Report RECEivEi
Date: May 21, 2015 JUN 3 0 2 015 00 ssoeT r;�
Sophia Yun CIT y SSOE Group
Crown Castle OF TIGAHp 320 Seven Springs Way, Suite 220
12725 Morris Road Extension, Suite 400 UILDING DIM!' Brentwood, TN 37027
Alpharetta, GA 30004 (615) 661-7585
(678) 259-2254 jshaikh @ssoe.com
Subject: Structural Analysis Report
Carrier Designation: T-Mobile Co-Locate
Carrier Site Number: P001373B
Carrier Site Name: Greenburg
Crown Castle Designation: Crown Castle BU Number: 824338
Crown Castle Site Name: Greenburg
Crown Castle JDE Job Number: 334334
Crown Castle Work Order Number: 1062031
Crown Castle Application Number: 290281 Rev. 1
Engineering Firm Designation: SSOE Group Project Number: 015-00428-00 BC 0733
Site Data: 11744 SW Pacific Hwy, Tigard, OR 97223, Washington County
Latitude 45°26'6.17", Longitude -122° 45'33.14"
130 Foot—Valmont Monopole Tower
Dear Ms. Sophia Yun,
SSOE Group is pleased to submit this "Structural Analysis Report" to determine the structural integrity of the
above mentioned tower. This analysis has been performed in accordance with the Crown Castle Structural
`Statement of Work' and the terms of Crown Castle Purchase Order Number 788263, in accordance with
application 290281, revision 1.
The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we
have determined the tower stress level for the structure and foundation, under the following load case, to be:
LC5: Existing + Proposed Equipment Sufficient Capacity
Note:See Table I and Table II for the proposed and existing/reserved loading.respectively.
The analysis has been performed in accordance with the 2014 Oregon Structural Specialty Code based upon an
ultimate 3-second gust wind speed of 110 mph converted to a nominal 3-second gust wind speed of 85 mph per
section 1609.3.1 as required for use in the TIA-222-G Standard per Exception #5 of Section 1609.1.1. Exposure
Category C and Risk Category II were used in this analysis
We at SSOE Group appreciate the opportunity of providing our continuing professional services to you and
Crown Castle. If you have any questions or need further assistance on this or any other projects please give us
a call.
Structural analysis prepared by: Junaid I. Shaikh
,�p. •z
Respectfully submitted by: ,, OFF•P,c) # GINE /0
/41,\4.
80746
OREGON ,s,
Sean B. Smith, SE
Department Manager 1`s eH 1� � 5 1115
... tiC
tnxTower Report-version 6.1.4.1 'c1A/ 8 5�
May 21, 2015
130 Ft Monopole Tower Structural Analysis CCI BU No 824338
Project Number 015-00428-00, Application 290281, Revision 1 Page 2
TABLE OF CONTENTS
1) INTRODUCTION
2) ANALYSIS CRITERIA
Table 1 - Proposed Antenna and Cable Information
Table 2 - Existing and Reserved Antenna and Cable Information
Table 3- Design Antenna and Cable Information
3) ANALYSIS PROCEDURE
Table 4 - Documents Provided
3.1)Analysis Method
3.2)Assumptions
4) ANALYSIS RESULTS
Table 5—Section Capacity (Summary)
Table 6—Tower Component Stresses vs. Capacity
4.1) Recommendations
5) DISCLAIMER OF WARRANTIES
6) APPENDIX A
tnxTower Output
7) APPENDIX B
Base Level Drawing
8) APPENDIX C
Additional Calculations
tnxTower Report-version 6.1.4.1
May 21, 2015
130 Ft Monopole Tower Structural Analysis CCI BU No 824338
Project Number 015-00428-00, Application 290281, Revision 1 Page 3
1) INTRODUCTION
The existing 130' monopole has twelve sides and is evenly tapered from 41" (flat-flat) at the base to 14.76" (flat-
flat) at the top. It has three major sections, connected with slip joints. The structure is galvanized and has no
tower lighting.
The tower was originally designed for Western Wireless by Valmont Industries, Inc. of West Highway, Nebraska
for a 85 mph wind speed with 0.5" radial ice in accordance with EIA/TIA-222-E.
2)ANALYSIS CRITERIA
The structural analysis was performed for this tower in accordance with the requirements of TIA-222-G
Structural Standards for Steel Antenna Towers and Antenna Supporting Structures using a 3-second gust wind
speed of 85 mph with no ice, 30 mph with 1" ice thickness and 60 mph under service loads, exposure category
C.
The design of the existing structure meets the requirements of TIA-222-G and ASCE 7-05 for wind loading and
the seismic provisions of the 2014 Oregon Structural Specialty Code (OSSC), TIA-222-G and ASCE 7-05.
Seismic loads were considered utilizing the TIA-222-G standard. Based on TIA-222-G, the seismic effects may
be ignored due to the earthquake spectral response acceleration at short periods (Ss) for this site being less
than or equal to 1.00. The wind effects control the maximum tower loading.
Table 1 -Proposed Antenna and Cable Information
Center Number Number Feed
Mounting Line of Antenna Antenna Model of Feed Line Note
Level (ft) Elevation Antennas Manufacturer Lines Size(in)
(ft)
127.0 131.0 3 RFS Celwave APXVFWW24X-C-NA20 2 7/8 1
w/Mount Pipe I I
Notes:
1) See Appendix B for the proposed coax layout.
Table 2-Existing and Reserved Antenna and Cable Information
Center Number Number Feed
Mounting Line of Antenna Antenna Model of Feed Line Note
Level (ft) Elevation Antennas Manufacturer Lines Size(in)
(ft)
134.0 1 GPS GPS_A
3 Andrew TMBXX-6517-R2M w/ 16 1-5/8
Mount Pipe 1 1-1/4
3 Nokia FRIG 1 1/2
1 Raycap RNSNDC-7771-PF-48
132.0 3 Andrew TMBX0(-6517-R2M w/
Mount Pipe
127.0 3 Andrew TMBX-6517-R2M w/
Mount Pipe
2 I Raycap RNSNDC-7771-PF-48 8 1-5/8 1
r 6 1 Andrew E15S08P78
131.0 3 RFS Celwave IAPXI7DWV-17DWV-S-E-
A20 w/Mount Pipe
2 Nokia FXFB
127.0 1 (Platform Mount[LP 713-1]
tnxTower Report-version 6.1.4.1
May 21, 2015
130 Ft Monopole Tower Structural Analysis CCI BU No 824338
Project Number 015-00428-00, Application 290281, Revision 1 Page 4
' Center Number Number Feed
Mounting Line of Antenna Antenna Model of Feed Line Note
Level (ft) Elevation Antennas Manufacturer
(ft) Lines Size(in)
119.0 6 Jaybeam wireless PCSS065-19-2 w/Mount
118.0 Pipe 6 1-5/8
118.0 1 1 I T-Arm Mount[TA 602-3]
114.0 I 1 Radiowaves I SP1-5.2
113.0 I 2 Radiowaves I HP2-23 2 1/2
109.0 3 Kathrein 1840 10057 w/Mount Pipe 1 3/8
110.0 3 3/8
3 Nextnet wireless r BTS-2500 3 1/4
109.0 1 Pipe Mount[PM 601-3]
2 Amphenol BXA-171063-8CF-EDIN-X
w/Mount Pipe
1 Antel BXA-185063/12CF w/
Mount Pipe
1 Antel BXA-185085/12CF w/
Mount Pipe
2 Antel BXA-70040/8CF w/Mount
Pipe
1 Antel BXA-70063-8CF-EDIN-X
w/Mount Pipe -
90.0 90.0 BXA-70063/8CF w/ Mount 13 1-5/8
2 Antel Pipe 1 1/2
1 Antel BXA-70080-8CF-EDIN-0
w/Mount Pipe
1 CSS FAXP19-45-0 w/Mount
Pipe
1 CSS XP20-45-0D w/Mount
Pipe
I 3 Ericsson 1 RRU-11
I 1 I Raycap I RCMDC-3315-PF-48
I 1 I 1 T-Arm Mount[TA 602-3]
Notes:
1) Existing equipment to be removed;not considered in this analysis.
Table 3 - Design Antenna and Cable Information
Center Number Number Feed
Mounting Line of Antenna Antenna Model of Feed Line
Level (ft) Elevation Antennas Manufacturer Lines Size(in)
(ft)
130 130 12 Generic D8978H90
1 I Mini Platform
110 110 I 12 Generic I D8978H90
1 I Mini Platform
100 100 I 1 Generic I 4'6GHz Dish
80 I 80 I 1 I Generic I 4'6GHz Dish I I
tnxTower Report-version 6.1.4.1
May 21, 2015
130 Ft Monopole Tower Structural Analysis CCI BU No 824338
Project Number 015-00428-00, Application 290281, Revision 1 Page 5
3) ANALYSIS PROCEDURE
Table 4 - Documents Provided
Document Remarks Reference Source
Geotechnical Reports Dames& Moore Doc ID#: 3512100 Crown DMZ
Job#: 32140- 001-016, dated 6/18/96 1
T Tower Foundation
Drawings Miller Consulting Engineers
Job#: 960455, dated 6/28/96 Doc ID#: 3675342 Crown DMZ
Tower Manufacturer Valmont Order#: 13135-96, Doc ID#: 3675330 Crown DMZ
Drawings dated 6/17/96
Previous Structural GPD Associates, LLC
Analysis Project#: 2013777.824338.01 Doc ID#: 4023237 Crown DMZ
dated 6/11/12
3.1) Analysis Method
tnxTower(version 6.1.4.1), a commercially available analysis software package, was used to create a
three-dimensional model of the tower and calculate member stresses for various loading cases.
Selected output from the analysis is included in Appendix A.
3.2) Assumptions
1) The tower and foundation were constructed in accordance with their original design and
maintained per the manufacturer's specifications, are in good condition, and the tower is twist free
and plumb.
2) All member connections are assumed to have been designed to meet or exceed the load carrying
capacity of the connected member unless otherwise specified in this report.
