InspectionsLocation:
Record Type:
Inspection Type:
Result:
Comments:
Inspection Date:
Record ID:
Inspector:
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223 Tel: 503.718.2439
14680 SW 117TH PL, TIGARD, OR, 97224
Residential - Fire Protection System
999 Sprinkler final
PASS - No C of O
FPS2015-00036
David Young
Approved back flow test report received.
1 1/2" Wilkins model 350, serial # 1122.
Obstructed head in closet ok per NFPA 13 D section 8.2.5-(1)
Violation Summary:
Inspector Contractor
Location:
Record Type:
Inspection Type:
Result:
Comments:
Inspection Date:
Record ID:
Inspector:
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223 Tel: 503.718.2439
14680 SW 117TH PL, TIGARD, OR, 97224
Residential - Fire Protection System
999 Sprinkler final
FAIL
FPS2015-00036
David Young
Provide approved back flow test report for FPS back flow devise.
Provide obstruction protection above shelf for head in lower level closet by stairwell in
back room, 18" obstruction clearance.
Violation Summary: