Loading...
Specifications 1.■17? St/ & J -, ,'Ot• 7650 S. W.Beveland St. TM RIPPEY Tigard, Oregon 97223 CONSULTING ENGINEERS Phone: (503)443-3900 Fax: (503)443-3700 STRUCTURAL CALCULATIONS PROJECT: 12000 SW GARDEN PL.—SUITE 12178—RTU LOCATION: TIGARD,OREGON CLIENT: WILLAMETTE HVAC DATE: OCTOBER 1,2015 PROJECT NUMBER: 15259 TABLE OF CONTENTS: ITEM SHEET NUMBER GENERAL NOTES N1 DETAIL SK1-SK3 CALCULATIONS Cl-C3 DESCRIPTION: THIS DESIGN PACKAGE INCLUDES SKETCHES AND CALCULATIONS FOR INSTALLATION OF NEW MECHANICAL RTU AND CURB TO REPLACE AN EXISTING MECHANICAL RTU AND CURB. SKETCHES PROVIDE ATTACHMENTS OF UNIT TO CURB AND CURB TO EXISTING STRUCTURE. z..fto • cz= J$5 2PE • GGON LPG 4 KYLE 4 tom: 0/6 .• . • . . . ". • . 1. • • . •' . • . :' GENERAL STRUCTURAL NOTES CODE REQUIREMENTS: CONFORM TO THE 2012 INTERNATIONAL BUILDING CODE AS AMENDED BY THE 2014 OREGON STRUCTURAL SPECIALTY CODE. DESIGN CRITERIA: • DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE 2012 INTERNATIONAL BUILDING CODE. IN ADDITION TO THE DEAD LOADS,THE FOLLOWING LOADS WERE USED FOR DESIGN,WITH LIVE LOADS REDUCED PER IBC: RTU MODEL:BRYANT LEGACY 582J-04A (WT.490 LBS) CURB WEIGHT 94 LBS ROOF LIVE LOAD:25 PSF SNOW BASIC WIND SPEED(3-SEC GUST): 120 MPH(ULT) WIND EXPOSURE:B SEISMIC SITE CLASS:D SDS:0.610 ap:2.5 RI):6.0 EXISTING CONDITIONS: THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,DIMENSIONS AND ELEVATIONS. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES FROM CONDITIONS SHOWN ON THE DRAWINGS PRIOR TO THE START OF THE WORK. TEMPORARY CONDITIONS; THE CONTRACTOR SHALL BE RESPONSIBLE FOR STRUCTURAL STABILITY OF THE NEW AND EXISTING STRUCTURES AND WALLS DURING CONSTRUCTION. THE STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER THE FINAL CONFIGURATION ONLY. CARPENTRY: SAWN LUMBER DESIGN IS BASED ON THE NATIONAL DESIGN SPECIFICATION,LATEST EDITION. SAWN LUMBER SHALL CONFORM TO WEST COAST LUMBER INSPECTION BUREAU OR WESTERN WOOD PRODUCTS ASSOCIATION GRADING RULES. ALL LUMBER NOT SPECIFICALLY NOTED TO BE D.F.#2 OR BETTER.ALL WOOD IN PERMANENT CONTACT WITH CONCRETE OR CMU SHALL BE PRESSURE TREATED UNLESS AN APPROVED BARRIER IS PROVIDED. FRAMING ACCESSORIES AND STRUCTURAL FASTENERS SHALL BE MANUFACTURED BY SIMPSON STRONG-TIE COMPANY(OR ENGINEER APPROVED EQUAL)AND OF THE SIZE AND TYPE SHOWN ON THE DRAWINGS AND ATTACHED PER MANUFACTURER'S REQUIREMENTS AND RECOMMENDATIONS UNLESS NOTED OTHERWISE. HANGERS NOT SHOWN SHALL BE SIMPSON HU OF SIZE RECOMMENDED FOR MEMBER. ALL FRAMINGNAILS SHALL BE COMMON NAILS. NO BOX NAILS ALLOWED. FASTENERS AND ACCESSORIES IN CONTACT WITH PRESERVATIVE TREATED WOOD MUST BE HOT DIPPED GALVANIZED OR HAVE 7MAX COATING. MECHANICAL: TIIE CONTRACTOR SHALL COORDINATE SEISMIC RESTRAINTS OF ELECTRICAL EQUIPMENT,MECHANICAL,PLUMBING,FIRE SPRINKLER, MACHINERY,AND ASSOCIATED PIPING WITH THE STRUCTURE. ANY CONNECTIONS TO STRUCTURE NOT CONFORMING TO SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION(SMACNA),OR SPECIFICALLY DETAILED ON THE MECHANICAL ENGINEER'S DRAWINGS,SHALL BE DESIGNED IN ACCORDANCE OF THESE GENERAL NOTES,BY AN ENGINEER REGISTERED IN THE STATE OF OREGON,AND SHALL BE SUBMITTED TO THE ENGINEER PRIOR TO FABRICATION. FLASHING AND WATERPROOFING: - ALL FLASHING AND WATERPROOFING SHATL.BE BY OTHERS UNLESS NOTED OTHERWISE ON THE PLANS. TM RIPPEY 12000 SW GARDEN PL. - SUITE 12178 - RTU By: JW Data: 10445 1 X 1 Consulting Engineers 7650 SW Bcvcland Street Chic By: Date: Suite 100 Tigard,Oregon 97223 Job it; 15259__ _ Phone:(503)443-3900 shoot: Ni Of, r E»u \� ,w/ , � y Fa r ti EXISTING K'1'U AND CURB TO BE �� "�' REPLACED WTIH (E)4x14 PURLINS„ �� 81011 O/C• � �. a:/;v�, � Y NEW RTU AND o `° : � �' CURB,SEE 1ISK2 :�:� (E)GL BEAMS Cc, �a 77,''-4-' �� �„ 46% ; ... 