Specifications • //rt C 2 CS- .2
f'- i4/6 G,) /76F7CT
rallrin ALAN
Kagit ij:ECIEWED
APR 2 8 2015
DESIGN ASSOCIATES, T CITY OF TIGARD
- IL DIG DIVISION
Four D Construction
22151A
GRAVITY LOADS DESIGNED TO AFPA NDS-05
FLOOR - 40# LIVE, 10# DEAD
ROOF - 25# SNOW
17# DEAD (SHAKE/COMP)
19# DEAD (CONC. TILE)
CEILING - 20# LIVE, 10# DEAD
DECKS - 40# LIVE, 10# DEAD
EXITS/STAIRS - 100# TOTAL LOAD
BEAM CALCULATIONS
ALAN MASCORD DESIGN ASSOCIATES,INC. 1305 N.W. 18TH AVE. PORTLAND, OR. 97209
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
Mil Location:R1-MULT RAFTER BR 3 DORMER. . Larry aWlc 9.0ield /
@ StruCalc 9.0
Multi-Loaded Multi-Span Beam 1,1 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] Portland,OR 97210
(2) 1.5 IN x 7.25 IN x 6.5 FT
�,��fr`r �
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:01 AM
Section Adequate By:61.2%
Controlling Factor:Moment
CAUTIONS
*Laminations are to be fully connected to provide uniform transfer of loads to all members
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.05 IN L/1497
Dead Load 0.03 in
Total Load 0.08 IN L/921
Live Load Deflection Criteria L/360 Total Load Deflection Criteria:U240
REACTIONS A
Live Load 625 lb 623 lb
Dead Load 391 lb 390 lb
Total Load 1016 lb 1013 lb
Bearing Length 0.54 in 0.54 in
BEAM DATA Center
Span Length 6.5 ft
Unbraced Length-Top 0 ft 6.5 ft
Unbraced Length-Bottom 6.5 ft
Live Load Duration Factor 1.15
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 5 plf
Bending Stress: Fb= 900 psi Fb'= 1242 psi Total Uniform Load 5 plf `
Cd=1.15 CF=1.20 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 207 psi Load Number One
Cd=1.15 Live Load 153 lb
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 92 lb
Comp.-Ito Grain: Fc- L= 625 psi Fc-1'= 625 psi Location 5.5 ft
Controlling Moment: 1687 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
3.31 Ft from left support of span 2(Center Span) Load Number One Two
Created by combining all dead loads and live loads on span(s)2 Left Live Load 188 plf 61 plf
Controlling Shear: -953 lb Left Dead Load 113 plf 37 plf
At a distance d from right support of span 2(Center Span) Right Live Load 188 plf 61 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 113 plf 37 plf
Load Start 0 ft 5.5 ft
Comparisons with required sections: Read Provided Load End 5.5 ft 6.5 ft
Section Modulus: 16.3 in3 26.28 in3 Load Length 5.5 ft 1 ft
Area(Shear): 6.91 in2 21.75 in2
Moment of Inertia(deflection): 24.81 in4 95.27 in4
Moment: 1687 ft-lb 2720 ft-lb
Shear: -953 lb 3002 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
LaLocation: R1-DORMER DOUBLERS Widdield
StruCalc 9.0
Multi-Loaded Multi-Span Beam 12111 2187 NW Reed St.Suite 100
[2015 International Building Code(2012 NDS)] _Portland,OR 97210 or
(2)1.5 INx7.25INx5.33FT ` �
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:11 AM
Section Adequate By:210.2%
controlling Factor:Moment
CAUTIONS
'Laminations are to be fully connected to provide uniform transfer of loads to all members
'DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN L/4296
Dead Load 0.01 in
Total Load 0.03 IN L12501
Live Load Deflection Criteria:U360 Total Load Deflection Criteria:L/240
REACTIONS A
Live Load 333 lb 333 lb
Dead Load 239 lb 239 lb
Total Load 572 lb 572 lb
Bearing Length 0.31 in 0.31 in
BEAM DATA Center
Span Length 5.33 ft
Unbraced Length-Top 0 ft 5.33 ft
Unbraced Length-Bottom 5.33 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 125 plf
#2-Douglas-Fir-Larch Uniform Dead Load 85 plf
Base Values Adjusted Beam Self Weight 5 plf
Bending Stress: Fb= 900 psi Fb'= 1080 psi Total Uniform Load 215 plf
Cd=1.00 CF=1.20
Shear Stress: Fv= 180 psi Fv'= 180 psi
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Comp.1 to Grain: Fc- = 625 psi Fc--i'= 625 psi
Controlling Moment: 762 ft-lb
2.66 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: 446 lb
At a distance d from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Rea'd Provided
Section Modulus: 8.47 in3 26.28 in3
Area(Shear): 3.72 in2 21.75 in2
Moment of Inertia(deflection): 9.14 in4 95.27 in4
Moment: 762 ft-lb 2365 ft-lb
Shear: 446 lb 2610 lb
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) nii Larry Widdifield
Location:U1-HDR OVER BR 4 WINDOW StruCalc 9.0
Multi Loaded Multi Span Beam 2187 NW Reed St.Suite 100 _ or
[2015 International Building Code(2012 NDS)] rie :_Portland,OR 97210
5.5 IN x 9.5 IN x 6.33 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:22 AM
Section Adequate By:30.6% '
Controlling Factor:Moment -
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.03 IN U2263
Dead Load 0.02 in -
Total Load 0.06 IN U1339
Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:L/240
REACTIONS A B
t
Live Load 1303 lb 1012 lb
Dead Load 903 lb 710 lb
Total Load 2206 lb 1722 lb 1,
Bearing Length 0.64 in 0.50 in TRt
1
SEAM DATA Center
Span Length 6.33 ft 1
Unbraced Length-Top 0 ft A 6.33 ft
Unbraced Length-Bottom 6.33 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 11 plf
Bending Stress: Fb= 875 psi Fb'= 875 psi Total Uniform Load 11 plf
Cd=1.00 CF=1.00 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 170 psi Fv'= 170 psi Load Number One
Cd=1.00 Live Load 1147 lb
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi Dead Load 765 lb
Comp.-L to Grain: Fc-1= 625 psi Fc--L'= 625 psi -
Location 3.17 ft
Controlling Moment: 4618 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN "
3.16 Ft from left support of span 2(Center Span) Load Number One Two _
Created by combining all dead loads and live loads on span(s)2 Left Live Load 277 plf 92 plf
Controlling Shear: 1848 lb Left Dead Load 184 plf 61 plf
At a distance d from left support of span 2(Center Span) Right Live Load 277 plf 92 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 184 plf 61 plf
Load Start 0 ft 3.17 ft
Comparisons with required sections: Req'd Provided Load End 3.17 ft 6.33 ft
Section Modulus: 63.33 in3 82.73 in3 Load Length 3.17 ft 3.16 ft
Area(Shear): 16.3 in2 52.25 in2
Moment of Inertia(deflection): 70.41 in4 392.96 in4
Moment: 4618 ft-lb 6032 ft-lb
Shear: 1848 lb 5922 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
Larry Widdifield
Location: U2-Beam over BR-3 StruCalc 9.0
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Suite 100
[2015 International Building Code(2012 NDS)] _Portland,OR 97210 or
6.75 INx13.5INx19.17FT ` �
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:21 AM
Section Adequate By: 10.4%
Controlling Factor:Deflection
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.51 IN L/450
Dead Load 0.36 in
-Total Load 0.87 IN U265
Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:L/240
REACTIONS A B
Live Load 3641 lb 3602 lb 3
Dead Load 2567 lb 2526 lb
Total Load 6208 lb 6128 lb 1
z
Bearing Length 1.41 in 1.40 in
- 11/111111/1113"1111111111121111.11111
BEAM DATA Center
Span Length 19.17 ft
A ft
Unbraced Length-Top O ft 19.171
Unbraced Length-Bottom 19.17 ft
Live Load Duration Factor 1.15
Camber Adj.Factor 1.5 UNIFORM LOADS Center
Camber Required 0.54 Uniform Live Load 0 plf
Notch Depth 0.00 Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 20 plf
24F-V4-Visually Graded Western Species Total Uniform Load 20 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by: Load Number One Two Three
Fb_cmpr= 1850 psi Fb'= 2678 psi Live Load 623 lb 623 lb 1177 lb
Cd=1.15 Cv=0.97 Dead Load 390 lb 390 lb 785 lb
Shear Stress: Fv= 265 psi Fv'= 305 psi Location 6.67 ft 13.67 ft 14.17 ft
Cd=1.15
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.-I-to Grain: Fc-I-= 650 psi Fc-1'= 650 psi Load Number One Two Three Four
Left Live Load 292 plf 342 plf 273 plf 143 plf
Controlling Moment: 32213 ft-lb Left Dead Load 193 plf 223 plf 181 plf 89 plf
9.97 Ft from left support of span 2(Center Span) Right Live Load 292 plf 342 plf 273 plf 143 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 193 plf 223 plf 181 plf 89 plf
Controlling Shear: -5887 lb Load Start 0 ft 3.17 ft 6.67 ft 13.67 ft
At a distanced from right support of span 2(Center Span) Load End 3.17 ft 6.67 ft 13.67 ft 19.17 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 3.17 ft 3.5 ft 7 ft 5.5 ft
Comparisons with required sections: Reci'd Provided
Section Modulus: 144.35 in3 205.03 in3
Area(Shear): 28.97 in2 91.13 in2
Moment of Inertia(deflection): 1253.83 in4 1383.96 in4
Moment: 32213 ft-lb 45754 ft-lb
Shear: -5887 lb 18514 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
Mill Larry 0
Widdifield9 /
Location:U3 HDR-Over Mater BR StruCalc 9.0
Multi-Loaded Multi-Span Beam Mill 2187 NW Reed St.Suite 100 of .
