Report l�Ll r°olcv I C75, s w 7,24-1,4 City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 February 24, 2009 II i i RE: FIRE SPRINKLER SYSTEM TIGARD Project Information Building Permit: BUP2009-00023 Construction Type: 3-B Tenant Name: Bridgeport Dist. Occupancy Type: S-1 Address: 15605 SW 72nd Occupant Load: NA Area: NA Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; National Fire Protection Association, Standard 13 (NFPA 13) 2002 edition and the State of Oregon Fire Code (OFC) 2007edition. GENERAL 1. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers on the property. Sections 6.2.9.1 & 6.2.9.2 NFPA 13. 2. The spare sprinklers shall be kept in a cabinet located where temperatures will not exceed 100 degrees "F" at any time. A special sprinkler wrench shall be provided and kept in the sprinkler cabinet to be used in the removal and installation of sprinklers. Sections 6.2.9.3 & 6.2.9.6 NFPA 13. 3. The clearance between the deflector and the top of storage shall be 18 inches or greater. Section 8.6.6.1 NFPA 13. The distance shall be increased to 36 inches for Large Drop sprinkler heads. Section 8.11.6 NFPA 13 4. Sprinklers shall be located a minimum of 4 inches from walls and spaced not less than 6 feet on center. Sections 8.6.3.3 & 8.6.3.4.1 NFPA 13. 5. Clearances shall be provided around all piping extending through platforms, foundations, walls and floors. The diameter of the hole shall be 2 inches larger than the penetrating pipe for pipe sizes 1 inch through 31/2 inches. The diameter of the hole shall be 4 inches larger than the penetrating pipe for pipe sizes 4 inches and larger 2 inches is required. Sections 9.3.4.1 & 9.3.4.2 NFPA 13. 6. All valves controlling the water supply for automatic sprinkler systems and all water flow monitoring devices shall be electrically monitored when the system serves more than 20 heads. Section 903.4 OFC 7 An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. Such sprinkler water-flow devices shall be Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard-or.gov • TTY Relay: 503.684.2772 activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Section 903.4.2 OFC 8. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to feed and cross mains. 9. The end sprinkler on a line shall be restrained against excessive vertical and lateral movement. 10.Sprinkler system piping shall be hydrostatically tested at 200 psi and shall maintain that pressure without loss for two hours. 11.All concealed spaces enclosed wholly or partly by exposed combustible construction shall be protected by sprinklers. 12.Dry systems shall be flowed through the remote inspectors test with the smallest sprinkler orifice used in the system. The time required for water flow to the inspectors test, the clapper trip time and the time it takes for the compressor to turn on shall be noted on the NFPA Completion Form. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson, Senior Plans Examiner (503) 718-2436 dann@tigard-or.gov 4 Aft. Vico I Flow ControlTyco Fire Products CENTRAL Customer Service/Sales: Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 Tel:(215)362-0700/(800)523-6512 Fax:(215)ro2-,,,,5,,,_,3:157.4 Series TY-B — 5.6 an 8. -factor Upright and Pendent Sprinklers - Standard Response, Standard Coverage obtained by utilizing the Series TY-B General Pendent Sprinkler in combination with the Model S2 Shield.Description WARNINGS , •-- °4, The Series TY-B,5.6 and 8.0 K-factor, The Series TY-B Sprinklers described . } Upright and Pendent Sprinklers de- herein must be installed and main- scribed in this data sheet are standard tained in compliance with this docu- it response - standard coverage, deco- ment, as well as with the applicable II i rative 5 mm glass bulb type spray standards of the National Fire Protec sprinklers designed for use in light, tion Association, in addition to the ordinary, or extra hazard, commercial standards of any other authorities hay- ----"-,1 4—.4.,_ occupancies such as banks, hotels, ing jurisdiction. Failure to do so may .