4 +r�A is WNµ e n? 1 SITE PLAN .,K1 7 /T TM RIPPEY BY �1 W DATE \]L/11. CONSULTING ENGINEERS 12000 SW GARDEN.PL. - SUITE 12178 - RTU CHKBY DATE 7650 S.W.Beveland St,Suite 100 JOB NO 15259 Tigard,Oregon 97223 Phone(503) 44--3900 SHEET SK1 OF N NEW RTU(BY SUPLLIER) WEIGHT(INCLUDING CURB)=584 LBS. ALIGN CURB EDGES OVER EXISTING FRAMING AS SHOWN. FOR EXACT LOCATION SEE MECHANIAL PLANS. • EXISTING 4x PURLINS @ 8'-0" O/C. EXISTING GLULAM BEAM I I EXISTING 2x > I TYP. SUB-PURLINS @ 2'-O" 0/C. I NEW 4x8 HEADER UNDER SHORT EDGE OF UNIT CURB. NEW 4x8 HEADER UNDER UNIT HANG AT EACH END WITH CURB. HANG FROM EXISTING SIMPSON LUS48 HANGER. PURLINS WITH SIMPSON LUS48 CUT EXISTING SUB-PURLINS HANGER. AS NECESSARY AND HANG _ FROM NEW HEADER WITH SIMPSON LUS HANGER. NOTES: -INSTALL ALL FRAMING PRIOR TO INSTALLING CURB. -ALL WATERPROOFING IS BY OTHERS. -SEE MECHANICAL PLANS FOR ALL OTHER INFORMATION. FRAMING PLAN AT RTU AMEN=T TM RIPPEY BY J W DATE CONSULTING ENGINEERS 12000 SW GARDEN.PL. -SUITE 12178- RTU CHK BY DATE 7650 S.W. Beveland St,Suite 100 JOB NO 15259 Tigard,Oregon 97223 Phone(503) 443-3900 SHEET Sf OF S 3..t-‘,t EQ. SPACED , MECANICAL UNIT 1113016,-1 WAYS BY OTHERS TYP. Ir( 16 GA. CLIPS W/ (S) *10 TEK SCREWS PER 16 GA. CLIP CLIP, (4) CLIPS REQ'D. N.T.S. SEE PLAN VIEW FOR 1 • A CLIP LOCATION I'-0", TYP.II t t ij _I WOOD BLOCKING �A CLIP REQUIRED LOCATION (4) TOTAL FLASHING AND INSULATION MECH. UNIT NOT SHOWN FOR CLARITY OUTLINE WATERPROOFING BY OTHERS PLAN VIEW N.T.S. CENTER CURB ON NEW PROVIDE *Im SCREWS OR EXISTING STRUCTURAL 1'-0" 0/C AND AT 6" FROM MEMBER ENDS OF CURB. MINIMUM 112" 1 Ali EMBED INTO STRUCTURAL MEMBER, TYP. a- CT I O\ AT Cum SK3 RTU-01 SCALE: 11/2" = 1'-0" 1M K TM RIPPEY BYJW DATE CONSULTING ENGINEERS 12000 SW GARDEN PL. - SUITE 12178 - RTU CHK BY DATE 7650 SW Beveland,Suite 100 Tigard,Oregon 97223 JOB NO 15259 Phone: (503)443-3900 Fax:(503)443-3700 SHEET SK3 OF f * 1veC1\• UNi tJG, "o 4r Wy n 9 ti3Z T2-IA, • C,tAJtJ WV. it( /(R)1 Gt. �Jg�tG . I S At,r,eJJ pall E P )e/Ni (E)6-t" 2"1 (Fi)P Aftki i ,o 11 I NF.+J h1 i4D(It t„ x '/•3)(t& as) ' O(s€a)A c 1E-ie F M: (10)(8) /$ = G bag ^�. FAtreA CAP4-C l Ft)/4 P1ANL (4Nr-s' (-4//WAIVER_ (O Pwect)i,, MDtrst ` ,s )((J t-a )(2,-o).7g-: 16000 F!b Lt x14 St,-rttW )(to '(ally -4 ° , TAFCLFA" C S"Zv Att,owfry k. 'k�r$I, 3oa oL r 1+ r.EC h 33( 0". rJ !. ckbAsE 214- C.-I'kClt � ��sa c� �� 10-)/>s r I,+ Mai- DANCrc,reo AS C-c�MA IO1NCrak.. kd Fitt. r-G^4N • / S. L „e,o/) L -sr vii AFPE.41,wa • I1 t Nc CAP C'/ = 32-porr oJ! . () at, aE44,. Gents ASS o -STEcxr-u/V OK tAfi y-L, ' SEE_ Pp g vtDIn f TM RIPPEY BY ,-.374 DATE CONSULTING ENGINEERS 12000 SW GARDEN PL. - SUITE 12178 - RTU CHK BY DATE 7650 S.W. Beveland St, Suite 100 SOB N015259 Tigard,Oregon 97223 Phone(503) 443-3900 SHEET C( of De..i 1Maps Summary Report http://ehpl-earthquake.cr,usgs.gov/designmaps/us/summary,php?tempi., UW Design Maps Summary Report User-Specified Input Building Code Reference Document 2012 International Building Code (which utilizes USGS hazard data available In 2008) Site Coordinates 45.432°N, 122.763°W Site Soil Classification Site Class D -"Stiff Soil" Risk Category I/II/III i I i S000m }{t iI ,,eel�B avter'tgn $�E F `tk X ti 'r lr E ; a - Px ) k i f ?7A's^st x' s v✓FS JJa f C g :„ / i } A. • G t F �1 t R+ i 3 s ^22 f : 3Nit3 I ii `Tsi G I3f '3'z :h s ': ' J>ss ^" : x•%.FL: ... fk~J / w E ki Iy k { i 1f yg 2� t * fj x t s a f s 3 k&"Npo �} f.s1Y y °c 3 Z Y s c i �: s k.s i Z k s Y k , aCvfx31# „r f� '� �1 x .