February 24, 2009 II
i
i
RE: FIRE SPRINKLER SYSTEM
TIGARD
Project Information
Building Permit: BUP2009-00023 Construction Type: 3-B
Tenant Name: Bridgeport Dist. Occupancy Type: S-1
Address: 15605 SW 72nd Occupant Load: NA
Area: NA Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; National Fire Protection Association, Standard 13 (NFPA 13)
2002 edition and the State of Oregon Fire Code (OFC) 2007edition.
GENERAL
1. A supply of spare sprinklers (never less than 6) shall be maintained on the
premises so that any sprinklers that have operated or been damaged in any way
can be promptly replaced. These sprinklers shall correspond to the types and
temperature ratings of the sprinklers on the property. Sections 6.2.9.1 & 6.2.9.2
NFPA 13.
2. The spare sprinklers shall be kept in a cabinet located where temperatures will
not exceed 100 degrees "F" at any time. A special sprinkler wrench shall be
provided and kept in the sprinkler cabinet to be used in the removal and
installation of sprinklers. Sections 6.2.9.3 & 6.2.9.6 NFPA 13.
3. The clearance between the deflector and the top of storage shall be 18 inches or
greater. Section 8.6.6.1 NFPA 13. The distance shall be increased to 36 inches
for Large Drop sprinkler heads. Section 8.11.6 NFPA 13
4. Sprinklers shall be located a minimum of 4 inches from walls and spaced not less
than 6 feet on center. Sections 8.6.3.3 & 8.6.3.4.1 NFPA 13.
5. Clearances shall be provided around all piping extending through platforms,
foundations, walls and floors. The diameter of the hole shall be 2 inches larger
than the penetrating pipe for pipe sizes 1 inch through 31/2 inches. The diameter
of the hole shall be 4 inches larger than the penetrating pipe for pipe sizes 4
inches and larger 2 inches is required. Sections 9.3.4.1 & 9.3.4.2 NFPA 13.
6. All valves controlling the water supply for automatic sprinkler systems and all
water flow monitoring devices shall be electrically monitored when the system
serves more than 20 heads. Section 903.4 OFC
7 An approved audible sprinkler flow alarm shall be provided on the exterior of the
building in an approved location. Such sprinkler water-flow devices shall be
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard-or.gov • TTY Relay: 503.684.2772
activated by water flow equivalent to the flow of a single sprinkler of the smallest
orifice size installed in the system. Section 903.4.2 OFC
8. The system piping shall be braced to resist both lateral and longitudinal
horizontal seismic loads to prevent vertical motion resulting from seismic loads.
The structural components to which bracing is attached shall be determined to be
capable of carrying the added applied seismic loads. Sway braces shall be
designed to withstand forces in tension and compression. Bracing shall be
attached directly to feed and cross mains.
9. The end sprinkler on a line shall be restrained against excessive vertical and
lateral movement.
10.Sprinkler system piping shall be hydrostatically tested at 200 psi and shall
maintain that pressure without loss for two hours.
11.All concealed spaces enclosed wholly or partly by exposed combustible
construction shall be protected by sprinklers.
12.Dry systems shall be flowed through the remote inspectors test with the smallest
sprinkler orifice used in the system. The time required for water flow to the
inspectors test, the clapper trip time and the time it takes for the compressor to
turn on shall be noted on the NFPA Completion Form.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson,
Senior Plans Examiner
(503) 718-2436
dann@tigard-or.gov
4
Aft.
Vico I Flow ControlTyco Fire
Products CENTRAL
Customer Service/Sales:
Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 Tel:(215)362-0700/(800)523-6512
Fax:(215)ro2-,,,,5,,,_,3:157.4
Series TY-B — 5.6 an 8. -factor
Upright and Pendent Sprinklers
- Standard Response, Standard Coverage
obtained by utilizing the Series TY-B
General Pendent Sprinkler in combination with
the Model S2 Shield.Description
WARNINGS , •-- °4,
The Series TY-B,5.6 and 8.0 K-factor, The Series TY-B Sprinklers described . }
Upright and Pendent Sprinklers de- herein must be installed and main-
scribed in this data sheet are standard tained in compliance with this docu- it
response - standard coverage, deco- ment, as well as with the applicable II i
rative 5 mm glass bulb type spray standards of the National Fire Protec
sprinklers designed for use in light, tion Association, in addition to the
ordinary, or extra hazard, commercial standards of any other authorities hay- ----"-,1
4—.4.,_
occupancies such as banks, hotels, ing jurisdiction. Failure to do so may .- -"
shopping malls, factories, refineries, impair the integrity of these devices.
` chemical plants, etc.
The owner is responsible for maintain-
` The recessed version of the Series ing their fire protection system and de- .
TY-B Pendent Sprinkler, where appli- vices in proper operating condition. .joit ._
cable, is intended for use in areas with The installing contractor or sprinkler
k a finished ceiling. It uses a two-piece manufacturer should be contacted `f - - ``
Style 10(1/2 inch NPT)or Style 40(3/4 relative to any questions.
inch NPT) Recessed Escutcheon.The . 4,
Recessed Escutcheon provides 1/2
inch (12,7 mm) of recessed adjust01.4114 Ai ,?
