Re: Lot 27, South View
Tigard, OR
Garage Door Header
Stonebridge Job Number: 1864
Engineer Job Number: DM 15-067
Dear Andy:
This letter is in response to your email dated Jan. 4, 2016 regarding the garage door header
being installed 3-1/2"too low. A new header of same size was installed over the header and
extends over the trimmers, but not to the end of wall. The existing header was left in place with
3-1/2"ripped out of bottom of header. The new header will take the vertical loads with no
modifications.
The lateral plans, S1 references detail 11/S2 where the header Is continuous to end of wall. The
lower header is continuous and serves as the member that reduces the aspect ratio of shear wall.
The upper header does not need to extend to end of wall. Please note that the vertical straps
are still required.
The attached photo matched the description above and no modifications are required.