3) All equipment model numbers, quantities, and centerline elevations are as provided in the CCI
CAD package, dated 05/15/15 with any adjustments as noted below.
a. Per recent site photos, the coax at the 90' level are shown in an incorrect location and
configuration. The base level drawing has been updated accordingly.
This analysis may be affected if any assumptions are not valid or have been made in error. SSOE
Group should be notified to determine the effect on the structural integrity of the tower.
4) ANALYSIS RESULTS
Table 5 -Section Capacity (Summary)
Section Component Critical SF`P_allow
No. Elevation(ft) Type Size Element P(K) (K) (Capacity Pass/Fail
L1 130-80.9167 Pole TP25.07x14.76x0.219 1 -9.80 1146.98 71.8 Pass
L2
80.9167 Pole TP32.16x23.7743x0.313 2 -16.47 2196.08 72.5 Pass
45.0834
L3 45.0834-0 Pole TP41x30.5011x0.375 3 -29.23 3341.22 74.1 Pass
•Summary
Pole(L3) 74.1 Pass I
Rating= 74.1 Pass
tnxTower Report-version 6.1.4.1
May 21, 2015
130 Ft Monopole Tower Structural Analysis CCI BU No 824338
Project Number 015-00428-00, Application 290281, Revision 1 Page 6
Table 6 -Tower Component Stresses vs. Capacity— LC5
Notes Component Elevation (ft) % Capacity Pass/Fail
1 Anchor Rods 65.8% Pass
1 Base Plate 37.3% Pass
1 Base Foundation (Structure) 68.4% Pass
1 Base Foundation (Soil Interaction) 71.9% Pass
Structure Rating (max from all components) = 74.1%
Notes:
1) See additional documentation in"Appendix C—Additional Calculations"for calculations supporting the%capacity
consumed.
4.1) Recommendations
The existing tower and its foundations are sufficient for the proposed loads and do not require
modifications.
5) DISCLAIMER OF WARRANTIES
SSOE Group has not performed a site visit to the tower to verify member sizes or antenna/coax loading. SSOE
Group shall be contacted immediately if the existing conditions are not as represented on the tower elevation
contained in this report in order to evaluate the significance of the discrepancy. SSOE Group has not performed
a condition assessment of the tower foundation. This report does not replace a full tower inspection
The engineering services rendered by SSOE Group in connection with this structural analysis are limited to an
analysis of the tower structure and theoretical capacity of its main structural members. Miscellaneous items
such as antenna mounts, etc., have not been designed or detailed as part of our work. We recommend that
material of suitable size and strength be purchased from a reputable tower manufacturer.
SSOE Group makes no warranties, expressed and/or implied, in connection with this report and disclaims any
liability arising from material, fabrication, and erection of this tower. SSOE Group will not be responsible
whatsoever for, or on account of, consequential or incidental damages sustained by any person, firm, or
organization as a result of any data contained in this report. The maximum liability of SSOE Group pursuant to
this report will be limited to the total fee received for preparation of this report.
tnxTower Report-version 6.1.4.1
May 21, 2015
130 Ft Monopole Tower Structural Analysis CCI BU No 824338
Project Number 015-00428-00,Application 290281, Revision 1 Page 7
APPENDIX A
TNXTOWER OUTPUT
tnxTower Report-version 6.1.4.1
I
■
130.0 ft
I DESIGNED APPURTENANCE LOADING
IIIJ I TYPE ELEVATION TYPE _ ELEVATION
(2)Beacon UgM(5.5"Dlam x9"Tall) 127 840 10057 w/Mourn Pipe 109
TMBXX-6517-R2M w/Maud Pipe 127 _ BTS-2500 109
FRIG 127 840 10057 w/Mount Pipe 109 BTS-2500
4X-C-w R PIS MBX)G51 Mou'Pipe 127 HP2- [PM 601-31 109
FRIG 127 HP2-23 109
P FXFB 127 SP1-5.2 109
APXVFVVW24X-C-NA20 w/Maud Pipe 127 BXA•70080•8CF-EDIN-0 w/Moot Pipe 90
TMBXX-65l7-R2M w/Mood Pipe 127 RRU-11 90
GPS_A 127 RCMDC-3315-PF-48 90
O ,, p
`-`i o r FRIG 127 (2)BXA-70040/8CF w/Mount Pipe 90
m v APXVFWW24X-C•NA20 w/Maul Pipe 127 AXP19-45-0 Wl Mount Pipe 90
RNSNDC-7771-PF-48 127 XP20.45.00 w/Mount Pipe 90
(2)6'x2"mount pipe 127 RRU-11 90
(2)6 x2"mount pipe 127 BXA-171063-8CF-EDIN-X w/Mount 90
(2)6 x 2"mount pipe 127 Pipe
Platform Mount[LP 713.1] 127 BXA-185083/12CF w/Mount Pipe 90
(2)PCSS065-19-2 w/Mount Pipe 118 BXA-70063/BCF w/Mount Pipe 90
(2)PCSS065.19.2 w/Mout Pipe 118 BXA-70063-8CF-EDIN-X w/Mount 90
(2)PCSS065.19-2 w/Mount Pipe 118 Pipe
6 x2"moult pipe 118 RRU-11 90
Is — 6 z 2"mount pipe 118
1 T-Arm Mount[TA 802-3] 90
6 z 2"mount pipe 118 BXA-171063-8CF-EDIN•X wl Mout 90
/ 80.9 ft
Pipe
T•Aml Mourn(TA 602.3( 118 BXA-185085/12CF w/Mount Pipe 90
840 10057 wl Moot Pipe 108 BXA-70063/8CF w/Mount Pipe 90
BTS-2500 109
MATERIAL STRENGTH
GRADE Fy Fu GRADE—T-- ---1 Fu
A572-65 65 ksi 80 Imi
N TOWER DESIGN NOTES
N m 0 1. Tower is located in Washington County,Oregon.
nt – a M 2. Tower designed for Exposure C to the TIA-222-G Standard.
o H M 3. Tower designed for a 85 mph basic wind in accordance with the TIA-222-G Standard.
4. Tower is also designed for a 30 mph basic wind with 1.00 in ice.Ice is considered to increase
in thickness with height.
5. Deflections are based upon a 60 mph wind.
6. Tower Structure Class II. •
7. Topographic Category 1 with Crest Height of 0.00 ft
■7
8. TOWER RATING:74.1%
/ 45.1 ft �11
ALL REACTIONS
ARE FACTORED
8 AXIAL
E N E g
_8 67 K
o SHEAR MOMENT
3 K / 310 kip-ft
TORQUE 0 kip-ft
30 mph WIND-1.0000 in ICE
AXIAL
29 K
3K I MOMENT
2
23 K � 2023 kip-ft
0.0ft
74 I TORQUE 1 kip-ft
s REACTIONS-85 mph WIND
▪ E c I o° s 1 .s
onn -I z t- a r m c3 3
/►/►A Al SSOE GROUP lob:BU 824338
55Qb320 Seven Springs Way,Suite 350 P`°pa'015-0028.00
Brentwood,TN 37027 c"":ccl Drawn by.15264AP":
Phone:(815)309-1994 Code' TIA-222-G Date:05/21/15 ScB1e: NTS
FAX:(615)661-7569 Path:c.1d:n1d15328931B11.824338.ed Dw9 Na-E-1
Feed Line Distribution Chart I
0' - 130'
nand Fit ...c ar
•
,3000 Face A Face B Face C 13900
127.00 127.00 ..-------
118.00 118.00
109.00 10.00
W
moo 90.00
80.92 _.. ._. ._. ._. .........80.92
m a
4 a
N LL -U
9 -
W ? ?
• -
F
z.
U LL
45.09 . s
..._... _. __ ._.._._ _. ....__... :.. ............ 45.08
8.00 8.00
0.00 0.00
•
r SSOE GROUP Job BU 824338
��990e 320 Seven Springs Way,Suite 350 "01°4'015.00428.00
)� Brentwood,TN 37027 al":CCi Drawnby.1528414*d'
Phone:(615)309-1994 code: TIA-222-G,Date:05/21/15 sc81e: NTS
FAX:(615)661-7569 Path c:ldgn1d153289318U-824338.ed Dw9 No.E-7
Page
trtxTower Job BU 824338 1 of 14
SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN37027 Client Designed by
Phone:(615)309-1994 COI
FAX:(615)661-7569 15264
Tower Input Data
There is a pole section.
This tower is designed using the TIA-222-G standard.
The following design criteria apply:
Tower is located in Washington County,Oregon.
Basic wind speed of 85 mph.
Structure Class II.
Exposure Category C.
Topographic Category 1.
Crest Height 0.00 ft.
Nominal ice thickness of 1.0000 in.
Ice thickness is considered to increase with height.
Ice density of 56 pcf.
A wind speed of 30 mph is used in combination with ice.
Temperature drop of 50°F. -
Deflections calculated using a wind speed of 60 mph.
A non-linear(P-delta)analysis was used.
Pressures are calculated at each section.
Stress ratio used in pole design is 1.
Local bending stresses due to climbing loads,feed line supports,and appurtenance mounts are not considered.
