Centurion Fire Protection, LLC
PO Box 1705; Oregon City, Oregon 97045
PHONE (503)894-0563 CCB#204812
(4\1 1210
Providence Suite 100 Remodel
12442 SW Scholls Ferry Road
Tigard, Oregon
FIRE PROTECTION
EQUIPMENT SUBMITTAL
•
Providence Suite 100 Remodel
12442 SW Scholls Ferry Road
Tigard, Oregon
FIRE PROTECTION EQUIPMENT SUBMITTAL INDEX
PRODUCT MAKE MODEL/ DESCRIPTION
1. SPRINKLERS TYCO Series TY-FRB Quick Response SSP
SIMILAR - SIN #TY3231
MATCH EXISTING Chrome w/Chrome Recessed Esc
2. PIPE BULLMOOSE TUBE Black Steel, Eddythread40, ASTM A795/A135
3. FITTINGS SMITH COOPER Cast Iron, Threaded, ASTM A126
SMITH COOPER Ductile Iron, Threaded, ASTM A536
**The above listed items are the proposed equipment to be used on this project, however we reserve the right
to use an 'equivalent' product or manufacturer at our discretion.
Centurion Fire Protection, LLC
PO Box 1705; Oregon City, Oregon 97045
PHONE (503)894-0563 CCB#204812
ENiLR!O\
Fn�
Chipotle T.I.
6198 Ulali Drive NE
Keizer, Oregon
FIRE PROTECTION
EQUIPMENT SUBMITTAL
tilcaWorldwide www t co-fire.com
Fire Protection Contacts y
Products
Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General spheres.Although corrosion-resistant
coated sprinklers have passed the -.
Descri ton standard corrosion tests of the appli -- °"+^°�°°`+ "
p cable approval agencies,the testing is
The TYCO Series TY-FRB, 2.8, 4.2, not representative of all possible cor- i
5.6, and 8.0 K-factor, Upright, Pen- rosive atmospheres. Consequently, :*
dent, and Recessed Pendent Sprin- it is recommended that the end user
klers described in this data sheet are be consulted with respect to the suit- t-' ,
quick response, standard coverage, ability of these coatings for any given = "'lit
decorative 3 mm glass bulb-type spray corrosive environment. The effects of - •
sprinklers designed for use in light or ambient temperature,concentration of _
ordinary hazard,commercial occupan- chemicals,and gas/chemical velocity,
cies such as banks, hotels,and shop- should be considered, as a minimum,
ping malls. along with the corrosive nature of the
chemical to which the sprinklers will be
The recessed version of the Series TY- exposed. I IN
FRB Pendent Sprinkler,where applica-
ble, is intended for use in areas with a An intermediate level of the Series TY-
finished ceiling.This recessed pendent FRB Pendent Sprinklers is detailed — -" ` .
sprinkler uses one of the following: in Technical Data Sheet TFP356, and E
Sprinkler Guards are detailed in Tech- j
• A two-piece Style 10 (1/2 inch NPT) nical Data Sheet TFP780.
or Style 40(3/4 inch NPT) Recessed
Escutcheon with 1/2 inch(12,7 mm)of
recessed adjustment or up to 3/4 inch NOTICE
(19,1 mm)of total adjustment from the The Series TY-FRB, 2.8, 4.2, 5.6, '4,
flush pendent position,or a and 8.0 K-factor, Upright, Pendent,
and Recessed Pendent Sprinklers
• A two-piece Style 20 (1/2 inch NP -1 described herein must be installed
or Style 30(3/4 inch NPT) Recessed and maintained in compliance with Sprinkler
Escutcheon with 1/4 inch(6,4 mm)of this document and with the applica-
recessed p
adjustment or up to 1/2 inch ble standards of the National Fire Pro- Identification
(12,7 mm)of total adjustment from the tection Association, in addition to the
flush pendent position. standards of any authorities having Number (SIN)
The adjustment provided by the jurisdiction. Failure to do so may impair
Recessed Escutcheon reduces the the performance of these devices. TY1131: Upright 2.8K, 1/2"NPT
accuracy to which the fixed pipe drops The owner is responsible for maintain- TY1231: Pendent 2.8K, 1/2"NPT
to the sprinklers must be cut. ing their fire protection system and TY2131: Upright 4.2K, 1/2"NPT
Corrosion-resistant coatings, where devices in proper operating condition. TY2231: Pendent 4.2K, 1/2"NPT
applicable, are utilized to extend the The installing contractor or sprinkler TY3131: Upright 5.6K, 1/2"NPT
life of copper alloy sprinklers beyond manufacturer should be contacted with TY3231: Pendent 5.6K,1/2"NPT
that which would otherwise be obtained any questions. TY4131: Upright 8.0K,3/4"NPT
when exposed to corrosive atmo- TY4231: Pendent 8.0K,3/4"NPT
TY4831: Upright 8.0K, 1/2"NPT
TY4931: Pendent 8.0K, 1/2"NPT
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING"that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 OCTOBER 2013 TFP171
• TFP171
Page 2 of 10
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE 7 - Bushing
�\ ¢ 1
7/16" ��M ;� 3
011 (11,1 mm) ,, _ .
NOM9ivm
2-1I/4" �
■ r i__■
(57,2 mm)� " 1
4
i (55,6 mm) 1-9/16"
(39,7 mm) 1 :/// !�' 5
``, /vorrw‘k. 1 i / / Orr% \ .s--%10-- g*
1/2" NPT** f WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. -----
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
y 1
GLVr/r_'_�_�. 1 i
o r
_____
___
_____
___
0114 7/16" ��1', �r 3
(11,1 mm) % } ���� i 2
NOMINAL I (5 6 mm)
MAKE IN 1
�r 2 3/16" 1-1/2" 4
(55,6 mm)
(38,1 mm) 5
i
\ ** ( 2-7/8"(73,0 mm)DIA. -
1/2" NPT** WRENCH STYLE 10 or 20 *
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
• TFP1T1
Page 3 of 10
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw
Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector*
PLATE SEATING
SURFACE
r//1°1iiii _ 1
7/16" 7--m 3 0114 (11,1 mm) � .��- y A T
NOMINAL A ��
MAKE IN ! 2-3/16"
Vim,, �� 2
l 2-3i/16 (55,6 mm)
• 1_ (55,6 mm) l
1-1/2" j I 4
(38,1 mm) I, 5
6*
1/2" NPT** f WRENCH STYLE 10 or 20 —.---2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE.._______
ti's-r————, �c?� y 1 1 / , ..,, ■■■
1/2"
____
_____________
______
(12,7 mm) . �f� 3
NOMINAL m A� 4AA�
(52-1/mm) 1-9/16" 4
(39,7 mm)
NPT** STYLE 30 or 40 6*
3/4" NPT WRENCH
FLATS RECESSED 2-7/8"(73,0 mm)DIA.
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS
8.0 K-FACTOR,3/4 INCH NPT
4 TFP171
Page 4 of 10
CEILING PLATE 1 - Frame 5 - Compression
SEATING SURFACE 2 - Button Screw
1 3 - Sealing 6 - Deflector
er-' Mi=,ny - $ t Assembly
3 4 - Bulb
7/16"
�— 21/4" 0
(11,1 mm) ro A
NOMINAL } (57,2 mm) I� 4 2
— I I r r * Temperature rating is
MAKE-IN I
2-3/16" 1-9/16" 4 indicated on Deflector.
(55,6 mm) , i (39,7 mm)
II ��!r�—5 ** Pipe thread connections
} ' -�+; v per ISO 7-1 can be
f _ --° 6 * provided on special
1/2" NPT** WRENCH request.
FLATS
UPRIGHT PENDENT CROSS SECTION
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical Design torque can distort the sprinkler Inlet
with consequent leakage or impairment
Data Criteria of the sprinkler.
The TYCO Series TY-FRB, 2.8, 4.2, Do not attempt to compensate for
Approvals insufficient adjustment in the Escutch-
UL and C-UL Listed 5.6, and 8.0 K-factor, Upright, Pen- eon Plate by under-or over-tightening
FM, LPCB, and NYC Approved dent,and Recessed Pendent Sprinklers the sprinkler. Re-adjust the position of
Refer to Table A and B for complete are intended for fire protection sys- the sprinkler fitting to suit.
approval information including tems designed in accordance with the
corrosion-resistant status. standard installation rules recognized Series TY-FRB Upright and Pendent
by the applicable Listing or Approval Sprinklers
Maximum Working Pressure agency (such as, UL Listing is based The Series TY-FRB Pendent and
Refer to Table C. on the requirements of NFPA 13, and Upright Sprinklers must be installed
FM Approval is based on the require- in accordance with the following
Discharge Coefficient ments of FM's Loss Prevention Data instructions.
