Report (5) tueezots-006 ? 7 RECEIVED -n5',-)- ca lJar7` o� ENWSTRUCTURAL ENGINEERS OCT 12 2015 Engineers Northwest Inc., P.S. CITY OF MAO BUILDING DIVISION October 9, 2015 T.E., INC. 830 North Riverside Drive, #200 Renton, WA 98057 Attn: Mr. Paal Ryan Re: Costco Wholesale -Tigard, OR New HVAC Replacement Units Paal, Engineers Northwest, Inc. has reviewed your mechanical drawings ME-1 and ME-2 dated July 2015 for the HVAC replacement units for the building referenced above. We find the existing roof framing structurally adequate according to IBC building code, Section 3403 allowances. If you have any questions regarding this letter, please feel free to contact us. Sincerely, ENGINE 'S NORTHWE , INC., P.S. Willy Chen, P. ., S.E. Vice President WC:bs ENW Job No.93085024 We get buildings built. • • 9725 Third Ave NE,Suite 207•Seattle,WA 98115 • 206.525.7560 • fax 206.522.6698 www.engineerenw.com TWINE Submittal Prepared For: Date:July 16, 2015 Costco, TEl Job Name: Costco Tigard OR MS Rx Repl 7855 SW DARTMOUTH TIGARD, OR 97223 Trane U.S. Inc. dba Trane is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 2 Packaged Gas/Electric Rooftop Units 1 Split System Air Conditioning Units (Small) The attached information describes the equipment we propose to furnish for this project,and is submitted for your approval. Trey Clemmer Trane 2333 158th Court NE Bellevue, WA 98008 Phone: (425) 586-1673 Cell: (425) 213-9111 Fax: (425) 643-4314 J:IJOBS11176192356121Costco Tigard OR MS Rx Repl Submittal July 16, 2015.doc Table Of Contents Product Summary 1 Packaged Gas/Electric Rooftop Units (Item Al) 3 Tag Data 3 Product Data 3 Performance Data 3 • Mechanical Specifications 5 Unit Dimensions 8 Weight, Clearance&Rigging Diagram 10 Accessory 12 Split System Air Conditioning Units (Small)(Item B1) 14 Tag Data 14 Product Data 14 Performance Data 14 Mechanical Specifications 16 Unit Dimensions 18 Weight, Clearance&Rigging Diagram 22 Accessory 23 Field Wiring 24 Field Installed Options-Part/Order Number Summary 25 Split System Air Conditioning Units(Small) 25 Costco Tigard OR MS Rx Repl July 16, 2015 Tag Data - Packaged Gas/Electric Rooftop Units (Qty: 2) Item Tag(s) Qty Description Model Number Al AC-7, AC-8 2 25 Ton Main Sales YHD300G4RXA--KAC1C2B00002B00000000000000 Product Data - Packaged Gas/Electric Rooftop Units Item: Al Qty: 2 Tag(s): AC-7, AC-8 Gas/Electric High efficiency Downflow 25 Ton 460/60/3 Reliatel Gas Heat- SS Ht Ex - Low Low Leak Economizer, Dry Bulb w/ Barometric Relief Single zone VAV standard w shaft ground Hinged panels/2" Pleated Filters Mery 8 Standard condenser coil with hail guard Through the base electric/gas Unit Mounted Circuit Breaker Powered convenience outlet Fan failure switch Economizer Fault Detection Diagnostics 1st Year Labor warranty Performance Data - Packaged Gas/Electric Rooftop Units Tags AC-7, AC-8 Design Airflow (cfm) 9600 Cooling Entering Dry Bulb (F) 81.00 • Cooling Entering Wet Bulb (F) 66.00 Ent Air Rel Humidity (%) 45.30 Ambient Temp (F) 88.60 Cooling Leaving Unit DB (F) 59.94 Cooling Leaving Unit WB (F) 56.69 Gross Total Capacity (MBh) 300.92 Gross Sensible Capacity (MBh) 246.75 Gross Latent Capacity (MBh) 54.17 Net Total Capacity (MBh) 276.55 Net Sensible Capacity (MBh) 222.38 Net Sensible Heat Ratio (Number) 0.80 Heating LAT (F) 19.49 Heating Temp Rise (F) 19.49 Output Htg Capacity (MBh) 203.00 Output Htg Capacity w/Fan (MBh) 227.37 Design ESP (in H2O) 0.500 Component SP Add (in H2O) 0.777 Field Supplied Drive Kit Required High Static Drive Kit Indoor Mtr. Operating Power(bhp) 7.74 Indoor RPM (rpm) 872 Indoor Motor Power (kW) 5.76 Outdoor Motor Power (kW) 2.00 Compressor Power (kW) 19.72 System Power (kW) 27.48 IPLV @ AHRI (IPLV) 13.0 MCA (A) 56.00 MOP (A) 70.00 Compressor 1 RLA (A) 21.20 Compressor 2 RLA (A) 12.20 Condenser Fan FLA (A) 2.90 FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 3 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Tags AC-7, AC-8 Evaporator Fan FLA(A) 11.00 Evaporator Face Area (sq ft) 31.42 Evaporator Face Velocity (ft/min) 306 Evaporator Fin Spacing (Per Foot) 180 Evaporator Rows ( ) 4 Min. Unit Operating Weight(Ib) 2017.0 Max Unit Operating Weight(Ib) 2440.0 Fan Motor Heat(MBh) 24.37 Evap Coil Leav Air Temp (DB) (F) 57.20 Evap Coil Leav Air Temp (WB) (F) 55.61 Dew Point Temp (F) 54.54 Rated capacity (AHRI) (MBh) 272.00 Exhaust fan power(kW) 0.56 Refrig charge (HFC-410A) -ckt 1 (Ib) 14.7 Refrig charge (HFC-410A) -ckt 2 (Ib) 8.3 ASHRAE 90.1 Yes Saturated Suction Temp Circuit 1 (F) 52.49 Saturated Discharge Temp Circuit 1 (F) 115.56 Saturated Suction Temp Circuit 2 (F) 48.67 Saturated Discharge Temp Circuit 2 (F) 120.49 IEER Rating () 13.00 EER @ AHRI Conditions (EER) 10.6 Total Static Pressure (in H2O) 1.277 FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 4 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Mechanical Specifications - Packaged Gas/Electric Rooftop Units Item: Al Qty: 2 Tag(s): AC-7, AC-8 General The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with AHRI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 3rd Edition. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than three screws to remove. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch, 1 pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material. The downflow unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8 inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting. Unit Top The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage. Filters Two inch standard filters shall be factory supplied on all units. Optional two inch pleated media filters shall be available. Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models shall have crankcase heaters, phase monitors and low and high pressure control as standard. Crankcase Heaters These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models. Refrigerant Circuits Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. Evaporator and Condenser Coils Microchannel coils will be burst tested by the manufacturer. Internally finned, 5/16(, copper tubes mechanically bonded to a configured aluminum plate fin shall be standard for evaporator coils. Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 psig and pressure tested to 450 psig. Sloped condensate drain pans are standard. Gas Heating Section The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative pressure gas valve shall be used on standard furnaces and a pressure switch on furnaces with modulating heat that requires blower operation to initiate gas flow. On an initial call for heat, the FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 5 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 combustion blower shall purge the heat exchanger 45 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NOx emissions. The 12%-25 tons shall have two stage heating (Gas/Electric Only). Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection. Indoor Fan Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an adjustable idler-arm assembly for quick-adjustment of fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Single Zone VAV - One Zone Variable Air Volume Mode Single zone VAV is designed for use in single zone applications like gymnasiums, auditoriums, manufacturing facilities, 9 9 9 PP 9Y 9 retail box stores, and any large open spaces, where there is a lot of diversity in the load profile. Single Zone VAV(SZ VAV) is an ideal replacement to yesterdays constant volume(CV)systems, by reducing operating costs while improving occupant comfort. SZ VAV systems combine Trane application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition. Trane algorithms meet/exceed ASHRAE 90.1-2010, SZ VAV energy-saving recommendations, and those of CA Title 24. The result is an optimized balance between zone temperature control and system energy savings. Depending on your specific application, energy savings can be as much as 20+%. Note: Building system modeling in energy simulation software like TRACE is recommended to evaluate performance improvements for your application. SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides the simplest and fastest commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control modules, logic and sensors are factory installed, and tested to assure the highest quality and most reliable system available. This means no special programming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need to be installed in the field. Single zone VAV is a quick and simple solution for many applications and is available from your most trusted rooftop VAV system solution provider-Trane. Variable Frequency Drive Variable Frequency Drives are factory installed and tested to provide supply fan motor speed Modulation. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass if required. Bypass control will simply provide full nominal airflow in the event of drive failure. Bypass mode is indicated in the unit wiring manual. Modulating gas heat models with SZVAV allow tighter space temperature control with less temperature swing. Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. High Pressure Cutout This option is offered for units that do not have High Pressure cutout as standard. Low Leak Economizer FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 6 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 This accessory meets low leak requirements for ASHRAE90.1, IECC, and Title 24 standards; Allows 100 percent outdoor air supply from 0-100 percent modulating dampers; Comes standard with Barometric Relief; can be paired with Powered exhaust for additional building evacuation; Can be paired with Fault Detection (FDD) to meet current mandatory Title 24 requirements; Dry Bulb; And, available for down flow applications. Fault Detection & Diagnostics (FDD) This offering meets the mandatory requirement of Title 24. This option provides detection of the following faults: Air temperature sensor failure/fault, not economizing when it should, Economizing when it should not, damper not modulating, and excessive outdoor air. The FDD System shall be certified by the Energy Commission as meeting the requirements. Discharge Line Thermostat A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with high pressure control. When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 VAC circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor. When the thermostat opens the fourth time, the ReliaTel control must be manually reset to resume operation on that stage. Stainless Steel Heat Exchanger Gas heat exchanger shall be of drum and tube design constructed from a minimum 304 Grade stainless steel. The stainless steel heat exchanger shall have a 10-year warranty as standard (Gas/ Electric Only). Tool-less Hail Guards Tool-less, hail protection quality coil guards are available for condenser coil protection. Hinged Access Doors Sheet metal hinges are available on the Filter/Evaporator Access Door and the Compressor/Control Access Door. This option is available on all downflow models. Two-Inch Pleated Filters Two inch pleated media filters shall be available on all models. Shaft Gounding Ring (FIYSHGR001,002A) 12.5-25 Ton Shaft grounding rings shall be factory installed on all VFD driven motors to provide a conductive discharge path away from the motor bearings to ground. Bearing Protection Ring shall be maintenance free circumferential ring of conductive micro fibers that discharges voltages to ground. Clogged Filter/Fan Failure Switch A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These indications will be registered with either a zone sensor with status indication lights or an Integrated Comfort System. Hinged Access Doors - Ultra High Sheet metal hinges are available on the Filter/Evaporator Access Door and the Compressor/Control Access Door. This option is available on all downflow models. FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 7 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Unit Dimensions - Packaged Gas/Electric Rooftop Units Item: Al Qty: 2 Tag(s): AC-7, AC-8 NOTES: 1.GAS CONNECTION PIPE SIZE 1/2" 2.THRU-THE-BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.(SELECTED OPTION:SEE ACCESSORY SHEET) . • • 1.. 