� i / 3 a �CT3kkf Q i 5 i / Y s a 1,9;:.,,,,9:::... rk 3 " k t V / k f 3 l i �"` /i x i3 . 3 r , k`:R ` Y K t ` c z v,� C S i�4 , 0,4 r. yn 3.^ > c� _ P �� s F / fl,f ; 3r% t i r } Jt 1 Jf F 'i ox f k> k 1{iIITy p Y: # Zf _e :: t :f k -7r _ s f Xx, ,F , Y r 3 F l e .J 7`4 (J .R C`' FxJ x t hr,t [ R / K 8 Gty � ha , /� k T ks i EE C [ x t C 0.- A l 5 E Ri C f . / df E sat I `.': . F E; ;?� :x.5 ma uiFsk E r >.. 'A>'Y.Ui in '�5�� to a1 k A, k� t / o_.�Y i :. .i .... < ..:: ....... .. '. .:'.' } T�.': ...... ....J........ I�iL :.: .......,.}� .... <�IwapQueAt;; USGS-Provided Output SS = 0.975 g SMS = 1.083 g SDS = 0.722 g S1 = 0.423 g SMl = 0.667 g Sol = 0.445 g For information on how the SS and Si values above have been calculated from probabilistic(risk-targeted) and deterministic ground motions in the direction of maximum horizontal response, please return to the application and select the "2009 NEHRP"building code reference document. MCER Response Spectrum Design Response Spectrum 0.89 1.10 0.00 0.99 0.72 • 0.99 0.64 0.77 0.56 in 0.6G 03 0.49 0.55 f Eil 0.40 t 0.44 0.32 0.33 • 0.24 0.22 0.16 0.11 0.00 0.00 0.00 0.00 0.20 0.40 0.60 0.00 1.00 1.20 1.40 1.60 1.00 2.00 0.00 0.20 0.40 0.60 0.90 1.00 1.20 1.40 1.60 1.20 2.00 Period, T(sec) Period,T(sec) Although this information is a product of the U.S.Geological Survey,we provide no warranty,expressed or implied,as to the accuracy of the data contained therein.This tool Is not a substitute for technical subject-matter knowledge. C@, Wind and Seismic Loads on Mechanical Unit Worksheet Calculates the wind and seismic forces for a rooftop mounted mechanical unit based on the ASC E 7-10. Hold down forces are calculated based on 0.6D + (0.6W or 0.7E) load cases. Wind and Seismic Loads on Mechanical Unit Windspeed:= 120mph Exposure:= "B" Vasd'= "rio (Is wind speed ASD?) Seismic Parameters SDS•_ .722 ap := 2.5 Rp := 6.0 IE:= 1.0 Building Dimensions Category:_ "II" Roof Elevation:= 16ft Building_Width:= 441ft Building_Depth:= 118ft Mechanical Unit Dimensions Displacement:= "Fan Unit" Weight:= 4901b UnitHeight:= 33in Width:= 44in Length:= 74in Curb:= 14in Curb_Width:= 37in (Dimension for Calculating Overturning Uplift) SUMMARY(ALL VALUES ARE ASD) Method Used= "ASCE 7-10-Section 29.5.1" D= 490 lb _ WWindUpliftASD= 409 lb Displacement= "Fan Unit" (From ACSE 29.5-3) �___ EASD= 1241b =2.542 ft eismic �— WWindASD = 553 lb (From ACSE 29.5-2) /r. hWind= 1.958ft X= 3.083ft � TWindTotalASD= 408 lb Notes: TseismicASD= –45 lb 1.Positive sign convention shown. Negative values indicate opposite direction 2.X equals the width between attachment points for overturning rEalk ppokiat OAFS PA COP-NE-R- Uat- 11) CAT (AY CO&Ca,#A-,S S VAR. Fort Gipt,ey-r- (wo2/3)f it scram,s z' 51*/U ,,s FAR Of /46,A 44 v.... (W?J Flr-,1-4. Assn A-4 a 10 ScR,t,_,s C 1'.�..,fie I1,0„ 1r � ttv (l,6,)( l(,)r �g�a 't• )( )(IS5)° S 1�`/ (,�')Sc, :t-�.