K=2.8 GPM/psi1/2 (40,3 LPM/bar112) Sheets). Only the Style 10, 20, 30, or
Step 1.Install Pendent sprinklers in the
K=4.2 GPM/psi1I2 (60,5 LPM/bar112) 40 Recessed Escutcheon, as applica pendent position. Install upright sprin-
K=5.6 GPM/psi1I2 (80,6 LPM/bar112) ble,is to be used for recessed pendent
K=8.0 GPM/psi112 (115,2 LPM/bar1/2) installations. klers in the upright position.
Step 2. With pipe-thread sealant
Temperature Rating Installation applied to the pipe threads, hand-
Refer to Table A and B. tighten the sprinkler into the sprinkler
The TYCO Series TY-FRB, 2.8, 4.2, fitting.
Finishes 5.6,and 8.0 K-factor,Upright,Pendent,
Sprinkler: Refer to Table D. Recessed and Recessed Pendent Sprinklersmust Step 3.Tighten the sprinkler into the
Escutcheon:White Coated, Chrome be installed in accordance with this sprinkler fitting using only the W-Type 6
Plated, or Brass Plated. section. Sprinkler Wrench(Figure 14).With refer-
ence to Figures 1 through 5,apply the
Physical Characteristics General Instructions W-Type 6 Sprinkler Wrench to the sprin-
Frame Bronze Do not install any bulb-type sprinkler if kler wrench flats.
Button Brass/Copper the bulb is cracked or there is a loss
Sealing Assembly Beryllium of liquid from the bulb. With the sprin- Series TY-FRB Recessed Pendent
Nickel w/TEFLON kler held horizontally, a small air bub- Sprinklers
Bulb Glass ble should be present. The diameter The Series TY-FRB Recessed Pendent
Compression Screw Bronze of the air bubble is approximately 1/16 Sprinklers must be installed in accor-
Deflector Copper/Bronze inch(1,6 mm)for the 135°F(57°C)and dance with the following instructions.
Bushing(K=2.8) Bronze 3/32 inch(2,4 mm)for the 286°F(141°C) Step A.After installing the Style 10,20,
Operation temperature ratings. 30, or 40 Mounting Plate, as applica-
A leak tight 1/2 inch NPT sprinkler joint ble,over the sprinkler threads and with
The glass bulb contains a fluid that shold be obtained by applying a min- pipe-thread sealant applied to the pipe
expands when exposed to heat.When imum to maximum torque of 7 to 14 threads, hand-tighten the sprinkler into
the rated temperature is reached, the ft.-lbs. (9,5 to 19,0 Nm). A leak tight the sprinkler fitting.
fluid expands sufficiently to shatter the 3/4 inch NPT sprinkler joint should be Step B.Tighten the sprinkler into the
glass bulb, allowing the sprinkler to obtained with a torque of 10 to 20 ft.- sprinkler fitting using only the W-Type
activate and water to flow. lbs. (13,4 to 26,8 Nm). Higher levels of 7 Recessed Sprinkler Wrench (Figure
TFP171
Page 5 of 10
SPRINKLER FINISH(See Note 5)
K BULB LIQUID NATURAL CHROME SIGNAL***
FACTOR TYPE TEMPERATURE COLOR BRASS PLATED WHITE
135°F(57°C) Orange
PENDENT 155`F(68°C) Red
(TY1231)
and 175°F(79°C) Yellow 1.2.3,4
UPRIGHT
(TY1131) 200°F(93°C) Green
286°F(141°C) Blue
135'F(57°C) Orange
2.8 RECESSED 1
1/2"NPT PENDENT 55°F(68°C) Red
(TY1231)* 175°F(79°C) Yellow
Figure 6
200'F(93°C) Green
1,2,4
135°F(57°C) Orange
RECESSED
PENDENT 155°F(68°C) Red
(TY1231)** 175°F(79°C) Yellow
Figure 7
200°F(93°C) Green
135°F(57°C) Orange
PENDENT 155°F(68°C) Red
(TY2231)
and 175°F(79°C) Yellow
UPRIGHT °
°
200 F 93 C
(TY2131) ( ) Green
286°F(141°C) Blue
135°F(57°C) Orange
4.2 RECESSED
1/2"NPT PENDENT 155°F(68°C) Red 1,2
(TY2231)* 175°F(79°C) Yellow
Figure 8
200°F(93°C) Green
135°F(57°C) Orange
RECESSED
PENDENT 155°F(68°C) Red
(TY2231)** 175°F(79°C) Yellow
Figure 9
200°F(93°C) Green
NOTES:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed
as Corrosion-Resistant Sprinklers.
Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
**Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT) 1/2"Total Adjustment Recessed Escutcheon,as applicable.
***Frame and Deflector only. Listings and approvals apply to color(Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
2.8 AND 4.2 K-FACTOR SPRINKLERS
15). With reference to Figures 1 to 4,
apply the W-Type 7 Recessed Sprinkler
Wrench to the sprinkler wrench flats.
Step C. After ceiling installation and
finishing, slide on the Style 10, 20, 30,
or 40 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFP171
Page 6 of 10
SPRINKLER FINISH(See Note 8)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME SIGNAL*** LEAD
FACTOR COLOR BRASS PLATED WHITE COATED
135°F(57°C) Orange
PENDENT
(TY3231) 155°F(68°C) Red
and 175°F(79°C) Yellow 1 2. 1 4. 5.6. 7 1,2,3. 5
UPRIGHT 200°F(93°C) Green
(TY3131)
286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 N/A
1/2"NPT (TY3231)*
Figure 10 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
PENDENT 175°F(79°C) Yellow 1,2,3,4,5 N/A
(TY3231)
Figure 11 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
(TY4D231) 155°F(68°C) Red
and 175°F(79°C) Yellow 1.2,3.4.5.6. 7 1,2.5
UPRIGHT 200°F(93°C) Green
(TY4131) 286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
8.0 PENDENT 175°F(79°C) Yellow 1,2,5 N/A
3/4"NPT (TY4231)*
Figure 12 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
PENDENT 175°F(79°C) Yellow 1,2,3,5 N/A
(TY4231)**
Figure 13 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
PENDENT 155°F(68°C) Red
8.0
(TY4931)
1/2"NPT and 175°F(79°C) Yellow 1,2,4,5,6 1,2,5
UPRIGHT 200°F(93°C) Green
(TY4831) 286°F(141°C) Blue
NOTES:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate
the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax
31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed
as Corrosion-Resistant Sprinklers.Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved
as a Corrosion-Resistant Sprinklers.
Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable.
*"Frame and Deflector only. Listings and approvals apply to color(Special Order).
N/A:Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFP171
Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME SIGNAL LEAD
FACTOR BRASS PLATED WHITE COATED
PENDENT(TY1231)
and
2.8 UPRIGHT(TY1131)
1/2"NPT 175 PSI(12,1 BAR) N/A
RECESSED
PENDENT(TY1231)
PENDENT(TY2231)
and
4.2 UPRIGHT(TY2131)
1/2"NPT 175 PSI (12,1 BAR) N/A
RECESSED
PENDENT(TY2231)
PENDENT(TY3231) 175 PSI
and (12,1 BAR)
5.6 UPRIGHT(TY3131) OR 250 SI(1(12,1BBAR) -- BAR)NPT (SEE NOTE 1)
RECESSED N/A
PENDENT(TY3231)
PENDENT(TY4231) 175 PSI
and (12,1 BAR)
8.0 UPRIGHT(TY4131) 175 PSI(12,1 BAR)
3/4"NPT
RECESSED N/A
PENDENT(TY4231)
8 p PENDENT(TY4931) 175 PSI
1/2"NPT and 175 PSI(12,1 BAR) (12,1 BAR)
UPRIGHT(TY4831)
NOTES:
1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the
Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York.
