FIRE PROTECTION
EQUIPMENT SUBMITTAL
tqCOWorldwide
Fire Protection
Contacts www.tyco-fire.com
Products
Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General EMM
The TYCO Series TY-FRB Sprinklers
Description described herein must be installed and
The TYCO Series TY-FRB,5.6 K-factor, maintained in compliance with this doc-
ument, as well as with the applicable
Upright TY313 and Pendent TY323
( ) ( ) standards of the National Fire Protec-
Sprinklers described in this data sheet tion Association,in addition to the stan-
are quick response,standard coverage, dards of any other authorities having
decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair
sprinklers designed for use in light or the performance of these devices. `
ordinary hazard,commercial occupan-
cies such as banks, hotels,and shop- T their fireprotection blsystem and
ping malls. devices in proper operating ycondition.
p p
The recessed version of the Series TY- The installing contractor or sprinkler
FRB Pendent Sprinkler,where applica- manufacturer should be contacted with -
ble,is intended for use in areas with a any questions.
finished ceiling.This recessed pendent
sprinkler uses one of the following: wx'i
• A two-piece Style 15 Recessed Sprinkler f- -,
Escutcheon with recessed adjust- Identification
ment up to 5/8 inch (15,9 mm)from ,
the flush pendent position. Number (SII`)
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust- TY313 . .. . .. . Upright 5.6K, 1/2-NPT
ment up to 1/2 inch (12,7 mm)from TY323 . .. . . . Pendent 5.6K, 1/2-NPT
the flush pendent position.
The adjustment provided by the Technical
Recessed Escutcheon reduces the Temperature Rating
accuracy to which the fixed pipe drops Data 135°F(57°C)
to the sprinklers must be cut. 155°F(68°C)
Intermediate level versions of Series Approvals 175°F(79°C)200°F(93°C)
TY-FRB Sprinklers are described in UL and C-UL Listed 286°F(93-C)
Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved
kler guards and shields are described CE Certified Finishes
in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler:Refer to Table A
and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated,
tant Sprinklers. Chrome Plated,or Brass Plated
Maximum Working Pressure Physical Characteristics
175 psi(12.1 bar) Frame. . . . . . . . . . . . . . . . . . . Bronze
250 psi(17.2 bar)' Button. . . . . . . . . . . . . .Brass/Copper
'The maximum working pressure of 250 psi Sealing Assembly. . . . . . . . .Stainless
IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON
Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb . . . . . . . . . . . . . . . . . . . . . .Glass
Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw. . . . . . . . Bronze
WARNING"that provides cautions K=5.6 GPM/psis/2(80,6 LPM/bar'/2) Deflector. . . . . . . . . . . . . . . . . Bronze
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4 FEBRUARY 2014 TFP172
TFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
6* I
5 7/16"
(11,1 mm) }
4 NOMINAL 2" I) I
MAKE-IN (50,8 mm) 1
2 2" 1-3/8"
3 (50,8 mm) (34,9 mm)
WRENCH
/ FLATS
1 1
1/2"NPT** DEFLECTOR* I� 2-7/8"(73,0 mm)DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Operation Installation
The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor,
WRENCH RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323)
(USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor-
END"A") fluid expands sufficiently to shatter the dance with this section.
glass bulb, allowing the sprinkler to
activate and water to flow. General Instructions
FIGURE 2 Do not install any bulb-type sprinkler if
W-TYPE 6 the bulb is cracked or there is a loss
SPRINKLER WRENCH Design of liquid from the bulb.With the sprin-
kler held horizontally, a small air bub-
WRENCH Criteria ble should be present. The diameter
of the air bubble is approximately 1/16
RECESS The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and
Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C)
Sprinklers are intended for fire protec- temperature ratings.
tion systems designed in accordance
with the standard installation rules rec- A leak-tight 1/2 inch NPT sprinkler joint
ognized by the applicable Listing or should be obtained by applying a min-
Approval agency(such as, UL Listing imum to maximum torque of 7 to 14
is based on the requirements of NFPA ft.-Ibs. (9,5 to 19,0 Nm). Higher levels
13, and FM Approval is based on the of torque can distort the sprinkler Inlet
PUSH WRENCH requirements of FM's Loss Prevention with consequent leakage or impairment
Data Sheets).Only the Style 15 or Style of the sprinkler.