[2015 International Building Code(2012 NDS)] f 4y :_Portland,OR 97210
5.5 IN x 11.51N x 6.67 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:23 AM
Section Adequate By:44.7%
Controlling Factor:Moment
PEFLECTIONS Center LOADING DIAGRAM
Live Load 0.03 IN U2604 '
Dead Load 0.02 in
Total Load 0.05 IN U1542
Live Load Deflection Criteria:U360 Total Load Deflection Criteria:U360
REACTIONS A B
Live Load 1891 lb 1665 lb
Dead Load 1305 lb 1154 lb
Total Load 3196 lb 2819 lb ,
Bearing Length 0.93 in 0.82 in !
. .TR2
REAM DATA Center x.. �
Span Length 6.67 ft ., ...
Unbraced Length-Top 3 ft A 6.67 ft
Unbraced Length-Bottom 6.67 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 14 plf
Bending Stress: Fb= 875 psi Fb'= 873 psi Total Uniform Load 14 plf
Cd=1.00 CI=1.00 CF=1.00
Shear Stress: Fv= 170 psi Fv'= 170 psi POINT LOADS-CENTER SPAN 7
Cd=1.00 Load Number One
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi Live Load 1583 lb
Comp.l to Grain: Fc-1= 625 psi Fc--L'= 625 psi Dead Load 1055 lb
1.
Location 2 ft
Controlling Moment: 6097 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN .
2.33 Ft from left support of span 2(Center Span) Load Number One Two -•
Created by combining all dead loads and live loads on span(s)2 Left Live Load 92 plf 383 plf
Controlling Shear: 3040 lb Left Dead Load 61 plf 255 plf
At a distance d from left support of span 2(Center Span) Right Live Load 92 plf 383 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 61 plf 255 plf
Load Start 0 ft 2 ft
Comparisons with required sections: Req'd Provided Load End 2 ft 6.67 ft
Section Modulus: 83.81 in3 121.23 in3 Load Length 2 ft 4.67 ft
Area(Shear): 26.83 in2 63.25 in2
Moment of Inertia(deflection): 162.69 in4 697.07 in4
Moment: 6097 ft-lb 8820 ft-lb
Shear: 3040 lb 7168 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
1111111 Larry Widdifield
Location:M1-HDR Over shop Door StruCalc 9.0
Multi-Loaded Multi-Span Beam ll 2187 NW Reed St.Suite 100
of
[2015 International Building Code(2012 NDS)] ,, ._Portland,OR 97210
5.5 IN x 11.5 IN x 3.5 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:02 AM
Section Adequate By: 129.2%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.00 IN L/8637
.Dead Load 0.00 in
Total Load 0.01 IN L/5247
Live Load Deflection Criteria:U360 Total Load Deflection Criteria:U240
REACTIONS A B
Live Load 1744 lb 1463 lbi.
Dead Load 1142 lb 958 lb
TR3 '
Total Load 2886 lb 2421 lb _-=--
Bearing Length 0.84 in 0.70 in TRI
SEAM DATA Center
Span Length 3.5 ft R... �s-
Unbraced Length-Top 3.5 ft 3.5 ft
Unbraced Length-Bottom 3.5 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 14 plf
Bending Stress: Fb= 875 psi Fb'= 873 psi Total Uniform Load 14 plf
Cd=1.00 C1=1.00 CF=1.00 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 170 psi Fv'= 170 psi Load Number One
Cd=1.00 Live Load 2074 lb
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi Dead Load 1287 lb
Comp.1-to Grain: Fc-1= 625 psi Fc-1'= 625 psi Location 1.5 ft
Controlling Moment: 3846 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
1.5 Ft from left support of span 2(Center Span) Load Number One Two Three
Created by combining all dead loads and live loads on span(s)2 Left Live Load 275 plf 0 plf 240 plf
Controlling Shear: 2485 lb Left Dead Load 170 plf 80 plf 90 plf
At a distance d from left support of span 2(Center Span) Right Live Load 275 plf 0 plf 240 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 170 plf 80 plf 90 plf
Load Start 1.5 ft Oft O ft
Comparisons with required sections: Req'd Provided Load End 3 ft 3 ft 3 ft
Section Modulus: 52.89 in3 121.23 in3 Load Length 1.5 ft 3 ft 3 ft
Area(Shear): 21.93 in2 63.25 in2
Moment of Inertia(deflection): 31.89 in4 697.07 in4
Moment: 3846 ft-lb 8816 ft-lb
Shear: 2485 lb 7168 lb
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) Ell Larry Widdifield
Location:M2-Between Shop and Garage StruCalc 9.0
Uniformly Loaded Floor Beam 2187 NW Reed St.Suite 100 of ,
[2015 International Building Code(2012 NDS)] elo ._Portland,OR 97210
5.5 INx11.5INx10.75FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:07 AM
Section Adequate By: 13.6%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.14 IN L/926
Dead Load 0.04 in
Total Load 0.18 IN L/722
Live Load Deflection Criteria:L/480 Total Load Deflection Criteria:L/360
REACTIONS A
Live Load 2258 lb 2258 lb
Dead Load 638 lb 638 lb
Total Load 2896 lb 2896 lb
Bearing Length 0.84 in 0.84 in
SEAM DATA Center
Span Length 10.75 ft
Unbraced Length-Top 0 ft 10.75 ft
Floor Duration Factor 1.00
Notch Depth 0.00
MATERIAL PROPERTIES FLOOR LOADING
#2-Douglas-Fir-Larch Si e 1 Side 2
Base Values Adjusted Floor Live Load FLL= 40 psf 40 psf
Bending Stress: Fb= 875 psi Fb'= 875 psi Floor Dead Load FDL= 10 psf 10 psf
Cd=1.00 CF=1.00 Floor Tributary Width FTW= 5.5 ft 5 ft
Shear Stress: Fv= 170 psi Fv'= 170 psi
Cd=1.00 Wall Load WALL= 0 plf
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi
SEAM LOADING
Comp.±to Grain: Fc-±= 625 psi Fc-1'= 625 psi Beam Total Live Load: wL= 420 plf
Controlling Moment: 7782 ft-lb Beam Total Dead Load: wD= 105 plf
5.375 ft from left support Beam Self Weight: BSW= 14 plf
Total Maximum Load: wT= 539 plf
Created by combining all dead and live loads.
Controlling Shear: 2432 lb
At a distance d from support.
Created by combining all dead and live loads.