Options
Consider Moments-Legs Distribute Leg Loads As Uniform Treat Feedline Bundles As Cylinder
Consider Moments-Horizontals Assume Legs Pinned Use ASCE 10 X-Brace Ly Rules
Consider Moments-Diagonals 4 Assume Rigid Index Plate Calculate Redundant Bracing Forces
Use Moment Magnification 4 Use Clear Spans For Wind Area Ignore Redundant Members in FEA
4 Use Code Stress Ratios Use Clear Spans For KL/r SR Leg Bolts Resist Compression
Use Code Safety Factors-Guys Retension Guys To Initial Tension All Leg Panels Have Same Allowable
Escalate Ice 4 Bypass Mast Stability Checks Offset Girt At Foundation
Always Use Max Kz 4 Use Azimuth Dish Coefficients J Consider Feedline Torque
Use Special Wind Profile J Project Wind Area of Appurt. Include Angle Block Shear Check
Include Bolts In Member Capacity Autocalc Torque Arm Areas Poles
Leg Bolts Are At Top Of Section SR Members Have Cut Ends 1 Include Shear-Torsion Interaction
Secondary Horizontal Braces Leg Sort Capacity Reports By Component Always Use Sub-Critical Flow
Use Diamond Inner Bracing(4 Sided) Triangulate Diamond Inner Bracing Use Top Mounted Sockets
Add IBC.6D+W Combination Use TIA-222-G Tension Splice Capacity
Exemption
Tapered Pole Section Geometry
Section Elevation Section Splice Nambrr Top Bottom Wall Bend Pole Grade
Length Length of Diameter Diameter Thickness Radius
ft f! ft Sides in in in in
Ll I30.00-80.92 49.08 4.08 12 14.7600 25.0700 0.2190 0.8760 A572-65
(65 ksi)
L2 80.92-45.08 39.92 4.92 12 23.7743 32.1600 0.3130 1.2520 A572-65
(65 ksi)
Job Page
tnxTower BU 824338 2 of 14
• SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN37027 Client Designed by
Phone:(615)309-1994 CCI
FAX. (615)661-7569 15264
Section Elevation Section Splice Number Top Bottom Wall Bend Pole Grade
Length Length of Diameter Diameter Thickness Radius
if ft ft Sides in in in in
L3 45.08-0.00 50.00 12 30.5011 41.0000 0.3750 1.5000 A572-65
(65 ksi)
Tapered Pole Properties
Section Tip Dia. Area / r C UC J It/Q w wit
in in2 in' in in in3 in' in2 in
LI 15.2807 10.2540 276.7380 5.2057 7.6457 36.1953 560.7462 5.0467 3.3688 15.382
25.9544 17.5244 1381.3939 8.8967 12.9863 106.3735 2799.0786 8.6250 6.1318 27.999
L2 25.5010 23.6457 1661.2778 8.3991 12.3151 134.8978 3366.1993 11.6377 5.5327 17.676
33.2945 32.0973 4155.1982 11.4012 16.6589 249.4284 8419.5581 15.7973 7.7800 24.856
L3 32.6459 36.3773 4214.0784 10.7852 15.7996 266.7209 8538.8653 17.9038 7.1693 19.118
42.4463 49.0547 10333.6372 14.5437 21.2380 486.5636 20938.7506 24.1432 9.9830 26.621
Tower Gusset Gusset Gusset Grade Adjust.Factor Adjust. Weight Mult. Double Angle Double Angle
Elevation Area Thickness Af Factor Stitch Bolt Stitch Bolt
(per face) A, Spacing Spacing
Diagonals Horizontals
ft ft2 in in in
• LI 1 1 1
130.00-80.92
L2 80.92-45.08 1 1 1
L3 45.08-0.00 1 I I
Feed Line/Linear Appurtenances - Entered As Round Or Flat
Description Sector Component Placement Total Number Start/End Width or Perimeter Weight
Type Number Per Row Position Diameter
ft in in plf
LDF7-50A(1-5/8") A Surface Ar 1 18.00-8.00 6 6 0.150 1.9800 0.82
(CaAa) 0.350
LDF7-50A(1-5/8") C Surface Ar 90.00-8.00 6 6 0.300 1.9800 0.82
(CaAa) 0.450
W BC-600(1/2") B Surface Ar 90.00-8.00 1 1 -0.400 0.5900 0.13
(CaAa) -0.400
LDF7-50A(1-5/8") B Surface Ar 90.00-8.00 7 6 -0.350 1.9800 0.82
(CaAa) -0200
Safety Line(3/8") C Surface Ar 130.00-8.00 1 1 0.000 0.3750 0.22
(CaAa) 0.000
Step Pegs C Surface Ar 130.00-8.00 1 1 0.000 0.8000 2.72
(CaAa) 0.000
Feed Line/Linear Appurtenances - Entered As Area
Description Face Allow Component Placement Total CAA, Weight
or Shield Type Number
Leg .t fi2/fi Pf
• 1/2"Power Cable C No Inside Pole 130.00-8.00 I No Ice 0.00 0.50
1/2"Ice 0.00 0.50
Page
tnxTower
Job BU 824338 3 of 14
SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCl _
FAX-(615)661-7569 15264
Description Face Allow Component Placement Total CAAA Weight
or Shield Type Number
Leg .R f(Ik pl
1"Ice 0.00 0.50
7/16"Ground Cable C No Inside Pole 130.00-8.00 1 No Ice 0.00 0.55
1/2"Ice 0.00 0.55
1"Ice 0.00 0.55
LDF4-50A(1/2") C No Inside Pole 127.00-8.00 1 No Ice 0.00 0.15
1/2"Ice 0.00 0.15
1"Ice 0.00 0.15
LDF7-50A(1-5/8") C No Inside Pole 127.00-8.00 16 No Ice 0.00 0.82
1/2"Ice 0.00 0.82
1"Ice 0.00 0.82
ASU9323TYP01(1-1/4) C No Inside Pole 127.00-8.00 I No Ice 0.00 1.05
1/2"Ice 0.00 1.05
1"Ice 0.00 1.05
LDF5-50A(7/8") C No Inside Pole 127.00-8.00 2 No Ice 0.00 0.33
1/2"Ice 0.00 0.33
1"Ice 0.00 0.33
LDF4-50A(1/2") C No Inside Pole 127.00-8.00 1 No Ice 0.00 0.15
1/2"Ice 0.00 0.15
1"Ice 0.00 0.15
LDF7-50A(1-5/8") C No Inside Pole 127.00-8.00 16 No Ice 0.00 0.82
1/2"Ice 0.00 0.82 .
1"Ice 0.00 0.82
LDF1-50A(1/4") C No Inside Pole 109.00-8.00 3 No Ice 0.00 0.06
1/2"Ice 0.00 0.06
1"Ice 0.00 0.06 •
LDF2-50(3/8") C No Inside Pole 109.00-8.00 3 No Ice 0.00 0.08
1/2"Ice 0.00 0.08
1"Ice 0.00 0.08
LDF4-50A(l/2") C No Inside Pole 109.00-8.00 2 No Ice 0.00 0.15
1/2"Ice 0.00 0.15
I"Ice 0.00 0.15
100266(7/16") C No Inside Pole 109.00-8.00 1 No Ice 0.00 0.08
1/2"Ice 0.00 0.08
1"Ice 0.00 0.08
7/16"Ground Cable C No Inside Pole 109.00-8.00 1 No Ice 0.00 0.55
1/2"Ice 0.00 0.55
1"Ice 0.00 0.55
Feed Line/Linear Appurtenances Section Areas
Tower Tower Face AR Ar CAAA CAAA 11'eight
Section Elevation In Face Out Face
ft .12 ft2 ft2 .112 K
LI 130.00-80.92 A 0.000 0.000 44.055 0.000 0.18
B 0.000 0.000 11.327 0.000 0.05
C 0.000 0.000 16.558 0.000 1.58
L2 80.92-45.08 A 0.000 0.000 42.570 0.000 0.18
B 0.000 0.000 44.684 0.000 0.21
C 0.000 0.000 46.780 0.000 1.38
L3 45.08-0.00 A 0.000 0.000 44.055 0.000 0.18
B 0.000 0.000 46.243 0.000 0.22
C 0.000 0.000 48.412 0.000 1.43
Feed Line/Linear Appurtenances Section Areas - With Ice .
tnxTower Job
Page
BU 824338 4 of 14
SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCI
• FAX: (615)661-7569 15264
Tower Tower Face Ice AR AF C.44 C.A4 Weight
Section Elevation or Thickness In Face Out Face
f Leg in .112 ft2 ft2 fie K
LI 130.00-80.92 A 2.242 0.000 0.000 75.858 0.000 1.31
B 0.000 0.000 23.191 0.000 0.43
C 0.000 0.000 68.376 0.000 2.62
L2 80.92-45.08 A 2.132 0.000 0.000 73.301 0.000 1.27
B 0.000 0.000 91.487 0.000 1.69
C 0.000 0.000 109.654 0.000 3.03
L3 45.08-0.00 A 1.925 0.000 0.000 74.833 0.000 1.25
B 0.000 0.000 92.832 0.000 1.65
C 0.000 0.000 110.812 0.000 3.02
Feed Line Center of Pressure
Section Elevation CPx CP/ CPx CPz
Ice Ice
Jt in in in in
LI 130.00-80.92 -0.4550 -0.6787 -0.3815 -0.2912
L2 80.92-45.08 -0.5200 -0.7722 -0.4058 -0.5213
L3 45.08-0.00 -0.5295 -0.7720 -0.4561 -0.5765
Shielding Factor Ka
Tower Feed Line Description Feed Line K K
Section Record No. Segment Elev. No Ice Ice
LI 10 LDF7-50A(1-5/8") 80.92-118.00 1.0000 1.0000
LI 15 LDF7-50A(1-5/8") 80.92-90.00 1.0000 1.0000
LI 16 WBC-600(112") 80.92-90.00 1.0000 1.0000
LI 17 LDF7-50A(I-5/8") 80.92-90.00 1.0000 1.0000
LI 18 Safety Line(3/8") 80.92-130.00 1.0000 1.0000
LI 19 Step Pegs 80.92-130.00 1.0000 1.0000
L2 10 LDF7-50A(1-5/8") 45.08-80.92 1.0000 1.0000
L2 15 LDF7-50A(1-5/8") 45.08-80.92 1.0000 1.0000
L2 16 WBC-600(1/2") 45.08-80.92 1.0000 1.0000
L2 17 LDF7-50A(1-5/8") 45.08-80.92 1.0000 1.0000
L2 18 Safety Line(3/8") 45.08-80.92 1.0000 1.0000
L2 19 Step Pegs 45.08-80.92 1.0000 1.0000
Discrete Tower Loads
Job Page tnxTower
BU 824338 5 of 14
SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCI .
FAX. (615)661-7569 15264
Description Face Offset Offsets: Azimuth Placement CAAA Ck44 Weight
or Type Hor- Adjustment Front Side
Leg Lateral
Vert
ft ` ft fi2 fi2 K
.t
ft
(2)Beacon Light(5.5"Diam B From Leg 4.00 0.0000 127.00 No Ice 0.28 0.28 0.01
x 9"Tall) 0.00 1/2"Ice 0.36 0.36 0.01
4.00 1"Ice 0.46 0.46 0.02
TMBXX-6 6517-R2M w/ A From Leg 3.86 15.0000 127.00 No Ice 8.98 6.96 0.07
Mount Pipe 1.04 1/2"Ice 9.65 8.18 0.14
5.00 1"Ice 10.29 9.14 0.22
FRIG A From Leg 3.86 15.0000 127.00 No Ice 2.79 1.10 0.06
1.04 1/2"Ice 3.02 1.27 0.07
5.00 1"Ice 3.25 1.44 0.09
FXFB A From Leg 3.86 15.0000 127.00 No Ice 4.13 1.12 0.06
1.04 1/2"Ice 4.40 1.30 0.08
0.00 1"Ice 4.68 1.49 0.10
APXVFWW24X-C-NA20 w/ A From Leg 3.86 15.0000 127.00 No Ice 11.31 9.70 0.09
Mount Pipe 1.04 l/2"Ice 11.93 10.80 0.18
4.00 1"Ice 12.55 11.77 0.27
TMBXX-65 1 7-R2M w/ B From Leg 3.86 15.0000 127.00 No Ice 8.98 6.96 0.07
Mount Pipe 1.04 1/2"Ice 9.65 8.18 0.14 .
5.00 I"Ice 10.29 9.14 0.22
FRIG B From Leg 3.86 15.0000 127.00 No Ice 2.79 1.10 0.06
1.04 1/2"Ice 3.02 1.27 0.07
5.00 1"Ice 3.25 1.44 0.09 .
FXFB B From Leg 3.86 15.0000 127.00 No Ice 4.13 1.12 0.06
1.04 1/2"Ice 4.40 1.30 0.08
0.00 1"Ice 4.68 1.49 0.10
APXVFWW24X-C-NA20 w/ B From Leg 3.86 15.0000 127.00 No Ice 11.31 9.70 0.09
Mount Pipe 1.04 1/2"Ice 11.93 10.80 0.18
4.00 1"Ice 12.55 11.77 0.27
TMBXX-6 6517-R2M w/ C From Leg 3.86 15.0000 127.00 No Ice 8.98 6.96 0.07
Mount Pipe 1.04 1/2"Ice 9.65 8.18 0.14
5.00 1"Ice 10.29 9.14 0.22
GPS_A C From Leg 3.86 15.0000 127.00 No Ice 0.30 0.30 0.00
1.04 1/2"Ice 0.37 0.37 0.00
7.00 1"Ice 0.46 0.46 0.01
FRIG C From Leg 3.86 15.0000 127.00 No Ice 2.79 1.10 0.06
1.04 1/2"Ice 3.02 1.27 0.07
5.00 1"Ice 3.25 1.44 0.09
APXVFWW24X-C-NA20 w/ C From Leg 3.86 15.0000 127.00 No Ice 11.31 9.70 0.09
Mount Pipe 1.04 1/2"Ice 11.93 10.80 0.18
4.00 1"Ice 12.55 1 1.77 0.27
RNSNDC-7771-PF-48 C From Leg 3.86 15.0000 127.00 No Ice 3.19 1.16 0.01
1.04 1/2"Ice 3.43 1.33 0.03
5.00 1"Ice 3.68 1.51 0.06
(2)6'x 2"mount pipe A From Leg 3.86 0.0000 127.00 No Ice 1.44 1.44 0.02
1.04 1/2"Ice 1.93 1.93 0.03
0.00 1"Ice 2.30 2.30 0.05
(2)6'x 2"mount pipe B From Leg 3.86 0.0000 127.00 No Ice 1.44 1.44 0.02
1.04 1/2"Ice 1.93 1.93 0.03
0.00 1"Ice 2.30 2.30 0.05
(2)6'x 2"mount pipe C From Leg 3.86 0.0000 127.00 No Ice 1.44 1.44 0.02
1.04 1/2"Ice 1.93 1.93 0.03
0.00 I"Ice 2.30 2.30 0.05
Platform Mount[LP 713-1] C None 0.0000 127.00 No Ice 31.27 31.27 1.51
1/2"Ice 39.68 39.68 1.93
1"Ice 48.09 48.09 2.35
(2)PCSS065-19-2 w/Mount A From Face 4.00 -30.0000 1 18.00 No Ice 6.24 3.35 0.04
Pipe 0.00 1/2"Ice 6.81 4.80 0.09 `
1.00 1"Ice 7.36 5.99 0.14
ZnxTower Job Page
BU 824338 6 of 14
- SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCI
- FAX:(615)661-7569 15264
Description Face Offset Offsets: Azimuth Placement C4A4 CAAA Weight
or Type Harz Adjustment Front Side
Leg Lateral
Vert
fi ° .R .1i2 1t2 K
it
.1
(2)PCSS065-19-2 w/Mount B From Face 4.00 -30.0000 118.00 No Ice 6.24 3.35 0.04
Pipe 0.00 1/2"Ice 6.81 4.80 0.09
1.00 1"Ice 7.36 5.99 0.14
(2)PCSS065-19-2 w/Mount C From Face 4.00 -60.0000 118.00 No Ice 6.24 3.35 0.04
Pipe 0.00 1/2"Ice 6.81 4.80 0.09
1.00 1"Ice 7.36 5.99 0.14
6'x 2"mount pipe A From Leg 3.86 0.0000 118.00 No Ice 1.44 1.44 0.02
1.04 1/2"Ice 1.93 1.93 0.03
0.00 I"Ice 2.30 2.30 0.05
6'x 2"mount pipe B From Leg 3.86 0.0000 118.00 No Ice 1.44 1.44 0.02
1.04 1/2"Ice 1.93 1.93 0.03
0.00 1"Ice 2.30 2.30 0.05
6'x 2"mount pipe C From Leg 3.86 0.0000 118.00 No Ice 1.44 1.44 0.02
1.04 1/2"Ice 1.93 1.93 0.03
0.00 1"Ice 2.30 2.30 0.05
T-Arm Mount[TA 602-3] C None 0.0000 118.00 No Ice 11.59 11.59 0.77
1/2"Ice 15.44 15.44 0.99
1"Ice 19.29 19.29 1.21
840 10057 w/Mount Pipe A From Face 1.00 -20.0000 109.00 No Ice 3.50 3.34 0.05
0.00 1/2"Ice 4.10 4.17 0.09
1.00 1"Ice 4.64 4.87 0.13
BTS-2500 A From Face 1.00 -20.0000 109.00 No Ice 2.12 0.96 0.04
0.00 1/2"Ice 2.32 1.12 0.05
1.00 1"Ice 2.53 1.29 0.06
840 10057 w/Mount Pipe B From Face 1.00 -20.0000 109.00 No Ice 3.50 3.34 0.05
0.00 1/2"Ice 4.10 4.17 0.09
1.00 1"Ice 4.64 4.87 0.13
BTS-2500 B From Face 1.00 -20.0000 109.00 No Ice 2.12 0.96 0.04
0.00 1/2"Ice 2.32 1.12 0.05
1.00 1"Ice 2.53 1.29 0.06
840 10057 w/Mount Pipe C From Face 1.00 -10.0000 109.00 No ke 3.50 3.34 0.05
0.00 1/2"Ice 4.10 4.17 0.09
1.00 1"Ice 4.64 4.87 0.13
BTS-2500 C From Face 1.00 -10.0000 109.00 No Ice 2.12 0.96 0.04
0.00 1/2"Ice 2.32 1.12 0.05
1.00 1"Ice 2.53 1.29 0.06
Pipe Mount[PM 601-3] C None 0.0000 109.00 No Ice 4.39 4.39 0.20
1/2"Ice 5.48 5.48 0.24
1"Ice 6.57 6.57 0.28
BXA-171063-8CF-EDIN-X A From Face 4.00 25.0000 90.00 No Ice 3.16 3.33 0.03
w/Mount Pipe 0.00 1/2"Ice 3.53 3.94 0.06
0.00 1"Ice 3.94 4.56 0.10
BXA-185085/12CF w/Mount A From Face 4.00 25.0000 90.00 No Ice 5.01 5.31 0.04
Pipe 0.00 1/2"Ice 5.56 6.48 0.08
0.00 1"Ice 6.08 7.37 0.14
BXA-70063/8CF w/Mount A From Face 4.00 25.0000 90.00 No Ice 10.89 7.63 0.06
Pipe 0.00 1/2"Ice 11.60 9.11 0.13
0.00 1"Ice 12.32 10.61 0.22
BXA-70080-8CF-EDIN-0 w/ A From Face 4.00 25.0000 90.00 No Ice 8.44 8.70 0.06
Mount Pipe 0.00 1/2"Ice 9.13 10.20 0.13
0.00 1"Ice 9.83 11.70 0.21
• RRU-11 A From Face 4.00 25.0000 90.00 No Ice 1.91 1.47 0.04
0.00 1/2"Ice 2.10 1.65 0.06
0.00 1"Ice 2.30 1.83 0.08
RCMDC-3315-PF-48 A From Face 4.00 25.0000 90.00 No Ice 4.33 2.56 0.03
- 0.00 1/2"Ice 4.61 2.79 0.06
0.00 I"Ice 4.90 3.04 0.10
Page
tnxTower
Job BU 824338 7 of 14
SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCI .
FAX. (615)661-7569 15264
Description Face Offset Offsets: Azimuth Placement CARA CAAA Weight
or Type Hor_ Adjustment Front Side
Leg Lateral
Vert
ft ft ft' ft1 K
f
it
(2)BXA-70040/8CF w/ B From Face 4.00 20.0000 90.00 No Ice 22.27 10.18 0.08
Mount Pipe 0.00 1/2"Ice 23.14 11.69 0.21
0.00 1"Ice 24.03 13.21 0.36
AXP19-45-0 w/Mount Pipe B From Face 4.00 20.0000 90.00 No Ice 4.91 3.25 0.03
0.00 1/2"Ice 5.34 3.84 0.07
0.00 1"Ice 5.79 4.45 0.11
XP20-45-0D w/Mount Pipe B From Face 4.00 20.0000 90.00 No Ice 7.12 4.75 0.04
0.00 1/2"Ice 7.74 5.85 0.09
0.00 1"Ice 8.33 6.69 0.15
RRU-11 B From Face 4.00 20.0000 90.00 No Ice 1.91 1.47 0.04
0.00 1/2"Ice 2.10 1.65 0.06
0.00 1"Ice 2.30 1.83 0.08
BXA-171063-8CF-EDIN-X C From Face 4.00 -20.0000 90.00 No Ice 3.16 3.33 0.03
w/Mourn Pipe 0.00 1/2"Ice 3.53 3.94 0.06
0.00 1"Ice 3.94 4.56 0.10
BXA-185063/12CF w/Mount C From Face 4.00 -20.0000 90.00 No Ice 5.01 5.31 0.04
Pipe 0.00 1/2"Ice 5.56 6.48 0.09 .
0.00 1"Ice 6.08 7.37 0.14
BXA-70063/8CF w/Mount C From Face 4.00 -20.0000 90.00 No Ice 10.89 7.63 0.06
Pipe 0.00 1/2"Ice 11.60 9.11 0.13
0.00 1"Ice 12.32 10.61 0.22 .
BXA-70063-8CF-EDIN-X w/ C From Face 4.00 -20.0000 90.00 No Ice 10.91 8.18 0.06
Mount Pipe 0.00 1/2"Ice 11.61 9.67 0.14
0.00 1"Ice 12.33 11.17 0.22
RRU-11 C From Face 4.00 -20.0000 90.00 No Ice 1.91 1.47 0.04
0.00 1/2"Ice 2.10 1.65 0.06
0.00 1"Ice 2.30 1.83 0.08
T-Arm Mount[TA 602-3] C None 0.0000 90.00 No Ice 11.59 11.59 0.77
1/2"Ice 15.44 15.44 0.99
I"Ice 19.29 19.29 1.21
Dishes I
Description Face Dish Offset Offsets: Azimuth 3 dB Elevation Outside Aperture Weight
or Type Type Hor_ Adjustment Beam Diameter Area
Leg Lateral Width
Vert
ft ° ° ft ft fit K
HP2-23 B Paraboloid From 1.00 -70.0000 109.00 2.04 No Ice 3.27 0.03
w/Radome Face 0.00 1/2"Ice 3.55 0.05
4.00 1"Ice 3.82 0.03
HP2-23 C Paraboloid From 1.00 40.0000 109.00 2.04 No Ice 3.27 0.03
w/Radome Face 0.00 1/2"Ice 3.55 0.05
4.00 I"Ice 3.82 0.03
SP1-5.2 C Paraboloid From 1.00 30.0000 109.00 1.00 No Ice 0.79 0.02
w/Radome Face 0.00 1/2"Ice 0.92 0.02
5.00 1"Ice 1.06 0.02
Job Page
tnxTower BU 824338 8 of 14
SSOE GROUP Project Date
•
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN37027 Client Designed by
Phone:(615)309-1994 C C I
FAX (615)661-7569 15264
Load Combinations
Comb. Description
No.
1 Dead Only
2 1.2 Dead+1.6 Wind 0 deg-No Ice
3 0.9 Dead+1.6 Wind 0 deg-No Ice
4 1.2 Dead+1.6 Wind 30 deg-No Ice
5 0.9 Dead+1.6 Wind 30 deg-No Ice
6 1.2 Dead+l.6 Wind 60 deg-No Ice
7 0.9 Dead+1.6 Wind 60 deg-No Ice
8 1.2 Dead+1.6 Wind 90 deg-No Ice
9 0.9 Dead+1.6 Wind 90 deg-No Ice
10 1.2 Dead+1.6 Wind 120 deg-No Ice
11 0.9 Dead+1.6 Wind 120 deg-No Ice
12 1.2 Dead+1.6 Wind 150 deg-No Ice
13 0.9 Dead+1.6 Wind 150 deg-No Ice
14 1.2 Dead+1.6 Wind 180 deg-No Ice
15 0.9 Dead+1.6 Wind 180 deg-No Ice
16 1.2 Dead+1.6 Wind 210 deg-No Ice
17 0.9 Dead+1.6 Wind 210 deg-No Ice
18 1.2 Dead+1.6 Wind 240 deg-No Ice
19 0.9 Dead+1.6 Wind 240 deg-No Ice
20 1.2 Dead+1.6 Wind 270 deg-No Ice
21 0.9 Dead+1.6 Wind 270 deg-No Ice
22 1.2 Dead+1.6 Wind 300 deg-No Ice
23 0.9 Dead+1.6 Wind 300 deg-No Ice
24 1.2 Dead+1.6 Wind 330 deg-No Ice
25 0.9 Dead+1.6 Wind 330 deg-No Ice
26 1.2 Dead+1.0 Ice+1.0 Temp
27 1.2 Dead+1.0 Wind 0 deg+1.0 Ice+1.0 Temp
28 1.2 Dead+1.0 Wind 30 deg+l.0 Ice+1.0 Temp
29 1.2 Dead+1.0 Wind 60 deg+1.0 Ice+1.0 Temp
30 1.2 Dead+1.0 Wind 90 deg+1.0 Ice+1.0 Temp
31 1.2 Dead+1.0 Wind 120 deg+1.0 Ice+1.0 Temp
32 1.2 Dead+1.0 Wind 150 deg+1.0 Ice+1.0 Temp
33 1.2 Dead+1.0 Wind 180 deg+1.0 Ice+1.0 Temp
34 1.2 Dead+1.0 Wind 210 deg+1.0 Ice+1.0 Temp
35 1.2 Dead+1.0 Wind 240 deg+1.0 Ice+1.0 Temp
36 1.2 Dead+l.0 Wind 270 deg+1.0 Ice+1.0 Temp
37 1.2 Dead+1.0 Wind 300 deg+1.0 Ice+1.0 Temp
38 1.2 Dead+1.0 Wind 330 deg+1.0 Ice+l.0 Temp
39 Dead+Wind 0 deg-Service
40 Dead+Wind 30 deg-Service
41 Dead+Wind 60 deg-Service
42 Dead+Wind 90 deg-Service
43 Dead+Wind 120 deg-Service
44 Dead+Wind 150 deg-Service
45 Dead+Wind 180 deg-Service
46 Dead+Wind 210 deg-Service
47 Dead+Wind 240 deg-Service
48 Dead+Wind 270 deg-Service
49 Dead+Wind 300 deg-Service
50 Dead+Wind 330 deg-Service
Maximum Member Forces
Section Elevation Component Condition Gov. Axial Major Axis Minor Axis
No. ft 1)pe Load Moment Moment
Comb. K kip ft kip-ft
Job Page .
tnxTower BU 824338 9 of 14
SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCl .
FAX (615)661-7569 15264
Section Elevation Component Condition Gov. Axial Major Axis Minor Axis
No. ft Type Load Moment Moment
Comb. K kip;fl kip-fl
LI 130-80.9167 Pole Max Tension 8 0.00 0.00 -0.00
Max.Compression 26 -32.25 -1.95 2.52
Max.Mx 8 -9.80 -396.66 -0.00
Max My 2 -9.98 -0.74 382.36
Max Vy 8 15.19 -396.66 -0.00
Max.Vx 2 -14.13 -0.74 38236
Max.Torque 6 1.25
L2 80.9167- Pole Max Tension 1 0.00 0.00 0.00
45.0834
Max.Compression 26 -45.42 -1.07 4.24
Max Mx 8 -16.47 -987.05 0.72
Max My 2 -16.61 -1.73 926.96
Max Vy 8 18.60 -987.05 0.72
Max Vx 2 -16.98 -1.73 926.96
Max.Torque 6 1.25
L3 45.0834-0 Pole Max Tension 1 0.00 0.00 0.00
Max.Compression 26 -66.93 0.34 6.39
Max.Mx 8 -29.23 -2022.73 1.71
Max.My 2 -29.23 -3.11 1872.63
Max.Vy 8 22.60 -2022.73 1.71
Max.Vx 2 -20.67 -3.11 1872.63 .
Max.Torque 6 1.24
Maximum Reactions
Location Condition Gov. Vertical Horizontal,X Hori=ontal,Z
Load K K K
Comb.
