Loading...
Report ti //4 zot• s4v /v1;41445 RTU-5 Project: --Untitled106 09/08/2015 Prepared By: 03:44PM REC.EITIVED NOV ll 8 2015 RTU-5 CITY OFTTC Rj BUILDING DIVISION Tag Cover Sheet Unit Report Certified Drawing Performance Report Unit Feature Sheet • Packaged Rooftop Builder 1.39s Page 1 of 9 Unit Report For RTU-5 Project: —Untitled106 09/08/2015 Prepared By: 03:44PM Unit Parameters Dimensions(ft. in.)&Weight(1b.)*** Unit Model. 48TCDD12A2A6-0A0G0 Unit Length 7'4.125" Unit Size• 12(10 Tons) Unit Width. 4' 11.5" Volts-Phase-Hertz- 460-3-60 Unit Height 4' 1.375" Heating Type- Gas *•* Total Operating Weight 975 lb Duct Cfg• Vertical Supply I Vertical Return Low Heat ""' Weights and Dimensions are approximate. Weight does Round Tube Plate Fin Coils not include unit packaging. Approximate dimensions are provided primarily for shipping purposes.For exact dimensions and weights,refer to appropriate product data catalog. Lines and Filters Gas Line Size. 3/4 Condensate Drain Line Size. 3/4 Return Air Filter Type. Throwaway Return Air Filter Quantity- 4 Return Air Filter Size. 20 x 20 x 2 Unit Configuration Medium Static Option(Belt Drive) Al/Cu-Al/Cu -�- Base Electromechanical Controls Standard Packaging 2-Speed indoor fan motor controlled by VFD Warranty Information 1-Year parts(std.) 5-Year compressor parts(std.) 10-Year heat exchanger-Aluminized(std.) No optional warranties were selected. NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods. • Ordering Information Part Number Description Quantity 48TCDD12A2A6-0A0G0 Rooftop Unit 1 Base Unit Medium Static Option(Belt Drive) None 2 Speed Fan Controller (VFD) Packaged Rooftop Builder 1.39s Page 2 of 9 , /uu , 2ofS- 0c7Fo r , G�us 1 USES S � Al t -r MicroMetl 48TC Al2,48TC D12-48TC D14,48TC E12-48TC E14, 50TC Al2,50TC Part Number: SUBMITTAL 012 50TC D14, 50TC E12-50TC E140 4682-0303-JC2-9A930 FORM NO. 16342-1D 19/8/2015 Power Exhaust Power Exhaust Specifications • The MicroMetl power exhaust includes the fully modulating slide-in Carrier MicroMetl External Static CFM Performance Full Load Motor economizer and power exhaust module,shipped from the factory as , Units Part Numbers in.wg(2) ' 0.1 0.2 0.25 0.3 Amps(1) RPM HP Weight a completely assembled economizer and power exhaust hood. 48/50TCA/D08,A09; 1682-0203 s 208/230V 3PH 3.3/3.4 50TCQ D08-D09; • Blower motor includes automatic internal thermal protection. 4682.0203 460V 3PH 1.7 48/50HC D08-009; 290 • Blower motor includes adjustable pulley. 50HCQ 008-009: 3800 3300 3000 2700 1725 1 lbs • Transformer,contactor,and relay are factory mounted in a 48/50TF,TM,HJ 008-009; 5882-0203 575V 3PH 1.1 NEMA box. 50TFO 008.009;50HJQ 008-009 • ETL Listed 48/50TC A/D12,D14;50TCQ 012; 1682-0303 208/230V 3PH 6.6/6.6 • 48/SOHOD12, 4682-0303 460V 3PH 4200 4075 4000 3850 ® 1725 2 295 01 Blowers have prelubricated ball bearings with rubber isolators 48/SOTF,TM,HJ 012-014; lbs and a dynamically balanced wheel. 