Loading...
Report fto5 o2o(s- ovr?; p - l D 5? S—�W � S c�C«C L Bulletin 110 Rev. W Model G °J ® klers Reliable Spray Upright, CD Spray Pendent And Conventional Product Description The Reliable Model G Automatic Sprinkler utilizes the center strut solder in compression principle of construc- tion. The fusible alloy is captured in the cylinder of the solder capsule by a stainless steel ball. When the fusible alloy melts, the ball moves into the cylinder allowing the cylinder to fall away from the sprinkler.When this happens, the lever is released to spring free from the sprinkler so s� that all of the operating parts clear from the waterway al- lowing the deflector to distribute the discharging water. Except for the parts in the cylinder as mentioned above, the sprinkler components are made from copper based Upright Pendent alloys for maximum corrosion protection. Lead plated,wa coated or wax over lead plated sprinklers are available or specially severe environments. Chrome plated sprinklers are available for decorative purposes. ; All sprinklers are individually hydrostatically tested. All sprinklers are identified as to their fusing point by mark- ings that appear on several of the operating parts and by an identifying color that appears on the frame. Sprinkler Types Standard Upright-This deflector configuration is normal- ly used with exposed piping installations. Water is distrib- uted laterally and downward in a wide pattern approximat- ing a hemisphere which is completely and uniformly filled with water in the form of small drops or spray. Standard Pendent-This deflector configuration is nor- Application and Installation mally used where the space above the piping is limited Standard sprinklers are used in fixed fire protection sys- or where a concealed piping installation is employed.The tems: Wet, Dry, Deluge or Preaction. Care must be exer- discharge characteristics of the standard pendent are cised that the orifice sizes, temperature ratings, deflector virtually identical to the standard upright as described styles and sprinkler spacings are in accordance with the above. latest published standards of the National Fire Protection Association or the approving authority having jurisdiction. Large and Small Orifice —By varying the orifice size, a The sprinklers must be installed with the Reliable Model large or small orifice sprinkler is created that will distrib- D Sprinkler Wrench. Any other type of wrench may dam- ute as much as 40% more water or 65% less water than age the sprinkler. the normal '/z" (15mm) orifice sprinkler. The approvals or listings of Reliable Automatic Sprin- klers by major approving organizations are shown in the Conventional —This deflector configuration is used pri- tabulated list provided on the back of this bulletin. marily in those countries where the LPC installation rules have precedence. The sprinkler is designed to distribute a portion of its water discharge upward against the ceil- ing with the balance downward. It may be installed in either the upright or the pendent position. Sprinklers with conventional deflectors are available with orifice sizes corresponding to light, ordinary and extra-high hazard installations. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Technical Data "K" Factor Sprinkler Sprinkler Identification Sprinkler Type Height Approvals Number SIN US Metric SSU SSP Standard-Upright(SSU)and Pendent(SSP) Deflectors Marked to Indicate Position 1/2"(15 mm)Standard Orifice with'/2"NPT(R'/2)Thread 5.62 81.0 2'/6" 73 mm 1,2,3,4,5,6,7 R1025 R1015 '/16"(11 mm)Small Orifice with 1/2"NPT(R'/2)Thread 4.24 61.0 2 7/6"(73 mm) 1,5 R1023 R1013 3/6"(10 mm)Small Orifice with'/2"NPT(R'/2)Thread 2.82 40.6 2 7/6"(73 mm) 1,2,5 R1021 R1011 5/16"(8 mm)Small Orifice with 112"NPT(R'/2)Thread 1.98 28.5 2'/a"(73 mm) 1,5 R1022 R1012 17/32"(20 mm)Large Orifice with '/2" NPT(R'/2)Thread 7.96 114.7 2 7/6"(73 mm) 1, 2, 5 R1026 R1016 7/32"(20 mm)Large Orifice with 3/4" NPT(R3/4)Thread 8.20 118.2 2 15/16"(75 mm) 1, 2,5 R1027 R1017 20 mm XHH with 20 mm Thread 8.20 118.2 75.4 mm 3,4,5 R1027 R1017 10 mm XLH with 10 mm Thread 4.10 59.1 73 mm 3,4,5 R1024 R1014 Conventional—Installed in Upright or Pendent Position 10mm XLH with 10mm Thread 4.10 59.1 73 mm 4 R1074 15mm Standard Orifice with(R'/2) Thread 5.62 81.0 73 mm 3,4,5,7 R1075 20mm XHH with(R3/4)Thread 8.20 118.2 75.4 mm 3,4 R1077 Temperature Ratings sprinklers with soap and water, ammonia or any other clean- Sprinkler Maximum ing fluids. Remove any sprinkler that has been painted (other Classification Rating Ambient Frame(') than factory applied)or damaged in any way. A stock of spare Temperature Color sprinklers should be maintained to allow quick replacement of OF °C OF °C damaged or operated sprinklers. Prior to installation, sprinklers Ordinary 135 57 100 38 Black should be maintained in the original cartons and packaging un- Ordinary 165 74 100 38 Uncolored Intermediate 212 100 150 66 White til used to minimize the potential for damage to sprinklers that High 286 141 225 107 Blue would cause improper operation or non-operation. Use only the (')Frame color does not apply to painted or plated sprinklers Model D Sprinkler Wrench for sprinkler removal and installation. -Use sprinkler rating as identified on operating parts. Any other type of wrench may damage the sprinkler. Approval Organizations Finishes f't 1. Underwriters Laboratories, Inc. and UL Standard Finishes Certified for Canada (cULus). Bronze —All Temperature Ratings 2. Factory Mutual Research Corporation Chrome —All Temperature Ratings 3. Loss Prevention Council White(2) —All Temperature Ratings 4. Pleniere Assemblee Only Frame and Deflector are Painted 5. VdS Schadenverhutung GmbH Special Application Finishes 6. N.Y.C. BS&A No. 587-75-SA or Bright Brass Plated —Only frame,deflector and cap are plated. 135°F(57°C), 165°F N.Y.C. MEA 258-93-E (74°C),212OF(100°C)Temp.Rating. 7. EC Certificate: 1438-CPD-0054(R1015) Black Plated —Only frame,deflector and cap are plated.All Temp.Ratings. Polyester Coated(2)(4) —Only frame and deflector are coated. 1438-CPD-0053(R1025) Lead Plated —165°F(74°C),212°F(100°C)and 286°F(141°C)Temp.Ratings. 1438-CPD-0052(R1075) Wax-Coated(3) —165°F(74°C)Clear Wax,212°F(100°C) Brown Wax. 1438-CPD-0056(R1077) Wax-Coated Over Ordering Information Lead Plated j3t —165°F 74°C Clear Wax,212°F(100°C) Brown Wax. Specify (') Other colors and finishes are available.Consult factory for details. 1. Model G (2) UL listed and NYC MEA Approved only. (3) 212°F(100°C)brown wax may be used on 286°F(141°C) 2. Deflector sprinklers when maximum ambient temperatures do not exceed 150°F • Upright (660C).UL Listed,FM Approved,NYC MEA 258-93-E. • Pendent (4) FM Approved for R1027 only. • Conventional 3. Nominal Orifice Maintenance 4. Inlet Thread Model G Sprinklers should be inspected and the sprinkler 5. Temperature Rating system maintained in accordance with NFPA 25. Do not clean 6. Finish The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by Reliable Automatic Sprinkler Co., Inc. Recycled (800)431-1588 Sales Offices Paper iable (800)848-6051 Sales Fax Revision lines indicate updated or new data. Rel (914)829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.04/15 P/N 9999970005 Bulletin 014 Rev. M co ■� p Model F1 FR Series Rel ble Quick Response o Glass Bulb Sprinklers Model F1 FR56 Sprinkler Types , Standard Spray Upright f Standard Spray Pendent Conventional Upright/Pendent Vertical Sidewall Model F1 FR56 Recessed Sprinkler Types Upright Pendent Conventional Standard Spray Pendent Horizontal Sidewall Model F1 FR56 Concealed Sprinkler Types Standard Spray Pendent Model F1 FR42, F1 FRXLH & F1 FR28 Sprinkler Types Vertical Sidewall Horizontal Sidewall Recessed Standard Spray Upright Pendent/Fl/F2 Standard Spray Pendent Model F1 FR40 Sprinkler