Report Generated by ical COMcheck-Web Compliance Software
jp.Ar
Mechan g
3UL 9 2015
2014 Oregon Energy Efficiency Specialty Code LIT OV'MN"
Section 1 : Project Information BU1LD1 1 pIV[SIO ,
Project Type: a W-✓per-"""''
Envelope Compliance Method: Simplified Trade-Off
Project Title :
Construction Site: Owner/Agent: Designer/Contractor:
Section 2: General Information
Building Location(for weather data): Adair Village,Oregon
Climate Zone: 4c
Section 3: Mechanical Systems List
Quantity System Type&Description
1 HVAC System(Unknown):
Heating: 1 each-Central Furnace,Gas, Capacity=60 kBtu/h
Proposed Efficiency=95.00%Et,Required Efficiency=80.00%Et
Cooling: 1 each-Split System,Capacity=36 kBtu/h,Air-Cooled Condenser, Unknown Economizer
Proposed Efficiency= 13.00 SEER,Required Efficiency= 13.00 SEER
Fan System: Unspecified
Section 4: Requirements Checklist
In the following requirements, blank checkboxes identify requirements that the applicant has not acknowledged as being met. Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Requirements Specific To: HVAC System :
art. Equipment meets minimum efficiency: Central Furnace(Gas): 80.00%Et(or 78%AFUE)
1 `. Equipment meets minimum efficiency: Split System: 13.00 SEER
uk3. Energy recovery ventilation systems.Individual fan systems that have both a design supply air capacity of 5,000 cfm or greater and a
minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system.
Exception(s)
J Where energy recovery systems are prohibited by the International Mechanical Code.
J Systems serving spaces that are not cooled and are heated to less than 60°F.
U Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy.
J Type 1 kitchen exhaust hoods.
j Cooling systems in climates with a 1-percent cooling design wet-bulb temperature less than 64°F(18°C).
J Systems requiring dehumidification that employ series-style energy recovery coils wrapped around the cooling coil when the
evaporative coil is located upstream of the exhaust air stream.
J Systems exhausting toxic,flammable,paint exhaust,corrosive fumes,or dust.
• Laboratory fume hood systems that include qualifying features.
Plans reference page/section:
G�e(ieric Requirements: Must be met by all systems to which the requirement is applicable:
1. Calculation of heating and cooling loads. Design loads are determined in accordance with the procedures described in the
ASHRAE/ACCA Standard 183.Alternatively,design loads have been determined by an approved equivalent computation procedure.
Project Title: Report date: 07/08/15
Data filename: Page 6 of 10
J 2. Packaged Electric Equipment.Specified packaged electrical equipment has a heat pump as the primary heating source.
Nn" Exception(s)
j Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities.
j Requirement is not applicable.
Plans reference page/section:
Cooling equipment economizers:The total capacity of all cooling equipment without economizers must be less than 240 kBtu/h. This
project lists 36 kBtu/h capacity without economizers.That portion of the equipment serving dwelling units and guest rooms is not
included in determining the total capacity of units without economizers.
Plans reference page/section:
4+' Equipment and system sizing. Heating and cooling equipment and systems capacity do not exceed the loads calculated in accordance
with Section 503.2.1.
Exception(s):
J Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate
automatically only when the primary equipment is not operating.
J Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that
have the capability to sequence the operation of each unit based on load.
Plans reference page/section:
,+iVAC Equipment Performance Requirements.Reported efficiencies have been tested and rated in accordance with the applicable test
procedure.The efficiency has been verified through certification under an approved certification program or, if no certification program
exists,the equipment efficiency ratings are supported by data furnished by the manufacturer.
Thermostatic Controls.The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that
respond to temperature within the zone.
Plans reference page/section:
Li 7. Heat pump supplementary heat. Heat pumps having supplementary electric resistance heat have controls that,except during defrost,
//if—prevent supplementary heat operation when the heat pump can meet the heating load.
Plans reference page/section:
La_8"-Set point overlap restriction.Where used to control both heating and cooling,zone thermostatic controls provide a temperature range
or deadband of at least 5°F(2.8°C)within which the supply of heating and cooling energy to the zone is capable of being shut off or
reduced to a minimum.
Exception(s)
J Thermostats requiring manual change over between heating and cooling modes.
