Plans ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE 1. THIS SYSTEM IS GRID-INTERTIED VIA A AC ALTERNATING CURRENT UL-LISTED POWER-CONDITIONING INVERTER. BLDG BUILDING 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. CONC CONCRETE 3. A NATIONALLY-RECOGNIZED TESTING RECEIVEP DC DIRECT CURRENT LABORATORY SHALL LIST ALL EQUIPMENT IN EGC EQUIPMENT GROUNDING CONDUCTOR COMPLIANCE WITH ART. 110.3. CITY OF TIGARD (E) EXISTING 4. WHERE ALL TERMINALS OF THE DISCONNECTING REVIEWED£OR CODE COMPLIANCE EMT ELECTRICAL METALLIC TUBING MEANS MAY BE ENERGIZED IN THE OPEN POSITION, FSB FIRE SET-BACK A SIGN WILL BE PROVIDED WARNING OF THE Approved: [ IA"' JUN 0 2015 GALV GALVANIZED HAZARDS PER ART. 690.17. OTC: [ I (ATV 0i, 1161 GEC GROUNDING ELECTRODE CONDUCTOR 5. EACH UNGROUNDED CONDUCTOR OF THE �������� Toil GND GROUND MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY Permit#: it(. �-)1 - ti 1sIOI\, HDG HOT DIPPED GALVANIZED PHASE AND SYSTEM PER ART. 210.5. Address: "J(T3 *) t O .3 F"( J I CURRENT 6. CIRCUITS OVER 250V TO GROUND SHALL Imp CURRENT AT MAX POWER COMPLY WITH ART. 250.97, 250.92(B). Site #:1)30,3 Isc SHORT CIRCUIT CURRENT 7. DC CONDUCTORS EITHER DO NOT ENTER B Date: .7 1,g, --- kVA KILOVOLT AMPERE BUILDING OR ARE RUN IN METALLIC RACEWAYS OR kW KILOWATT ENCLOSURES TO THE FIRST ACCESSIBLE DC LBW LOAD BEARING WALL DISCONNECTING MEANS PER ART. 690.31(E). MIN MINIMUM 8. ALL WIRES SHALL BE PROVIDED WITH STRAIN (N) NEW RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY OFFICE COPY NEUT NEUTRAL UL LISTING. NTS NOT TO SCALE 9. MODULE FRAMES SHALL BE GROUNDED AT THE OC ON CENTER UL-LISTED LOCATION PROVIDED BY THE PL PROPERTY LINE MANUFACTURER USING UL LISTED GROUNDING POI POINT OF INTERCONNECTION HARDWARE. PV PHOTOVOLTAIC 10. MODULE FRAMES, RAIL, AND POSTS SHALL BE SCH SCHEDULE BONDED WITH EQUIPMENT GROUND CONDUCTORS. S STAINLESS STEEL STC STANDARD TESTING CONDITIONS TYP TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V VOLT Vmp VOLTAGE AT MAX POWER VICINITY MAP INDEX_ Voc VOLTAGE AT OPEN CIRCUIT W WATT I _� ° PV1 COVER SHEET 3R NEMA 3R, RAINTIGHT . "° g " � � � �_ �� '� - ' PV2 SITE PLAN _ PV3 STRUCTURAL VIEWS ' PV4 UPLIFT CALCULATIONS ' �` `� _ PV4 THREE LINE DIAGRAM LICENSE GENERAL NOTES � � � � �: Cutsheets Attached OR # 180498 1. ALL WORK TO BE DONE TO THE 2014 OSSC cii � ., ��RGC, CGC1 AND 2012 IBC. �.2. ALL ELECTRICAL WORK SHALL COMPLY WITH ' "' „.THE CURRENT NATIONAL ELECTRIC CODE AS " ` AMENDED BY THE OREGON ELECTRICAL SPECIALTY . . , "` CODE. ''- MODULE GROUNDING METHOD: ZEP SOLAR �`. 3 �'., _I " REV BY DATE COMMENTS AHJ: Tigard ' ��DATE COMMENTS 4. [r " UTILITY: Portland General Electric ' l (� '+�i ©©_ i meiro, riert and Oregon, Sta e tore gon, U.S. Geological S urvey©lil� CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: J B—9 7 2 2 7 7 8 00 PREMISE OWNER: DESCRIPTION: DESIGN: CONTAINED OF SHALL NOT EXCEPT CE USED FOR THE ERNSTER, CARLA ERNSTER RESIDENCE Luke Levin ti:',',SolarCity BENEFIT OF ANYONE EXCEPT SD FOR TT INC., MOUNTING SYSTEM: NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C 13173 BOUNEFr ST 5.98 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: PORTLAND, OR 97223 THE SALE AND USE OF THE RESPECTIVE (23) REC # REC260PEZ 3055 Mateo, CA Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV DATE: 638-1028 Maieo, CA 94402 PERMISSION OF SOLARCITY INC. INVERTER' T:(650)636-1028 F:(650)638-1029 ABB ; PVI-5000-OUTD-US-Z-A (503) 521-8577 COVER SHEET PV 1 6/26/2015 (888) SOL—OTY(765-2489) www.sdarciiy.com PITCH: 22 ARRAY PITCH:22 MP1 AZIMUTH: 180 ARRAY AZIMUTH: 180 MATERIAL: Comp Shingle STORY: 1 Story Fence a o a LEGEND 12" FS . — — — —�� , ���I 0 (E) UTILITY METER & WARNING LABEL ME =MIMI ® &INVERTER W/WARNING LABELS RATED DC DISCO MIMI 1-1:15-1 DC DISCONNECT & WARNING LABELS Equipment under shed __ �MI . Ri nv; O AG 0 F'� AC DISCONNECT & WARNING LABELS A3 _ 0 0 0 0 0 DC JUNCTION/COMBINER BOX & LABELS L��J MP1 Ni ) _ D 0 DISTRIBUTION PANEL & LABELS (, 14 ' 1, D