Report r� Fl%zoiso '17••• • • • • • • • • • • • . . l � 3 • • .. •• . . . • Y • ... • • •. • • • ••• • • • • • . • . .•• METRO Safety&Fire, Inc,. 143 .SE Sjaik St': ". RECEIVED Portland;Or'gon ;972 .3.•* 5.Q3;231,-2999 SEP 2 3 2015• • CITY OF TIGARD ' ' •" "' " • • BUILDING DIVISION • •• • ••• • • Description of Scope of work for: Deacon General Contracting — Triangle Point — 2nd Floor Tenant Improvement — NW Management — Tigard Oregon — Fire Alarm System Modification. As part of a tenant improvement for the suite on the 2nd floor of the building we are relocating (10) horn strobes and removing (4) smoke detectors from the area. The one manual pull station located at the rear exit will remain in it's current location The existing fire alarm panel is a Silent Knight 5820XL, which utilizes (4) notification circuits. In addition to the (4) on board circuits there is a notification expansion panel next to the fire alarm panel that provides an additional (4) notification circuits. The circuit that serves the suite that the tenant improvement is being conducted is from the notification expansion panel circuit #3. Since we are only relocating the current devices, no additional circuits will need to be provided. (See the "voltage drop" calc.) The notification expansion panel is a Silent Knight 5495. (Data sheet provided) The horn strobes currently in place are Edwards EGC-HDVM. (see voltage drop calc's and spec sheets) When any of the smoke detectors, sprinkler water flow, or manual pull stations are activated, the horn strobes will activate and remain activated until silenced by someone at the fire alarm panel or remote annunciator. The system is monitored by a UL listed central station. INTELLIKNIGHT FIRE ALARM CONTROL PANEL • • • ••• • • ••• • • • ••• •• •• •• •• •• •• • •• • SILENT • • • IntelliKnight® Model 5820XL KNIGHT • • • • • ••• : ••• •• : •• • : : • • •: •• Addressable Fire • • ••• • ••• • • by Honeywell ••• ••• ••• • Arta' fn Control System Tha.lp,telliKpight.$ystem is the easy way to mike; Qf:fire alarm technology. • • • • • • • • • • • ••• • • IntelliKnight 5820XL is the first fire alarm system to provide you with revolutionary value and performance in addressable sensing technology. The 5820XL FACP offers exclusive, built-in digital communication, distributed intelligent power, a modular design and an expanded, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the 5820XL system, or to locate your nearest source, please call 800-328-0103. Description 5820XL is an intelligent addressable fire alarm control panel (FACP). The basic 5820XL system can be expanded by adding modules such as 5860 remote annunciator, 5815XL signalling 1 line circuit expander, 5824 serial/parallel printer interface - ... �; module (for printing system reports), and 5895XL intelligent =` power module. 5820XL supports SD or SK devices. 5820XL also features a powerful built-in dual line fire communicator that allows for reporting of all system activity to a remote monitoring location. Features • Built in support for 99 SK detectors and 99 SK modules, expandable to 396 SK detectors and 396 SK modules using System Sensor protocol • Built in support for 127 SD devices, expandable to 508 SD 6:11,4 devices using the SD protocol. •�R°° • Uses standard wire—no shielded or twisted pair required • Built-in digital communicator Model 5820XL • Central station reporting by point or by zone • Built-in synchronization for appliances from AMSECO®, • 6 amp power supply and maximum Gentex®, Faraday, System Sensor, and Wheelock® charging capacity of 35 amp hours (An additional cabinet enclosure is required for • FlexputTM I/O circuits batteries in excess of 18 amp hours) • Supports Class B (Style 4)and Class A(Style 6) configuration • Programmable date setting for Daylight for SLC, SBUS, and Flexput circuits Saving Time • 13 pre-programmed output cadences (including ANSI-3.41) and 4 programmable outputs Installation • Built-in annunciator with 80-character LCD display The 5820XL can be surface or flush • RS-485 bus provides communication to system accessories mounted • Built-in RS-232 and USB interface for programming via PC • Built-in Form C trouble relay rated at 2.5 amps at 27.4 VDC Compatibility • Improvements in SKSS software deliver five times faster The 5820XL signal line circuit (SLC) uploads/downloads supports multiple device types of the same • Two built-in Form C programmable relays rated at 2.5 amps protocol: at 27.4 VDC • SK (System Sensor) • Plex-1 door option combines a dead front cabinet door with a SD clear window, limiting access to the panel while providing • single button operation of the reset and silence functions You cannot mix SD and SK SLC devices on a FACP. INTELLIKNI$3HT FIRE ALARM CONTROL PANEL . • • • • • ••• • • •• • • • • . • • • • • • • • • • • • • • • • • •• . IntelliKnight Model 5820XL ••• ••• ••• . ••• Addressable Fire Alarm Contrp,Panel••• • ;• • •• ••• • ••• • .. .. • • • • • • • • • • Indicator Lights 5820XL future:a 4 ppipggwir•Upply: required to start a new system.The General Alarm (Red): Flashes when in and maxi fiurrAitterx ch$rgtng: : •••• built-in keypad and 5860 remote alarm; solid when alarm silenced capacity of 35 amp hours.An additional annunciator give on-site access to all cabinet enclosure(PN RBB)is required programming.You can also program Supervisory(Yellow): Flashes when a for batteries in excess of 18 amp hours. remotely using the 5660 Silent Knight supervisory condition exists; solid when Flexput circuits on 5820XL control can Software Suite,which is Windows- supervisory silenced be individually programmed to function based software. System Troubles(Yellow): Flashes as notification circuits, auxiliary power when a trouble condition exists; solid outputs, or initiation circuits that Built-In Digital Communicator when trouble silenced support both 2-and 4-wire smoke detectors. 5820XL features a built-in UL listed System Silenced(Yellow): On when an digital communicator for remote The 5820XL system operates on non- alarm, trouble or supervisory condition twisted, unshielded cable when wired reporting of system activity and system has been silenced but not yet cleared in compliance with standard wiring programming.The communicator has System Power(Green): Flashes for AC practices as called out in the National the ability to seize two telephone lines failure; solid when power systems are Electric Code 760-51 specifications for to report alarms and troubles to a normal power-limited fire protective signalling monitoring facility.The communicator cables. No special wiring is required. supervises two phone lines and will System Application 5820XL provides 13 preset notification activate a trouble signal if a line failure S Y pp is sustained for more than 45 seconds. 5820XL has one built-in signalling line cadence patterns(including ANSI 3.41) Other communication features include: circuit(SLC)which supports multiple and four user programmable selections retry if communication fails, two phone devices dependent on protocol being for fire alarm notification. number capability, download phone used.Three additional loops can be Two programmable general purpose number capability and Touch-Tone or added using the 5815XL SLC Form C relay outputs are provided on rotary dialing.The communicator is expanders to increase overall capacity. 5820XL. compatible with SIA and Ademco Additionally, the IntelliKnight system Contact ID.The format is selectable by The 5820XL SLC loops support features a built-in walk test and auto- multi le device types, including: account number. p yp g� programming. Its innovative, dead-front • Addressable photoelectric smoke cabinet design allows for flush or detector surface mounting. System maintenance •V, • Addressable ionization smoke is easy to perform. .•. •- yl\•i,.il , detector User Interface ------ • Addressable heat sensor The 5820XL built-in annunciator with q, ;a • Addressable duct smoke detector 80 character LCD display and large .... �� a • Contact module easy-to-use tactile touchpad can be • Relay output module used for system operation, .4..1 t ai '16 programming and maintenance. It has ,r t►r .. • Addressable notification module five LEDs for alarm, supervisory, • Addressable beam detector(SK system trouble, system silenced and protocol only) system power. System operations • Addressable multi-criteria smoke include silencing alarms and troubles, Approvals detector(SK protocol only) resetting alarms and the display of NFPA 13, NFPA 15, NFPA 16, alarm troubles and memory.The NFPA 72: Central Station; Remote • Addressable multi modules(SK system's non-volatile event history protocol only) buffer stores 1000 events for viewing Signalling; Local Protective Signalling from the built-in or remote annunciator. Systems;Auxiliary Protected Premises The following advanced sensor Unit;&Water Deluge Releasing capabilities are available with 5820XL: System operation can be initiated with Service. Suitable for automatic, a mechanical firefighter's key or a valid manual,waterflow, sprinkler • Automatic drift compensation 4-to 7-digit operator's code. Maintenance alert supervisory(DACT non-coded) •• Programming signalling services. • Built-in sensor test to comply with The IntelliKnight system offers several Other Approvals: UL Listed; NFPA 72 calibration testing options to simplify and speed up CSFM 7170-0559: 135; requirements • programming.The JumpStart®feature MEA 429-92-E Vol. VI; FM Approved minimizes programming G. INTELLIKNIGHT FIRE ALARM CONTROL PANEL • • • • ••• • • •• • • • • . • • • • • • • • • • • • • • • • • •. IntelliKnight Model 5820XL • Addressable Fire Alarm Contrdl•Ranel••• ••• •• •:" •• • • • • • • • • •• • • ••• •• ••• • . • • • • . • • • •• •• ••• • ••• • IntelliKnight 5820XL ••• • • • •• •• 1A6ndows Addresstle Fire/ lerm•Ststirn • • Fac61 • • • • Management Software SK(System Censor) Preto€e.Devic es ••Nindaws Based • ••• • • UpiDownload Scttware • t, i 0 _ Compatble CS ''~ Receiver r' ` '.