Report Ffs ),0 15-- 00o w 7 ✓ / ` S k ,t X REVIEWED REVISE AND RESUBMIT ID ELTA14795 S.W. 72"0 Avenue �' _REJECTED MAKE CORRECTIONS NOTED PORTLAND, OR 97224 Vendor is entirely responsible for performance of his PHONE 503-620-4020 FIRE, productis). Corrections or comments made on the 1 NC■ FAX 503-620-1058 shop drawings dunn this review do not relieve ■■ CCB# 64174 contractor from complance with requirements of the drawings and speciffications. This check is only for review of general conformance with the design concept of the protect and general compliance wrlh the information given in the contract documents- The contractor is responsible for. confirming and correlating all quantities and dimensions. selecting fabrication processes and techniques of construction coordinating work with that of all other trades; and performing work in a safe and satisfactory manner. VLMK CONSULTING ENGINEERS (503)222-4453 Date: 10/16/15By: JCS QCD Freezer Expansion RECEIVED OCT 19 2015 High Pile Storage , . Tigard, OR CITY OFTIGAKD BUILDING DIVISION DATA SUBMITTAL FOR FIRE PROTECTION SYSTEM October 5, 2015 DELTA FIRE, INC. PROJECT # 15-5400 FIRE PROTECTION CONTRACTORS QCD Freezer High Pile Storage October 5,2015 Page 2 of 2 TABLE OF CONTENTS Pipe & Fittings Steel Pipe Ductile Iron Screwed Fittings Victaulic Mechanical Tee Style#922 Hangers Anvil Ring Hanger Fig#69 Anvil Threaded Rod Sammy GST 20 Vertical Screw Sprinkler Heads Tyco Model DS-2, 11.2K, 1", 286 Degree Dry Chrome Pendent Hydraulic Calculations FIRE PROTECTION CONTRACTORS DELT 14795 S.W. 72od Avenue PORTLAND, OR 97224 PHONE 503-620-4020 FIRE, INC 6 4-1 058 . CCB# 641 } Pipe FIRE PROTECTION CONTRACTORS •- Ii —i a- I� — I- INUCf'CNIJ N I `� -= _=Pipe and Supply Corp. Pipe Specification A135 Specification A135 NPS 1/4--30", Schedules 10, 40 and XL THD, Lightwall Scope Covers two grades of electric resistance welded steel pipe. Grade A is adapted for flanging and bending and is suitable for welding. Purpose for which pipe is intended should be stated on order. Kinds of Steel Permitted Open-hearth Basic-oxygen For Pipe Material Electric-furnace Permissible Variations The minimum wall thickness at any point shall not be more than 12.5%under the nominal wall thickness specified. in Wall Thickness Threadable,lightwall(XL)must meet manufacturers minimums. Chemical C max% Mn max% P max% S max Requirements Seamless or ERW Grade A 0.25 0.95 0.05 0.06 Grade B 0.30 1.20 0.05 0.06 Tensile Grade A Grade B Requirements Tensile Strength,min.,psi 48,000 60,000 Yield Strength,min.,psi 30,000 35,000 NDE& Hydrostatic inspection test pressures for plain end and threaded are specified. Hydrostatic pressure shall be maintained Hydrostatic for not less than 5 seconds for all sizes of electric resistance weld pipe. Non-destructive electric test should be in accordance Testing with practices E213,method E227 or practice E213. Permissible Variations Plus or Minus 10%schedule 10 in Weights per Foot Plus 10%minus 3 1/2%schedule 40 Permissible Variations Plus or minus 1% in Outside Diameter Mechanical Tests Tensile Test--Transverse returned on pipe NPS 8 and larger. Specified Flattening test--Three steps required with weld located 0°or 90°from the line of direction of force required. Number of Flattening and tensile on one length of pipe from each lot of 400 lengths or less of a style. Tests Required Lengths Pipe shall be furnished in 38'with a minimum of 20 ft. Pipe furnished to schedule 10 shall be in a specified length between 16 and 22 ft. Required Markings Rolled,Stamped or Stenciled(Mfgrs.Option) on Each Length Name or brand of manufacturer. (On Tags attached to Kind of pipe,that is,electric-resistance welded A,electric welded B,same schedule wall thickness,schedule 10 or 40,NL each Bundle in case ASTM A135 of Bundled Pipe) Length of pipe. General End finish may be plain end beveled or plain end square cut. Information 90° ELBOW , z ANVIL: sii iaHV__ Ductile Iron MATERIAL SPECIFICATIONS ,,. .r Ductile iron threaded fittings are W. & ULC Listed & .. ; FM Approved for 500 psi service. 1'1,+ ' r Ductile iron per ASTM A536 Class 65-45.12, Dimensions conform to ASME B16.3 Threads are NPT per ANSI/ASME B1.20.1. NOTICE:Duchlc iron Fittings hove higher tensile strength than that of steel pipe.Therefore,over tightening can cove damage to pipe threads which may couse leakage.Ductile iron fittings should be tightened three turns beyond hand tight,but no more thin four Mn s E a FM Latta APPROVED 90° ELBOW to.t.trovnppoieOstey. n4Lnww.s site or*More N an.anwert oom or 05e44141 N MOT SLIM Beta senuin* Nominal Site Moo.Working Dimensions Approx- Pressure. A 8 Wt.Each AEIAt own) P51(APO h(marl M.lmmJ fEs.!fg! ,4 1 500 1.50 1.50 0.62 2:' 1y, 500 1.15 1.15 090 t �; ,. B ,. 14i 500 1.94 1.44 1.20 I ..}_ -I- 2 500 2.25 2.25 1.85 A-Woking Pressure Rcei gs ore for rehvencc only and based On Sch 10 pipe For the blest ULIULC. and FM pressure ratings versus pipe schedule.please visit arwihntl.corn or contact your local Anvil Reptesenlulive. r. 45° ELBOW = A!W!L �SPF/RNv � Ductile Iron MATERIAL SPECIFICATIONS 1 \ Ductile iron threaded fittings are UL & ULC Listed & FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-45-12. Dimensions conform to ASME B16.3 Threads are NPT per ANSI/ASME 81.20.1. NOTICE:Ductile.ran Finings have higher tensile strength Pion that of steel pipe.Therefore,over tightening con cause damage to pipe threads which may cause leakage.Ductile iron fittings should be tightened three turns beyond hand tight,but no more than Four turns c®w p Ma APPROVED Fa tiorovappoM°Arts rrta lnMStors. 45° ELBOW sac aY YnbMe Y www,mtra nom or atria n.e Mme'Sawa lUp ur.m.. Nominal Sire Max.Working Dimensions Approx. Pressure• A E Wt.Fork it immi PSI(APc In.fmm) M.(min) lbs.AO ',9: 1 500 i 1.12 1.12 0.46 500 129 1.29 073 A 1. 500 1 43 1.43 0.92 mr' • 2 500 1.68 1.6E 1.50 ti? ♦-Working Pressure Ror,ogs are For rerceence only and based on Sch.40 pipe for the latest US/ULC. and FM pressure rotirsgs versus pwpe schedule.please visit at vilintl.conr or contact your local Anvil Pepreienloliva. STRAIGHT TEE (nr ANVIL s /FINVI Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded fittings are UL & ULC Listed & FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-45.12, ��+` Dimensions conform to ASME B16,3 Threads are NPT per ANSI/ASME B1.20.1. NOTICE.Ductile iron fittings have higher tensile strength thon that of steel pipe.Therefore,o er tightening con cause domtoge to pipe threads which may cause leakage.Ductile iron fittings should be tightened three turns beyond band tight,but no more than four turns, c®w <% rte- APPROVED STRAIGHT TEE r"`"'"°y"°°'"°'t"""°`' camel an+r,.r seats RefpprYhlf Nominal Site Moe.Working Dimensions Approx. Pressure• A 8 Wt.Each rq inn r,! P51(kilt 6t.Germ h.(earth as,04) t o I 500 1.50 1.50 0.85 B 1— 500 1.15 115 1.22 L i- 1 50" 1.94 1.94 1.55 A--.--..--A_._•.I 2 500 2.25 2.25 2.45 •-Wori:ing Frr-swrr Rot ngs ore CO,rekeence only and based on Sch d0 pipe For the latest UL/ULC, and FM pressure sing:versus pipe schedule.please visit amnlintl.00m or contact your local Anvil Representative. BUSHINGS : ANv!L <CC<sPFi > Ductile Iron MATERIAL SPECIFICATIONS � ' Ductile iron threaded finings are UE & ULC Listed & 4w,,. ° _, ° , FM Approved for 500 psi service. `� pP P Ductile iron per ASTM A536 Class 65-45-12. Dimensions conform to ASME 816,14 __, Threads are NPT per ANSI/ASME 81.20.1. NOTICE:Ductile iron Fittings her a higher'ensile strength thou that of stool pipe Therefore,over tightening can cause damage ks pipe threods which may cause teokoge.Ductile iron fittings should be tightened three turns beyond hand tight,but no more than Four turns. C®14 FM L*IU APPROVED r cy lni*gvAn4vorF Onlawfs•rdLnfinkr, nu oar riebsR.e fe amrieti corn a rxrxr:1 ee Ar il'sakrs.Finormoroatv. Nominal Size Max.Working Dimensions Style Approx. Pressure• A 8 C WI.Each k.(raw PSI attx) m.(amt) k(rai) Av.frrA^t! lbs.AO C-`I } 1 x 2 500 0.75 0.25 1.42 Outside 0.22 B ;A IS 14.05 A 1 xih 500 ' 0.75 0.25 1.42 Outside 0.17 a 1 :`iA2:, !.P:p: t 2J ti oi 1'h x 1 500 0.80 0.28 1.76 Outside 0.28 Inside Head i4 ,i 1 .x 1 500 0.63 0.31 2.00 Outside 0.45 six 1 A 500 0.83 0.31 2.00 Outside 0.30 (* C-1-1 } .1502 11111MBOM B 2 x 1 500 0.68 0.41 1.95 Inside 0.61 t rrx25 1-5,: 10.414 j A 2 x 134 500 0.68 1 0.34 2.4E Outside 0 73 Outside Head 2 x 1.' 