Specifications 1.■17? St/ & J -, ,'Ot•
7650 S. W.Beveland St.
TM RIPPEY Tigard, Oregon 97223
CONSULTING ENGINEERS Phone: (503)443-3900
Fax: (503)443-3700
STRUCTURAL CALCULATIONS
PROJECT: 12000 SW GARDEN PL.—SUITE 12178—RTU
LOCATION: TIGARD,OREGON
CLIENT: WILLAMETTE HVAC
DATE: OCTOBER 1,2015
PROJECT NUMBER: 15259
TABLE OF CONTENTS:
ITEM SHEET NUMBER
GENERAL NOTES N1
DETAIL SK1-SK3
CALCULATIONS Cl-C3
DESCRIPTION:
THIS DESIGN PACKAGE INCLUDES SKETCHES AND CALCULATIONS FOR
INSTALLATION OF NEW MECHANICAL RTU AND CURB TO REPLACE AN EXISTING
MECHANICAL RTU AND CURB. SKETCHES PROVIDE ATTACHMENTS OF UNIT TO CURB
AND CURB TO EXISTING STRUCTURE.
z..fto
• cz= J$5 2PE
• GGON
LPG
4 KYLE 4
tom: 0/6
.• . • . . . ". • . 1.
•
• . •' . • . :'
GENERAL STRUCTURAL NOTES
CODE REQUIREMENTS:
CONFORM TO THE 2012 INTERNATIONAL BUILDING CODE AS AMENDED BY THE 2014 OREGON STRUCTURAL SPECIALTY CODE.
DESIGN CRITERIA: •
DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE 2012 INTERNATIONAL BUILDING CODE. IN ADDITION TO THE
DEAD LOADS,THE FOLLOWING LOADS WERE USED FOR DESIGN,WITH LIVE LOADS REDUCED PER IBC:
RTU MODEL:BRYANT LEGACY 582J-04A (WT.490 LBS)
CURB WEIGHT 94 LBS
ROOF LIVE LOAD:25 PSF SNOW
BASIC WIND SPEED(3-SEC GUST): 120 MPH(ULT)
WIND EXPOSURE:B
SEISMIC SITE CLASS:D
SDS:0.610
ap:2.5
RI):6.0
EXISTING CONDITIONS:
THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,DIMENSIONS AND ELEVATIONS. THE CONTRACTOR SHALL NOTIFY
THE ENGINEER OF ANY DISCREPANCIES FROM CONDITIONS SHOWN ON THE DRAWINGS PRIOR TO THE START OF THE WORK.
TEMPORARY CONDITIONS;
THE CONTRACTOR SHALL BE RESPONSIBLE FOR STRUCTURAL STABILITY OF THE NEW AND EXISTING STRUCTURES AND WALLS DURING
CONSTRUCTION. THE STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER THE FINAL CONFIGURATION
ONLY.
CARPENTRY:
SAWN LUMBER DESIGN IS BASED ON THE NATIONAL DESIGN SPECIFICATION,LATEST EDITION. SAWN LUMBER SHALL CONFORM TO
WEST COAST LUMBER INSPECTION BUREAU OR WESTERN WOOD PRODUCTS ASSOCIATION GRADING RULES. ALL LUMBER NOT
SPECIFICALLY NOTED TO BE D.F.#2 OR BETTER.ALL WOOD IN PERMANENT CONTACT WITH CONCRETE OR CMU SHALL BE PRESSURE
TREATED UNLESS AN APPROVED BARRIER IS PROVIDED. FRAMING ACCESSORIES AND STRUCTURAL FASTENERS SHALL BE
MANUFACTURED BY SIMPSON STRONG-TIE COMPANY(OR ENGINEER APPROVED EQUAL)AND OF THE SIZE AND TYPE SHOWN ON THE
DRAWINGS AND ATTACHED PER MANUFACTURER'S REQUIREMENTS AND RECOMMENDATIONS UNLESS NOTED OTHERWISE. HANGERS
NOT SHOWN SHALL BE SIMPSON HU OF SIZE RECOMMENDED FOR MEMBER. ALL FRAMINGNAILS SHALL BE COMMON NAILS. NO BOX
NAILS ALLOWED. FASTENERS AND ACCESSORIES IN CONTACT WITH PRESERVATIVE TREATED WOOD MUST BE HOT DIPPED GALVANIZED
OR HAVE 7MAX COATING.
MECHANICAL:
TIIE CONTRACTOR SHALL COORDINATE SEISMIC RESTRAINTS OF ELECTRICAL EQUIPMENT,MECHANICAL,PLUMBING,FIRE SPRINKLER,
MACHINERY,AND ASSOCIATED PIPING WITH THE STRUCTURE. ANY CONNECTIONS TO STRUCTURE NOT CONFORMING TO SHEET METAL
AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION(SMACNA),OR SPECIFICALLY DETAILED ON THE MECHANICAL
ENGINEER'S DRAWINGS,SHALL BE DESIGNED IN ACCORDANCE OF THESE GENERAL NOTES,BY AN ENGINEER REGISTERED IN THE STATE
OF OREGON,AND SHALL BE SUBMITTED TO THE ENGINEER PRIOR TO FABRICATION.
FLASHING AND WATERPROOFING: -
ALL FLASHING AND WATERPROOFING SHATL.BE BY OTHERS UNLESS NOTED OTHERWISE ON THE PLANS.
