Report 13u14--,70/6- --00 t Premier Fire Consulting, LLC 13337 South St., Suite 151, Cerritos, CA 90703 • Tel. 562. 865. 5134 • Fax. 562. 865. 2004 August 26, 2015 15 City of Tigard 13125 SW Hall Blvd. Tigard, OR 97223 Subject: Request for Alternate Means & Methods to Accept 2015 IFC for Smoke and Heat Vent Requirements for UPS Supply Chain Solutions located at 14160 SW 72"d Ave., Suite 150,Tigard, OR 97224 Attention: Plan Check Dear Plan Check, UPS Supply Chain Solutions currently occupies the building at the above-mentioned address, with plans to expand into Suite 150 in the near future. The building is a type III-B construction, and is fully sprinklered with a design-density sprinkler system designed to provide .495 gallons over the most remote 2,000 square feet of building area with 286 degree heads. The fire sprinkler system will be upgraded to provide .60 gallons per minute over the most remote 2,000 square feet of building area with 286 degree heads. The warehouse(Suite 150)is approximately 11,838 square feet. There will be approximately 7,220 square feet of high-piled rack storage in the warehouse. The products to be stored are semi-conductor production equipment,mainframes,network switches, routers,hard drives,computers,and the spare parts to repair them.These products are classified as cartoned unexpanded plastics, a high hazard commodity. The top of storage height in this warehouse will not exceed 20'-0". The warehouse currently has no skylights or smoke vents installed, but will need some smoke vents installed to meet high piled storage requirements.Per Table 910.3 of the 2014 Oregon Fire Code, a 1:50 vent to floor ratio is required for high piled storage of high-hazard commodities 20'-0" or less in height. To meet this requirement would necessitate the installation of 8 new smoke vents in this warehouse,creating a financial hardship for the current tenant/owner. The purpose of this letter is to request an alternate means and methods approach for the acceptance of the recently released 2015 edition of the International Fire Code, on which the Oregon Fire Code is based. This most recent edition of the code makes significant changes to the way heat and smoke venting requirements are calculated. In the current code, the number i of heat and smoke vents required is based upon the commodity classification and the overall storage height. The new code, specifically section 910.3.3, simply bases the number of smoke vents required on the cubic volume of the warehouse.The formula used is: Avg=V/9000,where AvR=the required aggregate vent area(sq.ft.); and V=volume(cu.ft.)of the area that requires smoke removal. Utilizing this formula for UPS would mean dividing the cubic volume of the warehouse, 312,724(11,838(the area of hps)x 26.417(the height of the warehouse))by 9000, which results in 34.75 square feet of smoke venting required. Divide this number by 32 (the area of 1 smoke vent), and we end up with 1.09 smoke vents required for this warehouse. Therefore, 2 new smoke vents will be installed over the high piled storage area to meet the requirements set forth by section 910.3.3 of the 2015 International Fire Code. We are requesting that the City of Tigard will accept the 2015 IFC in regards to smoke venting for UPS, which would allow