Loading...
Specifications PWU ENGINEERING INC. D EC 2 2 2015 n Email: muengineerinq(a-comcast.net CITY C)!-- !__ Ph: (503) 810-8309 J Structural Calculations: Job # LEN15433 Date: 12/14/15 Project: Burlington E 3-Car Master Reuse Garage Left Lot 26, Oak Crest, Tigard, OR Lennar Homes c, �GINFF �� 19421 PE '� 2 EGON Y 22 1°'v yILIP `N Expires: 06/30/2016 The following calculations are for lateral wind and seismic engineering and gravity loading of the beams and columns. Non-prescriptive foundations are outside the scope of this design and require approval from a geotechnical engineer. If the project is located on a sloping lot, the foundation system needs to be approved by a geotechnical engineer prior to construction. Failure to do so invalidates this design. The need for retaining walls for the project is the sole responsibility of the builder and a design will be included only if information provided by the builder,such as sections and drawings,are provided indicating where they are needed. All retaining wall designs should be verified by the geotechnical engineer of record for the subdivision or lot prior to construction. Failure to do so invalidates their design. The design is based on information provided by the client who is solely responsible for its accuracy. The engineering represents the finished product. Discrepancies from information provided by the client invalidate this design. PWU Engineering shall have no liability (expressed, or implied), with respect to the means and methods of construction workmanship or the actual materials used in construction. PWU Engineering Inc.shall have no obligation of liability,whether arising in contract(including warranty),Tort(including active, passive, or imputed negligence) or otherwise, for loss or use, revenue or profit, or for any other incidental or consequential damage. �PWU ENGINEERING INC. Ph: 503 810-8309, Email: pwuengineering@comcast.net The following calculations are for the Burlington E 3-Car Master plans for Plan approvals. Wind Loading: Per ASCE 7. Fig 6-2 See attached elevations for wind loading breakdown per level. 136mph Ultimate 3-sec gust Exposure B for Category I and II structure, Which is equal to 105mph ASD per the 2012 IBC and IRC with state amendments The mean roof height of the house h —26.0 approximately. D C MVVFRS A Direction _End Zones 2a�. C A MVVFRS Direction 2a ' End Zones Note: End zone may occur at any corner of the building. a= .10*50' =5.0' or for h =26' a= .4(h)=.4(26')= 10.4' a=5.0' controls a must be larger than .04(50')=2.0' and 3' Therefore: 2a= 10.0' see Fig 6-2 ASCE 7, and Figure above. Seismic Loading: D1 seismic design category per the latest edition of the state adopted code based on the 2012 IBC and IRC SDs= .76, R=6.5, W= weight of structure V= [1.2 SDs/(R x 1.4)] W V= .100 W Roof Dead load= 15 psf Floor Dead load= 15 psf Interior Wall Dead load= 6 psf Exterior Wall Dead load= 12 psf A Wind per ASCE 7 �PWU ENGINEERING INC. Project Burlington E 3-Car Direction Front to Back 3s Gust Roof Least Speed Exp. Angle A L(ft) hAVG(ft) 105mph B 33.7 1.00 50.0 26.0 D 8:12 �5 predw \ A Ertl Zones a= 5.0 ft A 19.7 ps ora= 10.4 ft B 13.5 psf Check 10psf min and a> 2.0 ft o A D rection C 15.7 psf load across all and a> 3.0 ft 2e D 10.8 psf zones. End Zonas 2a 10.0 ft Note:End zone may occur at any carom of fhe 6uidKV. WR L(ft) 10.0 20.0 10.0 hA(ft) 4.0 4.0 hB(ft) 8.0 8.0 he(ft) 4.0 hD(ft) 8.0 W(plf) 0.01 186.8 149.211 186.81 0.01 0.01 0.01 0.01 0.0 0.0 200.0 WR AVG 1 168.0 plf 10psf min load: 120.0 plf 100.0 , _• Governing value: 168.0pl 0.0 '' . •� . •fR W2 L(ft) 10.0 10.0 20.0 10.0 hA(ft) 4.5 5.5 10.0 he(ft) 4.0 he(ft) 4.5 10.0 hD(ft) W(plf) 142.7 179.01 157.01 1977or 3.31 0.01 0.01 0.01 0.0 0.0 300.0 W2AVGJ 166.5 plf 200.0 lopsf min load: 97.0 If ' ' IZI P P i oo.o �� 1 r Governing value: 166.5 pl 0.0NrP W, L(ft) hA(ft) hB(ft) he(ft) hD(ft) W(plf)1 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.0 0.0 1.o W1 AVG #DIV/0! 10psf min load: #DIV/0! 0.5 Governing value: #DIV/0! 0.0 11�IIIIIrIllllrlllllrlllllrlll11rI1111rI111U11.. .�imnrnn!rnumuflrunuwurnlnrnulrnl.,. �IIIIIrI1111rI1111rlIlllrllll;'■Illllrlllllrlllllrlllllrllll!: alai+nnlrmnrlullnunrnuunu!rnnlrllu!nonr.:illlr�. �Iinl Inruulrnll!■nulrnuunulrnmrnlcrnlnrl�aunurul�,� �I1:IIIIr1111lrlllll/IIIIIrI1lQrll'."i::Illlrlllllrlllgrll!ifrlllf!rll1�IIi� O �IIIIIri�ll!rI1111rI1111rI1111rI1111r111111.IIIIUI!IIIr111r' �IIIIIr1411rI:111rI1111rIUIlrl111lr1111111PL1lIII iifGiisil►" ��j\\ d11rI11J1111111r1i Illrlllll�llllllllllrlllll�lll[ILi O AI�IIIIIrl16"�IIIIIIIIIIIrI1111rIIiuiiu11rI1LUL ill KIlr I iiI1111Clllllrllli.rllll�rlllllrlllllrlllllrlllllrlllllrlll• nil,�nunr:lulr��uirinllrnnlrnulrnuluulunlr- /I 1r111ILUILI I11;IIIrI1111�tu111�11111Nu111�11111lIIIII�' ��� �������� ..ni�uiran n.� .rnn,�e.:.x:!11 rllll rllll.'�,11r1111 I ,I II I .+t!r111115:?'�?��?it,r�lf'�II!iiC��lllrlli;!f11111Clllli:7illlrll � a111I I II1�� O �" ..I!rllli!�111iiCln:iiliiiiCl:a/Ilill�l III!rllllli!i:!IrI�111rI1111r ��I'!l___—L�—�1►1` IIrIClIrI111i�I11fIr111:!rll�:I/II:�IrI1111111111rlllllrh:���Illllrllllll ��� airI1111rIU:!rI11NlC'1111rI11;i311111r111i!UIII■IIIIIrI1111r1111i:'1111rI11L�....,�....,.� `` �� �I I' IIIIrAlitIrllll;111111ti;I!;11111!►:IIIIrIlili:1u11r11111r11111rI1111rIi:ILHILI;rlu[Illllll1,•.. �Ir11111►`IIIIIri!Illrfllll►`III!;i[All 1r1u1111:!IIrIt111� Will IIIJAWIltu-mad 111!!!I11!!!I11!!!!tl!!!!111"ll 11 !■_!111!--allI-JLIL—�1�_r• CLAOSIC-CMA117 RATIO ABOVE(3-DYK POM � _ iiilt Iilil IIIII IIIII IIIII IIIII Illlt IIIII � ( ��_ FRONT r Wind per ASCE 7 �PWU ENGINEERING INC. Project Burlington E 3-Car Direction Side to Side 3s Gust Roof Least Speed Exp. Angle W(ft) hAVG(ft) 105mph B 33.7 1.00 50.0 26.0 ernnd 8:12 a= 5.0 ft D,fetpn ones A 19.7 psf ora= 10.4 ft B 13.5 psf Check 10psf min and a> 2.0 ft D A C 15.7 ps load across all and a> 3.0 ft 2e Direction D 10.8 psf zones. End Zones Note:Ir d zone may occur M any corner W the 2a 10.0 ft twldN. WR L(ft)l 10.0 23.5 10.0 hA(ft) 4.0 4.0 hB(ft) 7.0 7.0 he(ft) 4.0 hD(ft) 7.0 W(pif) 0.0 173.31 138.41 0.01 173.3 0.01 0.01 0.0 0.0 0.0 200.0 WR AVG 154.4 plf 10psf min load: 110.0 plf 100.0 Governing value: 154.4 pl o o W2 L(ft)l 10.0 23.5 6.5 3.5 6.5 hA(ft) 10.0 5.5 10.0 4.5 hB(ft) 3.0 he(ft) 10.0 4.5 hD(ft) W(plf) 0.01 197.0 157.01 179.01 197.01 129.21 0.01 0.01 0.0= 300.0 W2 AVG 167.0 plf 200.0 10psf min load: 96.8 plf 100.0 ,. Governing value: 0 pl 167. o.o W1 L(ft) hA(ft) hB(ft) he(ft) hD(ft) W(plf) 0.01 0.0110.0 0.01 0.01 0.01 0.01 0.01 0.0 0.0 W1 AVG I #DIV/0! 1.0 10psf min load: #DIV/0! 0.5 Governing value:I #DIV/0! 0.0 n n n TOP Kate a o 6 n TOr I•LAT[ � II p TO LEFT SIDE ELEVATION �.•.►�• _I ul n TOP P�.CT! i n TOP PLATE } REAR ELEVATION Q �( Q V Q TOP run — — � 0 Q TOP PL.A1L' i a are-r�R - r-c fRIGPT SIDE ELEVATION V.•.r-o- Seismic & Governing Values �PWU ENGINEERING INC. Project Burlington E 3-Car \VVVV Seismic Loading per latest edition of state adopted code based on 2012 IBC and IRC Design V= [1.2 SDs/(R x 1.4)]W Category R SDs D1 6.5 0.76 Roof Dead Load: 15psf Floor Dead Load: 15psf Interior Wall Dead Load: 6psf V Exterior Wall Dead Load: 12psf Check Seismic Front to Back vs Wind Seismic Wind WR = [0.100 * (15+5+3) * 43 ft] = 99.1 pil F1-68.0 plf Wind Governs W2 = [0.100 * (15+5+3+4) * 50 ft] + 99.1 plf= 234.4 plf < 334.5 plf Wind Governs W, _ [0.100 * (15+5+3+4) * + 234.4 pl = 234.4 plf #DIV/0! #DIV/0! #DIV/0! Check Seismic Side to Side vs Wind Seismic Wind WR = [0.100 * (15+5+3) * 40 ft] = 92.2 plf < 154.4 plf Wind Governs W2 = [0.100 * (15+5+3+4) * 50 ft] + 92.2 pl = 227.5 pl < 321.5 plf Wind Governs W, = [0.100 * (15+5+3+4) + 227.5 plJ= 227.5 plf #DIV/01 #DIV/0! #DIV/0! Redundancy factor= 1.0 per ASCE 7 section 12.3.4.2 Line Loads �PWU ENGINEERING ZNC. Project Burlington E 3-Car High Roof Diaphragm -Upper Floor Walls Line A.2 P = 3.36 k LTOTAL = 21.0 ft v = 3.36 k / 21.0 ft = 160 plf IType A Wall h = 8.0 ft LWORST = 21.0 ft MOT = 160 plf * 8.0 ft * 21.0 ft = 26.88 kft MR = (15 psf 3.0 ft + 12 psf * 8.0 ft) * (21.Oft)2 / 2 0.6 = 18.65 kft + (Olb * 0.0 ft + 0 Ib * 0.0 ft = 0.00 kft + 18.65 kft = 18.65 kft T = 26.88kft - 18.65kft / 21.0 ft = 0.39 k + 0.00 k = 0.39 k No hd req'd Line B P = 3.36 k LTOTAL = 29.5 ft v = 3.36 k / 29.5 ft = 114 plf IType A Wall h = 8.0 ft LWORST = 14.0 ft MOT = 114 plf * 8.0 ft * 14.0 ft = 12.76 kft MR = (15 psf 3.0 ft + 12 psf * 8.0 ft) * (14.Oft)2 / 2 * 0.6 = 8.29 kft + 0 Ib * 0.0 ft + 0 Ib * 0.0 ft = 0.00 kft + 8.29 kft = 8.29 kft T = 12.76kft - 8.29kft / 14.0 ft = 0.32 k + 0.00 k = 0.32 k No hd req'd Line 1 P = 2.09 k LTOTAL = 19.3 ft v = 2.09 k / 19.3 ft = 108 plf IType A Wall h = 8.0 ft LWORST = 4.0 ft MOT = 108 plf * 8.0 ft 4.0 ft = 3.47 kft MR = (15 psf * 2.0 ft + 12 psf * 8.0 ft) * (4.Oft)2 / 2 0.6 = 0.60 kft + 0 Ib * 0.0 ft + 0 Ib * 0.0 ft = 0.00 kft + 0.60 kft = 0.60 kft T = 3.47kft - 0.60kft / 4.0 ft = 0.72.k + 0.00 k = 0.72 k No hd req'd Line 2 P = 3.36 k LTOTAL = 12.3 ft v = 3.36 k / 12.3 ft = 274 plf IType A Wall h = 8.0 ft LWORST = 12.3 ft MOT = 274 plf * 8.0 ft * 12.3 ft = 26.87 kft MR = (15 psf * 14.0 ft + 12 psf * 8.0 ft) * (12.3ft)2 / 2 * 0.6 = 13.78 kft + 0 Ib 0.0 ft + 500 Ib * 9.0 ft = 4.50 kft + 13.78 kft = 18.28 kft T = 26.87kft - 18.28kft / 12.3 ft = 0.70 k + 0.00 k = 0.70 k No hd req'd Line 3 P = 1.27 k LTOTAL = 7.0 ft v = 1.27 k / 7.0 ft = 182 plf 7Type A Wall See FTAO Calc No hd req'd Low Roof/Upper Floor Diaphragm -Main Floor Walls Line A.1/A.2 P = 7.52 k LTOTAL = 47.5 ft v = 7.52 k / 47.5 ft = 158 plf Type A Wall h = 9.0 ft LWORST = 21.0 ft MOT = 158 plf 9.0 ft 21.0 ft = 29.93 kft MR = (15 psf 2.0 ft + 12 psf * 9.0 ft) * (21.Oft)2 / 2 0.6 = 18.3 kft + 0 Ib * 0.0 ft + 0 Ib * 0.0 ft = 0.00 kft + 18.3 kft = 18.3 kft T = 29.93kft - 18.3kft / 21.0 ft = 0.56 k + 0.00 k = 0.56 k No hd req'd Line B P = 7.52 k LTOTAL = 42.0 ft v = 7.52 k / 42.0 ft = 179 plf Type A Wall h = 9.0 ft LWORST = 42.0 ft MOT = 179 plf * 9.0 ft 42.0 ft = 67.71 kft MR = (15 psf * 2.0 ft + 12 psf * 9.0 ft) * (42.Oft)2 / 2 * 0.6 = 73.03 kft + 0 lb * 0.0 ft + 0 Ib * 0.0 ft = 0.00 kft + 73.03 kft = 73.03 kft T = (67.71 kft - 73.03kft) 42.0 ft = 0.00 k + 0.00 k = 0.00 k No hd req'd Line 1 P = 4.34 k LTOTAL = 16.5 ft v = 4.34 k / 16.5 ft = 263 plf IType B Wall See FTAO Calc No hd req'd Line 2 P = 7.54 k LTOTAL = 26.5 ft ---]v = 7.54 k / 26.5 ft = 284 plfType A Wall h = 9.0 ft LwoRST = 12.5 ft MOT = 284 plf * 9.0 ft * 12.5 ft = 31.99 kft MR = (15 psf * 2.0 ft + 12 psf 9.0 ft) * (12.5ft)2 / 2 * 0.6 = 6.47 kft + 0 lb * 0.0 ft + 500 Ib * 10.0 ft = 5.00 kft + 6.47 kft = 11.47 kft T = (31.99kft - 11.47kft) 12.5 ft = 1.64 k + 0.00 k = 1.64 k Use type 1 hd Line 3 P = 3.20 k LTOTAL = 10.5 ft v = 3.20 k / 10.5 ft = 304 plf Type B Wall h = 6.5 ft LwoRST = 1.8 ft MOT = 304 plf * 6.5 ft * 1.8 ft = 3.46 kft MR = (15 psf * 2.0 ft + 12 psf 6.5 ft) * (1.8ft)Z / 2 * 0.6 = 0.10 kft + 0 Ib * 0.0 ft + 500 Ib * 1.8 ft = 0.88 kft + 0.10 kft = 0.97 kft T = 3.46kft - 0.97kft / 1.8 ft = 1.42 k + 0.00 k See FTAO Calc Use type 1 hd on garage piers only Force Transfer Around Opening (FTAO) WOPWU ENGINEERING INC. Diekmann Technique @ Upper Floor Line 3 L, = 3.5ft Lo= 6.Oft L2= 3.5ft V= 1.27 k vA= -42 pif vp= 261 pif VF= -42 pif hu = 1.0 ft F, = 0.78k F2= 0.78k VB= 181 Of VG= 181 Of ho= 5.0 ft F, = 0.78k F2= 0.78k hL= 2.0 ft vc_ -42 pif VE= 261 pif VH= -42 pif J. T H = 0.78k H = 0.78k H=j 1.27 k * 8.0 ft) /13.0 ft= 0.78 k H:W Ratios 5.0 ft : 3.5 ft = 1.4 : 1 vh= 1.27 k/ 7.0ft= 181 pif 5.0 ft : 3.5 ft = 1.4 : 1 v„= 0.78 k/ 3.0 ft= 261 pif Use: Type A Wall 261 pif* 6.00 ft= 1.56 k F, = ( 1.56 k* 3.5 ft) 7.0ft= 0.78k F2= ( 1.56 k* 3.57)/ 7.0 ft= 0.78 k Use: (2) Bays BLKG T+C Couple after Dead Load is applied for hoidown requirements MR= [( 15psf* 2ft+ 12psf* 8.Oft) * (13.0 ft)^2 * 0.6/2] + (0.0 ft *5001b) = l 6.39 kft T= 0.78 kft- (6.39 kft / 13.0 ft) = 0.29 k +0.00k= 0.29 k No hd reg'd Force Transfer Around Opening (FTAO) I PwU ENGINEERING INC. Diekmann Technique @ Main Floor Line 1 L, = 3.5ft Lo= 5.Oft L2= 4.0ft V= 1.97 k VA= 26 plf vp= 355 pif VF= 26 plf hu = 1.0 ft F, = 0.83 k F2 = 0.95 k VB= 263 pif VG= 263 pif ho= 5.0 ft F, = 0.83k F2= 0.95k hL= 3.0 ft vc= 26 plf VE= 355 plf VH = 26 pif H = 1.42k H = 1.42k H=j 1.97k *9.Oft) 12.5 ft 1.42k H:WRatios 5.0 ft : 3.5 ft 1= 1.4 : 1 vh= 1.97 k/ 7.5ft= 263 plf 5.Oft : 4.Oft = 1.3 : 1 v„= 1.42 k/ 4.0 ft= 355 plf Use: Type B Wall = 355 plf* 5.00 ft= 1.78 k F, = ( 1.78k 3.5 ft) 7.5ft= 0.83k F2= ( 1.78 k ` 4.0 ft)/ 7.5 ft= 0.95 k Use: (2) Bays BLKG T+C Couple after Dead Load is applied for hoidown requirements MR= [( 15psf* 5 ft+ 12psf* 9.0 ft) (12.5 ft)^2 -0.6/2] +( 0.0 ft *5001b) = 8.58 kft T= 1.42 kft- (8.58 kft / 12.5 ft) =0.73 k +0.00k= 0.73 k No hd reci'd Force Transfer Around Opening (FTAO) �PWU ENGINEERING INC. Diekmann Technique @ Main Floor Line 3 L, = 3.5ft Lo = 6.Oft L2= 3.5ft V= 2.13 k vA= -117 plf vp= 491 plf VF= -117 plf hu = 1.0 ft F, = 1.47k F2 = 1.47k VB= 304 plf VG= 304 plf ho= 6.0 ft F, = 1.47k F2= 1.47k hL= 2.0 ft vc_ -117 plf VE= 491 pif VH= -117 plf H = 1.47k H = 1.47k H= (2.13k *9.Oft) 13.0 ft 1.47k H:WRatios 6.O ft : 3.5 ft = 1.7 : 1 vh= 2.13 k/ 7.0ft= 304 plf 6.Oft : 3.5ft = 1.7 : 1 v„ =I 1.47 k/ 3.0 ft= 491 plf Use: Type B Wall 491 plf* 6.00 ft= 2.95 k F, = (2.95 k3.5 ft) 7.0ft= 1.47k F2= (2.95 k' 3.5 ft)/ 7.0 ft= 1.47 k Use: (2) Bays BLKG T+C Couple after Dead Load is applied for holdown requirements MR= [( 15psf* 5ft+ 12psf* 9.0ft) * (13.0 ft)^2 - 0.6/2] +( 13.0 ft *5001b) = 15.78 kft T= 1.47 kft- ( 15.78 kft / 13.0 ft) = 0.26 k +O.00k= 0.26 k No hd reg'd .2 .}e--} e A B ne i I onaraw e�nwoay ur"Y= i � i o TowDam 4 nsv r �� am cow (V IM h)pM'!M[MT10/6St ICM I!r►b MUM UPPER FLOOR LATERAL PLAN w..r-a MaW WALL.M" TO w WHCATHM UNK CM COL WRAP 01 DAYW ret DCT WAW VM rTAO PIrTHOD 2 B .• -.e B . . . . . . . . . . . . . . . . . . . . . . . . eAAAA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . e A dill MLL M" TO WL O c NSA un cem off F FtA P ff DCT tvsv rA. P-Y rOR rTAO PCfiHOD TT' B B 1 1 raw WTen to L UP WC Wo U#LL HlttM GA tAPiet HOLDO" CCTami TOP OF WT[PI PMY CC Wuesrmmu POR SALL AND COTTOM Q TYM TW-]HOLDO@r PM HCAOM M W'-r MAX scwmxL[ret DCT LOW rot DOTAL MW MAIN FLOOR LATERAL PLAN M•.r-w B A e � YA I I e � n._ W4 A A orrCNALL awnwaaM e LAYCW I I _ I ';• WM WALL WAV '';• e L J UN cam ooLL WRAP cv DAYS FM ear IMM UPPER FLOOR LATERAL PLAN *am MALL NLWV TO IM SMAUM Lx um COL GIVAP n)WAYS roe ow Io Aaa Tae"AO Pln10D -- -- ----� . 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . e . . . . . . . . : :. .ilii -. . 2 . . . . . b'-r 1 1 e c�z TO LTA"a-M e 3 TO!!cm m GTAW Tis m TSA»Tree osr THM nOle"AO r7nbo TT' B B 1 POIN.Teti uTALL LFP MPUM Tame NOLDau11s so LULL Walaw MAY m.esTTNTeD Tae Tonus+TOP or on" TYPE 764 NOLOCUM Pee U4LL ANO 00 lCM Q r••Pee Pn LAST WeAPM Is•'-r PM FM MAL LAST MAIN FLOOR LATERAL PLAN HOLDOWN SCHEDULE MARK Boundary Tension of DF Tension of HF Anchor Anchor nchor Tensio NUMBER HOLDOWN Studs Allowable Lbs Allowable Lbs Mono Pour Two Pour End Corner S=2550, S=2550, 1 HDU2-SDS2.5 (2)2x 3075 2215 SSTB16 SSTB20L w=3610 w=3610 2 HDU4-SDS2.5 (2)2x 4565 3285 SB%X24 SB%X24 w=66� w=66705 3 HDU5-SDS2.5 (2)2x 5645 4065 SB%X24 SB 8X24 w=66705 w=66705 SSTB28 (NOTE 6.) SSTB34 (NOTE 6.) S=6395, S=7315, 4 HDU8-SDS2.5 (3)2x 7870 5665 8"MIN STEMWALL 8"MIN STEMWALL w=7615 w=8710 8 HDU11-SDS2.5 (1)6x 9535 6865 PA68-36, 10"min PA138-36, 10"min embed into 32"min embed into 32"min 9 HHDQ14-SDS2.5 (1)6x 14445 10350 width footing.If at width footing.If at retaining wall lap retaining wall lap anchor with vert reinf anchor with vert rein bar hooked to Ftg. bar hooked to Ftg. 5 MSTC28 (2)2x 3000 2590 N/A N/A 6 MSTC40 (2)2x 4335 3745 N/A N/A 7 MSTC66 (2)2x 5660 5660 N/A N/A Notes: 1 . Install all holdowns per manufactureer specificaiton per C-2011 Simpson Strong Tie catalog. 2. Match studs on schedule for walls below on all wall to wall holdowns. 3. (2)2x studs nailed together with (2) rows of 16d @ 3" o.c. staggered. Trimmer stud may be used as part of boundary member. 4. Refer to shearwall schedule and typical shearwall details for wall locations and configurations. 5. Refer to Simpson catalog for minimum embed of anchors into concrete. 6. Increase footing depth or stemwall height as required for 288" minimum embedment depth. SHEARWALLSONLY REQ'D ON INTERIOR SHEARWALLS. MARK REF NOTES: (a,i) Note: (b) EDGE NAILING FEILD NAILING SILL TO CONCRETE SILL TO WOOD SHEAR TRANSFER CAPACITY CAPACITY NUMBER SHEATHING NAIL SIZE SPACING SPACING CONNECTION. Note: (c) CONNECTION. Note (g) CLIPS (h) Lb/Ft(SEISMIC) Lb/Ft (WIND) A 16"OSB (1) SIDE 8d 6" 12" "Dia.A.B. @ 30"o/c 16d @ 4"o/c A35 @ 24"o/c 255 357 B ifi"OSB (1) SIDE(f) 8d 4" 12" Dia.A.B. @ 18"o/c (m) 16d @ 22"o/c A35 @ 15"o/c 395 553 C t6"OSB (1) SIDE(e,f) 8d 3" 12" 2"Dia.A.B. @ 12"o/c (m) 16d @ 2"o/c A35 @ 12"o/c 505 707 D 16"OSB (1) SIDE (e,f) 8d 2" 12" 2"Dia.A.B. @ 11"o/c (m) 16d @ 2"o/c A35 @ 9"o/c 670 938 E 18"OSB (2) SIDE (d,e,f) 8d 6" 12" 2"Dia.A.B. @ 12"o/c (m) 16d @ 2"o/c A35 @ 12"o/c 510 714 F 16"OSB (2) SIDE (d,e,f) 8d 4"Staggered 12" 2"Dia.A.B. @ 8"o/c (m) 16d @ 3"o/c(2) rows staggere A35 @ 6"o/c 790 1106 G is"OSB (2) SIDE(d,e,f) 8d 3"Staggered 12" 2"Dia.A.B. @ 7"o/c (m) 16d @ 2"o/c(2)rows staggered HGAI OKT @ 8"o/c 1010 1414 H 1s"OSB (2) SIDE(d,e,f) 8d 2"Staggered 12" Dia.A.B. @ 52"o/c (m) 16d @ 12"o/c(2)rows staggered HGAI OKT @ 6"o/c 1340 1876 Notes: a) All wall construction to conform to SDPWS Table 4.3A. b) Use Common Wire Nails for all wood sheathing and cooler nails for gypboard sheathing. c) A.B. minimum 7"embed into concrete. 3"x3"x/4"plate washers req'd at all shear wall A.B. in seismic zone D, E, F. d) Panel joints shall be offset to fall on different framing members or framing shall be 3x or thicker and nails on each side shall be staggered. e) 3x or Dbl 2x framing at all panel edges and nails shall be staggered. f) All edges blocked. g) Common Wire Nails. h) Clip to be attached from continuous blocking to top of continuous top plates. Clips are not required at Gyp Bd walls but blocking is attached per the toenailing schedule. i) See attached typical shearwall details. j) Sheathing to be Structrual I Sheathing. k) Values are for framing of H-F. m) 3x, Dbl 2x, or 2x Flat at panel edges. Stagger nails. See note C for plate washers and details for plate washer edge distance. On sill plates of all walls use a single 2x sill and 2x blocking in between the studs for plywood edge nailing surface. �PWU ENGINEERING INC. Ph: 503 810-8309, Email: pwuengineering@comcast.net 20(W)= 21j, ove t7p4 UT# r L = 26 ` w= 2t0�1 R= 2.73k ,2.lok 6iT*2- 277' 277' = 24opt� 6Ts R: 2.8q k 2.rok qct j.� s' ti.73k -9Yk 2.SYk sgs L 67 �L• l �,; 2.1a l< HDR @ Roof �PWU ENGINEERING INC. Loads and criteria Total Span:j 5.00 ft I =60 in Fully Braced?j Yes Point Loads Load Location Pressure Treated?i No # DL LL TL 1 0 Ib Repetitive Use?l No 2 0 Ib 3 0 Ib Wet Service?l No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent CID 1.00 # DL LL TL Start End Total CF 1.40 1 -238 plf -350 pif -588 plf 0.00 ft 5.00 ft 5.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft Deflection Criteria 4 0 plf j 0.00 ft TL U240 1 0.25 in 5 1 0 plf 0.00 ft LLI U480 1 0.13 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 0 plf 0.00 ft 5 0 plf 0.00 ft -800 -600 -400 -200 CL a 0 J 5.00 ft 200 400 600 R1 A 1.47 k 1. 800 PWU Engineering Inc.02013,Software 0.02,3/06/14 HDR @ Roof �PWU ENGINEERING INC. Results -800 -600 -400 -200 & M 0 M 200 5.00 ft 400 600 R1 R2 1.47 k 1.47 k 800 Type: Reactions (k) Douglas Fir-Larch #2 DL LL TL TL R, 595 Ib 875 Ib 1470 Ib 1.47 k R2 595 Ib 875 Ib 1470 Ib 1.47 k Size: 2000 (1) 4x8 D F#2 1500 1000 A 25.38 in' a 500 S 30.66 in' „ o 1 111.15 in4 n -500 F,; 180 psi -1000 Fb- 1260 psi -1500 F x 106 1.60 -2000 VAllowable 3.05 k 2000 MAllowable 3.22 k-ft Design values are based off NDS 2005 Edition,published by American a 1500 Wood Council. 1000 m Shear Moment 0 500 VMAX 1.47 k MMAX 1.84 k-ft VAllowable Allowable 3.05 k M 3.22 k-ft 0 Ratio 0.48 Ratio 0.57 0.00 OK OK -0.01 S Deflection `o -0.02 TL LL -0.03 Actual 0.05 in 0.03 in W o.oa Criteria 0.25 in 0.13 in Ratio 0.19 0.22 -0.05 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 HDR @ GT2 �P �EN�GINE�ERZNG� INC. Loads and criteria Total Span:j 5.00 ft I =60 in Fully Braced?l Yes Point Loads Load Location Pressure Treated?i No # DL LL TL 1 -11481b -16881b -28351b 0.75 ft Repetitive Use?j No 2 0 Ib 3 0 Ib Wet Service?i No 4 0 Ib 5 i 0 Ib Sustained Temperature? T:5 100'F Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total CF 1.20 1 -238 plf -350 pif -588 plf 0.00 ft 0.75 ft 0.75 ft 2 -51 plf -75 plf -126 plf 0.75 ft 5.00 ft 4.25 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 0 plf 0.00 ft TLI U240 1 0.25 in 5 1 0 plf 1 0.00 ft LLI 0480 1 0.13 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 PIT 0.00 ft 4 0 plf 0.00 ft 5 0 plf 0.00 ft -800 -2.84 k -600 -400 w -200 CL a 0 5.00 ft R2 200 0.77 k 400 600 R1 3.05 k 800 PVVU Engineering Inc.02013,Software 0.02,3/06/14 HDR @ GT2 �PWU ENGINEERING INC. Results -800 -2.84 k -600 -400 w -200 c. a 0 200 5.00 ft LR2 400 600 R1 3.05 k 800 Type: Reactions (k) DL LL TL TL Douglas Fir-Larch #2 R, 1233 Ib 1813 Ib 3045 Ib 3.05 k R2 310 Ib 456 Ib 766 Ib 0.77 k Size: 4000 (1) 4x10 DF#2 3000 A 32.38 int a 2000 S 49.91 in' 1 230.84 in4 n 1000 F,; 180 psi 0 Fb' 1080 psi E'x 106 1.60 -1000 VAllowable 3.89 k 2500 MAllowable 4.49 k-ft 2000 Design values are based off NDS 2005 Edition,published by American .e Wood council. 1500 c £ 1000 Shear Moment 0 500 VMAX 3.05 k MMAX 2.12 k-ft VAllowable Allowable 3.89 k M 4.49 k-ft 0 Ratio 0.78 Ratio 0.47 0.00 OK OK -0.01 Deflection c 0.01 TL LL d -0.02 Actual 0.02 in 0.01 in o -0.02 Criteria 0.25 in 0.13 in Ratio 0.08 0.10 -0.03 OK OK PWtJ Engineedng Inc.02013,Software 0.02,3/06/14 HDR @ GT3 �PWU ENGINEERING INC. Loads and criteria Total Span:j 5.00 ft I =60 in Fully Braced?j Yes Point Loads Load Location Pressure Treated?i No # DL LL TL 1 -16401b -24001b -40401b 0.75 ft Repetitive Use?l No 2 0 Ib 3 0 Ib Wet Service?i No 4 0 Ib 5 i 0 Ib Sustained Temperature? T:5 1000° Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total Cv 1.00 1 -170 plf -250 pif -420 plf 0.00 ft 0.75 ft 0.75 ft 2 -68 pif -100 plf -168 plf 0.75 ft 5.00 ft 4.25 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 0 plf 0.00 ft TLI U240 1 0.25 in 5 1 0 pifI 1 0.00 ft LLI U480 1 0.13 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 Plf 0.00 ft 4 0 pif 0.00 ft 5 0 plf 0.00 ft -800 -4.04 k -600 -400 w -200 c a 0 0 200 5.00 ft R2 1.04 k 400 600R1 4.03 k 800 PWU Engineering Inc.02013,Software 0.02,3/06/14 HDR @ GT3 �PWU ENGINEERING INC. Results -800 -600 -400 -200 a a 0 M All 200 5.00 ft R2 1.04 k 400 600 R1 800 4.03 k Type: Reactions (k) Boise Glulam 24F-V4 DL LL TL TL R, 1635 Ib 2394 Ib 4029 Ib 4.03 k R2 422 Ib 618 Ib 1040 Ib 1.04 k Size: 5000 (1) 3'/2'x9" GL 4000 A 31.50 in 3000 � 2000 S 47.25 in' 1000 1 212.63 in4 y F,; 265 psi 0 Fb' 2400 psi -1000 E'x 106 1.80 2000 VAllowable 5.57 k 4000 MAllowable 9.45 k-ft Design values are based off BOISE GLULAM Specifier Guide, ,p 3000 published by Boise Cascade EWP dated 02/28/13. 2000 d Shear Moment 0 1000 VMAX 4.03 k MMAX 2.90 k-ft VAllowable Allowable 5.57 k M 9.45 k-ft 0 Ratio 0.72 Ratio 0.31 0.00 OK OK `- -0.01 Deflection o TL LL d Actual 0.03 in 0.02 in o 0.02 Criteria 0.25 in 0.13 in Ratio 0.11 0.13 -0.03 OK OK PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #1v�PWU ENGINEERING INC. Loads and criteria TotalSpan:1 3.50 ft 1 =42 in Fully Braced?i Yes Point Loads Load Location Pressure Treated?l No # DL LL TL 1 0 Ib Repetitive Use?i No 2 0 Ib 3 0 Ib Wet Service?i No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total CF 0.90 1 -60 plf -160 pif -220 plf 0.00 ft 3.50 ft 3.50 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 1 0 plf, 0.00 ft TLI 0240 0.18 in 5 0 plf 0.00 ft LL U480 0.09 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 1 0 plf 0.00 ft 5 0 plf 0.00 ft -250 -200 -150 -100 C -50 a 0 co 50 3.50 ft 100 150 R1 R2 200 0.39 k LL.39 k 250 PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #1 �PWU ENGINEERING INC. Results -250 -200 -150 -100 w -50 a 0 0 50 3.50 ft 100 150 R1 R2 200 0.39 k 0.39 k 250 Type: Reactions (k) L Douglas Fir-Larch #2 DL LL TTLR, 105 Ib 280 Ib 385 Ib 0.39 k R2 105 Ib 280 Ib 385 Ib 0.39 k Size: 600 (1) 2x14 DF#2 400 A 19.88 int 200 S 43.89 in' o d 1 290.78 in4 v200 F,; 180 psi -400 Fb' 1 810 psi E'x 106 1.60 -600 VAllowable 2.39 k 400 MAllowable 2.96 k-ft Design values are based off NDS 2005 Edition,published by American 300 Wood Council. 200 m Shear Moment 0 100 VMAX 0.39 k MMAX 0.34 k-ft VAllowable Allowable 2.39 k M 2.96 k-ft 0 Ratio 0.16 Ratio 0.11 0.O0 OK OK 0.00 Deflection `0 0.00 TL LL d Actual 0.00 in 0.00 in o 0.00 Criteria 0.18 in 0.09 in Ratio 0.01 0.01 0.00 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 Beam #2 MPWU ENGINEERING INC. Loads and criteria Total Span:j 13.00 ft I = 156 in Fully Braced? Yes Point Loads Load Location Pressure Treated?i No # DL LL TL 1 -105 Ib -280 Ib -385 Ib 6.50 ft Repetitive Use?l No 2 0 Ib 3 0 Ib Wet Service?l No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent CID 1.00 # DL LL TL Start End Total Cv 1.00 1 -143 pif -380 pif -523 plf 0.00 ft 6.50 ft 6.50 ft 2 -203 plf -540 plf -743 plf 6.50 ft 13.00 ft 6.50 ft 3 0 plf 0.00 ft Deflection Criteria 4 0 plf 0.00 ft TLI U240 1 0.65 in 5 0 plf1 0.00 ft LLI U480 1 0.33 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 pif 0.00 ft 4 0 plf 0.00 ft 5 0O 0.00 ft -1500 -1000 -500 w -0.39 k a a 0 13.00 ft 500 1000 R1 3.95 k R2 4.66 k 1500 PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #2 � P �EN�GINEE�RING INC. Results -1500 -1000 -500 w -0.39 k CL -a 0 0 13.00 ft 500 1000 R1 3.95 k L4. 66 k 1500 Type: Reactions (k) Boise Glulam 24F-V4 DL LL TL TL R1 1076 Ib 2870 Ib 3946 Ib 3.95 k R2 1271 Ib 3390 Ib 4661 Ib 4.66 k Size: 6000 (1) 5%N12" GL 4000 A 66.00 int 2000 S 132.00 in' o d 1 792.00 in4 y -2000 Fv' 265 psi Fb- 2400 psi -aooa F x 106 1.80 -6000 VAllowable 11.66 k 20000 MAllowable 26.40 k-ft Design values are based off BOISE GLULAM Specter Guide, a 15000 published by Boise Cascade EWP dated 02/28/13. 10000 d Shear Moment 0 5000 VMAX 4.66 k MMAX 14.63 k-ft -71 . V Allowable Allowable 11.66 k M 26.40 k-ft 0 Ratio 0.40 Ratio 0.55 0.00 OK OK � -0.10 Deflection `s -0.20 TL LL d Actual 0.31 in 0.22 in o -0.30 Criteria 0.65 in 0.33 in Ratio 0.47 0.69 -0.40 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 Beam #3 MPWU ENGINEERING INC. Loads and criteria Total Span:j 7.00 ft I = 84 in Fully Braced?i Yes Point Loads Load Location Pressure Treated?l No # DL LL TL 1 0 Ib Repetitive Use? No 2 0 Ib 3 0 Ib Wet Service?i No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent CID 1.00 # DL LL TL Start End Total CF 0.90 1 -60 plf -160 plf -220 plf 0.00 ft 7.00 ft 7.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 1 0 plf 0.00 ft TLI U240 1 0.35 in 5 1 0 plf 1 0.00 ft LLI U480 I 0.18 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 0 plf 0.00 ft 5 0 plf 0.00 ft -250 -200 -150 -100 C, -50 a a 0 50 7.00 ft 100 150 R1 R2 200 0.77 k 0.77 k 250 PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #3 � PW�EN�GINEE�RING INC. Results -250 -200 -150 -100 �= -50 a 0 co 50 7.00 ft 100 150 R1 R2 200 0.77 k0.77 k 250 Type: Reactions (k) Douglas Fir-Larch #2 DL LL TL TL R, 210 Ib 560 Ib 770 Ib 0.77 k R2 210 Ib 560 Ib 770 Ib 0.77 k Size: 1000 (1) 2x14 DF#2 500 A 19.88 int n^ S 43.89 in3 o 1 290.78 in4 n F,; 180 psi -500 Fb' 810 psi F x 106 1.60 1000 VAllowable 2.39 k 1500 MAllowable 2.96 k-ft Design values are based off NDS 2005 Edition,published by American 1000 Wood Council. c m Shear Moment c 500 VMAX 0.77 k MMAX 1.35 k-ft VAllowable Allowable 2.39 k M 2.96 k-ft 0 Ratio 0.32 Ratio 0.45 0.00 OK OK _ -0.01 Deflection o TL LL Actual 0.03 in 0.02 in o o.oz Criteria 0.35 in 0.18 in Ratio 0.07 0.11 -0.03 OK OK PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #4 -�PWU ENGINEERING INC. Loads and criteria TotalSpan:1 4.00 ft 1 =48 in Fully Braced?i Yes Point Loads Load Location Pressure Treated? No # DL LL TL 1 0 Ib Repetitive Use? No 2 0 Ib 3 0 Ib Wet Service?i No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total CF 1.40 1 -247 pif -240 plf -487 plf 0.00 ft 1.50 ft 1.50 ft 2 -68 pif -100 plf -168 pif 1.50 ft 4.00 ft 2.50 ft 3 0 pif 0.00 ft Deflection Criteria 4 0 pif 0.00 ft TLI U500 1 0.10 in 5 0 pif 1 0.00 ft LLI U500 1 0.10 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 pif 0.00 ft 2 0 pif 0.00 ft 3 0 plf 0.00 ft 4 0 pif 0.00 ft 5 0 plf 0.00 ft -800 -600 -400 -200 CL a 0 co 0 4.00 ft 200 400 R2 0.43 k 600 R1 800 0.72 k PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #4 � P �EN�GZNEE�RING INC. Results -800 -600 -400 -200 a 0 111, All J 200 4.00 ft 400 R2 0.43 k 600 R1 800 0.72 k Type: Reactions (k) Douglas Fir-Larch #2 DL LL TL TL R, 354 Ib 371 Ib 725 Ib 0.72 k R2 186 Ib 239 Ib 426 Ib 0.43 k Size: 800 (1) 4x8 DF#2 600 ------- ---- — — A 25.38 int400 a 200 S 30.66 in' 0 1 111.15 in4 N F,; 180 psi -200 Fb- 1260 psi -400 F x 106 1.60 -600 VAllowable 3.05 k 600 MAllowable 3.22 k-ft _ 500 Design values are based off NDS 2005 Edition,published by American 400 Wood Council. 300 m Shear Moment c 200 VMAX 0.72 k MMAX 0.54 k-ft � 100 VAllowable Allowable 3.05 k M 3.22 k-ft 0 Ratio 0.24 Ratio 0.17 0.00 OK OK 0.00 Deflection o 0.00 TL LL d -0.01 Actual 0.01 in 0.00 in o 0.01 Criteria 0.10 in 0.10 in Ratio 0.09 0.05 -0.01 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 Beam #5 � PWU ENGINEERING INC. Loads and criteria Total Span:j 7.00 ft I = 84 in Fully Braced?i Yes Point Loads Load Location Pressure Treated?l No # DL LL TL 1 0 Ib Repetitive Use?i No 2 0 Ib 3 0 Ib Wet Service?l No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent CD 1.00 # DL LL TL Start End Total CF 1.40 1 -75 pif -200 plf -275 pif 0.00 ft 7.00 ft 7.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft Deflection Criteria 4 0 plf 0.00 ft TLI U240 1 0.35 in 5 0 plf 0.00 ft LLI U480 1 0.18 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 0 plf 0.00 ft 5 0 pif 0.00 ft -400 -300 -200 ., -100 w CL a 0 All a 7.00 ft 100 200 R1 j R2 300 0.96 k 0.96 k 400 PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #5 Nz"U ENGINEERING INC. Results -400 -300 -200 w -100 a 0 A All C 100 7.00 ft J 200 R1 R2 300 0.96 k 0.96 k 400 Type: Reactions (k) DL LL TL TL Douglas Fir-Larch #2 R, 263 Ib 700 lb—]- 963 Ib 0.96 k R2 263 Ib 700 Ib 963 Ib 0.96 k Size: 1500 (1) 4x8 DF#2 1000 A 25.38 int 500 S 30.66 in' o m 1 111.15 in4 N500 F,; 180 psi -1000 Fb' 11260 psi F x 106 1.60 1500 VAllowable 3.05 k 2000 MAllowable 3.22 k-ft Design values are based off NDS 2005 Edition,published by American a 1500 Wood Council. 1000 m SheMoment 0 500 VMAX 0.96 k MMAX 1.68 k-ft VAllowable Allowable 3.05 k M 3.22 k-ft 0 Ratio 0.32 Ratio 0.52 0.00 OK OK -0.02 2 Deflection o- o.oa TL LL -0.06 Actual 0.08 in 0.06 in o o.oa Criteria 0.35 in 0.18 in Ratio 0.24 0.35 1 -0.10 OK OK PWIJ Engineering Inc.02013,Software 0.02,3/06/14 Beam #6 �PWU ENGINEERING INC. Loads and criteria Total Span:j 3.50 ft 1 -7-47171 Fully Braced?j Yes Point Loads Load Location Pressure Treated?l No # DL LL TL 1 0 Ib Repetitive Use? No 2 0 Ib 3 0 Ib Wet Service?i No 4 0 Ib EE] 5 1 0 Ib Sustained Temperature? T<_ 100°F Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total CF 1.20 1 -171 plf -200 pif -371 plf 0.00 ft 3.50 ft 3.50 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 1 0 plf 0.00 ft .rLj U240 1 0.18 in 5 1 1 0 plf 0.00 ft LLI 0480 I 0.09 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 0 plf 0.00 ft 5 0 plf 0.00 ft -500 -400 -300 -200 .� -100 a 0 0 0 100 3.50 ft 200 300 400 R1 R2 500 0.65 k 0.65 k PVVU Engineering Inc.02013,Software 0.02,3/06/14 Beam #6 �PWU ENGINEERING INC. Results -500 -400 -300 -200 C, -100 a 0 M All 0 100 3.50 ft 200 300 400 R1 R2 0.65 k 500 0.65 k Type: Reactions (k) Douglas Fir-Larch #2 DL LL TL TL R, 299 Ib 350 Ib 649 Ib 0.65 k Rs 299 Ib 350 Ib 649 Ib 0.65 k Size: 1000 (1) 4x10 DF#2 500 A 32.38 in' S 49.91 in' o d 1 230.84 in4 CO F„' 180 psi -500 Fb' 1 1080 psi F x 106 1.60 -1000 VAllowable 3.89 k 600 MAllowable 4.49 k-ft _ 500 Design values are based off NDS 2005 Edition,published by American a 400 Wood Council. 300 m Shear Moment c zoo VMAX 0.65 k MMAX 0.57 k-ft � 100 VAllowable Allowable 3.89 k M 4.49 k-ft 0 Ratio 0.17 Ratio 0.13 0.00 OK OK � 0.00 Deflection s` 0.00 TL LL d Actual 0.00 in 0.00 in o 0.00 Criteria 0.18 in 0.09 in Ratio 0.02 0.02 0.00 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 Beam #7 MPWU ENGINEERING INC. Loads and criteria Total Span:j 5.00 ft I =60 in Fully Braced?j Yes Point Loads Load Location Pressure Treated?i No # DL LL TL 1 0 Ib Repetitive Use?i No 2 0 Ib 3 0 Ib Wet Service?l No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent CID 1.00 # DL LL TL Start End Total CF 1.40 1 -201 plf -280 plf -481 pif 0.00 ft 5.00 ft 5.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 1 0 pif, 0.00 ft TLI U240 1 0.25 in 5 1 1 0 pif 1 0.00 ft LLI U480 I 0.13 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 pif 0.00 ft 2 0 plf 0.00 ft 3 0 Plf 0.00 ft 4 0 pif 0.00 ft 5 0 plf 0.00 ft -600 -400 -200 w a 0 0 0 All 5.00 ft 200 400 R1 R2 1.20 k 1.20 k 600 PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #7 �PWU ENGINEERING INC. Results -600 -400 -200 CL a 0 5.00 ft 200 400 R1j R2 1.20 k 1.20 k 600 Type: Reactions (k) Douglas Fir-Larch #2 DL LL TL TL R, 503 Ib 700 Ib 1203 Ib 1.20 k R2 503 Ib 700 Ib 1203 Ib 1.20 k Size: 1500 (1) 4x8 DF#2 1000 A 25.38 in' 500 S 30.66 in' ,� o 1 111.15 in4 y -500 F,; 180 psi -1000 Fb- 1260 psi F x 106 1.60 15oa VAllowable 3.05 k 2000 MAllowable 3.22 k-ft Design values are based off NDS 2005 Edition,published by American 1500 Wood Council. 1000 m Shear Moment 0 500 VMAX 1.20 k MMAX 1.50 k-ft VAllowable Allowable 3.05 k M 3.22 k-ft 0 Ratio 0.39 Ratio 0.47 0.00 OK OK � -0.01 Deflection s 0.02 TL LL Actual 0.04 in 0.02 in o -0.03 Criteria 0.25 in 0.13 in Ratio 0.15 0.18 -0.04 OK OK PWII Engineering Inc.02013,Software v1.02,3/06/14 f Beam #8 �PWU ENGINEERING INC. Loads and criteria Total Span:j 3.75 ft I =45 in Fully Braced?j Yes Point Loads Load Location Pressure Treated? No # DL LL TL 1 0 Ib Repetitive Use? No 2 0 Ib 3 0 Ib Wet Service? No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent CID 1.00 # DL LL TL Start End Total CF 1.40 1 -426 pif -880 pif -1306 plf 0.00 ft 3.75 ft 3.75 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 0 plf 0.00 ft TLI U240 1 0.19 in 5 1 0 plf 0.00 ft LL U480 0.09 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 1 0 plf 0.00 ft 5 1 0 plf 0.00 ft -1500 -1000 -500 w c a 0 3.75 ft 500 1000 R1 2.45 k R2 2.45 k 1500 PWU Engineering Inc.02013,Software 0.02,3/06/14 Beam #8 �WWU ENGINEERING INC. Results -1500 -1000 -500 CL -0 0 J 3.75 ft 500 1000 R1 R2 1500 2.45 k 12.45 k Type: Reactions (k) DL LL TL TL Douglas Fir-Larch #2 R, 799 Ib 1650 Ib 2449 Ib 2.45 k R2 799 Ib 1650 Ib 2449 Ib 2.45 k Size: 3000 (1) 4x8 DF#2 2000 A 25.38 in' 1000 S 30.66 in' o 111.15 in4 y -1000 F„' 180 psi -2000 Fb' 1260 psi F x 106 1.60 -3000 VAllowable 3.05 k 2500 MAllowable 3.22 k-ft 2000 Design values are based off NDS 2005 Edition,published by American a Wood Council. 1500 c E 1000 Shear Moment 0 500 VMAX 2.45 k MMAX 2.30 k-ft VAllowable Allowable 3.05 k M 3.22 k-ft 0 Ratio 0.80 Ratio 0.71 0.00 OK OK -0.01 Deflection c -0.02 TL LL d Actual 0.03 in 0.02 in o -0.03 Criteria 0.19 in 0.09 in Ratio 0.17 0.23 -0.04 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 HDR @ Den �PWU ENGINEERING INC. Loads and criteria Total Span:j 6.00 ft I =72 in Fully Braced?l Yes Point Loads Load Location Pressure Treated?l No # DL LL TL 1 0 Ib Repetitive Use? No 2 0 Ib 3 0 Ib Wet Service? No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent CD 1.00 # DL LL TL Start End Total CF 1.20 1 -250 pif -370 pif -620 plf 0.00 ft 6.00 ft 6.00 ft 2 0 plf 0.00 ft 3 0 pif 0.00 ft Deflection Criteria 4 1 1 0 plf 0.00 ft TLI U500 1 0.14 in 5 1 0 pif 1 0.00 ft LLI U500 1 0.14 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 pif 0.00 ft 4 1 0 pif 0.00 ft 5 0 plf 0.00 ft -800 -600 -400 ., -200 w CL v 0 M All 6.00 ft 200 400 600 R1 R2 1.86 k 11.86 k 800 PWU Engineering Inc.02013,Software v1.02,3/06/14 HDR @ Den �PWU ENGINEERING INC. Results -800 -600 -400 -200 a 0 0 M All 200 6.00 ft 400 600 R1 F R2 1.86 k 1.86 k 800 Type: Reactions (k) Douglas Fir-Larch #2 DL LL TL TL R, 750 Ib 11101b 1860 Ib 1.86 k R2 750 Ib 11101b 1860 Ib 1.86 k Size: 3000 (1) 4x10 DF#2 2000 A 32.38 int 1000 S 49.91 in' o d 230.84 in4 v -1000 F,; 180 psi -2000 Fb' 1080 psi 3ooa F x 106 1.60 VAllowable 3.89 k 3000 MAllowable 4.49 k-ft _ 2500 Design values are based off NDS 2005 Edition,published by American 2000 Wood Council. 1500 m 1000 Shear Moment 0 VMAX 1.86 k MMAX 2.79 k-ft 500 VAllowable Allowable 3.89 k M 4.49 k-ft 0 Ratio 0.48 Ratio 0.62 0.00 OK OK -0.02 Deflection `o TL LL d Actual 0.05 in 0.03 in o O.oa Criteria 0.14 in 0.14 in Ratio 0.34 0.20 O.os OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 t HDR @ 1-Car Garage z"U ENGINEERING INC. Loads and criteria Total Span:j 8.00 ft I = 96 in Fully Braced?j No Unbraced Length:1 8.00 ft Point Loads Load Location Pressure Treated?l No # DL LL TL 1 -850 Ib -12501b -21001E 6.75 ft Repetitive Use?i No 2 0 Ib 3 0 Ib Wet Service?i No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total Cv 1.00 1 -131 plf -75 pif -206 pif 0.00 ft 6.75 ft 6.75 ft 2 -267 plf -275 plf -542 pif 6.75 ft 8.00 ft 1.25 ft 3 0 pif 0.00 ft Deflection Criteria 4 1 0 plf 0.00 ft TLI U240 1 0.40 in 5 0 pif 0.00 ft LL U480 0.20 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 0 plf 0.00 ft 5 0 plf 1 0.00 ft -600 -400 -2.10 k -200 w CL 0 A Ile All R1 8.00 ft 200 1.18 k 400 R2 2.98 k 600 PVVU Engineering Inc.02013,Software v1.02,3/06/14 HDR @ 1-Car Garage HRPWU ENGINEERING INC. Results -600 -400 -2.10 k -200 w CL a 0 All �° R1 8.00 ft 200 1.18 k 400 R2 [2.918k 600 Type: Reactions (k) Boise Glulam 24F-V4 DL LL I TL TL R, 670 Ib 515 Ib 1185 Ib 1.18 k R2 1398 Ib 15851b 29831b 2.98 k Size: 2000 (1) 3'/"x9" GL 1000 A 31.50 int 0 S 47.25 in' ,� -1000 d 1 212.63 in4 N2000 F,; 265 psi -3000 Fb' 2323 psi F x 106 1.80 -4000 VAllowable 5.57 k 4000 MAllowable 9.15 k-ft Design values are based off BOISE GLULAM Specter Guide, 3000 published by Boise Cascade EWP dated 02/28/13. 2000 m Shear Moment 1000 VMAX 2.98 k MMAX 3.41 k-ft VAllowable Allowable 5.57 k M 9.15 k-ft 0 Ratio 0.54 Ratio 0.37 0.00 OK OK _ -0.05 Deflection `o TL LL Actual 0.10 in 0.05 in o 0.10 Criteria 0.40 in 0.20 in Ratio 0.25 0.24 -0.15 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 HDR @ 2-Car Garage �P �EN�GZNE�ERZNG� INC. Loads and criteria Total Span:j 16.00 ft I = 192 in Fully Braced? No Unbraced Length:1 16.00 ft Point Loads Load Location Pressure Treated? No # DL LL TL 1 0 Ib Repetitive Use?l No 2 0 Ib 3 0 Ib Wet Service? No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total Cv 1.00 1 -165 plf -125 pif -290 plf 0.00 ft 16.00 ft 16.00 ft 2 0 pif 0.00 ft 3 0 pif 0.00 ft Deflection Criteria 4 0 pif 0.00 ft TLI U240 1 0.80 in 5 0 OfI 0.00 ft LLI U480 1 0.40 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 1 1 0 pif 0.00 ft 5 0 pif 0.00 ft -400 -300 -200 _ -100 w CL All a 0 co 100 16.00 ft 200 300 R1 R2 2.32 k 2.32 k 400 PWU Engineering Inc.02013,Software v1.02,3/06/14 HDR @ 2-Car Garage �PWU ENGINEERING INC. Results -400 -300 -200 w -100 a 0 M All 0 100 16.00 ft 200 300 R1 R2 2.32 k 2.32 k 400 Type: Reactions (k) Boise Glulam 24F-V4 DL LL TL TL R, 1320 Ib 1000 Ib 2320 Ib 2.32 k R2 1320 Ib 1000 Ib 2320 Ib 2.32 k Size: 3000 (1) 3'/2'x10'/" GL 2000 A 36.75 int 1000 S 64.31 in' ,� o 337.64 in4 y -1000 F,; 265 psi -2000 Fb' 2032 psi E' x 106 1.80 3000 VAllowable 6.49 k 10000 MAllowable 10.89 k-ft 8000 Design values are based off BOISE GLULAM Specifier Guide, .e published by Boise Cascade EWP dated 02/28/13. 6000 C E 4000 Shear Moment 0 2000 VMAX 2.32 k MMAX 9.28 k-ft VAllowable Allowable 6.49 k M 10.89 k-ft 0 Ratio 0.36 Ratio 0.85 0.00 OK OK -0.20 Deflection `s a.ao TL LL Actual 0.70 in 0.30 in o -0.60 Criteria 0.80 in 0.40 in Ratio 0.88 0.76 -0.80 OK OK PWU Engineering Inc.02013,Software 0.02,3/06/14 , HDR @ Greatroom ���EN�GZNE�ERXNG� INC. Loads and criteria Total Span:j 5.00 ft I =60 in Fully Braced?i Yes Point Loads Load Location Pressure Treated?l No # DL LL TL 1 -12331b -18131b -30461b 1.50 ft Repetitive Use?l No 2 0 Ib 3 0 Ib Wet Service?i No 4 0 Ib 5 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent CD 1.00 # DL LL TL Start End Total Cv 1.00 1 -477 pif -730 plf -1207 plf 0.00 ft 1.50 ft 1.50 ft 2 -239 pif -380 plf -619 pif 1.50 ft 5.00 ft 3.50 ft 3 0 pif 0.00 ft Deflection Criteria 4 1 1 0 pif 0.00 ft TLI U240 1 0.25 in 5 1 0 pif1 0.00 ft LLI U480 1 0.13 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 plf 0.00 ft 3 0 plf 0.00 ft 4 0 plf 0.00 ft 5 0 pif 0.00 ft -2500 -2000 -1500 -1000 w -500 a a 0 All 500 5.00 ft 1000 R2 1500 2.59 k 2000 R1 2500 4.43 k PWU Engineering Inc.02013,Software 0.02,3/06/14 HDR @ Greatroom � U ENGINEERING INC. Results -2500 -2000 -1500 -1000 a -500 0 M 500 5.00 ft 1000 R2 1500 2.59 k 2000 R1 2500 4.43 k Type: Reactions (k) Boise Glulam 24F-V4 DL LL TL TL R, 1763 Ib 2665 Ib 4428 Ib 4.43 k R2 1020 Ib 1573 Ib 2592 Ib 2.59 k Size: 6000 (1) 3%'x9" GL 4000 A 31.50 int a 2000 S 47.25 in' 1 212.63 in4 y 0 F„' 265 psi -2000 Fb' 2400 psi E'X 106 1.80 4000 VAllowable 5.57 k 6000 MAllowable 9.45 k-ft 5000 Design values are based off BOISE GLULAM Specifier Guide, a 4000 published by Boise Cascade EWP dated 02/28/13. 3000 d 2000 Shear Moment 0 1000 VMAX 4.43 k MMAX 5.28 k-ft 0 VAllowable Allowable 5.57 k M 9.45 k-ft -1000 Ratio 0.80 Ratio 0.56 0.00 OK OK _ -0.02 Deflection o TL LL Actual 0.06 in 0.03 in o o.oa Criteria 0.25 in 0.13 in Ratio 0.22 0.27 -0.06 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 r HDR @ Kitchen �PWU ENGINEERING INC. Loads and criteria Total Span:j 5.00 ft I =60 in Fully Braced?l Yes Point Loads Load Location Pressure Treated?i No # DL LL TL 1 -11051b -16251b -27301b 4.75 ft Repetitive Use?j No 2 0 Ib 3 0 Ib Wet Service? No 4 0 Ib 5 01 Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total Cv 1.00 1 -290 plf -455 pif -745 plf 0.00 ft 4.75 ft 4.75 ft 2 -477 plf -730 plf -1207 pif 4.75 ft 5.00 ft 0.25 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 1 0 plf 0.00 ft TL U240 1 0.25 in 5 1 1 0 plf 1 0.00 ft LLI U480 I 0.13 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 plf 0.00 ft 2 0 pif 0.00 ft 3 0 pif 0.00 ft 4 0 plf 0.00 ft 5 0 pif 0.00 ft -2500 -2000 -1500 -2.73 k -1000 -500 a a 0 co 500 R1 5.00 ft 1000 2.00 k 1500 R2 2000 4.57 k 2500 PWU Engineering Inc.02013,Software 0.02,3/06/14 HDR @ Kitchen �PWU ENGINEERING INC. Results -2500 -2000 -1500 -2.73 k -1000 a -500 -a 0 500 R1 5.00 ft 1000 2.00 k 1500 R2 2000 4.57 k 2500 Type: Reactions (k) Boise Glulam 24F-V4 DL LL TL TL Rf 780 Ib 1220 Ib 2001 Ib 2.00 k R2 1819 Ib 2748 Ib 4567 Ib 4.57 k Size: 4000 (1) 3'/2'x9" GL 2000 A 31.50 int 0 S 47.25 in' 1 212.63 in4 n -2000 F„' 265 psi -4000 Fb' 2400 psi F x 106 1.80 so0o VAllowable 5.57 k 3000 MAllowable 9.45 k-ft _ 2500 Design values are based off BOISE GLULAM Specifier Guide, 2000 published by Boise Cascade EWP dated 02/28/13. - 1500 m 1oo0 Shear Moment 0 VMAX 4.57 k MMAX 2.69 k-ft 500 V 5.57 k M 9.45 k-ft 0 Allowable Allowable Ratio 0.82 Ratio 0.28 0.00 OK OK � -0.01 Deflection `s -0.02 - TL LL d Actual 0.03 in 0.02 in o -0.03 Criteria 0.25 in 0.13 in Ratio 0.13 0.16 -0.04 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14 HDR @ Nook �PWU ENGINEERING INC. Loads and criteria TotalSpan:1 8.00 ft 1 = 96 in Fully Braced?l Yes Point Loads Load Location Pressure Treated?l No # DL LL TL 1 -11901b -17501b -29401b 2.00 ft Repetitive Use?i No 2 -595 Ib -875 Ib -1470 Ib 7.00 ft 3 0 Ib Wet Service?i No 4 0 Ib 5 i 0 Ib Sustained Temperature? T:5 100°F Uniform Loads Load Factors Load Extent Co 1.00 # DL LL TL Start End Total CV 1.00 1 -239 plf -380 plf -619 plf 0.00 ft 7.00 ft 7.00 ft 2 -477 pif -730 pif -1207 pif 7.00 ft 8.00 ft 1.00 ft 3 0 plf 0.00 ft Deflection Criteria 4 1 1 0 plf 1 0.00 ft TLI U240 1 0.40 in 5 0 plf 0.00 ft LL L/480` 0.20 in Triangular Loads Max Load Extent # DL LL TL Zero End Max End Total 1 0 pif 0.00 ft 2 0 plf 0.00 ft 3 0 plf 1 0.00 ft 4 0 plf 0.00 ft 5 0 plf 0.00 ft -2500 -2000 -1500 2.94 k -1000 -1.47 J1 w -500 CL a 0 All 500 8.00 ft 1000 1500 2000 R1 R2 4.90 k 5.05 k 2500 PWU Engineering Inc.82013,Software 0.02,3106114 HDR @ Nook \ PWU ENGINEERING INC. Results -2500 -2000 -1500 -2.94 k -1000 -1.47 k w -500 a 0 0 o 500 8.00 ft 1000 1500 2000 1 R1 R2 2500 fl 4.90 k 5.05 k Type: Reactions (k) Boise Glulam 24F-V4 DL LL TL TL R, 1936 Ib 2964 Ib 4900 Ib 4.90 k RZ 1995 Ib 3051 Ib 5047 Ib 5.05 k Size: 6000 (1) 3Y2rx10'/" GL 4000 A 36.75 int 2000 S 64.31 in' ,� 0 1 337.64 in4 y 2000 F,; 265 psi -4000 Fb' 1 2400 psi E'x 106 1.80 soon VAllowable 6.49 k 10000 MAllowable 12.86 k-ft 8000 Design values are based off BOISE GLULAM Specifier Guide, a published by Boise Cascade EWP dated 02/28/13. 6000 c 4000 Shear Moment a 2000 VMAX 5.05 k MMAX 8.98 k-ft VAllowable Allowable 6.49 k M 12.86 k-ft Ratio 0.78 Ratio 0.70 0.00 OK OK � -0.05 Deflection 00.10 TL LL d Actual 0.17 in 0.11 in o -0.15 Criteria 0.40 in 0.20 in Ratio 0.44 0.53 -0.20 OK OK PWU Engineering Inc.02013,Software v1.02,3/06/14