3.VERIFY WEI DIMENSION INSTALLER GHT,DOCUMENTS CONNECTION,BEFORE AND INSTALLATION ALL WITH /==/2. X11 64 1/8" DOWNFLOW CONDENSATE DRAIN IN C ONN 1"NPT 6411/16" , GAS CONNECTION(SEE NOTE 1) I • • 121 11/16" 33 3/16" 15/16" 7/8"DIA.HOLE • 8 1 �� (UNIT CONTROL WIRE) �/ 2 11/16" 84 3/16" '-3"DIA.HOLE (UNIT POWER WIRE) PACKAGED GAS/ELECTRIC-DOWNFLOW ISOMETRIC DRAWING 4 1/4" 1 15/16"— ------2B 3/4" 26 7/16" j r — ---1 4 1/4"— sittt knt011 RETURN SUPPLY 68 11/16" 76 5/16" 0 • PACKAGED GAS/ELECTRIC-DOWNFLOW PLAN VIEW DRAWING FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 8 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Unit Dimensions - Packaged Gas/Electric Rooftop Units Item: Al Qty: 2 Tag(s): AC-7, AC-8 ELECTRICAL / GENERAL DATA GENERAL PERFORMANCE Standard Motor (1)(3) Model(Ton): YHD300G(25.0) Minimum Circuit Ampacity: '56.0 Unit Operating Voltage Range: '414-506 Maximum Fuse Size: 70.0 • Unit Primary Voltage: 460 Maximum(HACR)Circuit Breaker: 70.0 Unit Secondary Voltage: - Unit Hertz: 60 Standard Oversized Motor (1)(4) Accessory Oversized Motor (1)(4) Unit Phase: 3 . Minimum Circuit Ampacity Minimum Circuit Ampacity: Maximum Fuse Size: Maximum Fuse Size: EER: (5) '10.6 Maximum(HACR)Circuit Breaker Maximum(HACR)Circuit Breaker: GAS HEATING COMPRESSOR Heating Models: 'Low Circuit#1/2 Heating and 1 Stage Input(BtuIti) 250,000/175,000 Heating and 1 Stage Output(Btu/h): 203,000/142,000 Number: '2 Horsepower 12.8/6.9 Min./Max.Gas Input- Phase: 3 Pressure Natural or LP(in w.c): 2.5/14.0 Rated Load Amps: 21.2/12.2 Gas Connection Pipe Size: 1/2" Locked Rotor Amps: 158.0/100.0 INDOOR MOTOR Standard Motor Standard Oversized Motor (4) Accessory Oversized Motor (4) Number (3) '1 Number Number Horsepower 7.5 Horsepower Horsepower: Motor Speed(RPM): 3,450 Motor Speed(RPM): Motor Speed(RPM): Phase: 3 Phase: Phase: Full Load Amps: 11.0 Full Load Amps: Full Load Amps: Locked Rotor Amps: 74.0 Locked Rotor Amps: Locked Rotor Amps: OUTDOOR MOTOR POWER EXHAUST COMBUSTION BLOWER (Field Installed Power Exhaust) MOTOR Number '2 Horsepower 'N/A (Gas-Fired Heating only) Horsepower: 1.0 Motor Speed(RPM): N/A Horsepower: '0.1 Motor speed(RPM): 1,125 Phase: N/A Motor Speed(RPM): 3500/2800 Phase: 1 Full ll Load Amps: N/A Phase: 1 Full Load Amps: 2.9 Locked Rotor Amps: N/A Full Load Amps: 1 0.8 Locked Rotor Amps: 5.8 Locked Rotor Amps: 2.00 FILTER REFRIGERANT 121 Circuit#1/2 Type: Throwaway Type: 'R-410 Furnished: Yes Factory Charge Number 8/4 Circuit#1/2: 14.2 lb/8.2 lb Recommended Size: 20"x20"x2"/20"x16'k2 NOTES: - 1. Maximum(HACR)Circuit Breaker sizing is for installations in the United States only. 2. Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 3. Value include Standard Motor. 4. Value include Oversized Motor 5. EER is rated at AHRI conditions and in accordance with DOE test procedures. FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 9 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Weight, Clearance & Rigging Diagram - Packaged Gas/Electric Rooftop Units Item: Al Qty: 2 Tag(s): AC-7, AC-8 . IIII‘ CLEARANCE 68" (1727 2mm) • CLEARANCE 36" CLEARANCE FROM THE (914.4mm) TOP OF UNIT 72" (1828.8mm) r r o CLEARANCE 60" e (1524mm) P CLEARANCE 48" . tie a B DOWNFLOW-PACKAGED GAS/ELECTRIC CLEARANCE UNIT OUTLINE 414/0 k% ROOF OPENING 76 1/2" . 81" DOWNFLOW-PACKAGED GAS/ELECTRIC ROOF OPENING CLEARANCE FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 10 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Weight, Clearance & Rigging Diagram - Packaged Gas/Electric Rooftop Units Item: Al Qty: 2 Tag(s): AC-7, AC-8 INSTALLED OPTIONS NET WEIGHT DATA . Accessory Accessory Economizer 250.0 lb Motorized Outside Air Damper 117C)n Manual Outside air Damper Oversized Motor • High Static Drive Thru the Base Electrical 23.0 lb ��((r i�,,-,,\�X11 I/�I 1111`.s,,,.,,,,I�� Wt Unit Mounted Circuit Breaker 10.0 lb Unit Mounted Disconnect 0 n 1 Power Exhaust 111111// A\���� Hinged Doors 27.0 lb \\\' /I Zone Sensor ( LPG Conversion Kit B W v \‘‘,.7., Powered Convenience Outlet Roof Curb 38.0 lb CORNER WEIGHT BASE UNIT WEIGHTS CORNER WEIGHTS CENTER OF GRAVITY SHIPPING NET OAO © 0 E F 2684.0 lb 2207.0 lb 702.0 lb 579.0 lb 422.0 lb 507 0 lb 57" 35" NOTE: 1.CORNER WEIGHTS ARE GIVEN FOR INFORMATION ONLY - 2.TO ESTIMATE SHIPPING WEIGHT OF OPTION/ACCESSORIES ADD 5 LBS TO NET WEIGHT. 