N'' LC LOAD CENTER & WARNING LABELS gek Tir 1J IocktTi Gard O DEDICATED PV SYSTEM METER 0 STANDOFF LOCATIONS • CONDUIT RUN ON EXTERIOR - CONDUIT RUN ON INTERIOR (E)DRIVEWAY GATE/FENCE Front Of House 0 HEAT PRODUCING VENTS ARE RED r,7-.1 1k 'I INTERIOR EQUIPMENT IS DASHED L-J 13173 Bouneff St SITE PLAN N TOTAL ARRAY AREA (SF): 417 Scale: 3/32" = 1' �� • TOTAL ROOF AREA (SF): 4082 w `r E TOTAL ARRAY AREA IS a 10.21 O 1' 10' 21' PERCENT OF TOTAL ROOF AREA �•�-1111. S CONFIDENTIAL– THE INFORMATION HEREIN JOB NUMBER J B-9722778 00 PREMISE OWNER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE ERNSTER, CARLA ERNSTER RESIDENCE Luke Levin ��'!, • BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: .j;,SOIarClty NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C 13173 BOUNEFF ST 5.98 KW PV ARRAY PART TO OTHERS OUTSIDE HE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES PORTLAND, OR 97223 THE SALE AND USE OF THE RESPECTIVE (23) REC # REC260PEZ 3055 t "way THE SALE EQUIPMENT, WITHOUT THE WRITTEN PAGE NNE SHEET: REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY WITHOUT INC. INVERTER: T:(650)638-1028 F:(650)638-1029 n, ABB # PV1-5000-OUTD-US-Z-A (503) 521-8577 SITE PLAN PV 2 6/26/2015 (888)–soL–aTY(765-2489)www.eolorolty.aa V0°..° (E) 2x4 (E) 2x6 PV MODULE /\ 5/16" BOLT WITH LOCK INSTALLATION ORDER • & FENDER WASHERS • LOCATE RAFTER, MARK HOLE STRUCTURE MEETS THE ZEP LEVELING FOOT (1) LOCATION, AND DRILL PILOT PRESCRIPTIVE REQUIREMENTS ZEP ARRAY SKIRT (6) HOLE.OF THE OSISC SECTION 305.4 (4) ,)-). ) ) SEAL PILOT HOLE WITH POLYURETHANE SEALANT. jE) LBW ZEP COMP MOUNT C ZEP FLASHING C ����-�� �:1! (`) INSERT FLASHING.-- ACEINSIWAY411010 / 1' ' - 10'-5" /r_5'-11" -/ -6'-11" j (E) COMP. SHINGLE (4) PLACE MOUNT. (E) ROOF DECKING / + (E) LBW -f- (5} INSTALL LAG BOLT WITH 5/16" DIA STAINLESS (5) SEALING WASHER. SIDE VIEW OF MP1 NTS STEEL LAG BOLT LOWEST MODULE SUBSEQUENT MODULES / INSTALL LEVELING FOOT WITH A WITH SEALING WASHER (6) BOLT & WASHERS. MP1 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES (2-1/2" EMBED, MIN) LANDSCAPE 72" 24" STAGGERED (E) RAFTER STANDOFF PORTRAIT 48" 20" RAFTER 2x10 @ 24"OC ROOF AZI 180 PITCH 22 STORIES: 1 Scale: 1 1/2" = 1' ARRAY AZI 180 PITCH 22 Comp Shingle CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: J13-9722778 ; PREMISE OWNER: DESCRIPTION: DESI( CONTAINED SHALL NOT BE USED FOR THE 9722778 00 ERNSTER, CARLA ERNSTER RESIDENCE Luke Levin \,I. BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: -=�� SolarC�ty. NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type A PART TO OTHERS OUTSIDE THE RECIPIENTS P ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: PORTLAND, OR 97223 THE SALE AND USE OF THE RESPEC114f (23) REC # REC26OPEZ 3055 Clearview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN 'iNvERTER. PAGE NNE: SHEET: REV.. DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. (503) 521-8577 STRUCTURAL VIEWS PV 3 6/26/2015 (888)(SOL,CIT�!(765-2489)_ ABB # PVT-5000—OUTD—US—Z—A _ x 111 11 UPLIFT CALCULATIONS 06.26.2015 '`'`_ PV System Structural Version#46.4 ' , o�aI 'Y Desian Software Risk t., ` 4' r ,''- Camp Roof Comp Roof _ 2 Roof 22° t 24'0,C PV System Module Orientation Landscape and Portrait fAV `;. 409 sf PV Module Width 39" PV Module length 66" Standoff(Attachment Hardware) Comp Mount Type C Reduced Ground/Roof Live/Snout. -. Ground Snow Load pg 25.0 psf ]ASCE Table 7-1 SwToundIng Roof Snow 70% 17.5 psf ]ASCE Eq:7.4-1 Roof Snow Over PV Modules 70% 17.5 p4 1 ASCE Eq:7.4-1, Inlift 0011111111*Iberia Wind Design Code ASCE 7-05 ' Wind Design Method Partially!FUWY Enclosed Method Basic Wind Speed V 95 mph ' Fig.6-1 Exposure Category C ' Section 6.5.6.3 Roof Style Gable Roof 'Hg.6-11B/C/D-14A/B Mean Roof Height h 15 ft Section 6.2 Effective Wind Area(1 Module) A 17.8 sf IBC 1509.7.1 irilld Prewar*Calculation Coefficients Wind Pressure Exposure Kz 0.85 Table 6-3 Topographic Factor Kzt 1.00 Section 6.5.7 Wind Directionality Factor Kd 