Plans reference page/section:
�6ptimum Start Controls.Each HVAC system has controls that vary the start-up time of the system to just meet the temperature set
point at time of occupancy.
Plans reference page/section:
LyO.Off-hour controls. Each zone is provided with thermostatic setback controls that are controlled by either an automatic time clock or
programmable control system.
Exception(s):
• Zones that will be operated continuously.
ZI Zones with a full HVAC load demand not exceeding 6,800 Btu/h(2 kW)and having a readily accessible manual shutoff switch.
Plans reference page/section.
11.Shutoff damper controls.Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers.
iv Exception(s):
J Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less.
Plans reference page/section:
12.Freeze Protection and Snow melt system controls. Freeze protection systems,such as heat tracing of outdoor piping and heat
Nrexchangers,including self-regulating heat tracing, include automatic controls capable of shutting off the systems when outdoor air
temperatures meet code criteria.
Plans reference page/section:
Project Title: Report date: 07/08/15
Data filename: Page 7 of 10
J 13.Separate air distribution systems.Zones with special process temperature requirements and/or humidity requirements are served by
/ti/r—separate air distribution systems from those serving zones requiring only comfort conditions,or shall include supplementary control
provisions so that the primary systems may be specifically controlled for comfort purposes only.
Exception(s):
3 [503.2.4.8+]Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process
temperature and humidity control.
Plans reference page/section.
U 14.Humidity control.If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a zone or
N� zones,a humidity control device is provided.
Plans reference page/section:
J 15.Humidity control.Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce relative
humidity in excess of 30 percent.Where a humidity control device is used for dehumidification, it is set to prevent the use of fossil fuel
N// or electricity to reduce relative humidity below 60 percent.
Exception(s):
3 Hospitals,process needs,archives,museums,critical equipment,and other non-comfort situations with specific humidity
requirements outside this range.
Plans reference page/section:
J 16.Humidity control.Where a humidity control device exists it is set to maintain a deadband of at least 10%relative humidity where no
active humidification or dehumidification takes place.
Ai/ Exception(s):
• Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10
percent higher than required in section 503.2.3, HVAC equipment performance requirements.
Plans reference page/section:
teriVentilation.Ventilation,either natural or mechanical,is provided in accordance with Chapter 4 of the International Mechanical Code.
Where mechanical ventilation is provided,the system has the capability to reduce the outdoor air supply to the minimum required by
Chapter 4 of the International Mechanical Code.
Plans reference page/section.
▪ 18.Demand controlled ventilation(DCV). DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger than 150 ft2
Syr for multiple zone systems.
Exception(s):
3 Systems with energy recovery complying with Section 503.2.6
3 Spaces less than 750 ft2(69.7 m2)where an occupancy sensor turns the fan off,closes the ventilation damper,or closes the
zone damper when the space is unoccupied.
Plans reference page/section:
LI 19.Kitchen hoods. Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code.
N. Exception(s):
❑ Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems.
O Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6.
Plans reference page/section:
J 20.Enclosed parking garage ventilation controls.In Group S-2,enclosed parking garages used for storing or handling automobiles employs
Rlj--- automatic carbon monoxide sensing devices.
Plans reference page/section.
▪ 21.Duct and plenum insulation and sealing.All supply and return air ducts and plenums are insulated with the specified insulation.When
/to.. located within a building envelope assembly,the duct or plenum is separated from the building exterior or unconditioned or exempt
spaces by a minimum of R-8 insulation.All ducts,air handlers and filter boxes are sealed.Joints and seams comply with Section 603.9
of the International Mechanical Code.
Exception(s):
3 When located within equipment.
• When the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15°F(8"C).
• 22.Low-pressure duct systems.All longitudinal and transverse joints.seams and connections of low-pressure supply and return ducts are
1,„f-�, securely fastened and sealed with welds,gaskets,mastics(adhesives),mastic-plus-embedded-fabric systems or tapes installed in
accordance with the manufacturer's installation instructions.
Exception(s):
Project Title: Report date: 07/08/15
Data filename: Page 8 of 10
J Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g.
pressure classification.
Plans reference page/section:
• 23.Medium-pressure duct systems.All ducts and plenums designed to operate medium-pressure are insulated and sealed in accordance
�,L�
t— with Section 503.2.7. Pressure classifications specific to the duct system are clearly indicated on the construction documents.