IN TO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for
ENGAGEMENT for recessed pendent installations. insufficient adjustment in the Escutch-
WITH SPRINKLER
WRENCHING AREA eon Plate by under-or over-tightening
FIGURE 3 the sprinkler. Re-adjust the position of
W-TYPE 7 RECESSED the sprinkler fitting to suit.
SPRINKLER WRENCH Upright and Pendent Sprinklers
The Series TY-FRB Upright and Pen-
dent Sprinklers must be installed
in accordance with the following
instructions.
Step 1.Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
TFP172
Page 3 of 4
Step 3. Tighten the sprinkler into the 2-7/8"DIA.
sprinkler fitting using only the W-Type
6 Sprinkler Wrench(Figure 2).With ref-
erence to Figure 1,apply the W-Type 6 2-1/4"DIA.
Sprinkler Wrench to the wrench flats. FACE OF (57,2 mm)
Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLEAi
19,0 Nm). FITTING
5/8"(15,9 mm)
Recessed Pendent Sprinklers FLUSH
The Series TY-FRB Recessed Pendent 3/8±5/16"
Sprinklers must be installed in accor- (9,5±7,9 mm)
dance with the following instructions.
Step A.After installing the Style 15 or }}M 1/8°
Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm)
kler threads, and with pipe-thread
sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
hand-tighten the sprinkler into the TY-FRB PLATE
sprinkler fitting. 3/4"(19,1 mm)
FIGURE 4
SERIES TY-
Step B.Tighten the sprinkler into the
sprinkler fitting using only the W Type FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
7 Recessed Sprinkler Wrench(Figure RECESSED ESCUTCHEON
3).With reference to Figure 1,apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque 2-7/8"DIA.
sprinklers 7 to 14 ft.-Ibs. (9,5 to 19,0 (73,0 mm)
Nm). FACE OF
Step C.After ceiling installation and fin- SPRINKLER 2-1/4"DIA.
ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm)
Closure over the Series TY-FRB Sprin- 5/16±1/4" 1/2"(12,7 mm)
kler and push the Closure over the (7,9±6,4 mm)
Mounting Plate until its flange comes in + FLUSH
contact with the ceiling. �'-� ,
Care and
IMI
UNTING
Maintenance SURFACE (3,2 mm)
The TYCO Series TY-FRB,5.6 K-factor,
Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
Sprinklers must be maintained and ser- TY-FRB PLATE 7/8^(22,2 mm)
viced in accordance with this section. FIGURE 5
Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
work on the fire protection system RECESSED ESCUTCHEON
that it controls, obtain permission to
shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav-
systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing
and notify all personnel who may be corrosive products of combustion,but contractor or sprinkler manufacturer
affected by this action. have not operated,should be replaced regarding any questions.
if they cannot be completely cleaned
Absence of the outer piece of an by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec-
escutcheon, which is used to cover bbrushing it with ft bristle ommended to be inspected, tested,
by wa sorse brush.a clearance hole, can delay sprinkler and maintained by a qualified Inspec-
operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local
The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes.
klers are not used for hanging any after installation. Sprinklers damaged
objects and that the sprinklers are only by dropping, striking, wrench twist/
cleaned by means of gently dusting slippage,or the like,must be replaced.
with a feather duster;otherwise,non- Also, replace any sprinkler that has a
operation in the event of a fire or inad- cracked bulb or that has lost liquid from
vertent operation may result. its bulb.(Ref. Installation Section.)
Sprinklers which are found to be leak- The owner is responsible for the
ing or exhibiting visible signs of corro- inspection,testing,and maintenance of
sion must be replaced. their fire protection system and devices
in compliance with this document,as
Automatic sprinklers must never be well as with the applicable standards
painted, plated, coated, or other- of the National Fire Protection Associa-
wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the
TFP172
Page 4 of 4
P/N* 77 - XXX - X - XXX
SPRINKLER TEMPERATURE
FINISH RATINGS
SIN 1 NATURAL BRASS 135 135°F(57°C)
370 5.6K UPRIGHT(1/2"NPT) TY313 3 PURE WHITE(RAL9010)-- 155 155°F(68°C)
POLYESTER
371 5.6K PENDENT(1/2-NPT) TY323 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C)
POLYESTER
Use suffix"I"for ISO 7-1 connection; 9 CHROME PLATED 200 200°F(93°C)
for example,77-370-4-175-1
••Eastern Hemisphere sales only
286 286°F(141°C)
TABLE A
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Limited Ordering
Warranty Procedure
For warranty terms and conditions,visit Contact your local distributor for avail-
www.tyco-fire.com. ability.When placing an order,indicate
the full product name and Part Num-
ber(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify:Series TY-FRB Upright or Pen-
dent(specify)Sprinkler, SIN (specify),
K=5.6,Quick Response,(specify)tem-
perature rating, (specify) finish, P/N
(specify,refer to Table A).