0.85 Table 6-4 Importance Factor 1 1.0 Table 6.1 Velocity Pressure qh qh =0.00256(Kz)(Kzt)(Kd)(VA2)(I) Equation 6-15 16.7 psf Ext.Pressure Coefficient(Up) GCp(Up) -0.88 Hg.6-118/C/0-14N8 Ext.Pressure Coeffident(Down) GCp(Down) 0.45 rig.6-118/C/D•14A/B Design Wind Pressure p p=qh(GCp) Equation 6-22 Wind Pressure Up p(up) -14.6 psf Wind Pressure Down p(down) 10.0 psf �OWi�4I Stando f i. If-Direction Max Allowable Standoff Spacing Landscape 72" 39" Max Allowable Cantilever l.anrlscape 24" NA Standoff Configuration Landscape Staggered Max Standoff Tributary Area Trtb 20 sf PV Assembly Dead Load W-PV 3 psf Net Wild Uplift at Standoff 7-adual -252 lbs Uplift Capacity of Standoff T-allow 500 lbs Standoff Decnand/CapacKy DCR ',10.0111r, Max Allowable Standoff Spacing Portrait 48' 66" Max AftwobleC,aMllever P'rxtrat .��'�� � 20" NA -- Standoff Configuration Portrait ' Max Standoff Tom . 1 E. _ �.Pe Net W nd at Standoff u a, ..T";. : PV Assembly Dead Load W-PV 3 Uplift Capacty of Standoff T-allow 500 Hs CONFIDENTIAL A THE INFORMATION HEREIN JOB NUMBER JB-9722778 00 ERNSTER, CARLA ERNSTER RESIDENCE Luke Levin �.�l, PREMISE DESCRp110ft DESIGIk `\, BENEFIT O SHALL NOT E USED FOR THE SoIarCity NOR SH1E m ou 13173 BOUNEFF ST NOR SHALL IT BE DISCLOSED IN WMOLE OR IN Comp Fount Type C 5.98 KW PV A PART TO OTHERS OUTSIDE THE RECIPIENT'S ORGANIZATION, EXCEPT IN CONNECTION WITH M(XX ES: PORTLAND, OR 97223 THE SALE AND USE OF THE RESPECnME (23) REC # REC260PEZ 3055 CIearre'War SOLARCITY EQUIPMENT. WITHOUT THE % ITTEN PAGE WIC SHEET: REV DATE: Sm Moteo CA 94402 PERMISSION OF SOLARCITY INC ABB# PVI-5000-OUTD-US-Z-A (503) 521-8577 UPLIFT CALCULATIONS PV 4 6/26/2015 ( >(SO�L'a131�('65-2;89)w:f.6.a i c,m Label Lo)( cation: Label Location: Label Location: • CAUTION: SOLAR CIRCUIT (C)(ICCB) MAXIMUMAC _ A (AC)(POI) WARNING (P01) Per Code: OPERATING CURRENT Per Code: Per Code: IFC 605.11.1.4 MAXIMUM AC _ V NEC 690.54 INVERTER OUTPUT NEC 690.64.B.7 ZS Comp Edge Zone Calculations 1 of 4 OPERATING VOLTAGE CONNECTION P g ZS Comp Edge Zone Calculations 2 of 4 Label Location: • THIS OVER DO NOT RELOCATE RRENT pSotar 3/26/15 �e��O�a� 3/26/15 PHOTOVOLTAIC DC (DC) (INV) DE CE DISCONNECT Per Code: at of calculations is intended to show that ZS Comp has sufficient strength to allow for attachment Down Force Spacing NEC 690.14.C.2 Label Location: igs of at least 48"in Edge Zones whether the modules are orientated in landscape or portrait.The Allowable Down Force Load WARNING (AC) (P01) ations will vary the design variables to account for the worst case for each failure mode that is being down force spacing = module width x design load ELECTRIC SHOCK HAZARD Per Code: Label Location: ed. DO NOT TOUCH TERMINALS NEC 690.17(4) DC Wind Down Calculations Label Location: WARNING ( ) (INV) TERMINALS ON BOTH LINE AND Per Code: All variable the same as above except for roof pitch MAXIMUM POWER--A (DC) (INV) LOAD SIDES MAY BE ENERGIZED ELECTRIC SHOCK HAZARD ral Design Information: Roof Pitch POINT CURRENT(Imp) NEC 690.35 F Per Code: IN THE OPEN POSITION THE DC CONDUCTORS OF THIS ( ) Ile Size: 39"x 65' Basic Wind Speed= 120 mph 14 30 45 MAXIMUM POWER- PHOTOVOLTAIC SYSTEM ARE TO BE USED WHEN NEC 690.53 stem Weight= 3 psf Ground Snow Load= 30 psf GCN landscape= 0.5 0.9 0.9 POINT VOLTAGE(Vmp) UNGROUNDED AND INVERTER IS MAXIMUM SYSTEM MAY BE ENERGIZED GCN portrait= 0.4 0.9 0.9 VOLTAGE(Voc) V UNGROUNDED Mount Allowable Loads GC SHORT-CIRCUIT_ Duration Wind Snow g landscape- psf A desi n load - 15.35 27.64 27.64 CURRENT(Isc) Label Location: ►��r PV SYSTEM (AC) Uplift= 656 lbs N/A ;, •iwtga1��- design load Portrait= 12.28 27.64 27.64 psf DISCONNECT FOR Lateral= 357 lbs 290 lbs 858I8 note:use 10 psf minimum UTILITY OPERATION n Force= 1074 lbs 771 lbs OREGON q Snow Calculations �� To account for unbalanced snow loads,ground snow loads will be used for roof pitches 30 degrees and lower. Label Location: `F ` 10'O' Per section 7.6.1 of ASCE 7-10 unbalanced snow loads do not need to be considered for slopes above 30 :hment Spacing Calculations frr soy P WARNING (DC)(CB) S a degrees. Per Code: cin EXPIRES 12/31/16 ELECTRICAL SHOCK HAZARD Allowable Uplift Load FOR PAGES 1-4 DO NOT TOUCH TERMINALS NEC 690.17(4) Label Location: lift spacing= Ground Snow Load= 30 psf TERMINALS ON BOTH LINE AND PHOTOVOLTAIC POINT OF (P01) module length or width x design load Roof Pitch LOAD SIDES MAY BE ENERGIZED INTERCONNECTION Per Code: Uplift Calculations 14 30 IN THE OPEN POSITION WARNING:ELECTRIC SHOCK DC VOLTAGE IS HAZARD.DO NOT TOUCH NEC 690.17.4; NEC 690.54 ALWAYS PRESENT WHEN TERMINALS.TERMINALS ON )SSC and ASCE 7-10 Method 2 Design Snow Load 29.11 25.98 psf SOLAR MODULES ARE BOTH THE LINE AND LOAD SIDE GCN (snow load spread over the length of the rafter) EXPOSED TO SUNLIGHT MAY BE ENERGIZED IN THE OPEN 00256 KZ Ktt Kd VZ I POSITION. FOR SERVICE Down Force Load Roof Pitch DE-ENERGIZE BOTH SOURCE is Wind Speed= 120 mph Combinations: 14 30 AND MAIN BREAKER. Exposure= C Roof Zone= Edge Zone D+S= 31.16 25.10 psf PV POWER SOURCE )rtance Factor= 1.0 K,= 0.98 from Table 6-3 D+0.6*W= 12.91 19.18 psf Label Location: MAXIMUMAC _ A Gable/Hip Roof K = 1.0 D+0.75*0.6*W+0.755 31.59 31.91 psf OPERATING CURRENT z,- per 6.5.7.2 WARNING (DC)(INV) MAXIMUMAC _ Per Code: OPERATING VOLTAGE V ase Roof Pitch= 14 degrees Kd= 0.85 from Table 6-4 ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED NEC 690.5(C) Roof Height= 30 GCN landscape= -1.6 Allowable Spacing for Down Force NORMALLY GROUNDED effective area= 13.0 ft2 GCN portrait= -1.5 CONDUCTORS MAY BE effective area= 21.7 ft2 landscape down force spacing = 39"x 31I91psf x 144 �Z =89" UNGROUNDED AND ENERGIZED Plandscape= -49.13 psf Label Location: CAUTION (P01) DUAL POWER SOURCE qh= 30.71 psf Pportrait= -46.06 psf _ 7711bs in Per Code: portrait down force spacing x 144-= 53" SECOND SOURCE IS NEC 690.64.B.4 p j p g 65"x 31.91psf jt2 Label Location: PHOTOVOLTAIC SYSTEM odd Combination:0.6D+0.6W(ASCE Section 2.4.1 equation 7) PHOTOVOLTAIC AC (AC)(P01) (AC):AC Disconnect _ DISCONNECT Per Code: (C): Conduit gnol adndswpe- 27.73 psf NEC 690.14.C.2 (CB): Combiner Box portrait= -25.89 psf Label Location: (D): Distribution Panel dscape uplift spacin g = 656 lbs in 87" (D) (POI) (DC): DC Disconnect 39"x 27.73 psf x 144 ft2 = CAUTION Per Code: (IC): Interior Run Conduit 6561bs in PHOTOVOLTAIC SYSTEM (INV): Inverter With Integrated DC Disconnect ortrait uplift spacing = x 144-=56" CIRCUIT IS BACKFED NEC 690.64.B.4 65"x 25.89 psf ft2 (LC): Load Center (M): Utility Meter (P01): Point of Interconnection CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR vb'il4 _ j 3055 Clearview Way THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED �� San Mateo,CA 94402 IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENT'S ORGANIZATION, Label Set ���t�` T:(650)638-1028 F:(650)638-1029 EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE ,, So Ia rC i ty.: (888)-SOL-CrTY(765-2489)www.soIarcity.com SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. 1 . k ' v ;■ ENERGIZING LIFE TOGETHER ,,.. REC REC PEAK ENERGY Z LINK 5ERIE5 _...i.1,i. 65.55±O.I _ HIGH PERFORMANCE —: , 1 EFFEIENCY SOLAR PANELS 10 YEAR PRODUCT WARR' 25 YEAR L�jEAR POWER 'N„. OUTPUT WARRANTY R EC F EAK ,.n , 4r'14 O�T)'*pnC US IMPORT DUTY FREE 2.47 C` ��' •=e t ,,r : TEMPERATURER ATINGS •- - Nominal Operating Cell Temperature(NOCT) 457°C(±2°C) Z ' K1/4 L I I I' TemperatureCoeffitientofPM,,, 0.40%/C `; t_ lv Temperature CoeffcientofVpr -0.27%/°C ;. _ Temperature Coefficientoflsr 0.024%J C. < - 'a—'ee: -- �' -Link Series solar All measurements in inches panels are the perfect choice for building ECEC T nr_i,r iiA?7 REC260PEZ GENERAL DATA solar systems that combine long lasting Nominal Power-P,�,,,(Wp) 260 Cell Type 6o REC PE mull i rystall Iii\t product quality with reliable power output. Watt Classsorting-(Wp) •/5 3stringsof2Ocellswithbypassdiodec Nominal Power Voltage-V (V) 307 F Glass: 0.125insolarglasswithanti-reflection ; REC combines high quality design and surface treatment Nominal Power Current-I (A) 8.50 I Back Sheet' Double la erhi hl resistant of ester :,i,l, manufacturingstandardstaproducehigh y g y P v Open Circuit Voltage-V�(V) 37.8 7 performance solar panels wit"1 Frame. Anodizedaluminum(blabk) ShortCircuitCurrent-Ix(A) 9.01 { ZepGroovecompatible t r1COR pro Tlliln nuallty. Panel Efficiency(%) 158 � luncGonOnx: IP67rated 0156 in(12 AWG)solar cable.2 x 4774 m The electrical characteristics are within•/-10%of the indicated values of I Va and P at standard Test conditions(STC) i OM PA Values at standard test conditions STC(alrmass AM l.S,irradiance 1000 W�ma,cell temperature 7TF(25°C)) € Connectors H4 Amphenol �QG T�� At low irradiance of 200W/m'(AM1.5&cell 77'F(25°C))at least 97%of the 5TC panel efficiency will be achieved origin: Made in Singapore • • ELECTRICAL DATA,�NOCT REC260PEZ MAXIMUM RATINGS 7, �� Nominal Power P,•,v(Wp) 197 ( Operational Temperature: -40..+185°F(40 85°C)ry I COMPp�� Nominal Power Voltage-V ,(V) 29.0 ' Maximum System Voltage- 1000VUL iii Nominal Power Current-Iim,(A) 6.81 oad: 50)bs/ft�(2400Pa)longside MORE POWER COMPATIBLE WITH PER FT, ZEP GROOVE FRAME Open Circuit Votage-Vrx(V) 35.7 301bs/ft'(1436 Pa)short side Short CircuitCurrent-Ix(A) 7.24 eeFuseRating !SA Nominal operating cell temperature NOC7(tl00 W/rrr AMIS,windspeedl m/s,ambient temperature fi8'F(20'Cl. ' Max Reverse Current: 15A o�ry \/ CERTIFICATION MECHANICAL DATA Spy `. .a F )Oyearproductwarranty. Dimensions 65.55x39.02x1.57in(1665x991x40mm) c (L Its 25 year linear power output warranty Area: 1775ft2(1b5mz US IMPORT EASY LL USTro (max.degression in performance of 0.7%p.a.). ) DUTVFREE INSTALL ULIi!d,Fuerating.TypeLClassC Weight: 431bs(19.Skgj Note! Al[give n specifications are subject tochange jd rout notice at any time. REC is a leading global provider of solar energy solutions. With more than 15 years of experience,we offer sustainable,high performing ^ products.services and investments for the solar industry.Together with our partners,we create value by providing solutions that better I� meet the world's growing energy needs.REC is headquartered in Norway and listed on the Oslo Stock Exchange(ticker:RECSOL).Our 1,600 employees worldwide generated revenues of USD 647 mill ion in 2013. www.recgroup.com ikkA. A1111111k ., A -4'SOIafCity Zep Solar Next-Level PV Mounting Technology II DWV Debris Guard for composition shingle roofs PHOTOVOLTAIC MODULE\ j/ DWV DEBRIS GUARD,„,,,.. ;' COMP ROOF MOUNT MOO COMP ROOF �jjjj O DWV Debris Guard Construction Detail Debris Guard,close up ���OMPq t'e�� Prevent blockages and keep vents open with the DWV Debris Guard. Protects against: • 0 . 1`.6 S- • Leaves • Rain • Pine needles • Insects • Snow • Birds DWV Debris Guard is made of rugged 26 gauge galvanized steel. zepsolar.com This document does not create any express warranty by Zep Solar or about its products or services.Zep Solar's sole warranty is contained in the written product warranty for each product.The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty.The customer is solely responsible for verifying the suitability of ZepSolar's products for each use.Specifications are subject to change without notice.Patents and Apps.zspats.com. Document#800-1677-001 Rev A Date last exported:April 3,2015 4:04 PM GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #8 GEC TO TWO (N) GROUND Panel Number: No label Inv 1: DC Ungrounded INV 1 —(1)ABB # PVT-5000-OUTD-US-Z-A LABEL: A —(23)REC g REC260PEZ OR # 180498 • RODS AT PANEL WITH IRREVERSIBLE CRIMP Meter Number:23 782 459 FCI Inverter; Zigbee 5000W, 240V, 96.5% PV Module; 260W, 236.6W PTC, MC4, 40mm, Black Frame, ZEP Enabled RGC, CGC1 Underground Service Entrance INV 2 Voc: 37.8 Vpmax: 30.7 INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER (E 200A MAIN SERVICE PANEL E3 200A/2P MAIN CIRCUIT BREAKER ADJUST MIN. ACTIVATION VOLTAGES! (E) WIRING COOPER CUTLER-HAMMER Inverter 