Plans reference page/section:
J 24.High-pressure duct systems. Ducts designed to operate at high-pressure are insulated and sealed in accordance with Section 503.2.7.
Lit_ In addition,ducts and plenums are leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual.
Plans reference page/section:
▪ 25.Air system balancing. Each supply air outlet and zone terminal device is equipped with means for air balancing in accordance with the
,U/--requirements of IMC 603.17. Discharge dampers intended to modulate airflow are prohibited on constant volume fans and variable
volume fans with motors 10 horsepower.
Plans reference page/section:
6.Manuals. The construction documents require that an operating and maintenance manual be provided to the building owner by the
mechanical contractor.See long description for specifications.
Plans reference page/section:
• 27.Air System Design and Control.Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets the provisions
A44----of Sections 503.2.10.1 through 503.2.10.2.
Plans reference page/section:
• 28.Allowable fan floor horsepower. Each HVAC system at fan system design conditions does not exceed the allowable fan system motor
,O-- nameplate hp(Option 1)or fan system bhp(Option 2)as shown and calulated in requirement details.
Exception(s).
• Hospital and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure relationships
necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation.
• Individual exhaust fans with motor nameplate horsepower of 1 hp or less.
Plans reference page/section:
❑ 29.Motor nameplate horsepower.For each fan,the selected fan motor is no larger than the first available motor size greater than the brake
horsepower(bhp).
NA-Exception(s):
• For fans less than 6 bhp.where the first available motor larger than the brake horsepower has a nameplate rating within 50
percent of the bhp,selection of the next larger nameplate motor size is allowed.
Li For fans 6 bhp and larger,where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp,
selection of the next larger nameplate motor size is allowed.
Plans reference page/section:
J 30.Large Volume Fan Systems. Fan systems over 8,000(7 m3/s)cfm without direct expansion cooling coils that serve single zones reduce
A/4- airflow based on space thermostat heating and cooling demand.A two-speed motor or variable frequency drive reduces airflow to a
maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical
Code,whichever is greater.
Exception(s):
J Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity
levels or supplying an exhaust system.
Plans reference page/section:
▪ 31.All air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at ARI conditions greater than
or equal to 110,000 Btu/h that serve single zones have their supply fan operation controlled according to code specific requirements.
Exception(s):
J Systems where the function of the supply air is for purposes other than temperature control, such as maintaining specific humidity
levels or supplying an exhaust system.
Plans reference page/section:
• 32.Series fan-powered terminal unit fan motors.Fan motors for series fan-powered terminal units are electronically-commutated motors
/0.--and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1-2006 at full load rating
conditions.
Plans reference page/section:
Project Title: Report date: 07/08/15
Data filename: Page 9 of 10
33.Hot Gas Bypass Limitation.For cooling systems<=240 kBtu/h,maximum hot gas bypass capacity is no more than 50%total cooling
4/,,. - capacity.
Plans reference page/section:
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications
and other calculations submitted with this permit application.The proposed mechanical systems have been designed to meet the 2014 Oregon
Energy Efficiency Specialty Code requirements in COMcheck-Web and to comply with th- andato re. it ents in the Requirements
Checklist.
(76442.-.:ce 7/6-P4'1.-/7/ 4
Name-Title Sig . ure Date
Section 6: Post Construction Compliance Statement
HVAC record drawings of the actual installation,system capacities,calibration information,and performance data for each equipment
provided to the owner.
HVAC O&M documents for all mechanical equipment .• system provided to the ner by the mechanical contractor.
43Alritten HVAC balancing and operations report prodded t •- o+rylner.
The above post construct' n requir ents have been/ompl 41d.
lip-4
Principal Mechanical Designer-Name Signature Date
Project Title: Report date: 07/08/15
Data filename: Page 10 of 10
RECEIVED
JUL 9 2015
A.
LHL Homes Office �'YUFTIGARD 111
BUILDING DIVISION
11580 SW 67th Ave
Tigard, OR 97223
Remove and replace an existing furnace and air conditioner like for like.
Carrier furnace
59SC5A060A
95% AFUE
Vent out roof two pipe with PVC. Use existing chimney as chase.
Reconnect to existing gas and electrical.