Recessed Escutcheon
Specify:Style 15 Recessed Escutcheon
with(specify*)finish,P/N(specify*)
Specify:Style 20 Recessed Escutch-
eon with(specify*)finish, P/N(specify*)
*Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
GLOBAL HEADQUARTERS 1400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700
Copyright®2014 Tyco Fire Products,LP. All rights reserved. Y'(�CO
TEFLON is trademark of The DuPont Corporation. Fire Protection Products
Eddythread 40
A Lightweight Schedule 40 Replacement Pipe
That Has a Corrosion Resistance Ratio of 1.0
Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe
products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our
customers have an option to buy a carefully designed replacement for Schedule 40 that:
• Has a Corrosion Resistance Ratio of 1.0
• Has a Pressure Rating of 300 psi
• Is Lighter Weight Than Schedule 40
• Is Approved by Factory Mutual and Listed by Underwriters Laboratories
• Is Produced in Accordance to ASTM A-135 and A-795
• Can be Used With Standard Schedule 40 Threaded Fittings,
Couplings and Valves
• Is Produced From Steel With Excellent Properties of
Strength and Threadability
• Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems'
• Offers Lower Freight Costs
EDDYTHREAD 40 SPECIFICATIONS
N'ili j . -----BUNDLE
1 1.461 1.083 70
1 1/4 2.070 1.418 51
1 1/2 2.547 1.654 44
2 3.308 2.123 30
CORROSION RESISTANCE RATIOS
NOMINALii , SCHEDULE40 EDDYTH . 40
1 1.00 1.00
1 1/4 1.00 1.00
1 1/2 1.00 1.00
2 1.00 1.00
Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems
1819 Clarkson Road For additional information, c �L us �
Chesterfield,MO 63017 contact your salesperson today at
QN, BLXL nnoosE TueE conVN2AAllY (800)3254467 (800)325-4467 or(636)537-2600 USTEa
FAX:(636)537-2645 in the USA,or from Canada
www.bullmoosetube.com call(800)882-4666 FM
A company e-mail:salesru bullmoosetube.com
•ntntovco
All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation.
8/08
x s
.' 1 II
C@US
APPROVED
Fig. 35E 3-90'Elbow LISTED
'-�
SizeA Packin Weight;
11 Part Number
in �in Inner Master Ib
1/2 35E 3004 1.13 100 200 0.2
1 3/4 35E 3008 1..31.1_ 70 -t�t0'- . 0.3
A 1 35E 3010 1.50 40 80 0.5
5b 'dA 7 .
1-112 35E 3014 1.94 18 36 1.1
2 35 , .
3020 2.25 �10 20 t.8„
2-1/2 35E 3024 2.70 4 8 3.2
Fig. 35RE3- 90D Reducing Elbow
B SIze A B Pac Ina Weight
Part Number
in in in Inner Master Ib
3/4 x 112 35RE3006004 1.20 1.22 80 160 0.3
1(235R O�OOQ4.` 1 26 .. 70 140 0.4
i
i A 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4
i T 1/4 z 112_ 35RE3Q�J2004
1-114 x 3/4 35RE3012006 1.45 1.63 35 70 0.6
1 4 x 1, E,Q12010. 1.58. 7 30 _ 6Q 0.7.