TM RIPPEY 12000 SW GARDEN PL. - SUITE 12178 - RTU
By: JW Data: 10445
1 X 1 Consulting Engineers
7650 SW Bcvcland Street Chic By: Date:
Suite 100
Tigard,Oregon 97223 Job it; 15259__ _
Phone:(503)443-3900 shoot: Ni Of,
r
E»u \� ,w/
, �
y
Fa
r
ti
EXISTING K'1'U
AND CURB TO BE �� "�'
REPLACED WTIH (E)4x14 PURLINS„
�� 81011 O/C• � �. a:/;v�, � Y
NEW RTU AND o `° : � �'
CURB,SEE 1ISK2 :�:�
(E)GL BEAMS Cc,
�a 77,''-4-' �� �„
46%
; ... 4
+r�A
is
WNµ
e
n?
1 SITE PLAN
.,K1
7
/T TM RIPPEY BY �1 W DATE
\]L/11. CONSULTING ENGINEERS 12000 SW GARDEN.PL. - SUITE 12178 - RTU CHKBY DATE
7650 S.W.Beveland St,Suite 100
JOB NO 15259
Tigard,Oregon 97223
Phone(503) 44--3900 SHEET SK1 OF
N
NEW RTU(BY SUPLLIER)
WEIGHT(INCLUDING CURB)=584 LBS.
ALIGN CURB EDGES OVER EXISTING
FRAMING AS SHOWN. FOR EXACT
LOCATION SEE MECHANIAL PLANS. •
EXISTING 4x
PURLINS @ 8'-0" O/C. EXISTING GLULAM BEAM
I
I
EXISTING 2x > I TYP.
SUB-PURLINS
@ 2'-O" 0/C. I
NEW 4x8 HEADER UNDER
SHORT EDGE OF UNIT CURB.
NEW 4x8 HEADER UNDER UNIT HANG AT EACH END WITH
CURB. HANG FROM EXISTING SIMPSON LUS48 HANGER.
PURLINS WITH SIMPSON LUS48 CUT EXISTING SUB-PURLINS
HANGER. AS NECESSARY AND HANG
_ FROM NEW HEADER WITH
SIMPSON LUS HANGER.
NOTES:
-INSTALL ALL FRAMING PRIOR TO INSTALLING CURB.
-ALL WATERPROOFING IS BY OTHERS.
-SEE MECHANICAL PLANS FOR ALL OTHER INFORMATION.
FRAMING PLAN AT RTU
AMEN=T
TM RIPPEY BY J W DATE
CONSULTING ENGINEERS 12000 SW GARDEN.PL. -SUITE 12178- RTU CHK BY DATE
7650 S.W. Beveland St,Suite 100 JOB NO 15259
Tigard,Oregon 97223
Phone(503) 443-3900 SHEET Sf OF
S
3..t-‘,t
EQ. SPACED ,
MECANICAL UNIT 1113016,-1 WAYS
BY OTHERS TYP. Ir(
16 GA. CLIPS W/ (S)
*10 TEK SCREWS PER 16 GA. CLIP
CLIP, (4) CLIPS REQ'D. N.T.S.
SEE PLAN VIEW FOR 1 • A
CLIP LOCATION I'-0", TYP.II t t ij _I
WOOD BLOCKING �A
CLIP
REQUIRED LOCATION
(4) TOTAL
FLASHING AND INSULATION MECH. UNIT
NOT SHOWN FOR CLARITY OUTLINE
WATERPROOFING BY OTHERS PLAN VIEW
N.T.S.
CENTER CURB ON NEW
PROVIDE *Im SCREWS OR EXISTING STRUCTURAL
1'-0" 0/C AND AT 6" FROM MEMBER
ENDS OF CURB. MINIMUM 112" 1
Ali EMBED INTO STRUCTURAL
MEMBER, TYP.
a- CT I O\ AT Cum
SK3 RTU-01 SCALE: 11/2" = 1'-0"
1M K TM RIPPEY BYJW DATE
CONSULTING ENGINEERS 12000 SW GARDEN PL. - SUITE 12178 - RTU CHK BY DATE
7650 SW Beveland,Suite 100
Tigard,Oregon 97223 JOB NO 15259
Phone: (503)443-3900
Fax:(503)443-3700 SHEET SK3 OF
f
* 1veC1\• UNi
tJG, "o 4r Wy n 9 ti3Z T2-IA, •
C,tAJtJ WV. it(
/(R)1 Gt. �Jg�tG
. I S At,r,eJJ pall E P )e/Ni (E)6-t" 2"1
(Fi)P Aftki i ,o 11 I NF.+J h1 i4D(It
t„ x '/•3)(t& as) ' O(s€a)A c 1E-ie F
M: (10)(8) /$ = G bag
^�. FAtreA CAP4-C l Ft)/4 P1ANL (4Nr-s' (-4//WAIVER_
(O Pwect)i,, MDtrst ` ,s )((J t-a )(2,-o).7g-: 16000 F!b
Lt x14
St,-rttW )(to '(ally -4 ° , TAFCLFA"
C S"Zv Att,owfry k.
'k�r$I, 3oa
oL r 1+ r.EC h 33( 0". rJ !. ckbAsE 214-
C.-I'kClt � ��sa c� �� 10-)/>s r
I,+ Mai- DANCrc,reo AS C-c�MA
IO1NCrak.. kd Fitt. r-G^4N • / S. L „e,o/) L -sr vii
AFPE.41,wa
• I1 t Nc CAP C'/ = 32-porr
oJ!
. () at, aE44,. Gents ASS o -STEcxr-u/V OK
tAfi y-L, ' SEE_ Pp g vtDIn f
TM RIPPEY BY ,-.374 DATE
CONSULTING ENGINEERS 12000 SW GARDEN PL. - SUITE 12178 - RTU CHK BY DATE
7650 S.W. Beveland St, Suite 100 SOB N015259
Tigard,Oregon 97223
Phone(503) 443-3900 SHEET C( of
De..i 1Maps Summary Report http://ehpl-earthquake.cr,usgs.gov/designmaps/us/summary,php?tempi.,
UW Design Maps Summary Report
User-Specified Input
Building Code Reference Document 2012 International Building Code
(which utilizes USGS hazard data available In 2008)
Site Coordinates 45.432°N, 122.763°W
Site Soil Classification Site Class D -"Stiff Soil"
Risk Category I/II/III
i
I i S000m }{t iI ,,eel�B avter'tgn $�E F `tk X ti 'r lr
E ; a - Px ) k i f ?7A's^st x' s v✓FS JJa f C g :„
/ i } A. • G t F �1 t R+ i
3 s ^22 f : 3Nit3
I ii `Tsi G I3f '3'z :h
s ': ' J>ss ^" : x•%.FL: ... fk~J / w E ki Iy k { i 1f yg
2� t * fj x t s a f s 3 k&"Npo �}
f.s1Y y °c 3 Z Y
s c i �: s k.s i Z k s
Y k , aCvfx31# „r f� '� �1 x .� i
/
3 a �CT3kkf Q i 5 i / Y s a 1,9;:.,,,,9:::...
rk 3 " k t V
/ k f 3 l i �"` /i x i3 . 3 r , k`:R ` Y K t
` c z v,� C S i�4 , 0,4 r. yn 3.^ > c� _ P �� s F / fl,f ; 3r% t i r } Jt
1 Jf F 'i ox f k> k 1{iIITy p Y: # Zf _e :: t :f k -7r _ s f Xx, ,F , Y
r 3 F l e .J 7`4 (J .R C`' FxJ x t hr,t [ R /
K 8 Gty � ha , /� k T ks i EE C [ x t C
0.- A l 5 E Ri C
f .
/ df E sat I `.': .
F E; ;?�
:x.5 ma uiFsk E r >.. 'A>'Y.Ui in '�5�� to a1 k A, k� t /
o_.�Y i
:. .i .... < ..:: ....... .. '. .:'.' } T�.': ...... ....J........ I�iL :.: .......,.}� ....
<�IwapQueAt;;
USGS-Provided Output
SS = 0.975 g SMS = 1.083 g SDS = 0.722 g
S1 = 0.423 g SMl = 0.667 g Sol = 0.445 g
For information on how the SS and Si values above have been calculated from probabilistic(risk-targeted) and
deterministic ground motions in the direction of maximum horizontal response, please return to the application and
select the "2009 NEHRP"building code reference document.
MCER Response Spectrum Design Response Spectrum
0.89
1.10 0.00
0.99 0.72 •
0.99 0.64
0.77 0.56
in 0.6G 03 0.49
0.55 f Eil 0.40 t
0.44 0.32
0.33 • 0.24
0.22 0.16
0.11 0.00
0.00 0.00
0.00 0.20 0.40 0.60 0.00 1.00 1.20 1.40 1.60 1.00 2.00 0.00 0.20 0.40 0.60 0.90 1.00 1.20 1.40 1.60 1.20 2.00
Period, T(sec) Period,T(sec)
Although this information is a product of the U.S.Geological Survey,we provide no warranty,expressed or implied,as to the accuracy of
the data contained therein.This tool Is not a substitute for technical subject-matter knowledge.
C@,
Wind and Seismic Loads on Mechanical Unit
Worksheet Calculates the wind and seismic forces for a rooftop mounted mechanical unit based
on the ASC E 7-10. Hold down forces are calculated based on 0.6D + (0.6W or 0.7E) load cases.
Wind and Seismic Loads on Mechanical Unit
Windspeed:= 120mph
Exposure:= "B"
Vasd'= "rio (Is wind speed ASD?)
Seismic Parameters
SDS•_ .722
ap := 2.5
Rp := 6.0
IE:= 1.0
Building Dimensions
Category:_ "II"
Roof Elevation:= 16ft Building_Width:= 441ft Building_Depth:= 118ft
Mechanical Unit Dimensions
Displacement:= "Fan Unit"
Weight:= 4901b
UnitHeight:= 33in
Width:= 44in
Length:= 74in
Curb:= 14in
Curb_Width:= 37in (Dimension for Calculating Overturning Uplift)
SUMMARY(ALL VALUES ARE ASD) Method Used= "ASCE 7-10-Section 29.5.1"
D= 490 lb _ WWindUpliftASD= 409 lb
Displacement= "Fan Unit" (From ACSE 29.5-3)
�___ EASD= 1241b
=2.542 ft
eismic �— WWindASD = 553 lb
(From ACSE 29.5-2)
/r.
hWind= 1.958ft
X= 3.083ft �
TWindTotalASD= 408 lb
Notes: TseismicASD= –45 lb
1.Positive sign convention shown. Negative values indicate opposite direction
2.X equals the width between attachment points for overturning rEalk
ppokiat OAFS PA COP-NE-R- Uat- 11) CAT (AY CO&Ca,#A-,S S VAR. Fort Gipt,ey-r-
(wo2/3)f it scram,s z' 51*/U ,,s FAR Of /46,A 44 v....