- -" shopping malls, factories, refineries, impair the integrity of these devices. ` chemical plants, etc. The owner is responsible for maintain- ` The recessed version of the Series ing their fire protection system and de- . TY-B Pendent Sprinkler, where appli- vices in proper operating condition. .joit ._ cable, is intended for use in areas with The installing contractor or sprinkler k a finished ceiling. It uses a two-piece manufacturer should be contacted `f - - `` Style 10(1/2 inch NPT)or Style 40(3/4 relative to any questions. inch NPT) Recessed Escutcheon.The . 4, Recessed Escutcheon provides 1/2 inch (12,7 mm) of recessed adjust01.4114 Ai ,? - ment or up to 3/4 inch (19,1 mm) of Model/Sprinkler '-;� AP total adjustment from the flush pen- dent position.The adjustment provided Identification by the Recessed Escutcheon reduces the accuracy to which the fixed pipe Numbers drops to the sprinklers must be cut. Corrosion resistant coatings, where TY3151 - Upright 5.6K,1/2"NPT Temperature Ratings applicable, are utilized to extend the TY3251 - Pendent 5.6K,1/2"NPT Refer to Table A life of copper alloy sprinklers beyond TY4151 - Upright 8.0K,3/4"NPT that which would otherwise be ob- TY4251 - Pendent 8.0K,3/4"NPT Finishes • tained when exposed to corrosive at- TY4851 - Upright 8.0K,1/2"NPT Sprinkler: Refer to Table A mospheres. Although corrosion resis- TY4951 - Pendent 8.0K,1/2"NPT Recessed Escutcheon:White Coated, tant coated sprinklers have passed the Chrome Plated, (Other colors are standard corrosion tests of the appli- available on request.) Technical - cable approval agencies,the testing is Physical Characteristics not representative of all possible cor- DataFrame Bronze rosive atmospheres. Consequently, it Button Brass/Copper is recommended that the end user be Sealing Assembly Approvals �, consulted with respect to the suitability Beryllium Nickel w/Teflont UL and C-UL Listed. F 43 of these corrosion resistant coatings FM, LPCB, and NYC Approved. Bulb Glass for any given corrosive environment. (Refer toTable Afor completeapproval Compression Screw Bronze The effects of ambient temperature, information including corrosion resis Deflector Copper concentration of chemicals, and tant status.) iu gas/chemical velocity, should be con- y sidered, as a minimum, along with the Maximum Working Pressure C ►, corrosive nature of the chemical to 175 psi (12,1 bar) f . which the sprinklers will be exposed. Discharge Coefficient a • An intermediate level version of the K=5.6 GPM/psi1/2 (80,6 LPM/bar1I2) o . Series TY B Pendent Sprinkler can be K=8.0 GPM/psi112(115,2 LPM/bar1/2) } Page 1 of 8 FEBRUARY,,2002 TFP151 (1-5.1) Page 2 of 8 TFP151 . ESCUTCHEON 7/16"(11,1 mm) STYLE 10 PLATE SEATING ** NOMINAL RECESSED * SURFACE 1/2 MAKE-IN ESCUTCHEON SSU NPT DEFLECTOR 6* t . .— - `_%.. �._ 7/16" 1f 5 2-3/16" } ��''� (11,1 mm) (55,6 mm) Iii A� NOMINAL 4 ihil ` MAKE-IN I I 1-1/2" itiIlh. IMO -.z —. 2 (38,1 mm) 2 3/16" �� - - _ - (55,6 mm) 00, 111 WRENCH 0 3 .,� �r �,.��,, FLATS ( 1 SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. —moi 1/2"NPT** I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2-Button Assembly 5-Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 STANDARD RESPONSE SERIES TY-B UPRIGHT(TY3151)AND PENDENT(TY3251)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2"(12,7 mm) STYLE 40 PLATE SEATING ** NOMINAL RECESSED * SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR 6* iii --- 0,1=4 ,ill 7 1/2" 'ter 5 2-5/16" �t •M. (12,7 mm) (58,7 mm) ��=A1 ill 7foil MAKE-INL I I 4 lir 1-9/16" I IIIMIMmw J� 2-1/4" Po i so 2 (39,7 mm) 4 I (57,2 mm) 10# 'V Ge WRENCH —_ 3 IIFLATS = SSP DEFLECTOR* 2-7/8"(73,0 mm)DIA. 1 3/4"NPT** PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 -Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2-Button Assembly 5-Compression 7-Ejection orifice seat on frame. Screw Spring **Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 STANDARD RESPONSE SERIES TY-B UPRIGHT(TY4151)AND PENDENT(TY4251)SPRINKLERS 8.0 K-FACTOR, 3/4 INCH NPT . • r,,;rrr i 4 ill) Sammy .W1.11, e, Iliere ...A t Patent/6.510.861 r ...) , ,,,,,. P American Made \, ScrewsTM � Threaded Rod Hangers •yr Self-Drilling • Self-Tapping • One-Step Anchoring System for WOOD • STEEL • CONCRETE t J ...and other products available! , 1 0 re tat* PIP! .air I 1 c; 1 4$ 10, r ,, ,x.,.,„A,_ a 1 41,-‘,, f A Some screws are... a . 0 . Att. ' i 1.1 APPROVED LISTED I ) Check us out on line at iiii www.sammysuperscrew.com Speedy Products,Inc. •2472 East Seventh Avenue•North St.Paul,MN 55109 1.