5OTFQ 012-014 5682-0303 575V 3PH 2.4 • Uses filter rack and filter access door shipped with HVAC unit. Note: • Gear driven damper blades for smooth operation. (1)For proper wire sizing to the unit add unit full load amps and MicroMetl power exhaust full load amps. • Modulating power exhaust (2)External static would be specific to each job and may include return air duct, dampers in return air and/or return grilles. option available. (3)Power exhaust connector on logic may be set to bring power exhaust on when outside air is fully open and return air is fully • Hardware cloth over closed.This may or may not be used with modulating power exhaust. relief damper (4)Follow all Codes,verify with local authority. Power Exhaust Part Numbers C tone. ® uam `682-0'03-JC-9A920 SinlgeAdj.Dry Bulb Single Speed •682-0.03-JC-DA920 Differential Dry Bulb Indoor Fan Units '682-0'03-JC-54920 Single Adjustable Enthalpy ,,.-=-2-7.,„.--.....„ '682-0.03-JC-DE920 Differential Enthalpy `� '682-0.03-JC2-9A920 SinlgeAdj.Dry Bulb Side View 2-Speed Indoor *682-0'03-JC2-DA920 Differential Dry Bulb Economizer motor Fan Unit •682-0"03-JC2-54920 Single Adjustable Enthalpy Drive gear attached to and harness '682-0'03-JC2-DE920 Differential Enthalpy the motor Access door •!: I Note: shipped with I111 4 r 'var driven 1. Unit fan speed is defined by character 17(Electrical Options)of Carrier HVAC unit ___„,,, dampers unit part number Filters29 7/8” The correct economizer must be ordered so the proper wiring harness is included for the RTU. Evaporatio2. RTU must be electromechnical ONLY to function with W7220 controller. coilRTU5 with Comfortlink,Premierlink,or RTU Open will not work/� _ ' 3. Contact factory for actuator only options for Comfortlink,Premierlink ° Ne I/, and RTU Open units r Access doors to blower - W7220 Controller for-JC-Series gli motor and power exhaust 0(Panel shipped with PE/Economizer) controls(opposite side) Control_ Access The-JC2-Series is installed in HVAC 0, 0 unit control panel 3 1/2" NOTE:If RTU has Hinged Panels Option(selected under Service Options),MicroMetl T Relief hinged filter access doors must be ordered. Please contact MicroMetl for pricing and -I - damper part number. The factory hinged filter access door cannot be used. Weight: 245 lbs THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MIROMETL'S WRITTEN CONSENT MicroMetl Corporation... Indianapolis Indiana — 1-800-662-4822, Sparks Nevada — 1-800-884-4662, Longview Texas — 1-903-248-4800 • • Certified Drawing for RTU-5 Project: —Untitled106 09/08/2015 Prepared By: 03:44PM NOTES. UNITED r o.BOO 4400 IHIS sOrER/Nr is THE PROPERTY or CARRIER CORIORIIIOR sue Iss1oX or THOSE D A•I Ncs 00 DacuNEXrs OUTDOOR 0 TECHNOLOGIES SYRACUSE.If ASS IS D[l IY(R[D UION iNE[NIR[55(ONO it ION tNAI Ix[ ROES NOT CONSIITUFE PART PERFORMANCE OR 1. DIMENSIONS ARE IN INCHES. DIMENSIONS UNIT COIL TYPE K H CON1EA r1 NTLI NOT B[DI SCLOS[0 OR USER NI iNWi CAAA ITR IN f 1 ARE IN (N 7ERS. d1 7/1 33 15 718 CARRIER /500/ CORPONAIION'S NRIIT[N CONSENT. ACCEPTANCE OF CONTRACT. 