Types Standard Spray Pendent Model F1 FR42, F1 FR40, F1 FRXLH & F1 FR28 Recessed Sprinkler Types Standard Spray Pendent �' + ' r Model F1 FR56LL & F1 FR42LL NSF Certified Low Recessed Concealed Recessed Lead Sprinkler Types Horizontal Sidewall Pendent Pendent/FP Standard Spray Pendent with less than 0.25% Lead am Content Listing & Approvals The following organizations provide Listings or Approvals for various Model F1 FR series sprinklers. See the Design and Installation table in this Bulletin for information on XLH Upright XLH Pendent XLH Recessed specific listings and approvals applicable to each sprin- Pendent F1/F2 kler. 1. Underwriters Laboratories Inc. and Certified for Product Description Canada (cULus). Reliable Model F1FR series sprinklers 2. FM Approvals (FM) are quick-response automatic sprin- 3. Loss Prevention Certification Board (LPCB) klers with a glass bulb thermal element. 4. Vertrauen durch Sicherheit (VdS) Model F1 FR series sprinklers are Stan- 5. NSF Certified to NSF/ANSI Standard 61 Annex G dard Spray sprinklers, with the excep- tion of the Model F1FR56 Conventional XLH Recessed (NSF) 6. EC Certificate: 0786-CPD-40239 (RA1414), 0786- sprinkler which is an Old-style/Conven- Pendent FP CPD-40251 (RA1425), 0786-CPD-40252 (RA1475) tional sprinkler. (EC) The Model F1 FR Series automatic sprinklers utilize a 3.0 UL Listing Category mm frangible glass bulb.These sprinklers have demonstrat- ed response times in laboratory tests which are five to ten Sprinklers, Automatic&Open (VNIV) times faster than standard response sprinklers. This quick Quick Response Sprinkler response enables the Model F1 FR Series sprinklers to apply water to a fire faster than standard-response sprinklers of the same temperature rating. The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely man- ufactured glass capsule. This glass bulb is specially con- structed to provide fast thermal response. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 ,tl , At normal temperatures, the glass bulb contains the fluid Model F1 FR Series sprinklers must be installed with the in both the liquid and vapor phases. The vapor phase can Reliable sprinkler installation wrench identified in the Design be seen as a small bubble. As heat is applied, the liquid and Installation Information table in this Bulletin. Any other expands, forcing the bubble smaller and smaller as the liq- wrench may damage the sprinkler. A leak tight sprinkler joint uid pressure increases. Continued heating forces the liquid can be obtained with a torque of 8 to 18 Ib-ft(11 to 24 N-m). to push out against the bulb, causing the glass to shatter, Do not tighten sprinklers over the maximum recommended opening the waterway and allowing the deflector to distrib- installation torque. Exceeding the maximum recommended ute the discharging water. installation torque may cause leakage or impairment of the Model F1 FR Series sprinklers provide a wide range of op- sprinkler. tions where quick-response, glass bulb sprinklers are used: Recessed Sprinklers • Pendent, recessed pendent, upright, horizontal side- Model F1 FR Series Recessed sprinklers are to be installed wall, and vertical sidewall deflectors as shown in Fig. 1, Fig. 2,or Fig.3, as applicable to the spe- • K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 cific model being installed.The Recessed Escutcheon Data metric), and 5.6 (80 metric) table in the Bulletin identifies the only recessed escutcheons • Flush, recessed, and concealed installations that are permitted to be used with each Model F1 FR Series See the Design and Installation Information table in this Recessed sprinkler.The use of any other recessed escutch- Bulletin for information on the approvals and availability of eon will void all approvals and negate all warranties. specific Model F1FR series sprinkler configurations. Concealed Sprinklers Model F1 FR Recessed Pendent and