Plans ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES
A AMPERE 1. THIS SYSTEM IS GRID-INTERTIED VIA A
AC ALTERNATING CURRENT UL-LISTED POWER-CONDITIONING INVERTER. RECEIVED
BLDG BUILDING 2. THIS SYSTEM HAS NO BATTERIES, NO UPS.
CONC CONCRETE 3. A NATIONALLY-RECOGNIZED TESTING SEP 2 2 2015
DC DIRECT CURRENT LABORATORY SHALL LIST ALL EQUIPMENT IN
EGC EQUIPMENT GROUNDING CONDUCTOR COMPLIANCE WITH ART. 110.3. CITY OF TIGARD
(E) EXISTING 4. WHERE ALL TERMINALS OF THE DISCONNECTING
EMT ELECTRICAL METALLIC TUBING MEANS MAY BE ENERGIZED IN THE OPEN POSITION, CITY OF TIGARD BUILDING DIVISION
FSB FIRE SET-BACK A SIGN WILL BE PROVIDED WARNING OF THE REVIEWED FOR CODE COMPLIANCE
GALV GALVANIZED HAZARDS PER ART. 690.17.
GEC GROUNDING ELECTRODE CONDUCTOR 5. EACH UNGROUNDED CONDUCTOR OF THE Approved, i 0'
CND GROUND MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY OTCs
HDG HOT DIPPED GALVANIZED PHASE AND SYSTEM PER ART. 210.5.
I CURRENT 6. CIRCUITS OVER 250V TO GROUND SHALL Permit#: 04/27-20 VS---4 ) I
Imp CURRENT AT MAX POWER COMPLY WITH ART. 250.97, 250.92(B). Address: ���? � (�L�
Isc SHORT CIRCUIT CURRENT 7. DC CONDUCTORS EITHER DO NOT ENTER
kVA KILOVOLT AMPERE BUILDING OR ARE RUN IN METALLIC RACEWAYS OR Suite #: r
kW KILOWATT ENCLOSURES TO THE FIRST ACCESSIBLE DC $fi, -4j7, 77---- Date: �l !
LBW LOAD BEARING WALL DISCONNECTING MEANS PER ART. 690.31(E). ,
MIN MINIMUM 8. ALL WIRES SHALL BE PROVIDED WITH STRAIN
(N) NEW RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY
NEUT NEUTRAL UL LISTING.
NTS NOT TO SCALE 9. MODULE FRAMES SHALL BE GROUNDED AT THE OFFICE COPY
OC ON CENTER UL-LISTED LOCATION PROVIDED BY THE
PL PROPERTY LINE MANUFACTURER USING UL LISTED GROUNDING
POI POINT OF INTERCONNECTION HARDWARE.
PV PHOTOVOLTAIC 10. MODULE FRAMES, RAIL, AND POSTS SHALL BE
SCH SCHEDULE BONDED WITH EQUIPMENT GROUND CONDUCTORS.
S STAINLESS STEEL
STC STANDARD TESTING CONDITIONS
TYP TYPICAL
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
Vmp VOLTAGE AT MAX POWER VICINITY MAP INDEX
Voc VOLTAGE AT OPEN CIRCUIT
W WATT ..
■
3R NEMA 3R, RAINTIGHT Y f;.
PVt COVER SHEET
PV3 STRUCTURAL PLAN
x P TRUCTURAL VIEWS
` at, PV4 UPLIFT CALCULATIONS
1 , L ;` PV5 THREE LINE DIAGRAM
LICENSE GENERAL NOTES E 4 =- PV6 ELECTRICAL CALCULATIONS
Cutsheets Attached
OR # 180498 1. ALL WORK TO BE DONE TO THE 2014 OSSC _ .
RGC, CGC1 AND 2012 IBC.
2. ALL ELECTRICAL WORK SHALL COMPLY WITH � F3Pf'CVC�lh
THE CURRENT NATIONAL ELECTRIC CODE AS
AMENDED BY THE OREGON ELECTRICAL SPECIALTY
CODE.
MODULE GROUNDING METHOD: ZEP SOLAR
)� REV BY DATE COMMENTS
AHJ: Tigard �� � iiet a e � � t CO REVA NAME DATE COMMENTS
City Park .— .;
. s •
ID.
UTILITY: Portland General Electric
M r Portlan •re on, State of Ore on. U.S. Geolo icaI Survey . .
J B-9723010 00 PREMISE OWNER: DESCRIPTION: DESIGN:
CONFIDENTIAL A THE I BE USED FOR THE JOB NUMBER: Brady ilchrist -.;; So�arCity
CONTAINED SHALL NOT BE USED FOR THE KOEPKE BRUCE B. KOEPKE RESIDENCE y
BENEFIT OF ANYONE EXCEPT SOLARCLE INC., MOUNTING SYSTEM: 12630 SW GLACIER LILY CIR 6.5 KW PV ARRAY
NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C
PART TO OTHERS OUTSIDE THE RECIPIENTS TIGARD, OR 97223 3055 Cleo,view Way
ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: San Mateo, CA 94402
SHEET: REV: DATE:
THE SALE AND USE T. THE UT THE (25) REC # REC26OPEZ PAGE NAME: T:(650)638-1028 F:(650)638-1029
PERMISSION EQUIPMENT, WITHOUT THE WRITTEN INVERTER:
PERMISSION OF SOLARCITY INC. SOLAREDGE #SE6000A US-ZB-U 5035247432 COVER SHEET PV 9/17/2015 (888)-sa clTr(765-2489) www.solarcity.com
PITCH: 24 ARRAY PITCH:24
MP1 AZIMUTH: 180 ARRAY AZIMUTH: 180
MATERIAL: Comp Shingle STORY: 2 Stories
PITCH: 24 ARRAY PITCH:24
MP2 AZIMUTH: 270 ARRAY AZIMUTH: 270
MATERIAL: Comp Shingle STORY: 2 Stories
PITCH: 24 ARRAY PITCH:24
_ MP3 AZIMUTH:90 ARRAY AZIMUTH:90
MATERIAL: Comp Shingle STORY: 2 Stories
-«\; 11
I nv ' I
\ / I 1
4 \, I 0
M »
( I I
L� Dl li
---- , I Ell z LEGEND
I
6 4 o O (E) UTILITY METER & WARNING LABEL
6hz
v = Q I�"-F _ ® INVERTER W/ INTEGRATED DC DISCO
ili N
& WARNING LABELS
` { 1_1[2,-CH DC DISCONNECT & WARNING LABELS
I AC
F...� AC DISCONNECT & WARNING LABELS
ED
I O DC JUNCTION/COMBINER BOX & LABELS
DISTRIBUTION PANEL & LABELS
_ _ FSB_ _ _ _
�° �� Lc LOAD CENTER & WARNING LABELS
_ O DEDICATED PV SYSTEM METER
STANDOFF LOCATIONS
--- CONDUIT RUN ON EXTERIOR
CONDUIT RUN ON INTERIOR
__ GATE/FENCE
0 HEAT PRODUCING VENTS ARE RED
r--1
1; ;I INTERIOR EQUIPMENT IS DASHED
L-J
SITE PLAN N
TOTAL ARRAY AREA (SF): 453 Scale: 1/8" = 1' W " E
TOTAL ROOF AREA (SF): 2339
TOTAL ARRAY AREA IS a 19.37 0 1' 8' 16'
PERCENT OF TOTAL ROOF AREA S
PREMISE OWNER: DESCRIPTION: DE
SIGN:CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: J8-9723010 00 ilchrist .:;;So�arCity.