TABLE C
MAXIMUM WORKING PRESSURE
Care and corrosive products of combustion, but tion Service in accordance with local
have not operated, should be replaced requirements and/or national codes.
if they cannot be completely cleaned
Maintenance by wiping the sprinkler with a cloth or Care must be exercised to avoid dam-
The TYCO Series TY-FRB must be by brushing it with a soft bristle brush. age to the sprinklers -before, during,
and after installation. Sprinklers dam-
maintained and serviced in accordance
Care must be exercised to avoid dam- aged by dropping, striking, wrench
with this section. age to the sprinklers - before, during, twist/slippage, or the like, must be
Before closing a fire protection system and after installation. Sprinklers dam- replaced. Also, replace any sprinkler
main control valve for maintenance aged by dropping, striking, wrench that has a cracked bulb or that has lost
work on the fire protection system twist/slippage, or the like, must be liquid from its bulb. (Ref. Installation
that it controls, obtain permission to replaced. Also, replace any sprinkler Section).
shut down the affected fire protection that has a cracked bulb or that has lost
systems from the proper authorities liquid from its bulb. (Ref. Installation Initial and frequent visual inspections of
and notify all personnel who may be Section.) random samples are recommended for
affected by this action. corrosion-resistant sprinklers to verify
Y The owner is responsible for the the integrity of the corrosion-resistant
Absence of the outer piece of an inspection,testing, and maintenance of material of construction. Thereafter,
escutcheon, which is used to cover their fire protection system and devices annual inspections per NFPA 25 should
a clearance hole, can delay sprinkler in compliance with this document, as suffice.
operation in a fire situation. well as with the applicable standards
of the National Fire Protection Associa- Inspections of corrosion-resistant
Sprinklers which are found to be leak- tion (e.g., NFPA 25), in addition to the sprinklers are recommended at close
ing or exhibiting visible signs of corro- standards of any other authorities hav- range, instead of from the floor level
sion must be replaced. ing jurisdiction. Contact the installing per NFPA. Inspection at close range
Automatic sprinklers must never be contractor or sprinkler manufacturer can better determine the exact sprin
painted, plated, coated, or other- regarding any questions. kler condition and the long-term integ
wise altered after leaving the factory. rity of the corrosion-resistant material,
9 Y Automatic sprinkler systems are rec- which can be affected by the corrosive
Modified sprinklers must be replaced. ommended to be inspected, tested, conditions present.
Sprinklers that have been exposed to and maintained by a qualified Inspec-
TFP171
Page 8 of 10
2-7/8" DIA. _ 2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm)
1/2±1/8` 1/2"(12,7 mm)
(15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm)
, 2-1/4" DIA. 2-1/4" DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm) MOUNTING ( FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
I 1/8" I 1/8'
(3,2 mm) ' 1 I i (3,2 mm)
T�A / Ara,i ? MOUNTING MOUNTING � 1 SURFACE lip
SURFACE -� I '
/
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)I
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 6 FIGURE 7
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT
2-7/8"DIA. _ _ 2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) i 1/4'(6,4 mm) (12,7±3,2 mm) 1/4" 6,4 mm
2-1/4" DIA. _� 2-1/4"DIA. _� ( )
/ FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
/ 1/8" 1/8"
(3,2 mm) / (3,2 mm)it
lj..:7/;\ ,,, MOUNTING 10 t
MOUNTING SURFACE
SURFACE 1 .. ■ ..
CLOSURE SERIES 1-1/4"(31,8 mm)I CLOSURE SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 8 FIGURE 9
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT
TFP171
Page 9 of 10
2-7/8"DIA. _ _ 2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 1/4"(6,4 mm
2-1/4"DIA. 2-1/4" DIA. ( mm)
FACE OF (57,2 mm) 1 MOUNTING / FACE OF (57,2 mm)
SPRINKLER I MOUNTING
PLATE SPRINKLER PLATE
FITTING FITTING
I 1/8" / 1/8"
(3,2 mm) (3,2 mm)
i G1 fj Z-7 it I1771-
�� -� /
�\ / ,,, ` MOUNTING IN
MOUNTING SURFACE `y� ;
SURFACE/ ---,M.,..-- /
CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE/
SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT
2-7/8"DIA. 2-7/8" DIA.