1-112 x 112 35RE3014004 1.52 1.75 30 60 0.6
1-1/2 x 3)4 „3`, iM.1 06, 1:52. 1 75, 25, .. 5b 0.7 ,
1-112 x 1 35RE3014010 1.65 1 80 20 40 0.8
1-1/2 x
'1-t/4 N35RE301401-" 1.82 1 88. 18 36 1A
2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0
2x3/4 35RE3020006 1.60 1&97 18 36 1.0
2 x 1 35RE3020010 1.73 2.02 16 32 1.2
2x 1.-1/4 , ,r wE3020012 190 1 j2:. 24 1.3
2 x 1-1/2 _35RE3020014 2.02 2.16 10 201.5
2-
1/2 x 1 112 35RE3024014 2.16 2 51,';; 6, 12- 2.2
2-112 x 2 35RE3024020 2.39 2.60 6 12 2.5
Fig. 35F 3-45'Elbow
Size Part Number A Packin Weight
A in in Inner Master Ib
112 35F 3004 0.88 150 300 0.2
\ 3/4 35F 3006 0.98 80 160 0.3
1 35F 3010 1.13 40 80 0.5
\i 1-1/4 35F 3012 1.29 25 50 0.7'
I i �A
1-112 35F 3014 1.44 20 40 1.0
wx�
2 35F 3026 1.69 16 26 1.6
2-112 35F 3024 1.95 4 8 2.7
Fig. 35T 3- Tee
Size Part Number A Packin Weight
in in Inner Master Ib
112 35T 3004 1.13 80 160 0.3
A 3/4 35T 3006 1.31 30 60 0.5
- T" 1 35T 3010 1.50 25 50 0.7
1 1-1/4 35T3012 1.75 10 20 1.1
A ��A 1-112 35T 3014 1.94 10 20 1.5
2 35T 3020 2.25 6 12 2.4
2-112 35T 3024 2.70 4 8 4.3
111 SMITH-COOPER INTERNATIONAL' TOLL FREE 1-800-766-0076 • FAX(323)890-4456 %-HTw.smithcooper.com
a.
T Ductile Irong0I
C VI. US FM
APPROVED
A
Fig. 35CP3 -Straight Coupling with Ribs LISTED
Size . A Packin Weight,
in Part Number in Inner Master Ib
1/2 35CP3004 1.38 200 400 0.1
3/4 35CF30061.63 ,100 200 02 .
1 35CP3010 1.75 60 120 0.4
1-1/4 ': t35C,P3Q12 " 200 35; „70 0.5 .
1-1/2 35CP3014 2.1925 50 0.7
7 35 ,I? 02U 2.62° . 15S 30 1.2 ..
2-1/2 35CP3024 3.00 9 18 2.2
Fig. 35RC3 -Hex Reducing Coupling
Size A Packin Weight
Part Number
In in Inner Master,.,,,,, Ib
1 x 1/2 35RC3010004 1.69 80 160 0.3
A I x 3/4 35RC�30�0006,` 1 69 .. 60 ' 120 0.4,
1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6
2 x 1(not hex) 35RC30200i0 ' 2.81 20 40 1.0
Fig. 35HB3 -Hex Bushing
g
Size partNumber A : Packin Weight
g in in Inner Master Ib
1 x 1/2 35HB3010004 1.06 180 360 0.2
JA 1x3/4 35H83010006 ' 106 18Q 360 0.1
i 1-1/4 x 1 35H63012010 1.19 90 180
1 0 2
-1/2 x `.Y35HB3014010 ` : .. 1,.255'. 150., ' :. 0.4
-- 1-1/2x1-1/4 35HB3014012 1.25 75 150 0.3
2z1
b;;35HB30200fib 1.38 40 80 0.6
2 x 1-1/4 35HB3020012 1.38 40 80 0.6
2 x 1-1/2 35H83020014 j 1.38 40 80 0.6
Fig. 35SP3 -Square Head Plug
Size part Number A Packin Weight
in in Inner Master Ib
1/2 35SP3004 0.94 600 1200 0.07
' A 3/4 35SP3006 1.12 350 700 0.1
1 35SP3010 1.25 200 400 0.1
1-1/4 35SP3012 1.37 100 200 0.3
1-1/2 35SP3014 1.44 80 160 0.4
2 35S03020 1.50 45 96 6.6
Fig. 35U 3- Union with Brass Seat
tipA Size A Pac Ing Weight
in Part Number in Inner I Master Ib
1 35U 3010 2.19 20 40 1.0
1-1/4 35U 3012 2.50 15 30 1.2
Lf I Ll 1-1/2 35U 3014 2.62 10 20 1.7
2 35U 3020 1 3.12 6 12 2.4
113 SMITH-COOPER INTERNATIONAL" • TOLL FREE 1-800-766-0076 FAX(323)890-4456 0 NNaw.smithcooper.com
SPEC v FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING 21 11 00
[oil >
FlexHead Industries,Inc.
• Flexible design provides versatility for Jr
changes in floor plan or occupancy
FLEXHW • Compatible with any FM/UL approved r E.
i��_ sprinkler head
N D U S T R I E S qo • 100%leak tested system w
• Industrial grade,all welded, no 0-ring con .
struction,uses all stainless steel components y° s
1. Product Name • Adjustable height and sprinkler alignment/
FlexHead Commercial Sprinkler Connections center-of-tile uniformity
• Rated up to 300 psi (2066 kPa) with no
2. Manufacturer additional hangers required
FlexHead Industries,Inc. • Easy friction loss/water pressure calculations
56 Lowland St.
Holliston,MA 01746 • Bracket provides uniformity with any suspend- a
(800) A 017 75 ed or gypsum board ceiling system
• Compatible with BlazeMaster® CPUC Fire
(508)893-9596
508 893-6020 Sprinkler Systems
Fax:
( ) • Approved for use in suspended ceiling sys-
E-mail:salesl@FlexHead.com tems with light, medium and heavy load
www.flexhead.com ceiling systems(ASTM C635,C636)
• True-bore 1"(25A mm) internal corrugated
3. Product Description hose diameter,which produces friction loss
BASIC USE values similar to hard pipe armovers Suspended ceiling installation
FlexHead manufactures flexible stainless steel • Fully braided hose provides excellent protection
hose assemblies and a bracketing system that against pressure surges
connect sprinkler heads to the branch lines. • 2006 IBC and SEI/ASCE 7-05 compliant for
These systems install in less than a fifth of the sprinklers installed in seismic design classes
time that it takes to install hard pipe armovers, C and D/E/F
which allows for rapid installation or relocation • Provides green benefits to building owners
of sprinkler heads in suspended ceilings. COMPOSITION&MATERIALS SYSTEM COMPATIBLE
Each FlexHead unit comes with a mount- Every FlexHead connection comes complete are also 304 stainless steel and are fully welded
ing bracket and a 1-piece,leak tested sprin- with the flexible hose and attachment bracket. using a proprietary welding process(no 0-rings).
kler drop.The mounting bracket is compati- Each connection is made from 100% factory FlexHead is leak tested to 175 psi(1205 kPa)and
ble with any suspended or gypsum board tested Type 304 stainless steel.The hose nipples has burst pressure of over 2000 psi(13,780 kPa),
ceiling system.
With any contractor installed sprinkler ';
head of choice, this pressure/leak tested , 'yf
system is available in 2- 6'(0.6- 1.8 m)hose
lengths, making it ideal for any commercial
application. In addition, FlexHead both mini-
mizes the cost and simplifies the labor
required to bring unsprinklered buildings up
to code. It installs in minutes, even in the ,Y
most restrictive of spaces.
All FlexHead commercial sprinkler connec-
tions are Factory Mutual(FM)approved and
UL listed and are manufactured in an FM/UL
audited facility.
BENEFITS
• Reduced labor costs and callbacks
• Expedites retrofitting buildings with con-
fined spaces
• Predictable installation eliminates bidding
problems and scheduling delays
• Fast-track construction for rapid building
occupancy
Gypsum board ceiling installation
SPEGDATO aid MMi-TEC are regstered traderteAa of Reed Bsev Irc.The ten port TEGDATA formot corfoms to the ediorid style
of Tte c�tftjdbn Spedficatlan Imt1tde a,d k used with tt,ir pem*sion.Tte rrord—fuer is resporsiae for ted,;ml 000.acv.c2309 Reed Co strahcr Data.All%ghts Reseryed. SmartBuilding!n c1c x
SPEC v FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING 21 11 00
FlexHead Industries,Inc.
The bracket system is made from galvanized Lection field. Consult NFPA, FM, UL and state
sheet metal and is approved and compatible and local guidelines prior to installation.
for use with light,medium and heavy load ceil- METHODS
ing systems(ASTM C635,C636)or gypsum board Each FlexHead ceiling sprinkler connection
ceiling systems,
includes a mounting bracket and a 1-piece,
SIZES leak tested FlexHead sprinkler drop.
FlexHead is available in 2,3',4',5'or 6'(0.6,0.9, Attach the bracket to the t-bar ceiling grid;
1.2 1.5 or 1.8 m)hose lengths. then attach the FlexHead sprinkler to the sub-
main.Secure the sprinkler to the bracket.Test
4.Technical Data installation of sprinkler system for any leaks
APPLICABLE STANDARDS per NFPA guidelines. Suspended ceiling installation in a confined
American Society of Civil Engineers (ASCE) - PRECAUTIONS space
SEI/ASCE 7-05, Section 13.5.6 Suspended Consult the manufacturer's installation instruc-
Ceilings tions for complete installation information. 8. Maintenance
ASTM International Failure to follow the cited instructions may Contact the manufacturer for complete
cause personal injury. During maintenance or maintenance information.