500 0 68 i 0.34 2.4E Outside 0,61 I • •-Working Pressure Ratings ore for reference only and based on 5ch.AO pipe.For she latest Ul1ULC, and FM pressure ratings versus pipe schedule,please visit orsvilintl.conr or contort your local Anvil Representative. CAP : nn �sPFifv Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded fittings are UL& ULC Listed & FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-45-12. Dimensions conform to ASME B16,14 Threads are NPT per ANSI/ASME B1.20.1. NOTICE:Duch le iron fittings have higher+ensile strength than that of stool pipe.Therefore,over tightening can covse darnage to pipe threads which may cause leakage.Ductile iron fittings should be tightened three turns beyond hand light,but no more than lour turns C a'a rM LISTED APPROVED Ld Lea rus.App-owl Delos and tmisfua CAP ■rr ear&knee a wr«rnthtl corn or oonuer an Inca'Seas Rapatanuine Nominal Size Max.Working Dimensions Approx. Pressure. A WI.Each k, fnett! PSI fiPc; h.(xer? lb!. fig; 1 500 1.16 0.32 t 3d50 A 1 : 500 1.28 0.43 1 . 500 1.33 0.60 3450 2 500 1.4 5 0.91 ?SSn •-Working Pressure Rotugs are for refoernce only and based on Sch 40 pipe For the latest UVULC, and FM pressure ratings versus p pe schedule,please visit anvri ntl.conr or contact your local Anvil RepresenMiive. COUPLING z ANVIL (CC—PF/PlItNI Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded fittings are UL& ULC Listed & FM Approved for 500 psi service, Ductile iron per ASTM A536 Class 65-45-12, Dimensions conform to ASME B16,14 Threads are NPT per ANSI/ASME B1.20.1. NOTICE:Ductile iron finings have higher tmssile strength Ikon that of steel pipe.Therefore,over tightening can souse damage to pipe threads which cause leakage.Ductile iron fittings should be ti htened three turns may �g ng 9 beyond pond tight,but no more than four turns C©at V um. APPROVE° ru intresiaap'oiai Canals and Lewiston. COUPLINGexit:nw*oboe a.xw.rn«W corn or *coma an kw"Situ Rearessnsta. Nominal Size Max.Working Dimensions Approx. Pressure♦ Wt.Each PS?(A Ci lr.fan) lhs (1y' C 500 1 5 1.67 0.40 0 tE 1 500 1.43 0.57 -- -- - 4 c 0 24 1.: 500 7.15 0.75 0.34 2 500 2.5'1 1.15 •-Working Pressure Ratings ore for reference only and bused on Seth,10 pipe For the latest UI/UtC, and FM pressure ratings versus prpe schedule.please vinii dtwlintl,eo.n or contort your local Anvil Representative. • CROSS iAniviL Cf; PF/FWVL Ductile Iron MATERIAL SPECIFICATIONS s Ductile iron threaded fittings are UL & ULC Listed & FM Approved for 500 psi service. II Ductile iron per ASTM A536 Class 65-45.12, t`R ' 1 Dimensions conform to ASME B16.3 /* Threads are NPT per ANSI/ASME B1.20.1. NOTICE:Ductile iron finings have higher tensile strength thon shot of steel pipe.Therefore,over tightening can cause damage to pipe threads which may couse leakoge.Ductile iron finings should be tightened three turns beyond bend tight,but no more than Iuur turns. g©IS FM UMII APPROVED CROSS r a I.I.+puatwo ar Aims gnu Lrn4a lumc ar MoOam at rn aamwtl corn or contbn an Nwr Sun Rateaynuaa. Nominal Size Max,Working Dimensions Approx. Pressure• A g W1.Each it On) PSI OM le(nm It GRmJ lbs.(kg) - 1 500 1.50 1.50 0.98 1 . 500 1.75 1,75 150 t M11111111111111 1 500 194 1.94 1.90 Ar 2 500 2.25 2.25 7.9 5 + T { Ir { 1 .x 1 500 1.58 U7 I.27 A ., /1111111MMI 1 x 1 500 1.65 1.80 1.48 2 x 1 500 1.73 7.07 2.10 •-Working Pressure R,remgs are for refr,ence only and based on Sell.40 pipe.For the latest UIJULC. and FM pressure ratings versus pipe schedule,please cisii omr+linul om or contact your local Anvil Representative REDUCING 90° ELBOW .. z /11Vv!L �SPF�fafV1/�.j Ductile Iron MATERIAL SPECIFICATIONS • r�.:• Ductile iron threaded fittings are UL & ULC Listed & FM Approved for 500 psi service. 1k) � Ductile iron per ASTM A536 Class 65-45.12. Dimensions conform to ASME B16.3 Threads are NPT per ANSI/ASME B1.20.1. NOTICE:Ductile iron fittings hove higher'ensile strength than that of steel pipe.Therefore,over tightening con cause damage b pipe threads whits may cause leakage.Ductile iron fittings should be tightened three turns beyond hand tight,but no mare than four hens, c®'s FM Upl� APPtlatrt:0 REDUCING 90° ELBOW `'vise Dew, �` ' tisR ar vnWsm u.ww.anvirtl can a mown ar,M r Saw Rftworuwr Nominal Size Alex.Working Dimensions Approx. Pressure. A 8 W9.Each In.fmml PS/IAN L (nm) It lnaoo) 1k 114) 1 z._...__.._ 500 1.26 1.36 0.44 1 x 500 1,37 1,45 0 52 --B-I 1 ;x 500 1.34 1.53 0 64 3493 - --� 1 x 500 1.45 1.62 0.72 A 1.i x 1 500 1.58 1.61 0.75 4 x 1 500 1.65 1.80 0.92 49 X 23 to y7 114 x 1 Yr 500 1.82 1.88 1.08 (1r i 4,!' 2 x h 500 1.49 1.88 1.08 2 x 500 1.60 1.97 1.24 411 e.4 2 x 1 500 133 2.02 1.40 2 x 1'h 500 1.90 2.10 1.52 3o)3. 2 x 11/4 500 2.02 2.16 1.65 ♦-Wiwi ing Pressure Rc ngs are for reference only and based on Sell 40 pipe.For Ore latest UL/ULC, and FM pressure ratings versus pipe schedule,please visit onvil ntl.corn or contact your local Anvil Representative. REDUCING COUPLING sr ANVIL W /Fwv, Ductile Iron MATERIAL SPECIFICATIONS Ductile iron threaded fittings are UL & ULC Listed & FM Approved for 500 psi service. Ductile iron per ASTM A536 Class 65-45-12. Dimensions conform to ASME B16.3 Threads are NPT per ANSI/ASME 81.20.1. • NOTICE:Ductile iron finings have higher'ensile strength than that of steel pipe.Therefore,over tightening con cause damage to pipe tlrreods which may cause leakage.Ductile iron finings should be tightened three turns beyond hand tight,but no more than four turns C®m FM With APPROVED REDUCING COUPLING `a` Apr"at tAl"and` ' .�wwvbs+nx wraanlrC tom mew::an Ain Sabot Raerowsnaative Nominal Size Mox.Working Dimensions Approx. PressureA A WI.Each k, Inset! PSI(kPc) M.(earn? (bs (kg) • 1 x 5� 1.69 _.� 0.39 42 92 1 x 3i 500 1,69 0.53 -wafting Pressure Ratings ore for(defence o.4 end based on Sd.40 pipe.For the latest ULJULC. and FM pressure ratings versus pipe schedule please visit onvilinttcom or contocr your local Anvil Representative • • REDUCING TEE (.11' ANVIL Ductile Iron .- . .... MATERIAL SPECIFICATIONS t al , Ductile iron threaded fittings are Ul& ULC Listed & C FM Approved for 500 psi service. , Ductile co nform oenfor per ASm to TMAA5s3m6E Ei .3 Class 1 2. Dimensions I-..-A-•1-B-•-1 Threads ore NPT per ANSI/ASME B1.20.1. REDUCING TEE NOTICE:Nook nen linings he higher tensile strength felon thor of steel pipe.nserellore,over tightening con cause dcsmoge to pipe thread%-which Max. Dimensions_ moy covse leokoge.Duchle Iron finings should be tightened three turns Nominal She Working kpriocixo.1 beyond hand light,but no more than four term, Pressure* A 8 ( Az(mtn) PSI tik) M.(am) in.(mm) In(rim) Ibs.AO CC)" <> MU APPR OW 0 I X1/2X1 500 1.50 1.36 1.50 0.64 io■Urangvappnwal OA.*wId Laneslana 25 t i 5 Y 5 345{} . ., ' Nit ourvarbsaa at anewArtfrA cam or maw an Anwar Saial liaaraamaim, 1X3/4X1 soo 1.50 1.45 1 50 0.73 25 K'10 Y 25 545,'T •.' REDUCING TEE 500 1.76 1.26 1.36 0.71 25 x?5) 15 354i 7; Ili x3/4 1.37 1.37 1.45 0.76 kiox. Dimensions Approx. 25 a 754 7: -.-- 7,, ''' Nominal Size Working - Wt.[orb 1x1x1Y, 500 1.67 1.67 1.58 0.98 Pressure* A B ( ._ 25)25;37 .1,- ' 1 x 1 x 1Y; 500 1.80 1.80 ' 1.65 1.16 tn.No PSI OW tn.one kl.(mm) In.(mm) Lbs.Op 1 ,X 1-1 .: 50,:.) 1.52 1.52 ' 1.75 1.24 1Vix,1xVI 500 1.34 1.26 1.53 0.82 , . .• ."..).86 . .), bit 11/41 1 S00 1.65 1.65 1.80 1.30 1'141*Y, 500 1.45 1.37 1.62 0.90 J0.4 40i?..: ..' -.1. r7 41 15 N x 116x 11/4 500 1.82 1.82 1.86 1.48 1 ' xIx1 500 1.58 1.50 1.67 1,00 4'.;.,40 ir..ri ' ' 25 Ph elWx2 500 2.16 6 ' 2.16 2.02 1 98 11/4 x 1 x 1V4 500 1.75 1.67 1.75 1.08 5 0 0 1.88 1.80 1 8 7 1.42 2 x 1 x 2 500 7.25 2.02 2.25 215 11/4x1x1'h . 37 x1'5 7 4t? 3455 ?x 1 Ax2 500 2.75 230 2.25 2.30 11/4x11/4xV: SOO 1.34 1.34 1.53 0.86 , ??'a 32 15 343;.; , 7 1'I;x 5i 500 149 141 1.8E 1.50 1Y.111140C 500 1.45 1.45 1.62 0.92 ;:1)?5 ,%.: 37/ 3i i■1 9 a 3;Y 32)20 347 „it 3 .: 2 x 11/2x1/4 500 1.60 ' 152 1.91 1.62•1V4x114x1 SOO 1.58 138 1.67 0.95 :!?f 7, ',1 3i' 32)32 1 2i 34.5,:l ,:' '., 2) 1 4 x 1 500 1.73 1.65 2.02 1.64 1Y4x Prix 116 500 1.88 1.88 1.82 1.45 .:,ti 2 x 1. x1'.', 500 1.90 181 210 1.80 11¼4x1Y4x 2 500. 2.10 ' 2,10 1,90 1.75 2 x 1,':*1 59 500 202 1.94 i16 200 114x1x1/2 500 1.41 1.34 1.66. 0.95 1'..'.x 1 x', 50 1.5? 137 1.75 1.14 2 1 4 x 2 500 2.25 ' 216 7.25 235 509 - 1,49- 1.49 2x2x11: ,i lit Lao ' ivsx 1 xi s6o 1.65 1.5C 180 1.17 1x 7 x`.;_ 500 ' 1.60 1.60 1.91 1.68 11/2 x 1 x l,.., 500 1.82 1.61 ' 1.88 1.34 r..:'r 2x2x1, 50) 1.73 1.73 202 1.85 1Y?x 1 x 1'4 500 ' 1.94 1.80 1.94 1.45 4,,',k.`,/.; ■•C .:,, - .- 2).2x1/4 00 liix1Y,x V, 500 141 1.34 166 1.05 - 5 1.90 1.90 2 10 2_04 40k.12,!) 2)2x 1... 500 2.02 2.02 2.16 2.18 159 x1V 0'4 500 1.52 ' 1.45 1 /5 1.15 :. '1.15o 4[:•..k,32,2," . .... 2)2x 7.,:. 500 2 60 2.60 2 39 3 61 11/2x 1V4x 1 500 1.65 1.58 1.80 1.25 ..rk.p.,;',• 41,,s .2 , 2 x 2x-,,,■ 50' 1.74 1.60 2.37 278 11..6x1V■x? 500 2.16 2.10 ' 2.02 130 .,,,. 53 34 ':-',;:' p p, A-Worlung Pressure Ratings ore Iv rekraaKe only end hosed on S .10 ppc 1-o,If* 1,,,:x 1. x . 