Loading...
Plans (50) RECEIVED tq Worldwide www.tyco-fire.com Fire Protection A=FB 4 2016 Contacts Products Series TY-FRB, 5.6 K-fact&LDI NG DIVISION Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General F . 11 1 The TYCO Series TY-FRB Sprinklers Description described herein must be installed and maintained in compliance with this doc- 1"' The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable Upright(TY313)and Pendent(TY323) standards of the National Fire Protec- Sprinklers described in this data sheet tion Association,in addition to the stan- are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction. Failure to do so may impair sprinklers designed for use in light or the performance of these devices. ordinary hazard,commercial occupan- cies such as banks, hotels, and shop- The owner is responsible for maintain- ping malls. ing their fire protection system and devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent ,, sprinkler uses one of the following: , • A two-piece Style 15 Recessed Sprinkler Escutcheon with recessed adjust- Identification a ment up to 5/8 inch (15,9 mm)from the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 . . . . . . . Upright 5.6K, 1/2-NPT ment up to 1/2 inch (12,7 mm) from TY323 . .. . . . Pendent 5.6K, 1/2-NPT the flush pendent position. The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of SeriesApprovals 175°F(79°C)TY-FRB 200°F(93°C) Sprinklers are described in UL and C-UL Listed 286°F(93-C) Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure physical Characteristics 175 psi(12.1 bar) Frame. . . . . . . . . . . . . . . . . . . Bronze 250 psi(17.2 bar)" Button. . . . . . . . . . . . . .Brass/Copper "The maximum working pressure of 250 psi Sealing Assembly. . . . . . . . .Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories, Inc.(UL). Bulb . . . . . . . . . . . . . . . . . . . . . .Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw. . . . . . . . Bronze WARNING'that provides cautions K=5.6 GPM/psi112(80,6 LPM/bars/2) Deflector. . . . . . . . . . . . . . . . . Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 a tq �� Worldwide www.tyco-fire.com Fire Protection Contacts Products Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General The owner is responsible for maintain- ing their fire protection system and Descri t/On devices in proper operating condi- p tion. Contact the installing contrac- tor TYCO Series DS-1 Dry Type Sprinklers, or product manufacturer with any questions. 5.6K Pendent, Upright, and Horizontal Sidewall,Quick Response(3 mm bulb) The Series DS-1 Dry-Type Sprinklers and Standard Coverage are decora- must only be installed in fittings that tive glass bulb automatic sprinklers meet the requirements of the Design designed for commercial use.Dry-type Criteria section. �a sprinklers are typically used where: • pendent sprinklers are required on Sprinkler dry pipe systems that are exposed I` i to freezing temperatures (e.g., Identification sprinkler drops from unheated portions of buildings) Numbers (SINS) • sprinklers and/or a portion of the 3/4 Inch NPT: connecting piping are exposed to TY3935 -Pendent freezing temperatures;for example, TY3735 -Horizontal Sidewall I sprinkler drops from wet systems 1 Inch NPT: into freezers, sprinkler sprigs TY3235 -Pendent from wet systems into unheated TY3135 -Upright attics, or horizontal piping exten- TY3335 -Horizontal Sidewall sions through a wall to protect an Technical ' unheated areas such as loading docks, overhangs, and building exteriors Data • sprinklers are used on systems that Approvals UL and C-Urove Listed are seasonally drained to avoid e. FM Approved freezing(e.g., vacation areas) NYC Approved under MEA 352-01-E Previous New York City Approval and Finishes MEA certification numbers apply to Sprinkler:Natural Brass,Chrome Plated, The Series DS-1 Dry-Type Sprinklers product as shown in this data sheet. or Signal White described herein must be installed In accordance with Section BC 3502 and maintained in compliance with this of the Construction Code,current NYC Escutcheon:Signal White,Chrome Plated, document,as well as with the applica- Approvals for use in the City of New or Brass Plated We standards of the National Fire Pro- York apply to all products that contain Physical Characteristics tection Association(NFPA),in addition UL or FM Approvals and Listings; Inlet.............................Copper to the standards of any authorities therefore, not all products currently PoCopper ke.......................Sterols having jurisdiction. Failure to do so Approved for use In the City of New Casing may impair the performance of these York will carry an actual MEA Certifi- CasingInsert .........''••Galvanized Carbon Steel devices. ............•••••• Bronze Cation number. Bulb Seat...................Stainless Steel Refer to Tables A and B. Bulb............••••••.••••.......•Glass IMPORTANT Compression Screw.................Bronze Always refer to Technical Data Maximum Working Pressure Deflector......................... Bronze Sheet TFP700 for the "INSTALLER 175 psi(12,1 bar) Frame ............................Bronze WARNING" that provides cautions Inlet Thread Connections Guide Tube.................Stainless Steel p Water Tube.................Stainless Steel with respect to handling and instal- 3/4 Inch NPT Spring.....................Stainless Steel lation of sprinkler systems and com- 1 Inch NPT or ISO 7-R 1 Plug Spring' ................ Stainless Steel ponents. Improper handling and Sealing Assembly. Beryllium Nickel w/TEFLON installation can permanently damage Discharge Coefficient Escutcheon...................Carbon Steel a sprinkler system or its compo- K=5.6 gpm/psil/2(80,6 Ipm/barl/2) 'For 3/4 inch NPT only nents and cause the sprinkler to fail Temperature Ratings to operate in a fire situation or cause Refer to Tables A and B it to operate prematurely. Page i of 10 June 2015 TFP510 GO ` �V orldwide Frre Protection f a I V Ems'Contacts www.tyco-fire.com Products FFP 4 ?