CONTAINED SHALL NOT BE USED FOR THE KOEPKE BRUCE B. KOEPKE RESIDENCE Brady y
BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: 12630 SW GLACIER LILY CIR 6.5 KW PV ARRAY
NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C
PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD, OR 97223 3055 Clearview Way
ORGANIZATION, EXCEPT IN CONNECTION WITH S30 Mateo, CA 9Way
SHEET: REY DATE:
- THE SALE AND USE OF THE RESPECTIVE (25) REC # REC260PEZ PAGE NAME: T:(650)638-1028 F:(650)638-1029
SOLARCITY EQUIPMENT, 1WTHOUT THE WRITTEN INrERTER:
PERMISSION OF SOLARCITY INC. SOLAREDGE #SE6O00A-US-ZB-U 5035247432 SITE PLAN PV 2 9/17/2015 (ase) pn(765-2489) www.sdarcity.com
(E) 2x4 ® (E) 2x4 iii .‘.4" PRE-MANUFACTURED TRUSS RE-MANUFACTURED TRUSS
STRUCTURE MEETS THE STRUCTURE MEETS THE
PRESCRIPTIVE REQUIREMENTS PRESCRPTIVE REQUIREMENTS
0 OF THE OSISC SECTION 305.4 OF THE OSISC SECTION 305.4
5'-5" / 5'-4" / 1 It
5'-6" 5'-1"
2
1' (E) LBW 1'- �' (E) LBW
�
SIDE VIEW OF MP1 NTS SIDE VIEW OF MP2 NTS
A ®
MP1 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES MP2 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES
LANDSCAPE 72" 24" STAGGERED LANDSCAPE 72" 24" STAGGERED
PORTRAIT 48" 20" PORTRAIT 48" 20"
TOP CHORD 2x4 @ 24" OC ROOF AZI 180 PITCH 24 STORIES: 2 TOP CHORD 2X4 @ 24" OC ROOF
AZI 270 P TCH 24 STORIES: 2
ARRAY AZI 180 PITCH 24
BOT CHORD 2x4 @24" OC Comp Shingle BOT CHORD 2x4 @24" OC Comp Shingle
(E) 2x4 PV MODULE
/ 5/16" BOLT WITH LOCK INSTALLATION ORDER
el � PRE-MANUFACTURED TRUSS & FENDER WASHERS / LOCATE RAFTER, MARK HOLE
STRUCTURE MEETS THE ZEP LEVELING FOOT (1) LOCATION, AND DRILL PILOT
HOLE.
3\� OF THE OSISC REQUIREMENTS
ECCTIONM305.4 ZEP ARRAY SKIRT (6) 2) SEAL PILOT HOLE WITH
4„ 01. I (4) POLYURETHANE SEALANT.
I! ZEP COMP MOUNT C 1 WA� � �I;f _
6'-9" / 5 -2' / ►�--
ZEP FLASHING C `jam �4■��� (3) INSERT FLASHING.
1'—i� (E) LBW ZEP
...■•■ .::_-
(E) COMP. SHINGLE (4) PLACE MOUNT.
. SIDE VIEW OF MP3 NTS
C (E) ROOF DECKING VANE (5) INSTALL LAG BOLT WITH
5/16" DIA STAINLESS (5) SEALING WASHER.
MP3 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES STEEL LAG BOLT LOWEST MODULE SUBSEQUENT MODULES INSTALL LEVELING FOOT WITH
LANDSCAPE 72" 24" STAGGERED WITH SEALING WASHER ( BOLT & WASHERS.
(2-1/2" EMBED, MIN)
PORTRAIT 48" 20
ROOF AZI 90 PITCH 24 STORIES: 2 (E) RAFTER STAN DOFF
TOP CHORD 2x4 @ 24" OC ARRAY AZI 90 PITCH 24 1
BOT CHORD 2x4 @24" OC Comp Shingle Si Scale: 1 1/2" = 1'
PREMISE OWNER: DESCRIPTION: DESIGN:
CONFIDENTIAL -A THE INFORMATION HEREIN JOB NUMBER: Jg-9723010 00 KOEPKE, BRUCE B. KOEPKE RESIDENCE Brady Gilchrist -�,,,SoIarCity CONTAINED SHALL NOT BE USED FOR THE '
BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: 12630 SW GLACIER LILY CIR 6.5 KW PV ARRAY
NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C
PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES TIGARD, OR 97223 3055 Cleorview Way San Mateo, CA 94402
ORGANIZATION,
AND USE EOF THE CONNECTION SPECTIVE�TM (25) REC # REC260PEZ PAGE NAME: SFIEET. REV DATE: T:(650)638 1028 F:(650) 638-1029
SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN W R,ER: 5035247432 STRUCTURAL VIEWS
PERMISSION OF soLARCITY INC. SOLAREDGE #SE6000A-US-ZB-U PV 9/17/2015 (Bea)-soL-aTY(765-2489) wwwsdarclty.com
UPLIFT CALCULATIONS
09.17.2015
S I rC�ty PV System Structural Version#49.2
Desian Software
Project Information&Table Of Contents _
Risk Category: II
PV System Type SoiarCity SleekMount'"
Comp Roof Comp Roof
Layers of Comp Roofng 2
Roof Slope 24°
Rafter Spacing 24"O.C.
PV System Module Orientation Landscape and Portrait
PV Module Area 1111111k ARM 444 sf 4M1110.