• ASTM C635 Standard Specification for the
Manufacture, Performance, and Testing of inspection of FlexHead product,the facility fire
Metal Suspension Systems for Acoustical Tile protection system must be inactive. Do not 9•Technical Services
and Lay-in Panel Ceilings attempt relocation or maintenance of FlexHead Design assistance and technical support are
• ASTM C636 Standard Practice for Installation product while fire protections system is live, available upon request from the manufacturer's
of Metal Ceiling Suspension Systems for BUILDING CODES trained staff.
Acoustical Tile and Lay-In Panels Current data on building code requirements 10. Filing Systems
FM Global Technologies LLC (FM) - FM Class and product compliance may be obtained • MANU-SPEC®
Number 1637 Approval Standard for Flexible from the manufacturer's technical support • Additional product information is available
Sprinkler Hose with Threaded End Fittings specialists. Installation must comply with the from the manufacturer upon request.
International Code Council(ICC) requirements of applicable local, state and
• ICC International Building Code(IBC),2006 national code jurisdictions.
Section 803.9 Acoustical Ceiling Systems 6.Availability&Cost
Section 1613 Earthquake Loads
National Fire Protection Association(NFPA) AVAILABILITY
• NFPA 13 Standard for the Installation of For information on product availability or to
Sprinkler Systems locate an authorized FlexHead distributor,
• NFPA 13D Standard for the Installation of contact FlexHead Industries,Inc.
Sprinkler Systems in One- and Two-Family COST
Dwellings and Manufactured Homes Budget installed cost information may be
• NFPA 13R Standard for the Installation of obtained from the manufacturer upon request.
Sprinkler Systems in Residential Occupancies
up to and Including Four Stories in Height 7.Warranty
Underwriters Laboratories, Inc. (UL) - UL 2443 FlexHead Industries,Inc.,warrants that its prod-
Standard for Flexible Sprinkler Hose with Fittings ucts will be free from defects in materials and
for Fire Protection Service workmanship under normal conditions of use
APPROVALS and service for a period of 1 year from date of
sale.The obligation under this warranty is limited
Underwriters Laboratories, Inc.(UL)- UL Listed, to repairing or replacing any product that is
VENF.D(5269,Flexible Sprinkler Hose Fitting returned with transportation charges prepaid
PHYSICAL/CHEMICAL PROPERTIES within 1 year after the date of original sale and
Test reports are available to design professionals that an examination by FlexHead shows to their FGG/BM®System Compatible indicates this
upon request. satisfaction to have been defective in materials product has been tested and is monitored on
or workmanship,under normal conditions of use an ongoing basis to assure chemical compati-
and service. The decision as to whether to bility with FlowGuard Gold®,BlazeMaster®,and
5. Installation repair or to replace any product shall be made Corzan®pipe and fittings.
PREPARATORY WORK by FlexHead Industries,and any repair shall be FGG/BM®,FlowGuard Gold®,BlazeMoster®,and
Installation should only be performed by qual- made at their facility. Contact the manufac- Corzan®are registered trademarks of Noveon
iffii'eddd and licensed technicians in the fire pro- turer for complete limited warranty details. IP Holdings Corp.
SfEGDATA•and N W J-PEe are registered trodemaAcs of Reed asevier Inc.the ten part SPEGDATA fc`md corfoms to Me edtorid style
of The Corctruct&Spedfiootim Im"Lfie and a used with their pemmsion.The manfacturer is respomble for tedrical acc-uacy.•2709 Reed Co trteon Data.All Rights Reserved. Sma rtBu ild ing i!,,dc x
Threaded Accessories
B3205 - Threaded Rod (right-hand threads- both ends) (TOLCO Fig.103)
B3205L - Threaded Rod (right&left hand threads) n
Size Range: 3/8"-16 thru 3"-4 rod s�`��>h
Material: Steel
Function: Recommended for use as a hanger support in hanger assemblies. TL
Rod is threaded on both ends with right hand threads of the length shown.Also A
available with left and right hand threads-specify Fig. B3205L when ordering. Thmad size
Maximum Temperature: 750°F(399°C)
Finish: Plain.Contact B-Line for alternative finishes and materials.