_016 Series TY-FRB 5.6 K-factor It[ V of O'GARD Upright, Pendent, and Reces' Ar P nt Sprinklers Quick Response, Standard Coverage General MOTM The TYCO Series TY-FRB Sprinklers w Description described herein must be installed and maintained in compliance with this doc- The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable """ Upright(TY313)and Pendent(TY323) standards of the National Fire Protec- c S rinklers described in this data sheet p tion Association,in addition to the stan- are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction. Failure to do so may impair 1, sprinklers designed for use in light or the performance of these devices. ordinary hazard,commercial occupan- cies such as banks, hotels, and shop- The owner is responsible for maintain- ping malls. ing their fire protection system and devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: • A two-piece Style 15 Recessed Sprinkler Escutcheon with recessed adjust- Identification ment up to 5/8 inch (15,9 mm)from the flush pendent position. „ Number (SIN) 3 • A two-piece Style 20 Recessed x Escutcheon with recessed adjust- TY313 ... . . . . Upright 5.61K, 1/2"NPT .a , ment up to 1/2 inch (12,7 mm) from TY323 ... . . . Pendent 5.61K, 1/2-NPT the flush pendent position. � The adjustment provided by the Technical Temperature Ratin Recessed Escutcheon reduces the p 9 accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of SeriesApprovals 175°F(79°C) ° TY-FRB Sprinklers are described in UL and C-UL Listed 286°F(200°F(9393C) -C) Technical Data Sheet TFP357. Sprin- FM, LPCB, and VdS Approved kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi(12.1 bar) Frame. . . . . . . . . . . . . . . . . . . Bronze 250 psi(17.2 bar)" Button. . . . . . . . . . . . . .Brass/Copper -- "The maximum working pressure of 250 psi Sealing Assembly. . . . . . . . .Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories, Inc.(UL). Bulb . . . . . . . . . . . . . . . . . . . . . .Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw. . . . . . . . Bronze WARNING"that provides cautions K=5.6 GPM/psi'/2(80,6 LPM/bar'12) Deflector. . . . . . . . . . . . . . . . . Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page i of 4 FEBRUARY 2014 TFP172 tq �� Worldwide www.tyco-fire.com Fire Protection Contacts Products Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General The owner is responsible for maintain- ing their fire protection system and .. Description devices in proper operating condi- p tion. Contact the installing contrac- TYCO Series DS-1 Dry Type Sprinklers, tor or product manufacturer with any 5.6K Pendent, Upright, and Horizontal questions. 1, Sidewall,Quick Response(3 mm bulb) The Series DS-1 Dry-Type Sprinklers and Standard Coverage are decora- must only be installed in fittings that tive glass bulb automatic sprinklers meet the requirements of the Design designed for commercial use.Dry-type Criteria section. :` sprinklers are typically used where: • pendent sprinklers are required on Sprinkler dry pipe systems that are exposed to freezing temperatures (e.g., Identification sprinkler drops from unheated �■ portions of buildings) Numbers (SI NS) • sprinklers and/or a portion of the 3/4 Inch NPT: 11 connecting piping are exposed to TY3935 -Pendent freezing temperatures;for example, TY3735 -Horizontal Sidewall *., `- �: sprinkler drops from wet systems t Inch NPT: "" into freezers, sprinkler sprigs TY3235 -Pendent from wet systems into unheated TY3135 -Upright attics, or horizontal piping exten- TY3335 -Horizontal Sidewall sions through a wall to protect an Technical unheated areas such as loading docks, overhangs, and building Data exteriors • sprinklers are used on systems that Approvals are seasonally drained to avoid UL and C-UL Listed freezing(e.g., vacation areas) FM Approved NYC Approved under MEA 352-01-E Inolmn Previous New York City Approval and Finishes MEA certification numbers apply to Sprinkler:Natural Brass,Chrome Plated, The Series DS-1 Dry-Type Sprinklers product as shown in this data sheet. or Signal White described herein must be installed In accordance with Section BC 3502 and maintained in compliance with this of the Construction Code,current NYC Escutcheon:Signal White,Chrome Plated, document,as well as with the applica- Approvals for use in the City of New or Brass Plated We standards of the National Fire Pro- York apply to all products that contain Physical Characteristics tection Association(NFPA),in addition UL or FM Approvals and Listings; Inlet.............................Copper to the standards of es per having jurisdiction. Failure tohdotiso therefore, not all products currently Yoke .. ..................... stainless eel Approved for use in the City of New Casing ......... .. Galvanized Carbon Steel may impair the performance of these York will carry an actual MEA Certifi- Insert . Bronze devices. cation number. Bulb Seat................... Stainless Steel Refer to Tables A and B. Bulb...............................Glass IMPORTANT Compression Screw.................Bronze Always refer to Technical Data Maximum Working Pressure Deflector......................... Bronze Sheet TFP700 for the `INSTALLER 175 psi(12,1 bar) Frame ............................Bronze WARNING' that provides cautions Inlet Thread Connections Guide Tube.................Stainless Steel with respect to handling and instal- 3/4 Inch NPT Spring prier Tube.................Stainless Steel p g.....................Stainless Steel lation of sprinkler systems and com- 1 Inch NPT or ISO 7-R 1 Plug Spring' ................ Stainless Steel ponents. Improper handling and Sealing Assembly. Beryllium Nickel w/TEFLON installation can permanently damage Discharge Coefficient Escutcheon...................Carbon Steel a sprinkler system or its compo- K=5.6 gpm/psil/2(80,6 Ipm/bars/2) For 3/4 inch NPT only nents and cause the sprinkler to fail Temperature Ratings to operate in a fire situation or cause Refer to Tables A and B it to operate prematurely. Page i of 10 June 2015 TFP510