481C-A08 RTPF [10481 16581 [x031 2. CENTER OF GRAVITY 49 3/8 37 1/4 27 7/8 CONNECTION SIZES /81C-009 RTPF 112531 [9461 17081 A 1 3/8' 1351 DIA FIELD POWER SUPPLY HOLE 3, DIRECTION OF AIR FLOW 48 TC-Al2 RTPF 49 3/8 31 1/4 15 7/8 40-3/8 112531 19461 1403] [10261 8 2 I/2' [6/)DIA POWER SUPPLY KNOCKOUT 48TC-D08 RIPE 41 1/4 33 15 I/O __ C 1 3/4' 1571 DIA GAUGE ACCESS PLUG 170481 16581 14031 , 49 3/8 31 1/4 15 1/8 D 1/8' 1221 DIA FIELD CONTROL WIRING HOLE /81C-D09 RIPE 172531 19461 14031 E 3/4'-11 NPT CONDENSATE DRAIN 181C-D12 RTPF 49 3/8 31 1/4 15 1/8 ECONOMIZER HOOD 20.7// [12531 1946] 14031 IOPTIONALI 1 F I/4'-14 NPT GAS CONNECTION 48TC-DOB NC HN IIECTION (/1 33 23 G 2/• [511NDIA PT G APOWER S NSUPPLY KNOCK-OUT 110481 16581 0584.2] 4810-812 MCHM 49 3/8 31 1/4 Ii . • • [(0531 09161 [279.11 I I THRU-THE-BASE CHART (FIELD INSTI RTPF -ROUND TUBE, PLATE FIN (COPPER/ALUM( ' NOM -NOVATION(ALUM/ALUM) • ///7%^\\\\\ _ _ C THESE HOLES REOU IAED FOR USE WITH ACCP KITS. ���II/I//I/ 1����� 36.3/8 12-5/8 CRBTNPWROD4A01:GAS THRU CURB [9251 [3211 CRBTNPWAOOQA01:GAS THRU BASEPAN RETURN AIR RETURN 1\\\\`�®�///�� n I ( AIR NC0ITHREADED WIRE REO'D(MAX.)HOLE 1 CONDUIT SIZE USE SIZES MAL .. 11 e w 1/2' ACC. 7/8' 122.21 FILTER ACCESS PANEL I X I/O' 246 7/e' 122 21 • (TOOL-LESS) E SATE / \ CNNOPENANE Y 11/1" 1002,0011 POWER 1 3/4' [4/.11 DRAIN OPENING 28.3/1 • CONDENSER // ��1Ni IN BASEPAx 17311 37.5/8 40-3/8 y 2 R (004)3/4'FPT GAS 1 3/4. 111,11 COIL iTUAV1Z. ) I,- SUPPLY 19551 (10271 I�IIP i[C:�\m/)�lllllillll K SEE THRU AIR SUPPLY 10021 PROVIDES 3/4' FPT THRU CURB INDOOR COIL f1.728VNOW,'.��/�///DNI ,Y THE BASE AIR FLANGE d FITTING. HOLE SIZE: 2' 150.81 ACCESS PANEL TAIL '�` .'.�,,/�A� CHART • BACK '0'4691 8 16 via • 116911412] 03551 71 I -_ i �!I �1 THRU-THE-BASE CHART (FIOP1. 12707 FOR•THRU-THE-BASEPAN'FACTORY OPTION, LTU ,I ��R Xf C11Z:1� I - r FITTINGS FOR ONLY A. Y. 6 1 ARE PROVIDED. R • i FOR BELOW LISTED MODELS. A FIELD L 6.1/4 SUPPLIED I/O'ADAPTER IS REOUIRED d 11591 BETWEEN BASE PAN FITTING AND GAS VALVE. 29-5/8 11001 FLUE 3.1/1 4SHCO.SR08 [1511 HOOD 7/ 1831 13561 • TOP 25-v2 t H [6411 1.1/4 4-S/8 1321 11-7/8 -- 13021 11181 9 i __ I ELECTRICAL CONTROL BOA • FILTER DISCONNECT ACCESS PANEL • LOCATION E SAD. CONDENSER B. :�II CONDENSATE • COIL 0 I DRAIN INDOOR BLOWER K __ 7 OPifONAL ® ACCESS - RETURN _ OPTIONAL ,, FACTORY AIA FACTORY INSTALLED i , OUTSIDE INSTALLED 27•718 DISCONNECT 21.3/° AIR CONVENIENCE I IP 11091 • F e4,--HANDLE 13.1/8 C [7061 • 26 OUTLET C7 L [1711 SUPPLY AIR \ 16591 44. b I HANDLE�= / + ! I 1 --_ U 6-5/8 I, + 11681 0/511 8�- =i18 T ;100 I I I I : : 00� 015n 3-3/1 �- 1 6-5/8 L 7 t t 4-3/8 1951 59.1/2 [TT [2141 11171 2.5/8 115101 TTP 31 12141 [1611 39-2/8 [1711 01551 19401 42-3/8-� CURB _ LEFT WIDTH 82278] AIR 4 110751 * RETURN RELIEFBAROME W FRONT RIGHT SHEET DATE SDP[RC[0[D 48TC 08-12 SINGLE ZONE ELECTRICAL REY 1 OF 2 03-08-10 11-24-08 COOLING WITH GAS HEAT 48TM500985 F Packaged Rooftop Builder 1.39s Page 3 of 9 Certified Drawing for RTU-5 Project: -Untitled106 09/08/2015 Prepared By: 03:44PM ON UCTEOLOGIES P.O 8 D+.8x1d C0(s Pawxr IsI rom REgUR41q sq1 Rxs R[DMGOR 1 STD. UNIT CORNER CORNER CORNER CORNER CARRIER 13221 toroRATION'S(IIltcONSE.T.OUTDOOR C.G. .UNIT WEIGHTWEIGHT WEIGHT(01 WEIGHT (U WEIGHT (D) COIL TYPE LBS. KG. LBS. KG. IBS. KG. LBS. NG. LBS. NG. K Y 2 48TC-A08 RTPF 780 354 178 B1 158 12 209 95 236 107 41 1/2 110541 33 7/8(8601 20 1/2 15211 R+R STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING. FOR OTHER OPTIONS AND ACCESSORIES. REFER TO THE PRODUCT DATA CATALOG. 481C-409 RTPF 920 418 212 96 183 83 243 110 282 128 40 7/8(10381 34 18641 23 1/8(5871 481C-Al2 RTPF 930 422 216 98 196 89 247 112 272 123.5 42[10611 33 1/8(8411 24 1/4 [6161 ' 481C-D08 RIPE 835 379 164 14,5 170 77.2 255 115.8 246 111.7 44 7/8(11401 35 5/8(9051 19 3/8(4921 481C.D09 RIFF 930 422 228 103.5 187 85 232 105.3 283 128.5 39 3/4(10101 32 7/8(8351 18 5/8(4731 4810.012' RIFF 940 421 231 104.9 189 85.8 234 106.2 286 129 8 39 3/4(10101 33 18381 18 1/2(4701 48TC-D08 MCHN 805 365.5 160 72.6 153 69.5 240 109 260 118 43[10921 36 3/8(9241 20 3/8(517.71 48TC.D12 MCHY 895 406.3 185 84 176 79.9 260 118 .274 124.4 42 7/8[10891 35 1/2 (9021 22 7/8(581) . RTPF •ROUND TUBE. PLATE FIN (COPPER/ALUM) CORNER A CORNER B NCH •NOVATION(ALUM/ALUM( To,.v .w))42. • L, .I; -i lIR1�i',lliiiii(ia �a CORNER D ILI CORNER C TOP N • s 1 • µ' .• . 2 kr. 1rlooo � . ..- .=, : 00� FRONT MEI DATE 40)0800804 48TC 08-12 SINGLE ZONE ELECTRICAL 8[0 2OF2 03-08-10 11-24-08 COOLING WITH GAS HEAT 48TM500985 F • • Packaged Rooftop Builder 1.39s • Page 4 of 9 Certified Drawing for RTU-5 Project: -Untitled106 09/08/2015 Prepared By: 03:44PM Service Clearance > ':4' • C11247 LOCATION DIMENSION CONDITION 48-In(1219 mm) •Unit disconnect Is mounted on panel 36-in(914 mm) •If dimension-13 Is 12-in(305 mm) A 18-In(457 mm) •No disconnect,convenience outlet option •Recommended service clearance(use electric screwdriver) 12-In(305 mm) •Minimum clearance(use manual ratchet screwdriver) 36-In(914 mm) •Unit has economizer B 12-In(305 mm) •If dimension-A Is 36-in(914 mm) Special •Check for sources of flue products within 10-ft of unit fresh air Intake hood C 36-In(914 mm) •Side condensate drain is used 18-In(457 mm) •Minimum clearance 48-in(1219 mm) •No flue discharge accessoryinstalled,surface is combustible material 42-in(1067 mm) •Surface behind servicer is grounded(e.g.,metal,masonry wall,another unit) D 36-in(914 mm) •Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass) Special •Check for adjacent units or building fresh air intakes within 10-ft of this unit's flue outlet NOTE:Unit not designed to have overhead obstruction.Contact Application Engineering for guidance on any application planning overhead obstruction or vertical clearances. aussa s.ca Packaged Rooftop Builder 1.39s Page 5 of 9 Performance Summary For RTU-5 Project: —Untitled106 09/08/2015 Prepared By: 03:44PM Part Number:48TCDD12A2A6-0A0GO ARI EER. 11.10 IEER. 12.8 Base Unit Dimensions Unit Length• 88.1 in Unit Width. 59.5 in •Unit Height. 49.4 in Operating Weight Base Unit Weight. • 940 lb Medium Static Option (Belt Drive). 15 lb 2 Speed Fan Controller (VFD)• 20 lb Total Operating Weight. 975 lb Unit Unit Voltage-Phase-Hertz. 460-3-60 Air Discharge. Vertical Fan Drive Type• Belt Actual Airflow. 4000 CFM Site Altitude. 0 ft Cooling Performance Condenser Entering Air DB. 95.0 F Evaporator Entering Air DB• 80.0 F Evaporator Entering Air WB. 67.0 F Entering Air Enthalpy. 31.44 BTU/lb Evaporator Leaving Air DB• 57.7 F Evaporator Leaving Air WB• 57.2 F Evaporator Leaving Air Enthalpy. 24.54 BTU/Ib Gross Cooling Capacity. 124.10 MBH Gross Sensible Capacity. 