8/31/2015 Strand: Installation Instructios::Horizontal California Valves
STRAND EARTHQUAKE CONSULTANTS
Earthquake Safety Equipment
PROFILE — PRODUCTS
PRODUCTS
PAPERS
DOWNLOAD _
ZONE . 1111:":111L _..,i
CONTACT US CALIFORNIA (formerly known as Koso) Seismic Gas Shutoff Valves
HOME Horizontal CALIFORNIA Valves
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Installation and maintenance must be done to the Click here to view installation steps
requirements of the local building code or
governing agency; or, in the absence of local building codes, to the requirements of the
National Fuel Gas Code (ANSI Z223.1), and, if applicable, the National Electrical
Code (ANSI/NFPA 70). Installation and maintenance must be performed by personnel
having the qualifications required by law to install and service natural gas lines and
equipment.
Whenever possible, the valve should be installed in the gas line before the line enters
the protected structure. Generally this is on the customer's side of the meter; but may
be upstream of the meter if allowed by the utility.
Install valve in upright position with the gas flow in the direction of the arrow on the
valve body. The plumb chain in the level indicator on the side of the valve must be
centered in the hole in the bracket through which it passes.
till/ _:: If the valve is installed so the gas flow is in the direction OPPOSITE
, tegy, ' • S W on the valve body, the valve WILL NOT OPERATE
alP � ` - .
VALVE INSTALLATION
The valve must be rigidly mounted to the earth, to the Turning effort
foundation, or near the foundation of the protected Model
•
(inch-pounds)
3t,MAUI G., w dm( movements will be transmitted to
• ...�_.__ the acceleration trigger mechanism located within the 300/310 560
13a1W assembly. 301/311 750
302/312 875
The valve should only be installed in gas lines whose 303/313 940
OFFICE COPY maximum pressure will never exceed the pressure rating
stamped on the valve's nameplate band. During 314 1190
installation, when making pipe connections to the valve 315 1310
body, the turning effort on the valve body's pipe threads 316 1500
SHALL NOT EXCEED the figures in the table to the
right.
After the installation is complete, the gas service should be restored according to the
directions given below under "Opening& Resetting of the Valve."
VERIFICATION OF VALVE OPERATION
http://www.strandearthquake.com/prod seis GSVIns_horizmodel.html 1/2
8/31/2015 Strand::Installation Instructios::Horizontal California Valves
Unless otherwise specified by code, it is recommended that the valve be inspected at
least once a year to assure it is level and has not been damaged. If the valve is found
to be out of level or appears damaged, the customer should call a qualified gas service
person to arrange repairs.
Warning: Read the following sections before attempting to reset the valve.
OPENING&RESETTING OF THE VALVE—MODELS 300,301,302,303
When the valve is closed, a Red Bar will be visible through the window in the position
indicator,which is located on the bottom of the red bonnet,just above the clamp band.
To open the valve, first verify that the main gas shutoff valve is closed, then gently
rotate the Reset Cam(located on the side of the valve)in the direction indicated by the
"to open" arrow, until the Green Bar is visible through the window. Release the turning
effort. If reset has occurred, the Reset Cam will return to its original position, and the
Green Bar will remain visible through the window. The valve is now open, and the
acceleration trigger mechanism is set to respond to a seismic disturbance. The main
gas shutoff valve may now be opened.
OPENING&RESETTING OF THE VALVE—MODELS 310,311,312,313,314,314F,
315,315F,316,316F,317F,318,318F,&319F
When the valve is closed, a Red Bar will be visible through the window in the position
indicator,which is located on the bottom of the red bonnet,just above the clamp band.
To open the valve, first verify that the main gas shutoff valve is closed, then gently
rotate the Reset Cam(located on the side of the valve)in the direction indicated by the
"to open" arrow, which will open the pressure-release poppet in the center of the
valve's disc. Hold the Reset Cam in this position until the pressure equalizes across
the valve's disc. Then, with very little turning effort, continue rotating the Reset Cam
until the Green Bar is visible through the window. Release the turning effort. If reset
has occurred,the Reset Cam will return to its original position, and the Green Bar will
remain visible through the window. The valve is now open, and the acceleration trigger
mechanism is set to respond to a seismic disturbance. The main gas shutoff valve may
now be opened.
Warning: If the reset shaft does not return to its original position, or the valve remains
closed and will not reset, the gas service must be shut off and the valve replaced
before service can be restored. If the valve will not reset, please call the factory or
your distributor for technical service.
After an Earthquake
The acceleration trigger mechanism within the valve has been factory tested to verify
• that the finished valve complies with national (ASCE 25-97) and state (California 12-
16-1) standards. Gas plumbing damage may have occurred during an earthquake or
aftershock. If a gas leak exists, gas service should be turned off at the main shut-off
valve. Do not restore the gas service without assistance from a qualified person. You
will be safer if you let authorized personnel restore service.
•
http://www.strandearthquake.coin/prod_seis_GSVrns_horizmodel.html 2/2
STRAND EARTHQUAKE CONSULTANTS
• Earthquake Safety Equipment
16
PROFILE — q ,. .. -: PRODUCTS
PRODUCTS
00 PAPERS
DOWNLOAD
ZONE ---_1111 - &A
CONTACT US Installation Instructions for Horizontal CALIFORNIA Valves
HOME
ITA41 1'. r .rw
S. } :
in
i
I. Original meter set assembly 2. Turn gas off at manual valve
(MSA) & connection to upstream of meter. Note: If
houseline stub before work has manual valve is difficult to open,
' begun contact your gas utility for
assistance.
r 4�^ M
ihl •
II
3. Loosen meter swivel. 4. Take care not to ruin gasket
when removing union. Note: If
gasket is damaged, call your gas
utility for replacement.
A
Ir%. 117"--,1-
ID
A
5. Remove existing plumbing 6. With original plumbing removed,
. downstream of meter. build new plumbing from
structure to meter.
• _
8. Use telfon tape or liquid sealant
on all joints.
7. Configure new plumbing with
CALIFORNIA Valve.
i
w ,. .:11141111111J.
2
9. Install union gasket and new 10. CALIFORNIA Valve must be
plumbing from meter to building. installed level. Note: Use
leveling chain to confirm that the
seismic valve is level.
• __..et
im 41: •
.
•
11. Install stablizer bracket (Unistrut 12. Finish meter plumbing system
or equivalent) to plumbing with CALIFORNIA Valve.
(within 6" of seismic valve) and Note: For aesthetics, level the
secure to building. stabilizer bracket.
k
1441.11
13. While gas is still off, open 14. Turn gas on at meter inlet valve;
• seismic valve. Do not open do not use pipe wrench. Note:
against gas pressure. Open gas valve slowly to
prevent damage to regulator.
r
15. Use soapy solution to check for
leaks. 16. Apply paint to all new plumbing
to prevent rust.
Back
•
•