5/8±1/4" (73,0 mm) ~' 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) - 1/2"(12,7 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm)
/ FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
/ (3,2 mm) / (3,2 mm)
` r a__ — ■ P77'
1 �% ! `
l' [-- 511�Tir MOUNTING 1iIh1�
MOUNTING SURFACE
SURFACE � 1
/
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 12 FIGURE 13
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR,3/4 INCH NPT 8.0 K-FACTOR, 3/4 INCH NPT
W113 WRENCH
RECESS
ENCH RECESS
(END"A"USED FOR / ��
1/2" NPT MODELS)
4 4
WRENCH RECESS
(END"B" USED FOR le.....,
3/4"NPT MODELS) PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14 FIGURE 15
W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED
WRENCH SPRINKLER WRENCH
TFP171
Page 10 of 10
P/N 57 - XXX - X - XXX
I �
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C)
331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 155 155°F(68°C)
(RAL9010)*
340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F(79°C)
(RAL9003)
341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK 200 200°F(93°C)
(RAL9005)"
370 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C)
371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED
390 8.0K UPRIGHT(3/4"NPT) TY4131 •Eastern Hemisphere sales only.
**Available in only 2.8K,4.2K,and
391 8.0K PENDENT(3/4"NPT) TY4231 8.0K,155°F(68°C)and 200°F(93°C);
requires lead time to manufacture.
360 8.0K UPRIGHT(1/2"NPT) TY4831*
361 8.0K PENDENT(1/2"NPT) TY4931*
TABLE D
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB (Specify SIN),
(specify K-factor), (specify Pendent or
Upright) Sprinkler (specify) tempera-
ture rating, (specify) finish or coating,
P/N (specify from Table D)
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*)
finish, P/N (specify*)
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
*Refer to Technical Data Sheet TFP770
GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
Copyright®2013 Tyco Fire Products,LP. All rights reserved. t"l Co
TEFLON is trademark of The DuPont Corporation. Fire Protection Products
Eddyth read 40
A Lightweight Schedule 40 Replacement Pipe
That Has a Corrosion Resistance Ratio of 1.0
Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe
products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our
customers have an option to buy a carefully designed replacement for Schedule 40 that:
• Has a Corrosion Resistance Ratio of 1.0
• Has a Pressure Rating of 300 psi
• Is Lighter Weight Than Schedule 40
• Is Approved by Factory Mutual and Listed by Underwriters Laboratories
• Is Produced in Accordance to ASTM A-135 and A-795
• Can be Used With Standard Schedule 40 Threaded Fittings,
Couplings and Valves
• Is Produced From Steel With Excellent Properties of
Strength and Threadability
• Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems*
• Offers Lower Freight Costs
EDDYTHREAD 40 SPECIFICATIONS
NOMINAL PIPE SIZE (in) WEIGHT(lbslft) I.D. (in) BUNDLE SIZE
1 1.461 1.083 70
1 1/4 2.070 1.418 51
1 1/2 2.547 1.654 44
2 3.308 2.123 30
CORROSION RESISTANCE RATIOS
NOMINAL PIPE SIZE (in) SCHEDULE 40 EDDYTHREAD 40
1 1.00 1.00
1 1/4 1.00 1.00
1 1/2 1.00 1.00
2 1.00 1.00
'Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems
1819 Clarkson Road For additional information, u
Chesterfield,MO 63017 contact your salesperson today at C .L us Apo
V T� COMPANY 325-4467 (800)325-4467 or(636)537-2600 LISTED -
FAX:(636)537-2645 in the USA,or from Canada
www.bullmoosetube.com call(800)882-4666 41>
A C A o company e-maitsales @bullmoosetube.com
APPROVED
All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation.