Comparisons with required sections: Rea'd Provided
Section Modulus: 106.72 in3 121.23 in3
Area(Shear): • 21.46 in2 63.25 in2
Moment of Inertia(deflection): 361.16 in4 697.07 in4
Moment: 7782 ft-lb 8840 ft-lb
Shear: 2432 lb 7168 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
Eli Larry Widdifield
Location:M3-FLr joist supporting BR-3 Dormer StruCalc 9.0
Multi-Loaded Multi-Span Beam ill 2187 NW Reed St.Suite 100 0f
[20'15 International Building Code(2012 NDS)] Portland,OR 97210
(2)1.51N x 11.25 IN x 10.0 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:02 AM
Section Adequate By:0.2%
Controlling Factor:Moment
CAUTIONS
*Laminations are to be fully connected to provide uniform transfer of loads to all members
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.07 IN U1645
Dead Load 0.07 in
Total Load 0.14 IN U854
Live Load Deflection Criteria:U360 Total Load Deflection Criteria:U240
REACTIONS A B +
Live Load 636 lb 739 lb
Dead Load 697 lb 602 lb
Total Load 1333 lb 1341 lb
Bearing Length 0.71 in 0.72 in
BEAM DATA Center
Span Length 10 ft
Unbraced Length-Top 0 ft A +o n
Unbraced Length-Bottom 10 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 7 plf
Bending Stress: Fb= 900 psi Fb'= 900 psi Total Uniform Load 7 plf
Cd=1.00 CF=1.00
Shear Stress: Fv= 180 psi Fv'= 180 psi POINT LOADS-CENTER SPAN
Cd=1.00 Load Number One
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Live Load 600 lb
Comp.- to Grain: Fc--L= 625 psi Fc-1'= 625 psi Dead Load 360 lb
Location 6 ft
Controlling Moment: 4738 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
5.8 Ft from left support of span 2(Center Span) Load Number One Two Three Four
Created by combining all dead loads and live loads on span(s)2 Left Live Load 100 plf 52 plf 26 plf 0 plf
Controlling Shear: 1308 lb Left Dead Load 140 plf 20 plf 28 plf 20 plf
At a distanced from left support of span 2(Center Span) Right Live Load 100 plf 52 plf 26 plf 0 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 140 plf 20 plf 28 plf 20 plf
Load Start 1.5 ft 6 ft 1.5 ft O ft
Comparisons with required sections: Reo'd Provided Load End 6 ft 10 ft 6 ft 1.5 ft
Section Modulus: 63.17 in3 63.28 in3 Load Length 4.5 ft 4 ft 4.5 ft 1.5 ft
Area(Shear): 10.9 in2 33.75 in2
Moment of Inertia(deflection): 100 in4 355.96 in4
Moment: 4738 ft-lb 4746 ft-lb
Shear: 1308 lb 4050 lb
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) Larry Widdifield
Location:M4 FLR JSTS Fron of Garage
11111Larry
9.0
Multi-Loaded Multi-Span Beam III 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] ___vl1 eJ .:Portland,OR 97210
5.125 IN x 18.0 IN x 10.0 FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:03 AM
Section Adequate By:3228.0%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.00 IN UMAX
Dead Load 0.00 in
Total Load 0.01 IN UMAX
Live Load Deflection Criteria:U360 Total Load Deflection Criteria:U240
REACTIONS A B
i
Live Load 187 lb 322 lb
Dead Load 252 lb 278 lb
Total Load 439 lb 600 lb
Bearing Length 0.13 in 0.18 in
SEAM DATA Cefligf . , . . -. _. _ ...,_ ... ._... <>.v,_,.._.n.. ..._. .. ....._. ..._„
Span Length 10 ft
Unbraced Length-Top 0 ft ion
Unbraced Length-Bottom 10 ft
Live Load Duration Factor 1.00
Camber Adj.Factor 1.5 UNIFORM LOADS Center
Camber Required 0
Notch Depth 0.00 Uniform Live Load 0 plf
Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 20 plf
24F-V4-Visually Graded Western Species Total Uniform Load 20 plf
Base Values Adiusted
POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by:
Fb cmpr= 1850 psi Fb'= 2400 psi LoadNumber
Cd=1.00 Live Looadd217 IOne
Dead Load 130 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi
Location 6 ft
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN ^
Comp.-L to Grain: Fc-L= 650 psi Fc-1'= 650 psi Load Number One o
Left Live Load 14 plf 52 plf
Controlling Moment: 1663 ft-lb Left Dead Load 20 plf 20 plf
6.0 Ft from left support of span 2(Center Span) Right Live Load 14 plf 52 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 20 plf 20 plf
Controlling Shear: -462 lb Load Start 0 ft 6 ft
At a distanced from right support of span 2(Center Span) Load End 6 ft 10 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 6 ft 4 ft
Comparisons with required sections: Reo'd Provided
Section Modulus: 8.32 in3 276.75 in3
Area(Shear): 2.61 in2 92.25 int
Moment of Inertia(deflection): 29.91 in4 2490.75 in4
Moment: 1663 ft-lb 55350 ft-lb
Shear: -462 lb 16298 lb
„ Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
Larry Widdifield
Location:M5-Main Beam Over Garage StruCalc 9.0
Multi-Loaded Multi-Span Beam III2187 NW Reed St.Suite 100
[2015 International Building Code(2012 NDS)] �r� Portland,OR 97210 or
5.125 IN x 18.0 IN x 20.0 FT
�1
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:04 AM
Section Adequate By:34.0%
controlling Factor: Moment
DEFLECTIONS Center WADING DIAGRAM
Live Load 0.36 IN L/669
.Dead Load 0.30 in
Total Load 0.66 IN L/366
Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:L/240
1
REACTIONS A B 2
Live Load 4402 lb 4605 lb i
Dead Load 3313 lb 4374 lbiillinillil
Total Load 7715 lb 8979 lb
Bearing Length 2.32 in 2.70 in • `
_ TR1, .1 ,
REAM DATA Cen er T� s_ L_ . --
Span Length 20 ft
Unbraced Length-Top 0 ft 20ft
Unbraced Length-Bottom 20 ft
Live Load Duration Factor 1.00
Camber Adj.Factor 1.5
Camber Required 0.45 ' UNIFORM LOADS Center
Notch Depth 0.00 Uniform Live Load 0 plf
Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 20 plf
24F-V4-Visually Graded Western Species Total Uniform Load 20 plf
Base Values Adiusted
Bending Stress: Fb= 2400 psi Controlled by: POINT LOADS CENTER SPAN
Fb_cmpr= 1850 psi Fb'= 2316 psi
Load Number One Two
Cd=1.00 Cv=0.96 Live Load 739 lb 739 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Dead Load 602 lb 602 lb
Cd=1.00 Location 6.5 ft 13 ft
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Cgmp. L to Grain: Fc-1= 650 psi Fc-1'= 650 psi Load Number One Two Three Four
Left Live Load 413 plf 250 plf 310 plf 150 plf
Controlling Moment: 39867 ft-lb Left Dead Load 256 plf 150 plf 150 plf 342 plf
11.0 Ft from left support of span 2(Center Span) Right Live Load 413 plf 250 plf 310 plf 150 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 256 plf 150 plf 150 plf 342 plf
Controlling Shear: -7619 lb Load Start 0 ft 6.5 ft 13 ft 13 ft
At a distanced from right support of span 2(Center Span) Load End 6.5 ft 13 ft 20 ft 20 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 6.5 ft 6.5 ft 7 ft 7 ft
Comparisons with required sections: Reo'd Provided
Section Modulus: 206.57 in3 276.75 in3
Area(Shear): 43.12 in2 92.25 in2
Moment of Inertia(deflection): 1632.81 in4 2490.75 in4
Moment: 39867 ft-lb 53411 ft-lb
Shear: -7619 lb 16298 lb
page 1
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) Larry Widdifield J
Location:M6-Garage dr HDR ® StruCalc 9.0
Multi-Loaded Multi-Span Beam N 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] _ .._Portland,OR 97210
5.125 IN x 13.5IN x 16.5 FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:05 AM
Section Adequate By: 1.0%
Controlling Factor:Deflection
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.27 IN L/737
Dead Load 0.28 in -
Total Load 0.54 IN L/363
Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:L/360
REACTIONS A B
Live Load 2286 lb 2286 lb
2
Dead Load 2558 lb 2558 lb
Total Load 4844 lb 4844 lb I1
Bearing Length 1.45 in 1.45 in TR' . 4
TR2 i TRS 9
REAM DATA enter
ro
Span Length 16.5 ft s � „���,F_.��,N .��.,,•..� ... .._..,.,„�o.,�:�,�.�,�,r_� , �
� .�.�,�.�r<,,, ,
Unbraced Length-Top 16.5 ft -16.5k