PV Module Width 39"
PV Module Length IMIltir = 66"`
Standoff(Attachment Hardware) Comp Mount Type C
Reduced Ground/Roof Live/Snow Loads
Ground Snow Load pg 25.0 psf ASCE Table 7-1
Surrounding Roof Snow 100% 25.0 psf 'ASCE Eq:7.4-1
Root Snow Over PV Modules 100% 25.0 psf 'ASCE Eq: 7.4-1
Wind Design Criteria TM
Wind Design Code ASCE 7-05
Wind Design Method Partially/Fully Enclosed Method.l
Basic Wind Speed V 95 mph Fig.6-1
Exposure Category 11.1.11B E C ' Section 6.5.6.3
Roof Style Gable Roof 'Fig.6-11B/u0-14A/B
Mean Roof Height h -IIIIIIIIIIIIIt 25 ft Section 6.2
Effective Wind Area(I Module) A 17.8 sf IBC 1509.7.1
Wind Pressure Calculation Coefficients ,,
Wind Pressure Exposure IQ 0.95 Table 6-3
Topographic Factor Kzt ��� 1.00 Section 6.5.7
Wind Directionality Factor Kd 0.85 Table 6-4
Importance Factor I 1.0 Table 6-1
Velocity Pressure qh qh 0.00256(1(z)(Kzt)(Kd)(V^2)(I) Equation 6-15
18.6 psf
Ext.Pressure Coefficient(Up) GCp(Up) -0.88 Fig.6-11B/C/D-14A/B
Ext.Pressure Coefficient(Down) GCp(Down) 0.45 Fia.6-118/C/D-14A/B
Design Wind Pressure p p= qh(GCp) Equation 6-22
Wind Pressure Up p(up) -16.2 psf
Wind Pressure Down p(down) 10.0 psf
Allowable Standoff Spacings
' X-Direction Y-Direction
Max Allowable Standoff Spacing Landscape 72" 39
Max Allowable Cantilever Landscape 24" NA
Standoff Configuration Landscape Staggered
Max Standoff Tributary Area Trib 20 sf
PV Assembly Dead Load W PV 3 psf
Net Wind Uplift at Standoff T-actual -285 1bs
- Uplift Capacity of Standoff T-allow 500 Ihs
Standoff Demand/Capacity DCR 57.0%
Max Allowable Standoff Spacing Portrait 48" 66
Max Allowable Cantilever Portrait 20" NA
• Standoff Configuration Portrait Staggered
Max Standoff Tributary Area Trib 22 sf Alit
PV Assembly Dead Load W-PV 3 psf
Net Wind Uplift at Standoff T-actual -319 lbs p- '
I)plift Capacity of Standoff Tallow 500 lbs
Standoff Demand/Capacity DCR 63.8% 4E6. MIME
PREMISE OWNER: DESCRIPTION: DESIGN:
• CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: Mg-8723010 0 0 Brady ilchrist .:;;So1arCity
CONTAINED SHALL NOT BE USED FOR THE KOEPKE, BRUCE B. KOEPKE RESIDENCE y
BENEFIT OF ANYONE EXCEPT IN WHOLE INC., MOUNTING SYSTEM: 1 2630 SW GLACIER LILY CIR 6.5 KW PV ARRAY
NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C
PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIC A R D, OR 97223
3055 Cleo-view Way
ORGANIZATION, EXCEPT IN CONNECTION WITH SHEET: REY. DALE: S3O Mateo, CA 94402
THE SALE AND USE EQUIPMENT, WIT RESPECTIVE (25) REC # REC260PEZ PAGE NAME: T:(65D)S38-tO28 FA 94402 238-1029
PE MISSIONEOFISOELARCITY INC.OT THE WRITTEN INVERTER: 5035247432 UPLIFT CALCULATIONS PV 4 9/17/2015 (848)-SOL—CITY(765-2489)wwwsolarcity.com
SOLAREDGE #SE6000A-US-ZB-U
GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE
Inv 1: DC Ungrounded —(25)REC i REC260PEZ OR # 180498
• BOND (N) #8 GEC TO (E) GROUND ROD Panel Number:NoMatch g INV 1 —(1))SOLAREDGE ##SE6000A—US—ZB—U LABEL: A M RGC, CGC1
AT PANEL WITH IRREVERSIBLE CRIMP Meter Number:24 540 125 Inverter; 6000W, 240V, 97.5%; w/Unifed Disco and ZB, AFCI PV Module; 260W, 236.6W PTC, MC4, 40mm, Black Frame, ZEP Enabled
Underground Service Entrance INV 2 Voc: 37.8 Vpmax: 30.7
INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDEN11FIER
(E 200A MAIN SERVICE PANEL
E5 200A/2P MAIN CIRCUIT BREAKER Inverter 1
(E) WRING COOPER WDC'. 200A/2P Meter Socket O SE6000AREDGZB- U DCI M1,MP2: 1x13
l
_ EGC J
(E) LOADS A _ I 240V I I— C
L1
• { •• L2_tr •� DC. I
I I N � DG I l�) II aT�lD m 35A/2P --�_, GND�_— -V GEC TN ✓—DG Yc1 MP2,MP3: 1x12III
C7 �� _ G: J
• ——— —
m m • • B ®--- EGC ———eTF—— '
V
I
(1)Conduit Kit; 3/4- EMT
N
—
J EGCIGEC J
o-
z—z
CD
— T GEC ,,
TO 120/240V
SINGLE PHASE
UTILITY SERVICE I
Voc* = MAX VOC AT MIN TEMP
POI-(1)CUTLER—HAMMER I BR235 PV BACKFEED BREAKER A -(1)COOPER #B—Line Meter Socket 011 ^C PV —(25)SOLAREDGE 300—e2NA4AZS DC
Breaker, 35A 2P, 2 Spaces Meter Socket; 125A, 4-14AWG, Ring Type /—� PowerBox ptimizer, 300W, H4, DC to DC. ZEP
—(1)AW CAP; B—Line Meter Socket Accessory
—(1)Milbank !CL200D /Itron CIS
Solid—State Single—Phase Meter; Digital
•
(2)AWG/10, PV Wire, 600V, Block Voc* =500 VDC Isc =15 ADC
I (1)AWG #8, TNWN-2, Block 1
OPI—( AWG #8, THWN-2, Red 1 �(1)AWG f6, Stranded Bore Copper EGC Vmp =350 VDC Imp=9.53 ADC
II (1)AWG #10, THWN-2, White NEUTRAL Vmp =240 VAC Imp=25 MC 1/���1(1)Conduit Kit;.3/4' EMT
—(1)AWG #8, THWN-2, Green EGC/GEC-(1)Conduit Kit; 3/4' EMT (2)AWG 110, PV Wire, 600V, Black Voc* =500 VDC Isc =15 ADC
O (1)AWG/6, Stranded Bare Copper EGC Vmp =350 VDC Imp=8.8 ADC
(1)Conduit Kit; 3/4' EMT
' PREMISE OWNER: DESCRIPTION: DESIGN:
• CONTANEDIAL A THE T BE US D THN JOB NUMBER: J g-972301 O OO ilchrist .:;;So�arCity.
CONTAINED SHALL NOT BE USED FOR THE KOEPKE, BRUCE B. KOEPKE RESIDENCE Brady y
BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: 1 2630 SW GLACIER LILY CIR 6.5 KW PV ARRAY
NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C
PART TO OTHERS OUTSIDE THE RECIPIENTS MOODIEST TIGARD, OR 97223 3055 Cleannew Nby
SOLARCITY ORGANIZATION, EXCEPT IN CONNECTION WITH SHEET; REV DATE: San Mateo, CA 94402
THE SALE AND USE OF THE RESPECTIVE (25) REC # REC260PEZ PAGE NAME: T:(650)638-1028 F:(650)638-1029
PERMISSION EOFISOLARCITY INC.T THE WRITTEN INVERTER: 5035247432 THREE LINE DIAGRAM PV 5 9/17/2015 (888)—Sa—CITY(765-2489)www.salarcity.com
SOLAREDGE #SE6000A-US-ZB-U
ELECTRICAL CALCULATIONS Module: 25 REC 260PEZ 234.3 Inv Power WPTC Voltage Drop Calculations Version 5.8.0
Inverter 1: 1 SolarEdge 6000 AFCI 0.98 6000 5711.06 Vdrop= Imp) . (2`Length)*(Resistance) / Vmp)
Module: REC 260PEZ 234.3 I Imp(A) Max. Length(ft) Wire
Inverter 2: String: 9.53 50 AWG#10 at Max Ave Hi:87 deg F
Module: REC 260PEZ 234.3 Vdrop= (9.53 100 0.00124 Ohms) / 350 0.35
Branch: 25 I 15 AWG#8 at Max Ave Hi:87 deg F
Inverter 3: Vdrop= (25 30 0.00078 Ohms) / 240 0.09
Module: REC 260PEZ 234.3 Total voltage drop in DC conductors=
Inverter 4: Inverter: I I at 240V
Vdrop= Ohms) / 240 V
Total: 25 Modules Total Inv Pwr: 6000 5711.06 PTC Combined I I I at 240V
Photovoltaic Module Electrical Specifications: Total STC: 6500 Vdrop= Ohms) / 240 V
Voc: 37.8 V deg F deg C
Vmp: 30.7 V Record Low Temp: 8 -13 Total voltage drop in AC conductors=
Isc: 9.01 A Max Average Hi Temp: 87 31 Total voltage drop in AC and DC conductors=
Imp: 8.5 A Record Hi Temp:
Tvoc: -0.1 V/deg C
Tisc: 2.16 mA/deg C
String Type A and 2 Combined Strings Type A Voc Correction Method: Manuf TVoc Data Branch Circuit Type A 1 way wire length: N/A
SolarEdge 6000 AFCI Voc Correction Factor: 1 I strings per branch 1 strings per branch 2
13 REC 260PEZ Inverter Min Vdc Input: 350 13 modules per series string modules per series string
Min Vmp at Max Temp: 333.65 Voc= 500 V Voc= V
Voc= 500 Max Voc at Min Temp: 500 Vmp= 350 V Vmp= V
Vmp= 350 Inverter Max Vdc Input: 500
Isc= 15 Isc= 15 A Isc= A
Max String Size: 20 Imp= 9.53 A Imp= A
Imp= 9.53 1-way wire length: 50
Icont= 15 Art 690.8(A)(1) Icont= 15 A Icont= A Art 690.8(A)(1)
1.a Conductor AWG #10 PV Wire 2.a Conductor 1: N/A
Conductor 2:
Icont'1.25=(Amps) 15 Conductor 1 Conductor 2
30 deg C ampacity= 40 Icont' 1.25=(Amps) 18.75
1.b Icont=(Amps) 15 I 30 deg C ampacity= N/A
Start ampacity 40 2.b Icont=(Amps) 15
Temperature derate(%=F) 0.76 Start ampacity N/A
Conduit fill derate(%=#) 1 Temperature derate(%=F) N/A
I
Derated ampacity 30.4 Conduit fill derate(%=#) N/A
1 c Derated ampacity N/A I
Icont* 1.25=(Amps) 15 2.c Term 1 Term 2
Ampacity 40 Temp table N/A
1 Icont*1.25=(Amps) 18.75
1.d Icont* 1.25=(Amps) 15 Ampacity N/A
-OCP Size= 15
Inverter Type A Output 2_d OCP Size= I 20
SolarEdge 6000 AFCI I 1 way wire length: 15 ft Combined Inverter Output
Icont= I 25 I A Art 690.8(A)(1) Service Voltage=
3.a Icont* 1.25=(Amps) 31.25 Art 690.8(B)(1) Total Inverter Power= 1 way wire length= 15
OCP Size= 35 Art 240.6(A) Icont=#of inverters*max inverter current Art 690.8(A)(1)
Icont=(Amps)
3.b Conductorl AWG #8 THWN-2 at 90 deg C:Table 310.16 4.a Icont'1.25=(Amps) 31.25 Art 690.8(B)(1)
Icont* 1.25=(Amps) _31.25 35 Art 240.6(A)
I OCP size=
30 deg C ampacity= 55 4.b Conductor: I AWG #8 THWN-2 at 90 deg C:Table 310.16
3.c Icont=(Amps) 25
Icont* 1.25=(Amps) 31.25
Start ampacity S5 30 deg C ampacity= 55
Temperature derate(%=F) 0.91 4 c Icont=(Amps) 25
Conduit fill derate(%_#) 1 55
Start ampacity
Derated ampacity 50.05 I Temperature derate(%=F) 0.91
3.d Icont* 1.25=(Amps) 31.25 Conduit fill derate(%_#) 1
Ampacity 50 Derated ampacity 50.05 I
4.d Icont* 1.25=(Amps) 31.25
Ampacity 50
PREMISE OWNER: DESCRIPTION: DESIGN:
CONFIDENTIAL - THE INFORMATION BE USED HEREIN NUMBER: 8_9723010 00 Brady ilchrist '��;:SOla�CU
CONTAINED SHALL NOT BE USED FOR THE KOEPKE BRUCE B. KOEPKE RESIDENCE y J y
BENEFIT OF ANYONE EXCEPT SOLARCITY INC., IAOUN11NC SYSTEM: 12630 SW GLACIER LILY CIR 6.5 KW PV ARRAY
NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C
PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES:
TI G A R D, OR 97223
3055 Clearview Way
ORGANIZATION, EXCEPT IN CONNECTION VAIN San Mateo, CA 94402
SHEET: REV DATE:
THE SALE AND USE OF THE RESPECTIVE (25) REC # REC260PEZ PAGE NAME: T:(650) 638-1028 F:(650)638-1029
PERMISSION E EOFISOLARCITY I C. THE WRITTEN INWR1ER 5035247432 ELECTRICAL CALCULATIONS PV 6 9/17/2015 (888)-SOL-C1TY(765-2489) www.sdorcity.com
SOLAREDGE #SE6000A-US-ZB-U
Label Location: Label Location: Label Location:
CAUTION: SOLAR CIRCUIT (C)(IC)(CB) MAXIMUM AC A (AC)(P01) WARNING (PO1)
Per Code: OPERATING CURRENT Per Code: Per Code:
IFC 605.11.1.4 MAXIMUM AC - V NEC 690.54 INVERTER OUTPUT NEC 690.64.B.7
OPERATING VOLTAGE CONNECTION
DO NOT RELOCATE
Label Location: THIS OVERCURRENT
PHOTOVOLTAIC DC (DC)(INV) DEVICE
DISCONNECT Per Code:
• NEC 690.14.C.2 Label Location:
WARNING (AC) (POI)
Per Code: Label Location:
ELECTRIC SHOCK HAZARD NEC 690.17(4) WARNING (DC)(INV)
Label Location: DO NOT TOUCH TERMINALS Per Code:
TERMINALS ON BOTH LINE AND ELECTRIC SHOCK HAZARD
MAXIMUM POWER- A (DC)(INV) LOAD SIDES MAY BE ENERGIZED NEC 690.35(F)
POINT CURRENT(Imp) Per Code: IN THE OPEN POSITION THE DC CONDUCTORS OF THIS
MAXIMUM POWER- PHOTOVOLTAIC SYSTEM ARE TO BE USED WHEN
POINT VOLTAGE(Vmp) V NEC 690.53 UNGROUNDED AND INVERTER IS
MAXIMUM SYSTEM MAY BE ENERGIZED UNGROUNDED
VOLTAGE(Voc) v
SHORT-CIRCUIT Label Location:ab
CURRENT(Isc) A L_ Lab
PV SYSTEM
DISCONNECT FOR
UTILITY OPERATION
Label Location:
WARNING (DC)(CB)
ELECTRICAL SHOCK HAZARD Per Code:
DO NOT TOUCH TERMINALS NEC 690.17(4) Label Location:
TERMINALS ON BOTH LINE AND PHOTOVOLTAIC POINT OF (P01)
LOAD SIDES MAY BE ENERGIZED INTERCONNECTION Per Code:
IN THE OPEN POSITION WARNING: ELECTRIC SHOCK NEC 690.17.4; NEC 690.54
DC VOLTAGE IS HAZARD. DO NOT TOUCH
ALWAYS PRESENT WHEN TERMINALS.TERMINALS ON
SOLAR MODULES ARE BOTH THE LINE AND LOAD SIDE
EXPOSED TO SUNLIGHT MAY BE ENERGIZED IN THE OPEN
POSITION. FOR SERVICE
DE-ENERGIZE BOTH SOURCE
AND MAIN BREAKER.
PV POWER SOURCE
Label Location: MAXIMUM AC _ A
OPERATING CURRENT
WARNING (DC)(INV) MAXIMUM AC -
Per Code: OPERATING VOLTAGE V
ELECTRIC SHOCK HAZARD NEC 690.5(C)
IF A GROUND FAULT IS INDICATED
NORMALLY GROUNDED
CONDUCTORS MAY BE
UNGROUNDED AND ENERGIZED
Label Location:
CAUTION (P01)
• DUAL POWER SOURCE Per Code:
SECOND SOURCE IS NEC 690.64.B.4
Label Location: PHOTOVOLTAIC SYSTEM (AC):AC Disconnect
PHOTOVOLTAIC AC (AC)(P01) (C): Conduit
DISCONNECT Per Code: (CB): Combiner Box
NEC 690.14.C.2 (D): Distribution Panel
Label Location: (DC): DC Disconnect
CAUTION (D) (P01) (IC): Interior Run Conduit
PHOTOVOLTAIC SYSTEM Per Code: (INV): Inverter With Integrated DC Disconnect
CIRCUIT IS BACKFED NEC 690.64.B.4 (LC): Load Center
(M): Utility Meter
(P01): Point of Interconnection
CONFIDENTIAL- THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR 'vkif� 3055 Clearview Way
THE BENEFIT OF ANYONE EXCEPT SMARMY INC., NOR SHALL IT BE DISCLOSED +- ■ San Mateo,CA 94402
IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, Label Set �'% T:650)638-1028 F:(650)638-1029
EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE fI� So1ar( ��� (888)-SOL-CITY(765-2489)www.wlarcity.com
SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. o
a ZS Comp Edge Zone Calculations 1 of 4 ZS Comp Edge Zone Calculations 2 of 4
3/26/15 3/26/15
ZepSolar ZepSotar
This set of calculations is intended to show that ZS Comp has sufficient strength to allow for attachment Down Force Spacing
spacings of at least 48"in Edge Zones whether the modules are orientated in landscape or portrait.The Allowable Down Force Load
down force spacing= module width x design load
calculations will vary the design variables to account for the worst case for each failure mode that is being
checked.
Wind Down Calculations
All variable the same as above except for roof pitch
General Design Information: Roof Pitch
Module Size: 39"x 65" Basic Wind Speed= 120 mph 14 30 45
System Weight= 3 psf Ground Snow Load= 30 psf GCN landscape= 0.5 0.9 0.9
GCN portrait= 0.4 0.9 0.9
Comp Mount Allowable Loads design load 15.35 27.64 27.64 psf
g landscape= p
Load Duration Wind Snow 4,- = AFY design load�nrait= 12.28 27.64 27.64 psf
Uplift= 656 lbs N/A x.'.,.+O∎t..��
note:use 10 psf minimum
Lateral= 357 lbs 290 lbs tha 85818
Down Force= 1074 lbs 771 lbs Calculations
m OREGON c
1/4r To account for unbalanced snow loads,ground snow loads will be used for roof pitches 30 degrees and ower.
'4'. v,,, Per section 7.6.1 of ASCE 7-10 unbalanced snow loads do not need to be considered for slopes above 30
Attachment Spacing Calculations degrees.