-1-41 stoatzaatr 0. Internet 5820XL SK-212UD Connectan VrsorA rm L , IP Communicator j 5895XL --E= ■ h•uIaen Pk.,Madura I! 3F.rmCF.dovs ' 9=con 4 —I ' E�e1 IPIInM N � �-- Faro!: 5815XL 8 PS;z7 stc Exx1Id0• _• I 5860 5824 ,,��,, �,, Demoto^r ninon-or Rnt.r Gct>nw Medu - ,-4., V .7161It5 41:n.•S•/�.+f) �a • - g 6 Flexpur ti 'Ti' 110 Circuits e . 5815XL can be Inputs 51.C F-enoe or outputs n - .. 6 Flelpa° 6 I' I/0 Circuits S ! MA can be Inputs El it .. ' 4 s:.. _-- outputs „ ll�� $ Z. Ent:9ROle>IIRn1 dVnAr: ® N (/-1' a . snnw.n.frm •• l - •B200SR Mil �1K4on SK-Mordtor SK-Iso S oNro-0 SK l SKAcdlmate SKdone 6 ,� • Md0::170 Add•ei5C1e 1-90 eoletx Axreesoble SLp Mra000 3oanier Mull crter9 zone ---- lu„arr Modulo Mxule Ildnud on x::11'01 6000 0'10160 Int.re, 5860 DOtOCtl M00.10 moWWJ Module 001001cr Motto AeRp Nnuneolci ,Z.-rrd' tfir 1 ciiii ILL-11-2141' 0 SK•Phato SKMon8or-2 SK-Rdaymon-2 131C-Hcaa B224R6 822481 1321OP 8K-PIn O-T Doe Monte Ad r..1 a 6K-Heal-fOR Rainy la.ou nw.o, ■ 5880 -nct.00001 Mcaule Due Vera SI(•K�4KT ?ase na.e eax — ' Inal VOW MI m o-n. \DueaVera k-e<at-H LED reel& Detector Hoot de.Orrns I-M [I 1 i 1 J1 i I 1I1 I I 1 4 5883 PSoo In-erfr Moroi? SK-Beam SC-Mon-1O SRPt81-DA SK-Duct 6K-Mrdmon SK4Aetay-8 BK.Zane SK-Rdoy SK43eam4 Adoros0.de ta'K-peiLBA A oroszda Mortar POOP 000.1 000r00,aca Ado00:000 A ac_'.ddc Norma aLtnseoe DUO MoaUIO Mocutr n-educe Relay Bern Deaalnr N.,,'0 Po I Scour D3eCe MOW'e 1100.1 a MIIMMI 5865-4 or 5865-3 I Use the 5880 to control up to 4 __. '�•4 Sh Imo P (:POta Sn'✓el - 1 5883 Relay Interface Modules INTELLIKNIGHT FIRE ALARM CONTROL PANEL , • • • • • ••• • • •• . • • • . • • • • • • • • • • IntelliKnight Model 5820XL •• Addressable Fire Alarm Control Panel . . • ••• - • •• •• • • • • •••• •• • • • • • • • • •• • •• •••• ••• ••• • • • • • • • • • • • •• ... . a.. a Specifications S-BUS•Aoceeeorios • .. .. Miscellaneous Accessories . . • • . • • • • • Electrical 5860/R Remote Fir An n Le:ci:tor • • 5660 Silent Knight Software Suite Primary AC: Features the same€Ocher actor t aokliit. (SKSS)• 120 VRMS at 50/60 Hz, 2.5A or LCD display keypad and tirefignter's User-friendly Windows software for• 240 VRMS at 50/60 Hz, 1.4A keyswitch as the 5820XL. 5860 is gray remote programming of 5820XLs using Total Accessory Load: 6A @ 27.4 VDC, and 5860R is red. a PC. Upload and view panel account power-limited 5815XL Signal Line Circuit Expander information, event history, and detector Standby Current: 215 mA The SLC expander is used to add more status. Alarm Current: 385 mA addressable devices to the IntelliKnight 5670 Silent Knight Software Suite system. 5820XL supports three (SKSS) Flexput Circuits: 5815XL's. Each 5815XL can support 99 Powerful end-user facility management Six programmable circuits which can be SK detectors and 99 SK modules or software allows viewing of detector programmed individually as. 127 SD devices. status and event history via modem or Notification circuits: 3A @ 27.4 VDC 5895XL Intelligent Power Module direct connection. per circuit, power-limited Adds 6 amps of power, 6 Flexput I/O Plex-1 Auxiliary power circuits: 3A @ 27.4VDC circuits and 2 Form C relay circuits to a Dead front cabinet door with clear per circuit, power-limited 5820XL system. window to limit access to the FACP. Initiation Circuits: 100 mA @ 27.4VDC 5496 Intelligent Power Module RBB per circuit, power limited A 6 amp notification power expander Remote battery box accessory cabinet. that provides four power-limited notifi- Use if backup batteries are too large to Physical cation appliance circuit outputs. fit into FACP cabinet. Dimensions: Flush Mount Dimensions: 5880 LED/10 Module 16"W x 10" H x 6" D 14.5"W x 24.75"H x 3.9"D Features 40 LED outputs, 8 normally (406 mm W x 254 mm H x 152 mm D) (36.8 W x 62.9 H x 9.8 D cm ) open dry contact inputs, and one piezo SD505-DTS-K output. Remote test switch. Used with Overall Dimensions: 5865-3 and 5865-4 SD505-DUCTR. Provides remote key 16.2"W x 26.4"H x 4.2"D Remote LED Annunciator operated test function and annunciation (40.6 W x 67 H x 11.8 D cm) Features 30 programmable LED (15 of detector alarm. red and 15 yellow)outputs, and a piezo SD and SK Devices Weight. 28 lbs. (12.8 kg) sounder. The 5865-4 adds a silence See the specification sheets listed Color: Red and reset switch to the package. below for a complete listing of the SD Battery Charging Capacity: 7.0-35 AH 5883 Relay Board and SK devices. Features 10 general purpose Form C 53624 SD Devices Data Sheet Battery Size: 18 AH max allowed in relays. Used with 5880 module. 53623 SK Devices Data Sheet control panel cabinet. Larger capacity 5824 Serial/Parallel Printer batteries can be housed in RBB Interface Module accessory cabinet. Provides one parallel and one RS-232 serial port for connecting a printer to Telephone Requirements: the 5820XL. Use to print a real-time log FCC Part 15 and Part 68 approved of system events, detector status Type of Jack: RJ31X(two required) reports,and event history. Interfaces with building control system. This document is not intended to be used for installation purposes.We try to keep our SILENT Made in America Irt4 KNIGHT product information up-to-date and accurate We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice For more information,contact Silent Knight 12 Clintonville Road,Northford,CT 06472 PN 350210 Rev H2 by Honeywell Phone (203)484-7161,Fax (203)484-7118.www.silentknight.com. ©2012 Honeywell International Inc. . IntelliKnight&JumpStart are Registered Trademarks of Silent Knight Flexput is a Trademark of Silent Knight in '�o 00 '') `-) o -) o 00 " FIRE SYSTEM ACCESSORY 0 0 0 0 0 0 0 0 0 o c . o c . .. O O Oo On o 0 0 0' --. :0 0- - • • • • • • • • • • • • • • • • • •• • •• •• Firppt� er 5495 u ., - • • • • • • • •• • � �` � .__,. ::.: ; -- : Drstribuf : •Power Module t~ 4•wr,- ......z4 _- - Fl / "�- look& in an:emetga cy; •• •••m k... •AO },.,.." ;.� � •2 The Firepower 5495 Distributed Power Module by Silent Knight is the most- wiii 4 "--'.';_, powerful and cost-effective power supply available today. It delivers 6 amps of L=_-.,.�; 4• - " - notification appliance circuit power and built-in synchronization for appliances from System Sensoro,Gentex®, Wheelock and Faraday—what you need to drive power-hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. And,ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost-effective notification power supply available, you need Firepower 5495. Call Silent Knight today for more information at 1-800-446-6444. Firepower 5495 • Independent trouble relay resistors provided. Since the 5495 Distributed Power Module • AC loss delay option shuts off power draws very little power from the control, The firepower 5495 is a 6 amp to non-essential high-current it is possible to connect one Firepower notification power expander that accessories like magnetic door 5495 to each notification circuit on the provides its own AC power connection, holders control panel and still provide full battery charging circuit, and backup • Built-in synchronization for supervision of the notification circuits all battery for use with fire and security appliances from System the way back to the control panel. controls such as the Silent Knight Sensor®,Gentex'a, Wheelock and Model 5208 Fire Control Faraday /Communicator.The 5495 is the cost- __ ~� T ---`1 effective solution for powering • Stand alone operation. , notification appliances required by the • Lightweight design adds to ease of . ,- _• Americans with Disabilities Act(ADA)- installation and reduces shipping The 5495 has built-in ANSI cadence costs . - .—- ` - pattern,which can upgrade older • Operates with most polarized, UL ; . - _ - -- control panels that lack cadence Listed notification devices n: capability. • UL 864& 1481 listed Features • CSFM approved r � � .�,-- • UL Listed for 6 amps of notification power • ANSI Cadence pattern output - _ = ; • Power supply's advanced switch capability built-in - - mode design reduces damaging Connection to Local Fire Control - heat and manages power up to 50% Firepower 5495 may be connected to a ' - more efficiently than other systems local fire control which utilizes Class A I - ._ • Dip switches allow for easy or Class B type notification circuits reconfiguration operating between 9 and 32 VDC.The = , - �_ �- +`�� • 24 VDC filtered output voltage control panel's notification circuit is -- '' • Four power-limited notification connected to one of the inputs on the ' outputs; 2 Class A or 4 Class B, or 1 5495.The control panel's notification Firepower 5495 Class A and 2 Class B circuit end-of-line resistor is also Distributed Power Module connected across two terminals on the • Additional continuous auxiliary Firepower 5495,which provides output supervision between the 5495 and the • 3 amps per output circuit fire control panel. Polarized audible t SILENT • 2 inputs; 2 Class B or 2 Class A and/or visual notification devices are NI KNIGHT • Ground fault detector/indicator then connected to the 5495 signal circuits using the 4 7kfl end-of-line ,9 FIRE'S'?STEM ACCESSORY , ,0 00 OD 0 0 0 ' 0 00 0 0 0 0 3 0 0 0-..0 ._(D O O 0 0 , i. ._ 0 0 00 00 O 0 . a0 .;0 Q O --. • •. . • • • • • • • • • • • • • • • • • .00 Firepower 5495,_= • • • • • ••• �,�'] L'_ Distributed Power Module • •• •••• • ••• � ); 5 • • • • • •• • • r,� • .. ... • ... • .0 . Supervision Current:• • • Input Firepower 5495 supervises a • ... ••• •• •••voltage range: 9 - 32 VDC p p Standby•••7�ptA variety of functions including: Alarm 175 mA Battery charging • Low AC power. Auxiliary capacity 33.0 AH • Low battery condition. power circuit: 1 Ambient Temp.: 32°to 120° F • Earth ground fault. Notification 0° to 49° C • Auxiliary output power limit circuits: 4 Mechanical condition. Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or configuration: 2 Class A(Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40 64 cm H x output. (1 Class A& 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights Firepower 5495 creates a trouble condition on the host control signal Amps per AC power on : Green circuits to which it is connected. output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow Firepower 5495 still maintains the Notification Ground fault: Yellow ability to be activated by the host circuit output: 20.4 to 27.3 VDC control. In addition, the 5495 @ 3.0 amps each, Aux Trouble Yellow provides a Form C trouble relay 4.7 kO. EOL Output output as an alternative to using resistor required troubles (1-4): Yellow the notification circuit trouble. on each Class B Approvals: Electrical Specification circuit UL: 864 & 1481 AC Input 120 VAC at 2 amps No. of inputs 2 NFPA: 72 Input CSFM Output: 24 VDC at 6 amps configuration: 2 Class B or 2 Class A Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power Input Module 5495 Signal 3 (Optional) Signal 4 120 VAC Aux.Power Trouble Output Local Fire Control (Alternative to notification circuit trouble.) ItoSILENT KNIGHT 7550 Meridian Circle,Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763-493-6435 FORM#350395, Rev 04/02 FAX: 763-493-6475 World Wide Web:http://www.silentknight.com Copyright 2002 Silent Knight • • •• •• •• • • • • •• • • • • •• • •• • •• •• •• •• • • • • •• •• • • • • • • Application :•: : : Invtallati®rt anccl�ounting Genesis strobes are UL 1971-listed for use indoors as ceiling-or • All models are intended for indoor wall or ceiling applications wall-mounted public-mode notification appliances for the hearing only. Horn-strobes mount to any flush North-American 4"square impaired. Prevailing codes require strobes to be used where ambi- electrical box. • ••• ent noise conditions exceed 105 dBA(87dBA in Canada);wliere : . •• : : . . •: • • ••• • ••• /• occupants use hearing protection,and in areas of public acoom- • • • modation as defined in the Americans with Disabilities Act(see.• ••• • 0 �JO' ✓ �� application notes—USA). °� Combination horn-strobe signals must be installed in accorcMcg • • • •' C•' ' (141 i 4with uidelines established for strobe devices. o\•• • • • • � / Strobes Genesis strobes are UL 1971-listed for use indoors as ceiling-or o g wall-mounted public-mode notification appliances for the hearing impaired.Prevailing codes require strobes to be used where ambi- ent noise conditions exceed specified levels,where occupants use hearing protection, and in areas of public accommodation. Genesis ceiling horn strobes simply unlatch and twist to open. Consult with your Authority Having Jurisdiction for details. This gains access to mounting screws and the selectable candela switch.The shallow depth of Genesis devices leaves ample room All Genesis strobes exceed UL synchronization requirements behind the signal for extra wiring.Once installed with the cover in (within 10 milliseconds other over a two-hour period)when used place, no mounting screws are visible. with a synchronization source. Synchronization is important in order to avoid epileptic sensitivity. Edwards recommends that these fire alarm horn-strobes always be installed in accordance with the latest recognized edition of NOTE:The flash intensity of some visible signals may not be adequate national and local fire alarm codes. to alert or waken occupants in the protected area. Research indicates that the intensity of strobe needed to awaken 90%of sleeping persons Field Configuration is approximately 100 cd.Edwards recommends that strobes in sleeping Depending on the model, Genesis horn-strobes may be set for 15 rooms be rated at at least 110 cd. to 95,or 95 to 177 candela output(see ordering information).The WARNING:These devices will not operate without electrical power.As output setting is changed by simply opening the device and sliding fires frequently cause power interruptions, further safeguards such as the switch to the desired setting.The horn-strobe does not have backup power supplies may be required. to be removed to change the output setting.The setting remains visible through a small window on the front of the device after the cover is closed. Horns The horn-strobe comes factory set for high dB output. Low dB Genesis horn output reaches as high as 99 dB(peak)and output