Pole Max Vert 26 66.93 0.00 -0.00
Max.H, 21 21.94 22.50 -0.03
Max.H, 3 21.94 -0.03 20.64
Max.M, 2 1872.63 -0.03 20.63
Max.M, 8 2022.73 -22.56 0.01
Max.Torsion 6 1.24 -18.54 10.32
Min.Vert 9 21.94 -22.56 0.01
Min.Hz 9 21.94 -22.56 0.01
Min.H, 15 21.94 0.02 -20.61
Min.M, 14 -1868.47 0.02 -20.61
Min.M, 20 -2015.33 22.50 -0.03
Min.Torsion 18 -1.20 18.51 -10.33
Tower Mast Reaction Summary
Load Vertical Shear, Shear, Overturning Overturning Torque
Combination Moment,M Moment,M
K K K kip-.1t kip-.11 tapJt
Dead Only 24.38 -0.00 0.00 -0.54 0.03 -0.00
1.2 Dead+1.6 Wind 0 deg-No 29.25 0.03 -20.63 -1872.63 -3.11 -0.48
Ice
0.9 Dead+1.6 Wind 0 deg-No 21.94 0.03 -20.64 -1848.93 -3.08 -0.48
Ice
1.2 Dead+1.6 Wind 30 deg-No 29.25 10.72 -17.88 -1622.07 -975.68 -0.97 -
Ice
tnxTower Job Page
BU 824338 10 of 14
• SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCI
• FAX(615)661-7569 15264
Load Vertical Shear, Shears Overturning Overturning Torque
Combination Moment,M Moment,M
K K K lap-/t kep J1 kip ft
0.9 Dead+1.6 Wind 30 deg-No 21.94 10.72 -17.88 -1601.26 -963.29 -0.97
Ice
1.2 Dead+1.6 Wind 60 deg-No 29.25 18.54 -10.32 -935.73 -1687.30 -1.24
Ice
0.9 Dead+l.6 Wind 60 deg-No 21.94 18.54 -10.32 -923.66 -1665.89 -1.24
Ice
1.2 Dead+1.6 Wind 90 deg-No 29.25 22.56 -0.01 -1.71 -2022.73 -1.12
Ice
0.9 Dead+1.6 Wind 90 deg-No 21.94 22.56 -0.01 -1.53 -1997.64 -1.12
Ice
1.2 Dead+1.6 Wind 120 deg- 29.25 19.34 10.75 953.63 -1725.47 -0.71
No Ice
0.9 Dead+1.6 Wind 120 deg- 21.94 19.34 10.75 941.80 -1703.80 -0.71
No Ice
1.2 Dead+1.6 Wind 150 deg- 29.25 10.87 18.15 1636.08 -984.34 -0.11
No Ice
0.9 Dead+1.6 Wind 150 deg- 21.94 10.87 18.15 1615.53 -971.90 -0.11
No Ice
1.2 Dead+1.6 Wind 180 deg- 29.25 -0.02 20.61 1868.47 2.23 0.47
No Ice
0.9 Dead+1.6 Wind 180 deg- 21.94 -0.02 20.61 1845.16 2.21 0.47
No Ice
1.2 Dead+1.6 Wind 210 deg- 29.25 -10.72 17.89 1622.12 975.47 0.96
No Ice
▪ 0.9 Dead+1.6 Wind 210 deg- 21.94 -10.72 17.89 1601.65 963.09 0.96
No Ice
1.2 Dead+1.6 Wind 240 deg- 29.25 -18.51 10.33 935.97 1684.11 1.20
No Ice
0.9 Dead+1.6 Wind 240 deg- 21.94 -18.51 10.33 924.23 1662.74 1.20
No Ice
1.2 Dead+1.6 Wind 270 deg- 29.25 -22.50 0.03 2.74 2015.33 1.12
No Ice
0.9 Dead+l.6 Wind 270 deg- 21.94 -22.50 0.03 2.87 1990.34 1.12
No Ice
1.2 Dead+1.6 Wind 300 deg- 29.25 -1927 -10.75 -955.17 1717.95 0.71
No Ice
0.9 Dead+1.6 Wind 300 deg- 21.94 -19.27 -10.75 -942.98 1696.39 0.71
No Ice
1.2 Dead+1.6 Wind 330 deg- 29.25 -10.84 -18.17 -1639.25 981.33 0.13
No Ice
0.9 Dead+1.6 Wind 330 deg- 21.94 -10.84 -18.17 -1618.32 968.93 0.13
No Ice
1.2 Dead+1.0 Ice+1.0 Temp 66.93 -0.00 0.00 -6.39 0.34 0.00
1.2 Dead+l.0 Wind 0 deg+1.0 66.93 0.02 -2.53 -271.41 -1.23 0.04
Ice+1.0 Temp
1.2 Dead+1.0 Wind 30 deg+1.0 66.93 1.30 -2.19 -236.46 -136.02 -0.03
Ice+1.0 Temp
1.2 Dead+1.0 Wind 60 deg+1.0 66.93 2.24 -1.27 -139.84 -234.34 -0.10
Ice+1.0 Temp
1.2 Dead+1.0 Wind 90 deg+1.0 66.93 3.14 -0.01 -7.84 -309.61 -0.13
Ice+1.0 Temp
1.2 Dead+1.0 Wind 120 66.93 2.49 1.40 131.41 -245.32 -0.13
deg+1.0 Ice+1.0 Temp
1.2 Dead+1.0 Wind 150 66.93 1.33 2.27 227.61 -137.05 -0.09
deg+1.0 Ice+l.0 Temp
• 1.2 Dead+1.0 Wind 180 66.93 -0.01 2.52 257.99 1.78 -0.04
deg+1.0 Ice+1.0 Temp
1.2 Dead+1.0 Wind 210 66.93 -1.30 2.19 223.56 136.63 0.03
deg+1.0 Ice+1.0 Temp
• 1.2 Dead+1.0 Wind 240 66.93 -2.24 1.27 126.97 234.58 0.09
deg+1.0 Ice+1.0 Temp
Job Page
tnxTower BU 824338 11 of 14
SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN37027 Client Designed by
Phone:(615)309-1994 CCI
FAX:(615)661-7569 15264
Load Vertical Shear, Shear, Overturning Overturning Torque
Combination Moment,M, Moment,M,
K K K kip f kip f} hip ft
1.2 Dead+1.0 Wind 270 66.93 -3.13 0.02 4.93 309.34 0.13
deg+1.0 Ice+l.0 Temp
1.2 Dead+1.0 Wind 300 66.93 -2.48 -1.40 -144.50 245.05 0.13
deg+1.0 Ice+1.0 Temp
1.2 Dead+1.0 Wind 330 66.93 -1.33 -2.27 -240.90 137.34 0.10
deg+1.0 Ice+1.0 Temp
Dead+Wind 0 deg-Service 24.38 0.01 -5.75 -518.45 -0.85 -0.14
Death-Wind 30 deg-Service 24.38 2.98 -4.98 448.94 -269.80 -0.27
Dead+Wind 60 deg-Service 24.38 5.16 -2.87 -259.16 466.63 -0.35
Dead+Wind 90 deg-Service 24.38 6.28 -0.00 -0.85 -559.77 -0.32
Dead+Wind 120 deg-Service 24.38 5.38 2.99 263.38 -477.23 -0.20
Dead+Wind 150 deg-Service 24.38 3.03 5.05 452.08 -272.21 -0.03
Dead+Wind 180 deg-Service 24.38 -0.01 5.74 516.54 0.63 0.13
Dead+Wind 210 deg-Service 24.38 -2.98 4.98 448.20 269.77 0.27
Dead+Wind 240 deg-Service 24.38 -5.15 2.88 258.47 465.77 0.34
Dead+Wind 270 deg-Service 24.38 -6.27 0.01 0.38 557.73 0.31
Dead+Wind 300 deg-Service 24.38 -5.37 -2.99 -264.56 475.17 0.20
Dead+Wind 330 deg-Service 24.38 -3.02 -5.06 -453.71 271.40 0.04
Solution Summary
Sum of Applied Forces Sum of Reactions
Load PX PY PZ PX PY PZ %Error
Comb. K K K K K K
1 0.00 -24.38 0.00 0.00 24.38 -0.00 0.000%
2 0.03 29/5 -20.64 -0.03 29.25 20.63 0.023%
3 0.03 -21.94 -20.64 -0.03 21.94 20.64 0.018%
4 10.72 -29.25 -17.88 -10.72 29.25 17.88 0.001%
5 10.72 -21.94 -17.88 -10.72 21.94 17.88 0.001%
6 18.54 -29.25 -10.32 -18.54 29.25 10.32 0.001%
7 18.54 -21.94 -10.32 -18.54 21.94 10.32 0.001%
8 22.57 -29.25 -0.01 -22.56 29.25 0.01 0.024%
9 22.57 -21.94 -0.01 -22.56 21.94 0.01 0.019%
10 19.34 -29.25 10.75 -19.34 29.25 -10.75 0.001%
11 19.34 -21.94 10.75 -19.34 21.94 -10.75 0,001%
12 10.87 -29.25 18.15 -10.87 29.25 -18.15 0.001%
13 10.87 -21.94 18.15 -10.87 21.94 -18.15 0.001%
14 -0.02 -29.25 20.62 0.02 29.25 -20.61 0.023%
15 -0.02 -21.94 20.62 0.02 21.94 -20.61 0.018%
16 -10.72 -29.25 17.89 10.72 29.25 -17.89 0.001%
17 -10.72 -21.94 17.89 10.72 21.94 -17.89 0.001%
18 -18.51 -29.25 10.33 18.51 29.25 -10.33 0.001%
19 -18.51 -21.94 10.33 18.51 21.94 -10.33 0.001%
20 -22.51 -29.25 0.03 22.50 29.25 -0.03 0.024%
21 -22.51 -21.94 0.03 22.50 21.94 -0.03 0.019%
22 -19.27 -29.25 -10.75 19.27 29.25 10.75 0.001%
23 -19.27 -21.94 -10.75 19.27 21.94 10.75 0.001%
24 -10.84 -29.25 -18.17 10.84 29.25 18.17 0.001%