1 IND 200A/2P Meter Socket Disconnect 0 ABB T DC. Vstart = 120V PVT-5000-OUTD-US-Z-A , I DC- / MP 1: 1x12 A �� (E) LOADS I ` ( . . B �• I 240v r — EGC J /--�-�j. • u • • 0 ■~• 1 �_ L2 •� DC. 1 1* 1� 30A/2P N —�= DC- I n Vstart = 120V - { GND} -- } cND EGC/ •� DC. C, 14 I� �� A �/ ��� GEC T N DG DG MP 1: 1x11 • O B I II GND EGC __— kGC Mi I (1)Conduit Kit; 3/4" EMT N F J_ _ I � V EGC/GEC —j z—z C, t GEC r 1 TO 120/240V I 1 SINGLE PHASE I I UTILITY SERVICE I I I I II I I I I I I I I I —L Voc* = MAX VOC AT MIN TEMP POI-(1)CUTLER-HAMMER BR230 PV BACKFEED BREAKER A -(1)COOPER 0 B—Line Meter Socket 011 �� D Breaker, 30A 2P, 2 Spaces Meter Socket; 125A, 4-14AWG, Ring Type _(2)Ground Rod; 5/8" a 8', Copper — 1)AW CAP; B—Line Meter Socket Accessory —(1)Milbank l CL200D /Itron C1 S Solid—State Single—Phase Meter; Digital B (1)CUTLER-HAMMER /DG221URB Disconnect; 30A, 240Voc, Non—Fusible, NEMA 3R —(1)CUTLER—HAMMER 4 DGO3ONB Ground/Neutrol K'it; 30A, General Duty(DC) (1)AWG #10, THWN-2, Block — _ O���(1)AWG 10, 1HWN-2, Red (2)AWG �tt0, PV Wire, 600V, Black Voc* =500.14 VDC Isc =9.01 ADC 3 / O § (1)AWG #6, Stranded Bare Copper EGC Vmp =368.4 VDC Imp=8.5 ADC (1)AWG #10, THWH-2, White NEUTRAL Vmp =240 VAC Imp=23 MC -(1)Conduit Kit; 3/4" EMT (1)AWG #8, THWN-2, Green EGC/GEC-(t)Conduit Kit;.w,EMT , . . . . (2)AWG p10, PV Wire, 600V, Block Voc* =458.46 VDC Isc =9.01 ADC O —(1)AWG #6, Stranded Bore Copper EGC Vmp =337.7 VDC Imp=8.5 ADC (1)Conduit Kit; 3/4" EMT PREMISE OWNER: DESCRIPTION: DESIGN: CONTAINEDAL A 7HE IN BE USED R HIN NUMBER: JB-9722778 00 ERNSTER, CARLA ERNSTER RESIDENCE Luke Levin ��t.COh��I}`, BEN FIT O SHALL NOT E CE USED FOR THE ��,� 1.1 NEREST LL IT ANYONE D EXCEPT IN WHOIE INC., CompSYSou: 1 31 73 BOUNEFF ST 5.98 KW PV ARRAY NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH "LIES: PORTLAND, OR 97223 THE SALE AND USE OF THE RESPECTIVE (23) REC # REC260PEZ 3055 Clearview Woy SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV. DATE: T:(650)638 Ma B F:(650)638 1029 PERMISSION of SOLARCITY INC. ABB # PVT-5000-OUTD-US-Z-A (503) 521-8577 THREE LINE DIAGRAM PV 5 6/26/2015 (888)-sot-WY(765-2489)www.solarcity.com ZS Comp Edge Zone Calculations 3 of 4 ZS Comp Edge Zone Calculations 4 of 4 Zep S o la r 3/26/15 Zep S o la r 3/26/15 Lateral Spacing Module Deflection Spacing The lateral force on the system increases as the pitch of the roof increases,but the amount of snow on the landscape module spacing=-1.4545 x Maximum Uplift or Down Force Pressure+120.7273 roof decreases for slopes greater than 30 degrees.With this in mind,the lateral force will be checked at 30 degrees with ground snow load and 45 degrees with sloped roof snow. portrait module spacing = -0.8182 x Maximum Uplift or Down Force Pressure+79.909 Allowable Lateral Load Maximum Uplift Pressure Landscape= -27.73 lateral spacing = module width x design load Maximum Uplift Pressure Portrait= -25.89 Snow Calculations Maximum Down Force Pressure= 31.91 psf Ground Snow Load= 30 psf PS=C5 Pf Roof Pitch= 31 45 'degrees landscape module spacing =-1.4545 x 31.91 psf+120.7273=74" Pf=0.7CeCtlpg Ce= 0.9 C5= 0.71 0.45 C,= 1.2 pf= 22.68 22.7 psf portrait module spacing=-0.8182 x 31.91 psf+79.909= 54" I= 1.0 p5= 16.1 10.2 psf Calculation Summary Roof Pitch Calculated Edge Zone Spacing 27 30 31 45 Spacing Check Landscape Portrait Design Snow Load 26.73 25.98 13.80 7.22 psf Uplift 87" 56" (snow load spread over the length of the rafter) Down Force 89" 53" Lateral 30° 27" 30° Lateral Force Component 74" 48" 44" Down Force Load Roof Pitch Module Deflection 74" 54" Combinations: 27 30 31 45 D+S= 13.50 14.49 8.65 7.22 psf As can be seen in the table above,for Design Wind Speeds up to 120 mph and Ground Snow Loads up to 30 D+0.75*0.6W+0.75S 10.46 11.24 _ 6.88 5.95 psf psf with modules orientated in landscape,the system is strong enough to be installed at 72"on center in the Edge Zone.When modules are installed in portrait,the spacing for edge zone installations can be 