may be selected by cutting a jumper on the circuit board. features a unique multiple frequency tone that results in excel This reduces the output by about 5 dB. lent wall penetration and an unmistakable warning of danger.All models may be configured for either coded or non-coded signal circuits. They can also be set for low dB output with a jumper cut that reduces horn output by about 5 dB. Wiring The suggested sound pressure level for each signaling zone used Field wiring terminals accommodate#18 to#12 AWG(0.75 mm2 with alert or alarm signals is at least 15 dB above the average ambient to 2.5 mm2)wiring.Horn/strobes are interconnected with a single sound level,or 5 dB above the maximum sound level having a duration pair of wires as shown below. of at least 60 seconds,whichever is greater,measured 5 feet(1.5 m) above the floor.The average ambient sound level is,A-weighted sound Q pressure measured over a 24-hour period. To next Doubling the distance from the signal to the ear will theoretically appliance, Polarity shown in �� '� end-of-line result in a 6 dB reduction of the received sound pressure level. alarm condition rill 1 ►a�©' or return to The actual effect depends on the acoustic properties of materials '��' ���' control in the space. A 3 dBA difference represents a barely noticeable OD equipment change in volume. 0 Note:Strobes must have continuous voltage. Dimensions I 6.8"dia. (173 mm) 1.0" /(25 mm) 0 60115 mm) • Page 2 of 4 CAT:\ S.1 =S T S85001-0559 Not to:;. ',srd fc' ir, a:iat a-, o..rpos:s. Issue 9.2 • • • •• • •• • • • • •• • • • • ••• ••• •• •• •• ••• • • • • ••. ••• • • • •• • •• Current Draw • • • • • • . • • •• EGC-HDVM Temporal Horn-strobe:High dB Setting EGC-HDVMH High cd Temporal Horn-strobe:High dB Setting . UL 15cd 30cd 75cd ••• ••95 cd �•• • �95ci• • 115 cd 150 cd 177 cd •Rating RMS RMS RMS • • 14M6 • • • • RM9• RMS RMS RMS • • ••• __•_.. ••• • •-- 16 Vdc 147 190 316 5 • 672 • • .341• • 399 506 570 16 Vfwr 189 253 417 • ••451 ••• • ••187 • 578 670 711 EGC-HDVM Temporal Horn-strobe:High dB Setting • • •:I. • • •ZGCrkIDVMH High cd Temporal Horn-strobe:High dB • • • • • s ttn Typical 15 cd 30 cd 75 cd V cdo•• ••• •• pp 115 cd 150 cd 177 cd Current RMS Mean RMS Mean RMS Mean RMr9•Mean • • • RMS• Mean RMS Mean RMS Mean RMS Mean 16 Vdc 111 95 152 143 281 276 333 328 324 322 377 374 477 474 554 551 20 Vdc 91 80 124 117 219 214 257 251 258 256 299 296 369 366 417 414 24 Vdc 80 71 108 101 185 180 212 207 220 217 252 249 304 301 341 338 33 Vdc 69 62 89 84 144 140 160 156 172 169 188 185 223 220 244 241 16 Vfwr 153 81 218 123 388 240 420 268 463 265 535 312 665 400 718 442 20 Vfwr 141 70 190 100 325 188 378 219 392 211 439 240 517 287 587 334 24 Vfwr 135 64 176 90 280 154 310 180 346 179 382 212 458 246 498 271 33 Vfwr 139 61 167 80 241 122 254 133 296 142 323 152 358 178 387 194 EGC-HDVM Temporal Horn-strobe:Low dB Setting EGC-HDVMH High cd Temporal Horn-strobe:Low dB Setting Typical 15 cd 30 cd 75 cd 95 cd 95 cd 115 cd 150 cd 177 cd Current RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean 16 Vdc 108 91 149 139 275 269 327 322 317 315 378 376 480 477 544 542 20 Vdc 87 75 120 113 214 209 250 245 252 250 292 290 364 362 414 411 24 Vdc 76 66 103 97 180 175 205 201 212 211 245 243 297 295 334 332 33 Vdc 64 57 85 80 138 135 153 150 159 157 181 179 215 213 234 232 16 Vfwr 141 76 204 118 384 239 418 265 461 265 521 305 656 396 705 432 20 Vfwr 127 65 176 95 312 181 371 214 381 208 437 242 508 285 576 326 24 Vfwr 118 60 162 82 262 149 301 171 335 172 370 195 440 235 485 264 33 Vfwr 127 56 155 73 229 116 249 129 285 134 308 149 349 169 373 186 Notes and Comments 1 Current values are shown in mA 2 UL Nameplate Rating can vary from Typical Current due to measurement methods and instruments used. 3. Edwards recommends using the Typical Current for system design including NAG and Power Supply loading and voltage drop calculations. 4 Use the Vdc RMS current ratings for filtered power supply and battery AH calculations.Use the Vfwr RMS current ratings for unfiltered power supply calculations. 5 Fuses,circuit breakers and other overcurrent protection devices are typically rated for current in RMS values Most of these devices operate based upon the heating affect of the current flowing through the device.The RMS current(not the mean current)determines the heating affect and therefore,the trip and hold threshold for those devices. 6. Our industry has used'mean'currents over the years. However,UL will direct the industry to use the 2004 RMS values in the future. dBA output Light output - (effective cd) UL464 Average Peak High dB J — —I— Percent of UL rating versus angle Temporal , Temporal Setting i Temporal ' Steady <<.,......., Steady i Steady 120 110 MO 00 90 70 50 50 40 00 20 I0 0 10 70 30 40 50 . ID 40 00 100 110 120 90 16 Vdc 79.8 83.2 90.6 93.6 24 Vdc 83.3 85.4 93.6 96 6 1 33 Vdc 85 87.8 95.7 98.7 7s 75. Low dB UL464 Average Peak 6,-6\1\TemporaV ' TemporaV Setting Temporal Steady Steady Steady 16 Vdc 75 79.3 86 3 88.7 -45. ns 24 Vdc 78 83 88.8 92.4 \.ao ao 33 Vdc 80.9 85.9 91.8 95.1 5 o, 15• Notes 1.All values shown are dBA measured at 10 feet(3 01m):2.UL464 values measured in reverberation room,3.Average and Peak values are measured in anechoic chem- .