Order By: Part number,rod size,length and finish
..rd Design
Thread Size Thread Length TL i i
Part No. A in. (MM) Lbs. (kN) Lbs. (M)
83205-e/ X.-L!f 3/e" 16 21/2" (63.5) 730 (3.25) 572 (2.54)
B3205-Illx;'L'„ ;:` 112"-13 21/2 (63.5) 1350 (6.00) 1057 (4.70)
832053-5 X'L a`; 5/e"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52)
3/0-10 3" (76.2) 3230 (14.37) 2530 (11.25)
632053-N]*0L ."' 2/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60)
B32064 x'L' ' `"'' V-8 4" (101.6) 5900 (26.24) 4620 (20.55)
63205-11h'x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93)
B3205-11/4x' IV 11/4"-7 5" (127.0) 9500 (42.25) 7440 (33.09)
B3205-1112 x'L'` 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07)
1332051,3/,4x'L' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79)
B3205-2 x IV 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29)
1332053-21/4 x'L', 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51)
B3205-2112 x.'L' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64)
83205-23/4 X'L' 23/4"-4 11.1 (279.4) 49400 (219.73) 38687 (172.08)
B3205-3 X'L'- 3"-4 12" (304.8) 60100 1 (267.32) 47066 1 (209.35)
ATR -All Threaded Rod 120" (3.o5m)Lengths (TOLCO Fig.100)
Fig. 99-All Threaded Rod Cut To Length
Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length
Material: Steel
Maximum Temperature: 750°F(399°C)
Finish: Plain.Contact B-Line for alternative finishes and materials.
Order By: Part number,rod diameter and finish
Part No.-Size x Length Threads Recommended Load Approx. ii R.
ATR ..
ATR 1/4"X 120 99-1/4"X length 20 240 (1.07) 12 (5.44)
ATR 3/8"x 120 99.3/4"x length 16 730 (3.24) 29 (13.15)
ATR 1h"x 120 99-1h"x length 13 1350 (6.00) 53 (24.04)
ATR 5/8"x 120 99-5/8"X length 11 2160 (9.60) 89 (40.37)
ATR /4"X 120R,/,4',xlength 10 3230 (14.37) 123 (55.79)
ATR 712"x 120 "x length 9 4480 (19.93) 170 (77.11)
ATR 1"x 120 " length 8 5900 (26.24) 225 1 (102.06)
Al dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line
Pipe Hangers&Supports 236 Revised 412812014
by E_T•N
Pipe Hangers
Fig. 200- "Trimline"Adjustable Band Hanger (B-Line Fig.B3170NF) ®TOLCC7
Fig. 20OF- "Trimline"Adjustable Band Hanger with Felt Lining (B-Line Fig.B3170NFF) @US
Fig. 200C - "Trimline'"Adjustable Band Hanger with Plastic Coated (B-Line Fig.B3170NFQ usrt o
Fig. 200S - "Trimline"Adjustable Band Hanger with Non-Captured Nut
FM
Size Range:
Fig. 200 - 1/2" (15mm)thru 8" (200mm)pipe
Material: Steel, Pre-Galvanized to G90 specifications
Function: For fire sprinkler and other general piping purposes. Knurled --
swivel nut design permits hanger adjustment after installation.
Features: ® -
• (1/2" (15mm)thru 2" (5omm)) Flared edges ease installation for all pipe
types and protect CPVC plastic pipe from abrasion. Captured design
keeps adjusting nut from separating with hanger. Hanger is easily s
installed around pipe. ® =
A
For hanger with non-captured nut order Fig. 200S.
• (21/2" (65mm)thru 8" (200mm)) Spring tension on nut holds it securely in _-
hanger before installation.Adjusting nut is easily removed.
Approvals: Underwriters Laboratories listed(1/2" (15mm)thru 8" (200mm)) - 200 3p
in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and Fig.zoo t to 200-2 F Fig.200-21/2204I/z to -a
Factory Mutual Engineering Approved(FM)(3/4" (20mm)thru 8" (200mm)). ro'
Conforms to Federal Specifications WW-H-171 E&A-A-1192A, Type 10
and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58,
Type 10.
Maximum Temperature: 650°F (343°C) OEM
Finish: Pre-Galvanized, Stainless Steel
materials will be supplied with (2) hex nuts
in place of a knurl nut.
Order By: Figure number and pipe size +
Designed to meet or exceed requirements of
FM DS 2-0.
