Loading...
Report RECD '' 'ED OFFICE COPY AUG 2 4 2015 CITY C BARD BUILDI;\. VIS;ON W YAT T FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 COST PLUS WORLD MARKET T . I . 10108 SW WASHINGTON SQUARE RD TIGARD, OREGON 97223 FIRE PROTECTION EQUIPMENT SUBMITTAL tLICQWorldwide www.tyco-fire.com Fire Protection Contacts _ Products . Series TY-B, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General NOTICE The Series TY-B Sprinklers described I jai • r.,� I Description herein must be installed and maintained T j t k.` in compliance with this document, as " The TYCO Series TY-B, 5.6 K-factor, well as with the applicable standards t `i Upright (TY315)and Pendent(TY325) of the National Fire Protection Associa- Sprinklers /�� described in this data sheet tion,in addition to the standards of any d�"� are standard response,standard cover- other authorities having jurisdiction. fp age,decorative 5 mm glass bulb type Failure to do so may impair the per for- spray sprinklers designed for use in mance of these devices. ,; light, ordinary, or extra hazard, corn- - " l� mercial occupancies such as banks, The owner is responsible for maintain hotels, shopping malls, factories, ing their fire protection system and refineries, and chemical plants. devices in proper operating condition. The installing contractor or sprinkler The recessed version of the Series manufacturer should be contacted with TY-B Pendent Sprinkler, where appli- any questions. cable,is intended for use in areas with a finished ceiling.This recessed pendent S pr sprinkler uses one of the following: p "_ 1 T74. • A two-piece Style 15 Recessed Identification r 1 Escutcheon with recessed adjust- ment up to 5/8 inch (15,9 mm) from Numbers (SINs) the flush pendent position. • A two-piece Style 20 Recessed TY315 Upright 5.6K, 1/2""NPT Escutcheon with recessed adjust- TY325 Pendent 5.6K, 1/2"NPT ,' •. ment up to 1/2 inch (12,7 mm)from the flush pendent position. Technical The adjustment provided by the Temperature Ratings Recessed Escutcheon reduces the Data 135°F(57°C) accuracy to which the fixed pipe drops 155°F(68°C) to the sprinklers must be cut. Approvals 175°F(79°C) UL and C-UL Listed 200°F(93°C) Intermediate level versions of Series FM, LPCB,and VdS Approved 286°F(141°C) TY-B Sprinklers are described in CE Certified 360°F(182°C)t Technical Data Sheet TFP352.Sprinkler guards and shields are described in Sprinklers with Polyester Finish are t UL.C-UL,and VdS Approved only Technical Data Sheet TFP780. UL and C-UL Listed as Corrosion- Resistant Sprinklers. Finishes Sprinkler: Refer to Table A Maximum Working Pressure Recessed Escutcheon:White Coated, 175 psi(12.1 bar) Chrome Plated,or Brass Plated 250 psi(17.2 bar)` 'The maximum working pressure of 250 psi Physical Characteristics (17.2 bar)only applies to the listing by Un- Frame Bronze IMPORTANT derwriters Laboratories, Inc.(UL). Button Brass/Copper Always refer to Technical Data Sealing Assembly Stainless Sheet TFP700 for the 'INSTALLER Discharge Coefficient Steel w/TEFLON WARNING" that provides cau- K= 5.6 GPM/psis 2(80,6 LPM/bar 2) Bulb Glass tions with respect to handling and Compression Screw Bronze installation of sprinkler systems and Deflector Bronze components. improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP152 TFP152 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. ' 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6 --- / 5 'mil 7/16--i " I !-_ (11,1 mm) —� i• _ 4 NOMINAL ' 2" I MAKE-IN �_ (50,82'm' I 2 r- `` q 2" 1-3/8"OP �1 0.` (50,8 mm) (34,9 mm) I ` r o 1 7 ri WRENCH 1/2"NPT** DEFLECTOR* [ 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-B UPRIGHT(TY315)AND PENDENT(TY325)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT,STANDARD RESPONSE �, Operation Installation The glass bulb contains a fluid which The TYCO Series TY-B, 5.6 K-factor, WRENCH RECESS expands when exposed to heat.When Upright(TY315)and Pendent (TY325) (USE ONLY the rated temperature is reached,the Sprinklers must be installed in accor- END"A") fluid expands sufficiently to shatter the dance with this section. ^ glass bulb, allowing the sprinkler to FIGURE 2 activate and water to flow. Do General Instructions not install any bulb type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss of SPRINKLER WRENCH _ Design liquid from the bulb.With the sprinkler held horizontally, a small air bubble _ WRENCH Criteria should be present.The diameter of the WREN RRCNS air bubble is approximately 1/16 inch The TYCO Series TY-B, 5.6 K-factor, (1,6 mm)for the 135°F (57°C) to 3/32 Upright(TY315)and Pendent(TY325) inch (2,4 mm) for the 360°F (182°C) � Sprinklers are intended for fire protec temperature ratings. /I—� tion systems designed in accordance with the standard installation rules A leak-tight 1/2 inch NPT sprinkler recognized by the applicable Listing joint should be obtained by applying a or Approval agency (e.g., UL Listing minimum-to-maximum torque of 7 to 14 `� is based on the requirements of NFPA ft.-Ibs. (9,5 to 19,0 Nm). Higher levels N.r, 13, and FM Approval is based on the of torque may distort the sprinkler inlet PUSH WRENCH requirements of the FM Loss Preven- and cause leakage or impairment of the IN TO ENSURE tion Data Sheets). Only the Style 15 sprinkler. ENGAGEMENT or Style 20 Recessed Escutcheon, as Do not attempt to compensate for WITH SPRINKLER applicable,is to be used for recessed insufficient adjustment in the escutch- WRENCHING AREA pendent installations. eon plate by under-or over-tightening FIGURE 3 the sprinkler. Readjust the position of W-TYPE 7 RECESSED the sprinkler fitting to suit. SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-B Upright and Pendent Sprinklers must be installed in accor- dance with the following instructions. Step 1. Install pendent sprinklers in the pendent position; install upright sprinklers in the upright position. . Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP152 Page 3 of 4 Step 3.Tighten the sprinkler into the 2-7/8"DIA. sprinkler fitting using only the W-Type – (73,0 mm) . 6 Sprinkler Wrench (Figure 2). With reference to Figure 1,apply the W-Type 2-1/4"DIA. 6 Sprinkler Wrench to the wrench flats. FACE OF — (57,2 mm) — Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER - 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers i \ - FLUSH The Series TY-B Recessed Pendent 3/8±5/16" =_1 1 Sprinklers must be installed in accor- (9,5±7,9 mm) _api. . 1/ i dance with the following instructions. + ' g� } Step A.After installing the Style 15 or MOUNTING 1/8" J Style 20 Mounting Plate,as applicable, SURFACE (3,2 mm) over the sprinkler threads and with -- — pipe-thread sealant applied to the pipe CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) threads,hand-tighten the sprinkler into TY-B PLATE 3/4"(19,1 mm) the sprinkler fitting. Step B.Tighten the sprinkler into the FIGURE 4 sprinkler fitting using only the W-Type SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325) 7 Recessed Sprinkler Wrench -Type WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 3).With reference to Figure 1,apply the RECESSED ESCUTCHEON W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8"DIA. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After the ceiling is installed or SPRINKLER —2-1/4"DIA. the finish coat is applied,slide on the FITTING (57,2 mm) —� Style 15 or Style 20 Closure over the 5/16±1/4" Series TY-B Sprinkler and push the (7,9±6,4 mm) 1/2"(12,7 mm) Closure over the Mounting Plate until - FLUSH its flange contacts the ceiling. 1 Care and t I } MOUNTING 1/8 J Mainteance SURFACE (3,2 mm) The TYCO Series TY-B, 5.6 K-factor, Upright(TY315)and Pendent(TY325) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-B PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325) main control valve for maintenance WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. The owner is responsible for the system from the proper authorities Sprinklers that have been exposed to inspection,testing,and maintenance of and notify all personnel who may be corrosive products of combustion,but their fire protection system and devices affected by this action. have