SECTION 1. PRICE FAN POWERED VARIABLE VOLUME
EPIC LAND SOLUTIONS SUITE 370
einStrY SUBMITTALS
n or Year aiud�
CONTENTS
Section 1 : Fan Powered Variable
Volume
��Nnstry
u.or ro.�nriarq
Date Printed:6/5/2015
Job Name:Buckeye Pacific
All-In-One
Detailed Submittal Schedule
Terminals
q Qty I Model Inlet Dia Max Primary(CFM) I Min Primary(CFM) I Fan Flow(CFM) EC Capacity(kW) MCA I MOP V EAT(°F) LAT(°F) T Liner Steps I Sequence Acc.1 Acc.2 Acc.3
1 1 If FPV8 12 1000 400 1000 6.00 29.20 30 277-1 69.30 82.80 FG75 2 7003 HB PS FTRM31
Desc:FG75-3/4"Thick Fiberglass Liner(Standard)I 2-Number of Steps 1 7003-VAV-Intermittent tan:CP101/NO/DA Clg*electric heat I HB-Hanger Brackets(set of 4-Shipped Loose)I PS-Protective Shroud I FTRM31-1"MERV 3 Return Air Filter/Disposable)
The order and sale are made pursuant to the terms of the Sales Agreement and the Sales Policies set out in the latest Customer Service Handbook.
Q:\AIO Jobs\Mike Muhle\Buckeye Pacific.aio-projx
Page 1 of 1
Performance Notes Date Printed:6/5/2015
1. Dashes (--) indicate NC values less than 20.
2. NC values are calculated based on procedures outlined in AHRI Standard 885-2008, "A Procedure for Estimating Occupied
Space Sound Levels in the Application of Air Terminals and Air Outlets."
3. Sound power levels are given in decibels (dB).
4. "** Discharge sound power levels 2008" do not include duct end reflection. For the most current data based on ASHRAE
Standard 130-2008 and AHRI Standard 880-2011 reference "Discharge sound power levels."
5. Dashes (--) indicate sound power levels below 36-29-26-22-19-17 for each octave band; values below these sound power
levels are considered below significance per AHRI 880.
6. Minimum operating pressure is the minimum static pressure required to operate the terminal unit assembly at maximum
primary flow with a wide open damper.
7. Airflow is given in cubic feet per minute (cfm).
8. Air pressure drop is given in inches water gauge (in. w.g.), and water pressure drop is given in feet of water gauge (ft. w.g.).
9. NC values are derived from sound power levels obtained in accordance with ASHRAE Standard 130-2008 and AHRI Standard
880-2011, which include duct end reflection corrections.
10. * NC values are derived from sound power levels obtained in accordance with ASHRAE Standard 130-2008 and AHRI
Standard 880-2008.
These values are NOT the most current method for estimating NC values because AHRI 880-2008 does not include duct end
reflection corrections.
11. Terminal unit assembly is ETL certified in accordance with UL1995 and CSA 22.2.236.
Page 1 of 1
FPV8 Fan Powered, VAV - Pneumatic Controls By Price
priE Submittal Sheet
FPV8 Fan Powered Variable Volume, Pneumatic Controls by Price
L
BACKDRAFT RETURN
DAMPER K i- ---1 E AIR
`-I I
I I I
lif I
_______ ___= W
LU I _ „ PRIMARY
®DISCHARGE i F AIR
( )6"(152)I 1,- 25
SLIP k DRIVE CONNECTION 9i"(241)-SZ.6-12
11i'(292)-SZ.14-16
18'(457) MAXIMUM DOOR SWING ELECTRIC COIL
.1--- HINGED ENCLOSURE
DOOR
Dimensions- IMPERIAL UNITS (inches) Standard Motor
Unit Maximum Fan Primary Air Return Air Inlet Outlet Duct Unit Motor Full Load Amps
Size CFM Inlet D _ E B C W H L K Gauge Size H.P. 115V 208V 240V 277N,
3012 1350 12 12 151A 14 121/2 31 171/2 36 1/8 16 '/4 22 3012 1/4 4.7 0.8 0.7 1.7
Controls
MOTOR & HEATER MULTI—POINT SENSOR •• Pressure independent
CONTROLS C/W GAUGE TAPS •• Pneumatic controls are supplied and
r factory mounted by Price
irll' rr
rp • Controls mounted on left hand side of
c 3 i� , DIA.=A—k(3) E H unit
�
� I All control components utilize 20 PSI
'� t (138 KPa) clean, dry control air
BLOWER) D I--1"(25) • PS- Protective Control Cover Included
ACCESS PANEL -r--6"(152)
PROTECTIVE SHROUD • Multi-point primary airflow sensor
supplied by Price
Notes ell us
ell i CERTIFIED
• 22 Ga. zinc coated steel casing. Mechanically sealed and gasketed, leak resistant construction c y -.