Carrier Air conditioner Q
24ABB336 •
rs
13 SEER.
m
Replace existing air conditioner like for like same location. ®�—tine
Remove and replace refrigeration line. V!
Reconnect to existing electrical.
OMSC 2014
402.1 and 402.2 Natural ventilation
Existing openable windows and doors exceed 4%of floor area.
Pyramid Heating and Cooling
9409 NE Colfax St SW BAYLOR ST
Portland, OR. 97220 •
503-786-9522
CCB #59382
01 150 FT
59SC5A
ComfortTM Series Single—Stage
4—Way Multipoise Carrier
Condensing Gas Furnace
Series 2 turn to the experts
Product Data
installation.
• Installation flexibility with a 360-degree rotating elbow.
' • More than twelve different venting options,including optional
through-the-cabinet downflow and horizontal venting.
Q • Ideal condensing furnace height 35"(889 mm)cabinet:short
enough for taller coils,but still allows enough room for service.
t • Silicon Nitride Power Heat"' Hot Surface Igniter.
• Aluminized-steel primary heat exchanger.
o • Stainless-steel condensing secondary heat exchanger.
LJ • High-quality corrosion-resistant prepainted steel cabinet with
C! I(I 7
hemmed edges for safety.
I • Factory-configured ready for upflow applications.
• Direct-vent/sealed combustion,single-pipe venting or ventilated
combustion air.
• PSC blower motor,single-speed inducer motor,and single-stage
gas valve.
\ • Self-diagnostics with SuperBrite LED.
Al1203 • Approved for Twinning applications(040-12 through 120-20
The 59SC5 Multipoise Comfort Series Condensing Gas Furnace sizes,only).
features energy efficiency of 95.5% AFUE gas efficiency and
workhorse PSC blower motor. This gas furnace also features • Propane convertible(See accessory list).
4-way multipoise installation flexibility, and is available in nine • Approved for Manufactured Housing/Mobile Home applications
model sizes. The 59SC5 can be vented for direct vent/two-pipe, (except 140,000 Btuh input)with MH accessory kit.
ventilated combustion air, or single-pipe applications. All units
• Convenient Air Purifier and Humidifier electrical connections.
meet California Air Quality Management District emission
requirements, are design certified in Canada, and are certified for • Residential installations may be eligible for consumer financing
mobile/manufactured home use. through the Retail Credit Program.
• Certified to leak 2%or less of nominal air conditioning CFM
STANDARD FEATURES delivered when pressurized to 1-in.water column with all
• 4-way multipoise design for upflow,downflow or horizontal present air inlets,air outlets,and condensate drain port(s)sealed.
,,,
E
a MCA CERTIFIED ;r'�'
Comfort
a I�
SERIES N I!.e 0 tteAHRI Certified..Mark indicates a y CERTIFIED
manulacturcr'a participation in the program.for *
verification of certification fur individual products.
,�90 1 go to www.ahridirectory.org.
Q a-fu GbcO
I
CASING RATED HEATING
DIMENSIONS(IN.) OUTPUTt HEATING AIRFLOW COOLING
SAP ORDERING CFM MOTOR HP
NO. Heating @ 0.5 ESP SPEED TAPS
H D W (BTUH)T AFUE CFM# ESP (in.W.C.)
(In.W.C.)
59SC5A040S14--10 35 29.5 14.2 39,000 95.5% 820 0.10 625-905 1/2-4
59SC5A040S17-12 35 29.5 17.5 39,000 95.5% 1000 0.10 650-1050 1/2-5
59SC5A080S14-10 35 29.5 14.2 58,000 95.5% 840 0.12 675-1130 1/2-4
..---,. 59SC5A060S17-14 35 29.5 17.5 58,000 _ 95.5% 980 0.12 650-1420 1/2-5 _i--
59SC5A080S17-16 35 29.5 17.5 78,000 95.5% 1040 0.15 810-1600 3/4-5
59SC5A080S21-20 35 29.5 21.0 78,000 95.5% 1695 0.15 1335-1970 . 1 -5
59SC5A100S21-14 35 29.5 21.0 97,000 95.5% 1510 0.20 915-1545 1/2-4
59SC5A100S21-20 35 29.5 21.0 97,000 95.5% 1680 0.20 1345-2085 1-5
59SC5A120S24--20 35 ' 29.5 24.5 117,000 95.5% 2245 0.20 1320-2105 1-5
59SC5A140S24-20 35 29.5 24.5 135,000 95.5% 2175 0.20 1290-2035 1-5
t Capacity in accordance with DOE test procedures. Ratings are position dependent. See rating plate.