Unbraced Length-Bottom 16.5 ft
Live Load Duration Factor 1.00
Camber Adj.Factor 1
Camber Required 0.28 UNIFORM LOADS Center
Notch Depth 0.00 Uniform Live Load 0 plf
Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 15 plf
24F-V4-Visually Graded Western Species Total Uniform Load 15 plf
Base Values Adjusted
Bending Stress: Fb= 2400 psi Controlled by: POINT LOADS-CENTER SPAN
•
Load Number One Two
Fbcmpr= 1850 psi Fb'= 2328 psi Live Load 636 lb 636 lb
Cd—=1.00 CI=0.97 Dead Load 697 lb 697 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Location 5 ft 11.5 ft
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.-L to Grain: Fc-1= 650 psi Fc-1'= 650 psi Load Number One Two Three -
Left Live Load 187 plf 220 plf 187 plf
Controlling Moment: 20562 ft-lb Left Dead Load 252 plf 147 plf 252 plf
8.25 Ft from left support of span 2(Center Span) Right Live Load 187 plf 220 plf 187 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 252 plf 147 plf 252 plf
Controlling Shear: -4395 lb Load Start 0 ft 5 ft 11.5 ft
At a distance d from right support of span 2(Center Span) Load End 5 ft 11.5 ft 16.5 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 5 ft 6.5 ft 5 ft
Comparisons with required sections: Read Provided
Section Modulus: 105.99 in3 155.67 in3
Area(Shear): 24.88 in2 69.19 in2
Moment of Inertia(deflection): 1040.79 in4 1050.79 in4
Moment: 20562 ft-lb 30200 ft-lb
Shear: -4395 lb 12223 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) ® page
Larry Widdifield
Location:M7-BM BTWN GREAT RM/KITCHEN StruCalc 9.0
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Suite 100
of
[2015 International Building Code(2012 NDS)] _Portland,OR 97210
5.51N x 12.0 IN x 18.67 FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:27 AM
Section Adequate By: 15.9%
Controlling Factor:Deflection
DEFLECTIONS aulei WADING DIAGRAM
,Live Load 0.54 IN L/417
_Dead Load 0.16 in
Total Load 0.70 IN L/321
Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:L/240
REACTIONS A
Live Load 2614 lb 2614 lb
Dead Load 787 lb 787 lb
Total Load 3401 lb 3401 lb
Bearing Length 0.95 in 0.95 in
ElEAM DATA Center
Span Length 18.67 ft , .,_, ..__�, ;.F: . . -..., . ._„_r,.._,. .,-
Unbraced Length-Top 0 ft 18.67 ft
Unbraced Length-Bottom 18.67 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 1 UNIFORM LOADS Center
Camber Required 0.16 Uniform Live Load 280 plf
Notch Depth 0.00 Uniform Dead Load 70 plf
MATERIAL PROPERTIES Beam Self Weight 14 plf
24F-V4-Visually Graded Western Species Total Uniform Load 364 plf
Base Values Adjusted
Bending Stress: Fb= 2400 psi Controlled by:
Fb cmpr= 1850 psi Fb'= 2400 psi
Cd=1.00
Shear Stress: Fv= 265 psi Fv'= 265 psi
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi
Comp.1 to Grain: Fc- = 650 psi Fc- = 650 psi
Controlling Moment: 15873 ft-lb
9.34 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -3061 lb
At a distance d from right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 79.37 in3 132 in3
Area(Shear): 17.32 in2 66 in2
Moment of Inertia(deflection): 683.21 in4 792 in4
Moment: 15873 ft-lb 26400 ft-lb
Shear: -3061 lb 11660 lb
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) Larry Widdifield
Location:M8-Joists over Dining Rm ® StruCalc 9.0
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] Portland,OR 97210
(2)1.5 INx11.25INx11.0FT �
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:06 AM
Section Adequate By: 146.5%
Controlling Factor:Moment
CAUTIONS
*Laminations are to be fully connected to provide uniform transfer of loads to all members
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.04 IN L/3043
Dead Load 0.03 in
Total Load 0.07 IN U1793
Live Load Deflection Criteria:U360 Total Load Deflection Criteria:U360
REACTIONS A
Live Load 413 lb 413 lb
Dead Load 288 lb 288 lb
Total Load 700 lb 700 lb
Bearing Length 0.37 in 0.37 in
BEAM DATA Center
Span Length 11 ft
Unbraced Length-Top 0 ft »n B
Unbraced Length-Bottom 11 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Cen er
MATERIAL PROPERTIES Uniform Live Load 75 plf
#2-Douglas-Fir-Larch Uniform Dead Load 45 plf
Base Values Adjusted Beam Self Weight 7 plf
Bending Stress: Fb= 900 psi Fb'= 900 psi Total Uniform Load 127 plf
Cd=1.00 CF=1.00
Shear Stress: Fv= 180 psi Fv'= 180 psi 4
Cd=1.00 •
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Comp. L to Grain: Fc- L= 625 psi Fc-1'= 625 psi
Controlling Moment: 1926 ft-lb
5.5 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -588 lb
At a distance d from right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Reed Provided
Section Modulus: 25.68 in3 63.28 in3
Area(Shear): 4.9 in2 33.75 int
Moment of Inertia(deflection): 71.48 in4 355.96 in4
Moment: 1926 ft-lb 4746 ft-lb
Shear: -588 lb 4050 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
BE Larry Widdifield
Location:M9-BM Between Foyar and Dining StruCalc 9.0
Multi-Loaded Multi-Span Beam EN 2187 NW Reed St.Suite 100
[2015 International Building Code(2012 NDS)] _Portland,OR 97210 of
5.5 INx12.0INx9.5FT �
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:24 AM
Section Adequate By: 11.3%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
-Live Load 0.14 IN L/800
,Dead Load 0.09 in
Total Load 0.23 IN L/486
Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:L/240
REACTIONS A B
Live Load 3823 lb 3766 lb 2
Dead Load 2623 lb 2379 lb
Total Load 6446 lb 6145 lb wimilimmilmI
Bearing Length 1.80 in 1.72 in
BEAM DATA Center -
Span Length 9.5 ft :._..,_. ,. _-.. ,r�_,_—. ;, s
. .,.. :.>.
Unbraced Length-Top 0 ft A 9.5 ft
Unbraced Length-Bottom 9.5 ft
Live Load Duration Factor 1.00
Camber Adj.Factor 1 UNIFORM LOADS Center
Camber Required 0.09 Uniform Live Load 0 plf
Notch Depth 0.00 Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 14 plf
24F-V4-Visually Graded Western Species Total Uniform Load 14 plf
Base Values Adjusted
Bending Stress: Fb= 2400 psi Controlled by: POINT LOADS-CENTER SPAN
Load Number One Two
Fb_cmpr= 1850 psi Fb'= 2400 psi Live Load 720 lb 4044 lb
Cd=1.00 Dead Load 270 lb 2696 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Location 4 ft 5 ft
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.-1-to Grain: Fc- L= 650 psi Fc-1'= 650 psi Load Number One Two Three
Left Live Load 301 plf 541 plf 240 plf
Controlling Moment: 23720 ft-lb Left Dead Load 264 plf 304 plf 120 plf
4.94 Ft from left support of span 2(Center Span) Right Live Load 301 plf 541 plf 240 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 264 plf 304 plf 120 plf
Controlling Shear: 5896 lb Load Start O ft 4 ft 5 ft
At a distance d from left support of span 2(Center Span) Load End 4 ft 5 ft 9.5 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 4 ft 1 ft 4.5 ft
Comparisons with required sections: Rea'd Provided
Section Modulus: 118.6 in3 132 in3
Area(Shear): 33.37 in2 66 in2
Moment of Inertia(deflection): 390.74 in4 792 in4
Moment: 23720 ft-lb 26400 ft-lb
Shear: 5896 lb 11660 lb
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF)
Ell Larry Widdifield0
LocaMulti-Loaded Muion: lti-Span Sp n B R over a 2187 N
Door Ic W Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] __,1,40,16.14,{._Portland,OR 97210
5.5INx7.25INx5.OFT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:18 AM
Section Adequate By:50.9%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.02 IN L/2584
Dead Load 0.02 in
Total Load 0.04 IN L/1517
Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:U240
REACTIONS A_
Live Load 938 lb 938 lb
Dead Load 659 lb 659 lb •
Total Load 1597 lb 1597 lb
Bearing Length 0.46 in 0.46 in