500 1.41 1.41 1.16 1.15 ciacnk:oclUiLjayourC. tøtnws. orsesppe verses ppe schedule,please visit csnwofinti corn or .. 1 ... qq�C ® UL FM ® VdS (LK Fire Outlet-T SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating 1/2,1/4,and 1"/15,20 • and 25 mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and , other outlet products.Available for 11/4 through 76.1 mm/32 to 76.1 mm piping systems,Style 922 outlets are UL/ULC Listed, LPC,Vds/FM approved for branch connections on wet and dry systems. �.. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up ti to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard,lightwall,Schedule 5 and other specialty pipes.* It is supplied with a clear,rust inhibitive coating.Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing:Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Gasket: • Grade"E"EPDM-Type A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Gasket System. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical require- ments of ASTM A-449 and physical requirements of ASTM A-183. • • JOB/OWNER CONTRACTOR ENGINEER System No. _ Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. .CtauIiC REV_D • IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS 10.5 2 Fire Lock® Outlet-I SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 • 1 L1 DIMENSIONS Nominal Size Hole p pprox. inches/mm Diameter Dimensions-inches/millimeters Weight Each Run X Branch +0.06/+1.5 Y Z 1 FPTt -0.00/-0.0 T* V W Y Z lbs/kg • 111111 1'/, X 1 1'/r6 1.30 1.83 1.10 3.87 2.56 1.0 _ 32 15 312 310 46.5 27.9 983 65.0 0.45 IT 13/46 1.18 1.83 1.10 3.87 2.56 1.1 :��\�■ I 20 30.2 32.5 46.5 27.9 98.3 65.0 0.50 �•, ,•' W 1 1 1 1 3/,6 1.52 2.18 1.10 3.87 2.56 1.2 �/ MI 25 30.2 38.6 55.4 27.9 98.3 65.0 0.54 11/2 1/2 13/46 1.42 1.95 1.22 4.08 2.56 1.2 40 X 15 _ 30.2 36.1 49.5 31.0 103.6 65.0 0.54 3/4 1 3/16 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 49.5 31.0 103.6 65.0 0.54 • 1 1 3/16 1.64 2.30 1.22 4.08 2 56 1.3 25 30.2 41.7 58.4 31.0 103.6 65.0 0.59 2 h 13A6 1.66 2.19 1.46 4.60 2.56 1.3 50 X 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 3/a 13/. 1.64 2.19 1.46 4.60 2.56 1.4 20 { 30.2 41.7 55.6 37.1 116.8 65.0 0.64 1 13/16 1.88 2.54 146 460 2.56 1.5 25 30.2 47.8 64.5 37.1 116.8 65.0 0.68 21/2 X 1/2 I 13/1* 1.91 244 1.71 5.40 2.56 1.6 65 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73 3A 13/16 1.89 244 1.71 5.40 2.56 1.6 20 30.2 48.0 62.0 43.4 137.2 65.0 0.73 1 13/16 2.13 2.79 1.71 5.40 2.56 1.6 25 30.2 54.1 70.9 43.4 137.2 65.0 0.73 1/' 76.1 mm X 1 3/16 1.91 2.44 1.71 5.50 2.56 1.6 15 30.2 48.5 62.0 43.4 139.7 65.0 0.73 3A 13/46 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 62.0 43.4 139.7 65.0 0,73 1 1 3/16 2.13 2.79 1.71 5.50 1.56 1.7 • 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional) male pipe threads only.Use of male threaded products with special features,such as probes,dry pen- dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify suitability in advance may result in assembly problems or leakage. , °Center of run to engaged pipe end for NPT threads(dimensions are approximate). www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ictauI1C° 10.522 F,EV1? IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS 1 0.52 �. _ ----- --- — _ III R UL FM ® VdS LUX FireLock® Outlet-i SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 1.-i PERFORMANCE Equivalent Length of Nominal Size V Pipe Inches/mm Feet/meters 11/4 X 1 8.5 32 25 2.6 11/2 X 1 8.5 40 25 2.6 2 1 I 8.5 50 X 25 2.6 2 Yz X 1 8.5 65 25 2.6 76.1 mm X 1 8.5 25 2.6 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. uCtaulid REV_D 10.52_3 FireLock® Ou`ie "tli 0 <> AN. SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 • • WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. • US&WORLD HEADQUARTERS CANADA CENTRAL AND SOUTH AMERICA P.O. Box 31 905-884-7444 1-610-559-3300 Easton, PA 18044-0031 USA 905-884-9774(fax) 1-610-559-3608(fax) 4901 Kesslersville Road viccanada @victaulic.com vical @victaulic.com Easton, PA 18040 USA EUROPE ASIA PACIFIC 1-800-PICK-VIC(1-800-742-5842) 32-9-381-15-00 86-21-54253300 1-610-559-3300 32-9-380-44-38(fax) 86-21-54253671 (fax) 1-610-250-8817(fax) viceuro @victaulic.be vicap @victaulic.com pickvic@victaulic.com UNITED KINGDOM MIDDLE EAST www.victaulic.com 11111111111 IIIIIIIl�IIIIIliiiIII1111111111 44(0) 1438741100 971-4-883-88-70 44(0) 1438313883(fax) 971-4-883-88-60(fax) WCAS-6QKGYH viceuro @victaulic.be UPDATED 8/2006 10.52 3355 REV D rCtaUlrC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2006 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 10.52 ELI . 14795 S.W. 72od Avenue PORTLAND, OR 97224 PHONE 503-620-4020 • FIRE, INC . CCB# 64 74 1058 Hangers FIRE PROTECTION CONTRACTORS PIPE RINGS :E .N.m.11...• Fig. 69 Adjustable Swivel Ring, Tapped Per NFPA Standards • Size Range:1/2"through 8" Material:Carbon steel Finish:U Galvanized Service:Recommended for suspension of non-insulated stationary pipe line. m- - - Maximum Temperature:650°F ∎ Approvals:Complies with Federal Specification A-A-1192A(Type 10) WW-H-171-E(Type 10),ANSI/MSS SP-69 and MSS SP-58(Type 10). • UL Listed and FM Approved(Sizes 3/4"-8"). ,'i ' Features: , • Threads are countersunk so that they cannot become burred or damaged. • Knurled swivel nut provides vertical adjustment after piping is in place. • Captured swivel nut in the'/2"through 6"sizes.The capture is permanent in the bottom portion of the band,allowing the hanger to be opened during installation if desired,but not allowing the nut to fall completely out. Ordering:Specify size,figure number and name. Note:The acceptability of galvanized coatings at temperatures above 450°F is at the discretion of the end user. Metric nut available upon request.Non-captured nut also available upon request. mie $ ci 11/4'through 8"pipe 1/2"through 1"pipe FIG. 69: LOADS (LBS) • WEIGHT (LBS) • DIMENSIONS (IN) Pipe Size Max Load Weight Rod Size A B C F 1/2 0.10 2'/e 2 19/6 3/4 0.10 23/4 1'/8 1%6 1 300 0.10 29/16 111/26 1 11/4 0.10 2% _ 1% % 11/2 0.10 3/8 23/4 1% 2 0.11 31/4 23/6 11/2 21/2 525 0.20 4 23/4 15/16 3 0.20 3t3A6 215/6 13/16 4 650 0.30 4"A6 313/16 5 0.54 55/6 43/6 19/16 6 1,000 0.65 '/2 6 11A6 59/6 21/4 8 1.00 8 7 2"A6 Note:Reflects changes in rod diameter from previously published data per recent revisions in MSS-SP-58&69 PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: Catalog PH-2008 HANGER RODS Fig. 146 Continuous Threaded Rod Size Range: /4"through 1'/2"Stocked in six,ten,and twelve foot lengths.Other even foot lengths can be furnished to order. Material:Carbon steel;rod threaded complete length. Finish:❑Plain or 3 galvanized. Maximum Temperature:650°F. Ordering:Specify rod diameter and length,figure number, name and finish. Note:The acceptability of galvanized coatings at temperatures above 450°F is at the discretion of the end user. Length ►i A FIG. 146: LOADS(LBS)•WEIGHTS(LBS) DIMENSIONS(IN) Rod Size Threads Max Load Weight A per Inch per Ft. 650° F '/4 20 240 0.12 3/e 16 730 0.30 '/2 13 1,350 0.53 5/e 11 2,160 0.84 % 10 3,230 1.20 '/e 9 4,480 1.70 1 8 5,900 2.30 11/4 7 9,500 3.60 11/2 6 13,800 5.10 Note:Other rod sizes available upon request.Class 2 fit is available upon request. PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: Catalog PH-2008 GST 'a` oo 1 SAMMYS '"lit WOOD • 1/4"Rod• Vertical Mount B. quantify 100 except as noted with this marking(•) Use#14 Nut Driver(Item#100) • Box quantity 50 Item # Model Rod Size Shk Dia Shk Lgth 20 GST .750 1/4-20 1/4 3/4 atJ ikon•1(x» 21 GST 100 1/4-20 1/4 1 22 GST 200 1/4-20 1/4 2 23 GST 300 1/4-20 1/4 3 24• GST 600 1/4-20 1/4 6 See page 13 for Stainless Steel WOOD•3/8"Rod•Vertical Mount .Fate:Screws less than 2"in Use#14 Nut Driver(Item#100) length will be plated yellow. Greater than 2"are clear FM Test UL Test UL/FTA zinc per ASTbf1633111 Item 4 Model Rod Size Shk Dia Shk Lgth Load,lb. Load,lb. Pipe Size Actual Pullout 10 GST.75 3/8-16 1/4 314 5644-6 Pry 11 GST 10 3/8-16 1/4 1 210# 7/16 OSB 6704-3/4•'Ry .FM V. 12 GST 20 3/8-16 1/4 2 9404 8504 3/4-2 1/2 17604-Fir ru,i:, >1,. FM I. 27 • GST 25-380 3/8-16 3/8 2 1/2 15004 4 21134-Fir , 13 GST 30 3/8-16 1/4 3 14754 15004 3/4-4 20604-Fir 403• GST 40 3/8-16 1/4 4 21804-Fir 14 • GST 60 3/8-16 1/4 6 22304-Fir WOOD • 112"Rod• Vertical Mount Use#14SW Nut Driver(Item#101) • Item # Model Rod Size Shk Dia Shk Lgth Actual Pullout 8 • GST 2 1/2-13 1/4 2 1760#- Fir 1914m%.(iirma11) 06• GST 2.5-381 1/2-13 3/8 2 1/2 2113€- Fir Amr.r s hN'mutt he tired for arrem rwr with IC.-rap 15• GST 3 1/2-13 1/4 3 2275#-Fir 16• GST 4 1/2-13 1/4 4 2180#-Fir 17• GST 6 1/2-13 1/4 6 22304- Fir Installations Not less than 2"nominal width < (11r2")Page-S for installation instructions. t ( E Installation ,r t i!- per NFPA 13 ` "�li rc r:at E [, °e y c 3 a'c i z 5 a �..e Sammy ' C S ■ Mail ^9 (5. s°"""' " 1 TGI Joist/Truss v • Consult truss manufacturer for recommended installation point. Wood Flooring (See"Special Notes" / on"pair 0 1 I Sammy h.. ES I / w Wood Joist Lower lace of r a- '-� �^mY beam or Joist •••• V Fr Minimum 2"imbedment into base material for NFPA 13 compliance For vortical use. __.. — II Install In center f ••• Sammy of lower face. Double Sheetrock Ceiling I :ii II you don't see II.cell ua et i I II A1.888.773.0001 4 Wood-Sammys 'J Note:Must be installed with appropriate nut driver to comply with warranty. DELTDPORTLAND,7 ORT A D,7 OR 97224e PHONE 503-620-4020 " FIRE, INC. CCB# 641674 1058 S •rin kl er ea s FIRE PROTECTION CONTRACTORS tqcoWorldwide • Fire Protection Contacts www.tyco-fire.com Products Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage General - Sprinkler Description Identification ` TYCO Series DS-2 Dry-Type Sprinklers, Numbers (SiNs) 11.2K Pendent, Standard(5 mm bulb) F' and Quick Response (3 mm bulb), TY5255-Standard Response and Standard Coverage are decora- TY5235--Quick Response tive glass bulb automatic sprinklers ` typically used where: Technical 3 I • pendent sprinklers are required on ! • dry pipe systems that are exposed Data t to freezing temperatures(e.g.,sprin- /. ! p kler drops from unheated portions of Approvals a buildings) UL and C-UL Listed ': • sprinklers and/or a portion of the NYC Approved under MEA 173-02-E I connecting piping may be exposed to Refer to Table A. <. freezing temperatures(e.g.,sprinkler Maximum Working Pressure ,�`.,,� ' drops from wet systems into freezers) 175 psi(12,1 bar) "' NOTICE Inlet Thread Connections f ..: 1 . Series DS-2 Dry-Type Sprinklers I ch NPT described herein must be installed SO O 7-R 1 1 and maintained in compliance with Discharge Coefficient Operation this document, as well as with the Refer to Table C. When TYCO Series DS-2 Dry-Type e a pp licable standards of the National Temperature Ratings Sprinklers, 11.2K Pendent, Standard Fire Protection Association(NFPA), in Refer to Table A. (5 mm bulb) and Quick Response (3 addition to the standards of any other mm bulb), and Standard Coverage authorities having jurisdiction.Failure to Finishes are in service,water is prevented from do so may impair the performance of Sprinkler: Refer to Table D. entering the assembly by the Plug with these devices. Escutcheon:Refer to Table D. Gasketed Spring Plate Seal(Ref.Figure The owner is responsible for main- Physical Characteristics 1)in the Inlet of the sprinkler. taming their fire protection system and Inlet Copper The glass bulb contains a fluid that devices in proper operating condition. Yoke Stainless Copper el expands when exposed to heat.When Contact the installing contractor Casing Galvanized Carbon Steel the rated temperature is reached,the or product manufacturer with any Insert. Bronze fluid expands sufficiently to shatter questions. Bulb Seat Bronze the glass bulb, and the Bulb Seat is Series DS-2 Dry-Type Sprinklers must Bulb Glass released. only be installed in fittings that meet Compression Screw Bronze The compressed Spring is then able the requirements of the Design Criteria Deflector Bronze to expand and push the Water Tube as section. Frame Bronze Guide Tube Stainless Steel well as the Guide Tube outward. This Water Tube Stainless Steel action simultaneously pulls inward on Spring Stainless Steel the Yoke, withdrawing the Plug with IMPORTANT Gasketed Spring Gasketed Spring Plate Seal from the Always refer to Technical Data Plate Seal Beryllium Nickel Inlet,allowing the sprinkler to activate Sheet TFP700 for the "INSTALLER w/TEFI.ON and flow water. WARNING"that provides cautions Pin Stainless Steel with respect to handling and instal- Button Spring Stainless Steel lation of sprinkler systems and Escutcheon Carbon Steel . components.Improper handling and installation can permanently damage a sprinkler system or its compo nents and cause the sprinkler to fail • to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 October 2014 TFP530 TFP530 Page 2 of 8 TY5255 Design • Standard Response TY5235 Criteria Quick Response TYCO Series DS-2 Dry Type Sprinklers, with Flush Escutcheon 11.2K Pendent, Standard(5 mm bulb) (Figure 2) and Quick Response(3 mm bulb),and Standard Coverage are intended for with Recessed Escutcheon use in fire sprinkler systems designed Temperature Bulb (Figure 3) in accordance with the standard Rating Color Code with Extended Escutcheon coverage installation rules recog- . (Figure 4) nized by the applicable listing agency (e.g., UL Listing is based on NFPA 13 without Escutcheon requirements). (Figure 5) Sprinkler Fittings SPRINKLER FINISH Install 1 inch NPT Series DS-2 Dry-Type Sprinklers in the 1 inch NPT outlet or Natural Chromed Signal run of the following fittings: Brass Plated White • malleable or ductile iron threaded 135°F(57°C) Orange tee fittings that meet the dimen- sional requirements of ANSI B16.3 155°F(68°C) Red (Class 150) 175°F(79°C) Yellow 1,2,3 • cast iron threaded tee fittings that meet the dimensional requirements 200°F(93°C) Green of ANSI B16.4(Class 125) 286°F(141°C) Blue Do not install Series DS-2 Dry Type Sprinklers into elbow fittings.The Inlet Notes: of the sprinkler can contact the interior • 1. Listed by Underwriters Laboratories,Inc.(UL.I,maximum order length of 48 inches of the elbow. 2. Listed by Underwriters Laboratories for use In Canada(C-UL),maximum order length of 48 inches 3. Approved by the City of New York under MEA 173-02-E The unused outlet of the threaded tee is TABLE A plugged as shown in Figure 9. SERIES DS-2 STANDARD& QUICK RESPONSE, STANDARD COVERAGE You can also install Series DS-2 DRY-TYPE PENDENT SPRINKLERS Dry-Type Sprinklers in the 1 inch NPT LABORATORY LISTINGS AND APPROVALS outlet of a GRINNELL Figure 730 Mechanical Tee. However, the use of yT �O, — INLET the Figure 730 Tee for this arrangement PLUG WITH .6 is limited to wet pipe systems. g GASKETED SPRING • ■ PLATE SEAL 4 .� The configuration shown in Figure 8 is 47 -_¢ PIN only applicable for wet pipe systems +;� ` where the sprinkler fitting and water- SPRING a� e YOKE filled pipe above the sprinkler fitting are r 3 ;1 not subject to freezing and where the 11 ;" length of the dry-type sprinkler has the INLET BAND ∎1 % PLUG minimum exposure length depicted in 1. 1 SPRING Figure 10.Refer to the Exposure Length WATER TUBE — q i'- ■ section. 11W CASING For wet pipe system installations of i I 1 inch NPT Series DS-2 Dry-Type GUIDE ■ 11 Sprinklers connected to CPVC piping, TUBE ly of INSERT use only the following TYCO CPVC � ; fittings: VENT HOLE 11011 I BULB • 1" x 1" NPT Female Adapter (P/N 8145) FRAME • 1" x 1" x 1" NPT Sprinkler Head 3 or 5 mm Adapter Tee(P/N 80249) BULB 06� For dry pipe system installations, use COMPRESSION ,Q=b • only the side outlet of maximum 2-1/2- SCREW hif DEFLECTOR inch reducing tee when locating Series FIGURE 1 DS-2 Dry Type Sprinklers directly SERIES DS-2 STANDARD&QUICK RESPONSE below fig ration sho. n neFigue, use DRY-TYPE PENDENT SPRINKLER the u e complete shown in drainage r m ASSEMBLY assure complete water drainage from above Series DS-2 Dry Type Sprinklers and the branchline. Failure to do so may result in pipe freezing and water damage. TFP530 Page 3 of 8 Clearance Space Temperatures for Heated Areal In accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13, when Ambient Temperature 40°F 50°F 60°F connecting an area subject to freezing . Exposed to (4°C) (10°C) (16°C) and an area containing a wet pipe Discharge End of Sprinkler Minimum Exposed Barrel Length2, sprinkler system,the clearance space Inches around the sprinkler barrel of dry-type (mm) sprinklers must be sealed. Due to temperature differences between two 40°F 0 0 0 areas, the potential for the formation (4°C) of condensation in the sprinkler and 30°F subsequent ice build-up is increased.If (-1°C) 0 0 0 this condensation is not controlled, ice build-up can occur that might damage 20°F 4 0 0 the dry-type sprinkler and/or prevent (-7°C) (100) proper operation in a fire situation. 10°F 8 1 • Use of the Model DSB-2 Dry Sprinkler (-12°C) (200) (25) 0 Boot, described in Technical Data Sheet TFP591 and shown in Figure 11, . 0°F 12 3 0 can provide the recommended seal. (-18°C) (305) (75) -10°F 14 4 1 (-23°C) (355) (100) (25) -20°F 14 6 3 (-29°C) (355) (150) (75) -30°F 16 8 4 (-34°C) (405) (200) (100) -40°F 18 8 4 (-40°C) ' (455) (200) (100) -50°F 20 10 6 (-46°C) (510) (255) (150) -60°F 20 10 6 (-51°C) (510) (255) (150) Notes: 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph(16.6 kph). TABLE B EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS NOTICE Exposure Length Do not install Series DS-2 Dry-Type When using dry sprinklers in wet pipe Sprinkler into any other type fitting sprinkler systems to protect areas without first consulting the Technical subject to freezing temperatures, use Services department. Failure to use the Table B to determine a sprinkler's appropriate fitting may result in one of appropriate exposed barrel length the following: to prevent water from freezing in the connecting pipes due to conduction. • failure of the sprinkler to operate prop- The exposed barrel length measure- erly due to formation of ice over the ment must be taken from the face of Inlet Plug or'binding of the inlet Plug the sprinkler fitting to the surface of the •inufficient engagement of the Inlet structure or insulation that is exposed pipe-threads with consequent leakage to the heated area. Refer to Figure 10 for an example. . Drainage For protected area temperatures In accordance with the minimum between those given above, the requirements of the National Fire minimum recommended length from Protection Association for dry pipe the face of the fitting to the outside of . sprinkler systems, branch, cross, the protected area may be determined and feed-main piping connected to by interpolating between the indicated dry sprinklers and subject to freezing values. temperatures must be pitched for proper drainage. TFP530 Page 4 of 8 K-factor K-factor, 1' `; LENGTH, gpm/psi112 1 Inches(mm) (Ipm/bar��2) I SPRINKLER FITTING 2-1/2 to 6-1/4 11.2 FACE OF (REFER TO DESIGN (63 mm to 159 mm) (161,3) SPRINKLER I ( CRITERIA SECTION) FITTING 6-1/2 to 10-1/2 11.1 (165 mm to 267 mm) (159,8) ORDER LENGTHS: 3-5/8"DIA. _, 10-3/4 to 14-3/4 11.0 3"to 48" (92,1 mm) (273 mm to 375 mm) (158,4) (76,2 to 1219,2 mm) I ( 15 to 18 3/4 10.9 _ IN 1/4"(6,4 mm) 2-3/4'DIA. , (381 mm to 476 mm) (157,0) INCREMENTS 1-(69,9 mm) I 19 to 23 10.8 (483 mm to 584 mm) (155,5) FACE OF _ j 23-1/4 to 26-3/4 10.7 CEILING f (591 mm to 679 mm) (154,1) /%1 ■� 27-1/4 to 31-1/4 10.6 (692 mm to 794 mm) (152,6) 2-1/4±1/8"* � 31 mm to 895 m 10.5 (57,213,2 mm) *ESCUTCHEON (800 mm to 895 mm} (151,2) ■/ WILL PERMIT 35-1/2 to 39-1/2 10.4 ±1/4'(6,4 mm) (902 mm to 1003 mm) (149,8) ■__. ADJUSTMENT 39-3/4 to 43-1/2 10.3 (1010 mm to 1105 mm) (148,3) FIGURE 2 43-3/4 to 48 10,2 SERIES DS-2 DRY-TYPE PENDENT WITH FLUSH ESCUTCHEON (1111 mm to 1219 mm) (146,9) STANDARD RESPONSE(TY5255)OR QUICK RESPONSE(TY5235) Notes: K-factor Length is determined as follows: • Elusb:Order Length from Figure 2 plus 1/2 Inch . (12,7 mm) (__ I i • Oacs5.s>Td:Order Length from Figure 3 plus 1/4 L_ t inch(6,3 mm) `- -� • Extended:Order Length from Figure 4 plus 3-1/4 SPRINKLER FITTING • inch(62,6 mm) • Without Escutcheon:Order Length from Figure 5 FACE OF (REFER TO DESIGN minus 2-1/4 inches(57,2 mm) SPRINKLER l CRITERIA SECTION) TABLE C FITTING DISCHARGE COEFFICIENTS ORDER LENGTHS: - 3-5/8" DIA. 3-1/2"to 48" (92,1 mm) (88,9 to 1219,2 mm) I I IN 1/4"(6,4 mm) 2-3/4"DIA. INCREMENTS }(69,9 mm)' FACE OF • CEILING I M 1-5/8±1/8"* 60111 "ESCUTCHEON (41,3±3,2 mm) k■/\ WILL PERMIT m 1 X3/8"(9,5 mm) ! _._ —_ ._. ADJUSTMENT FIGURE 3 SERIES DS-2 DRY-TYPE PENDENT WITH RECESSED ESCUTCHEON STANDARD RESPONSE(TY5255)OR QUICK RESPONSE(TY5235) TFP530 Page 5 of 8 r- -' a I �-- SPRINKLER FITTING (A) SPRINKLER FACE OF (REFER TO DESIGN �-. WRENCHING ORDER LENGTHS: SPRINKLER CRITERIA SECTION) AREA 1"to 45-1/4" FITTING 3-5/8"DIA._ _ WRENCH (25,4 to 1149,4 mm) (92,1 mm) RECESS i�� IN 1/4"(6,4 mm) ` INCREMENTS FACE OF 2-3/4"DIA. .�IAi CEILING r(69,9 mm) 1 %III ib� II PUSH WRENCH ��� � IN TO ENSURE O` FOR ORDER LENGTHS ENGAGEMENT ti <3-1/4"(82,6 mm): *ESCUTCHEON WITH SPRINKLER �� 4-718±1/8"(123,8±3,2 mm)* WILL PERMIT WRENCHING AREA rif or ±5/8"(15,9 mm) FOR ORDER LENGTHS ADJUSTMENT FIGURE 6 a 3-1/4"(82,6 mm): W-TYPE 17 5-5/8±1/8"(142,9±3,2 mm)** *"ESCUTCHEON SPRINKLER WRENCH iiiiii■■�\ WILL PERMIT t1-3/8"(34,9 mm) !!! ADJUSTMENT FIGURE 4 SERIES DS-2 DRY-TYPE PENDENT WITH EXTENDED ESCUTCHEON STANDARD RESPONSE(TY5255) OR QUICK RESPONSE(TY5235) \ r- FACE OF SPRINKLER FITTING 4 I (REFER TO DESIGN �J,t')'w I SPRINKLER CRITERIA SECTION) c FITTING p{ I DO NOT ORDER LENGTHS: FIGURE 7 5"to 48" DO NOT GRASP DEFLECTOR (127,0 to 1219,2 mm) IN 1/4"(6,4 mm) INCREMENTS 1 -- MINIMUM 2-1/4"(57,2 mm) DEFLECTOR TO CEILING 1 I - FIGURE 5 SERIES DS-2 DRY-TYPE PENDENT WITHOUT ESCUTCHEON STANDARD RESPONSE(TY5255) OR QUICK RESPONSE(TY5235) TFP53O Page 6 of 8 • A leak-tight 1 inch NPT sprinkler joint should be obtained byt applying TO WET SIDE FACE OF a minimum-to-maximum torque of SYSTEM OUTLET SPRINKLER 1 20 to 30 ft-lbs. (26,8 to 40,2 Nm). • PLUGGED FITTING Higher Nm). • of with consequent torque may distort leakagthe e I HEATED DIM HEATED EXPOSURE or impairment of the sprinkler. AREA AREA (SELEENDGETSH GN Do not attempt to compensate SPRINKLER CRITERIA for insufficient adjustment in an DSB-2 FITTING DSB-2 SECTION) Escutcheon Plate by under or over- BOOT (SEE DESIGN BOOT tightening the sprinkler.Re-adjust the CRITERIA position of the sprinkler fitting to suit. SECTION) Note:Install pendent sprinklers only in the pendent position. The Deflector of 77777 ' ' ilk III, a pendent sprinkler must be parallel to the ceiling. Step 1. With a non-hardening pipe- thread thread sealant such as TEFLON applied . to the Inlet threads, hand-tighten the • sprinkler into the sprinkler fitting. Do FIGURE 8 not grasp the sprinkler by the Deflector SPRINKLER FITTING FIGURE 10 (Ref•Figure 7). HEATED AREA EXPOSURE LENGTH Step 2. Wrench-tighten the sprinkler using either. RUN STRAP TIES • a pipe wrench on the Inlet Band or the � ,. (ENDS ON Casing(Ref.Figure 1) 1 r– PLUGGED D OPPOSING • the W-Type 17 Sprinkler Wrench on SIDES OF the Wrench Flat(Ref. Figure 2) SPRINKLER BOOT) Apply the Wrench Recess of the TO DRY FITTING _ DSB-2 BOOT W-Type 17 Sprinkler Wrench to the SYSTEM (SEE DESIGN — Wrench Flat. CRITERIA ADHESIVE SECTION) Note: If sprinkler removal becomes AREA „ -3/4”DIA. necessary, remove the sprinkler using SUBJECT T al (69,9 mm) the same wrenching method noted TO DSB-2 CLEARANCE g FREEZING BOOT n HOLE above.Sprinkler removal is easier when anon hardening sealant was used INSULATED and torque guidelines were followed. �■w1 FREEZER After removal, inspect the sprinkler for liar 111111 y��;j_:_,: STRUCTURE damage. j^+ DS-2 Step 3.After installing the ceiling and 1i���_J SHOWN applying a ceiling finish, slide on the O tiI WITH FLUSH outer piece of the escutcheon until it ESCUTCHEON comes in contact with the ceiling. Do not lift the ceiling panel out of its normal FIGURE 11 position. FIGURE 9 MODEL DSB-2 DRY SPRINKLER SPRINKLER FITTING BOOT WITH SERIES DS-2 When using the Deep Escutcheon, UNHEATED AREA DRY-TYPE PENDENT SPRINKLER hold the outer piece in contact with the mounting surface(ceiling or wall).Then Installation the sprinkler Casing. With reference rotate the inner piece approximately to Figure 7,do not grasp the sprinkler 1/4 turn with respect to the outer piece. hold TYCO Series DS-2 Dry-Type Sprinklers, by the Deflector. Failure to follow this togetherthe Deep Escutcheon firmly. 11.2K Pendent, Standard (5 mm bulb) instruction may impair performance of and Quick Response(3 mm bulb),and the device. Standard Coverage must be installed in Do not install any bulb-type sprinkler if accordance with this section. the bulb is cracked or there is a loss of liquid from the bulb.With the sprinkler General Instructions Series DS-2 Dry Type Sprinklers must held horizontally, a small air bubble should be present.The diameter of the only be installed in fittings that meet • the requirements of the Design Criteria air bubble is the 13 approximately 57° 1/16 inch to section. Refer to the Design Criteria (1,6 mm)for the 135 F(57°C)rating to 1/8 inch(3,2 mm)for the 360°F(182°C) section for other Important require- rating. ments regarding piping design and sealing of the clearance space around TFP530 Page 7 of 8 Care and Automatic sprinkler systems are recom- mended to be inspected, tested, and Maintenance maintained by a qualified Inspection Service in accordance with local TYCO Series DS-2 Dry-Type Sprinklers, requirements and/or national codes. 