Uplift Spacing EXPIRES: 12/31/16
Allowable Uplift Load FOR PAGES 1-4 Ground Snow Load= 30 psf
uplift spacing= module length or width x design load
Roof Pitch
14 30
Wind Uplift Calculations Design Snow Load 29.11 25.98 psf
2014 OSSC and ASCE 7-10 Method 2
(snow load spread over the length of the rafter)
P=ghGCN
qh=0.00256 KZ K„Kd V2 I Down Force Load Roof Pitch
Basic Wind Speed= 120 mph Combinations: 14 30
Exposure= C Roof Zone= Edge Zone D+S= 31.16 25.10 psf
Importance Factor= 1.0 KZ= 0.98 from Table 6-3 D+0.6*W= 12.91 19.18 psf
Gable/Hip Roof K,t= 1.0 per 6.5.7.2 D+0.75*0.6*W+0.755 31.59 31.91 psf
Uorst Case Roof Pitch= 14 degrees Kd= 0.85 from Table 6-4
GCN P
Roof Height= 30
GC landscape= -1.6 Allowable Spacing for Down Force
iscape effective area= 13.0 ft2 GCN portrait=-1.5 7711bs in
,ortrait effective area= 21.7 ft2 landscape down force spacing= 39"x 31.91psf x 144-ft2 =89"
Plandscape= -49.13 psf
• qh= 30.71 psf Pportrait= -46.06 psf portrait down force spacing = 65"x 31191psf x 144-ft2
= 53"
• Uplift Load Combination:0.6D+0.6W(ASCE Section 2.4.1 equation 7)
design load landscape= -27.73 psf
design load portrait -25.89 psf
656 lbs in
landscape uplift spacing =
39"x 27.73 psf x 144 ftZ =87"
656 lbs
portrait uplift spacing = 65"x 25.89 psf x 144-= 56"
3 of 4 ZS Comp Edge Zone Calculations 4 of 4
0 25 Comp Edge Zone Calculations 3/26/15
Ze Solar 3/26/15 ZepSolar
P
Lateral Spacing Module Deflection Spacing
landscape module spacing= -1.4545 x Maximum Uplift or Down Force Pressure+120.7273
The lateral force on the system increases as the pitch of the roof increases,but the amount of snow on the
roof decreases for slopes greater than 30 degrees.With this in mind,the lateral force will be checked at 30
degrees with ground snow load and 45 degrees with sloped roof snow. portrait module spacing=-0.8182 x Maximum Uplift or Down Force Pressure+79.909
Allowable Lateral Load Maximum Uplift Pressure Landscape= -27.73
lateral spacing = module width x design load Maximum Uplift Pressure Portrait= -25.89
Maximum Down Force Pressure= 31.91 psf
Snow Calculations
Ground Snow Load= 30 psf
PS=C5 Pf Roof Pitch= 31 45 degrees landscape module spacing =-1.4545 x 31.91 psf+ 120.7273=74"
pf=0.7CeC.1Ipg Ce= 0.9 C5= 0.71 0.45
Cc= 1.2 pf= 22.68 22.7 psf portrait module spacing=-0.8182 x 31.91 psf+79.909= 54"
I= 1.0 IN= 16.1 10.2 psf
Calculation Summary
Roof Pitch Calculated Edge Zone Spacing
Spacing Check Landscape Portrait
27 30 31 45 ,
Design Snow Load 26.73 25.98 13.80 7.22 psf Uplift 87" 56"
(snow load spread over the length of the rafter) Down Force 89" 53"
30° 27° 30°
Lateral 74" 48" 44"
Lateral Force Component
Down Force Load Roof Pitch Module Deflection 74" 54"
Combinations: 27 30 31 45
D+S= 13.50 14.49 8.65 7.22 psf As can be seen in the table above,for Design Wind Speeds up to 120 mph and Ground Snow Loads up to 30
D+0.75.0.6W+0.755 10.46 11.24 6.88 5.95 psf psf with modules orientated in landscape,the system is strong enough to be installed at 72"on center in the
Edge Zone.When modules are installed in portrait,the spacing for edge zone installations can be 48"on
center for most roof pitches.For roof pitches that are greater than 27 but less than 31°,the maximum
Allowable Spacing for Lateral Force
attachment spacing is 44".
30 degree roof pitch
2901bs in
landscape lateral spacing= 39"x 14.49 psf x 144 f=74"
tz
290ibs in
portrait lateral spacing = 65"x 14.49 psf x 144 f=44"
tz
Portrait spacing is less than 48".Try roof pitch of 27 degrees
. 2901bs in
portrait lateral spacing= 65"x 13.50 psf x 144 ftz =48"
0 ,.....,. 0 Next Level PV Mounting Technology
`'�SOIarCity Zep Solar Next-Level PV Mounting Technology ^SOiarCity Zep Solar
IP Zep System Components
for composition shingle roofs
lir
,.. sat Up-roof `
-s
.4 $
Interlock _erre<rro.rn,
Ground Z<p
--�.e.lew tea Jl
t
., Zep Cow PvModule �"
.�
T
Zep Gruaw.ei - ,•-
\ __._. Roof Anachment
Array Skrt °`""'—
i
oMPq T�
ti` e�F Description % ui� J� . '�'
,, • • PV mounting solution for composition shingle roofs �` � ����
�Aeonvnt\e Works with all Zep Compatible Modules
• Auto bonding UL-listed hardware creates structual and electrical bond
• Zep System has a UL 1703 Class"A"Fire Rating when installed using Comp Mount Interlock Leveling Foot
()LISTED modules from any manufacturer certified as"Type 1"or'Type 2" Part No.850-1397
Part No.850-1382 Part No.850-1388
Listed to UL 2582& Listed to UL 2703 Listed to UL 2703
Mounting Block to UL 2703
(01) Specifications
▪ Designed for pitched roofs
• Installs in portrait and landscape orientations t� bik, at---1
• Zep System supports module wind uplift and snow load pressures to 50 psf per UL 1703
• Wind tunnel report to ASCE 7-05 and 7-10 standards `�\ ! a
• • Zep System grounding products are UL listed to UL 2703 and ETL listed to UL 467 �7 toy,
• Zep System bonding products are UL listed to UL 2703 44ala‘l
- • Engineered for spans up to 72"and cantilevers up to 24" DC Wire Cli
• Zep wire management products listed to UL 1565 for wire positioning devices Ground Zep Array Skirt,Grip,End Caps Clip
• Attachment method UL listed to UL 2582 for Wind Driven Rain Part No.850-1172 Part Nos.500-0113, Part No.850-1448
Listed to UL 2703 and 850-1421,850-1460. Listed UL 1565
ETL listed to UL 467 850-1467
Listed to UL 2703
zepsolar.com
zepsolar.com
This document does not create any express warranty by Zep Solar or about its products or services.Zep Solar's sole warranty is contained in the written product warranty for This document does not create any express warranty by Zep Solar or about its products or services.Zep Solar's sole warranty is contained in the written product warranty for
5 Y M each product The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty.The customer is solely
each probed.The end-user documentation Solar's with products Solar's products S constitutes ccant the sole specifications to change without to in .the tents and warranty.The customer is solely responsible for verifying the suitability of Zep Solar's products for each use.Specifications are subject to change without notice.Patents and Apps zspats.com.
responsible for venfying the suitability of Zep Solar's products for each use.Specifications are subject to change without notice.Patents and Apps zspats.com. P rdY 9 Y P P P 1 g
02 27 15 ZS for Comp Shingle Cutsheet Rev 04.pdt Page: 1 of 2 02 27 15 ZS for Comp Shingle Cutsheet Rev 04.01 Page: 2 of 2
cc
SolarEdge Power Optimizer
solar ` NI solar Module Add-On for North America
— P300 / P350 / P400
SolarEdge Power Optimizer
P300 P350 P400
Module Add-On For North America I— (for 60-cell PV (for 72-cell PV (for 96-cell PV
modules) modules) modules)
P300 / P350 / P400 0- tour
Rated Input DC Power' ..-r. 300 iSO 400 W
Absolute Maximum Input Voltage(Vtx at lowest temperature) 48 60 80 Vdc
»• ^.. - O MPPT Operating Range S 48 I 8 60 I 8-80 Vdc
Maximum Short Circuit Current(Isc) SO Adc
Maximum DC Input Current 12.5 Mc,e., Maximum Efficiency 99.5 %
,..,,, »y w Weighted Efficiency __. _. _ 98.8... %
*,. Overvoltage Category - n
.y».,.. „i.„ ,, ,. '.. OUTPUT DURING OPERATION(POWER OPTIMIZER CONNECTED TO OPERATING INVERTER)
Maximum Output Current IS Al r
GU Vdc
^ OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM INVERTER OR INVERTER OFF)
L.L Safety Output Voltage per Power Optimizer.. _._ 1 Vdc
„, STANDARD COMPLIANCE
,3 ±_
EMC FCC Part15 Class B,IEC61000-6-2,IEC61000 6 3
2 Safety IEC62109-1(class II Safety),IA 1 741
,.- RoHS _Yes
INSTALLATION SPECIFICATIONS
Maximum Allowed System Voltage 1000 Vdc
Dimensions(W x Lx H) 141 x 212 x40.5/5.55 x 8.34 x 1.59 mm/in
Weight(including awes) 950/2.1 gr/lb
Input Connector . . MC4/Amphenol/Tyco
Output Wire Type/Connector Double Insulated;Amphenol
Output Wire Length 0.95/3.0 I 1.2/3.9 m/ft
,
Operating Temperature Range
-40-45/-40-+185 .C/
F
w = Protecton Rating IP65/NEMA4
Relative Humidity 0.100 %
ei eaa stc w..a mmre.uere a w m.sn rm.-ww....w..e
PV SYSTEM DESIGN USING A SOLAREDGE THREE PHASE THREE PHASE
INVERTER SINGLE PHASE 2O8V 480V
PV power optimization at the module-level Minimum Strang Length(Power Op misers) 8 i 10 18
Maximum String Length(Power Optimizers) 25 25
— Up to 25%more energy Maximum Power per String 5250 6000 I 50
12754 W
— Superior efficiency(99.5%) Parallel Strings of OiAerent Lengths or OrientaltaM Yes
- Mitigates all types of module mismatch losses,from manufacturing tolerance to partial shading
r — Flexible system design for maximum space utilization
— Fast installation with a single bolt
— Next generation maintenance with module-level monitoring
- Module-level voltage shutdown for installer and firefighter safety
USA - GERMANY - ITALY - FRANCE - JAPAN - CHINA - ISRAEL - AUSTRALIA wwW.solaredge.us
1
•
. & ■11,IPPIkA/\A ENERGIZING LIFE TOGETHER RCC REC PEAK ENERGY Z LINK SERIES
• 65.55 t0.1 q Q / '
15 8% EEFFUIENLY
HIGH PERFORMANCE �� YEAR PRODUCT WARRANTY
SOLAR PANELS '
YEAR WEAR POWER
rar 1:
OUTPUT WARRANTY "'
R CCPEAK •
— OAT V'Fh' US IMPORT DUTY FREE
E RGY , �, , , •
1 TEMPERATURE RATINGS
a, Nominal Operating Cell Temperature(NOCT) 45.7°C(i2°C)
R TemperatureCoeffitiffientofP 040%/°C
�� Temperature Coecient ofVor -0.27%/°C c
Temperature Coefficient of I„ 0.024%/°C 1
REC Peak Energy Z-Link Series solar All measurements In ruche, t :.
1 IIIIV' IP•pi,j•,,,,,,,,panels are the perfect choice for building REC260PEZ GENERAL DATA
solar systems that combine long lasting N>rnirelPower-P (Wp) C' Ce'.I Type 60 REC PE multi-crystalline
rev,Watt Class nalPo Sorting-(Wp) ,/_5 a 3swingso120c ells with bypass diodes product quality with tellable power output. 30.7 1 Glass: 0.125 in solar glass with anti-reflection !h
Nominal Power Voltage-Vt,W(V) €: surface treatment
REC combines high lord quality design and Nominal Power Current-I,Pe(A) 8.50 `
, Back Sheet: Douhlelayerhighlyresifacetreatmtnt
manufacturing t0 produce high- Open Circuit Voltage-Va(V) 378 1 Frame: Anodized aluminum(black)
performance solar panels with Short Circuit Current-1 (A) 901 2epGroovetompatible
158 Junction 8ox: 1P67 rated
uncompromising gUd11ty. Panel Efficiency(%) 1:. 0156in(12AWG)solercahle,2x47241n
The electrical characteristicsare within•/-10%of the indicated values ofIyc�Va and P.,at standard Test conditions(SIC) I,. Conne[tors H4Amphenol
Q GOM PA TSB Values at standard test conditions STC(amass AM 1.5,irradiance 1000 W/m',cell temperature 77°F(25°C)). *ill iii
At low irradiance of 200W/m'(AM 1.5 A cell temperature 77*F(25C)( tleast 97%of the STC panel efficiency will be achieved. Origin: Made in Singapore
�: REQ60PEZ MAJfIMUM RATINGS
~ .7„.// ELECTRICAL DATAnNOf.'