(W?J Flr-,1-4. Assn A-4 a 10 ScR,t,_,s C 1'.�..,fie I1,0„
1r � ttv
(l,6,)( l(,)r �g�a 't• )( )(IS5)° S 1�`/ (,�')Sc, :t-�.-15 i }` k-
��I//yJ l�< i'S (J4 St/i-C,1A p+i C iFS Pi.,t vo ` ':J
582J
GAS HEAT/ELECTRIC COOLING Lbryant
SINGLE PACKAGED ROOFTOP 14 SEER
3 TO 5 NOMINAL TONS
Heating&Cooling Systems
Product Data
i JEGACYTM
L I N E
tEGA(
' 1117
j _ n
PliroP
C08515
(Shown with optional Louvered Hail Guard)
(f_) ASHRAE
Peron COMPLIANT
MODEL NUMBER NOMENCLATURE
Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Example: 5 8 2 J E 0 6 A 0 7 2 AOB O AA
Unit Type Packaging and Control
582-Gas Heat RTU,Legacy Series A= Standard Packaging,electro mechanical
controls that require W7212 EconoMi$er IV
Model B= LTL Packaging,electro mechanical
J - Puron®(R-410A)Refrigerant controls that require W7212 EconoMi$er IV
C= Standard Packaging,electro mechanical
controls that require W7220 EconoMi$er X
Voltage F = LTL Packaging,electro mechanical
E = 460-3-60 controls that require W7220 EconoMi$er X
J = 208/230-1-60
P = 208/230-3-60 Factory Installed Options
T = 575-3-60
OA =None
NOTE:See the 582J 3 to 5 ton Price Pages
Cooling Tons for a complete list of factory installed
N 04- 3 tons options.
co
05- 4 tons
06- 5 tons
Outdoor Air Options
A= None
Refrig.System/Gas Heat Options B = Temperature Economizer, Barometric Relief,
A= Standard One Stage cooling models/Nat.Gas Heat Standard Leak(W7212 or W7220)
B = Standard One Stage cooling models/Low NOx Heat E = Temperature Economizer, Barometric Relief,
C= Standard One Stage cooling models/SS HX Heat Standard Leak w/CO2(W7212 or W7220)
G= One-Stage cooling models/Alum Heat Exchanger H= Enthalpy Economizer,Barometric Relief,
with Perfect Humidity TM' Standard Leak(W7212 or W7220)
H = One-Stage cooling models/Low NOx Heat L = Enthalpy Economizer,Barometric Relief,
with Perfect Humidity Standard Leak w/CO2(W7212 or W7220)
J = One-Stage cooling models/Stainless Steel Exchanger Q= Motorized 2 Position Damper
with Perfect Humidity U= Temperature Economizer,Barometric Relief,
Ultra Low Leak(W7220)
Heat Level Input W= Enthalpy Economizer,Barometric Relief,Ultra Low Leak
•
Standard/Stainless Steel (1M220)
072=72,000
115=115,000 Indoor Fan Options
150=150,000 0 = Direct Drive ECM
Low NOx 2 = Medium Static Option
060=60,000 3 = High Static Option
090=90,000
120=120,000 Coil Options(RTPF)(Outdoor-Indoor-Hail Guard)
A= Al/Cu-Al/Cu
B= Precoat Al/Cu-Al/Cu
Note:On single phase(J)voltage code)models,the C= E-coat Al/Cu-Al/Cu
following are not available as a factory installed option: D= E-coat Al/Cu-E-coat Al/Cu
-Perfect Humidity E = Cu/Cu-Al/Cu
-Coated Coils or Cu Fin Coils F = Cu/Cu-Cu/Cu
-Louvered Hail Guards M= Al/Cu-Al/Cu—Louvered Hail Guard
-Economizer or 2 Position Damper N= Precoat Al/Cu-Al/Cu—Louvered Hail Guard
-Powered 115 Volt Convenience Outlet P= E-coat Al/Cu-Al/Cu—Louvered Hail Guard
Q= E-coat Al/Cu-E-coat Al/Cu—Louvered Hail Guard
R= Cu/Cu-Al/Cu—Louvered Hail Guard
S = Cu/Cu-Cu/Cu—Louvered Hail Guard
C14337
4
Table 2-AHRI COOLING RATING TABLE
NET
NOM. TOTAL
UNIT COOLING CAPACITY COOLING POWER SEER EER
STAGES (TONS) CAPACITY
(MBH)
582J*04 1 3 35.4 3.0 14.0 12.00
582J*05 1 4 47.5 4.0 14.0 12.00
. 582J*06 1 5 58.5 4.9 14.1 12.00
LEGEND NOTES:
AHRI - Air Conditioning,Heating and Refrigeration 1. Rated in accordance with AHRI Standard 210/240.
• Institute Test Standard 2. Ratings are based on:
ASHRAE - American Society of Heating,Refrigerating Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor
and Air Conditioning,Inc. air temp and 95°F(35°C) db outdoor air temp.
EER - Energy Efficiency Ratio 3. All 582J units comply with ASHRAE 90.1 Energy Standard for
SEER - Seasonal Energy Efficiency Ratio minimum SEER and EER requirements.
4. 582J units comply with US Energy Policy Act (2005). To
evaluate code compliance requirements, refer to state and
local codes.
N AI9R CERTIFIED.
USLo www.anrdirectory.org
Use of the AHRI Certified
TM Mark indicates a
manufacturer's
participation in the
A IRAE program For verification
of certification for individual
products,go to
www.ahridi rectory.org.