Heating CFM at factory default blower motor heating tap settings.
ESP-External Static Pressure
a FEATURES AND BENEFITS
j Direct or Single-pipe Venting, or Optional Ventilated
HYBRID HEAT®Dual Fuel system-This system can provide
CI) Combustion Air - This furnace can be installed as a 2-pipe
orn more control over your monthly energy bills by automatically
in (Direct Vent) furnace, in an optional ventilated combustion air
selecting the most economical method of heating. With HYBRID application, or in single-pipe, non-direct vent applications. This
HEAT components,our system automatically switches between the provides added flexibility to meet diverse installation needs.
gas furnace and the single-stage electric heat pump as outside
temperatures change to maintain greater efficiency and comfort Sealed Combustion System-This furnace brings in combustion
than with any traditional single-source heating system. The heat air from outside the furnace, which results in especially quiet
pump also delivers high-efficiency cooling in the summer. operation. By sealing the entire combustion vestibule, the entire
Power Heat" Igniter-Carrier's unique SiN igniter is not only furnace can be made quieter,not just the burners.
physically robust but it is also electrically robust. It is capable of Monoport Burners - The burners are specially designed and
running at line voltage and does not require complex voltage finely tuned for smooth, quiet combustion and economical
regulators as do other brands.This unique feature further enhances operation.
the gas furnace reliability and continues Carrier's tradition of Bottom Closure - Factory-installed for side return; easily
technology leadership and innovation in providing a reliable and removable for bottom return. The multi-use bottom closure can
durable product. also serve for roll-out protection in horizontal applications,and act
Reliable Heat Exchanger Design-The aluminized steel, clam as the bottom closure for the optional return air base accessory.
shell primary heat exchanger was re-engineered to achieve greater Blower Access Panel Switch - Automatically shuts off 115-v
efficiency out of a smaller size. The first two passes of the heat power to furnace whenever blower access panel is opened.
exchanger are based on the current 80% product, a design with Quality Registration - Our furnaces are engineered and
more than ten years of field-proven performance and success. manufactured under an ISO 9001 registered quality system.
These innovations, paired with the continuation of a crimped, Certifications - This furnace is CSA (AGA and CGA) design
no-weld seam create an efficient, robust design for this essential certified for use with natural and propane gases. The furnace is
component. factory-shipped for use with natural gas. A CSA listed gas
The condensing heat exchanger, a stainless steel fin and tube conversion kit is required to convert furnace for use with propane
design, is positioned in the furnace to extract additional heat. gas.The efficiency is AHRI efficiency rating certified.This furnace
Stainless steel coupling box componentry between heat exchangers meets California Air Quality Management District emission
has exceptional corrosion resistance in both natural gas and requirements.
propane applications.
4-Way Multipoise Design - One model for all applications -
there is no need to stock special downflow or horizontal models
when one unit will do it all. The new heat exchanger design allows
these units to achieve the certified AFUE in all positions.
2
SPECIFICATIONS
The furnace should be sized to provide 100 percent of the design method to calculate heating load estimates and select the furnace.
heating load requirement plus any margin that occurs because of Excessive oversizing of the furnace may cause the furnace and/or
furnace model size capacity increments. None of the furnace vent to fail prematurely,customer discomfort and/or vent freezing.
model sizes can be used if the heating load is 20,000 BTU or Failure to follow these guidelines is considered faulty installation
lower. Use Air Conditioning Contractors of America (Manual J and/or misapplication of the furnace;and resulting failure,damage,
and S); American Society of Heating, Refrigerating, and or epairs may impact warranty coverage.