3.NET WEIGHT OF OPTIONAL ACCESSORIES SHOULD BE ADD TO UNIT WEIGHT WHEN ORDERING FACTORY INSTALLED ACCESSORIES. 4.WEIGHTS FOR OPTIONS NOT LISTED ARE<5 LBS. 5.WEIGHT ARE OF BASE UNIT ONLY FOR TOTAL WEIGHT.10 DIGIT FACTORY INSTALLED • • OPTION(ECONOMIZER AND/OR OVERSIZED MOTOR OR FIOP/ACCESSORY WEIGHT • MUST BE ADDED. • • • • . I � ..,.i..�����1\ j j , NNNNNN'NiN,: „„„/ o Ti RIGGING AND CENTER OF GRAVITY FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 11 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Accessory - Packaged Gas/Electric Rooftop Units Item: Al Qty: 2 Tag(s): AC-7, AC-8 c J o¢ _ 0 U U Z N W (00< n' <<, X11 �����, 1 0 W - U C7 C7 `\ 2 i O w ■ (V co } II o w r z cn zN z¢w W CO Q rn N N J Z Qza N o U Z W N�¢U FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 12 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16. 2015 Accessory - Packaged Gas/Electric Rooftop Units Item: Al Qty: 2 Tag(s): AC-7, AC-8 • il- th*Ati / fb M.\\ 01 / ft //// itzX liP1 \ 001 0 Z 0 U . W % } CC ° 0 W ,o) U 7 U -----± 0 O J u_ Z 0 0 / w . Q m a co cn w U U 7 --...._ J w z Q a o O W O O I uJ w N 2 0 Z 0 0 w FLD =Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 13 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Tag Data -Split System Air Conditioning Units (Small) (Qty: 1) Item Tag(s) Qty Description Model Number B1 OU/IU-1 1 1.5 - 5 Ton Unitary Split Systems ( 4TWA3036B4000-GAM5B0B06M-1S-0----00 SSC 0-0--0 Product Data - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 4TWA3 Heat Pump Outdoor Unit 3 Ton - Nominal Cooling Capacity Major Design Sequence 460 Volt 3 Phase 60 Hertz Good Multi-poise 4-way Better, Entry level Hi EFF, multispeed Major designs sequence 21.0" wide x 21.5" deep 3 Ton air handler Mid EFF Multi-speed Power Supply System Control Type Evaporator defrost control (Fld) Head pressure control (Fld) 3.60/4.80 kW Electric Heater with Ckt Brk for 208/240V 1 Phase 60 Hz (Fld) 1st Year labor warranty Performance Data - Split System Air Conditioning Units (Small) Tags OU/IU-1 Design clg outdoor DB (F) 88.10 • Cooling EDB (F) 80.00 Cooling EWB (F) 66.00 Rated gross capacity (AHRI) (Btuh) 36000.00 Clg net total capacity (Btuh) 37018.00 Clg net sensible capacity (Btuh) 28911.00 Clg net latent capacity (Btuh) 8106.00 Calc clg LDB (F) 57.30 Calc clg LWB (F) 55.60 SEER @ AHRI (btuh/watt) 15.00 EER @ AHRI (EER) 12.5 Cooling airflow (cfm) 1200 Min system airflow clg (cfm) 1050 Max system airflow clg (cfm) 1350 Min system airflow htg (cfm) 1050 Max system airflow htg (cfm) 1350 AHRI airflow(cfm) 1200 AHRI reference number( ) 7871297 Compressor power @ (specific Ambient) (W) 2366.0 Condenser fan power @ (specific SP) (W) 219.0 Supply fan power© (specified SP) (W) 295.0 ASHRAE 90.1 S6.4.1 compliant Yes Htg outdoor DB (F) 20.00 Heating airflow (cfm) 1200 Heating capacity @ 47F (Btuh) 34800.00 COP @ AHRI 47F (with Air Handler) (COP) 3.60 COP @ AHRI 17F (with Air Handler) (COP) 2.40 Heating capacity © 17F (Btuh) 21800.00 HSPF @ AHRI (btuh/watt) 8.20 Heating EDB (F) 65.00 Htg system net capacity (Btuh) 22810.00 Htg system LDB (F) 82.60 FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 14 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16, 2015 Tags OU/IU-1 AHRI high compressor power heating mode (W) 2318.0 AHRI low compressor pwer heating mode (W) 2147.0 AHRI condenser fan power heating mode (W) 219.0 AHRI supply fan power heating mode (W) 295.0 Blower capability 3.0 ton to 3.5 ton airflow 80 to 90 second blower off delay Not Required OD AHRI Model (Each) -1.00 • FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 15 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16, 2015 Mechanical Specifications - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 4TWA3 Heat Pump General Unit Shall be fully charged from the factory for matched indoor section and up to 180" of piping. This unit must be designed to operate at outdoor ambient temperatures as high as 115.0 F. Cooling capacities shall be matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit shall be UL listed. Exterior must be designed for outdoor application. 