COMPLIANT
Table 3-HEATING RATING TABLE - NATURAL GAS & PROPANE
AL/SS HEAT EXCHANGER THERMAL
TEMP RISE AFUE
UNITS GAS HEAT INPUT/OUTPUT INPUT/OUTPUT (DEG F) EFFICIENCY (%)
STAGE 1 (MBH) STAGE 2(MBH) (/)
LOW - 65/50 25- 55 82.0% 81.0%
04 MED - 90/73 45- 85 82.0% 81.5%
a)
HIGH - - - - -
t LOW - 65/50 20- 55 82.0% 81.0%
O.
m 05 MED - 90/73 30- 65 82.0% 81.2%
_c HIGH - 130/105 45- 80 82.0% 81.0%
rn LOW - 65/50 10- 55 82.0% 81.0%
06 MED - 90/73 25- 65 82.0% 81.2%
HIGH - 130/105 35- 80 82.0% 81.0%
LOW - 72/56 25- 55 82.0% N/A
04 MED 82/66 115/89 55- 85 80.0% N/A
d
HIGH - - - - -
as LOW - 72/56 25- 55 82.0% N/A
r
w 05 MED - 115/90 35- 65 81.0% N/A
2 HIGH 120/96 150/117 50- 80 80.0% N/A
~ LOW - 72/56 20- 55 82.0% N/A
06 MED - 115/90 30- 65 81.0% N/A
HIGH 120/96 150/117 40- 80 80.0% N/A
NOTES:
Heat ratings are for natural gas heat exchangers operated at or below 2000 ft (610 m).For information on propane or altitudes above 2000 ft
(610 m),see the Application Data section of this book,Accessory Propane/High Attitude kits are also available.
In the USA the input rating for altitudes above 2000 ft(610m)must be derated by 4%for each 1000 ft(305 m)above sea level.In Canada,
the input rating must be derated by 10%for altitudes of 2000 ft(610 m)to 4500 ft(1372 m)above sea level.
8
Table 6—MINIMUM - MAXIMUM AIRFLOW RATINGS- NATURAL GAS & PROPANE
HEAT COOLING AL HX HEATING SS HX HEATING
VOLTAGE UNIT LEVEL
MINIMUM MAXIMUM MINIMUM MAXIMUM MINIMUM MAXIMUM
LOW 900 1970 900 1970
582J*04 MED 900 1500 800 1520 800 1520
HIGH - - - -
LOW 900 2470 900 2470
SINGLE 582J*05 MED 1200 2000 1050 2280 1050 2280
PHASE
HIGH 1230 2190 1230 2190
LOW 900 3290 900 3290
582J*06 MED 1500 2500 1050 2730 1050 2730
HIGH 1230 2820 1230 2820
LOW 990 2190 990 2190
582J*04 MED 900 1500 1000 1550 1000 1550
HIGH - - - -
LOW 990 2190 990 2190
inTHREE PHASE 582J*05 MED 1200 2000 1330 2460 1330 2460
HIGH 1390 2220 1390 2220
LOW 990 2730 990 2730
582J*06 MED 1500 2500 1330 2880 1330 2880
HIGH 1390 2780 1390 2780
10
Table 7-PHYSICAL DATA (COOLING) 3 - 5 TONS
582J*04 582,11*05 582J*08
Refrigeration System
• #Circuits/#Comp./Type 1/1/Scroll 1/1/Scroll 1/1/Scroll
Puron®refrig.(R-410A)1 phase (Ibs-oz) 7.1 10.5 16.0
Puron®refrig.(R-410A)3 phase (lbs-oz) 7.1 10.5 14.5
Perfect Humidity Puron®refrig.charge(lbs-oz) 10.4 15.3 26.0
Metering Device(A) Acutrol Acutrol Acutrol
Perfect Humidity Metering Device(B) Acutrol+TXV Acutrol+TXV Acutrol+TXV
High-press.Trip/Reset(psig) 630/505 630/505 630/505
Low-press.Trip/Reset(psig) 54/117 54/117 54/117
Compressor Capacity Staging(%) 100% 100% 100°%
Evap.Coll
Material(Tube/Fin) Cu/Al Cu/Al Cu/Al
Coil type 3/8-in RTPF 3/8-in RTPF 3/8-in RTPF
Rows/FPI 3/15 3/15 4/15
Total Face Area(ft2) 5.5 5.5 7.3
Condensate Drain Conn.Size 3/4-in 3/4-in 3/4-in
Perfect Humidity Coll
Material(Tube/Fin) Cu/Al Cu/Al Cu/Al
Coil type 3/8-in RTPF 3/8-in RTPF 3/8-in RTPF
Rows/FPI 1/17 2/17 2/17
Total Face Area(ft2) 3.9 3.9 5.2
Evap.Fan and Motor
Motor Qty/Drive Type 1/Direct 1/Direct 1/Direct N
Standard Max BHP 1 1 1 u)
Static RPM Range 600-1200 600-1200 600-1200
1 phase Motor Frame Size 48 48 48
Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
L Fan Diameter(in) 10 x 10 10 x 10 10 x 10
Motor Qty/Drive Type 1/Belt 1/Belt 1/Belt
Max BHP 1.2 1.2 1.2
Medium RPM Range 560-854 560-854 770-1175
Static Motor Frame Size 48 48 48
1 phase Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
L Fan Diameter(in) 10 x 10 10 x 10 10 x 10
Motor Qty/Drive Type 1/Belt 1/Belt 1/Belt
High Max BHP 1.5 1.5 1.5
Static RPM Range 770-1175 770-1175 1035-1466
1 phase Motor Frame Size 56 56 56
Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter(in) 10 x 10 10 x 10 10 x 10
Motor Qty/Drive Type 1/Direct 1/Direct 1/Direct
Max BHP 1 1 1
Standard RPM Range 600-1200 600-1200 600-1200