them to do business in your jurisdiction. We appreciate your time and understanding in this matter and look forward to a favorable resolution that is agreeable to all concerned parties in this matter. If you should have any questions regarding this matter,please feel free to call me at 562-292-4134. Sincerely, Kevin Gray • ARCHITECTURAL SPECIALTIES INC. MANUFACTURER OF: 2221 S.E. OCHOCO PORTLAND, OREGON 97222 ROOF HATCHES MAIL ADDRESS: P.O. BOX 22325 MILWAUKIE, OREGON 97269-2325 ROOF HATCHES SMOKE VENTS PHONE (503) 232-2966 FAX (503) 232.4028 WIVW.ARCHSP.COM SUNROOMS SCOPE OF WORK Section ??— Smoke Vent Skylights Quantity Description 2 Model 52101 SLSV Single lid smoke vents with clear over white double domes, 165° fusible links and mill finish extruded aluminum frames. 2 OSHA compliant Fall Protection screens with black painted finish. NOTES: 1. Product proposed for use is manufactured by Architectural Specialties, Inc. and is specified. 2. EXCLUSIONS: Installation, Fasteners, Anchors, Curbs, Flashing, Field Measurements, Structurals and Accessories. 3. Please allow approximately six to eight week's lead-time. (CD135-FEB'13)Ultra Tape SV CCB# 59161 A'; Architectural SINGLE LID SMOKE VENT S S •ecialties Inc. P.O.Box 22325 (503)232-2966 . Portland;OR 97269 FAX 232-4025 STANDARD SIZES irzy. Model No. Outside Curb Dimension 1111111 SLSV52141 51"X 99" Extruded Alum. L SLSV5252 51"X 51" Acrylic Domes Frame ----_,.....xt0 SPECIFICATIONS: Architectural Specialties, I ‘.............-::: nc., Smoke Vents shall be equipped with a UL fusible link designed to open at 165°F. The Smoke Vent shall be completely factory assembled ready , J , for installation on a roof curb according to .,„� ,, manufacturer's recommendations. Acrylic domes ( > ;; to conform to AAMA 1601.1-1976 for a design itimi ” Ik load of 40 psf. All operation mechanisms shall be IF enclosed within the unit. The acrylic dome(s) are �� formed to a specified shape from a single sheet of ' " clear and/or translucent type CC2 fire rated acrylic plastic. Skylight frame and retainer cap shall be 6063-T5 extruded aluminum with mininnun wall � Ilyi-,1-.1 thickness of .070 inches The skylight frame shall have an integral condensation gutter and exterior weep holes. All mitered corners are to be welded by the heliarc process. SAFETY CONSIDERATIONS: While Architectural Specialties, Inc. skylights are U.L. Fusible Link _ N designed to support the weight of snow, ice and the - , ' - force of normal winds, they are not designed to withstand the weight of people. If human safety Operable Mechanism becomes a consideration, skylights should be protected by railing, grids or screens. Call for a quote if required. ` Curb/Flashing NOTE: Double glazed skylights are subject to i by others formation of condensation between domes. This may be objectionable when both domes are transparent. *Minimum recommended curb pitch is'A":12". **Units not to be used as openable skylights. ***Use stainless steel or aluminum fasteners. Contractor: Project Name: J Architect: Mildren Design Group Project Address: Distributor: City/ State: WWW.ARCHSP.COM APPROVAL SHEET/156(DSC 6-1-03) -INSTALLATION INSTRUCTIONS .•• •As soon as units have been received at jobsito,open cartons or crates and Inspect to Insure that the units were not damaged during shipping. . . 