-15 i }` k- ��I//yJ l�< i'S (J4 St/i-C,1A p+i C iFS Pi.,t vo ` ':J 582J GAS HEAT/ELECTRIC COOLING Lbryant SINGLE PACKAGED ROOFTOP 14 SEER 3 TO 5 NOMINAL TONS Heating&Cooling Systems Product Data i JEGACYTM L I N E tEGA( ' 1117 j _ n PliroP C08515 (Shown with optional Louvered Hail Guard) (f_) ASHRAE Peron COMPLIANT MODEL NUMBER NOMENCLATURE Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Example: 5 8 2 J E 0 6 A 0 7 2 AOB O AA Unit Type Packaging and Control 582-Gas Heat RTU,Legacy Series A= Standard Packaging,electro mechanical controls that require W7212 EconoMi$er IV Model B= LTL Packaging,electro mechanical J - Puron®(R-410A)Refrigerant controls that require W7212 EconoMi$er IV C= Standard Packaging,electro mechanical controls that require W7220 EconoMi$er X Voltage F = LTL Packaging,electro mechanical E = 460-3-60 controls that require W7220 EconoMi$er X J = 208/230-1-60 P = 208/230-3-60 Factory Installed Options T = 575-3-60 OA =None NOTE:See the 582J 3 to 5 ton Price Pages Cooling Tons for a complete list of factory installed N 04- 3 tons options. co 05- 4 tons 06- 5 tons Outdoor Air Options A= None Refrig.System/Gas Heat Options B = Temperature Economizer, Barometric Relief, A= Standard One Stage cooling models/Nat.Gas Heat Standard Leak(W7212 or W7220) B = Standard One Stage cooling models/Low NOx Heat E = Temperature Economizer, Barometric Relief, C= Standard One Stage cooling models/SS HX Heat Standard Leak w/CO2(W7212 or W7220) G= One-Stage cooling models/Alum Heat Exchanger H= Enthalpy Economizer,Barometric Relief, with Perfect Humidity TM' Standard Leak(W7212 or W7220) H = One-Stage cooling models/Low NOx Heat L = Enthalpy Economizer,Barometric Relief, with Perfect Humidity Standard Leak w/CO2(W7212 or W7220) J = One-Stage cooling models/Stainless Steel Exchanger Q= Motorized 2 Position Damper with Perfect Humidity U= Temperature Economizer,Barometric Relief, Ultra Low Leak(W7220) Heat Level Input W= Enthalpy Economizer,Barometric Relief,Ultra Low Leak • Standard/Stainless Steel (1M220) 072=72,000 115=115,000 Indoor Fan Options 150=150,000 0 = Direct Drive ECM Low NOx 2 = Medium Static Option 060=60,000 3 = High Static Option 090=90,000 120=120,000 Coil Options(RTPF)(Outdoor-Indoor-Hail Guard) A= Al/Cu-Al/Cu B= Precoat Al/Cu-Al/Cu Note:On single phase(J)voltage code)models,the C= E-coat Al/Cu-Al/Cu following are not available as a factory installed option: D= E-coat Al/Cu-E-coat Al/Cu -Perfect Humidity E = Cu/Cu-Al/Cu -Coated Coils or Cu Fin Coils F = Cu/Cu-Cu/Cu -Louvered Hail Guards M= Al/Cu-Al/Cu—Louvered Hail Guard -Economizer or 2 Position Damper N= Precoat Al/Cu-Al/Cu—Louvered Hail Guard -Powered 115 Volt Convenience Outlet P= E-coat Al/Cu-Al/Cu—Louvered Hail Guard Q= E-coat Al/Cu-E-coat Al/Cu—Louvered Hail Guard R= Cu/Cu-Al/Cu—Louvered Hail Guard S = Cu/Cu-Cu/Cu—Louvered Hail Guard C14337 4 Table 2-AHRI COOLING RATING TABLE NET NOM. TOTAL UNIT COOLING CAPACITY COOLING POWER SEER EER STAGES (TONS) CAPACITY (MBH) 582J*04 1 3 35.4 3.0 14.0 12.00 582J*05 1 4 47.5 4.0 14.0 12.00 . 582J*06 1 5 58.5 4.9 14.1 12.00 LEGEND NOTES: AHRI - Air Conditioning,Heating and Refrigeration 1. Rated in accordance with AHRI Standard 210/240. • Institute Test Standard 2. Ratings are based on: ASHRAE - American Society of Heating,Refrigerating Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor and Air Conditioning,Inc. air temp and 95°F(35°C) db outdoor air temp. EER - Energy Efficiency Ratio 3. All 582J units comply with ASHRAE 90.1 Energy Standard for SEER - Seasonal Energy Efficiency Ratio minimum SEER and EER requirements. 4. 