Static Motor Frame Size 48 48 48
3 phase Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter(in) 10 x 10 10 x 10 11 x 10
Motor Qty/Drive Type 1/Belt 1/Belt 1/Belt
Max BHP 1.7 1.7 2.9
Medium RPM Range 770-1175 920-1303 1035-1466
Static Motor Frame Size 48 56 56
3 phase Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter(in) 10 x 10 10 x 10 10 x 10
Motor Qty/Drive Type 1/Belt 1/Belt 1/Belt
High Max BHP 2.9 2.9 2.9
Static RPM Range 1035-1466 1208-1639 1303-1687
3 phase Motor Frame Size 56 56 56
Fan Qty/Type 1/Centrifugal 1/Centrifugal 1/Centrifugal
Fan Diameter(in) 10 x 10 10 x 10 10 x 10
Cond.Coll
1 phase Material(Tube/Fin) Cu/Al Cu/Al Cu/Al
Coil type 3/8-in RTPF 3/8-in RTPF 3/8-in RTPF
Rows/FPI 1/17 2/17 2/17
Total Face Area(ft2) 16.5 16.5 21.3
3 phase Material(Tube/Fin) Cu/Al Cu/Al Cu/Al
Coil type 3/8-in RTPF 3/8-in RTPF 3/8-in RTPF
Rows..Fins/in. 1/17 2/17 2/17
Total Face Area(ft2) 16.5 14.6 18.8
Cond.fan/motor
Qty/Motor Drive Type 1/Direct 1/Direct 1/Direct
Motor HP/RPM 1/8/825 1/4/1100 1/4/1100
Fan diameter(in) 22 22 22
Filters
RAFilter#/Size(in) 2/16x25x2 2/16x25 x2 4/16x25x2
OA inlet screen#/Size(in) 1/20 x24 x 1 1/20 x 24 x 1 1/20 x 24 x 1
11
Table 9-PHYSICAL DATA (HEATING - THREE PHASE UNITS) 3 - 5 TONS
582JE/P/T04 582JE/P/T05 582JE/P/T06
Electrical
Three Phase Three Phase Three Phase
Gas Connection
#of Gas Valves 1 1 1
Nat.gas supply line press(in.w.g.)/(PSIG) 4—13/0.18—0.47 4—13/0.18—0.47 4—13/0.18—0.47
LP supply line press(in.w.g.)/(PSIG) 11 —13/0.40—0.47 11 —13/0.40—0.47 11 —13/0.40—0.47
Heat Anticipator setting(Amps)
1st stage 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14
Natural Gas Heat
#of stages/#of burners(total) 1/2 1/2 1/2
Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT
LOW Rollout switch opens/closes 195/115 195/115 195/115
Temperature Rise 25—55 25—55 20—55
#of stages/#ofburners(total) 1or2/3 1/3 1/3 N
Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT c0
MED Rollout switch opens/closes 195/115 195/115 195/115 in
Temperature Rise 55—85 35—65 30—65
#of stages/#of burners(total) — 1 or 2/3 1 or 2/3
Connection Size — 1/2—in NPT 1/2—in NPT
HIGH Rollout switch opens/closes — 195/115 195/115
Temperature Rise — 50—80 40—80
Liquid Propane Heat
#of stages/#of burners(total) 1/2 1/2 1/2
Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT
LOW Rollout switch opens/closes 195/115 195/115 195/115
Temperature Rise 25—55 25—55 20—55
#of stages/#of burners(total) 1 or 2/3 1/3 1/3
Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT
MED Rollout switch opens/closes 195/115 195/115 195/115
Temperature Rise 55—85 35—65 30—65
#of stages/#of burners(total) — 1 or 2/3 1 or 2/3
Connection Size — 1/2—in NPT 1/2—in NPT
HIGH Rollout switch opens/closes — 195/115 195/115
Temperature Rise — 50—80 40—80
Low NOx Gas Heat
#of stages/#of burners(total) 1/2 1/2 1 /2
Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT
LOW Rollout switch opens/closes 195/115 195/115 195/115
Temperature Rise 20—50 20—50 15—50
#of stages/#of burners(total) 1/3 1/3 1/3
Connection Size 1/2—in NPT 1/2—in NPT 1/2—in NPT
MED Rollout switch opens/closes 195/115 195/115 195/115
Temperature Rise 30—60 30—60 25—60
#of stages/#of burners(total) — 1/3 1/3
Connection Size — 1/2—in NPT 1/2—in NPT
HIGH Rollout switch opens/closes — 195/115 195/115
Temperature Rise — 40—70 35—70
— Not applicable
13
582J
NOTES: 0 Jul TED P.O.LOS Am THIS MAW IS INN 1.10•710 Of CAMEO CaPONATIM OUNISS ION a T[S[118.1105 a IOCU1N Ira
TECHNOLOGIES STIKUNE.n AND IS MAINIFI UPON NC MISS CONDITION it TN[ IONS qT C015TITUT[POT P111ONMK1 a
I. DIMENSIONS-ARE IN INCHES. DIMENSIONS COUNTS R■nS IN II a CONSENT 51 UM I/OS unm
IN I I ARE IN MILLIMETERS. UNIT J X It PHASE) K 13 PHASE) CARRIER oral CaPg8n01 S enru CONSENT KCVTAIN[a 10011101.