44 .:2';'...?..;,•;!# • • - - - ANGLE .00'34 1. Check well opening and curb construction for correct • dimensions and squareness. Opening should have `-, ', wood curb(min. 1 1/2'x 4') on all four sides secured " 1_'': L'J W000 CURB O :4:-,-.,\,•••::::::::OpF "' s:� to structure. gwl:�;:. ;: BUILT-UP _ i7�` :'ti ��A,Q �' BASE FLASHING ="}�•'�'�`:"t=«•: � GRAVEL 2. Check that curb flashing has been completed property. =`+'^•a.:y.-.Ina . -1.4?...- {ttM1i,-.i1::..:.,_ '•'':U is `V ROOFING FELTS CANT STRIPS • 'CAUTION -- :%,<s'' �' UNIT , -;µ;>,'"'."''", r„C,.iy•r+: ®BUTYL CAULKING .: " ''.• : OR TAPE �;I4.:-�.�-�'��.� '.,_.. .. 11,...`• .. :....17..: F ==`r,: 'Caution—Do not allow roofing materials to come in F`` .—4. .; contact with dome. Remove protective wrapping after .�%+ i:; installation. �` f_:r;,;. K;,�..:,t 3. Apply caulking or tape all around lop of curb to a.i.,V,\ c"`` properly weather seal unit. . / iho :zZSFr- - • '11 .-<:s-• s�:�ca.�at..+. 4. Center unit over opening. Press firmly Into sealant. • %,;;r �^:3.;.Sj,;, <,;. 2, Note: If unit does not slip down easily onto curb, do ylylY,t".0:4 <:, ; . ,,; ,,,., not force. Recheck opening and curb dimensions and ..`:- '>'�; F i '?::>_„n ". s5: �1� 1 !r� �,�. J1 ;a LNG L ` ! IOL3..ri1kAuID'S • 9 INC.L CONSTRUCTION INSPECTION • 5405 N.Lagoon Avenue MATERIALS INSPECTION NONELDIN UCTIV(TESTING CHEMICAL ANALYSIS P.O,Box 17126 WELDING CEATI f ICATION PHYSICAL TESTING Ponland,Oregon 97217-0126 SOIL TESTING ASSAYING ASSAYING Phone:(503)289-1778 FAX:289.1918 • December 27 , 1990 Architectural Specialties P . O . Box 22325 Portland, OR 97222 Attn : Herb Kroeger • •. Subiect : Load-Release tests performed per your P.-0 . >""4515 . Item: One ( 1 ) Double Lid Smoke Vent, Model : 52101 ( each leaf spring loaded with activation by U. L`. ' listed fusible link, ) • Ref : Frame ; 6063-T5 (0 . 07" Thick) Dome : Clear/Tinted C-C2 Acrylic Plastic (0. 25 " Thick exterior dome ) (0. 125" Thick interior dome ) * Report: T . D. Uniform Load Test Results - Smoke Vent P. 10 psi Dome lid opened to 901 under load Smoke Vent B 10 psf Dome lid opened to 90° under load It has been a pleasure serving you . If 9 Y we may be of further assistance , please feel free to contact the undersigned at ( 503 ) 289-1778. • Rehectfu ly N l•1 T TE TING LABORATORIES, INC . P t I ish Supervisor, Special Projects • Report No. 340863 *Revised 1/03/91 • AS A MUTUAL PR OTECT10N TO CLIENTS.THE PUBLIC AND OUSSCLVES,ALL REPORTS ARC SUBMITTED AS TN( CONAIOENNAL PROPERTY Of CLICNTS ANDARC IN T(NDEDfOR THE USE Or OURCLIENTS ONLY.NOOTMERPERSON' • OR ENTITY MAY UTILIZE THE REPORT OR ANY PORTION TNCR(O'WITHOUT OUR WRITTEN AVTNORIEATIOW- INC.RAO TESTING 3310 Hill Avenue, Everett,WA 98201 Phone:(425)259-6799 FAX:(425)259-4936 . email:qualtest @premierl.net AAMA/WDMA/CSA 101/I.S. 2/A440-05 • STRUCTURAL TEST REPORT • 52006-575 REPORT TO: ARCHITECTURAL SPECIALTIES P.O. BOX 22325 PORTLAND, OR 97269 ORIGINAL REPORT NUMBER: S2006-575 ORIGINAL REPORT DATE: 09/25/2006 PRODUCT: 1308 mm X 2527 mm (52" X 100") CURB MOUNT ACRYLIC DOME SKYLIGHT. • Report No: S2006-575 INC,QUALITY TESTING 3310 Hill Avenue, Everett,WA 98201 Phone:(425)259-6799 ' FAX: (425) 259-4936 • email:qualtest @premierl.net REPORT TO: • Architectural