J3EAM DATA Center •
Span Length 5 ft
Unbraced Length-Top 0 ft 5ft B
Unbraced Length-Bottom 5 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 375 plf
#2-Douglas-Fir-Larch Uniform Dead Load 255 plf
Base Values Adjusted Beam Self Weight 9 plf
Bending Stress: Fb= 750 psi Fb'= 750 psi Total Uniform Load 639 plf
Cd=1.00 CF=1.00
Shear Stress: Fv= 170 psi Fv'= 170 psi
Cd=1.00
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi
Comp. L to Grain: Fc- L= 625 psi Fc-1'= 625 psi
Controlling Moment: 1996 ft-lb
2.5 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: 1213 lb
At a distance d from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 31.93 in3 48.18 in3
Area(Shear): 10.71 in2 39.88 in2
Moment of Inertia(deflection): 27.63 in4 174.66 in4
Moment: 1996 ft-lb 3011 ft-lb
Shear: 1213 lb 4519 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
111111•
Larry Widdifield
Location:M11-Bm between Great Rm&Hall StruCalc 9.0
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Suite 100
[2015 International Building Code(2012 NDS)] Portland,OR 97210 of
5.125 INx12.0INx6.0FT �` �
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:19 AM
Section Adequate By: 1250.6%
Controlling Factor:Shear •
REFLECTIONS Center LOADING DIAGRAM
_ Live Load 0.01 IN UMAX
Dead Load 0.00 in
Total Load 0.01 IN U8319
Live Load Deflection Criteria: U360 Total Load Deflection Criteria:U240
REACTIONS A
Live Load 714 lb 714 lb
Dead Load 469 lb 469 lb
Total Load 1183 lb 1183 lb
Bearing Length 0.36 in 0.36 in
REAM DATA Center
Span Length 6 ft
Unbraced Length-Top 0 ft 6ft
Unbraced Length-Bottom 6 ft
Live Load Duration Factor 1.00
Camber Adj.Factor 1 UNIFORM LOADS Center
Camber Required 0 Uniform Live Load 238 plf
Notch Depth 0.00 Uniform Dead Load 143 plf
MATERIAL PROPERTIES Beam Self Weight 13 plf
24F-V4-Visually Graded Western Species Total Uniform Load 394 plf
Base Values Adjusted
Bending Stress: Fb= 2400 psi Controlled by:
Fb cmpr= 1850 psi Fb'= 2400 psi
Cd=1.00
Shear Stress: Fv= 265 psi Fv'= 265 psi
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi
Comp.-L to Grain: Fc-1= 650 psi Fc-1'= 650 psi
Controlling Moment: 1774 ft-lb
3.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -804 lb
At a distance d from right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Rea'd Provided
Section Modulus: 8.87 in3 123 in3
Area(Shear): 4.55 in2 61.5 in2
Moment of Inertia(deflection): 21.29 in4 738 in4
Moment: 1774 ft-lb 24600 ft-lb
Shear: -804 lb 10865 lb
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) 1111 Larry Widdifield /
Location:M12-FRONT PORCH SIDE BM StruCalc 9.0
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] _Portland,OR 97210
3.5 IN x 11.25 IN x 3.0 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:19 AM
Section Adequate By:2496.2%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.00 IN UMAX ►
Dead Load 0.00 in
Total Load 0.00 IN UMAX
Live Load Deflection Criteria:U480 Total Load Deflection Criteria:L/360
REACTIONS A B
Live Load 188 lb 188 lb
Dead Load 125 lb 125 lb
Total Load 313 lb 313 lb
Bearing Length 0.14 in 0.14 in
)BEAM DATA Center
Span Length 3 ft
Unbraced Length-Top 0 ft aft B
Unbraced Length-Bottom 3 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 125 plf
#2-Douglas-Fir-Larch Uniform Dead Load 75 plf
Base Values Adjusted Beam Self Weight 9 plf
Bending Stress: Fb= 900 psi Fb'= 990 psi Total Uniform Load 209 plf
Cd=1.00 CF=1.10
Shear Stress: Fv= 180 psi Fv'= 180 psi •
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Comp.±to Grain: Fc- L= 625 psi Fc-±'= 625 psi
Controlling Moment: 235 ft-lb
1.5 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -119 lb
At a distance d from right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provide
Section Modulus: 2.84 in3 73.83 in3
Area(Shear): 0.99 in2 39.38 in2
Moment of Inertia(deflection): 2.37 in4 415.28 in4
Moment: 235 ft-lb 6091 ft-lb
Shear: -119 lb 4725 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF)
E. page
Larry Widdifield
Location:M13-FRONT PORCH FRONT BM StruCalc 9.0
Multi-Loaded Multi-Span Beam IIII 2187 NW Reed St.Suite 100
[2015 International Building Code(2012 NDS)] _Portland,OR 97210 or
3.5 INx11.25INx6.0FTrs'la .
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:20 AM
Section Adequate By: 1207.3%
Controlling Factor:Moment
DEFLECTIONS Center )LOADING DIAGRAM
Live Load 0.00 IN UMAX
Dead Load 0.00 in
Total Load 0.00 IN UMAX
Live Load Deflection Criteria: U480 Total Load Deflection Criteria:U360
REACTIONS A B
Live Load 150 lb 150 lb
Dead Load 161 lb 161 lb
Total Load 311 lb 311 lb
Bearing Length 0.14 in 0.14 in
SEAM DATA Center
Span Length 6 ft
Unbraced Length-Top 0 ft
Unbraced Length-Bottom 6 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 50 plf
#2-Douglas-Fir-Larch Uniform Dead Load 45 plf
Base Values Adjusted Beam Self Weight 9 plf
Bending Stress: Fb= 900 psi Fb'= 990 psi Total Uniform Load 104 plf
Cd=1.00 CF=1.10
Shear Stress: Fv= 180 psi Fv'= 180 psi
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Comp.L to Grain: Fc-L= 625 psi Fc-L'= 625 psi
Gontrolling Moment: 466 ft-lb
3.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -217 lb
At a distance d from right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 5.65 in3 73.83 in3
Area(Shear): 1.81 in2 39.38 in2
Moment of Inertia(deflection): 9.43 in4 415.28 in4
Moment: 466 ft-lb 6091 ft-lb
Shear: -217 lb 4725 lb
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) no Larry Widdifield
Location:M14-WINDOW HDR AT GREAT RM StruCalc 9.0
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] Portland,OR 97210
3.5 IN x 9.25 IN x 9.91 FT(3.3+3.3+3.2) �
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:25 AM
Section Adequate By: 174.2%
Controlling Factor:Shear
DEFLECTIONS Left Center Right LOADING DIAGRAM
Live Load 0.00 IN UMAX 0.00 IN UMAX 0.00 IN UMAX
Dead Load 0.00 in 0.00 in 0.00 in 4
Total Load 0.00 IN UMAX 0.00 IN UMAX 0.01 IN U6858
Live Load Deflection Criteria:U360 Total Load Deflection Criteria:L/240
REACTIONS A B C D
Live Load 608 lb 1570 lb 2353 lb 1117 lb
Dead Load 259 lb 601 lb 1203 lb 599 lb
Total Load 867 lb 2171 lb 3556 lb 1717 lb
Bearing Length 0.40 in 0.99 in 1.63 in 0.78 in
)SEAM DATA Left Center Right
Span Length 3.33 ft 3.33 ft 3.25 ft
Unbraced Length-Top O ft O ft O ft 3.33 ft 3.33 ft 3.25 ft ill-
Unbraced Length-Bottom 3.33 ft 3.33 ft 3.25 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Left Center Right
MATERIAL PROPERTIES Uniform Live Load 393 plf 393 plf 776 plf
#2-Douglas-Fir-Larch Uniform Dead Load 178 plf 178 plf 433 plf
Base Values Adjusted Beam Self Weight 7 plf 7 plf 7 plf
Bending Stress: Fb= 900 psi Fb'= 1080 psi Total Uniform Load 578 plf 578 plf 1216 plf
Cd=1.00 CF=1.20
Shear Stress: Fv= 180 psi Fv'= 180 psi
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Comp.1 to Grain: Fc- = 625 psi Fc--- = 625 psi •
-
Controlling Moment: 1212 ft-lb
1.85 Ft from left support of span 3(Right Span)
Created by combining all dead loads and live loads on span(s) 1,3
Controlling Shear: 1417 lb
At a distance d from left support of span 3(Right Span)
Created by combining all dead loads and live loads on span(s)2,3
Comparisons with required sections: Req'd Provided
Section Modulus: 13.47 in3 49.91 in3
Area(Shear): 11.81 in2 32.38 in2
Moment of Inertia(deflection): 8.19 in4 230.84 in4
Moment: 1212 ft-lb 4492 ft-lb
Shear: 1417 lb 3885 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
111111 Larry Widdifield
Location:M15-MULT JSTS OVER GREAT RM BUILT-INS/FIREPLACE StruCalc 9.0
Multi-Loaded Multi-Span Beam EN 2187 NW Reed St.Suite 100
[2015 International Building Code(2012 NDS)] Portland,OR 97210 or
(2) 1.5 INx11.25INx19.17FT(7.2+4.7+7.2)
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:26 AM
Section Adequate By: 166.9%
Controlling Factor:Moment
CAUTIONS
, *Laminations are to be fully connected to provide uniform transfer of loads to all members
DEFLECTIONS Left Center Right LOADING DIAGRAM
Live Load 0.01 IN L/7012 0.00 IN UMAX 0.01 IN U7012
Dead Load 0.01 in 0.00 in 0.01 in
Total Load 0.03 IN U3289 -0.01 IN U7093 0.03 IN U3289
Live Load Deflection Criteria:U360 Total Load Deflection Criteria:U240
REACTIONS A B C D
Live Load 516 lb 1258 lb 1258 lb 516 lb
Dead Load 633 lb 1363 lb 1363 lb 633 lb
Total Load 1149 lb 2622 lb 2622 lb 1149 lb
Bearing Length 0.61 in 1.40 in 1.40 in 0.61 in
BEAM DATA Left Center Right
Span Length 7.25 ft 4.67 ft 7.25 ft
Unbraced Length-Top O ft O ft O ft 7.25 ft 4.67 ft- 7.25 ft
Unbraced Length-Bottom 7.25 ft 4.67 ft 7.25 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Left Center Right
MATERIAL PROPERTIES Uniform Live Load 163 plf 163 plf 163 plf
#2-Douglas-Fir-Larch Uniform Dead Load 201 plf 201 plf 201P if
Base Values Adjusted Beam Self Weight 7 plf 7 plf 7 plf
Bending Stress: Fb= 900 psi Fb'= 900 psi Total Uniform Load 371 plf 371 plf 371 plf
Cd=1.00 CF=1.00
Shear Stress: Fv= 180 psi Fv'= 180 psi
- Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Comp. L to Grain: Fc-1= 625 psi Fc-1'= 625 psi
Controlling Moment: 1778 ft-lb •
3.12 Ft from left support of span 1 (Left Span)
Created by combining all dead loads and live loads on span(s) 1,3
Controlling Shear: -1258 lb
At a distance d from the right support of span 1 (Left Span)
Created by combining all dead loads and live loads on span(s)1,2
Comparisons with required sections: Read Provided
Section Modulus: 23.71 in3 63.28 in3
Area(Shear): 10.48 in2 33.75 in2
Moment of Inertia(deflection): 25.98 in4 355.96 in4
Moment: 1778 ft-lb 4746 ft-lb
Shear: -1258 lb 4050 lb
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) Larry Widdifield /
Location:Multi-Loaded Multi-Span Beam 1 ® StruCalc 9.0
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] ,ffJJ Portland,OR 97210
(2) 1.5 IN x 7.25 IN x 5.33 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0.1.7 4/22/2015 7:46:11 AM
Section Adequate By:210.2%
Controlling Factor:Moment
CAUTIONS
*Laminations are to be fully connected to provide uniform transfer of loads to all members
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN U4296
Dead Load 0.01 in
Total Load 0.03 IN U2501
Live Load Deflection Criteria:L1360 Total Load Deflection Criteria:L/240
REACTIONS e
Live Load 333 lb 333 lb
Dead Load 239 lb 239 lb
Total Load 572 lb 572 lb
Bearing Length 0.31 in 0.31 in
BEAM DATA Center
Span Length 5.33 ft - ,;...n ......_v . _.- r .. :..-.... .�.m.
Unbraced Length-Top 0 ft 5.33 ft B
Unbraced Length-Bottom 5.33 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 125 plf
#2-Douglas-Fir-Larch Uniform Dead Load 85 plf
Base Values Adjusted Beam Self Weight 5 plf.
Bending Stress: Fb= 900 psi Fb'= 1080 psi Total Uniform Load 215 plf
Cd=1.00 CF=1.20
Shear Stress: Fv= 180 psi Fv'= 180 psi
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Comp. L to Grain: Fc- = 625 psi Fc--- = 625 psi
Controlling Moment: 762 ft-lb
2.66 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: 446 lb
At a distance d from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Read Provided
Section Modulus: 8.47 in3 26.28 in3
Area(Shear): 3.72 in2 21.75 in2
Moment of Inertia(deflection): 9.14 in4 95.27 in4
Moment: 762 ft-lb 2365 ft-lb
Shear: 446 lb 2610 lb
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
1111111 Larry Widdifield
Location:FT1 - for Garage beam M-5 StruCalc 9.0
Footing 2187 NW Reed St.Suite 100
of
[2015 International Building Code(2012 NDS)] _Portland,OR 97210
Footing Size:2.66 FT x 2.66 FT x 12.00 IN
Reinforcement:#4 Bars @ 8.00 IN.O.C.E/W/(4)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:12 AM
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.66 ft
Length: L= 2.66 ft
Depth: Depth= 12 in
Effective Depth to Top Layer of Steel: d= 8.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 5.5 in
Column Depth: n= 5.5 in
FOOTING CALCULATIONS
F-5.5 in
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1269 psf
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf
Required Footing Area: Areq= 6.65 sf
Area Provided: A= 7.08 sf
Baseplate Bearing: 12 in
Bearing Required: Bear= 12617 lb
Allowable Bearing: Bear-A= 83566 lb Cj
Beam Shear Calculations(One Way Shear): 3 in
Seam Shear: Vu1 = 3047 lb
iylowable Beam Shear: Vc1 = 19751 lb � 2.66 n
Punching Shear Calculations(Two Way Shear):
Critical Perimeter: Bo= 55 in
Punching Shear: Vu2= 10276 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 102094 lb Live Load: PL= 4605 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 136125 lb Dead Load: PD= 4374 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 68063 lb Total Load: PT= 8979 lb
Controlling Allowable Punching Shear: vc2= 68063 lb Ultimate Factored Load: Pu= 12617 lb
Bending Calculations: Weight to resist uplift w/1.5 F.S.: U.R.= 684 lb
Factored Moment: Mu= 50341 in-lb
Nominal Moment Strength: Mn= 335000 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.69 in
Steel Required Based on Moment: As(1)= 0.11 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.69 in2
Controlling Reinforcing Steel: As-reqd= 0.69 in2
Selected Reinforcement: #4's @ 8.0 in.o.c.e/w(4)Min.
Reinforcement Area Provided: As= 0.79 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 12.96 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) Larry Widdifield
Location:FT1A- for Garage beam M-5(outside wall) StruCalc 9.0 /
Footing 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] _1.50.‘15. :._Portland,OR 97210
Footing Size:2.5 FT x 2.5 FT x 12.00 IN
Reinforcement:#4 Bars @ 7.00 IN.O.C.EM//(4)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:13 AM
Section Footing Design Adequate •
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.5 ft
Length: L= 2.5 ft
Depth: Depth= 12 in
Effective Depth to Top Layer of Steel: d= 8.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 5.5 in
Column Depth: n= 5.5 in
FOOTING CALCULATIONS
1-5.5 in {
Bearing Calculations: �
Ultimate Bearing Pressure: Qu= 1234 psf
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf
Required Footing Area: Areq= 5.71 sf
Area Provided: A= 6.25 sf
Baseplate Bearing: 12 in
Bearing Required: Bear= 11019 lb
Allowable Bearing: Bear-A= 83566 lb �' o P T
Beam Shear Calculations(One Way Shear):
in
Beam Shear: Vu1 = 2479 lb
Allowable Beam Shear: Vc1 = 18563 lb
Punching Shear Calculations(Two Way Shear): 2.5 n
Critical Perimeter: Bo= 55 in
Punching Shear: Vu2= 8704 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 102094 lb Live Load: PL= 4402 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 136125 lb Dead Load: PD= 3313 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 68063 lb Total Load: PT= 7715 lb
Controlling Allowable Punching Shear: vc2= 68063 lb Ultimate Factored Load: Pu= 11019 lb
Bending Calculations: Weight to resist uplift w/1.5 F.S.: U.R.= 604 lb
Factored Moment: Mu= 41321 in-lb
Nominal Moment Strength: Mn= 334058 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.74 in
Steel Required Based on Moment: As(1)= 0.09 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.65 in2
Controlling Reinforcing Steel: As-reqd= 0.65 in2
Selected Reinforcement: #4's @ 7.0 in.o.c.e/w(4)Min.