582J units comply with US Energy Policy Act (2005). To evaluate code compliance requirements, refer to state and local codes. N AI9R CERTIFIED. USLo www.anrdirectory.org Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the A IRAE program For verification of certification for individual products,go to www.ahridi rectory.org. COMPLIANT Table 3-HEATING RATING TABLE - NATURAL GAS & PROPANE AL/SS HEAT EXCHANGER THERMAL TEMP RISE AFUE UNITS GAS HEAT INPUT/OUTPUT INPUT/OUTPUT (DEG F) EFFICIENCY (%) STAGE 1 (MBH) STAGE 2(MBH) (/) LOW - 65/50 25- 55 82.0% 81.0% 04 MED - 90/73 45- 85 82.0% 81.5% a) HIGH - - - - - t LOW - 65/50 20- 55 82.0% 81.0% O. m 05 MED - 90/73 30- 65 82.0% 81.2% _c HIGH - 130/105 45- 80 82.0% 81.0% rn LOW - 65/50 10- 55 82.0% 81.0% 06 MED - 90/73 25- 65 82.0% 81.2% HIGH - 130/105 35- 80 82.0% 81.0% LOW - 72/56 25- 55 82.0% N/A 04 MED 82/66 115/89 55- 85 80.0% N/A d HIGH - - - - - as LOW - 72/56 25- 55 82.0% N/A r w 05 MED - 115/90 35- 65 81.0% N/A 2 HIGH 120/96 150/117 50- 80 80.0% N/A ~ LOW - 72/56 20- 55 82.0% N/A 06 MED - 115/90 30- 65 81.0% N/A HIGH 120/96 150/117 40- 80 80.0% N/A NOTES: Heat ratings are for natural gas heat exchangers operated at or below 2000 ft (610 m).For information on propane or altitudes above 2000 ft (610 m),see the Application Data section of this book,Accessory Propane/High Attitude kits are also available. In the USA the input rating for altitudes above 2000 ft(610m)must be derated by 4%for each 1000 ft(305 m)above sea level.In Canada, the input rating must be derated by 10%for altitudes of 2000 ft(610 m)to 4500 ft(1372 m)above sea level. 8 Table 6—MINIMUM - MAXIMUM AIRFLOW RATINGS- NATURAL GAS & PROPANE HEAT COOLING AL HX HEATING SS HX HEATING VOLTAGE UNIT LEVEL MINIMUM MAXIMUM MINIMUM MAXIMUM MINIMUM MAXIMUM LOW 900 1970 900 1970 582J*04 MED 900 1500 800 1520 800 1520 HIGH - - - - LOW 900 2470 900 2470 SINGLE 582J*05 MED 1200 2000 1050 2280 1050 2280 PHASE HIGH 1230 2190 1230 2190 LOW 900 3290 900 3290 582J*06 MED 1500 2500 1050 2730 1050 2730 HIGH 1230 2820 1230 2820 LOW 990 2190 990 2190 582J*04 MED 900 1500 1000 1550 1000 1550 HIGH - - - - LOW 990 2190 990 2190 inTHREE PHASE 582J*05 MED 1200 2000 1330 2460 1330 2460 HIGH 1390 2220 1390 2220 LOW 990 2730 990 2730 582J*06 MED 1500 2500 1330 2880 1330 2880 HIGH 1390 2780 1390 2780 10 Table 7-PHYSICAL DATA (COOLING) 3 - 5 TONS 582J*04 582,11*05 582J*08 Refrigeration System • #Circuits/#Comp./Type 1/1/Scroll 1/1/Scroll 1/1/Scroll Puron®refrig.(R-410A)1 phase (Ibs-oz) 7.1 10.5 16.0 Puron®refrig.(R-410A)3 phase (lbs-oz) 7.1 10.5 14.5 Perfect Humidity Puron®refrig.charge(lbs-oz) 10.4 15.3 26.0 Metering Device(A) Acutrol Acutrol Acutrol Perfect Humidity Metering Device(B) Acutrol+TXV Acutrol+TXV Acutrol+TXV High-press.Trip/Reset(psig) 630/505 630/505 630/505 Low-press.Trip/Reset(psig) 54/117 54/117 54/117 Compressor Capacity Staging(%) 100% 100% 100°% Evap.Coll Material(Tube/Fin) Cu/Al Cu/Al Cu/Al Coil type 3/8-in RTPF 3/8-in RTPF 3/8-in RTPF Rows/FPI 3/15 3/15 4/15 Total Face Area(ft2) 5.5 5.5 7.3 Condensate Drain Conn.Size 3/4-in 3/4-in 3/4-in Perfect Humidity Coll Material(Tube/Fin) Cu/Al Cu/Al Cu/Al Coil type 3/8-in RTPF 3/8-in RTPF 3/8-in RTPF Rows/FPI 1/17 2/17 2/17 Total Face Area(ft2) 3.9 3.9 5.2 Evap.Fan and Motor Motor Qty/Drive Type 1/Direct 1/Direct 1/Direct N Standard Max BHP 1 1 1 u) Static RPM Range 600-1200 600-1200 600-1200 1 phase Motor Frame Size 48 48 48 Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal L Fan Diameter(in) 10 x 10 10 x 10 10 x 10 Motor Qty/Drive Type 1/Belt 1/Belt 1/Belt Max BHP 1.2 1.2 1.2 Medium RPM Range 560-854 560-854 770-1175 Static Motor Frame Size 48 48 48 1 phase Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal L Fan Diameter(in) 10 x 10 10 x 10 10 x 10 Motor Qty/Drive Type 1/Belt 1/Belt 1/Belt High