TEST AND BALANCE
REPORT
WASHINGTON SQUARE MALL#K06
PROJECT: THE DUCK STORE
LOCATION: Tigard, Oregon
ARCHITECT: Ankrom Moisan Architects
ENGINEER: HVAC, Inc.
CONTRACTOR: Perlo Construction Company
MECHANICAL: HVAC, Inc.
iso
PROJECT PERFO ' ; ANCE GUARANTY
Pursuant to the agreement between:
PRECISIONAIRE NORTHWEST
And
HVAC, Inc.
The above testing and balancing agency will test and balance all systems in accordance with the plans
and specifications as prepared by;
Ankrom Moisan Architects, Inc.
All systems as outlined in these specifications shall be balanced to optimum performance capabilities
of the design and equipment. Testing and balancing shall be done in the accordance as published by the
Industry Standards.
{
As part of this performance guaranty,the Engineer,or Architect may call upon Precisionaire
Northwest to assist them with all technical or field problems pertaining to the final balanced condition of
the system.No extra charges will be made for these services.
PROJECT: THE DUCK STORE— WASHINGTON SQUARE MALL #K06
LOCATION: Tigard, Oregon
ENGINEER: HVAC, Inc.
GENERAL: Perlo Construction Company
Guarantee Period: 1 Year Completion Date: September 15, 2015
OR CCB #111307 WA PRECIN*915CS
PRECISIONAIRE NORTHWEST
P.O. Box 341
Canby,OR 97013
Office(503)651-3120 Email: pnw(a�canby.com Facsimile(503)651-3122
1
BT , e;
i
1
! 1
cisionairo NorthWest
Independent H.V.A.C.Testing &Balancing
Project: THE DUCK STORE -WASHINGTON SQUARE MALL
System: (E)VAV-1
DIRECT DRIVE FAN TEST
Manufacturer: TRANE
Model Number: YZD408A-VPEF
Serial Number: R07L78412A
Specified Actual Specified Actual
!Total CFM 2000 1925
Static Pressure I (E) I
Motor Amperage 4.3 1.6
Motor Voltage 115-1-60 119-1-60
Horse Power 1/3. ! 1/3. -'
Service Factor ! 1
Speed Tap Set On I SPEED CONTROLLER
ANNOTATION: ANNOTATION:
VAV-1 DD
1
PRW
precisionairo NorthWest
Independent A.V.A_C.Testing &Balancing
Project: THE DUCK STORE-WASHINGTON SQUARE MALL
System (E)VAV-1 SUPPLY
AIR DISTRIBUTION TEST SHEET
Terminal Room Terminal Factor Design Test 1 Test 2 Final
Number Number Code Size FPM CFM FPM CFM FPM CFM FPM CFM %
1 HALL CD-1 6" R 1 50 50 54 54 - 55 55 110%
2 Office CD-1 8" R 1 250 250 220 220 - 240 240 96%
3 Sales CD-2 12x12 1 250 250 240 240 - 245 245 98%
4 Sales CD-2 12x12 1 250 250 230 230 - 240 240 96%
5 Sales CD-2 12x12 1 250 250 230 230 - 230 230 92%
6 Sales CD-2 12x12 1 250 250 245 245 - 250 250 100%
7 Sales CD-2 12x12 1 250 250 225 225 - 230 230 92%
8 Sales CD-2 12x12 1 250 250 220 220 - 240 240 96%
9 Entry CD-2 8x8 1 1100 100 140 140 - 100 100 100%
10 Entry CD-2 8x8 1 100 100 130 130 - 95 95 95%
TOTALS 2000 1934 0 1925 96%
ANNOTATION:
VAV-1 AD SA
1
P*iv
Previsional,. North West
Independent H,V.A.C.Testing &Balancing ,r
Project THE DUCK STORE-WASHINGTON SQUARE MALL
ELECTRIC COIL/DUCT HEATER TEST REPORT
Rated Actual
Volts/ Voltage Amperage
Location Model No. KW Stages Phase Amps T1-T2 T2-T1 T3-T1 T1 T2 T3
(E)VAV-1 VPEF 11 2 208-3 30.5 212 215 213 30.7 31.1 30.6
VAV-1 EDH
1. N
Precisiona e Bit orthWest
_ Independent H.V.'.C.Testing&Balancing T
B.AL.AN$1 LEGEND
0 = DENOTES SUPPLY AIR TERMINAL
= D ENO IES RETURN AIR TERMINAL
= 1 NOTES EXHAUST MR TERMINAL