11.2K Pendent, Standard(5 mm bulb) and Quick Response(3 mm bulb), and Limited Standard Coverage must be maintained and serviced in accordance with this Warranty section. Before closing a fire protection system For warranty terms and conditions, main control valve for maintenance visit www.tyco-fire.com. work on the fire protection system that it controls, obtain permission to i dern shut down the affected fire protection Ordering systems from the proper authorities Procedure and notify all personnel who may be affected by this action. Contact your local distributor for Absence of the outer piece of an availability. When placing an order, escutcheon, which is used to cover a indicate the full product name and part clearance hole, may delay the time to number(P/N). sprinkler operation in a fire situation. A Vent Hole is provided in the Bulb Seat Dry-Type Sprinkler (Figure 1)to indicate if the Dry Sprinkler When ordering Series DS-2 Dry-Type is remaining dry. Evidence of leakage Sprinklers, 11.2K Pendent, Standard(5 from the Vent Hole indicates potential mm bulb)and Quick Response(3 mm leakage past the Inlet seal and the need bulb),and Standard Coverage,specify to remove the sprinkler to determine the following information: the cause of leakage(e.g.,an improper •SIN: installation or an ice plug). Close the TY5255—Standard Response fire protection system control valve and TY5235—Quick Response drain the system before removing the sprinkler. • Order Length: Dry-Type Sprinklers are furnished Sprinklers which are found to be based upon Order Length as measured leaking or exhibiting visible signs of from the face of the ceiling to the face corrosion must be replaced. of the sprinkler fitting(Ref.Figures 2 Automatic sprinklers must never be through 5).After the measurement is painted, plated, coated, or otherwise taken,round it to the nearest 1/4 inch altered after leaving the factory. increment. Modified sprinklers must be replaced, • Inlet Connections: Sprinklers that have been exposed to 1 Inch NPT corrosive products of combustion, but (Standard) have not operated, should be replaced if they cannot be completely cleaned ISO 7-R 1 by wiping the sprinkler with a cloth or (For information on ISO Inlet Thread by brushing it with a soft bristle brush. Connections, contact your Tyco Sales Representative.) Care must be exercised to avoid damage to the sprinklers — before, •Temperature Rating during,and after installation.Sprinklers •Sprinkler Finish damaged by dropping,striking,wrench • Escutcheon Type and Finish, as twist/slippage, or the like, must be applicable replaced. Also, replace any sprinkler that has a cracked bulb or that has lost • Part Number from Table D liquid from its bulb.(Refer to Installation Section.) Sprinkler Wrench The owner is responsible for the Specify W-Type 17 Sprinkler Wrench, inspection, testing, and mainte- P/N 56-010-4-118 nance of their fire protection system and devices in compliance with this Sprinkler Boot document, as well as with the appli- Specify Model DSB-2 Dry Sprinkler cable standards of the National Fire Boot,P/N 63-000-0-002 Protection Association(e.g., NFPA 25), This Part Number includes one (1) in addition to the standards of any other Boot, two (2) Strap Ties, and 1/3 oz. authorities having jurisdiction.Contact of Adhesive (a quantity sufficient for the installing contractor or product installing one boot). manufacturer with any questions. TFP530 Page 8 of 8 P/N` 61 - XXX - X - XXX ORDER LENGTH2 SPRINKLER ESCUTCHEON 055 5.50" SIN FINISH FINISH1 10 Standard Response Pendent TY5255 0 CHROME SIGNAL WHITE 082 8.25" with Flush Escutcheon (Figure 2) PLATED (RAL9003) 11 Standard Response Pendent TY5255 1 NATURAL SIGNAL WHITE 180 18.00" with Recessed Escutcheon (Figure 3) BRASS (RAL9003) 12 Standard Response Pendent TY5255 4 SIGNAL WHITE SIGNAL WHITE 187 18.75" with Extended Escutcheon (Figure 4) (RAL9003) (RAL9003) 13 Standard Response Pendent TY5255 5 NATURAL BRASS 372 37,25" without Escutcheon (Figure 5) BRASS PLATED 9 CHROME CHROME 480 48.00" PLATED PLATED 30 Quick Response Pendent TY5235 with Flush Escutcheon (Figure 2) TEMPERATURE Quick Response Pendent TY5235 I RATING 31 with Recessed Escutcheon (Figure 3) 0 135°F(57°C) 32 Quick Response Pendent TY5235 with Extended Escutcheon (Figure 4) Quick Response Pendent TY5235 1 155°F(68°C) 35 without Escutcheon (Figure 5) 2 175°F(79°C) Notes: 1. Escutcheon Finish applies to sprinklers with escutcheons. 2. Dry-Type Sprinklers are furnished based upon"Order Length'as measured per Figures 2 through 5,as 3 200°F(93°C) • applicable,and for each individual sprinkler where it is to be installed.After the measurement is taken, round it to the nearest 1/4 inch increment. ' Use Prefix`I"for ISO 7-R1 Connection(e.g..1-51-101-1-180). 4 286°F(141°C) TABLE D SERIES DS-2 STANDARD AND QUICK RESPONSE, STANDARD COVERAGE, DRY-TYPE SPRINKLERS PART NUMBER SELECTION GLOBAL HEADQUARTERS)1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright®2014 Tyco Fire Products,LP. All rights reserved. tqca TEFLON Is trademark of the DuPont Corporation. '7 Fire Protection Products attic° Worldwide Fire Protection Contacts www.tyco-fire.com Products Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage General Sprinkler h.,, Description Identification - . TYCO Series DS-2 Dry-Type Sprinklers, Numbers (SINS) :' 11.2K Pendent, Standard (5 mm bulb) : and Quick Response (3 mm bulb), TY5255—Standard Response and Standard Coverage are decora- TY5235—Quick Response tive glass bulb automatic sprinklers ��- i• typically used where: Technical • pendent sprinklers are required on i` dry pipe systems that are exposed Data ,'_ ' to freezing temperatures(e.g., sprin- / kler drops from unheated portions of Approvals buildings) UL and C-UL Listed �o NYC Approved under MEA 173-02-E I L • sprinklers and/or a portion of the . , connecting piping may be exposed to Refer to Table A. F--, freezing temperatures(e.g.,sprinkler Maximum Working Pressure , E ``. • drops from wet systems into freezers) 175 psi(12,1 bar) t` '` NOTICE Inlet Thread Connections grof : ",. 1 Series DS-2 Dry-Type Sprinklers I SO O 1 ch described herein must be installed 7-R 1 and maintained in compliance with Discharge Coefficient Operation this document, as well as with the Refer to Table C. When TYCO Series DS-2 Dry Type applicable standards of the National Temperature Ratings Sprinklers, 11.2K Pendent, Standard Fire Protection Association(NFPA), in Refer to Table A. (5 mm bulb) and Quick Response (3 addition to the standards of any other mm bulb), and Standard Coverage authorities having jurisdiction. Failure to Finishes are in service,water is prevented from do so may impair the performance of Sprinkler: Refer to Table D. entering the assembly by the Plug with these devices. Escutcheon: Refer to Table D. Gasketed Spring Plate Seal(Ref.Figure The owner is responsible for main- Physical Characteristics 1)in the Inlet of the sprinkler. taming their fire protection system and Inlet... Copper devices in proper operating condition. Plug Copper The glass bulb contains a fluid that Contact the installing contractor Yoke.. Stainless Steel expands when exposed to heat.When Contact product manufacturer with any Casing Galvanized Carbon Steel the rated temperature is reached,the or product Insert Bronze fluid expands sufficiently to shatter Bulb Seat Bronze the glass bulb, and the Bulb Seat is Series DS-2 Dry-Type Sprinklers must Bulb Glass released. only be installed in fittings that meet Compression Screw Bronze The compressed Spring is then able the requirements of the Design Criteria Deflector Bronze p to expand and push the Water Tube as section. Frame Bronze p Guide Tube Stainless Steel well as the Guide Tube outward.This Water Tube Stainless Steel action simultaneously pulls inward on IMPORTANT Spring Stainless Steel the Yoke, withdrawing the Plug with Gasketed Spring Gasketed Spring Plate Seal from the Always refer to Technical Data Plate Seal Beryllium Nickel Inlet, allowing the sprinkler to activate Sheet TFP700 for the "INSTALLER w/TEFLON and flow water. WARNING"that provides cautions Pin Stainless Steel with respect to handling and instal- Button Spring Stainless Steel lation of sprinkler systems and Escutcheon Carbon Steel components.Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail - to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 October 2014 TFP530 TFP53O Page 2 of 8 TY5255 Design Standard Response TY5235 Criteria Quick Response TYCO Series DS-2 Dry-Type Sprinklers, with Flush Escutcheon 11.2K Pendent, Standard(5 mm bulb) (Figure 2) and Quick Response(3 mm bulb),and Standard Coverage are intended for with Recessed Escutcheon use in fire sprinkler systems designed Temperature Bulb (Figure 3) in accordance with the standard Rating Color Code with Extended Escutcheon coverage installation rules recog- (Figure 4) nized by the applicable listing agency (e.g., UL Listing is based on NFPA 13 without Escutcheon requirements). (Figure 5) Sprinkler Fittings SPRINKLER FINISH Install 1 inch NPT Series DS-2 Dry-Type Sprinklers in the 1 inch NPT outlet or Natural Chromed Signal run of the following fittings: Brass Plated White • malleable or ductile iron threaded 135°F(57°C) Orange tee fittings that meet the dimen- sional requirements of ANSI B16.3 155°F(68°C) Red (Class 150) 175°F(79°C) Yellow 1,2,3 • cast iron threaded tee fittings that meet the dimensional requirements 200°F(93°C) Green of ANSI B16.4(Class 125) 286°F(141°C) Blue Do not Install Series DS-2 Dry Type Sprinklers into elbow fittings.The Inlet Notes: of the sprinkler can contact the interior 1. Listed by Underwriters Laboratories,Inc.