Max BHP 1.5 1.5 1.5 Static RPM Range 770-1175 770-1175 1035-1466 1 phase Motor Frame Size 56 56 56 Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter(in) 10 x 10 10 x 10 10 x 10 Motor Qty/Drive Type 1/Direct 1/Direct 1/Direct Max BHP 1 1 1 Standard RPM Range 600-1200 600-1200 600-1200 Static Motor Frame Size 48 48 48 3 phase Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter(in) 10 x 10 10 x 10 11 x 10 Motor Qty/Drive Type 1/Belt 1/Belt 1/Belt Max BHP 1.7 1.7 2.9 Medium RPM Range 770-1175 920-1303 1035-1466 Static Motor Frame Size 48 56 56 3 phase Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter(in) 10 x 10 10 x 10 10 x 10 Motor Qty/Drive Type 1/Belt 1/Belt 1/Belt High Max BHP 2.9 2.9 2.9 Static RPM Range 1035-1466 1208-1639 1303-1687 3 phase Motor Frame Size 56 56 56 Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal Fan Diameter(in) 10 x 10 10 x 10 10 x 10 Cond.Coll 1 phase Material(Tube/Fin) Cu/Al Cu/Al Cu/Al Coil type 3/8-in RTPF 3/8-in RTPF 3/8-in RTPF Rows/FPI 1/17 2/17 2/17 Total Face Area(ft2) 16.5 16.5 21.3 3 phase Material(Tube/Fin) Cu/Al Cu/Al Cu/Al Coil type 3/8-in RTPF 3/8-in RTPF 3/8-in RTPF Rows..Fins/in. 1/17 2/17 2/17 Total Face Area(ft2) 16.5 14.6 18.8 Cond.fan/motor Qty/Motor Drive Type 1/Direct 1/Direct 1/Direct Motor HP/RPM 1/8/825 1/4/1100 1/4/1100 Fan diameter(in) 22 22 22 Filters RAFilter#/Size(in) 2/16x25x2 2/16x25 x2 4/16x25x2 OA inlet screen#/Size(in) 1/20 x24 x 1 1/20 x 24 x 1 1/20 x 24 x 1 11 Table 9-PHYSICAL DATA (HEATING - THREE PHASE UNITS) 3 - 5 TONS 582JE/P/T04 582JE/P/T05 582JE/P/T06 Electrical Three Phase Three Phase Three Phase Gas Connection #of Gas Valves 1 1 1 Nat.gas supply line press(in.w.g.)/(PSIG) 4—13/0.18—0.47 4—13/0.18—0.47 4—13/0.18—0.47 LP supply line press(in.w.g.)/(PSIG) 11 —13/0.40—0.47 11 —13/0.40—0.47 11 —13/0.40—0.47 Heat Anticipator setting(Amps) 1st stage 0.14 0.14 0.14 2nd stage 0.14 0.14 0.14 Natural Gas Heat #of stages/#of burners(total) 1/2 1/2 1/2 Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT LOW Rollout switch opens/closes 195/115 195/115 195/115 Temperature Rise 25—55 25—55 20—55 #of stages/#ofburners(total) 1or2/3 1/3 1/3 N Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT c0 MED Rollout switch opens/closes 195/115 195/115 195/115 in Temperature Rise 55—85 35—65 30—65 #of stages/#of burners(total) — 1 or 2/3 1 or 2/3 Connection Size — 1/2—in NPT 1/2—in NPT HIGH Rollout switch opens/closes — 195/115 195/115 Temperature Rise — 50—80 40—80 Liquid Propane Heat #of stages/#of burners(total) 1/2 1/2 1/2 Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT LOW Rollout switch opens/closes 195/115 195/115 195/115 Temperature Rise 25—55 25—55 20—55 #of stages/#of burners(total) 1 or 2/3 1/3 1/3 Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT MED Rollout switch opens/closes 195/115 195/115 195/115 Temperature Rise 55—85 35—65 30—65 #of stages/#of burners(total) — 1 or 2/3 1 or 2/3 Connection Size — 1/2—in NPT 1/2—in NPT HIGH Rollout switch opens/closes — 195/115 195/115 Temperature Rise — 50—80 40—80 Low NOx Gas Heat #of stages/#of burners(total) 1/2 1/2 1 /2 Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT LOW Rollout switch opens/closes 195/115 195/115 195/115 Temperature Rise 20—50 20—50 15—50 #of stages/#of burners(total) 1/3 1/3 1/3 Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT MED Rollout switch opens/closes 195/115 195/115 195/115 Temperature Rise 30—60 30—60 25—60 #of stages/#of burners(total) — 1/3 1/3 Connection Size — 1/2—in