25 -10.84 -21.94 -18.17 10.84 21.94 18.17 0.001%
26 0.00 -66.93 0.00 0.00 66.93 -0.00 0.001%
27 0.02 -66.93 -2.53 -0.02 66.93 2.53 0.004%
28 1.30 -66.93 -2.20 -1.30 66.93 2.19 0.004%
29 2.24 -66.93 -1.27 -2.24 66.93 1.27 0.004%
30 3.14 -66.93 -0.01 -3.14 66.93 0.01 0.004%
31 2.49 -66.93 1.40 -2.49 66.93 -1.40 0.004%
32 1.33 -66.93 2.27 -1.33 66.93 -2.27 0.004%
•
33 -0.01 -66.93 2.53 0.01 66.93 -2.52 0.004%
34 -1.30 -66.93 2.20 1.30 66.93 -2.19 0.004%
Job Page
tnxTower
BU 824338 12 of 14
• SSOE GROUP
Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCU
• FAX: (615)661-7569 15264
Sum ofApplied Forces Sum of Reactions
Load PX PY PZ PX PY PZ %Error
Comb. K K K K K K
35 -2.24 66.93 1.28 2.24 66.93 -1.27 0.004%
36 -3.13 -66.93 0.02 3.13 66.93 -0.02 0.004%
37 -2.48 -66.93 -1.40 2.48 66.93 1.40 0,004%
38 -1.33 -66.93 -2.27 1.33 66.93 2.27 0.004%
39 0.01 -24.38 -5.75 -0.01 24.38 5.75 0.020%
40 2.99 -24.38 -4.98 -2.98 24.38 4.98 0.021%
41 5.17 -24.38 -2.87 -5.16 24.38 2.87 0.021%
42 6.29 -24.38 -0.00 -6.28 24.38 0.00 0.022%
43 5.39 -24.38 2.99 -5.38 24.38 -2.99 0.021%
44 3.03 -24.38 5.06 -3.03 24.38 -5.05 0.021%
45 -0.01 -24.38 5.75 0.01 24.38 -5.74 0.020%
46 -2.99 -24.38 4.98 2.98 24.38 4.98 0.021%
47 -5.16 -24.38 2.88 5.15 24.38 -2.88 0.021%
48 6.27 -24.38 0.01 6.27 24.38 -0.01 0.021%
49 -5.37 -24.38 -2.99 5.37 24.38 2.99 0.021%
50 -3.02 -24.38 -5.06 3.02 24.38 5.06 0.021%
• Non-Linear Convergence Results
Load Converged? Number Displacement Force
• Combination of Cycles Tolerance Tolerance
I Yes 4 0.00000001 0.00000001
2 Yes 6 0.00031640 0.00056541
3 Yes 6 0.00020748 0.00042283
4 Yes 9 0.00000001 0.00063461
5 Yes 9 0.00000001 0.00044699
6 Yes 9 0.00000001 0.00066339
7 Yes 9 0.00000001 0.00046685
8 Yes 6 0.00031279 0.00075630
9 Yes 6 0.00020497 0.00057010
10 Yes 9 0.00000001 0.00064817
II Yes 9 0.00000001 0.00045384
12 Yes 9 0.00000001 0.00064919
13 Yes 9 0.00000001 0.00045715
14 Yes 6 0.00031652 0.00058632
15 Yes 6 0.00020756 0.00044065
16 Yes 9 0.00000001 0.00065545
17 Yes 9 0.00000001 0.00046270
18 Yes 9 0.00000001 0.00063025
19 Yes 9 0.00000001 0.00044292
20 Yes 6 0.00031310 0.00071210
21 Yes 6 0.00020519 0.00053528
22 Yes 9 0.00000001 0.00066202
23 Yes 9 0.00000001 0.00046433
24 Yes 9 0.00000001 0.00064601
25 Yes 9 0.0000000I 0.00045478
26 Yes 5 0.00000001 0.00002811
27 Yes 7 0.00095123 0.00020949
28 Yes 7 0.00095094 0.00024223
29 Yes 7 0.00095093 0.00024388
30 Yes 7 0.00094693 0.00023200
31 Yes 7 0.00094819 0.00023635
32 Yes 7 0.00094970 0.00023163
33 Yes 7 0.00095122 0.00019771
34 Yes 7 0.00094958 0.00022713
35 Yes 7 0.00094865 0.00022800
Page
tnxTower
Job BU 824338 13 of 14
SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client I Designed by
Phone:(615)309-1994 CCI •
FAX:(615)661-7569 15264
36 Yes 7 0.00094446 0.00022778
37 Yes 7 0.00094590 0.00024491
38 Yes 7 0.00094843 0.00024019
39 Yes 5 0.00069499 0.00048567
40 Yes 5 0.00069305 0.00067604
41 Yes 5 0.00069268 0.00084556
42 Yes 5 0,00069288 0.00053270
43 Yes 5 0.00069167 0.00072288
44 Yes 5 0.00069256 0.00073842
45 Yes 5 0.00069503 0.00048391
46 Yes 5 0.00069294 0.00078966
47 Yes 5 0.00069246 0.00066991
48 Yes 5 0.00069262 0.00052777
49 Yes 5 0.00069142 0.00081187
50 Yes 5 0.00069241 0.00072717
Compression Checks
Pole Design Data
Section Elevation Size L L. Kl/r A P. +P„ Ratio
•
No. P.
ft ft ft in' K K 4)P.
LI 130-80.9167 TP25.07x14.76x0.219 49.08 0.00 0.0 16.9196 -9.80 1146.98 0.009
(1)
L2 80.9167- TP32.16x23.7743x0.313 39.92 0.00 0.0 31.0563 -16.47 2196.08 0.007
45.0834(2)
L3 45.0834-0(3) TP41 x30.5011 x0.375 50.00 0.00 0.0 49.0547 -29.23 3341.22 0.009
Pole Bending Design Data
Section Elevation Size Al.,, 4 M.r Ratio Al,. Wm, Ratio
No. M„. M_
t kip f kip ft 4,M,,, kip-ft kiPf 4A1„„
LI 130-80.9167 TP25.07x14.76x0.219 396.66 559.98 0.708 0.00 559.98 0.000
(1)
L2 80.9167- TP32.16x23.7743x0.313 987.05 1375.58 0.718 0.00 1375.58 0.000
45.0834(2)
1.3 45.0834-0(3) TP41 x30.5011 x0.375 2022.72 2761.74 0.732 0.00 2761.74 0.000
Pole Shear Design Data
Section Elevation Size Actual +V„ Ratio Actual ;T„ Ratio
No. V V. T T. .
ft K K i v„ kip II kiPf 4)T
LI 130-80.9167 TP25.07x14.76x0.219 15.19 573.49 0.026 1.13 1135.47 0.001
(1)
L2 80.9167- TP32.16x23.7743x0.313 18.60 1098.04 0.017 1.12 2789.23 0.000
45.0834(2)
Job Page
tnxTower
BU 824338 14 of 14
- SSOE GROUP Project Date
320 Seven Springs Way,Suite 350 015-00428-00 16:12:09 05/21/15
Brentwood,TN 37027 Client Designed by
Phone:(615)309-1994 CCU
• FAX: (615)661-7569 15264
Section Elevation Si:e Actual 4)V Ratio Actual 4T Ratio
No. V. V„ T„ T
fi K K 01/, k+P f kip f OT
L3 45.0834-0(3) TP41x30.5011x0.375 22.59 1670.61 0.014 1.12 5599.95 0.000
Pole Interaction Design Data
Section Elevation Ratio Ratio Ratio Ratio Ratio Comb. Allow. Criteria
No. P. M. M, V, T Stress Stress
Jt OP. OM •M,,, 4Vn 4T Ratio Ratio
LI 130-80.9167 0.009 0.708 0.000 0.026 0.001 0.718 1.000 482 ✓
(1) V
L2 80.9167- 0.007 0.718 0.000 0.017 0.000 0.725 1.000 482 ✓
45.0834(2) 4/ +,
L3 45.0834-0(3) 0.009 0.732 0.000 0.014 0.000 0.741 1.000 482 y
V
Section Capacity Table
Section Elevation Component Sire Critical P oPdm,. % Pass
No. ft Type Element K K Capacity Fail
LI 130-80.9167 Pole TP25.07x14.76x0.219 1 -9.80 1146.98 71.8 Pass
L2 80.9167- Pole TP32.16x23.7743x0.313 2 -16.47 2196.08 72.5 Pass
45.0834
13 45.0834-0 Pole TP41x30.5011x0.375 3 -29.23 3341.22 74.1 Pass
Summary ELC: Existing/Pro
posed(LC5)
Pole(L3) 74.1 Pass
Rating= 74.1 Pass
Program Version 6.1.4.1-12/17/2013 File:c:/dgn/d1532893BU-824338.eri
May 21, 2015
130 Ft Monopole Tower Structural Analysis CCI BU No 824338
Project Number 015-00428-00, Application 290281, Revision 1 Page 8
APPENDIX B
BASE LEVEL DRAWING
tnxTower Report-version 6.1.4.1
13A313SV8-3:01 213h101 8ffPL9 WWI SS3NISf18
enn3 A133VS
/M S93d ONIOIIID_\
-- 13$.31 1.1 06 01.11/G-1 (9)
':1.:',"1:11114!Itik
(031WISM)
M ----- •8
. . .
•
..