Recessed Horizon- Model F1 FR Series Concealed Pendent sprinklers are to tal Sidewall sprinklers are required to be used with Reliable be installed as shown in Fig. 4 or Fig. 5, as applicable to the Model F1, F2, or FP recessed escutcheons. See the Re- selected cover plate. Model F1FR56 Concealed Pendent cessed Escutcheon Data table in this Bulletin for listing and and Model F1 FR56LL Concealed Pendent sprinklers have approval information with each specific Model F1 FR series a factory-installed Model CCP cup. A protective cap is in- sprinkler. Model F1 and F2 recessed escutcheons, shown in stalled at the factory that should remain on the sprinkler until Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch the sprinkler is installed and should then be reinstalled on (19mm) and 1/2-inch (12.7mm) of adjustment, respectively the sprinkler until the cover plate is installed.The concealed Model FP recessed escutcheons, shown in Fig. 2, provide a sprinkler assemblies are completed by the installation of a 1/2-inch (12.7mm)threaded adjustment. Model CCP push-on/thread-off cover plate assembly. The Model F1FR56 Concealed Pendent and Model F1 FR56LL cover plate and sprinkler cup assemblies are joined using Concealed Pendent sprinklers are required to be used with a cover plate skirt with flexible tabs for threaded engage- Model CCP cover plates.A standard profile Model CCP cov- ment. A choice of two Model CCP cover plate assemblies er plate is available that provides up to 1/2-inch(12.7mm)of provides either 1/2-inch (13mm) or 5/8-inch (8mm) of cover cover plate adjustment. In addition,a low profile Model CCP adjustment. Do not install Model F1 FR Series Concealed cover plate is also available that provides up to 5/16-inch Pendent sprinklers in ceilings which have positive pressure (8.Omm) of cover plate adjustment. See the Design and In- in the space above. stallation Information and Listed and Approved Temperature Model F1 FR Series Concealed Pendent sprinklers require a Ratings tables in this Bulletin for further information on ap- 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The proved cover plate options. Model RC1 wrench is used to engage the sprinkler wrenching Application surfaces and to install the sprinkler in the fitting. Remove the Model F1 FR Series sprinklers are intended for use in protective cap to install the sprinkler,then reinstall the protective accordance with NFPA 13, FM Property Loss Prevention cap until the cover plate is installed. When inserting or remov- Data Sheets, and the requirements of the Authority Hav- ing the wrench from the sprinkler/cup assembly,care should be ing Jurisdiction. Care must be exercised that the k-factor, taken to prevent damage to the sprinkler. Do not wrench any temperature rating, deflector style, and sprinkler type are other part of the sprinkler/cup assembly. Installation is com- in accordance with the requirements of the applicable pleted by removing the protective cap from the sprinkler and design and installation standards. In addition, Model pushing the cover plate onto the cup.Final adjustment is made F1 FR Series sprinklers must be used in accordance with by hand turning the cover plate until the skirt flange makes full their listings and approvals, as well as the information contact with the ceiling.Cover plate removal requires turning the provided in this Bulletin. cover plate in the counter clockwise direction.After installation, Installation inspect all sprinklers to ensure that there is a gap between the Glass bulb sprinklers have orange bulb protectors or pro- cover plate and ceiling and that the four cup slots are open and tective caps to minimize bulb damage during shipping, han- free from any air flow impediment to the space above. dling and installation. Reliable sprinkler installation wrench- Concealed cover plate/cup assemblies are listed only for es are designed to install