Specialties, Inc. P.O. Box• 22325 Portland, OR 97269 • TEST DATE: 08/15/2006 TEST STANDARDS: AAMA/WDMA/CSA 101/I .S.2/A440-05 Standard Specification for Windows, Doors and Unit Skylights. • PERFORMANCE CLASS: • SKG-R20 1308 x 2527 (52 X 100) SECONDARY DESIGNATOR: DESIGN PRESSURE (DOWNLOAD) : 1200 pa(25 psf) NEGATIVE DESIGN PRESSURE(UPLIFT) : 960 pa( 20 psf) WATER RESISTANCE TEST PRESSURE: 140 pa(2.9 psf) DESCRIPTION OF SAMPLE TESTED MODEL/TYPE: Standard curb mount, Acrylic Dome Skylight. CONFIGURATION: 0 FF,.AME SIZE: 1308 mm(51 1/2")wide by 2527 mm(99 1/2") high. FRAME TYPE: All frame members were solid aluminum extrusions : JOINT CONSTRUCTION: All corners were mitered and welded. • • • Page 1 • Report No: S2006-575 GLAZING COMPONENTS: OVERALL: Smm(3/16") nominal. DOME RISE: 200mm(7 7/8") at the apex GLAZING SYSTEM: The acrylic dome was set against a pvc gasket on the interior side and retained with glazing tape and the exterior aluminum cap on the exterior. MOUNTING DESCRIPTION: The test sample was mounted on a 51 mm(2") wide by 152 mm(6") wood curb. The curb was fastened to a plywood sheathed wood table. TEST PROCEDURE: All pressures were applied from the interior side of the test chamber, acting inward for Positive Pressures (Downloading) and outward for Negative Pressures (Uplift) . The Water Spray Rack consisted of four water spray nozzles positioned 914 mm(36") above the exterior face of the skylight. These nozzles were spaced 610 mm(24") apart and.each nozzle. supplied a .610 mm(24") cone matching the required calibrated water spray application of 5 gallons per square foot per hour. All testing was performed with the skylight set . at a zero pitch. • • • Page 2 Report No: 52006-575 TEST RESULTS 5 .3 .2 Air Leakage Resistance Test at 75 pa (1.57 psf) . ASTM 5283-04 The tested specimen meets or exceeds the performance levels specified in AAMA/WDMA/CSA 101/T .S.2/A440-05 for air leakage resistance. Maximum Allowable = 1.5 L/s/m2 (0 .3 CFM/FT2) Optional Information at 75 pa(1.57 psf) . Total L/S (CFM) = 2.26 (4.79) ' Infiltration Rate 0. 68 L/s/m2 (0.13 CFM/ft2) 5.3 .3 Water Resistance Test . ASTM 5547-00 and ASTM E331-00 when applicable. • No Leakage after 4 cycles of 5 minutes at 140 pa(2 .9 psf) . 5.3.4.2 Uniform Load Deflection at Design Pressure ASTM 5330-02 No damage after positive 960 pa (20.0 psf) No damage after negative 960 pa(20.0 psf) Measured Deflection Positive < 1 mm(< 0.010 inches) Measured Deflection Negative < 1 mm(< 0.010 inches) Note: Deflection Measurements taken along the top cap frame jamb. 5.3.4.3 Uniform Load Structural Test. ASTM E330-02 No damage after positive 1920 pa (40.0 psf) . No damage after negative 1920 pa (40.0 psf) . • Page 3 • Report No: S2006-575 4 . 4 .3 Secondary Designator 5 . 3. 4 .3 Uniform Load Structural Test. ASTM E330-02 No damage after positive 2400 pa (50.0 psf) . - Notes: Negative (Uplift) loads are not required for Unit Skylights under the Secondary Designator. All uniform loads were maintained for a period of 60 seconds. • • • -This space left intentionally blank- • Page 4 Report No: S2006-575 Detailed assembly drawings showing wall thickness of all members, corner construction and hardware application have been compared to the sample submitted and are attached to this report. The results were