Loading...
Correspondence /lily ��U�G -000 l(�7G,j 5 Gv �>�rvr�ir✓ Dan Nelson From: Josh Reiser <jreiser@sazan.com> Sent: Tuesday,January 26, 2016 9:28 AM To: Dan Nelson Subject: RE: Mechanical plan review for CRC Attachments: M-100.pdf Mr. Nelson, Per our phone conversation this morning I have added the requested smoke dampers where the ductwork serving the rated corridors also serves adjacent spaces. Thank you. Josh Reiser PE, LEED AP BD+C GAZA N This c-mail mcssaoc, including any attachrncnts, is for the sole use of the intended rccipient(s)and may contain confidential; proprietary and/or privileged information. Any disclosure, copying distribution or use of this information to persons or entities other than the intended recipient(s)is prohibited. If you believe you have received this,email message in error, please notify the sender and immediately delete this message. From:Josh Reiser Sent: Monday,January 25, 2016 3:26 PM To: 'Dan Nelson' <DanN@tigard-or.gov> Cc:Jeff Harrison<iharrison@sazan.com> Subject: RE: Mechanical plan review for CRC Mr. Nelson, Please see the attached sketch for F/S Damper locations. Additionally, I have attached a submittal from our previous project for SD-3 & RG-3.These are the Diffusers/Grilles located in the two parallel corridors. Since the Ceiling in this corridors is rated we need our dampers at the diffusers. In the lobby area there is no rated ceiling so we have dampers at the rated walls. Please let us know if this is acceptable. . 1