Air-Conditioning Engineers; or other approved engineering
Heating Capacity and Efficiency 040-10 040-12 060-10 060-14 080-18 080-20 100-14 100-20 120-20 140-20
Input High (BTUH) 40,000 40,000 60,000 60,000 80,000 80,000 100,000 100,000 120,000 140,000
Heat
Output High (BTUH) 39,000 39,000 58,000 58,000 78,000 78,000 97,000 97,000 117,000 135,000
Heat
Certified Temperature 40-70 35-65 40-70 40-70 40-70 40-70 ' 40-70 40-70 40-70 45-75
Rise Range °F(°C) High Heat (22-39) (19-36) (22-39) (22-39) (22-39) (22-39) (22-39) (22-39) (22-39) (25-42)
Rated�ow Capacity and 6 Data - 040-10 040-12 0.12 -6.114 0.116, 080.20 100.14 100.20 1 r 40-
- X084. „„�.3 _ .,
0.20 0.20 0.20
Pressure(in.W.C.) Cooling 0.5 0.5 0.5 - 0.5 0.5 0.5 0.5 0.5 0.5 �0.5 N
Airflow Delivery High Heat 820 1000 840 980 1040 1895 1510 1680 2245 2175 0 co
Rated ESP(CFM) Cooling 905 1050 1130 1420 1600 1970 1545 2065 2105 2035
Cooling Capacity(tons) 400 CFM/ton 2 2.5 2.5 3.5 4 5 4 5 5 5 m
350 CFM/ton 2.5 3 3 4 4.5 5.5 4.5 6 6 6
Direct-Drive Motor Type Permanent Split Capacitor(PSC)
Direct-Drive Motor HP - 0.5 0.5 0.5 0.5 0.75 1 0.5 1 1 1
Motor Full Load Amps 6.2 6.8 8.2 8.8 ' 7.9 13.8 8.5 13.8 14.1 14.1
RPM Range 500-1150
Speed Selections 4 5 4 5 5 5 4 5 5 5
Blower NAleelDiaxWidth in. 11x7 11x8 11x7 11x8 11x8 11x10 11x10 11x10 11x11 11x11
Air Filtration System Field Supplied
Filter Used for Certified Watt Data* KGAWF**06UFR
Electrical Data .- 040-10 040-12 T060-10 1-060-14 f 080-16 080-20 .14 100-20 120-20 fl40-011
Input Voltage Volts-Hertz-Phase 115-60-1
Operating Voltage Range_l Min-Max 104-127
Maximum Input Amps Amps 6.8 8.3 7.0 8.4 9.6 14.5 7.6 14.6 14.9 14.9
Unit Ampacity Amps ' 9.5 11.4 -. 9.7 11.5 13.0 19.1 10.4 19.2 19.6 19.6
Minimum Wire Size AWG 14 14 14 14 14 12 14 12 12 12
Maximum Wire Length Feet 39 - 32 38 32 28 30 35 29 29 29
Minimum Wire Size (M) (11.9) (9.8) (11.6) (9.8) (8.5) (9.1) (10.7) (8.8) (8.8) (8.8)
Maximum Fuse/Ckt Bkr
(Time-Delay Type Recom- Amps 15 15 15 15 15 20 15 20 20 20
mended)
Transformer Capacity(24vac output) 40 VA
External Control Power Heating 27.9 VA
Available Cooling 34.6 VA
Controls 1 040-10 [040-12 1 060-10 1 060-14 1 080-16 L 080-20 i 100-14 1 100-20 1 120- 1110-20
Gas Connection Size 1/2"-NPT
Burners(Monoport) 2 2 3 3 4 4 5 5 6 7
Gas Valve(Redundant) Manufacturer White Rogers
Minimum Inlet Gas pressure(in.W.C.) 4.5
Maximum Inlet Gas pressure(in.W.C.) 13.6
Ignition Device Silicon Nitride
Limit Control 165 180 165 180 --- F7CM 200 180 180 160 155
Heating Blower Control(Heating Off-Delay) Adjustable:90, 120,150, 180 seconds
Cooling Blower Control(Time Delay Relay) 90 seconds
Communication System none
Thermostat Connections - Corn 24V,R,W,G,Y
Accessory Connections EAC(115vac);HUM(24vac)
* See Accessory List for part numbers available.