96.20 MBH Compressor Power Input- 8.90 kW Coil Bypass Factor 0.046 Heating Performance Heating Airflow. 4000 CFM Entering Air Temp• 70.0 F Leaving Air Temp• 104.3 F • Gas Heating Input Capacity. 120.0/180.0 MBH Gas Heating Output Capacity- 98.0/148.0 MBH Temperature Rise• 34.3 F Supply Fan External Static Pressure. 1.00 in wg Fan RPM• 993 Fan Power 2.67 BHP NOTE• Selected IFM RPM Range: 838-1084 Electrical Data Voltage Range. 414-506 Compressor#1 RLA• 7.7 Compressor#1 LRA• 52 Compressor#2 RLA• • 7.7 Compressor#2 LRA. 52 Indoor Fan Motor Type. MED Indoor Fan Motor FLA• 4.9 Combustion Fan Motor FLA(ea). 0.25 Power Supply MCA• 24 Packaged Rooftop Builder 1.39s Page 6 of 9 Performance Summary For RTU-5 Project: -Untitled106 09/08/2015 Prepared By: 03:44PM Power Supply MOCP(Fuse or HACR). 30 Disconnect Size FLA- 25 Disconnect Size LRA- 147 _ Electrical Convenience Outlet- None Outdoor Fan [Qty/FLA(ea)]. 2 10.8 Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage - Acoustics Sound Power Levels, db re 10E-12 Watts Discharge Inlet Outdoor 63 Hz 98.0 94.7 89.0 125 Hz 94.2 87.6 83.1 250 Hz 80.9 72.6 80.5 500 Hz 74.8 68.0 78.5 1000 Hz 71.1 65.7 75.5 2000 Hz 68.6 61.5 71.6 4000 Hz 71.8 61.7 69.6 8000 Hz 73.5 60.0 69.3 A-Weighted 82.3 75.5 82.0 Advanced Acoustics S F 0 r�+ s I �0 n 0 O Advanced Accoustics Parameters 1. Unit height above ground- 30.0 ft 2. Horizontal distance from unit to receiver 50.0 ft 3. Receiver height above ground- 5.7 ft 4. Height of obstruction- 0.0 ft 5. Horizontal distance from obstruction to receiver 0.0 ft 6. Horizontal distance from unit to obstruction- 0.0 ft • Detailed Acoustics Information Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 89.0 83.1 80.5 78.5 75.5_71.6,69.6 69.3 91.0 Lw B 62.8 67.0 71.9 75.3 75.5 72.8 70.6 68.2 81.1 LwA C 56.6 50.7 48.1 46.1 43.1_39.2 37.2 36.9 58.6 Lp D 30.4 34.6 39.5 42.9 43.1 40.4 38.2 35.8 48.7 LpA Legend A Sound Power Levels at Unit's Acoustic Center, Lw B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA Packaged Rooftop Builder 1.39s Page 7 of 9 Performance Summary For RTU-5 Project: —Untitled106 09/08/2015 Prepared By: 03:44PM C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be . appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. FanCurve - i N`a�°I�rv' 16 c\ \ i ci)14 \\ , \ \ • 12 - \ 4) \ \ \ 11) /gx RP1G1 \ \ � Gs _ N \ d \ \ \ .aIBHP— „,..XEFIti \ \ C4 ____WovI \ 400PP 02 \ \ \ \ \ 3.0o �2.00BHP _ (0. BHP 0..56H�P ,. NP 1.50BFP� 03 1 1 1 1 1 1 1 1 1 1 11 1 111 1 l I.1 1 1 I V` 1\1 1 (\I I 1 I . I I 1 QO C6 12 18 24 30 36 42 48 54 Airflow(CFM-thousands) RPM=993 BHP=2.67 MaximumRPM=1084 MaximumBHP=4.70 Note:Please contactapplicationengineeringforselectionsoutsidetheshadedregion. SC-SystemClwe RP-RatedPoint Packaged Rooftop Builder 1.39s Page 8 of 9 • Unit Feature Sheet for RTU-5 Project: —Untitled106 09/08/2015 Prepared By: 03:44PM Carrie WeatherMaker° — 48TC PACKAGED ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS 3,4,5,6,7.5,8.5,10,12.5,15 TONS STANDARD FEATURES INCLUDE: • Puron(R-410A)HFC efigerard ! � •ASHRAE 90.1 sors wiccmpflnt • Saalloompressorswithimtemslbnebrentand otierbsdprotecton ® moi • Single-stage000llngca,pe yonntmfon04-12 