• Primary damper blade constructed of two layers of heavy gauge galvanized steel with a
sandwiched peripheral gasket Intertek
• 1/2" (13)dia. plated solid steel shaft with end indicator mark showing damper position Assembly UL1995 & CSA236 listed
• Damper leakage rated below 2% of nominal flow at 3"w.g. (747Pa). Damper closing direction - Motor
CCw
•
• Units not to be used for temporary heat or ventilation during construction PSC Electric Motor 1 phase, 60
• Minimum 0.2"w.g. (50 Pa)external static pressure to operate cycle. Speed controller included
• Refer to submitted box schedule for air volumes and inlet sizes
PROJECT: Buckeye Pacific SUBMITTAL NO: 258514 SUBMITTAL DATE: 6/5/2015
ENGINEER: CUSTOMER:
DESCRIPTION: Fan Powered,VAV- Pneumatic Controls By Price
FPV8//I/7003/3012/EHP/CFM/277/1000//EC/6.0/277-1/2/IDSW//////FG75/HB/PS/FTRM31/////NO/DA/2/8-13/EHP///////////
Copyright Price Industries 2015 All metric dimensions()are soft converted.Imperial dimensions are converted to metric and rounded to the nearest millimeter.
larketinq Release version:2.15.5.2.All In One version:3.15.5 Paae 1 of 4
• FPV8 Fan Powered, VAV - Pneumatic Controls By Price
p ri pricev Submittal Sheet
Liner
FG75
3/4"Thick Fiberglass Liner(Standard)
Internal Insulation—Fiberglass 3/4" (19mm)Thick, Min.
HOUSING .�����,., 1.5# Density, which meets the requirements of NFPA90A••0.� and UL181.
i"(19)
R-value = 3.2
FIBERGLASS ,e.
INSULATION
HOUSING -
Electric Coil
-7/8"(22) B-7 7--3/4"(19) Standard Coil Notes
F -------- • Automatic reset thermal cutout • 20 Ga. galvanized steel construction
nu nuullnnnllnl 1 • Refer torsubmitted controol diagrams • Fan int
tslocked with heating
c 1111111 IIIIIIIIIIIIII M for standard control components to • Low watt density elements, high
be supplied grade nickel-chrome alloy
— — • Hinged access door • 70 CFM per kW minimum air flow
• Minimum 0.2"w.g. (50 Pa)external across heater coils
static pressure to operate • Assembly ETL certified to UL1995 &
• Slip and drive discharge connection CSA236
• Heater section not insulated • Single point electrical connection
• Magnetic contactors where required
IMPERIAL UNITS (inches)
Unit Size Outlet Duct M Electrical Configuration Selected Coil Features
BxC _
3012 14 x 12 1/2 . 15 Supply Voltage: • IDSW- Door Interlock Disconnect
• 277/10 (2 Wire) Switch
Stages/Control: 2
PROJECT: Buckeye Pacific SUBMITTAL NO: 258514 SUBMITTAL DATE: 6/5/2015
ENGINEER: CUSTOMER:
DESCRIPTION: Fan Powered, VAV-Pneumatic Controls By Price
FPV8//I/7003/3012/EHP/CFM/277/1000//EC/6.0/277-1/2/IDSW////l/FG75/HB/PS/FTRM31/Ill/NO/DA/2/8-13/EHP//I///I////
I Copyright Price Industries 2015 All metric dimensions()are soft converted.Imperial dimensions are converted to metric and rounded to the nearest millimeter.
larketino Release version:2.15.5.2.All In One version 3.15.5 Paae 2 of 4
• f, FPV8 Fan Powered, VAV - Pneumatic Controls By Price
prism Submittal Sheet
Filter
FTRM31
1" MERV 3 Return Air Filter(Disposable)
REINFORCED Unit Unit Size IMPERIAL UNITS (inches)
•�♦OvI�.♦�♦OI��♦�I��♦d�I•.♦�♦♦�.♦�♦OI MEDIA SIDE 9 W 1 -
H 1
♦ 34 ♦ ♦. ♦ 7 3
♦ 3012 14 /e 17 /e ii+4 ♦♦�I♦♦OI�♦OI♦.444M AIR ♦♦♦
4+444•44+444•444•4.0•4 H1 D ��OI�►��
�.♦ ♦♦ ♦♦ ♦♦ ♦♦ i♦ FLOW My 4? O
♦•j♦P♦4.j♦♦♦..j♦O♦�.j�0♦p+♦O4' ij♦OI�.��
♦♦i♦�♦♦i`�♦♦i`�♦♦i,��♦ei`�♦♦: `��o�' • Cardboard Frame
��►♦�. 1" {25) Nominal Filter Media
♦� , • MERV 3 Rating
Filter clipped to terminal
FILTERS ARE CLIPPED
TO TERMINAL CASING
Hanger Brackets
HB Suggested HB Locations
Image is for reference only. It may not reflect the exact arrangement of
accessories.
< 14"
(3 8/
J
\ 2"51)
TYP 2"TY5F 1
)w 2"(51) 1 (25) t9)JIIIIIP
0
s1"(13)
2 IIII*IIIIIII4Hllt
3i "(81)I 0 0 SHIPPED LOOSEJ/
ELECTRIC HEAT
• Hanger brackets are 12 Ga. zinc coated steel
• Brackets are shipped loose for field installation for use with threaded hanger rods (by others)
• Layout indicates suggested hanger bracket locations
PROJECT: Buckeye Pacific SUBMITTAL NO: 258514 SUBMITTAL DATE: 6/5/2015
ENGINEER: CUSTOMER:
DESCRIPTION: Fan Powered, VAV-Pneumatic Controls By Price
FPV8//1/7003/3012/EHP/CFM/277/1000//EC/6.0/277-1/2/IDSW//////FG75/HB/PS/FTRM31/////NO/DA/2/8-13/EHP///////////
Copyright Price Industries 2015 All metric dimensions()are soft converted.Imperial dimensions are converted to metric and rounded to the nearest millimeter,
larketina Release version:2.15.5.2.All In One version:3.15.5 Paae 3 of 4
FPV8 Fan Powered, VAV - Pneumatic Controls By Price
F rima Submittal Sheet
Control Sequence 7003
Kreuter CP101 -Variable Volume, Intermittent Fan, Pressure Independent VAV Cooling, Electric reheat, D.A. T-stat, N.O. Damper
AIR FLOW
FLOW SENSOR
HI LO
NORMALLY OPEN 5-10 PSI
DAMPER PNEUMATIC
`` ACTUATOR
GAUGE TAPS /
T
TYPE CP101
H L \ CONTROLLER
G-- . 8-13 PSI RESET
O
M j\ O
TO FAN PE SWITCH
AND ELECTRIC REHEAT COIL
�•J SEE WIRING DIAGRAM
I I
I I
DIRECT ACTING
MAIN AIR 1 OR 2 PIPE
20 PSI THERMOSTAT
(PNEUMATIC THERMOSTAT
PROVIDED BY OTHERS)
NOTES: Sequence of Operation -- Variable volume, intermittent fan, pressure
1.TOTAL AIR CONSUMPTION 0.017 SCFM. independant, normally open,direct acting cooling application with
electric reheat coil.
LEGEND An increase in space temperature increases the thermostat output pressure.
FACTORY PNEUMATIC TUBING When the thermostat output increases to 13 psi or more,the VAV box
FIELD PNEUMATIC TUBING damper is maintained at the preselected maximum flow setting.
A decrease in space temperature decreases the thermostat output pressure.
When the thermostat output decreases to 8 psi or less,the VAV box damper
CONTROL GRAPH is maintained at the preselected minimum flow setting.
Fan On At thermostat output pressures between 8& 13 psi the VAV damper
OPEN modulates between minimum&maximum cooling flow.
Reheat On Max.Cooling At thermostat output pressures below 8 psi the minimum flow setting is
i o maintained,and the thermostat will energize the unit fan to provide
recirculated air to the space. The thermostat will also control the electric
in rn in
V 7 a reheat coil.
" N Airflow is held constant at any given thermostat output pressure regardless
— Min.Cooling of changes in inlet duct static pressure.
1 1 1 . 1 CLOSE
Set Point Normally Open Damper:On failure of the main air supply the damper will
Cool Room Condition Warm fail to the open position.
PROJECT: Buckeye Pacific SUBMITTAL NO: 258514 SUBMITTAL DATE: 6/5/2015
ENGINEER: CUSTOMER:
DESCRIPTION: Fan Powered, VAV- Pneumatic Controls By Price
FPV8//1/7003/3012/EHP/CFM/277/1000//EC/6.0/277-1/2/IDSW//////FG75/HB/PS/FTRM31/////NO/DA/2/8-13/EHP///l///////
Copyright Price Industries 2015 All metric dimensions h are soft converted.Imperial dimensions are converted to metric and rounded to the nearest millimeter
larketino Release version:2.15.5.2.All In One version:3.15.5 Pace 4 of 4