- 1.888.773.0001 / Fax 1.651.773.5438 SWG Wood ,. . ... See page 13 for Stainless Steel SIDEWINDERS 0 wboo•ifir Rod 0 Horizontal Mount Bov quantify 100 eseept as noted With this marking (•) Use#14SW Nut Driver(Nan#101) • Boi yuantif'S0 Item# Model Rod Size Shk Dia Shk Lgth Actual Shear/Pullout #14sw(lien,#101) 300 SWG200 1/4-20 1/4 2 1725#- Pr Note:Screws less than 2"in length WOO' ♦`3/8"Rod•Horizontal Mount will he plated yellow. Greater than Use i l4SW Nut Driver(Item,l 01) 2"are clear zinc per ASTMB633111 UL Test UL Pipe Actual Item # Model Rod Size Shk Dia Shk Lgth Load, lb. Size Shear/Pullout 18 SWG 10 3/8-16 1/4 1 #14sw,I,.tow 1 t19 SWG 20 33//88:1166 1/4 2 1250# 3 1725# Fir 26 •• SWG 25-380 3/8 2 1/2 1500# 4 2249#- Fir 25 • SWG 30 3/8-16 1/4 3 If fastening through gusset plates,use the SWD 20(see page 5) Installations TGI Joist/Truss Consult truss manufacturer for I recommended installation point. I Sidewinder .-. (See"Special Notes" Floor Joist a-.j on'page i") la .-. Sidewinder • . . .� 1. a I �, WOOD INSTALLATION INSTRUCTIONS '. GST&SWG—See diagram figures 1-4,11-14 on page 18 and 19. Not less than 2"nominal width(1 1/2") (Self drilling& self-tapping into wood) up to 3 1/2"pipe;not less than 3" nominal width 4"&5"pipe Step 1: Insert the appropriate nut driver into a 3/8"or 1/2" portable drill: (a) Use#14 for GST for 3/8"and 1/4"rod; (b) Installation use #14SW for SWG, and for GST for 1/2" rod. per NFPA 13 1711, Step 2: Insert the screw into the nut driver. Now you are ready to install the screw. Step 3: Position drill and begin installation: (a) for installing GST drill should be in a vertical position; (b)for installing , 44 SWG drill should be in a horizontal position at a right angle _..........e:.:la .--. Sidewinder to the structural member. Minimum 21/2"from bottom for branch lines.Minimum 3"from Step 4: When the nut driver spins freely on the cap of the bottom for main lines.Exception: This requirement shah not apply to 2" screw installation is complete. or thicker nailing strips resting on top of steel beams. Step 5: Screw is now ready to receive 1/4", 3/8", 1/2" or metric all thread rod or bolt stock. ,I.Eye protection should be worn at all times when install- ing this product. Note:Must be installed with appropriate nut driver to comply with warranty. Wood-Sidewinders 5 ...ded7gggo • . P.O. Box 3365 SOUTH EL MONTE • CA 91733 . (818) 444-0541 • FAX (818) 444-3887 001/020 SWAY BRACE MODEL E SIZE Pipe size to be braced: 1" through 8" SCH 10 and SCH 40. Pipe size used for bracing: 1" and 1 1/4" SCH 40 IPS. MATERIAL Carbon Steel. FINISH Plain, `Electro-Galvanized and H.D.G. . APPROVALS (r.l° * Patented. * UL and cUL Listed. - * Must be used with AFCON listed Attachment Ends. FUNCTION For bracing fire sprinkler pipe against sway and seismic disturbances. The pipe attachment component used to secure the fire sprinkler piping to the brace pipe. INSTALLATION * Place assembly over sprinkler pipe to be braced. * Insert bracing pipe through MODEL "E" under channel bracket. * Tighten both hex nuts until gage spring lays flat. FEATURES * Can be used to brace SCH'10 and SCH 40 pipe. * Field adjustable - Eliminates pre-engineering of brace pipe length. * Requires no threading. * Can be used as a 4-way riser brace. * Gage spring allows easy verification of necessary minimum torque. (5LB/FT) ORDERING Part iE.1, Pipe size to be braced. Braced Pipe size and Finish. • P.O. Box 3365 SOUTH EL MONTE • CA 91733 • (818) 444-0541 • FAx (818) 444-3887 077 LOCKING ATTACHMENT END f 1 • A O /111131 610 Bead cup LntSolt MIMI gin SIZE • 1 and 1 1/4 inch bracing pipe. D � 1 MATERIAL n— " Carbon Steel. SIZE A B C D FINISH • Plain, Electro-Galvanized and H.D.G. 1" 1" 2" 2 1/32" r' 1 1/4" 1 1/8" 2 1/4" 2 9/16" 1 3/16" APPROVALS * Patented. * Underwriters Laboratories Listed FUNCTION The building attachment component used to secure brace pipe to the structure of this sway • bracing system. INSTALLATION " Insert brace pipe into fitting and against swivel bolt.. * Tighten set screw until it contacts tightly against the fitting. FEATURES * To be used with plain end pipe. * Swivel design allows attachment at any angle. * Visual inspection, proper torque when set screw head contacts bracket. * May be ordered with larger hole. - Consult factory. • ORDERING Part #, pipe size and finish.