-
ment or up to 3/4 inch (19,1 mm) of Model/Sprinkler '-;� AP
total adjustment from the flush pen-
dent position.The adjustment provided Identification
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe Numbers
drops to the sprinklers must be cut.
Corrosion resistant coatings, where TY3151 - Upright 5.6K,1/2"NPT Temperature Ratings
applicable, are utilized to extend the TY3251 - Pendent 5.6K,1/2"NPT Refer to Table A
life of copper alloy sprinklers beyond TY4151 - Upright 8.0K,3/4"NPT
that which would otherwise be ob- TY4251 - Pendent 8.0K,3/4"NPT Finishes •
tained when exposed to corrosive at- TY4851 - Upright 8.0K,1/2"NPT Sprinkler: Refer to Table A
mospheres. Although corrosion resis- TY4951 - Pendent 8.0K,1/2"NPT Recessed Escutcheon:White Coated,
tant coated sprinklers have passed the Chrome Plated, (Other colors are
standard corrosion tests of the appli- available on request.)
Technical
- cable approval agencies,the testing is Physical Characteristics
not representative of all possible cor- DataFrame Bronze
rosive atmospheres. Consequently, it Button Brass/Copper
is recommended that the end user be Sealing Assembly
Approvals �,
consulted with respect to the suitability Beryllium Nickel w/Teflont
UL and C-UL Listed. F
43
of these corrosion resistant coatings FM, LPCB, and NYC Approved. Bulb Glass
for any given corrosive environment. (Refer toTable Afor completeapproval Compression Screw Bronze
The effects of ambient temperature, information including corrosion resis Deflector Copper
concentration of chemicals, and tant status.) iu
gas/chemical velocity, should be con- y
sidered, as a minimum, along with the Maximum Working Pressure C
►, corrosive nature of the chemical to 175 psi (12,1 bar) f
. which the sprinklers will be exposed. Discharge Coefficient a
• An intermediate level version of the K=5.6 GPM/psi1/2 (80,6 LPM/bar1I2) o
. Series TY B Pendent Sprinkler can be K=8.0 GPM/psi112(115,2 LPM/bar1/2) }
Page 1 of 8 FEBRUARY,,2002 TFP151 (1-5.1)
Page 2 of 8 TFP151
. ESCUTCHEON 7/16"(11,1 mm) STYLE 10
PLATE SEATING ** NOMINAL RECESSED *
SURFACE 1/2 MAKE-IN ESCUTCHEON SSU
NPT DEFLECTOR
6*
t . .— -
`_%..
�._ 7/16" 1f 5
2-3/16" } ��''� (11,1 mm)
(55,6 mm) Iii A� NOMINAL 4
ihil
` MAKE-IN I I
1-1/2" itiIlh. IMO -.z —. 2
(38,1 mm) 2 3/16" ��
- - _ - (55,6 mm)
00, 111 WRENCH 0 3
.,� �r �,.��,, FLATS
( 1
SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. —moi 1/2"NPT** I
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5-Compression orifice seat on frame.
Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
STANDARD RESPONSE SERIES TY-B UPRIGHT(TY3151)AND PENDENT(TY3251)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2"(12,7 mm) STYLE 40
PLATE SEATING ** NOMINAL RECESSED *
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
6*
iii --- 0,1=4 ,ill 7
1/2" 'ter 5
2-5/16" �t •M. (12,7 mm)
(58,7 mm) ��=A1 ill 7foil MAKE-INL I I 4
lir 1-9/16" I IIIMIMmw J� 2-1/4" Po i so 2
(39,7 mm) 4 I (57,2 mm) 10# 'V Ge
WRENCH —_ 3
IIFLATS =
SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. 1 3/4"NPT**
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5-Compression 7-Ejection orifice seat on frame.
Screw Spring **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
STANDARD RESPONSE SERIES TY-B UPRIGHT(TY4151)AND PENDENT(TY4251)SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT .
• r,,;rrr i
4 ill)
Sammy .W1.11, e,
Iliere ...A
t
Patent/6.510.861
r ...)
, ,,,,,. P
American Made
\, ScrewsTM �
Threaded Rod Hangers •yr
Self-Drilling • Self-Tapping • One-Step
Anchoring System
for
WOOD • STEEL • CONCRETE t J
...and other products available!
,
1
0
re tat*
PIP!
.air I
1
c; 1
4$ 10, r
,, ,x.,.,„A,_ a 1
41,-‘,, f A
Some screws are... a
. 0 . Att. ' i 1.1
APPROVED LISTED
I
)
Check us out on line at
iiii
www.sammysuperscrew.com
Speedy Products,Inc. •2472 East Seventh Avenue•North St.Paul,MN 55109 1.-
1.888.773.0001 / Fax 1.651.773.5438
SWG Wood ,. .
...