sprinklers with bulb protectors in use with specific sprinklers.The use of any concealed cover place. Remove the bulb protector at the time when the sprin- plate/cup assembly other than the Reliable Model CCP with kler system is placed in service for fire protection. Removal Model F1 FR56 Concealed Pendent and Model F1 FR56LL of the bulb protector before this time may leave the bulb vul- Concealed Pendent sprinklers or the use of the Model CCP nerable to damage. Remove bulb protectors by undoing the Concealed cover plate assembly on any sprinkler with which clasp by hand. Do not use tools to remove bulb protectors. it is not specifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. 2. Technical Data: Sensitivity: Quick-response Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar) Design and Installation Information Nominal Nominal Nominal Listings Orifice Deflector/ Sprinkler Installation Approval Model K-factor Diameter Orientation Height Wrench SIN and Notes Approvals US Metric inches mm inches mm Pendent 2.25 57 D RA1411 cULus 2 F1FR28 2.8 40 3/8 10 1 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2 Upright 2.25 57 D RA1421 cULus 1,2 F1 FR40 4.0 57 3/8 10 Pendent 2.25 57 D RA1418 VdS Recessed Pendent 2.25 1 57 GFR2 RA1418 VdS Pendent 2.25 57 D RA1413 cULus 2 171 FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 Upright 2.25 57 D RA1423 cULus 1,2 F1 FR42LL 4.2 60 7/16 10 Pendent 2.25 57 D RA1410 cULus, NSF Recessed Pendent 2.25 1 57 GFR2 RA1410 cULus, NSF FIFRXLH Pendent 2.25 57 D RA14131 cULus 2 (F1 FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 with Pintle) Upright 2.25 57 D RA1423 cULus 1,2 Pendent 2.25 57 D RA1414 cULus, FM, 1,2,3,4 LPCB, VdS, EC Recessed Pendent 2.25 57 GFR2 RA1414cULus, FM, 1,2,3,4 LPCB,VdS, EC F1FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6 Upright 2.25 57 D RA1425 cULus, FM, 1,2,3,4 LPCB,VdS, EC "Conventional 2.25 57 D RA1475 LPCB,VdS, EC 4 (Pendent or Upright)" Pendent 2.25 57 D RA1415 cULus, NSF 1 F1FR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 GFR2 RA1415 cULus, NSF Concealed Pendent 2.25 57 RC1 RA1414 cULus, NSF 6 Horizontal Sidewall 2.63 67 D RA1435 cULus, FM 1,2,3,7 F1 FR56 5.6 80 1/2 15 Recessed Horizontal 2.63 67 GFR2 RA1435 cULus, FM 8 Sidewall F1FR56 5.6 80 1/2 15 Vertical Sidewall 2.25 57 D RA1485 cULus, FM, 1,2,3 19 (Pendent or Upright) LPCB cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating. 2>cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating. 3 Available with FM approved Polyester coating in black or white. Available with LPCB and VdS approved Polyester coating. (5)VdS and EC approvals of the FlFR56 Concealed Pendent sprinkler are for 155°F(68°C)temperature rated sprinklers only.VdS approved sprin- klers must use Norbulb brand glass bulbs with the 1/2-inch(12.7mm)adjustment Model CCP cover plate only. (6) Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates, available as either standard depth with 1/2-inch(12.7mm)of adjustment or low profile with 5/16-inch(8.0 mm)of adjustment. ">cULus Listing of the F1 FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1 FR56 Hori- zontal Sidewall sprinkler is for Light Hazard occupancies only. 8)cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (9)The F1 FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil- ing distance shall be 4 inches to 12 inches(102mm to 305mm). LPCB approval of the F1 FR56 Vertical Sidewall sprinkler is for installation in the Pendent position only. 3. Listed and Approved Temperature Ratings Ordinary Temp. Intermediate Temp. High Temp. Classification Classification Classification Deflector/ 100°F(38°C) Max.Ambient 150°F(65°C) Max. Ambient 225°F(107°C)Max. Model Orientationo Tem . Tem AmbientTem . 