13A31 11 LZ l 01.9/0-1 (91) •o • /— f
13$.31 Li LZI 01 J/1-1 (l)
13A31 1i LZ1 01.Z/t (1) \ `
(a71sNp 13$.31 1i LZl 01.8/S-t (9l)
13A31 Li Lzl o1.6/9-0-t (e) ( ( Zo CO \ 13$.31 li LZl 01.Z/1 (t)
(a3AAN3H 38 ol-a311v1SM)
13$.3113 LZ1 01.9/1 (z) I I to t0 I I (03TNiSM)
(03SOdONd) \ \ / 1 NO3V38 li act 0l.0/1 (l)
13/31 Li 001 at owomo.9l/L (t)
13A31 Li 601 01.z/t (z) \ \ / / (a3TNiSM)
13A31 Li 601 01.9l/L (1) \ _i /
13A31 li 601 01 ONA08O.91/L (l) \
13131 li 601 01.9/f(f) \
13$.31 li 601 0l.t/t (f) ■(Q371V1SM) _
13A3)13 06 01.8/0-t (L) 13/91 Li 8l1 OL.8/S-1 (9)
•
13$.31 1.1 06 01.0/1 (1) (ar1HLSM)
(0311v1SM)
1
f0M
Ir
May 21, 2015
130 Ft Monopole Tower Structural Analysis CC/BU No 824338
Project Number 015-00428-00, Application 290281, Revision 1 Page 9
APPENDIX C
ADDITIONAL CALCULATIONS
tnxTower Report-version 6.1.4.1
Stiffened or Unstiffened, Ungrouted, Circular Base Plate - Any Rod Material
TIA Rev G Assumption: Clear space between bottom of leveling nut and top of concrete not exceeding (1)*(Rod Diameter)
Site Data Reactions
BU#: 824338 Mu: 2022.73 ft-kips
Site Name: Greenburg Axial, Pu: 29.25 .kips
App#: 290281 Rev. 1 Shear.Vu:, 22.56 kips
Pole Manufacturer:I Other Eta Factor, n 0.55 TIA G(Fig. 4-4)
Anchor Rod Data If No stiffeners,Criteria I AISC LRFD <-Only Applcable to Unstiffened Cases
Qty: 12
Diam: 2.25 in
Rod Material: A615-J Anchor Rod Results Rigid
Strength (Fu): 100 ksi Max Rod (Cu+Vu/rj): 171.1 Kips AISC LRFD
Yield (Fy): 75 ksi Allowable Axial, D'Fu"Anet: 260.0 Kips cp'Tn
Bolt Circle: 48.95 in Anchor Rod Stress Ratio: 65.8% Pass
Plate Data
Diam: 54.95 in Base Plate Results Flexural Check Rigid
Thick: 2.75 in Base Plate Stress: 20.1 ksi AISC LRFD
Grade: 60 ksi Allowable Plate Stress: 54.0 ksi cp`Fy
Single-Rod B-eft 10.99 in Base Plate Stress Ratio: 37.3% Pass Y L Length:
26.74
Stiffener Data (Welding at both sides) n/a
Config: 0 Stiffener Results
Weld Type: Horizontal Weld : n/a
Groove Depth: in ** Vertical Weld: n/a
Groove Angle: degrees Plate Flex+Shear,fb/Fb+(fv/Fv)^2: n/a
Fillet H. Weld: <-- Disregard Plate Tension+Shear,ft/Ft+(fv/Fv)^2 n/a
Fillet V. Weld: in Plate Comp. (AISC Bracket): n/a
Width: in
Height: in Pole Results
Thick: in Pole Punching Shear Check: n/a
Notch: in
Grade: ksi
Weld str.: ksi
Pole Data
Diam: 41 in
Thick: 0.375 in
Grade: 65 ksi
#of Sides: 12 "0"IF Round
Fu 80 ksi
Reinf. Fillet Weld 0 "0" if None n
*0=none, 1 =every bolt,2=every 2 bolts, 3=2 per bolt
"Note:for complete joint penetration groove welds the groove depth must be exactly 1/2 the stiffener thickness for calculation purposes
CClplate 1.5-Circular Base G 1.3, Effective March 19, 2012 Analysis Date: 5/21/2015
88 ssoeM
Caisson Analysis(G)
824338
015-00428-00
Moment= 2022.73 k*ft
Axial= 29.25 k
Shear= 22.56 k
Foundation Data
Diameter= 5.5 ft
Length= 28 ft
Rebar Size= #10
#of bars= 20
Tie Size= #3
Clear Cover= 3 in
f'c= 4 ksi
Soil Capacity From Caisson Program Usina Additional Safety Factors
Additional Safety Factor from Caisson= 1.85
Phi(Soil)= 0.75
Capacity= 1/phi(soil) 1.33
71.9% O.K.
Additional Safety Factor 1.85
Moment Capacity of Drilled Concrete Shaft (Caisson) for TIA Rev F or G
Note: Shaft assumed to have ties, not s__piral,transverse reinforcing
Site Data Maximum Shaft Superimposed Forces
BU#: 824338 TIA Revision: G
Site Name: Greenburg Max. Factored Shaft Mu: 2155.96 ft-kips(*Note)
App#: 290281 Max. Factored Shaft Pu: 29.25 kips
Max Axial Force Type: Comp.
(*)Note: Max Shaft Superimposed Moment does not necessarily
Loads Already Factored equal to the shaft top reaction moment
For M(WL) 1.3 <----Disregard
For P(DL) 1.3 <----Disregard Load Factor Shaft Factored Loads
1.00 Mu: 2155.96 ft-kips
Pier Properties 1.00 Pu: 29.25 kips
Concrete:
Pier Diameter= 5.5 ft Material Properties
Concrete Area = 3421.2 in2 Concrete Comp. strength, fc= 4000 psi
Reinforcement yield strength, Fy= 60 ksi
Reinforcement: Reinforcing Modulus of Elasticity, E= 29000 ksi
Clear Cover to Tie= 3.00 in Reinforcement yield strain= 0.00207
Horiz. Tie Bar Size= 3 Limiting compressive strain =I 0.003
Vert. Cage Diameter= 4.83 ft ACI 318 Code
Vert. Cage Diameter= 57.98 in Select Analysis ACI Code=1 2008
Vertical Bar Size= 10 Seismic Properties
Bar Diameter= 1.27 in Seismic Design Category= D
• Bar Area = 1.27 in2 Seismic Risk = High
Number of Bars = 20
As Total= 25.4 in2 Solve <--Press Upon Completing All Input
A s/Aconc, Rho: 0.0074 0.74% (Run)
ACI 10.5 ,ACI 21.10.4, and IBC 1810. Results:
Min As for Flexural, Tension Controlled, Shafts: Governing Orientation Case: 1
(3)*(Sgrt(fc)/Fy: 0.0032
200/Fy: 0.0033 �
Mu i ���. Mu � ��t 8
■
i
Case 1 Case 2
Dist. From Edge to Neutral Axis: 10.58 in
Extreme Steel Strain, Et: 0.0146
Minimum Rho Check: et>0.0050, Tension Controlled
Actual Req'd Min. Rho: 0.33% Flexural Reduction Factor,cp: 0.900
Provided Rho: 0.74% OK
Ref. Shaft Max Axial Capacities, 4 Max(Pn or Tn):
Max Pu = 4=0.65) Pn. Output Note: Negative Pu=Tension
Pn per ACI 318 (10-2) 6796.24 kips For Axial Compression, cp Pn = Pu: 29.25 kips
at Mu=(4=0.65)Mn= 3239.23 ft-kips Drilled Shaft Moment Capacity, cpMn: 3154.12 ft-kips
Drilled Shaft Superimposed Mu: 2155.96 ft-kips
Max Tu, 4=0.9) Tn = 1371.6 kips
at Mu=4=(0.90)Mn= 0.00 ft-kips (Mu/cpMn,Drilled Shaft Flexure CSR: l 68.4%
Drilled_Shaft_Moment_Capacity, DSMC, Version 1.1 -Effective 04/01/2010 Analysis Date: 5/21/2015
CAISSON Version 12.10 4:14:21 PM Thursday, May 21, 2015
SSOE Group
**************************************************************************************************
* *
* CAISSON - Pier Foundations Analysis and Design - Copyright Power Line Systems, Inc. 1993-2011 *
* *
**************************************************************************************************
Project Title: BU# 824338
Project Notes: Greenburg
Calculation Method: Full 8CD
******* I N P U T D A T A
Pier Properties
Diameter Distance Concrete Steel
of Top of Pier Strength Yield
above Ground Strength
(ft) (ft) (ksi) (ksi)
5.50 1.00 4.00 60.00
Soil Properties
Layer Type Thickness Depth at Top Density CU KP PHI
of Layer
(ft) (ft) (lbs/ft^3) (psf) (deg)
1 Clay 3.00 0.00 115.0
2 Sand 9.00 3.00 115.0 3.000 30.00
3 Clay 16.00 12.00 120.0 600.0
Design (Factored) Loads at Top of Pier
Moment Axial Shear Additional Safety
Load Load Factor Against
Soil Failure
(ft-k) (kips) (kips)
SSOE Group Page 1/4
2022.7 29.3 22.56 1.85
******* R E S U L T S
2925 Idp* 26.a.Kies
V2200064 T77 11(S4
1==.1414.2odgmc Agolg al ly t
.)
. ................... '
31 WES
.?S:roP AOL1efDl151iAClltlpff4
5' (1:
3e'_':I6" j
.a
r'
26.40 psn
5431.t6;ps., IESAAM r: I IF ___ ._
.5
!29.0 (aP%'
yr
__-\ SOIL REACTIONS OK6RAM SIBR Ci:.CiR.%fl C.610 CiAG AA1:'
f
)
Calculated Pier Properties
Length Weight Pressure Pressure Total
Due To Due To End-Bearing
Axial Load Weight Pressure
(ft) (kips) (psf) (psf) (psf)
28.000 99.785 1231.2 4200.0 5431.2
Ultimate Resisting Forces Along Pier
Type Distance of Top of Layer Thickness Density CU KP Force Arm
SSOE Group Page 2/4
to Top of Pier
(ft) (ft) (lbs/ft^3) (psf) (kips) (ft)
Clay 1.00 3.00 115.0 0.00 2.50
Sand 4.00 9.00 115.0 3.000 384.24 9.40
Clay 13.00 1.02 120.0 600.0 26.98 13.51
Clay 14.02 13.98 120.0 600.0 -369.02 21.01
Shear and Moments Along Pier
Distance below Shear Moment Shear Moment
Top of Pier (with Safety Factor) (with Safety Factor) (without Safety Factor) (without Safety Factor)
(ft) (kips) (ft-k) (kips) (ft-k)
0.00 42.2 3777.1 22.8 2041.7
2.80 42.2 3895.3 22.8 2105.6
5.60 7.6 3987.7 4.1 2155.5
8.40 -88.0 3885.5 -47.6 2100.2
11.20 -228.3 3453.0 -123.4 1866.5
14.00 -368.4 2587.2 -199.2 1398.5
16.80 -295.7 1655.8 -159.8 895.0
19.60 -221.8 931.4 -119.9 503.5
22.40 -147.8 414 .0 -79.9 223.8
25.20 -73.9 103.5 -40.0 55.9
28.00 -0.0 -0.0 -0.0 -0.0
Reinforcement and Capacity
Total Reinforcement Usable Usable
Reinforcement Area Axial Moment
Percent Capacity Capacity
(in^2) (kips) (ft-k)
0.54 18.47 29.3 2226.5
US Standard Re-Bars (Select one of the following)
Quantity Name Area Diameter Spacing
(in^2) (in) (in)
93 #4 0.20 0.500 1.89
60 #5 0.31 0.625 2.93
42 #6 0.44 0.750 4.19
SSOE Group Page 3/4
31 #7 0.60 0.875 5.68
24 #8 0.79 1.000 7.33
19 #9 1.00 1.128 9.26
15 #10 1.27 1.270 11.73
12 #11 1.56 1.410 14.66
9 #14 2.25 1.693 19.55
SSOE Group Page 4/4