See page 13 for Stainless Steel SIDEWINDERS
0
wboo•ifir Rod 0 Horizontal Mount Bov quantify 100 eseept as noted With this marking (•)
Use#14SW Nut Driver(Nan#101) • Boi yuantif'S0
Item# Model Rod Size Shk Dia Shk Lgth Actual Shear/Pullout #14sw(lien,#101)
300 SWG200 1/4-20 1/4 2 1725#- Pr
Note:Screws less than 2"in length
WOO' ♦`3/8"Rod•Horizontal Mount will he plated yellow. Greater than
Use i l4SW Nut Driver(Item,l 01) 2"are clear zinc per
ASTMB633111
UL Test UL Pipe Actual
Item # Model Rod Size Shk Dia Shk Lgth Load, lb. Size Shear/Pullout
18 SWG 10 3/8-16 1/4 1 #14sw,I,.tow 1
t19 SWG 20 33//88:1166 1/4 2 1250# 3 1725# Fir
26 •• SWG 25-380 3/8 2 1/2 1500# 4 2249#- Fir
25 • SWG 30 3/8-16 1/4 3
If fastening through gusset plates,use the SWD 20(see page 5)
Installations
TGI Joist/Truss
Consult truss manufacturer for
I recommended installation point.
I Sidewinder .-. (See"Special Notes"
Floor Joist a-.j on'page i")
la .-. Sidewinder
•
. . .�
1.
a
I �,
WOOD INSTALLATION INSTRUCTIONS '.
GST&SWG—See diagram figures 1-4,11-14 on page
18 and 19.
Not less than 2"nominal width(1 1/2")
(Self drilling& self-tapping into wood) up to 3 1/2"pipe;not less than 3"
nominal width 4"&5"pipe
Step 1: Insert the appropriate nut driver into a 3/8"or 1/2"
portable drill: (a) Use#14 for GST for 3/8"and 1/4"rod; (b) Installation
use #14SW for SWG, and for GST for 1/2" rod. per NFPA 13 1711,
Step 2: Insert the screw into the nut driver. Now you are
ready to install the screw.
Step 3: Position drill and begin installation: (a) for installing
GST drill should be in a vertical position; (b)for installing
, 44
SWG drill should be in a horizontal position at a right angle _..........e:.:la .--. Sidewinder
to the structural member. Minimum 21/2"from bottom for
branch lines.Minimum 3"from
Step 4: When the nut driver spins freely on the cap of the bottom for main lines.Exception:
This requirement shah not apply to 2"
screw installation is complete. or thicker nailing strips resting
on top of steel beams.
Step 5: Screw is now ready to receive 1/4", 3/8", 1/2" or
metric all thread rod or bolt stock.
,I.Eye protection should be worn at all times when install-
ing this product.
Note:Must be installed with appropriate nut driver to comply with warranty. Wood-Sidewinders 5
...ded7gggo
•
.
P.O. Box 3365 SOUTH EL MONTE • CA 91733 . (818) 444-0541 • FAX (818) 444-3887
001/020
SWAY BRACE MODEL E
SIZE
Pipe size to be braced: 1" through 8" SCH 10 and SCH 40.
Pipe size used for bracing: 1" and 1 1/4" SCH 40 IPS.
MATERIAL
Carbon Steel.
FINISH
Plain, `Electro-Galvanized and H.D.G.
. APPROVALS
(r.l°
* Patented.
* UL and cUL Listed. -
* Must be used with AFCON listed Attachment Ends.
FUNCTION
For bracing fire sprinkler pipe against sway and seismic disturbances.
The pipe attachment component used to secure the fire sprinkler piping to the brace pipe.
INSTALLATION
* Place assembly over sprinkler pipe to be braced.
* Insert bracing pipe through MODEL "E" under channel bracket.
* Tighten both hex nuts until gage spring lays flat.
FEATURES
* Can be used to brace SCH'10 and SCH 40 pipe.
* Field adjustable - Eliminates pre-engineering of brace pipe length.
* Requires no threading.
* Can be used as a 4-way riser brace.
* Gage spring allows easy verification of necessary minimum torque. (5LB/FT)
ORDERING
Part iE.1, Pipe size to be braced. Braced Pipe size and Finish.
•
P.O. Box 3365 SOUTH EL MONTE • CA 91733 • (818) 444-0541 • FAx (818) 444-3887
077
LOCKING ATTACHMENT END
f 1
•
A
O
/111131
610 Bead
cup LntSolt
MIMI
gin
SIZE •
1 and 1 1/4 inch bracing pipe. D
� 1
MATERIAL n—
" Carbon Steel.
SIZE A B C D
FINISH
•
Plain, Electro-Galvanized and H.D.G. 1" 1" 2" 2 1/32" r'
1 1/4" 1 1/8" 2 1/4" 2 9/16" 1 3/16"
APPROVALS
* Patented.
* Underwriters Laboratories Listed
FUNCTION
The building attachment component used to secure brace pipe to the structure of this sway
• bracing system.
INSTALLATION
" Insert brace pipe into fitting and against swivel bolt..
* Tighten set screw until it contacts tightly against the fitting.
FEATURES
* To be used with plain end pipe.
* Swivel design allows attachment at any angle.
* Visual inspection, proper torque when set screw head contacts bracket.
* May be ordered with larger hole. - Consult factory.
•
ORDERING
Part #, pipe size and finish.