not operated,should be replaced in compliance with this document, as Absence of the outer piece of an if they cannot be completely cleaned by well as with the applicable standards escutcheon, which is used to cover wiping the sprinkler with a cloth or by of the National Fire Protection Associa- a clearance hole, can delay sprinkler brushing it with a soft bristle brush. tion (e.g., NFPA 25), in addition to the operation in a fire situation. Care must be exercised to avoid dam- standards of any other authorities hav- ing owner must assure that the age to the sprinklers- before, during, ing jurisdiction. Contact the installing and after installation. Sprinklers dam- contractor or sprinkler manufacturer sprinklers are not used for hanging regarding any questions. any objects and that the sprinklers are aged by dropping, striking, wrench only cleaned by means of gently dust- twist/slippage, or the like, must be Automatic sprinklers are recommended ing with a feather duster; otherwise, replaced. Also, replace any sprinkler to be inspected,tested,and maintained non-operation in the event of a fire or that has a cracked bulb or that has lost by a qualified Inspection Service in inadvertent operation may result. liquid from its bulb. (Ref. Installation accordance with local requirements Section.) and/or national codes. Sprinklers which are found to be leak Thereafter, annual inspections per ing or exhibiting visible signs of corro NFPA 25 are required;however,instead sion must be replaced. of inspecting from the floor level, a Automatic sprinklers must never be random sampling of close-up visual painted, plated, coated, or otherwise inspections should be made. altered after leaving the factory. - - --- TFP152 Page 4 of 4 P/N* 77 - XXX - X - XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 570 5.6K UPRIGHT(1/2'NPT) TY315 1 NATURAL BRASS 135 135°F(57°C) 571 5.6K PENDENT(1/2"NPT) TY325 3 PURE WHITE(RAL9010)" 155 155°F(68°C) POLYESTER •Use suffix 1"for ISO 7-1 connection; SIGNAL WHITE(RAL9003) for example,77-570-4-175-I 4 POLYESTER 175 175°F(79°C) 9 CHROME PLATED 200 200°F(93°C) '*Eastern Hemisphere sales only 286 286°F(141°C) 360 360°F(182°C) 000 OPEN*** *"OPEN indicates sprinkler assembly without Glass Bulb, Button,and Sealing Assembly TABLE A SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order,indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-B Upright or Pen- dent(specify)Sprinkler, SIN (specify), K=5.6, Standard Response, (specify) temperature rating,(specify)finish,P/N (specify,refer to Table A) Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish, P/N(specify*) Specify:Style 20 Recessed Escutcheon with(specify')finish, P/N(specify') •Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 Copyright®2014 Tyco Fire Products,LP. All rights reserved. t cc TEFLON is trademark of The DuPont Corporation. Fire Protection Products I. Ductile Iron Fittings- Class 300 UL/FM I QUALM PLUS c ® us APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED Size Part Number A Packing Weight �'`"�`"-' in in Inner Master lb 1/2 35CP3004 1.38 200 400 0.1 3/4 35CP3006 1.63 100 200 0.2 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35CP3014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling 111 . Size A Packing Weight N\ in Part Number in Inner Master lb 7® A 1 x 1/2 35RC3010004 1.69 80 160 0.3 1 x 3/4 35RC3010006 1.69 60 120 0.4 - i 1-1/4x3/4 35RC3012006 2.06 40 80 0.6 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B in in Inner Master lb ( ) 1 x 1/2 35HB3010004 1.06 180 360 0.2 kIA 1 x 3/4 - 35HB3010006 1.06 180 360 0.1 1-1/4x1 35HB3012010 1.19 90 180 0.2 1111 . i 35H83014010 1.25 75 11150 0.4 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 D . -..x' 35HB3020010 1.38 40 80 0.6 U 2 x 1-1/4 35H B3020012 1.38 40 80 0.6 C 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 T I Fig. 35SP3 -Square Head Plug E Size A Packing Weight in Part Number in Inner Master lb 1/2 35SP3004 0.94 600 1200 0.07 �. A 3/4.41.. 