secured by using the designated test methods and they indicate compliance with the performance requirements of the referenced specification. A copy of this report has been forwarded to the Administrator of the Certification Program. This report does not constitute certification of this product, which may only be granted by the Administrator. • This report is the joint property of Quality Testing and the Client to whom it is issued. Permission to reproduce this report by anyone other than Quality Testing and the Client must •be granted in writing by both of the above parties. This report may not be reproduced except in its entirety. The results in this report are actual tested values and are applicable to the sample tested only, using the components and construction methods described herein. • Randal J.V Voorst President • Page 5 • * yam. ${ �- . _ 11 .nt�, t� C `�' �y. 9r) — HativacTJRPit nF; .� 2 I S,.G, OCUIOCO PORTLAND, OREQON 9722. ' _ - MOM -'MAIL AlDR7 SS: P.O. 130:x"22325 M1 I AULa , OR L ON 97269.2325 -: °`' wan 1'L a PHONE (503) 232.290 !AX (503) 23;-402:1 WIVI A UIISP.COM '' SHADING COEFFICIENTS & TRANSMITTANCE OF ACRYLIC DOMES ,..,/ HUE COLOR TRANSMITTANCE (SC) SHADING ** (SHGC) Solar NUMBER PERCENTAGE (%) COEFFICIENT Heat Gain Coefficient Rohm 8t Visible Solar Single Double Double Haas Light Energy Dome Dome Dome Gray 2537 33 41 0.63 0.49 .426 Gray 2094 45 55 0.74 0.61 0.530 *Bronze 2412 27 35 0.53 0.43 0.374 Bronze 2404 49 56 0.72 0.62 0.539 *White 2447 50 53 0.60 0.45 0.391 White 2067 71 71 0.60 0.59 0.513 Clear Color-less 92 86 0.98 0.89 0.774 Inner dome assumed to be of clear colorless acrylic *Industry Standard colors **SHGC—Solar Heat Gain Coefficient value is figure is based off of calculations according to http://www.daviddarling.info/encyclopedia/S/AE_solar_heat_gain coefficient.html and is calculated as SC(shading coefficient)X 0.87=SHGC 3/16" Thick U-VALUE: Winter Heat U-VALUE: Summer Heat Gain Acrylic Loss Single Dome 1.20 0.80 Double Dome 0.70 0.50 Triple Dome 0.50 0.30 Values are per sq.ft.of opening area, not per st.ft.of dome surface. Values are for the acrylic portion of the skylights. U-Values are BTU/HR/SQ.FT./F) Serer/Templates/Acrylic U-Value Performance Chart(updated dec.2012) EAST COAST: 1-800-262-6669 . HOOF PRODUCTS, INC. WEST COAST: 1-866-500-8353 Model: RPSS-RT Retrofit Safety Screen for Installation at Top of Roof Curbs Standard Construction: Frame: Welded 14 ga. Galvanized steel. Safety Screen: 3/16"cold rolled Galvanized steel rods welded in 4"X4" 'grid pattern. All welds micro-sealed and prime painted after fabrication. -------- ---- ------- Added Options (When Reauired): RPI Job #: 4" X 4" GRID PATTERN Project:_ Ultra Tape T.I. Architect: Mildren Design Group TO INSTALL ON TOP OF NEW OR EXISTING ROOF CURBS O.D. I.D. —� iai� �• 14 GA. 1/4"DIA.HOLES IIUUI GALV. PRE-DRILLED l•i■■U.1 ,Ul / 6"0.C. 11..1111.11111111111 1■;■;■■.011111 111v111.11'■v.1 a 111111111.1.111111.1 - W 1011 ! ■■■■1 O — 1011,��■■■j ■I INN ONEimol1 • 5/8 1 /ima inox1 -�- - SAFETY SCREEN ♦..11 j■■i�1 3/16"COLD ROLLED GALV. --114- Ij•■■■•1■i ; I STEEL RODS WELDED IN I ■•,••!■11i1 4"X4" GRID PATTERN. SECTION -A (ISOI PLAN Qty. I.D. O.D. W Tag: 2 44" SQ. 48" SQ. 2" FOR INSTALLATION ON EXISTING 48" SQ.O.D. ROOF CURB RPSS-RT Page 1 of