- ber. Page 3 of 4 DATA S H E E T S85001-0559 Not to b) usrd for i,stallation ourou �... Issue 9.2 • • •• •• •• • • • • •• • • • • • • ••• • • •• • •• • • • •••• •• • • • • • • •• ••• ••• • •• • •• • •• • • •• •• ••• • •• • • • • •• •• • •• ••• •• • • • • •• •••• • ••• ••• ••• •• •• •••Speci ci�t oi�� • ••• :•• • • .•: Housing • • ~ e recn UV staMed,color impregnated engineered plastic.Exceeds 94V- ,� ; ,r 0 UL flammability rating.Red and white models available. Lens ••• ••• • Optipal Bade piaycarbonate(clear) • • • •N rtflA erap 4'•square box,2 1/8"(54 mm)deep(indoor wall or Contact us... Mounting • • • • • • • • • • • •••cod.y applicat onsbonly). Phone: 1-800-336-4206 • • • • • • • • • • Web: www.edwardssigna6ng.com Wire connections•• • Sc rear t6fm ialy:pingle input for both horn and strobe.#18 to#12 AWG(0.75 mm2 to 2.5 mm2)wire size Edwards Signaling is Operating environment Indoor:32-120'F(0-49'C)ambient temperature.93%relative humidity an EDWARDS brand. Meets or exceeds ULC-S525&ULC-S526,year 2004 UL 3 Farm Glen Boulevard requirements for standards UL1638 and UL1971,and complies Farmington,CT 06032 Agency listings/approvals with UL1480.All horn-strobes comply with ADA Code of Federal In Canada,contact Chubb Edwards... Regulation Chapter 28 Part 36 Final Rule.CSFM,MEA.FM pending. Email: inquiries @chubbedwards.com EGC-HDVM series temporal-tone horn-strobes:non-coded,filtered Web: www chubbedwards.com Operating voltage 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded(audible NAC only) ©2013 UTC Fire&Security Americas when used with optional EG1 M Genesis Signal Master) Corporation,Inc.All rights reserved. Strobe output rating UL 1971,UL 1638,ULC S526 selectable 15/30/75/95 cd(EGC- Specifcations subject to change HDVM)and 95/115/150/177 cd(EGC-HDVMH) without notice.Edwards is part of UTC EGC-HDVM series temporal-tone horn-strobes:one flash per second Climate,Controls&Security,a unit of United Technologies Corporation. synchronized with optional EG1 M Genesis Signal Master indefinitely Strobe flash rate within 10 milliseconds(or self-synchronized within 200 milliseconds over thirty minutes on a common circuit without EG1 M Genesis Signal Master)Temporal setting(private mode only):synchronized to temporal output of horns on same circuit Synchronization Sources EG1 M-RM.EBPS6A,EBPS1 OA,E-NAC, E-FSC,E-FSA EGC-HDVM series temporal-tone horn-strobes:temporal rate synchronized with optional EG1 M Genesis Signal Master indefinitely Horn pulse rate within 10 milliseconds(or self-synchronized within 200 milliseconds over thirty minutes on a common circuit without EG1M Genesis Signal Master) Temporal audible pattern /'-sec ON,'/sec OFF, 1/2 sec ON, 'h sec OFF, '/2 sec ON, 11/2 sec OFF,then repeat cycle Ordering Information Catalog Housing Ship Number Color Marking Description Wt.lbs (kg) EGC-HDVM White None EGCF-HDVM White "FIRE" Genesis Ceiling/Wall Horn-Strobe EGCFR-HDVM Red "FIRE" with selectable 15,30, 75,or 95 cd output 0.82 EGC-HDVMH White None Genesis Ceiling/Wall Horn-Strobe (1.8) EGCF-HDVMH White "FIRE" with selectable 95.115, 150,or 177 cd output White Field Configurable Ceiling Horn-Strobes may be ordered with or without optional'FIRE'marking Red Horn-Strobes come with'FIRE"marking. Page 4 of 4 DATA S HE=T S85001-0559 u.-;d for ui.tallat:on pureosas. Issue 9.2 . • •• •• •• • • • • •• • • • • • • • • • • • •• • • • •• ••• ••• • •• • •• • •• ... • • •• • • i, �•. •,, .,I,,, "_..'.,r i>Stiobes Horns, Bells,Chimes cEdwards • • • • • • • • • • • • • • • •• SignaIin . . • ••.•• . . • • .• . • ••• • • • • • • • • • •• ••• • ••• • ••• ••• • • •• •• • • • • • • ••• ••• •• Field Configurrb1'e ' •.• __ _______ __„,, Ceilin g Horn ,-,,, -Strobes I Genesis Series - , `' FM IYA 0 Pending One or more patents pending Overview Standard Features Genesis ceiling horn-strobes are small,compact,and attractive • Field configurable-no need to remove the device! audible-visible emergency signaling devices. Protruding no more - 15/30/75/95 cd and 95/115/150/177 cd models available than 1.6"(41 mm), Genesis horn-strobes blend with any decor. - Switch settings remain visible even after the unit is installed Thanks to patented breakthrough technology, Edwards Gen - Low/high dB settings esis strobes do not require bulky specular reflectors and lenses. • Unique low-profile design Instead, an exclusive cavity design conditions light to produce - 30 per cent slimmer profile than comparable signals a highly controlled distribution pattern. Significant development - No visible mounting screws efforts employing this new technology have given rise to a new - Available with white or red housings benchmark in strobe performance-FullLight technology. • Easy to install FullLight strobe technology produces a smooth light distribution - Fits all standard 4"square electrical boxes with plenty of pattern without the spikes and voids characteristic of specular room behind the signal for extra wire-no extension ring or reflectors.This ensures the entire coverage area receives consis- trim plate needed tent illumination from the strobe flash.As a result, Genesis strobes - Pre-assembled with captive hardware-no loose pieces with FullLight technology go well beyond the minimum UL-required - #18 to#12 AWG terminals-ideal for long runs or existing wir- "cross"pattern. ing Depending on the model,Genesis horn-strobes feature 15 to 95, • Unparalleled performance or 95 to 177 candela output(see ordering information),which is - Exclusive FullLight strobe technology produces the industry's selectable with a conveniently-located switch on the front of the most even light distribution device.The candela output setting is clearly visible even after final - Single high-efficiency microprocessor controls installation,yet it remains locked in place to prevent unauthorized both horn and strobe movement after installation. - Low current draw minimizes system overhead - Independent horn control provided over a single Genesis horn-strobes feature textured housings in architecturally neu- pair of wires tral white or eye-catching fire alarm red.An ingenious iconographic - Highly regulated in-rush current allows the maximum symbol indicates the purpose of the device.This universal symbol number of strobes on a circuit is code-compliant and is easily recognized by all building occu- - 100 dB peak-multiple frequency tone improves pants regardless of what language they speak. Models with"FIRE" wall penetration markings are also available. Page 1 of 4 DATA SHEET S85001-0559 Not to be used for 'rstallarion purposos. Issue 9.2 • AZ AFAA NAC Voltage Drop Calculator for Audio/Visual devices This calculator provided voltage drop calculations in three formats(Point to Point, End of Line, and Load Centering). Make sure that you know what meth od is accepted by, and the results do not exceed the limits set by the respective jurisdiction - I 1 Point to Point Method End of Line Method Load Centering Method Project Name Triangle Point 2nd Floor Suite CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 9/15/20151 Circuit Number NAC#2-3 Totals [ Voltage- Totals - Voltage Totals Voltage Area Covered NW Management Suite C urrent Distance Drop Current Distance Drop - - Current Distance Drop- Nominal System Voltage_ 19.2 _ - 1.002 335 1.06 1.002 335 2.061 1.002 335 1.031 Minimum Device Voltage _ 16 _ End of Line Voltage 18.14 End of Line Voltage 17.14 End of Line Voltage 18.17 To tal Circuit Current T 1.0021 Wire Ohm's Percent Drop 5.52% Percent Drop 10.73% Percent Drop 5.37% 1 _-- I -1 Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st device 1 42 14 _ 3.07 _ Standard W ire Resistance in Ohm_s per 1000 feet. •1/i/ Gaugaf orbajance of circuit 1 14 3.07 I 18=7.771 16=4.891 14=3.071 12=1.98 10=1.24 1 • Enter current intimps. j ii ance 18-14 Awg= Solid Conductors 12-10 Awg= Stranded Conductors • .150=• • :.•Lr - - Voltage Notes: -1 l - _, - 1-- 1 - I - i - - ••••Dgvice- Device .preyipus - At 1 Drop from Percent Wire resistance is doubled in the calculations for two wires(Positive and Negative) _ - •'•TfUmber Current 11. ,yiGe Device I source Drop The voltage calculated to the last device in any method must not be lower then I 'Device 1 ':•11066 42 18.94 0.258 1.35% the manufactures listed minimum operating voltage(IE: rated operating voltage 20-32 VDC). I device 2 • •• 0.175' • 33 18.75 0.448 2.33% 1 1 - 1 1 - - I I - I - :deMioe 3 • -• :0.175 • •• 32 18.60 0.598 3.11% Device vice Manufacturer 'Edwards Device Manufacturer System Sensor• •Oevice •4 • •0.097'•••• 38 18.47 0.734 3.82% Current - [ Current •14e 5 _ • 0.097 0 • 40 18.35 0.854 4.45% Horn Strobe @Rated Strobe Only @Rated •Vevice 6 - • ; 0.066' • 32 18.27 0.931 4.85% Model# Candela Voltage _ _ Model# 'Candela Voltage •'MICe7 ••• 0.066` 22 18.22 0.975 5.08% EGC-HDVM 15 0.066 _ SR 15 0.066 •17EV1ee 8 • ...'0.097' 16 18.20 1.001 5.21% 30 0.097 11411Me 9 0.066 27 18.17 1.028 5.35% 75 0.175 Device 10 0.097 53 18.14 1.060 5.52% 95 0.195 END 18.14 1.060 5.52% 110 0.212 END 18.14 1.060 5.52% END _ 18.14 1.060 5.52% END 18.14 1.060 5.52% END 18.14 1.060 5.52% _ END 18.14 1.060 5.52% END 18.14 1.060 5.52% END _ 18.14 1.060 5.52% END 18.14 1.060 5.52% END 18.14 1.060 5.52% Totals 1.002 I 335 1 End of Line Voltage l 18.14 . • .. . .