582J 04 33 3/8 II 7/8 14 7/8
2. CENTER OF GRAVITY 18171 [3771 13171
73 J/8 II 1)8 IB SIB CONNECTION SIZES
5821 OS 18171 13771 11721 A 1 3/8' [351 DIA FIELD POWER SUPPLY HOLE
3. Op,DIRECTION OF AIR FLOW
41 3/8 14 7/8 18 5/8 '
582J 06 110511 (3711 11721 B 2' 1501 DIA POWER SUPPLY KNOCKOUT
C 1 3N' 1511 DIA GAUGE ACCESS PLUG
0 i/B' 1221 DIA FIELD CONTROL WIRING HOLE
33-3/8
18181 E 3/1'-14 NP1 CONDENSATE DRAIN
F 1/2'-14 PI GAS CONNECTION
• 1 G 2 1/2 ' 1611 DIA POWER SUPPLY KNOCKOUT
32-1/4 E ECONOMIZER HOOD
18181 (OPTIONAL) 16
[4061
FILTER ACCESS PANEL I THRu.THE.BASE CHART
Ii00l L[S51 COMP, THESE HOLES REQUIRED FOR USE
• • • ACCESS CONDENSER CRBTNPWROOTA01, 003801
•PANEL I COIL ,� •• .L
THREADED WIRE REO'D HOLE
INDOOR COIL- J - - _ I CONDUIT SIZE USE SIZES IMAK.I (0:
ell
ACCESS PANEL I �� �1 ■ I/2' ACC. 1/8' 122.21 �/d
C 25.5/8 10-7/8 ' X 1/2' 240 1/8' 122.21- (n
I— O I _ _ ITnllli N' RETURN 16521 AIR 12171 RETURN
N 1 •_ 3/1' 1001,0031 POWER 1 1/8' 128,11
1 —— p 1AIR 2•• 10031 1/2' FPT GAS 1 3/16' 130.01
1/ '-n 111171 I FOR'TXRU-THE-BASEPAM FAC TORT OPTION,
•2.5/8--I „__„__�� FITTINGS FOR ONLY 0,1, 6 2 ARE PROVIDED BACK [611 l�J
111.
�� E ALT. I • SELECT EITHER 3/A'OR v2' I■1
y CURB W CONDE NSA IE 17-3/I ' FOR POWER, DEPENDING ON WIRE SIZE /�
O WIDTH 1 - 1 DRAIN OPENING [4511 29 3/8 ,. 10011 PROVIDES 3/4'FPT THOU CURB y
., I 1 J ,Z SUPPLY •- 26-1/2 17171 SUPPLY
FLANGE I FITTING.
co; 18.1/8 I AIR 16731 xy
11591 AIR
161/8 111/1 12-1/1
cc
14111 [3831 13121 SEE THRU THE 6.1/4 ,� c CA
11 I I BASE CHART \ •, e •[1511 • •-
A _
3-3/6
PC)
1 121/8 -- [55)
G 25 fLUE
- 1707]
CA 16361 11 DDI HOOD 18.1/2
I, T K TOF 11701
t0-1/2 N
1-1
11181 [2651
4
1321
1118] ril
,." EL EC IR IC AL
O •I ——_ DISCONNECT U. .1 L-I
Ar, I I LOCATION ����
Cr
N CONDENSER
COIL �I ACCESSLPANEL ACCESS BLOWER •
CONDFMSATDE FILTER hNN�I gig
221 EM-- --DRAIN _ O
11. . • J ii,I. __ 2531/8 OUTSIDE
1 [6381
OPTIONAL —_ I I 16-1/4 RETURN AIA
I INSTALLED _- , II 19-1/2 OPTIONAL
FACTORY ANDLE 1181/8 I
SUPPLY AIR I AIR
FACTORY
I [1911 INSTALLED 1 12891 I 7I
LI OUTLET — DISCONNECT — /1721-1/1 II EEL Eg ' • I _ [5191
11681 }7 1-516
�� =�8 6-5/B �(.](.] I �. (] �+ 11551 �! 1■
193/4 HANDLE 8.3/8 I 6-5/8 1 t 6 4
1951 16-3/1 - 3081/8 12131 [1691 [1771 11521
111871 [7611
7 4-318 _ 26.7/8
116881 16821 31-111 BAROMETRIC
17931
RELIEF
LEFT FLOW SUPPLY suvv
FRONT AIR RETURN
RIGHT AIR
0N[T DATE SUP[IC[ICS 582J 04-06 SINGLE ZONE ELECTRICAL RID
1 OF 2 08-14-14 - COOLING WITH GAS HEAT 48KC000284 _
c)
A
IV
v
0
UNITED P.O.DOS ODOR THIS DOCUMENT IS THE PROPERTY Or CARRIER CORPORATION SUBNISSIOR OF THESE DIANINOS OA DaUHEHTS
TECHNOLOGIES SHRKUSE.NT D IS DEUOERED UPON THE UPSETS CONDITION THUS THE DOES NOr COf TUASUE HADI GS OORIUNCE NR
STD. UNIT CORNER CORNER CORNER CORNER C G HEIGHT CARRIER 13221 CORPORAT.13E NO1 BE DINCSONED ON usm NIix0U1 uxneM Acc[ruNCE or canACr.
UNIT
WEIGHT WEIGHT 1A1 WEIGHT 1BI WEIGHT ICI WEIGHT EDl CORPORATION'S n1rrEN CasnT.
LBS. KG. LBS. KG. L85. KG. LBS. KG. LBS. KG. X -7 Z
582J 04 498 222 120 54 111 50 125 56 135 61 _ 35 3/4 19081 24 3/4(6281 18 7/8(1191
582J 05 544 246 130 58 126 57. 142 64 146 66 36 3/4 (9331 21 3/4(6281 18 7/8(1791
582J 06 597 270 141 64 156 70 158 71 142 64 39 1/8(9931 23 1/2(5971 20 1/8(5111
•STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING.
FOR OTHER OPTIONS AND ACCESSORIES. REFER TO THE PRODUCT DATA CATALOG.