3
MODEL NUMBER NOMENCLATURE
Example of Model Number
1-2 3 4 5 6 7-9 10 11-12 13 14 15-16
Family Htg.Stages Tier Base Effy. Major Series Mg.Cap. Motor Width Voltage Minor Series Airflow
59 T N 6 A 060 V 17 -- _ 14
08- 800 CFM
Family 10-1000 CFM
S-Single Stage 12-1200 CFM
T-Two Stage 14-1400 CFM
M-Modulating 16-1600 CFM
18-1800 CFM
C-Comfort 20-2000 CFM
P-Performance
N-Infinity 0-.90 AFUE 14-14.2" 22-2200 CFM
2-.92AFUE 17-17.5" Minor Series
3-.93AFUE 21-21,0" Voltage
5-.95 AFUE 040=40,000 BTU 24 24.5
6-.96 AFUE 060=60,000 BTU S-Standard
7-+97 AFUE 080=80,000 BTU E-Energy Efficient
100=100,000 BTU V-Variable Speed
120=120,000 BTU
Major Series 140=140,000 BTU
Not all familes have these models.
A12373
Q
LO
0
en FURNACE COMPONENTS
m
LO HOT SURFACE
GAS BURNER IGNITER MANUAL RESET
ROLLOUT SWITCH
---iii.. '11
FLAME ills !w-_i- W -.I-,limn
SENSOR ,;;;��
MANUAL RESET
III, rag!. --,. rid •
ROLLOUT SWITCH +
GAS VALVE I �ip I MAIN LIMIT SWITCH
,1.–. ,�_ a (BEHIND GAS VALVE)
OPERATING INSTRUCTIONS
SHOWN(LOCATED ON ij ' =-
NOT
MAIN FURNACE DOOR,SEE �•' ' y'OPERATING INSTRUCTIONS _��_ ' !ti�
INSIDE DOOR FIGURE). - I =��C •–'�4,
1// , INDUCER MOTOR
O�'/ r `/��A ASSEMBLY
ELECTRICAL JUNCTION J_���
BOX(IF REQUIRED, "'t%‘;` 0
LOCATION MAY VARY) ii�'j— 7 j�M
j •
BLOWER DOOR 47 •0'•
SAFETY SWITCH I: - ; -4—MEDIA CABINET
am
(...... 0
FURNACE ' BLOWER AND
CONTROL MOTOR
BOARD • '
C1 2a -®'
' A f CAPACITOR/
1 POWER CHOKE
(IF USED)
RATING PLATE NOT SHOWN I
(LOCATED ON BLOWER DOOR) '
REPRESENTATIVE DRAWING ONLY,SOME MODELS MAY VARY IN APPEARANCE.
A11408
4
AIR DELIVERY - CFM (BOTTOM RETURN WITH FILTER)
UNIT SIZE RETURN-AIR SPEED EXTERNAL STATIC PRESSURE(IN.W.C.
CONNECTION TAPS 2 0.1 L 0.2 0.3 OA ( 0.5 O.q. -. 0.7111. 0.8 0.9 1.0
Black 1100 1055 j 1010 960 905 850 795 740 885 820
040-10 SIDE OR Yellow 955 915 875 830 790 740 695 645 590 530
BOTTOM Blue 820 795 765 730 895 655 615 570 515 460
Red 730 710 680 855 825 595 555 515 485 400
Black 1245 1195 1150 1100 1050 1000 945 890 830 775
SIDE OR Yellow 1185 1120 1075 1030 980 925 870 815 780 710
040-12 BOTTOM Orange 1045 1015 965 925 885 840 790 740 695 840
Blue 1000 960 930 890 850 810 785 715 685 815
Red 735 725 700 680 650 - 825 590 555 515 470
Black 1340 1295 1245 1190 1130 1065 1005 895 815 725
060-10 SIDE OR Yellow 1035 1010 980 945 910 885 795 730 685 805
BOTTOM Blue 845 825 810 785 755 710 670 825 570 515
Red 5 770 750 730 710 675 840 600 560 510 455
Black 1685 1615 1550 1485 1420 1345 1270 1190 1105 985
SIDE OR Yellow 1340 1320 1295 1280 1215 1185 1110 1045 925 850
060-14 BOTTOM Orange 1050 1045 1035 1015 995 980 915 845 785 725
Q Blue 985 980 975 950 930 900 845 795 740 690
u7
N Red 5 735 720 700 875 850 620 595 560 520 480
Black 1870 1810 1740 1670 1600 1525 1440 1355 1270 1180
Yellow 1525 1495 1480 1415 1365 1305 1240 1170 1090 990
080-16 SIDE OR Orange 1375 1355 1330 1300 1260 1210 1155 1090 1025 940
BOTTOM — Blue 1045 1040 1030 1010 985 960 920 875 825 745
Red 5 880 885 850 835 810 785 750 715 865 605
Black 2360 2250 2160 2065 1970 1880 1785 1685 1580 1455