8/08
Cast Iron Threaded Fittiings
.. r
INTERNAT. I0 . N AL
Cast Iron Threaded Fittings
Specifications
• branded cast iron threaded fittings are UL Listed and FM Approved at 300psi
• Rated to 125# WSP
• Casting date on each fitting C 01 US
• Grey iron castings conform to ASTM A126 LISTED
• Cast iron fitting dimensions conform to ASME B16.4 Class 125
• NPT threads on fittings conform to ASME B1.20.1
APPROVED
• Cast iron fittings have SCI Trademark and are 100% air tested
• Manufacturing facility is ISO 9001:2008 and ISO 14001
• k i ''. Cast Iron Fittings - Class 125 UL/FM
I tufurrr i-I,u:;
c ® US
APPROVED
Fig. 37E 1 - 90°Elbow LISTED
A Size Part Number A Packing Weight
IN IN Inner Master LB
i
1/2 37E 1004 1.13 90 180 0.3
- ---r- 3/4_ 37E 1006 1.31 50 100 0.5
A � 1 37E 1010 1.50 35 70 0.8
11■■I -1/4 37E 1012 1.75 20 40 1.3
1-1/2 37E 1014 1.94 15 30 1.7
4', ``.' 37E 1020 2.25 7 14 2.7
2-1/2 37E 1024 2.70 4 8 4.3
Fig. 37RE1 - 90°Reducing Elbow
Size A B Packing Weight
,i IN Part Number IN IN Inner Master LB
1 x 1/2 37RE1010004 1.36 1.26 50 100 0.5
I _ 1 x 314 37RE1010006 1.45 1.38 40 80 0.7
1-1/4 x 1/2 37RE1012004 1.34 32 64 0.8
B 1-114 x 3/4 37RE1012006 1.63 1.45 28 56 0.9 1-1/4 x 1 37RE1012010 1.67 1.58 25 50 1.0
1-1/2 x 1/2 37RE1014004 1.75 1.52 25 50 1.0
1-1/2 x 3/4 37RE1014006 1.75 1.52 20 40 1.1
1-1/2 x 1 37RE1014010 1.80 *1,65 18 36 1.3
1-1/2 x 1-1/4 37RE1014012 1.88 1.82 14 28 1.5
2 x 1/2 37RE1020004 1.97 1.60 1 15 30 1.4
2 x 3/4 37RE1020006 1.97 1.60 15 30 1.6
2 x 1 37RE1020010 2.02 1.73 12 24 1.8
2 x 1-1/2 37RE1020014 2.16 2.02 10 20 2.3
Fig. 37F 1-45°Elbow
Size A Packing Weight
Part Number
IN IN Inner Master LB
til 1 37F 1010 1.26 40 80 0.7
41-1/4 37F 1012 1.29 22 44 1.2
A 1 112 37F 1014 1.44 16 32 1.5
IRMA 2 37F 1020 1.69 8 16 2.6
C Fig. 3771 - Tee
Size A Packing Weight
p Part Number
IN IN Inner Master LB
s jail' 1 A 1/2 37T 1004 1.13 60 120 0.4
T - 3/4 37T 1006 1.31 30 60 ® 0.7
1 1 37T 1010 1.50 20 40 1.1
I�. 1 1-1/4 37T 1012 1.75 12 24 1.8
(; u� y... 1-1/2 37T 1014 1.94 8 16 2.4
0 A A 2 37T 1020 2.25 5 10 3.8
N
Fig. 37RC1 -Hex Coupling
iltSize Part Number A Packing Weight
IliwiIN IN Inner Master LB
1 x 1/2 37RC1010004 1.69 60 120 0.5
A 1 x 3/4 37RC1010006 1.69 50 100 0.6
2 x 1 (not hex) 37RC1020010 2.81 16 32 1 1.5
l
I V
97 SMITH-COOPER INTERNATIONAL" • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www:smithcooper.com
• :_; 'j Cast Iron Fittings- Class 125 UL/FM
j ri Lrrf L ':u U
CGli) US 41110111/".
APPROVED
Fig. 37RT1 -Reducing Tee LISTED
Size Part Number A B _ Packing Weight
M' IN IN IN IN Inner Master LB•
C 1 x 1/2 37811010004 1.26 1.26 1.36 25 50 0.9
J 1 x 1/2 x 1 37R11010004010 1.50 1.36 1.50 24 48 0.9
1 x 3/4 37811010006 1.38 1.38 1.45 22 44 1.0