CORNER A CORNER B
111111 /^\\�. tO
oil
M
1 o1
3 x
y I 1
. • . •
a
CC Pt)
IN CORNER D CORNER C
0
I TOP ~y
C's
W5 M
1T I. •• VI
N ICI
C
IN
•
{
Z
„_...
_.
-- 51=
,..., J.
•
, 1 •
iL OO f •=•: : 0
FRONT
SHEET DATE SUNEIC(DES 582J 04-06 SINGLE ZONE ELECTRICAL Kr
2OF2 08-14-14 - COOLING WITH GAS HEAT 486C000284 _
_0
A
N
V
582J '
M '
• •
ROOF CURB A NOTES CONNECTOR PKG.ACC. GAS CONNECTION TYPE GAS FITTING POWER WIRING CONTROL WIRING ACCESSORY CONVENIENCE
ACCESSORY r 1.ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED. FITTING FITTING OUTLET WIRING CONNECTOR
2.INSULATED PANELS:25.4(11 THK.POLYURETHANE FOAM,44.511-3/41 B DENSITY. --- •
CRRFCURB001A01 14 3.DIMENSIONS IN()ARE IN MILLIMETERS. CRBTMPWROO1A01 THRU THE CURB 3/4.119)NPT
- (3`56) 4.ROOFCURB:18 GAGE STEEL.
5.ATTACH DUCTWORK TO CURB.(FLANGES OF DUCT REST ON CURB). - 3/4"(19)NPT 1I2 112.71 NPT 1/2"(12.71 NPT
CRRFCURBOO2A01 (B U) 6.SERVICE CLEARANCE 4 FEET ON EACH SIDE. CRBTMPWR003A01 THRU THE BOTTOM 1I2.112.7)NPT
7.EM43> DIRECTION OF AIR FLOW.
8.CONNECTOR PACKAGE CRBTMPWROOIA01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
1.3/4" 11 1
(44.51
21.00'
5.42" 1 11.96' - 125.4)
-� 11 3/4"(298.51 WIDE
[137.7] (303.81 INSULATED DECK PANELS,
1 l L "A" IIZI�y
252• W
552.2.2) v]
8 9/161217.5]WIDE
I INSULATED DECK PANEL 1: A
N I-314'
00 , I \ (44.4]
2 I 1'4-13/16" H SEE NOTE R2 `'J
4�• J SECTION E-E GAS SERVICE PLATE W I INSIDE �(
(126.01 70.87" SCALE 0.250 THRU THE CURB j4.. (63' /1 A v `1 1(1800.2) �, D]50.8](il :'� 2"SEE ! MT�I C _ ASSEMBLYQF �� I w REQUIRED)^'9 r (SEE NOTE N8)r: RETURN AIR CA OPENING ` ,
R='S 15.19' (b 1/3/4144.5) /
= [385.8] E E
F3.oD- �z1.e4• /T 21°
C I I 176.2) 554.7) .._ .J � V
re
Q 32.19'
1 [en.e) VIEW"B" -
/��
1/1 r CORNER DETAIL
16.03' RETURN AIR - �'1-3/4'
755.6) SUPPLY AIR (407.2) \ [44.4]
4
(I1 1355.6] OPENING til
INN _445, z
INN JI 1-- �.
C 1.75' 1--20.41" „ -3.00' GASKE UNIT •A• `
p.
CA
144.51 (518.31 (76.2) (SUPPLIED WITH CURB) 01•C --13'78' AIL(FIELD SUPPLIED) /
p, 1350.01 % 5'7-3/B' O
40.69" [1711.3]
11033.51 DUC Z
TYPICAL(4)SIDES
(FIELD SUPPLIED) j 7/16•. 3'-1 3/16" `��
OUNTER FLASHING [944.6] ` / ."
- - (FIELD SUPPLIED) � �/
et
14 "
NG FELT SEE VIEW"BEKI
\
(FIELD SUPPLIED) N
CERTIFIED DRAWING
T STRIP
17.01 (FIELD SUPPLIED) `�
•ss, I� DRAWNGRELEASE LEVEL PRODUCTION
OO 'DOPING MATERIAL
\j (FIELD SUPPLIED) ////}}}}���� UNLESS OTHERWISE SPECIFIED
\ \ i THIRD ANGLE DIMENSIONS ARE IN INCHES•I / ] \\\\\\\\` PROJECTION MATERIAL TOLERANCES ON.
\ 1 DEL 3 DEC ]DEC ANG KOS
Reim q 7 �HC"q A
f- t- f- f-
i
AUTHORIZATION NUMBER TITLE i«E
SUPPLY AIR RETURN AIR\ / ` - 1041738
"IGIDINSULATION CURB ASY,ROOF
`�. (FIELD SUPPLIED) ENGINEERING MANUFACTURING (004-007)
ENGINEERING REOUIREMENTS - -- - SIZE DRAWING NUMBER REV
\\, OVERALL DIM.5'-7 3/8'WAS 5'-7 7/8:18GA 7-005.Y-002 DRAFTER CHECKER 48TC400
D 427 B
A A MATERIAL WA 16 GA.:NAIL FIELD SUPPLIED WAS 04/22/13 MMC - - 1067888 WEIGHT - MMC 06/17/11�- SHEET S OF 5
WITH CURB SURFACE FINISH MFCIPURCH MODEL (NTERNAL USE ONLY1 NEST DRAWING SCALE DISTRIBUTION
REV REVISION RECORD DATE BY CHILD AMID ECN NO. _ PURCH - N/A MMC
_n
W
W
0
582J