models _ •Two-stage cooling capacity control au'08-16models _ I I •SEER'supto13.0,EER'supto11.1and IEER'supto11.2 . - •Acutrolrr refrigerant metering system • Exdu sive nonrarroaae composite condensate penin acconatroe with ASHRAE Standard 62.sloping design.side oroenterdrein • • Standard ccofing operation up to 115'F{46`C)and dawn to 413•F WC) • -down to 25'F(-4°C)nth winter s1ert'ka. • Pre-paintedexteriorpnnels and primer-coated interiorpanele tested to Put, - 500 hours salt spray protection • Fully insulated cabinet ' r_ • Exclusive IGC solid-state control for on-bostdiagnastssuithLED error code designation bumercorrtmllogioand ene.vysaving indoor Ifan motor delay —�, • Low NOD models that meet Callomia Air Ctualdy Management OpbOA3I Louvered Hail Guard Shown Induced draftg e s hest combustion design • Redundant gasvalvesetth up to tea stagesoihesting • Low pressure and high pressure switch protected. ASHRAE MAINTENANCE FEATURES: ® • Aooess panels with essygnp handles /l l Puron. • Innovative easystarting,no-strip smzw sonuraaccess panels •Two-inch disposable return airrs and Tool-less fiter access door COMPLIANT • Direct Drive ECM on 3 to 5 ton(-5 voltage only)rnodels end belt drive evaporator-fan motor and coley combinationsavaltabl on all models • New terminal board faclttating simple safetycrcuit troubleshooting and WEATHERMAKER SERIES simplfredcontrol box arrange/mot V1'eatherPlaker(48TC)units are one-piece gas heating,electric • Exclusive IGC sold-state -boarddiagnast�wih LED error code designation,bumerccntrol logic and energy saving indoor cooling units that are pre-wired and charged with Puron fan motor delay. (R-410)refrigerant. They are factory tested in both heating and cooling modes, and rated in accordance with AHRI INSTALLATION FEATURES: Standards 2101240 (04-06 sizes) and 340/360 (07-16 sizes). • Thru-the-battompayee/entry capabiray WeatherMatcer units are designed in accordance with UL • Single poirtgas and electric connections Standard 1995,and listed by the Underwriters'Laboratories. • Full perimeter base rat with butt-inrgging adapters and fork slats • Field convertible fmmvertxal to horumntalairflowfar stab mounting. (16 size models require field installed suppfyductoover). Approved and certified by: STANDARD WARRANTY: • 10-yearheatexohanger-15-year stainless steeloption r.^•.• CERfIHEO. • s-ye8rcompressor • -ye F C (1US Use a•aAlrwo.ree• • 3-year parts on NovationCondenseroois-whereavailable ru i, .awns• • Many optional upgrades also available nwA•n.w'• "O0'tlnFYvtriniueOPTIONS INCLUDE BUT ARE NOT LIMITED TO: a con-tato a...I CO ewa 5'a • PremierLinkn'and RTU Open Multi-Protocol DDC Controls ""•`"P0C'^"° • Supply and Return Air Smote Detectors,high stats motors C US • Louvered condenserootguards • Economizer,disconnect end convenience outlet options • Stainless Steel heat each rang eroption • Corrosion resistant cot coating. Certified to ISO 9001 • Hurrad'� dffs rc adaptive dehurruationsystem available onal models with RTPF condense/cols-Motor Master I oontratlrinduded • tinged access panels Fara cr4nis=aroma an]aJrsxre re?1 a re Pto5ro•Datt Cattzpsyla Packaged Rooftop Builder 1.39s Page 9 of 9