Reinforcement Area Provided: As= 0.79 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 12 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
,, Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
11111 Larry Widdifield
Location: FT2- in Garage for U2 (house side) StruCalc 9.0
Footing EN 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] Portland,OR 97210
Footing Size:2.5 FT x 2.5 FT x 12.00 IN – �
Reinforcement:#4 Bars @ 7.00 IN.O.C. ENV/(4)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:14 AM
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi 1-7.5 in I
Reinforcing Steel Yield Strength: Fy= 60000 psi I I
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.5 ft
Length: L= 2.5 ft
Depth: Depth= 12 in 12 in
Effective Depth to Top Layer of Steel: d= 8.25 in
COLUMN AND BASEPLATE SIZE –1–
Column
Column Type: Wood 3 in
Column Width: m= 5.5 in i_
Column Depth: n= 7.5 in I 2.5ft
I
FOOTING CALCULATIONS H-5.5 in-
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1282 psf
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf
Required Footing Area: Areq= 5.94 sf
Area Provided: A= 6.25 sf
Baseplate Bearing: 12 in
Bearing Required: Bear= 11635 lb
Allowable Bearing: Bear-A= 113953 lb P o o 7-
Beam Shear Calculations(One Way Shear): 3 in
Beam Shear: Vu1 = 2618 lb
allowable Beam Shear: Vc1 = 18563 lb
II
Punching Shear Calculations(Two Way Shear): 2.5 ft
Critical Perimeter: Bo= 59 in
Punching Shear: Vu2= 8835 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 90049 lb Live Load: PL= 5045 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 138600 lb Dead Load: PD= 2969 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 73013 lb Total Load: PT= 8014 lb
Controlling Allowable Punching Shear: vc2= 73013 lb Ultimate Factored Load: Pu= 11635 lb
Bending Calculations: Weight to resist uplift w/1.5 F.S.: U.R.= 604 lb
Factored Moment: Mu= 43631 in-lb
Nominal Moment Strength: Mn= 334058 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.74 in
Steel Required Based on Moment: As(1)= 0.10 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.65 in2
Controlling Reinforcing Steel: As-reqd= 0.65 in2
Selected Reinforcement: #4's @ 7.0 in.o.c.e/w(4)Min.
Reinforcement Area Provided: As= 0.79 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 12 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) 111111 Larry Widdifield
Location:FT2A-in Garage for U2(outer side) StruCalc 9.0��
Footing 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] Portland,OR 97210
Footing Size:2.33 FT x 2.33 FT x 12.00 IN ` s
Reinforcement:#4 Bars @ 7.00 IN.O.C.E/W/(4)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:15 AM
Section Footing Design Adequate
4
FOOTING PROPERTIES LOADING DIAGRAM -
Allowable Soil Bearing Pressure: Qs= 1500 psf ��'Sio 1
Concrete Compressive Strength: F'c= 2500 psi I I
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.33 ft
Length: L= 2.33 ft 12 in
Depth: Depth= 12 in
Effective Depth to Top Layer of Steel: d= 8.25 in P n o o
–1--
COLUMN
COLUMN AND BASEPLATE SIZE 3 in
Column Type: Wood _L
Column Width: m= 5.5 in
Column Depth: n= 7.5 in 2.33 ft
FOOTING CALCULATIONS I-5.5 in--I
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 909 psf
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf
Required Footing Area: Areq= 3.66 sf
Area Provided: A= 5.43 sf
Baseplate Bearing: 12 in
Bearing Required: Bear= 7045 lb
Allowable Bearing: Bear-A= 113953 lb r o n 9 -i-
Beam Shear Calculations(One Way Shear): — -3 in
Beam Shear: Vu1 = 1444 lb
Allowable Beam Shear: Vc1 = 17300 lb
Punching Shear Calculations(Two Way Shear): 2.33 ft
2.
Critical Perimeter: Bo= 59 in
Punching Shear: Vu2= 5094 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 90049 lb Live Load: PL= 2802 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 138600 lb Dead Load: PD= 2135 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 73013 lb Total Load: PT= 4937 lb
Controlling Allowable Punching Shear: vc2= 73013 lb Ultimate Factored Load: Pu= 7045 lb
Bending Calculations: Weight to resist uplift w/1.5 F.S.: U.R.= 525 lb
Factored Moment: Mu= 24623 in-lb
Nominal Moment Strength: Mn= 332916 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.79 in
Steel Required Based on Moment: As(1)= 0.06 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.60 in2
Controlling Reinforcing Steel: As-reqd= 0.60 in2
Selected Reinforcement: #4's @ 7.0 in.o.c.e/w(4)Min.
Reinforcement Area Provided: As= 0.79 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 10.98 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
Ell Larry Widdifield
Location:FT3-at Kit Great room&Dining StruCalc 9.0
Footing NI 2187 NW Reed St.Suite 100
of
12015 International Building Code(2012 NDS)) Portland,OR 97210
Footing Size:2.67 FT x 2.67 FT x 14.00 IN
Reinforcement:#4 Bars @ 6.00 IN.O.C.E/W/(5)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:16 AM
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
' Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.67 ft
Length: L= 2.67 ft
Depth: Depth= 14 in
Effective Depth to Top Layer of Steel: d= 10.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 4 in
Column Depth: n= 4 in
FOOTING CALCULATIONS I--4 in H
_ I I
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1292 psf
Effective Allowable Soil Bearing Pressure: Qe= 1325 psf
Required Footing Area: Areq= 6.95 sf
Area Provided: A= 7.13 sf 14 in
Baseplate Bearing:
Bearing Required: Bear= 13645 lb
Allowable Bearing: Bear-A= 44200 lb 0 0 0 0 T
Beam Shear Calculations(One Way Shear):
3 in
Beam Shear: Vu1 = 2457 lb
Allowable Beam Shear: Vc1 = 24631 lb
2.67 ft
Punching Shear Calculations(Two Way Shear):
Critical Perimeter: Bo= 57 in
Punching Shear: Vu2= 10946 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 131456 lb Live Load: PL= 6482 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 201413 lb Dead Load: PD= 2728 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 87638 lb Total Load: PT= 9210 lb
Controlling Allowable Punching Shear: vc2= 87638 lb Ultimate Factored Load: Pu= 13645 lb
Bending Calculations: Weight to resist uplift w/1.5 F.S.: U.R.= 804 lb
Factored Moment: Mu= 54647 in-lb
Nominal Moment Strength: Mn= 520212 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.86 in
Steel Required Based on Moment: As(1)= 0.10 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.81 in2
Controlling Reinforcing Steel: As-reqd= 0.81 in2
Selected Reinforcement: #4's @ 6.0 in.o.c.e/w(5)Min.
Reinforcement Area Provided: As= 0.98 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 13.02 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) ME Larry Widdifield
Location:FT4-Between Nook&Great Rm. StruCalc 9.0
Footing 11111 2187 NW Reed St.Suite 100 of .
[2015 International Building Code(2012 NDS)] ___,,,k4„..0.4,(.._Portland,OR 97210
Footing Size:2.5 FT x 2.5 FT x 12.00 IN
Reinforcement:#4 Bars @ 7.00 IN.O.C.E/W/(4)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:17 AM
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM r
Allowable Soil Bearing Pressure: Qs= 1500 psf ,
Concrete Compressive Strength: F'c= 2500 psi I--6 in—H
Reinforcing Steel Yield Strength: Fy= 60000 psi I I
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.5 ft
Length: L= 2.5 ft
Depth: Depth= 12 in 12 in
Effective Depth to Top Layer of Steel: d= 8.25 in
COLUMN AND BASEPLATE SIZE T
Column Type: Wood 3 in
Column Width: m= 4 in _L
Column Depth: n= 6 in I 2.5 ft
I
FOOTING CALCULATIONS 1-4 in-H
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1284 psf
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf
Required Footing Area: Areq= 5.94 sf
Area Provided: A= 6.25 sf
Baseplate Bearing: 12 in
Bearing Required: Bear= 11578 lb
Allowable Bearing: Bear-A= 66300 lb P n n 9
-T-
Beam
Beam Shear Calculations(One Way Shear): :3 in
Beam Shear: Vu1 = 2605 lb )
Allowable Beam Shear: Vc1 = 18563 lb
Punching Shear Calculations(Two Way Shear): I 2.5 ft
Critical Perimeter: Bo= 53 in
Punching Shear: Vu2= 9333 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 76519 lb Live Load: PL= 4877 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 134888 lb Dead Load: PD= 3146 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 65588 lb Total Load: PT= 8023 lb
Controlling Allowable Punching Shear: vc2= 65588 lb Ultimate Factored Load: Pu= 11578 lb
Bending Calculations: Weight to resist uplift w/1.5 F.S.: U.R.= 604 lb
Factored Moment: Mu= 43419 in-lb
Nominal Moment Strength: Mn= 334058 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.74 in
Steel Required Based on Moment: As(1)= 0.10 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.65 in2
Controlling Reinforcing Steel: As-reqd= 0.65 in2
Selected Reinforcement: #4's @ 7.0 in.o.c.e/w(4)Min.
Reinforcement Area Provided: As= 0.79 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 12 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) page
Larry Widdifield
Location:FT5-FRONT PORCH DINING SIDE @ HOUSE ® StruCalc 9.0
Footing Ell 2187 NW Reed St.Suite 100 of
[20'15 International Building Code(2012 NDS)] _Portland,OR 97210
Footing Size: 1.83 FT x 2.33 FT x 10.00 IN
Reinforcement in Long Direction:#4 Bars @ 7.00 IN.O.C./(3)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:10 AM
Reinforcement in Short Direction-center band(Equal to width of short side):#4
Bars @ 10.00 IN.O.C./(3)min.
Reinforcement in Short Direction-outside bands:#4 Bars @ 0.00 IN.O.C./0
tach band.
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in I 4 in--1
FOOTING SIZE I I
Width: W= 1.83 ft
Length: L= 2.33 ft
Depth: Depth= 10 in
Effective Depth to Top Layer of Steel: d= 6.25 in to in
COLUMN AND BASEPLATE SIZE F o c
i
Column Type: Wood 1-
Column
Column Width: m= 4 in 3 in
Column Depth: n= 4 in _L
FOOTING CALCULATIONS I 2.33 ft
I-4 in--I
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 378 psf
Effective Allowable Soil Bearing Pressure: Qe= 1375 psf
Required Footing Area: Areq= 1.17 sf
Area Provided: A= 4.26 sf
Baseplate Bearing: 10 in
Bearing Required: Bear= 2010 lb
Allowable Bearing: Bear-A= 44200 lb -T—
Beam
Beam Shear Calculations(One Way Shear):
3 in
Beam Shear: Vu1 = 556 lb
Allowable Beam Shear: Vc1 = 10294 lb
Punching Shear Calculations(Two Way Shear): I 1.83 ft
Critical Perimeter: Bo= 41 in
Punching Shear: Vu2= 1666 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 57656 lb Live Load: PL= 188 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 77813 lb Dead Load: PD= 1424 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 38438 lb Total Load: PT= 1612 lb
Controlling Allowable Punching Shear: vc2= 38438 lb Ultimate Factored Load: Pu= 2010 lb
Weight to resist uplift w/1.5 F.S.: U.R.= 343 lb
Short Direction: Long Direction:
Bending Calculations: Bending Calculations:
Factored Moment: Mu= 5516 in-lb Factored Moment: Mu= 7024 in-I)
Nominal Moment Strength: Mn= 189252 in-lb Nominal Moment Strength: Mn= 186758 in-ID
Reinforcement Calculations: Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.59 in Concrete Compressive Block Depth: a= 0.76 in
Steel Required Based on Moment: As(1)= 0.02 in2 Steel Required Based on Moment: As(1)= 0.02 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.50 in2 Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.4 in2
Controlling Reinforcing Steel: As-reqd= 0.50 in2 Controlling Reinforcing Steel: As-reqd= 0.4 in2
Selected Reinforcement: Short Dir:#4's @ 10.0 in.o.c.(3)Min. Selected Reinforcement: Long Dir:#4's @ 7.0 in.o.c.(3)Min.
Reinforcement Area Provided: As= 0.59 in2 Reinforcement Area Provided: As= 0.59 in2
Development Length Calculations: Development Length Calculations:
Development Length Required: Ld= 15 in Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 7.98 in Development Length Supplied: Ld-sup= 10.98 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
•
page
Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) III Larry Widdifield
Location:FT6-FRONT PORCH OUTER CORNER StruCalc 9.0
Footing nil 2187 NW Reed St.Suite 100 of
[2015 International Building Code(2012 NDS)] ____441400.0.}.W..._Portland,OR 97210
Footing Size:2.83 FT x 2.83 FT x 10.00 IN •
Reinforcement:#4 Bars @ 9.00 IN.O.C.E/W/(4)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:08 AM
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
r
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.83 ft
Length: L= 2.83 ft I-4 in-H
Depth: Depth= 10 in — I I
Effective Depth to Top Layer of Steel: d= 6.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood 10 in
Column Width: m= 4 in P 0 q
Column Depth: n= 4 in -r-
3 in
FOOTING CALCULATIONS _ _1_
I 2.83 ft
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 435 psf 1-4 in—I
Effective Allowable Soil Bearing Pressure: Qe= 1375 psf I I
Required Footing Area: Areq= 2.53 sf
Area Provided: A= 8.01 sf
Baseplate Bearing:
Bearing Required: Bear= 4403 lb io in
Allowable Bearing: Bear-A= 44200 lb p n 0 9
Beam Shear Calculations(One Way Shear):
Beam Shear: Vu1 = 1391 lb in
1 �
Allowable Beam Shear: Vc1 = 15919 lb =_
Punching Shear Calculations(Two Way Shear): i 2.e3 ft
Critical Perimeter: Bo= 41 in I.
Punching Shear: Vu2= 4002 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 57656 lb Live Load: PL= 338 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 77813 lb Dead Load: PD= 3145 lb •
Allowable Punching Shear(ACI 11-37): vc2-c= 38438 lb Total Load: PT= 3483 lb
Controlling Allowable Punching Shear: vc2= 38438 lb Ultimate Factored Load: Pu= 4403 lb
Bending Calculations: Weight to resist uplift w/1.5 F.S.: U.R.= 645 lb
Factored Moment: Mu= 18691 in-lb
Nominal Moment Strength: Mn= 251104 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.65 in
Steel Required Based on Moment: As(1)= 0.06 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.61 in2
Controlling Reinforcing Steel: As-reqd= 0.61 in2
Selected Reinforcement: #4's @ 9.0 in.o.c.e/w(4)Min.
Reinforcement Area Provided: As= 0.79 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 13.98 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
„ Project:22151A-FOUR D CONSTRUCTION(COMP ROOF) ® page
Larry Widdifield
Location:FT7-FRONT PORCH DEN SIDE StruCalc 9.0
Footing Ell 2187 NW Reed St.Suite 100
[2615 International Building Code(2012 NDS)] Portland,OR 97210 of
Footing Size:2.33 FT x 2.83 FT x 10.00 IN
Reinforcement in Long Direction:#4 Bars @ 10.00 IN.O.C./(3)min. StruCalc Version 9.0.1.7 4/22/2015 7:46:09 AM
Reinforcement in Short Direction-center band(Equal to width of short side):#4
Bars @ 9.00 IN.O.C./(4)min.
Reinforcement in Short Direction-outside bands:#4 Bars @ 0.00 IN.O.C./0
tach band.
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.33 ft
Length: L= 2.83 ft H4inH
Depth: Depth= 10 in I I
Effective Depth to Top Layer of Steel: d= 6.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood loin
Column Width: m= 4 in
Column Depth: n= 4 in —1--
3 in
FOOTING CALCULATIONS
I 2.83 ft I
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 343 psf H4 inH
Effective Allowable Soil Bearing Pressure: Qe= 1375 psf I I
Required Footing Area: Areq= 1.64 sf
Area Provided: A= 6.59 sf
Baseplate Bearing:
Bearing Required: Bear= 2955 lb 10 in
Allowable Bearing: Bear-A= 44200 lb p n ]
Beam Shear Calculations(One Way Shear): T
Beam Shear: Vu1 = 934 lb Sin
Allowable Beam Shear: Vc1 = 13106 lb
Punching Shear Calculations(Two Way Shear): 2.33 ft
Critical Perimeter: Bo= 41 in
Punching Shear: Vu2= 2628 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 57656 lb Live Load: PL= 150 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 77813 lb Dead Load: PD= 2111 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 38438 lb Total Load: PT= 2261 lb
Controlling Allowable Punching Shear: vc2= 38438 lb Ultimate Factored Load: Pu= 2955 lb
Weight to resist uplift w/1.5 F.S.: U.R.= 531 lb
Short Direction: Long Direction:
Bending Calculations: Bending Calculations:
Factored Moment: Mu= 10329 in-lb Factored Moment: Mu= 12546 in-b
Nominal Moment Strength: Mn= 251104 in-lb Nominal Moment Strength: Mn= 189343 in-b
Reinforcement Calculations: Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.65 in Concrete Compressive Block Depth: a= 0.59 in
Steel Required Based on Moment: As(1)= 0.03 in2 Steel Required Based on Moment: As(1)= 0.04 in2
Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.61 in2 Min.Code Req'd Reinf.Shrink./Temp.(ACI-10.5.4): As(2)= 0.5 in2
Controlling Reinforcing Steel: As-reqd= 0.61 in2 Controlling Reinforcing Steel: As-reqd= 0.5 in2
Selected Reinforcement: Short Dir:#4's @ 9.0 in.o.c.(4)Min. Selected Reinforcement: Long Dir:#4's @ 10.0 in.o.c.(3)Min.
Reinforcement Area Provided: As= 0.79 in2 Reinforcement Area Provided: As= 0.59 in2
Development Length Calculations: Development Length Calculations:
Development Length Required: Ld= 15 in Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 10.98 in Development Length Supplied: Ld-sup= 13.98 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.