NPT 1/2—in NPT HIGH Rollout switch opens/closes — 195/115 195/115 Temperature Rise — 40—70 35—70 — Not applicable 13 582J NOTES: 0 Jul TED P.O.LOS Am THIS MAW IS INN 1.10•710 Of CAMEO CaPONATIM OUNISS ION a T[S[118.1105 a IOCU1N Ira TECHNOLOGIES STIKUNE.n AND IS MAINIFI UPON NC MISS CONDITION it TN[ IONS qT C015TITUT[POT P111ONMK1 a I. DIMENSIONS-ARE IN INCHES. DIMENSIONS COUNTS R■nS IN II a CONSENT 51 UM I/OS unm IN I I ARE IN MILLIMETERS. UNIT J X It PHASE) K 13 PHASE) CARRIER oral CaPg8n01 S enru CONSENT KCVTAIN[a 10011101. 582J 04 33 3/8 II 7/8 14 7/8 2. CENTER OF GRAVITY 18171 [3771 13171 73 J/8 II 1)8 IB SIB CONNECTION SIZES 5821 OS 18171 13771 11721 A 1 3/8' [351 DIA FIELD POWER SUPPLY HOLE 3. Op,DIRECTION OF AIR FLOW 41 3/8 14 7/8 18 5/8 ' 582J 06 110511 (3711 11721 B 2' 1501 DIA POWER SUPPLY KNOCKOUT C 1 3N' 1511 DIA GAUGE ACCESS PLUG 0 i/B' 1221 DIA FIELD CONTROL WIRING HOLE 33-3/8 18181 E 3/1'-14 NP1 CONDENSATE DRAIN F 1/2'-14 PI GAS CONNECTION • 1 G 2 1/2 ' 1611 DIA POWER SUPPLY KNOCKOUT 32-1/4 E ECONOMIZER HOOD 18181 (OPTIONAL) 16 [4061 FILTER ACCESS PANEL I THRu.THE.BASE CHART Ii00l L[S51 COMP, THESE HOLES REQUIRED FOR USE • • • ACCESS CONDENSER CRBTNPWROOTA01, 003801 •PANEL I COIL ,� •• .L THREADED WIRE REO'D HOLE INDOOR COIL- J - - _ I CONDUIT SIZE USE SIZES IMAK.I (0: ell ACCESS PANEL I �� �1 ■ I/2' ACC. 1/8' 122.21 �/d C 25.5/8 10-7/8 ' X 1/2' 240 1/8' 122.21- (n I— O I _ _ ITnllli N' RETURN 16521 AIR 12171 RETURN N 1 •_ 3/1' 1001,0031 POWER 1 1/8' 128,11 1 —— p 1AIR 2•• 10031 1/2' FPT GAS 1 3/16' 130.01 1/ '-n 111171 I FOR'TXRU-THE-BASEPAM FAC TORT OPTION, •2.5/8--I „__„__�� FITTINGS FOR ONLY 0,1, 6 2 ARE PROVIDED BACK [611 l�J 111. �� E ALT. I • SELECT EITHER 3/A'OR v2' I■1 y CURB W CONDE NSA IE 17-3/I ' FOR POWER, DEPENDING ON WIRE SIZE /� O WIDTH 1 - 1 DRAIN OPENING [4511 29 3/8 ,. 10011 PROVIDES 3/4'FPT THOU CURB y ., I 1 J ,Z SUPPLY •- 26-1/2 17171 SUPPLY FLANGE I FITTING. co; 18.1/8 I AIR 16731 xy 11591 AIR 161/8 111/1 12-1/1 cc 14111 [3831 13121 SEE THRU THE 6.1/4 ,� c CA 11 I I BASE CHART \ •, e •[1511 • •- A _ 3-3/6 PC) 1 121/8 -- [55) G 25 fLUE - 1707] CA 16361 11 DDI HOOD 18.1/2 I, T K TOF 11701 t0-1/2 N 1-1 11181 [2651 4 1321 1118] ril ,." EL EC IR IC AL O •I ——_ DISCONNECT U. .1 L-I Ar, I I LOCATION ���� Cr N CONDENSER COIL �I ACCESSLPANEL ACCESS BLOWER • CONDFMSATDE FILTER hNN�I gig 221 EM-- --DRAIN _ O 11. . • J ii,I. __ 2531/8 OUTSIDE 1 [6381 OPTIONAL —_ I I 16-1/4 RETURN AIA I INSTALLED _- , II 19-1/2 OPTIONAL FACTORY ANDLE 1181/8 I SUPPLY AIR I AIR FACTORY I [1911 INSTALLED 1 12891 I 7I LI OUTLET — DISCONNECT — /1721-1/1 II EEL Eg ' • I _ [5191 11681 }7 1-516 �� =�8 6-5/B �(.](.] I �. (] �+ 11551 �! 1■ 193/4 HANDLE 8.3/8 I 6-5/8 1 t 6 4 1951 16-3/1 - 3081/8 12131 [1691 [1771 11521 111871 [7611 7 4-318 _ 26.7/8 116881 16821 31-111 BAROMETRIC 17931 RELIEF LEFT FLOW SUPPLY suvv FRONT AIR RETURN RIGHT AIR 0N[T DATE SUP[IC[ICS 582J 04-06 SINGLE ZONE ELECTRICAL RID 1 OF 2 08-14-14 - COOLING WITH GAS HEAT 48KC000284 _ c) A IV v 0 UNITED P.O.DOS ODOR THIS DOCUMENT IS THE PROPERTY Or CARRIER CORPORATION SUBNISSIOR OF THESE DIANINOS OA DaUHEHTS TECHNOLOGIES SHRKUSE.NT D IS DEUOERED UPON THE UPSETS CONDITION THUS THE DOES NOr COf TUASUE HADI GS OORIUNCE NR STD. UNIT CORNER CORNER CORNER CORNER C G HEIGHT CARRIER 13221 CORPORAT.13E NO1 BE DINCSONED ON usm NIix0U1 uxneM Acc[ruNCE or canACr. UNIT WEIGHT WEIGHT 1A1 WEIGHT 1BI WEIGHT ICI WEIGHT EDl CORPORATION'S n1rrEN CasnT. LBS. KG. LBS. KG. L85. KG. LBS. KG. LBS. KG. X -7 Z 582J 04 498 222 120 54 111 50 125 56 135 61 _ 35 3/4 19081 24 3/4(6281 18 7/8(1191 582J 05 544 246 130 58 126 57. 