135o F(57 C) 155o F(680 C) 1750 F(79o C) 200 F(93o C) 286OF(1410 C)Temp. Temp. Rating Temp. Rating Temp. Rating Temp. Rating Rating Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb Pendent cULus F1FR28 Recessed Pendent cULus Upright cULus F1FR40 Pendent VdS Recessed Pendent VdS Pendent cULus FlFR42 Recessed Pendent cULus - U ri ht cULus F1 FR42LL Pendent - cULus, NSF Recessed Pendent - cULus, NSF Pendent cULus F1 FRXLH Recessed Pendent cULus Upright cULus Pendent cULus, FM, LPCB,VdS, EC Recessed Pendent cULus, FM, LPCB, VdS, EC FlFR56 Concealed Pendent' cULus cULus,VdS,EC I cULus Upright cULus, FM, LPCB,VdS, EC "Conventional Pendent or Upright)" LPCB,VdS, EC Pendent - cULus, NSF FlFR56LL Recessed Pendent - cULus, NSF Concealed Pendent' cULus, NSF Horizontal Sidewall cULus, FM F1 FR56 Recessed Horizontal cULus, FM Sidewall F1 FR56 Vertical Sidewall(Pen- cULus, FM, LPCB dent or Upright) * Model F1 FR56 Concealed Pendent and F1 FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover plate. For Intermediate Temperature Classification sprinklers use a 165°F(74°C) temperature rated cover plate. Recessed Escutcheon Data Listed and Approved Recessed Escutcheons Deflector/ Model F1 Model F2 Model Fp Model Orientation (Fig. 1 &3) (Fig. 1 &3) (Fig.2) SIN 3/4-inch (19mm) 1/2-inch (12.7mm) 1/2-inch (12.7mm) adjustment adjustment adjustment F1FR28 Recessed Pendent cULus cULus cULus RA1411 F1FR40 Recessed Pendent VdS VdS VdS RA1418 FlFR42 Recessed Pendent cULus cULus cULus RA1413 F1 FR42LL Recessed Pendent cULus, NSF cULus, NSF cULus, NSF RA1410 FlFR42XLH Recessed Pendent cULus cULus cULus RA1413 F1 FR56 Recessed Pendent cULus, LPCB,VdS, cULus, FM, LPCB, cULus, VdS, EC RA1414 EC VdS, EC F1 FR56LL Recessed Pendent cULus, NSF cULus, NSF cULus, NSF RA1415 F1 FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435 4. 2 1/4"HOLE DIA ~ [57.2mm] 1 15/16°DIA [49.2mm] --- I" X 1/2" REDUCER TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS \ / FACE OF FITTING TO FACE OF CEILING DIMENSION F1 ESCUTCHEON AT MAXIMUM RECESS = 1'[25.4mm] L J AT MINIMUM RECESS = 318'[9.5mm] F1 ESCUTCHEON F2 ESCUTCHEON 3/4'[19mm] AT MAXIMUM RECESS = 3/4'[19mm] ADJUSTMENT 03 vu AT MINIMUM RECESS = 3I8[9.5mm] F2 ESCUTCHEON 1/2'[12.7mm] 1 A 1 F1 ESCUTCHEON ADJUSTMENT AT MAXIMUM RECESS = 7/8'[22.2mm] [32mmJ AT MINIMUM RECESS = 1-5/8'[41.3mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 1-1/8'[28.6mm] AT MINIMUM RECESS = 1-5/8'[41.3mm] 2 27/32"DIA. [72.2-1 Fig. 1 Model F1 FR56,F1 FR56LL,F1 FR42, F1 FR40, F1 FR42LL, F1 FRXLH&F1 FR28 Recessed Pendent sprinkler with Model F1 or F2 escutcheon I 1" X 1/2 REDUCER 2 5/8" DIA. [66.7mm] HOLE /N CEILING \ I 2 5/15" DIA. [58.7mm] CUP L -j- CEILING CEILING FACE OF FITTING TO FACE OF CEILING DIMENSION AT MAXIMUM RECESS = 1-1/2'[38mm] AT MINIMUM RECESS = 1'[25.4mm] I AT MAXIMUM RECESS = 9/16'[14.3mm] Y2'T 12.7mm] AT MINIMUM RECESS = 1'[25.4mm] ADJUSTMENT 3 114" DIA. [82.6mm] Fig.2 Model F1 FR56,F1 FR56LL, F1 FR42, F1 FR40, F1 FR421-L, F1 FRXLH&F1 FR28 Recessed Pendent sprinkler with Model FP escutcheon 5. • j FACE OF FITTING TO FACE OF CEILING DIMENSION F1 ESCUTCHEON AT MAXIMUM RECESS = 1'T25.4mm] AT MINIMUM RECESS = 3/8'T9.5mm] F1 ESCUTCHEON F2 ESCUTCHEON AT MAXIMUM RECESS = 1-3/8"T34.9mm] AT MAXIMUM RECESS = 3/4"T19mm] AT MINIMUM RECESS = 2-1/16"T52.4mm] AT MINIMUM RECESS = 3/8"T9.5mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 1-5/8"T41.3mm] 2 1/4" HOLE DIA. 1/8,. AT MINIMUM RECESS = 2-1/16"T52.4mm] [57.2mm] [3.2mm] 1" X 1/2" REDUCER NN 7-ANn 4""—12 1 15/16"" DIA. /nui _ �--xi � -- - [101.6mm-304.8mm] 149. mm] wn 2 27/32'" DIA. CEILING TO nm [72.2mm] DEFLECTOR TURN COLLAR UNTILTIGHT AGAINST WRENCH BOSS.SPRINKLER `\, F7 ESCUTCHEON 3/4"T 19mm] ADJUSTMENT F2 ESCUTCHEON 112'T12.7mm] ADJUSTMENT olv RECESSED HSW W/F1 OR F2 ESCUTCHEON (1) FM APPROVED FOR 4" — 6" [101.6MM — 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY. Fig.3 Model F1 FR56 Recessed Horizontal Sidewall sprinkler with Model F1 or F2 escutcheon I" x 7/2" REDUCING TEE OR ELBOW �— — -------+-------- ------ 2 518" DIA. 2 5/76 DIA — �; HOLE IN CEILING L_ _J CUP 00 dd 1 112" MAX. FACE OF FITTING --_-- —_' TO FACE OF CEILING DIMENSION CEIL ING 1 I --- 7/2" MAX. 75/76" COVER ADJUSTMENT j COVER PLATE / ASSEMBLY 3 5116" DIA. SPRINKLER CONCEALED, 1/2" ADJUSTMENT 017FG01A Fig.4 Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth 1/2-inch(12.7mm)adjustment-Model CCP cover plate 6. I" x 1/2" REDUCING TEE OR ELBOW —— — ------+—-—-—-— -—-— j 2 518" DIA. 2 5116" DIA HOLE IN CEILING -f- L_ _J CUP 0 tla 1 7/2" MAX. FACE OF FITTING TO FACE OF CEILING DIMENSION CEILING I 5176" MAX. 3/4 COVER ADJUSTMENT j COVER PLATE — ASSEMBL Y 3 5116 DIA. SPRINKLER CONCEALED, 5/16" ADJUSTMENT 017FG02A Fig.5-Model F1 FR56/1`1 FR56LL Concealed Pendent sprinkler with low profile 5/16-inch(8.Omm)adjustment-Model CCP cover plate Maintenance Material Data The Model F1 FR Series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA Frame: DZR Brass, OM Brass,or Low Lead Brass 25. Do not clean sprinklers with soap and water,ammonia or Deflector: CDA Alloy 220, 260, or 510 any other cleaning fluids. Remove dust by using a soft brush Load Screw\Pintle: CDA Alloy 360 or 544 or gentle vacuuming. Replace any sprinkler which has been CSP' CDA Alloy 651 or 693 painted (other than factory applied)or damaged in any way. A stock of spare sprinklers should be maintained to allow Washer: Nickel Alloy 440 or 360,coated with PTFE quick replacement of damaged or operated sprinklers. Adhesive Tape Finishes (1) Bulb: Glass Standard Finishes -Sprinkler Escutcheon Cover later') Bronze Brass Chrome Ordering Information Chrome Plated Chrome White Specify: Pol eser Plated 1. Sprinkler Model: [F1FR28][F1FR40][F1FR42] Coated(4)(5)(6) White Painted [F1FR42LL][FIFRXLH][F1FR56][F1FR56LL] S ecial AD lication Finishes 2. Sprinkler Deflector/Orientation: [Pendent][Recessed S rinkler Escutcheon Cover late(') Pendent][IJ prig ht][Conventional I[Horizontal Sidewall] Elect(oless Nickel Electroless Nickel Bright Brass [Recessed Horizontal Sidewal1][Vertical Sidewall] PTFE 1/2] 3 PTFE 3. Sprinkler threads: [1/2-inch NPT][ISO 7-R -Bright Brass Bright Brass Black Plating Black Plated Black Plated Black Paint 4. Sprinkler Temperature Rating: [135°F (57°C)][155°F Black Paint(2)(6) Black Paint Off White (68°C)][175°1` (79°C)][200°F (93°C)][286°F (141°C)] Off White(2)(e) Off White Satin Chrome 5. Sprinkler Finish Chrome Dull Chrome Dull 6. Escutcheon Model: [F1][F2][FP] (1)Other finishes and colors are available on special order. Consult the 7. Escutcheon Finish (where applicable) factory for details.Custom color painted sprinklers may not retain their 8. Cover plate Model: [standard profile CCP 1/2-inch UL Corrosion resistance listing.Coverplate custom paint is semi-gloss, (12.7mm) adjustment][low profile CCP 5/16-inch unless specified otherwise. (2) cULus Listed only. (8.Omm) adjustment] (3) 200°F(93°C)maximum. 9. Cover plate Temperature Rating: [135°F(57°C)for use (4) cULus listed "corrosion resistance" applies to SIN Numbers RA1435 with Ordinary Temperature sprinklers][165°F (74°C) (HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and for use with Intermediate Temperature sprinklers] RA1415 (Pendent) in standard black or white. Corrosion resistance in other polyester colors is available upon request. 10. Cover plate Finish (5) FM Approvals finish as"Polyester coated"applies to SIN Number RA1414,RA1435 and RA1425 in standard black or white. Note: When Model F1FR Series Recessed sprinklers are ordered, the (6)LPCB and VdS Approved finish applies only to RA1425,RA1414, RA1418 sprinklers and escutcheons are packaged separately. (VdS)and RA1475. (7)cULus listed Corrosion Resistant 7 Reliable . . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. " Manufactured by Reliable Automatic Sprinkler Co.,Inc. Recycled iabil ® (800)431-1588 Sales Offices Paper i (800)848-6051 Sales Fax (914)829-2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.06/15 P/N 9999970300