Fig.200
Fig.200C Fig.20OF
Pipe Size Rod Size A B Approx.Wt./100
Part No. in. (MM) in. (MM) in. (mm) Ibs. (kg)
200-1/2 1/2" (15) 3/8"-16 31/6' (79.4) 25/8" (66.7) 11 (5.0)
200-3/4 3/4" (20) 3/8"-16 31/8" (79.4) 21/2" (63.5) 11 (5.0)
200-1 1" (25) 3/B-16 33/8' (85.7) 25/8" (66.7) 12 (5.5) '
200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8' (73.0) 13 (5.9)
200-11/2 11/2" (40) 3/Er-16 37/8' (98.4) 27/8' (73.0) 14 (6.4)
200-2 2" (50) 3/8"-16 41/2" (114.3) 3" (76.3) 15 (6.9)
200-21t2 21/2' (65) 3/8'-16 55/8' (142.9) 41/8' (104.7) 27 (12.3)
200-3 3" (75) 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S
200-31/2 31/2' (90) 3/8"-16 73/8 (187.3) 51/4* (133.3) 34 (15.6)
200-4 4" (1 DO) 3/8"-16 73/8" (187.3) 5' (127.0) 35 (16.0)
200-5 5' (125) 1/2'-13 91/8" (231.8) 61/4" (158.7) 66 (30.2)
200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4)
200-8 8" (200) 1/2"-13 131/8' (333.4) 83/4 (222.2) 136 (62.3)
All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified.
Fire Protection Solutions B-Line
21 by E_T•N
AMU
• • • 1
Not less than Wood Flooring
2'nominal width Product Features
(t-v2�
4► •No pre-drilling required.
Not less than •Quick to install using the Sammy
3'nominal
thickness(2-12') Nut Driver with an 18V cordless
(depth or side Wood Joist drill/driver.
of vertical member)
•Saves time from traditional
T
Double Sheetrock methods.
Ceiling
•Reduces installation cost.
Composite I Truss •Made in the U.S.A.
Consi'L truss ma9ifacturer formay be required for GST
25-380,Too/available on page 10
Approvals Rod Part Model Screw Ultimate UL Test FM Test Box Case
Size Number D• City City
210(Ins-OSB)
1/4' 8002957 GST 100 1A x 1' 25 125
_ 670(314 Ply)
1/4" 8003957 GST 200 1/4 x 2" 1760(Fir) 25 125
8004957, GS7_31iQ 1Kx3". < ` 2060(flrl 25 125
3/8" 8006957 GST.75 1/4 x 3/4" 564(3/4"Ply) 25 125
210(7116'OSB)' 318' 8007957 GST 10 1M x 1' 670(3k'Ply) 300 25 125
Q 4 3/8' 8008957 GST 20 1/4 x 2" 1760(Fir) 850 1475 25 125
'• 318' 8068925 GST 2QSS 1K x 2' 1760(Flo 850 25 125
3/8" 8009925 GST 25-380 3/8 x 2-1/2" 2113(Fir) 1500 25 125
318' 8010957 GST 30Tf' 1M x 3 2060(Fir) 1500 1475 25 125 #14 BlackNut Driver
3/8' 8069925 GST 30-SS 1/4 x 3" 2060(Fir) 25 125 Part#8113910
318' 8011925 GST 40 19x4" 2180(Flo 25 125
3/8' 8012925 GST 60 1/4 x 6' 2230(Fir) 25 125
112' 8013925 GST 2 114 x 2' 1760(Flo 25 125
1/2" 8014925 GST 2.5-380 3/8 x 2-1/2" 2113(Fir) 25 125
1/Y 8015925 GST 3 ' 14 x 3' 2275(Flo 25 125
1/2" 8016925 GST4 1/4x4" 2180 (Fir) 25 125
112" 8017925 GST 6 19x6' 2230(Flo 25 125 #14 SW Red
Nut Driver
Part#8114910
Product Features
•Eliminates distortion of threaded rod. •Saves time from traditional methods.
•Accommodates up to 3%"x 12 pitch roof. •Reduces installation cost.
•Allows 17°deflection from vertical. •Made in the U.S.A.
DescriptionsApprovals Rod Part Model Screw Ultimate UL Test FM Test Min Box Case
Size Number
318' 8139957 SH-GST 20 iM x 2' 1257 R 1050 1475 25 125 125
3/8" 8141957 SH-GST 30 1/4 x 3' 1720(Fir) 1500 1475 25 125
#14 Black
Nut Driver
SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into Part#8113910
contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations.