Loading...
Report (54) CAS-CD s& C9 '711 April 18, 2013 Sprinkler 11a MICROMATIC®AND VIKING® TECHNICAL DATA MicromaticHP®STANDARD RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings Ml 49058 Telephone: 269-945-9501 Technical Services:877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Micromatic® and MicromaticHP® Standard Response Pendent Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several differ- ent finishes,temperature ratings, and K-Factors to meet design requirements.The special Polyester, Polytetrafluoroethylene (PTFE), and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive at- mospheres and are cULus listed as corrosion resistant as indicated in the Approval Chart.(Note: FM Global has no approval classification for PTFE and Polyester coat- ings as corrosion resistant.) Viking standard response sprinklers may be ordered and/or used as open sprinklers (glass bulb and pip cap assembly removed)on deluge systems. Refer to Ordering Instructions on page 11 b. _' 2. LISTINGS AND APPROVALS I-V1111101 rocs cULus Listed: Category VNIV .M FM Approved: Classes 2001, 2002, 2015, 2017, 2043 SEP 3 2013 NYC Approved: MEA 89-92-E,Volume 12 CITY OFTIGARD ABS Certified: Certificate 04-HS407984A-PDA BUILDING DIVISION VdS VdS Approved: Certificate G4040096, G4040098, G4060058, G4060059, G4980001, G4980002, G4980005, and G4980007 LPCB LPC Approved: Ref. No. 096e/06 and 167a/04 E CE Certified:Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40181,0832-CPD-2001,and 0832-CPD-2003 el MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008, and RINA Certificate No. MED497705C5 NOTE: Other International approval certificates are available upon request. Refer to Approval Charts 1-3 and Design Criteria on pages 11d-f for cULus Listing requirements, and refer to Approval Charts 4-5 and Design Criteria on pages 11g-h for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1997. Minimum Operating Pressure: 7 psi (0.5 bar)t Maximum Working Pressure:Sprinklers VK023 and VK122 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at (0.5 bar)up to 250 psi(17 bar)for high-pressure systems.High-pres- http://www.vikinggroupinc.com. sure (HP)sprinklers can be identified by locating "250" stamped on The Web site may include a more recent the deflector.All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page. maximum 175 psi(12 bar)wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65°F (-55°C) Overall Length: Refer to the Approval Charts f cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). • Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinkler 10139. Brass UNS-C84400 for all other sprinklers. Deflector:Phosphor Bronze UNS-C5100011-or Copper UNS-CI 9500 for Sprinklers 10139, 10142, 10170, 10173,and 10223.Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 09994, 10189, 10221, and 10222): Brass UNS-C36000 Form No. F_100397 Replaces page 11a-j, dated January 24, 2013. (Removed MED Approval from 10139) Sprinkler 11 b April 18, 2013 MICROMATIC®AND NIKING® TECHNICAL DATA MicromaticHP®STANDARD RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs©vikingcorp.com Bulb: Glass, nominal 5 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy,coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap for Sprinklers 09994: Brass UNS-C31400 or UNS-C31600 Pip Cap and Insert Assembly for all other Sprinklers: Copper UNS-C11000 and Stainless Steel UNS-S30400 Pip Cap Attachment(for Sprinklers 10189 and 10221): Brass UNS-C36000 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT coated Sprinklers: Belleville Spring- Exposed, Screw and Pipcap- ENT plated. ttNot for FM Approval. Ordering Information: (Also refer to the current Viking price list.) Order Micromatic®and MicromaticHP®Standard Response Pendent Sprinklers by first adding the appropriate suffix for the sprin- kler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix:Brass=A, Chrome-Enloy®=F,White Polyester=M-/W, Black Polyester=M-/B,Black PTFE=N,Wax Coated=C, Wax Over Polyester=V/W, ENT=JN Temperature Suffix: 135 °F (57 °C)=A, 155°F(68 °C)= B, 175"F (79 °C)= D, 200 °F (93 °C)= E, 212 "F (100 °C)= M, 286 °F (141 °C)=G, 360"F(182°C)=H, 500°F(260°C)=L, OPEN =Z(PTFE only). For example, sprinkler VK102 with a 1/2"thread, Brass finish and a 155°F (68 °C)temperature rating = Part No. 10139AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories"section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B(available since 2000). B.Wrench for Recessed Pendent Sprinklers: Part No. 16036W/B* (available since 2011) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool**Part No. 15915(available since 2010.) D.Wrench for Wax Coated Sprinklers: Part No. 13577W/B*(available since 2006) *A'A"ratchet is required(not available from Viking). **Allows use from the floor by attaching a length of 1"diameter CPVC tubing to the tool.Ideal for sprinkler cabinets.Refer to Bulletin F_051808. Sprinkler Cabinets: A. Six-head capacity: Part No.01724A(available since 1971) B.Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly.Water flowing through the sprinkler orifice strikes the sprinkler deflector,forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance requirements. 7. AVAILABILITY The Viking Micromatic®and MicromaticHP®Standard Response Pendent Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. April 18, 2013 Sprinkler 11c MICROMATIC®AND TECHNICAL DATA MicromaticHP®STANDARD RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Ordinary 135°F(57 °C) 100 °F(38°C) Orange Ordinary 155°F(68 °C) 100 °F(38°C) Red Intermediate 175°F(79°C) 150 °F (65 °C) Yellow Intermediate 200°F(93°C) 150 °F(65 °C) Green Intermediate 212 °F(100°C) 150 °F(65 °C) Green High 286°F(141 °C) 225°F(107°C) Blue Extra High 360°F(182 °C) 300°F(149°C) Mauve Ultra High3 500°F(260°C) 465°F(240 °C) Black Sprinkler Finishes: Brass, Chrome-Enloy®,White Polyester, Black Polyester, Black PTFE, and ENT Corrosion-Resistant Coatings':White Polyester,Black Polyester,and Black PTFE in all temperature ratings.ENT in all tempurature ratings except 135°F(57°C). Wax-Coated Brass and Wax over Polyesters for sprinklers with the following temperature ratings: 135 °F(57°C)Off-White Wax 155°F(68°C)Lt. Brown Wax 175°F(79 °C)Brown Wax 200°F (93°C)Brown Wax 212 °F (100 °C) Dk. Brown Wax6 286 °F (141 °C)Dk. Brown Wax6 Footnotes • 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above 300°F(149°C).Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300°F(149°C), response time may be severely retarded. The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments.Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment.For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester,ENT,and PTFE coatings.For PTFE coated open sprinklers only,the waterway is coated. For ENT coated automatic sprinklers,the waterway is coated. 5 Wax Over Polyester is unavailable for Sprinklers VK023 and VK122. 6 Wax meltin. •oint is 170°F 76°C for 212°F 100°C and 286°F 141 °C tem.erature rated s•rinklers. Wrench Flat r-r,='4;n I� Protective ■�I Sprinkler O �� Protective Cap Sprinkler Shield i 90996 m� Figure 1: Standard Sprinkler Wrench 10896WB Sprinkler 11d April 18, 2013 MICROMATIC®AND NIKING TECHNICAL DATA MicromaticHP® STANDARD RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Sprinkler Thread Size Nominal K- Overall Length Listings and Approvals3 Base Part SIN Factor (Refer also to Design Criteria on page 11f.) Number' NPT BSP U.S. metric2 Inches mm cULus4 NYC' VdS LPCB E Standard Orifice 10139 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Al,B4,C5,D3,F6 Al,64,C5 — — — — 1017312 VK102 -- 15 mm 5.6 80.6 2-3/16" 56 Al,B4,C5,D3,F6 Al,B4,C5 A2 A2, B4 -- 18020 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Al,B4,C5,D3 Al,B4,C5 A2 A2, B4 E213 E210•15 Large Orifice 10223 VK202 1/2" 15 mm 8.0 115.2 2-3/8" 60 Al,B4,C5,D3,F6 Al,B4,C5 A2 — -- -- 10142 VK202 3/4" 20 mm 8.0 115.2 2-5/16" 59 Al,B4,C5,D3, F6 Al,B4,C5 A2 A2 E313 E314 10170 VK202 -- 20 mm 8.0 115.2 2-3/8" 60 Al,64,C5, F6 -- A2 A2 E313 E314 Small Orifice10 1022111 VK003 1/2" 15 mm 2.8 40.3 2-3/16" 56 Al, B4,C5 See Footnote 8. -- -- — — 1018911.'2 VK003 -- 15 mm 2.8 40.3 2-3/16" 56 Al, B4, C5 — -- -- — — 1022211 VK004 1/2" 15 mm 4.2 57 2-1/4" 58 Al, B4, C5 See Footnote 8. -- — — — Approved Temperature Ratings • A-135"F(57°C),155°F(68°C),175°F(79°C),200°F(93°C),286 Approved Finishes °F(141 °C),and 360°F(182°C) 1 - Brass, Chrome-Enloy®, White Polyesters-6, Black Polyester56, and Black B- 135 °F (57 °C), 155°F(68 °C), 175°F(79 °C), and 200°F(93 PTFE5 °C) 2-Brass,Chrome-Enloy®,White Polyester',and Black Polyesters C-286°F(141 °C) 3-Brass and Chrome-Enloy® D-500°F(260'Cr 4-Wax-Coated Brass and Wax Over Polyesters E-155°F(68°C), 175°F(79°C),200°F(93°C),286°F(141 °C), 5- High Temperature 200 °F (93°C)Wax Coating (corrosion resistant); maxi- and 360°F(182°C) mum ambient temperature allowed at ceiling=150°F(65°C) F- 155°F(68°C), 175°F(79°C), 200°F(93°C),286°F(141 °C), 6-ENT' 360°F(182°C),and 500°F(260°C)9 Footnotes I Base part number is shown.For complete part number,refer to Viking's current price schedule. 2 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. 4 Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. cULus Listed as corrosion resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 'Accepted for use,City of New York Department of Buildings,MEA Number 89-92-E,Vol. 12. Meets New York City requirements,effective July 1,2008. 9 Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above 300°F(149°C).Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300°F(149°C), the response time of the Ultra-High temperature rated sprinkler may be severely retarded. 10Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. "The sprinkler orifice is bushed. 12Sprinklers 10173 and 10189 are available on special order. t3(E Certified,Standard EN 12259-1,EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. 14®MED Certified,Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. 15®MED Certified,RINA Certificate No.MED497705C5. April 18, 2013 Sprinkler 11e MICROMATIC®AND NEKING® TECHNICAL DATA MicromaticHP®STANDARD RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Sprinkler Thread Size Nominal K-Factor Overall Length Listings and Approvals' Base Part SIN (Refer also to Design Criteria on page 11f.) Number' NPT BSP U.S. metric2 Inches mm cULus4 NYC' VdS LPCB (E 12 (,f) Installed with the Viking Micromatice Model E-1 Recessed Escutcheon 10139 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 B3 - -- - - - 10173" VK102 - 15 mm 5.6 80.6 2-3/16" 56 B3 - - -- -- - 10223 VK202 1/2" 15 mm 8.0 115.2 2-3/8" 60 B3 - , -- - - - 10142 VK202 3/4" 20 mm 8.0 115.2 2-5/16" 59 83 - - - - - 10170 VK202 _ - 20 mm 8.0 115.2 2-3/8" 60 83 - -- -- - - Installed with the Viking Micromatice Model E-1 or E-2 Recessed Escutcheon 10139 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Al Al -- - -- - 1017311 VK102 - 15 mm 5.6 80.6 2-3/16" 56 Al - -- A2 - -- 18020 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Al Al - A2 B2 - 10223 VK202 1/2" 15 mm 8.0 115.2 2-3/8" 60 Al Al - -- - -- 10142 VK202 3/4" 20 mm 8.0 115.2 2-5/16" 59 Al Al - A2 B2 - 10170 VK202 - 20 mm 8.0 115.2 2-3/8" 60 Al -- - A2 B2 -- 10221910 VK003 1/2" 15 mm 2.8 40.3 2-3/16" 56 Al Al - -- - -- 10222910 VK004 1/2" 15 mm 4.2 57 2-1/4" 58 Al Al - - - - Installed with the Viking Microfast®Model F-1 Adjustable Escutcheon 10139 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Al Al - A2 - - 10223 VK202 1/2" 15 mm 8.0 115.2 2-3/8" 60 Al Al - -- - - 10221910 VK003 1/2" 15 mm 2.8 40.3 2-3/16" 56 Al Al - -- - -- Approved Temperature Ratings Approved Finishes A-135°F(57°C),155°F(68°C), 175"F(79°C),and 200°F(93"C) 1 -Brass,Chrome-Enloy°,White Polyester's,Black Polyesters',and Black PTFE' B-155°F(68°C), 175°F(79°C),and 200°F(93°C) 2-Brass, Chrome-Enloye,White Polyesters,and Black Polyesters C-286°F(141 °C) 3-ENT5 Footnotes 'Base part number is shown.For complete part number,refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. `Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. 5cULus Listed as corrosion resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. Accepted for use,City of New York Department of Buildings,MEA Number 89-92-E,Vol. 12. s Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated . wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. s The sprinkler orifice is bushed. . 10Sprinkler 10173 is available on special order. "(E Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40181,0832-CPD-2001,and 0832-CPD-2003. • Sprinkler 11f April 18, 2013 MICROMATIC®AND NIKING® TECHNICAL DATA MicromaticHP®STANDARD RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Sprinkler Thread Size Nominal Overall Length Listings and Approvals' Base Part SIN K-Factor (Refer also to Design Criteria below.) Number' NPT BSP U.S. metric2 Inches mm cULus4 NYC VdS LPCB C E0 Standard Orifice 09992 VK122 1/2" 15 mm 5.6 80.6 2-1/4" 58 Al, D2 See Footnote 5. -- -- -- -- Small Orifice' 099948,9 VK023 1/2" 15 mm 2.8 40.3 2-1/4" 58 Al See Footnote 5. -- — — -- Installed with the Viking Micromatic®Model E-1 or E-2 Recessed Escutcheon 09992 VK122 1/2" 15 mm 5.6 80.6 2-1/4" 58 Cl See Footnote 5. -- — -- 099948.9 VK023 1/2" 15 mm 2.8 40.3 2-1/4" 58 Cl See Footnote 5. -- -- -- -- Installed with the Viking Microfast®Model F-1 Adjustable Escutcheon 09992 VK122 1/2" 15 mm 5.6 80.6 2-1/4" 58 B1 See Footnote 5. -- — -- 099948.9 VK023 1/2" 15 mm 2.8 40.3 2-1/4" 58 B1 See Footnote 5. -- — — -- Approved Temperature Ratings A- 135"F(57"C), 155°F(68°C), 175°F(79"C), 200 °F(93°C),286°F(141 "C),and Approved Finishes 360"F(182°C) 1 - Brass, Chrome-Enloy®, White Polyester6,7, Black B-135°F(57"C),155°F(68"C),175"F(79"C),200°F(93"C),and 286°F(141 °C) Polyester6'7,and Black PTFE6 C-135°F(57°C), 155°F(68°C), 175"F(79"C),and 200°F(93°C) 2-Brass and Chrome-Enloy® D-500"F(260°C)70 Footnotes 'Base part number is shown. For complete part number,refer to Viking's current price schedule. 2 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. °Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. 5 Meets New York City requirements,effective July 1,2008. 6 cULus Listed as corrosion resistant. 'Other colors are available on request with the same Listings and Approvals as the standard colors. 8 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems only. 9 The sprinkler orifice is bushed. 10Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above 300°F(149°C).Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300°F(149"C), the response time of the Ultra-High temperature rated sprinkler may be severely retarded. cULus Listing Reauirements: Micromatic®and MicromaticHP®Standard Pendent Sprinklers are cULus Listed as indicated in Approval Charts 1-3 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light,Ordinary,and Extra Hazard occupancies.