4TWA3 Heat Pump Casing Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Corrosion and weatherproof CMBP-G30 DuraTuff base. 4TWA3 Heat Pump Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. 4TWA3 Heat Pump Compressor The Climatuff compressor features internal over temperature and pressure protector and total dipped hermetic motor. Other features include: centrifugal oil pump, and low vibration and noise. 4TWA3 Heat Pump Low Ambient Cooling As manufactured, this unit has a cooling capability to 55.0 F. The addition of an evaporator defrost control permits operation to 40.0 F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30.0 F. 4TWA3 Heat Pump Refrigerant Controls Refrigeration system controls include condenser fan and compressor contactor. High and low pressure controls are inherent to the compressor. Another standard feature is the liquid line dryer. GAMS Air-Tite II cabinet 2% or less air leakage Precision applied -durable door seals Specially designed air seal around refrigerant, condensate and conduit connections Double wall foamed cabinet system R-4.2 insulating value No loose fiber design Smooth cleanable interior design Sweat eliminating design Composite foamed cabinet doors Water proof cabinet design Integrated horizontal drain pans Modular cabinet with " alien wrench "quick latch" design Multi-position up/down flow horizontal left/right Side return option Control board protection pocket built into cabinet wall Alert port to view control board codes without door removal 10 alert codes Low voltage terminal connection point Quarter turn phillips head door fasteners Vortica blower with polarized plug connections and integrated slide deck for easy removal Patented enhanced coil fin Dual refrigerant compatible as shipped Slide in electric heaters with polarized plug connections (sold as accessory) UVC light kit with safety switch and polarized plug connections (sold as accessory) Labeled panels and connections Molded in 1" standard filter rail High efficiency ECM motor Soft start fan motor operation Built in fan delay modes Maximum width of 23 1/2" Compact 20 13/16" depth with doors removed FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 16 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Two tone color Fused 24v power Safety door switch 1-year warranty 10-year warranty registered Optional extended warranty available Heater Section - 1 Phase Vertical Air Handler A compartment is provided in the blower section for field installation of supplementary heater. Polarized plugs are provided for making electrical connections to the air handler control box from the supplementary heater. Head Pressure Control Accessory The Head Pressure Control (BAYLOAM***) accessory is a low voltage (24 Volts ) electronic head pressure control that cycles the condenser fan motor based on liquid temperature. The addition of this field installed Head Pressure Control accessory permits cooling operation to 0 deg F [-17.8 deg C] providing that non-bleed TXV's, quick start components, and compressor crankcase heat are provided with the system when required. Head Pressure Control Controls fan motor(on/off) in response to outdoor ambient temperature in conjunction with liquid line temperature. Accessory provides unit cooling operation to outdoor temperatures of OF FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 17 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 , Unit Dimensions -Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 1 I 21 3/4" NOTES , 1.BADGE ROTATION WILL KEEP BRAND IN CORRECT POSITION. 2.NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. 1 1/2" o--14 3/8"--°5 15/16"o- 3.