(UL),maximum order length of 48 inches of the elbow. 2, listed by Underwriters Laboratories for use in Canada(C-UL),maximum order length of 48 inches 3. Approved by the City of New York under MEA 173-02-E The unused outlet of the threaded tee is TABLE A plugged as shown in Figure 9. SERIES DS-2 STANDARD&QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE PENDENT SPRINKLERS You can also install Series DS-2 LABORATORY LISTINGS AND APPROVALS Dry-Type Sprinklers in the 1 inch NPT outlet of a GRINNELL Figure 730 Mechanical Tee. However, the use of PLUG WITH INLET the Figure 730 Tee for this arrangement GASKETED SPRING is limited to wet pipe systems. PLATE SEAL Ira► The configuration shown in Figure 8 is •J. PIN only applicable for wet pipe systems .- �-:k where the sprinkler fitting and water- SPRING 0/1.� 'te YOKE filled pipe above the sprinkler fitting are II !;P. not subject to freezing and where the s i' length of the dry-type sprinkler has the INLET BAND 1, s PLUG minimum exposure length depicted in SPRING Figure 10.Refer to the Exposure Length WATER TUBE ;1 , section. k fi 1 CASING For wet pipe system installations of .1s 1 inch NPT Series DS-2 Dry Type TUBE % Sprinklers connected to CPVC piping, GUIDE — iy INSERT use only the following TYCO CPVC it fittings: ttli VENT HOLE '`eingil Iq� BULB • 1" x 1" NPT Female Adapter (P/N � i SEAT 80145) FRAME • 1° x 1" x 1" NPT Sprinkler Head _�Ir 3 or 5 mm Adapter Tee(P/N 80249) BULB -�,�y For dry pipe system installations, use COMPRESSION '47m only the side outlet of maximum 2-1/2- SCREW �`e DEFLECTOR inch reducing tee when locating Series i�' DS-2 Dry Type Sprinklers directly . FIGURE 1 below the branchline. Otherwise, use SERIES DS-2 STANDARD&QUICK RESPONSE the configuration shown in Figure 9 to DRY-TYPE PENDENT SPRINKLER assure complete water drainage from ASSEMBLY above Series DS-2 Dry-Type Sprinklers and the branchline. Failure to do so may result in pipe freezing and water damage. TFP330 Page 3 of 8 • Clearance Space Temperatures for Heated Areal In accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13, when Ambient Temperature 40°F 50°F 60°F connecting an area subject to freezing • Exposed to (4°C) (10°C) (16°C) and an area containing a wet pipe Discharge End of Sprinkler Minimum Exposed Barrel Length2, sprinkler system,the clearance space Inches around the sprinkler barrel of dry-type (mm) sprinklers must be sealed. Due to 40°F temperature differences between two (4°C) 0 0 0 areas, the potential for the formation of condensation in the sprinkler and 30°F subsequent ice build-up is increased.If (-1°C) 0 0 0 this condensation is not controlled, ice build-up can occur that might damage 20°F 4 0 0 the dry-type sprinkler and/or prevent (-7°C) (100) proper operation in a fire situation. 10°F 8 1 Use of the Model DSB-2 Dry Sprinkler (-12°C) (200) (25) 0 Boot, described in Technical Data Sheet TFP591 and shown In Figure 11, 0°F 12 3 0 can provide the recommended seal. (-18°C) (305) (75) -10°F 14 4 1 (-23°C) (355) (100) (25) -20°F 14 6 3 (-29°C) (355) (150) (75) -30°F 16 8 4 (-34°C) (405) (200) (100) -40°F 18 8 4 (-40°C) (455) (200) (100) -50°F 20 10 6 (-46°C) (510) (255) (150) -60°F 20 10 6 (-51°C) (510) (255) (150) Notes: 1. For protected area temperatures that occur between values listed above,use the next cooler temperature, 2. These lengths are Inclusive of wind velocities up to 30 mph 06,6 kph). TABLE B EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS l NOTICE Exposure Length Do not install Series DS-2 Dry-Type When using dry sprinklers in wet pipe Sprinkler into any other type fitting sprinkler systems to protect areas without first consulting the Technical subject to freezing temperatures, use , Services department. Failure to use the Table 13 to determine a sprinkler's , appropriate fitting may result in one of appropriate exposed barrel length the following: to prevent water from freezing in the connecting pipes due to conduction. • failure of the sprinkler to operate prop- The exposed barrel length measure- erly due to formation of ice over the ment must be taken from the face of Inlet Plug or binding of the inlet Plug the sprinkler fitting to the surface of the •inufficient engagement of the Inlet structure or insulation that is exposed pipe-threads with consequent leakage to the heated area. Refer to Figure 10 for an example. Drainage For protected area temperatures In accordance with the minimum between those given above, the requirements of the National Fire minimum recommended length from Protection Association for dry pipe the face of the fitting to the outside of sprinkler systems, branch, cross, the protected area may be determined and feed-main piping connected to by interpolating between the indicated dry sprinklers and subject to freezing values. . temperatures must be pitched for proper drainage. TFP530 Page 4 of 8 • K-factor K-factor, r` _^ LENGTH, gpm/ps11/2 ■ _ Inches(mm) (Ipm/bar1/2) SPRINKLER FITTING 2-1/2 to 6-1/4 11.2 FACE OF (REFER TO DESIGN (63 mm to 159 mm) (161,3) SPRINKLER I I CRITERIA SECTION) FITTING 6-1/2 to 10-1/2 11.1 (165 mm to 267 mm) (159,8) ORDER LENGTHS: 3-5/8"DIA. 10-3/4 to 14-3/4 11.0 3"to 48" (92,1 mm) (273 mm to 375 mm) (158,4) (76,2 to 1219,2 mm) I I IN 1/4"(6,4 mm) 2 3/4" DIA. 15 to 18-3/4 10.9 �'�` (381 mm to 476 mm) (157,0) INCREMENTS ! 1 (69,9 mm) 19 to 23 10.8 I (483 mm to 584 mm) (155,5) FACE OF ( 23-1/4 to 26-3/4 10.7 CEILING (591 mm to 679 mm) (154,1) 1 /%1 I%� 27-1/4 to 31-1/4 10.6 j — (692 mm to 794 mm) (152,6) 2-1/4±1/8"* 31-i/2 to 35-1/4 10.5 (57,2±3,2 mm) � * ESCUTCHEON (800 mm to 895 mm) (151,2) ■ WILL PERMIT 35-1/2 to 39-1/2 10.4 I r f ±1/4"(6,4 mm) (902 mm to 1003 mm) (149,8) t m _. ADJUSTMENT 39-3/4 to 43-1/2 10.3 (1010 mm to 1105 mm) (148,3) FIGURE 2 43-3/4 to 48 10.2 SERIES DS-2 DRY-TYPE PENDENT WITH FLUSH ESCUTCHEON (1111 mm to 1219 mm) (146,9) STANDARD RESPONSE(TY5255)OR QUICK RESPONSE(TY5235) Notes: 1C-factor Length is determined as follows: • [Lab:Order Length from Figure 2 plus 1/2 inch - (12.7 mm) (" �� • Recessed:Order Length from Figure 3 plus 1/4 t inch(6,3 mm) / -�� • Extended:Order Length from Figure 4 plus SPRINKLER FITTING inchout EeC t) • pyflhout Esc tcffeon:Order Length Irom Figure 5 FACE OF (REFER TO DESIGN minus 2-1/4 Inches(57,2 mm) SPRINKLER I I CRITERIA SECTION) TABLE C FITTING I DISCHARGE COEFFICIENTS ORDER LENGTHS: _ 3-5/8"DIA. 3-1/2"to 48" !I (92,1 mm) (88,9 to 1219,2 mm) I I IN 1/4"(6,4 mm) 2-3/4"DIA. INCREMENTS (69,9 mm)---*-I I FACE OF ■ CEILING i \ , I ,A.1,,r 1" 1-518±1/8'* '1011 *WILL ESCUTCHEON PERMIT (41,3±3,2 mm) -- �h�k. ±3/8"(9,5 mm) ADJUSTMENT MENT FIGURE 3 SERIES DS-2 DRY-TYPE PENDENT WITH RECESSED ESCUTCHEON STANDARD RESPONSE(TY5255)OR QUICK RESPONSE(TY5235) TFP530 Page 5 of 8 I-M`- SPRINKLER FITTING SPRINKLER FACET F (REFER TO DESIGN IL--- CHING ORDER LENGTHS: SPRINKLER CRITERIA SECTION) EA 1"to 45-1/4' FITTING 3-5/8"DIA. (25,4 to 1149,4 mm) (92,1 mm) WRENCH IN 1/4"(6,4 mm) I I RECESS INCREMENTS FACE OF 2-3/4'DIA, CEILING I—(69,9 Tom) �!r �' O PUSH WRENCH ��� IN TO ENSURE FOR ORDER LENGTHS ENGAGEMENT *ESCUTCHEON WITH SPRINKLER �� <3-1/4"(82,6 mm): WILL PERMIT 4-7/8x1/8"(123,8±3,2 mm)* 15/8'(15,9 mm) WRENCHING AREA -or- FOR ORDER LENGTHS ADJUSTMENT FIGURE 6 2 3-1/4"(82,6 mm): W-TYPE 17 5-5/811/8"(142,913,2 mm)** 111710 ** ESCUTCHEON SPRINKLER WRENCH WILL PERMIT /'�/� ±1-3/8"(34,9 mm) Ilk_ ADJUSTMENT FIGURE 4 SERIES DS-2 DRY-TYPE PENDENT WITH EXTENDED ESCUTCHEON (i, STANDARD RESPONSE(TY5255)OR QUICK RESPONSE(TY5235) SPRINKLER FITTING FACE OF (REFER TO DESIGN p LI< SPRINKLER CRITERIA SECTION) c - FITTING w DO NOT ORDER LENGTHS: FIGURE 7 5'to 48" DO NOT GRASP DEFLECTOR (127,0 to 1219,2 mm) ' IN 1/4"(6,4 mm) INCREMENTS MINIMUM 2-1/4'(57,2 mm) DEFLECTOR TO CEILING -- f FIGURE 5 SERIES DS-2 DRY-TYPE PENDENT WITHOUT ESCUTCHEON STANDARD RESPONSE(TY5255)OR QUICK RESPONSE(TY5235) TFPS30 Page 6 of 8 A leak-tight 1 inch NPT sprinkler joint should be obtained by applying TO WET SIDE FACE OF a minimum-to-maximum torque of SYSTEM OUTLET SPRINKLER 20 to 30 ft.