(Small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied,with hydraulically calculated wet systems only.Exception:4.2K sprinklers maybe installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.) • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information.Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. April 18, 2013 Sprinkler 11g MICROMATIC®AND NIKING® TECHNICAL DATA MicromaticHP®STANDARD • RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Sprinkler Base Thread Size Nominal K-Factor Overall Length FM Approvals' Part Number' SIN NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria below.) Standard Orifice 10139 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Al C3,E4,Fl,G5 101738 VK102 — 15 mm 5.6 80.6 2-3/16" 56 Al,C3 E4,Fl,G5 18020 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Al C3,E4, Fl Large Orifice 10223 VK202 1/2" 15 mm 8.0 115.2 2-3/8" 60 B2,D3,F2,G5 10142 VK202 3/4" 20 mm 8.0 115.2 2-5/16" 59 B2,D3,F2,G5 10170 VK202 — 20 mm 8.0 115.2 2-3/8" 60 B2, D3, F2, G5 Small Orifice 10221' VK003 1/2" 15 mm 2.8 40.3 2-3/16" 56 D2 101897,8 VK003 — 15 mm 2.8 40.3 2-3/16" 56 D2 Approved Temperature Ratings A- 135 °F (57 °C), 155 °F(68 °C), 175 °F (79°C), 200 °F (93 °C), 212 °F (100 °C), Approved Finishes 286°F(141 °C),and 360°F(182°C) 1 -Brass, Chrome-Enloy®,White Polyesters,and Black Poly- B-135°F(57°C),155°F(68°C),175°F(79°C),200°F(93°C),286°F(141 °C),and esters 360°F(182°C) 2-Brass and Chrome-Enloy® C-135°F(57°C), 155°F(68°C), 175°F(79°C),200°F(93°C),and 212°F(100°C) 3-Wax-Coated Brass(corrosion resistant) D-135°F(57°C), 155°F(68°C), 175°F(79°C),and 200°F(93°C) 4-High Temperature 200°F(93°C)Wax Coating(corrosion E-286°F(141 °C) resistant); maximum ambient temperature allowed at F-500°F(260°C)s the ceiling= 150°F(65°C) G-155°F(68°C), 175°F(79°C),200°F(93°C),286°F(141 °C), 360°F(182 °C), ENT and 500°F(260*Cr Footnotes ' Base part number is shown. For complete part number,refer to Viking's current price schedule. 2 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. *FM Approved as standard response Non-Storage pendent sprinklers. For specific application and installation requirements,reference the latest ap- plicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). 5 Other colors are available on request with the same Approvals as the standard colors. 6 Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above 300°F(149°C).Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300°F(149°C), the response time of the Ultra-High temperature rated sprinkler may be severely retarded. 'The sprinkler orifice is bushed. 8 Sprinklers 10173 and 10189 are available on special order. Sprinkler 11h April 18, 2013 MICROMATIC®AND • NII<IN4 TECHNICAL DATA MicromaticHP®STANDARD RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Sprinkler Base Thread Size Nominal K-Factor Overall Length FM Approvals3 Part Number' SIN NPT BSP U.S. metric' Inches mm (Refer also to Design Criteria on page 11 i.) Installed with the Viking Micromatice Model E-1 Recessed Escutcheon 10139 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 C4 101737 VK102 — 15 mm 5.6 80.6 2-3/16" 56 C4 10223 VK202 1/2" 15 mm 8.0 115.2 2-3/8" 60 C4 10142 VK202 3/4" 20 mm 8.0 115.2 2-5/16" 59 C4 10170 VK202 — 20 mm 8.0 115.2 2-3/8" 60 C4 Installed with the Viking Micromatice Model E-1 or E-2 Recessed Escutcheon 10139 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Cl 101737 VK102 — 15 mm 5.6 80.6 2-3/16" 56 Cl 18020 VK102 1/2" 15 mm 5.6 80.6 2-3/16" 56 Cl 10223 VK202 1/2" 15 mm 8.0 115.2 2-3/8" 60 B2 10142 VK202 3/4" 20 mm 8.0 115.2 2-5/16" 59 B2 10170 VK202 — 20 mm 8.0 115.2 2-3/8" 60 B2 102216 VK003 1/2" 15 mm 2.8 40.3 2-3/16" 56 A34 Approved Temperature Ratings Approved Finishes A-135°F(57"C),155°F(68 CC),175°F(79°C),200°F(93°C),and 212"F(100"C) 1-Brass,Chrome Enloye,White Polyesters,and Black Polyesters B-135°F(57°C), 155°F(68"C), 175°F(79°C),and 200°F(93°C) 2-Brass and Chrome-Enloy® C-155°F(68°C), 175°F(79°C),and 200°F(93°C) 3-Brass 4-ENT Footnotes I Base part number is shown.For complete part number,refer to Viking's current price schedule. s Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. *FM Approved as standard response pendent Non-Storage sprinklers.For specific application and installation requirements,reference the latest ap- plicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). 5 Other colors are available on request with the same Listings and Approvals as the standard colors. 6 The sprinkler orifice is bushed. Sprinkler 10173 is available on special order. FM Approval Reauirements; The sprinklers indicated in Approval Charts 4 and 5 are FM Approved as standard response Non-Storage pendent sprinklers as indicated in the FM • Approval Guide.For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflector distance below the ceiling. • NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT:Always refer to Bulletin Form No.F_091699-Care and Handling of Sprinklers.Also refer to page SR1-3 for gen- eral care,installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data,the appropriate standards of NFPA, FM Global, LPCB,APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances,and standards,whenever applicable. April 18, 2013 Sprinkler 11i NIKING® MICROMATIC®AND TECHNICAL DATA MicromaticHP® STANDARD RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1 I I I lli =X11/ illi �L 1 I I .!_'1I 'l 'l. I 1wama1- -\ 1,,;111111 Sprinkler Wrench MR -i I t t 16036W/Bee for j iI recessed pendent j j sprinklers1111111 I Carefully slide the --.— **A 1/2' ratchet is required �1/ I wrench sideways (not available from Viking). 'I I around the protective f- "!!11{//l cap, ensuring engage- r s' Ment with the sprinkler cm m al�s=� ==� wrench flats. Figure 2: Wrench 16036WB for Recessed Pendent Sprinklers l i l 1 1 1 1 • - -] ===.7___7_ REM L ljj 1prnerrench13577W/Bxx for\�/ installing wax coated sprinklers AM Step 1; Carefully slide the ~ wrench sideways around l Wax Coated the sprinkler deflector. [--"------ 1 11:17 Pendent Sprinkler - - 1 1 L Step 2: Carefully press ' **A 1/2' ratchet is required MN the wrench upward and (not available from Viking), ensure engagement with 1 f the sprinkler wrench flats. Figure 3: Wrench 13577W/B for Wax Coated Sprinklers Sprinkler 11j April 18, 2013 MICROMATIC®AND TECHNICAL DATA MicromaticHP® STANDARD . VIKING® RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Ceiling Opening Size: 2-5/16" (58.7 mm) minimum 5-1/8" (54 mm) 2-1/2" (63.5 mm) maximum 1/2" NPT —_� •— 11583126\mo 11 1.1111rfitim—111.111 \ 2-1/4" 1-3/4" (58 mm) (44.5 mm) 2" 1-1/2" (38 mm) tit (51 mm) tif, Minimum / llIL Maximum Installed with a Pendent Sprinkler VK102 standard 1/8" surface– Installed with a Microfast mounted escutcheon. Model F-1 Adjustable Escutcheon Figure 4: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon Ceiling Opening Size: 2-5/16" (58.7 mm) minimum 2-1/8" 2-1/2" (63.5 mm) maximum 2-1/8" (54 mm) (54 mm) —� =1111491[21-1&I 1 MEM 1.47. /�V1-3 4" 1-1/8" (28.6 mm) / � 2"Minimum ` 1-1/8" (28.6 mm) (44.5 mm) (51 mm) Minimum Maximum i Maximum - _.. i Installed with a Micromatic Installed with a Model E-2 Model E-1 Recessed Escutcheon Thread–on Recessed Escutcheon Figure 5: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons Form No. F_100397 Replaces page 11a-j, dated January 24, 2013. (Removed MED Approval from 10139)