension load r / �1 Point of application of tension load is top of bracket Load on screws based on distance between screws Tension Load height —4.` 1-1 �2 f N (jIcY �_ screw 14 wI spacing base Attachment to HVAC unit consists of four#12 screws into base rail All four screws resist shear,two screws resist bending from tension Shear load on bracket not applicable,as HVAC unit is continuous around curb and is assumed to provide lateral stability in all directions. Input: Max tension load on bracket(maximum of seismic and wind) 175 lbs '$r'' F Oil PI/, / Number of attachment screws 4 5 C r' G--I-- Prying distance from bottom screw to top Bent plate 2.00 in Base of bracket 2.88 In Height of bracket 4.75 in Width of bracket 4.00 in Thickness of bracket 0.188 in Distance between screws(vertical) 1.50 In Bending moment at corner 503 in-lbs (tension load per restraint*base dimension) Output: Cross section area of bracket(width*thickness) 0.75 Section modulus of bracket 0.023 in A3 Bending stress on one-half of bracket 21,467 psi (bending moment/section modulus) Max allowable stress of steel(2/3 Fy,Fy=33 ksi) 33 22,000 psi Allowable stress/bending stress 1.02 >1.0 OK Clip is adequate G C .^+'`r r Tension force in screws from tension load 252 lbs (tension load*base/prying distance) Shear force per screw from tension load 44 lbs (tension load/#of screws) Allowable tension load on#12-14 HILTI self drilling screws 132 lbs (Per ICC report ESR 2196 Table 2 into 18 ga I.e.0.048") Allowable shear load on#12-14 HILTI self drilling screws 308 lbs (Per ICC Report ESR 2196 Table 4) Allowable tension load/(total tension load/(#of screws/2) 1.05 >1.0 OK Screw is adequate ' Allowable shear load I shear per screw 7.04 >1.0 OK Screw is adequate Individual allowable loads>individual applied loads Sufficient margin exists for slight differences in loading. Proposed angle brackets are therefore acceptable for the stated use with #12 Hilti Kwik Self drilling screws,when installed per manufacturer • guidelines,according to attached installation drawings. Limitations are indicated on the installation drawing. Paget• i rig CORBh COI`SULTIlG ENGI\EERS C. PROJECT NO: _I 260 — _ ___ 1905 NW 169th Place, Suite 121 I PROJECT f/t?►9C vim T /ti P9A-"^%I REV Beaverton,Oregon 97006 TITLE /;-6/t1, v ,.,] cL-(P P S DATE i/l8/r? CORBIN Tel: 503/645-0176 Fax: 503/645-0415 ORIGINATOR f) M CHK