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION ] '` 4.GAMS AIR HANDLERS ARE ALL TWO PIECE CABINETS. .' I 5.SEE WEIGHT AND RIGGING PAGE FOR CONDENSATE DRAIN I I I CONFIGURATION 1 1 ti 1 21 5/16" 183/8" 0 I I I 4rP 1 1„: 1 1/2" 9 3/16" 3" 3/8"LIQUID LINE • I 1UL1 , IIIIIIMP - I 5 I,.i_:_H 1 7/8"GAS LINE SEE NOTE 1 CONDENSATE DRAIN 55 11/16" 11111IMINIEMIIIII 1 /2" • 45 1/2" 21 13/16" ❑ 24 13/16" • I 1 M• f 1 17 1/8" - 1 1/2" 1 1/2" -° - - - 3 3/16" I , 183/8" GAM5AOA36 AIR HANDLER UNIT DIMENSION DRAWING Lioll 1741111 i 1 1/2" FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 18 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 'ELECTRICAL/GENERAL DATA GENERAL (1)(2)(4) (I MOTOR Itl FILTERS (3) Model: 'GAM5A0B36M31SA Number 1 Type: Throwaway • Horsepower 0.5 Furnished: No Unit Primary Voltage: 208 Motor Speed(RPM): 1050 Number: 1 Unit Secondary Voltage: 230 Phase: 1 Recommended: 20'X20"x1" Unit Hertz: 60 Full Load Amps: 41 Unit Phase: 1 Locked Rotor Amps: STANDARD (5) REFRIGERANT Weights 230 Volt/208 Volt Type: 'R410 Net: 142.0 lb Minimum Circuit Ampacity: '5.0/5.0 REF.Line Connections Brazed Shipping: 150.0 lb Maximum Overload Protection: 15.0/15.0 Coupling or Conn.Size-Gas. 7/8" Coupling or Conn.Size-Liq.: 3/8" ELECTRIC HEAT 230 Volt/208 Volt NOTES: n 4.80kW/3.60kW Capacity Circuit#1: N/A 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A (an standard 210/240).refer tothesplit system outdoor unit product data guides for performance data. Capacity Circuit#3: 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: 1 3.Minimum filter size for horizontal applications will be based on airflow selection Phase: 1 and will be calculated as follows: low velocity filter:face area(sq.ft.)=cfm/300 20/17.30 high velocity filter face area ft.) cfm/500 Heater Amps Per Circuit Circuit#1: 9 Y (sq. ) Heater Amps Per Circuit Circuit#2: N/A 4.For customer ease of filter maintenance,it is recommended that a properly sized,remote filter and grille be Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the filter being used Minimum Circuit Ampacity Circuit#1: 30.0I27.0 5.Standard mca and mop without electric heat. Minimum Circuit Ampacity Circuit#2: N/A Minimum Circuit Ampacity Circuit#3: N/A Maximum Overload Protection Circuit#1: 30.0/30 Maximum Overload Protection Circuit#2: N/A Maximum Overload Protection Circuit#3: N/A FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 19 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 -37 1/4 UNIT DIMENSTIONS DIM-D I '3/4" I DIM-E I '3/8" \\\\\1II1III//%:'A. NOTES , III,. I/ �" `° 1.TOP DISCHARGE AREA SHOULD BE ����\ IIlfl //���� UNRESTRICTED FOR AT LEAST 60" , ;.i; ABOVE UNIT UNIT SHOULD BE PLACED SO ROOF SERVICE PANEL :-- -- RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, SEE NOTE 2 _- _ ,: 34 1/4" AND SHOULD BE AT LEAST 12"FROM WALL AND j __j ALL SURROUNDING SHRUBBERY ON TWO SIDES. / OTHER TWO SIDES UNRESTRICTED. � �� �. 2.ELECTRICAL AND REFRIGERANT COMPONENT ��/ /i' hhi n �� �� CLEARANCES PER PREVAILING CODES. 444. '•... _ SEE NOTE 1 ELECTRICAL __ SERVICE PANEL ' IMF—�'MC111 7/8"DIA.HOLE 20' LOW VOLTAGE ' .l�� 37 1/4" LIQUID LINE SERVICE VALVE,0 1 1/8"DIA.K.O.WITH "E"LD.FEMALE BRAZE 7/8"DIA.HOLE IN CONTROL 1" CONNECTION WITH 1/4"SAE III BOX BOTTOM FOR FLARE PRESSURE TAP FITTING. ELECTRICAL POWER SUPPLY Icy • s" 1Ili 8 1/4" � b i; i� 5 3/8„ �n!�■ ' ■�� ���� 0 .IMIIIMIE LIQUID LINE SERVICE VALVE, \ "E"I.D.FEMALE BRAZE 33/6 `GAS LINE 1/4"TURN BALL - CONNECTION WITH 1/4"SAE SERVICE VALVE,"D"I.D.FEMALE FLARE PRESSURE TAP FITTING. 3 7/8" I I BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. GAS LINE SERVICE VALVE, "D"I.D.FEMALE BRAZED CONNECTION WITH 1/4"SAE • FLARE PRESSURE TAP FITTING. FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 20 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16, 2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 'ELECTRICAL/GENERAL DATA 'GENERAL - POWER CONN. COMPRESSOR Model: '4TWA3036 Minimum Circuit Ampacity: 7.0 Number: '1 Operating Voltage: '414-506 Maximum Circuit Breaker: 15.0 Phase: 3 Unit Primary Voltage: 460 Minimum Protection Rating: 15.0 Rated Load Amps: 5.1 Unit Secondary Voltage - Locked Rotor Amps: 35.0 Unit Hertz: 60 Unit Phase: 3 OUTDOOR MOTOR NOTES: Number: 1 1.Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on Horsepower 0.20 AHRI Standard 210/240. Motor Speed(RPM): 825 2.Calculated in accordance with N.E.C.Use only HACR circuit breakers or fuses. Phase: 3.Standard line lengths-60'.Standard lift-60'Suction and Liquid line. Full Load Amps 0.6 For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0 Locked Rotor Amps: 4.