35SP3006 1.12 350 700 0.1 •. AN I 1 35SP3010 1.25 200 400 0.1 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 - 0.6 Fig. 35U 3-Union with Brass Seat 0 A Size A Packing Weight Part Number in _ in Inner Master lb �-: ....r 1 35U 3010 2.19 20 40 1.0 1-1/4 35U 3012 2.50 15 30 1.2 1-1/2 35U 3014 2.62 10 20 1.7 2 35U 3020 3.12 6 12 2.4 113 SMITH-COOPER INTERNATIONALS • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com • ,;:,, . . _ 10.52 FireLock® Outlet-T `®us O VdS 9?�B SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating V,/,and 1/15,20 and 25mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and • other outlet products.Available for 11/2 through 76.1 mm/32 to 76.1 mm piping systems,Style 922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS r Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up to 300 psi/2068kPa and VdS rated up to 16bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard,lightwall,Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. • MATERIAL SPECIFICATIONS Housing:Ductile iron conforming to ASTM A-536,grade 65-45-12.Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Gasket: • Grade"E"EPDM-Type A (Violet color code).FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Gasket System. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: • Orange enamel(North America,Latin America,Asia Pacific) • Red enamel(Europe) JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.02009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ictaulid FEV G 10.52 1 • . 1 IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS 10.52 • FireLock® Outlet-T STYLE 922 DIMENSIONS Size Hole A • pprox. mchrelmni Dimensions-incheshnillimeters ' Weight Each Rim X Brach-1 EPTI Y Z 0.001.0.0 T. V W Y Z 1 Ihslkg 154 X 11 13/16 1.30 1.83 1.10 3.87 2.56 1.0 ��� \ 32 15 30.2 33.0 46.5 27.9 98.3 65.0 0.45 ift Illira. 20 1 0.2 1.28 6.5 1.10 98.3 65.0 .5� Zd 30.2 32.5 46.5 279 98.3 65.0 0.50 1 ■ u��� � VV ill 1 13/16 1.52 2.18 1.10 3.87 2.56 1.2 �� I I 25 30.2 38.6 55.4 27.9 98.3 65.0 0.54 11/2 K 13/16 1.42 1.95 1.22 4.08 2.56 1.2 40 X 15 30.2 36.1 49.5 31.0 103.6 65.0 0.54 114 1 3/16 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 49.5 31.0 103.6 65.0 0.54 1 13/16 1.64 2.30 1.22 4.08 2.56 1.3 25 30.2 41.7 58.4 31.0 103.6 65.0 0.59 2 54 13/16 1.66 2.19 146 4.60 2.56 1.3 50 X 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 14 13/16 1.64 2.19 1.46 4.60 2.56 1.4 20 30.2 41.7 55.6 37.1 116.8 65.0 0.64 1 13/16 1.88 2.54 146 4.60 2.56 1.5 25 30.2 47.8 645 371 116.8 65.0 0.68 211 lh 13/16 1.91 2.44 1.71 5.40 2.56 1.6 65 X 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73 14 1 3/16 1.89 2.44 1.71 5.40 2.56 1.6 20 30.2 48.0 62.0 43.4 137.2 65.0 0.73 1 13/16 2.13 2.79 1.71 5.40 2.56 1.6 25 30.2 54.1 70.9 43.4 137.2 65.0 0.73 76.1 mm X N 1 3/16 1.91 2.44 1.71 5.50 2.56 1.6 15 30.2 48.5 62.0 43.4 139.7 65.0 0.73 14 1 3/16 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 62.0 43.4 139.7 650 0.73 1 13/16 2.13 2.79 1.71 5.50 2.56 1.7 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional) male pipe threads only.Use of male threaded products with special features,such as probes,dry pen- dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify suitability in advance may result in assembly problems or leakage. "Center of run to engaged pipe end for NPT threads(dimensions are approximate). www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. gCVlgr..A • 72.52 2 REV G • IPS CARBON STEEL PIPE-HOLE CUT PRODUCTS 10.52 FireLock® Outlet-T STYLE 922 PERFORMANCE Equivalent Length of 1 inch Schedule 40 Steel Pipe(per UL Run Size x Outlet Size 213,Section 16)(C=120)•,FT 114 x 8.5 32 S 2.6 115 1 8.5 40 x 25 2.6 2 x 1 8.5 50 25 2.6 21.4 X 1 8.5 65 25 2.6 76.1 mm X 1 8.5 25 2.6 •Hazen-Williams coefficient of friction is 120 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. iCtaUIuC.' REV G 10.52 3 FireLock® Outlet STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing.Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. • NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 10.52 3355 REV G UPDATED 12/2009 iCtui`.P VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10.52