142 64 146 66 36 3/4 (9331 21 3/4(6281 18 7/8(1791 582J 06 597 270 141 64 156 70 158 71 142 64 39 1/8(9931 23 1/2(5971 20 1/8(5111 •STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING. FOR OTHER OPTIONS AND ACCESSORIES. REFER TO THE PRODUCT DATA CATALOG. CORNER A CORNER B 111111 /^\\�. tO oil M 1 o1 3 x y I 1 . • . • a CC Pt) IN CORNER D CORNER C 0 I TOP ~y C's W5 M 1T I. •• VI N ICI C IN • { Z „_... _. -- 51= ,..., J. • , 1 • iL OO f •=•: : 0 FRONT SHEET DATE SUNEIC(DES 582J 04-06 SINGLE ZONE ELECTRICAL Kr 2OF2 08-14-14 - COOLING WITH GAS HEAT 486C000284 _ _0 A N V 582J ' M ' • • ROOF CURB A NOTES CONNECTOR PKG.ACC. GAS CONNECTION TYPE GAS FITTING POWER WIRING CONTROL WIRING ACCESSORY CONVENIENCE ACCESSORY r 1.ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED. FITTING FITTING OUTLET WIRING CONNECTOR 2.INSULATED PANELS:25.4(11 THK.POLYURETHANE FOAM,44.511-3/41 B DENSITY. --- • CRRFCURB001A01 14 3.DIMENSIONS IN()ARE IN MILLIMETERS. CRBTMPWROO1A01 THRU THE CURB 3/4.119)NPT - (3`56) 4.ROOFCURB:18 GAGE STEEL. 5.ATTACH DUCTWORK TO CURB.(FLANGES OF DUCT REST ON CURB). - 3/4"(19)NPT 1I2 112.71 NPT 1/2"(12.71 NPT CRRFCURBOO2A01 (B U) 6.SERVICE CLEARANCE 4 FEET ON EACH SIDE. CRBTMPWR003A01 THRU THE BOTTOM 1I2.112.7)NPT 7.EM43> DIRECTION OF AIR FLOW. 8.CONNECTOR PACKAGE CRBTMPWROOIA01 IS FOR THRU-THE-CURB GAS TYPE PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS. 1.3/4" 11 1 (44.51 21.00' 5.42" 1 11.96' - 125.4) -� 11 3/4"(298.51 WIDE [137.7] (303.81 INSULATED DECK PANELS, 1 l L "A" IIZI�y 252• W 552.2.2) v] 8 9/161217.5]WIDE I INSULATED DECK PANEL 1: A N I-314' 00 , I \ (44.4] 2 I 1'4-13/16" H SEE NOTE R2 `'J 4�• J SECTION E-E GAS SERVICE PLATE W I INSIDE �( (126.01 70.87" SCALE 0.250 THRU THE CURB j4.. (63' /1 A v `1 1(1800.2) �, D]50.8](il :'� 2"SEE ! MT�I C _ ASSEMBLYQF �� I w REQUIRED)^'9 r (SEE NOTE N8)r: RETURN AIR CA OPENING ` , R='S 15.19' (b 1/3/4144.5) / = [385.8] E E F3.oD- �z1.e4• /T 21° C I I 176.2) 554.7) .._ .J � V re Q 32.19' 1 [en.e) VIEW"B" - /�� 1/1 r CORNER DETAIL 16.03' RETURN AIR - �'1-3/4' 755.6) SUPPLY AIR (407.2) \ [44.4] 4 (I1 1355.6] OPENING til INN _445, z INN JI 1-- �. C 1.75' 1--20.41" „ -3.00' GASKE UNIT •A• ` p. CA 144.51 (518.31 (76.2) (SUPPLIED WITH CURB) 01•C --13'78' AIL(FIELD SUPPLIED) / p, 1350.01 % 5'7-3/B' O 40.69" [1711.3] 11033.51 DUC Z TYPICAL(4)SIDES (FIELD SUPPLIED) j 7/16•. 3'-1 3/16" `�� OUNTER FLASHING [944.6] ` / ." - - (FIELD SUPPLIED) � �/ et 14 " NG FELT SEE VIEW"BEKI \ (FIELD SUPPLIED) N CERTIFIED DRAWING T STRIP 17.01 (FIELD SUPPLIED) `� •ss, I� DRAWNGRELEASE LEVEL PRODUCTION OO 'DOPING MATERIAL \j (FIELD SUPPLIED) ////}}}}���� UNLESS OTHERWISE SPECIFIED \ \ i THIRD ANGLE DIMENSIONS ARE IN INCHES•I / ] \\\\\\\\` PROJECTION MATERIAL TOLERANCES ON. \ 1 DEL 3 DEC ]DEC ANG KOS Reim q 7 �HC"q A f- t- f- f- i AUTHORIZATION NUMBER TITLE i«E SUPPLY AIR RETURN AIR\ / ` - 1041738 "IGIDINSULATION CURB ASY,ROOF `�. (FIELD SUPPLIED) ENGINEERING MANUFACTURING (004-007) ENGINEERING REOUIREMENTS - -- - SIZE DRAWING NUMBER REV \\, OVERALL DIM.5'-7 3/8'WAS 5'-7 7/8:18GA 7-005.Y-002 DRAFTER CHECKER 48TC400 D 427 B A A MATERIAL WA 16 GA.:NAIL FIELD SUPPLIED WAS 04/22/13 MMC - - 1067888 WEIGHT - MMC 06/17/11�- SHEET S OF 5 WITH CURB SURFACE FINISH MFCIPURCH MODEL (NTERNAL USE ONLY1 NEST DRAWING SCALE DISTRIBUTION REV REVISION RECORD DATE BY CHILD AMID ECN NO. _ PURCH - N/A MMC _n W W 0 582J