InspectionsLocation:
Record Type:
Inspection Type:
Result:
Comments:
Inspection Date:
Record ID:
Inspector:
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223 Tel: 503.718.2439
16672 SW 89TH PL, TIGARD, OR, 97224
Residential - Mechanical
699 Mechanical final
FAIL
MEC2015-00452
David Young
Minor label ELS 456607
Max breaker or fuse to be 35 amp min 20 amp. Original 40 amp in panel exceeds
maximum rating of new unit. Minor label inspection will be failed and electrical permit
from city of tigard required for ac re-connect.
Violation Summary:
Inspector Contractor
Location:
Record Type:
Inspection Type:
Result:
Comments:
Inspection Date:
Record ID:
Inspector:
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223 Tel: 503.718.2439
16672 SW 89TH PL, TIGARD, OR, 97224
Residential - Mechanical
699 Mechanical final
PASS - No C of O
MEC2015-00452
David Young
Electrical approved on separate permit.
Violation Summary:
Inspector Contractor