1 x 3/4 x 1 37RT1010006010 1.50 1.45 1.50 20 40 1.0
( )(-) 1 x 1-1/4 37RT1010012 1.67 1.67 1.58 15 30 1.4
B A 1-1/4 x 1/2 37R11012004 1.34 1.34 1.53 18 36 1.3
1-1/4 x 1/2 x 1-1/4 37RT1012004012 1.75 1.53 1.75 18 36 1.4
1-1/4 x 3/4 37RT1012006 1.45 1.45 1.62 15 30 1.4
1-1/4 x 3/4 x 1-1/4 37R11012006012 1.75 1.62 1.75 15 30 1.5
1-1/4 x 1 37RT1012010 1.58 1.58 1.67 15 30 1.6
1-1/4 x 1 x 1/2 37811012010004 1.34 1.26 1.53 20 40 1.1
1-1/4 x 1 x 3/4 37RT1012010006 1.45 1.38 1.63 16 32 1.2
1-1/4 x 1 x 1 37RT1012010010 1.58 1.50 1.69 15 30 1.4
1-1/4 x 1 x 1-1/4 37RT1012010012 1.75 1.69 1.75 12 24 1.6
1-1/4 x 1 x 1-1/2 37811012010014 1.88 1.80 1.82 12 24 1.8
1-1/4 x 1-1/2 37RT1012014 1.88 1.88 1.82 10 20 2.0
1-1/2 x 1/2 37RT1014004 1.41 1.41 1.66 12 24 1.6
1-1/2 x 1/2 x 1-1/4 37RT1014004012 1.81 1.56 1.88 12 24 1.7
1-1/2 x 1/2 x 1-1/2 37RT1014004014 1.94 1.66 1.94 12 24 1.8
1-1/2 x 3/4 37RT1014006 1.52 1.52 1.75 112 24 1.8
1-1/2 x 3/4 x 1-1/4 37R11014006012 1.94 1.66 1.88 12 24 1.7
1-1/2 x 3/4 x 1-1/2 37RT1014006014 1.94 1.75 1.94 -12 ;: 24 1.9
1-1/2 x 1 37811014010 1.65 1.65 1.80 10 20 1.9
1-1/2 x 1 x 1/2 37RT1014010004 1.44 1.25 1.69 18 36 1.3
1-1/2 x 1 x 3/4 37R11014010006 1.50 1 44 1.75 15 30 1.4
1-1/2 x 1 x 1 37RT1014010010 1.65 1.50 1.80 112 24 1.6
1-1/2 x 1 x 1-1/4 37RT1014010012 1.82 1.67 1.88 10 20 1.8
1-1/2 x 1 x 1-1/2 37RT1014010014 1.94 1.80 1.94 8 16 2.1
1-1/2 x 1-1/4 37811014012 1.82 1.82 1.88 8 16 2.2
1-1/2 x 1-1/4 x 1/2 37R11014012004 1.41 1.34 1.66 15 30 1.5
1-1/2 x 1-1/4 x 3/4 37811014012006 1.52 1.45 1.75 12 24 1.6
1-1/2 x 1-1/4 x 1 37RT1014012010 1.65 1.58 1.80 12 24 1.8
1-1/2 x 1-1/4 x 1-1/4 37RT1014012012 1.82 1.75 1.88 10 20 2.1
1-1/2 x 1-1/4 x 1-1/2 37RT1014012014 1.94 1.88 1.94 8 16 2.3
1-1/2 x 1-1/4 x 2 37RT1014012020 2.16 2.10 2.02 6 12 2.7
1-1/2 x 2 37RT1014020 2.16 2.16 2.02 5 10 2.9
2 x 1/2 37RT1020004 1.49 1.49 1.88 8 16 2.6
2 x 3/4 37RT1020006 1.60 1.60 1.97 8 16 2.6 C
2 x 1 37811020010 1.73 1.73 2.02 6 12 2.9 A
2 x 1 x 2 37RT1 020010020 2.25 2.02 2.25 5 10 3.1 s
2 x 1-1/4 37RT1020012 1.90 1.90 2.10 5 10 3.2 T
2 x 1-1/4 x 2 37RT1020012020 2.25 2.10 2.25 5 10 3.2
2 x 1-1/2 37811020014 2.02 2.02 2.16 5 10 3.3 I
2 x 1-1/2 x 1/2 37RT1020014004 1.49 1.41 1.88 8 16 2.1 R
2 x 1-1/2 x 3/4 37811020014006 1.60 1.52 1.97 8 16 2.2
2 x 1-1/2 x 1 37RT1020014010 1.73 1.65 2.02 8 16 2.4 0
2 x 1-1/2 x 1-1/4 37R11020014012 1.90 1.82 2.10 7 14 2.7 N
2 x 1-1/2 x 1-1/2 37RT1020014014 2.02 1.94 2.16 NE 14 2.9
2 x 1-1/2 x 2 37RT1020014020 2.25 2.16 2.25 5 10 3.4
2 x 2-1/2 37RT1020024 2.60 2.60 2.39 3 6 4.6
SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 98
Ductile Iron Threaded Fittings
{
ar �
+^may
'jiff ,
d o
fr
1/1/1/1"
s
1