-lbs. (26,8 to 40,2 Nm). • PLUGGED FITTING Higher levels of torque may distort the sprinkler Inlet with consequent leakage HEATED ■ I: HEATED EXPOSURE or impairment of the sprinkler. AREA AREA LENGTH Do not attempt to compensate (SEE DESIGN for insufficient adjustment in an SPRINKLER CRITERIA Escutcheon Plate by under or over- DSB 2 FITTING DSB-2 SECTION) tightening the sprinkler. Re-adjust the BOOT (SEE DESIGN BOOT CRITERIA position of the sprinkler fitting to suit. SECTION) Note:Install pendent sprinklers only in the pendent position. The Deflector of 77777 ' M l— a pendent sprinkler must be parallel to 1 re ri the ceiling. Step 1. With a non-hardening pipe- thread sealant such as TEFLON applied to the Inlet threads, hand-tighten the sprinkler into the sprinkler fitting. Do FIGURE 8 not grasp the sprinkler by the Deflector SPRINKLER FITTING FIGURE 10 {Ref. Figure 7). HEATED AREA EXPOSURE LENGTH Step 2. Wrench-tighten the sprinkler using either: / RUN STRAP TIES •a pipe wrench on the Inlet Band or the / �� rE-OUTLET • (ENDS ON Casing(Ref. Figure 1) •PLUGGED OPPOSING the W-Type 17 Sprinkler Wrench on -I R SIDES OF the Wrench Flat(Ref. Figure 2) SPRINKLER BOOT) TO DRY r— FITTING Apply the Wrench Recess of the— SYSTEM (SEE DESIGN DSB-2 BOOT W-Type 17 Sprinkler Wrench to the CRITERIA / ADHESIVE Wrench Flat. AREA SECTION) ,.. Note: If sprinkler removal becomes • SUBJECT -1- 2-9,9 mm) necessary, remove the sprinkler using TO DSB-2 �� {69,9 mm) the same wrenching method noted FREEZING iiv BOOT CLEARANCE HOLE above.Sprinkler removal is easier when a non-hardening sealant was used INSULATED and torque guidelines were followed. mom' FREEZER After removal,inspect the sprinkler for ��T Ilip .�,..I STRUCTURE damage. ICIDS-2 Step 3.After installing the ceiling and i, SHOWN applying a ceiling finish, slide on the ....c IN�t WITH FLUSH outer piece of the escutcheon until it ESCUTCHEON comes in contact with the ceiling. Do not lift the ceiling panel out of its normal FIGURE 11 position. FIGURE 9 MODEL DSB-2 DRY SPRINKLER When using the Deep Escutcheon, SPRINKLER FITTING BOOT WITH SERIES DS-2 hold When outer piece Deep contact with the UNHEATED AREA DRY-TYPE PENDENT SPRINKLER hold surface(ceiling or contact with Then rotate the inner piece approximately Installation the sprinkler Casing. With reference 1/4 turn with respect to the outer piece, to Figure 7,do not grasp the sprinkler to hold the Deep Escutcheon firmly TYCO Series DS-2 Dry-Type Sprinklers, by the Deflector. Failure to follow this together. 11.2K Pendent, Standard(5 mm bulb) instruction may impair performance of and Quick Response(3 mm bulb),and the device. Standard Coverage must be installed in Do not install any bulb-type sprinkler if accordance with this section. the bulb is cracked or there is lit loss o'f General Instructions liquid from the bulb.With the sprinkler held horizontally, a small air bubble Series DS-2 Dry-Type Sprinklers must should be present.The diameter of the only be installed in fittings that meet air bubble is approximately 1/16 inch the requirements of the Design Criteria (1,6 mm)for the 135°F(57°C)rating to section. Refer to the Design Criteria 1/8 inch(3,2 mm)for the 360°F(182°C) section for other important require- rating. ments regarding piping design and sealing of the clearance space around TPP53O Page 7 of 8 Care and Automatic sprinkler systems are recom- mended to be inspected, tested, and Maintenance maintained by a qualified Inspection Service in accordance with local • TYCO Series DS-2 Dry-Type Sprinklers, requirements and/or national codes. 11.2K Pendent, Standard(5 mm bulb) and Quick Response(3 mm bulb),and Limited Standard Coverage must be maintained and serviced in accordance with this Warranty section. Before closing a fire protection system For warranty terms and conditions, main control valve for maintenance visit www.tyco-fire.com. work on the fire protection system that it controls, obtain permission to i dern shut down the affected fire protection Ordering systems from the proper authorities Procedure and notify all personnel who may be affected by this action. Contact your local distributor for Absence of the outer piece of an availability. When placing an order, escutcheon, which is used to cover a indicate the full product name and part clearance hole, may delay the time to number(P/N). sprinkler operation in a fire situation. A Vent Hole is provided in the Bulb Seat Dry-Type Sprinkler (Figure 1)to indicate if the Dry Sprinkler When ordering Series DS-2 Dry Type is remaining dry. Evidence of leakage Sprinklers, 11.2K Pendent,Standard(5 from the Vent Hole indicates potential mm bulb)and Quick Response(3 mm leakage past the Inlet seal and the need bulb),and Standard Coverage,specify to remdve the sprinkler to determine the following information: the cause of leakage(e.g.,an improper •SIN: installation or an ice plug). Close the TY5255—Standard Response fire protection system control valve and TY5235—Quick Response drain the system before removing the • Length: sprinkler. Dry-Type Sprinklers are furnished Sprinklers which are found to be based upon Order Length as measured leaking or exhibiting visible signs of from the face of the ceiling to the face corrosion must be replaced. of the sprinkler fitting(Ref.Figures 2 Automatic sprinklers must never be through 5).After the measurement is painted, plated, coated, or otherwise taken,round it to the nearest 1/4 inch altered after leaving the factory. increment. Modified sprinklers must be replaced. • Inlet Connections: Sprinklers that have been exposed to 1 Inch NPT corrosive products of combustion, but (Standard) have not operated, should be replaced ISO 7-R 1 if they cannot be completely cleaned by wiping the sprinkler with a cloth or (For information on ISO Inlet Thread by brushing it with a soft bristle brush. Connections, contact your Tyco Care must be exercised to avoid Sales Representative.) damage to the sprinklers — before, •Temperature Rating during,and after installation.Sprinklers • Sprinkler Finish damaged by dropping,striking,wrench • twist/slippage, or the like, must be Escutcheon Type and Finish, as replaced. Also, replace any sprinkler applicable that has a cracked bulb or that has lost • Part Number from Table D liquid from its bulb.(Refer to Installation Section.) Sprinkler Wrench The owner is responsible for the Specify W-Type 17 Sprinkler Wrench, inspection, testing, and mainte- P/N 56-010-4 118 nance of their fire protection system and devices in compliance with this Sprinkler Boot document, as well as with the appli- Specify Model DSB-2 Dry Sprinkler cable standards of the National Fire Boot,P/N 63-000-0-002 • Protection Association(e.g., NFPA 25), This Part Number includes one (1) in addition to the standards of any other Boot, two (2) Strap Ties, and 1/3 oz. authorities having jurisdiction.Contact of Adhesive (a quantity sufficient for the installing contractor or product installing one boot). manufacturer with any questions. TFP530 Page 8 of 8 P/N* 61 - XXX - X - XXX ORDER LENGTH2 SIN SPRINKLER ESCUTCHEON 055 5.50" FINISH FINISH1 Standard Response Pendent TY5255 CHROME SIGNAL WHITE 10 with Flush Escutcheon (Figure 2) 0 082 8.25" PLATED (RAL9003) 11 Standard Response Pendent TY5255 1 NATURAL SIGNAL WHITE 180 18.00" with Recessed Escutcheon (Figure 3) BRASS (RAL9003) 12 Standard Response Pendent TY5255 4 SIGNAL WHITE SIGNAL WHITE 187 18.75" with Extended Escutcheon (Figure 4) (RAL9003) (RAL9003) 13 Standard Response Pendent TY5255 5 NATURAL BRASS 372 37.25' without Escutcheon (Figure 5) BRASS PLATED 9 CHROME CHROME 480 48.00" PLATED PLATED 30 Quick Response Pendent TY5235 with Flush Escutcheon (Figure 2) TEMPERATURE 31 Quick Response Pendent TY5235 I RATING with Recessed Escutcheon (Figure 3) 0 135°F(57°C) 32 Quick Response Pendent TY5235 with Extended Escutcheon (Figure 4) 1 155°F(68°C) 35 Quick Response Pendent TY5235 without Escutcheon (Figure 5) 2 175°F(79°C) Notes: 1. Escutcheon Finish applies to sprinklers with escutcheons. 2. Dry-Type Sprinklers are furnished based upon"Order Length'as measured per Figures 2 through 5,as 3 200°F(93°C) applicable,and for each individual sprinkler where it is to be installed.After the measurement is taken, round it to the nearest 1/4 inch increment. ' Use Prefix"I"for ISO 1-R1 Connection(e.g..i-61-101-1-18O). 4 286°F(141°C) TABLE D SERIES DS-2 STANDARD AND QUICK RESPONSE,STANDARD COVERAGE, DRY-TYPE SPRINKLERS PART NUMBER SELECTION GLOBAL HEADQUARTERS)1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright C 2014 Tyco Fire Products,LP. All rights reserved. tqc® TEFLON Is trademark of the DuPont Corporation. Fine Protection Products