•=15,20,25,30,40 and 50 foot lineset available. REFRIGERANT Type: R-410 Charge: 7.2 lb Line Size O.D.Gas: 3/4" 3/6" Line Size O.D.LIQ: C1 WEIGHT NET '264.0 lb SHIPPING 264.0 lb LLI C7 NOTES: C1.TOP DISCHARGE SHOULD BE UNRESTRICTED = FOR AT LEAST 60" ABOVE UNIT V7 C2.PLACE UNIT FROM WALL 0 C3.PLACE SHRUBBERY AT LEAST 12" C4 FROM UNIT ON TWO SIDES,OTHER SIDES UNRESTRICTED C4.PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT I Nilloafteummeimenumnin__ is C3 Pill C3 WEIGHT AND CLEARANCE FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 21 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Weight, Clearance & Rigging Diagram -Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 'fj' S 4� VERTICAL DOWNFLOW I I ( I a REFRIGERANT CONNECTION �� ! i DOWNFLOW CONDENSATE DRAIN Cr REFRIGERANT CONNECTION DOWNFLOW CONDENSATE DRAIN ni 04 1 : glamili '_ I In , I Q - REFRIGERANT CONNECTION VERTICAL UPFLOW IIIEWAIIIIIIIMIIIIII Will El :44:r.n E i <=oI REFRIGERANT CONNECTION �� HORIZONTAL LEFT FLOW Q %MN • DOWNFLOW CONDENSATE DRAIN El=> ! It I , C ni HORIZONTAL RIGHT FLOW DOWNFLOW CONDENSATE DRAIN NOTES MINIMUM UNIT CLEARANCE TABLE 1 NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. TO COMBUSTIBLE SERVICE CLEARANCE • 2.BADGE ROTATION WILL BRAND IN CORRECT POSITION. MATERIALS(REQUIRED) (RECOMMENDED) SIDE 0 2" FRONT 0 21" BACK 0 0 INLET DUCT 0 0 OUTLET DUCT 0 0 CLEARANCE NOTES: •1"FOR THE FIRST 3 FT.OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALED EXCEPT MODELS BAYHTR1405,1408,AND 1410 ARE APPROVED FOR 0"PLEMUM AND DUCT CLEARANCE IN THE UPFLOW CONFIGURATION ONLY ON TWE-P MODELS. FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 22 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Accessory -Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 THERMOSTAT AIR HANDLER OUTDOOR NOTES. UNIT 1 IN AC SYSTEM FOR MULTIPLE STAGES OF ELECTRIC HEAT,JUMPER W1 AND W2 TO GETHER IF COMFORT CONTROL HAS ONLY ONE STAGE OF HEAT. 24VACHOT FAN G ---- G 24 VAC ___ _ COMMON B/C — B — I " SOV OIN ; COOL/HEAT Y Y 1st STAGE � HEATING __ I 2nd STAGE W —'IW1 r EMERGENCY X2--— W2----X2 HEAT HEAT PUMP SYSTEM THERMOSTAT AIR HANDLER OUTDOOR UNIT 24 VAC HOT R ---H R FAN G ———-IGI 24 VAC COMMON B/C———— B ———— B COOL Y \ Y • HEATING W——— "I W1 HW2I AC SYSTEM AIR HANDLER HOOK-UP FIELD WIRING DIAGRAM FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 23 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 • Field Wiring - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): OU/IU-1 SINGLE SPEED / R /��—24 VAC O ^�/'� 0� REVERSING VALVE --e--.1 Y _COMPRESSOR G O.D.SENSOR T � BR/X2 or BK / W1 `,, 24 VAC COMMON W2 TO"FAULT"ON T'STAT W3 B V IIII 4441 �� TYPICAL AIR HANDLER I II II I I LOW VOLTAGE TERMINAL BOARD o o 0 O U TO POWER SUPPLY U r-1 o Ill PER LOCAL CODES a 0 0 0 INTER-COMPONENT WIRING c )O G 24 VOLT FACTORY WIRING ■ LINE VOLT 0 J 24 VOLT FIELD WIRING 000000 II LINE VOLT NOTES: 1.POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES 2.BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE 3.LOW VOLTAGE WIRING TO BE 18A.W.G.MINIMUM CONDUCTOR 4.USE COPPER CONDUCTORS ONLY 5.TERMINALS W2 AND W3 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2nd AND 3rd CONTACTORS ARE USED BY THE HEATER FOR CONTROLLING THE POWER TO ELECTRIC HEATING ELEMENTS. IF 2nd AND 3rd(BH AND CH)CONTACTORS ARE NOT USED, THEN FIELD CONNECTIONS W2 AND W3 CAN BE OMITTED AS APPROPRIATE. 6.IF ODT IS NOT USED,THEN CONNECT APPROPRIATE JUMPERS FROM W1 TO W2 AND W3 ON LVTB FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 24 of 25 Installed by Others Costco Tigard OR MS Rx Repl July 16,2015 Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family - Split System Air Conditioning Units (Small) • Item Tag(s)_ Qty Description Model Number • B1 OU/IU-1 1 1.5 - 5 Ton Unitary Split Systems ( 4TWA3036B4000- SSC GAM5B0B06M-1 S- 0----000-0--0 Field Installed Option Description Part/Ordering Number 3.60/4.80 kW Electric Heater with Ckt Brk for 208/240V 1 Phase 60 Hz BAYEAACO5BK1 BA Evaporator defrost control AY28X084• Head pressure control BAYLOAM103 FLD=Furnished by Trane U.S. Inc. dba Trane/ Equipment Submittal Page 25 of 25 Installed by Others