48"on Allowable Spacing for Lateral Force center for most roof pitches.For roof pitches that are greater than 27 but less than 31°,the maximum 30 degree roof pitch attachment spacing is 44". landscape lateral spacing= 39"x 14`49 psf x 144 in =74" portrait lateral spacing 2901bs in p acin _p g 65"x14.49psf x144ft2 =44" Portrait spacing is less than 48".Try roof pitch of 27 degrees portrait lateral s pacing= 290Ibs in p p g 65"x 13.50 psf x 144 ft2 =48" . ,,,,,,, ® re, 0 ,SoiarCity Zep Solar Next-Level PV Mounting Technology SolarCity Zep Soto r Next-Level PV Mounting Technology illZep System Components for composition shingle roofs ite ;° Up-roof IL r.....„,„ ,, ,07.„,, . ..... . . ...._..: Ground Zep Interlock hettiwt+ t . 11111410b, Leveltog Fuut j / 4 rr .. Zep Conp16M W Met& @fit, I;Cep Of l - 1 Root Armament Arley Sklrl i •1\ y1• ~QGOMPgT��`1n• •1q® Description `/I \ �� � W • PV mounting solution for composition shingle roofs \\ i`+ �� i.� Cprgppts0 • Works with all Zep Compatible Modules q. ��l ��r°~ l • Zep System UL 1703 Class A Fire Rating for Type 1 and Type 2 modules r • Auto bonding UL-listed hardware creates structual and electrical bond O LISTED Comp Mount Interlock Leveling Foot Part No.850-1345 Part No.850-1388 Part No 850-1397 Listed to UL 2582, Listed to UL 2703 Listed to UL 2703 Specifications Mounting Block to UL 2703 CD Designed for pitched roofs • Installs in portrait and landscape orientations � � �I • Zep System supports module wind uplift and snow load pressures to 50 psf per UL 1703 1 • Wind tunnel report to ASCE 7-05 and 7-10 standards �. %lb #11"611 • Zep System grounding products are UL listed to UL 2703 and ETL listed to UL 467 �f� kr:• Zep System bonding products are UL listed to UL 2703 `� L'i • Engineered for spans up to 72"and cantilevers up to 24" • Zep wire management products listed to UL 1565 for wire positioning devices Ground Zep Array Skirt,Grip,End Caps DC Wire Clip • Attachment method UL listed to UL 2582 for Wind Driven Rain Part No.850-1172 Part Nos.500-0113, Part No.850-1448 Listed to UL 2703 and 850-1421,850-1460, Listed UL 1565 ETL listed to UL 467 850-1467 zepsolar.com zepsolar.com Listed to UL 2703 This document does not create any express warranty by Zep Solar or about its products or services.Zep Solar's sole warranty is contained in the written product warranty for This document does not create any express warranty by Zep Solar or about its products or services.Zep Solar's sole warranty is contained in the written product warranty for each product.The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty.The customer is solely each product.The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty.The customer is solely responsible for verifying the suitability of Zep Solar's products for each use.Specifications are subject to change without notice.Patents and Apps:zspats.com. responsible for verifying the suitability of Zep Solar's products for each use.Specifications are subject to change without notice.Patents and Apps:zspats.com. 12 22 14 ZS for Comp Shingle Cutsheet Rev 02.pdf Page: 1 of 2 12 22 14 ZS for Comp Shingle Cutsheet Rev 02.pdf Page: 2 of 2 Solar inverters Additional highlights: - RS-485 communication interface ABB string inverters (for connection to laptop or data logger). PVI-5000/6000-TL-OUTD - Integrated Arc Fault Detection and Interruption(-A Version). 5kW to 6kW .,r 11111111 tt • it • an F• Technical data and types / Type code PVI-5000-OUTD-US PVI-6000-OUTD-US N „rs Input side "'°' `� Nominal output power 5000W 6000W ..r i Maximum output power ,,,,.... 5000W .........,_,..,_ 6000W Rated grid AC voltage 208V 240V 277V 208V 240V 277V Input side(DC) • Number of independent MPPT channels 2 Maximum usable power for each channel 4000W Absolute maximum voltage(Vmax) 600V ,_ _. .............. Start-up voltage(Vstart).................... ..._. 200V(ad1 1203 )..........................................................................._. Full power MPPT voltage range 200-530V Operating MPPT voltage range 0.7 x Vstart-580V Maximum current(Idcmax)for both MPPT In parallel 36A Maximum usable current 2............................................................................................... per channel... ..........._ 22A..... ............................. .... .. . Number of wire landing terminals per channel 2 Pairs Array wiring termination Terminal block,pressure clamp,AWG16-AWG6 Output side(AC) Grid connection type 10/2W Split-0/3W 10/2W 10/2W Split-0/3W 10/2W Adjustable voltage range(/min Vmax) 183V-228V 221V-264V 244V-304V 183V 228V 211V-264V 244V 304V Grid frequency 60Hz Adjustable grid frequency range 57-60.5Hz Maximum current(1...n....)A,� 27A s _ 201s. 30A,. .. 26.4... 24A. Designed for residential and small The wide input voltage range Highlights: Power factor >0.995 makes the inverter suitable to low Total harmonic distortion at rated power <2% commercial PV installations,this - Single phase and split phase output 36 25 A,/ 36 5 A,/ 5.115 Aoi "36.26A0/ 36.5 A / 3116 K Contributory fault current' inverter fills a specific niche in the power installations with reduced grid connection. 25.63ANMF 25.81A„, 22.45Aa 25 63AWM5 25.S1A�M, 22 45A Mfi__ ABB roduct line to cater for those string SIZ @. Grid wiring termination type Terminal block pressure clamp,AWG14-AWG4 P - Wide input range for increased Input installations producing between The transformerless operation offers p 9 stringing fl @xibility. Reverse polarity protection Yes 5kW and 20kW. high performance efficiencies of up t0 Over voltage protection type. Varistor 2 for each channel 97.1910. - The high speed and precise MPPT pv array ground fault detection Pre start-up Riso and Dynamic GFDI(requires floating arrays) algorithm offers real time power Output This inverter includes dual input Free remote monitoring capability p tracking and improved energy Anti islanding protection Meets UL 1741/IEEE1547 requirements Meets UL 1741/IEEE1547 requirements section to process two strings with available with every installation.This harvesting. Over-voltage protection type Varistor,2(L.-U/L -G) Varistor,2(L Lz/L-S) enables homeowners to view their Maximum AC OCPD Ratin• 35A 30A 25A 40A 35A 30A independent MPPT. - Outdoor NEMA 4X rated enclosure Efficient ` The high speed and precise MPPT energy production and offers installers g Pe p for unrestricted use under any Maximum efficiency 97.1% algorithm offers real-time power a proactive and economic way of CEC efficiency ss% 96 5% 96 5% 96% 96 5% 96 5% 9 Po environmental conditions. tracking and energy harvesting. maintaining and troubleshooting the - Integrated DC disconnect switch interface Operating pert ormance Graphic display Graphic display Flat efficiency curves ensure high system. in compliance with international Stand-by consumption <SW„M <8W„�,, efficiency at all output levels ensuring Standards(-S Version). Night time consumption <0 6w <0.6W„„v Communication consistent and stable performance — User-interface 16 characters x 2 lines LCD display across the entire input voltage and Remote monitoring(IxRS485 incl.) VSN700 Data Logger(opt) output power range. Wired local monitoring(1xRS485 incl.) PVI-USB-RS485_232(opt.) Environmental This outdoor inverter has been Ambient air operating temperature range 13°F to+140°F(-25 C to+60°C) -13°F to+140°F(-25°C to+60°C)with designed as a completely sealed unit to Berating above_122°F(50°C) • withstand the harshest environmental Ambient air storage temperature range.-, : -40°F to+176°F--- (-40-C to+80°C) -40°F to+17s_F.(40"C to+80°C) Relative humidity 0-100%RH condensing 0-100%RH condensing• conditions. Acoustic noise emission level <50 db(A) 1 m <50 db(A)®1 m I, ,� ,� Maximum operating attdutde without Berating 6560 ft(2000 nil 6560 ft(2000 m) Power and productivity 2.Inverter can apply that much current-Breaker w�X open for a better world' Pit,.,. 2 ABB Solar Invaders I Product flyer for PVI-5000/6000-TL-OUTD