•1 Nominal Power (VJp) 197 Operational Temperature: 40... 185°F(40...+85°C)
,....,„„ ,i,,,,,, 16A `w Nominal Power Voltage-V�,,,(V) 29.0 Maximum System Voltage. 1000VUL
�'QMPP� 6.81 Design Load: SOlbs/ft (2400Pa)longslde
Nominal Power Current-VI:(A)
MORE POWER COMPATIBLE WITH Open Circuit Voltage-V�(V) 35.7 30 Ibs/ft'(1436 Pa)short side
PER FT' ZEP GROOVE FRAME ( 7.24 Max Series Fuse Rating. 1S A
5hortGrcudCurrent-Ix A)
Nominal operanog cell temperature NOCT(WOO W/m'.AM LS.wlndspeed I m/s.ambient temperature 68°F(20°C) Max Reverse Current: 15 A
\ WARRANTY MECHANICAL DATA
G-j,, CERTIFICATION, l0 year product warranty. Dimensions 65.55 x 39.02 x1.57 in(1665 x 991 x 40 mm)
F'FF
c OA 25 year Ilnearpower output warranty Ar ea. 17.75 ftz(1.65 mu)
• US IMPORT EASY TO LISTED (max.degression in performance of 0.7%p.a.). Weight 43(bs(19.Skg)
DUTY FREE INSTALL u t Uua,Fire rating:Type 1,Class C
Note! All given specifications are subject to change
without notice at any time , ..
•
REC is a leading global provider of solar energy solutions. With more than 15 years of experience,we offer sustainable,high performing
products.services and investments for the solar industry.Together with our artners,we create value by providing solutions that better
meet the world's growing energy needs.REC is headquartered in Norway and listed on the Oslo Stock Exchange(ticker:RECSOL).Our 1,600 •employees worldwide generated revenues of USD 647 million in 2013. www.recgroup.com
a
Cl) solar - e • 1FI Single Phase Inverters for North America
solar - • • z CC :111 SE3000A-US/SE3800A-US/SE5000A-US/SE6000A-US/
SE7600A-US/SE10000A-US/SE11400A-US
. U-I
I- OUTPUT I 563000A•US I 563100A-U51 SE5000A-US I SE6000A-US I SE7600A-US I SE10000A US SE11400A-US I
__ .-. .
SolarEdge Single Phase Inverters CC 3980 0 208V
Nominal AC Power Output 3000 3800 5000 6000 7600 20000 0,240v 11400 VA
For Nlorth America LLI Max.AC Power Output 3300 4150 °2°8V 8350 1°8°3.2°8V 12000 VA
5450 0240V 10950 0240V .
AC Output Voltage Min.-Nom.-Max.01 _
,, /
SE3000A-US/SE3800A-US/SE5000A-US/SE6000A-US/ > 183-208-229 Vac
AC Output Voltage Min.-Nom.-Max.ol ,, . .
i / 1 i i 1
SE7600A-US/SE10000A-US/SE11400A-US Z. 211-240-264 Vac
AC Frequency Min.-Nom.-Max.m 59.3-60-60.5(with HI country setting 57-60-60.5) Hz
■
Max.Continuous Output Current 12.5 16 1 24 0 208V 1 25 32 1 48 0 208V 42.5 A
21 e 240V 42#240V
GFDI Threshold V 1 A
Utility Monitoring,Islanding Protection,Country Configurable Thresholds Yes Yes
ov e rfe, Maximum DC Power(STC) 4050 1 5100 F-----lAr,----Tml 10250 MOO 15350 W
1,,V1-25 ''ft. Transformer4ess,Ungrounded Yes
Max.Input Voltage 500 Vdc
1 legs%,,, z
N/430 an".4' , .,- Nom.DC Input Voltage 325 208V/350 240V
9.5 1 13 1 16.5 0 208V I is I 23 Vdc
. ., Max.Input Currentrn 1 33 0 208V 34.5 Adc
... 15.5#240V 30.5 0 240V
Max.Input Short Orcuit Current 45 Adc
# ' Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 600ke Sensitivity
Maximum Inverter Efficiency 97.7 98.2 98.3 98.3 98 98 98 %
.. ' %...-1,,,,, --.:,-K--,OF'06
4 1 541`'''''' 'VT ' .::.7:0, 97.5 el 208V 97•20$V•A4', 97.5 %
97.5
e,„',:, : 77,1 CEC Weighted Efficiency 97.5 98 97.5
98 0 240V 97.5•249V
Nrilz,:w,4,,,,..„ ,e Nighttime Power Consumption <2.5 , , <4,, ,, , ,, ,
t'...,7,1
4
.tr. ADDITIONAL POMMES
Supported Communication Interfaces
Revenue Grade Data,ANSI C12.1
Rapid Shutdown-NEC 2014 690.12 R5485,RS232,Ethernet,ZigBee(optional)
Optional iv
Functionality enabled when SolarEdge rapid shutdown kit is installed
- -'''''' ''' ''''='' '..t tt , STANDARD COMPLIANCE -..4.''''is lt,I.i!:- ^ :ff. ,,,,,t,
7.=11 W Pr< Safety UL1741,UL1699B,UL1998,CSA 22.2
Grid Connection Standards IEEE1547
V VV VV Emissions FCC part15 class B
4
--., _„..,.,...... INSTALLATION SPEaFICATIONS
AC output conduit size/AWG range ne minimum/16-6 AWG 3/4"minimum/8-3 AWG
a
AWG range
,, DC input conduit size/ft of strings/
Dimensions with Safety Switch 3/4"minimum/1-2 strings/16-6 AWG minimum/1-2 strings/
14-6 AWG
30.5 x 12.5 x 7.2/775 x 315 x 184
t (HxWx0) 775 x 315 x 260 mm
Weight with Safety Switch 51.2/23.2 I 54.7/24.7 88.4/40.1 lb/4
!. ., convection
nvection
Cooling Natural Convection and internal Fans(user replaceable)
.„ fan(user V a The best choice for SolarEdge enabled systems Noise 25 replaceable'
< <50 dBA
. " Integrated arc fault protection(Type 1)for NEC 2011 690.11 compliance Mln.-Max.Operating Temperature -13 to+140/-25 to+60(-40 to+60 version available)
Range
. .. Superior efficiency(98%) ..„,
Protection Rating NEMA 3R
.., Small,lightweight and easy to install on provided bracket -
A higher curreni source may be used;the inverten will limit Its input current to the value stated.
- Built-in module-level monitoring oi Revenue grade merter PM:SEmeocA-USOOONNR2(for 7600W Inverter SE7600A-U5002NNR2).
..'"''''- - 7'.'" t ......, v ' ::t R.:014:77p=1:6=NRSPII-Stfor 7603W InverterSE7600A-US007NNU4).
,- Internet connection through Ethernet or Wireless
- Outdoor and indoor installation
- Fixed voltage inverter,DC/AC conversion only ,
, .......„ .
. . .
. , ... .
- Pre-assembled Safety Switch for faster installation
- Optional-revenue grade data,ANSI C12.1 - '
- 0 rk. = Rol-IS
. . . . . .
USA-GERMANY-ITALY-FRANCE-JAPAN-CHINA-AUSTRALIA-THE NETHERLANDS-ISRAEL www.solaredge.us
6
are tradorrmuelrS of their respective owners Date 12 2014 v_os Sah;ecl IA change wittroat notice