BOTTOM or Yellow 2100 2030 1960 1885 1805 1720 1835 1545 1440 1305
080-20 TWO-SIDES 3,4 Orange 1840 1810 1785 1725 1665 1590 1515 1430 1335 1240
Blue 1705 1885 1680 1815 1570 1510 1445 1370 1280 1135
Red 1425 1410 1385 1385 1335 1290 1245 1190 1120 1050
Black 1750 1705 1680 1605 1545 1475 1405 1305 1220 1140
100-14 SIDE OR Blue 1550 1510 1470 1430 1380 1320 1245 1170 1095 1015
BOTTOM Yellows 1290 1255 1220 1180 1130 1075 1020 980 885 800
Red 5 1085 1045 1010 980 915 865 805 740 665 595
Black 2415 2330 2245 2155 2085 1985 1885 1760 1645 1530
BOTTOM or Yellow 2130 2075 2010 1945 1865 1785 1695 1600 1490 1375
100-20 TWO-SIDES 3.4 Orange 1830 1815 1785 1740 1685 1825 1550 1470 1370 1255
Blue 1690 1680 1655 1820 1580 1530 1485 1385 1295 1185
Red 1415 1405 1390 1370 1345 1305 1260 1200 1125 1050
Black 2440 2380 2295 2215 2105 1975 1815 1710 1575 1405
BOTTOM or Blue 2300 2245 2185 2090 2005 1855 1745 1835 1505 1370
120-20 TWO-SIDES 3.4 Yellow 1805 1780 1750 1705 1650 1595 1515 1430 1330 1230
Orange 5 1580 1550 1535 1505 1470 1420 1380 1285 1205 1130
Red 5 1390 1385 1370 1345 1320 1285 1230 1175 1105 1035
- Black 2410 2325 2230 2135 2035 1930 1820 1700 1575 1445
BOTTOM or Blue 2250 2175 2100 2020 1930 1825 1715 1600 1485 1370
140-20 TWO SIDES 3,4 Yellows 1740 1725 1700 1880 1610 1550 1470 1390 1295 1190
Oranges 1500 1495 1485 1485 1435 1390 1335 1285 1185 1090
Red 5 1350 1345 1335 1315 1290 1255 1210 1150 1080 995
NOTE:
1. A filter is required for each return—air inlet. Airflow performance includes a 3/4—in.(19 mm)washable filter media such as contained in a factory—author-
ized accessory filter rack. See accessory list. To determine airflow performance without this filter,assume an additional 0.1 in.w.c..available external static
pressure.
2. Blower speed taps are not always in the same order. Factory default blower connections are as follows:
a.Heating airflow—BLUE(also used for Continuous Fan)
b.Cooling airflow—BLACK(enabled when the Y terminal is energized)
ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION.
3. Airflows over 1800 CFM require bottom return,two—side return,or bottom and side return. A minimum filter size of 20"x 25"(508 x 635 mm)is required.
4. For upflow applications,air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
5. Highlighted areas indicate that this airflow range is beyond the range allowed for heating. THESE AIRFLOW RANGES MAY ONLY BE USED FOR COOL-
ING.
6. All airflows that are shown in BOLD exceed 0.58 watts per CFM at the given external static pressure.
6
24ABB3
Comfort TM 13 Air Conditioner
with Puron® Refrigerant Carrier
1 -1/2 to 5 Nominal Tons
turn to the expert
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
�� � ` Efficiency
;;' Irlir �rl;I1I I • 13 SEER/11 EER(based on tested combinations)
N'III�IA
�, ����Iul!�! ���N��►�"k • Microtube Technology'" refrigeration system
I � Ihi'iil �l1I c • Indoor air quality accessories available
1111 "lill�ll!!n IjII
s Sound
• Sound level as low as 72 dBA
• Sound level as low as 71 dBA with accessory sound
blanket
F{��«0uIUI11��;iilik Comfort
4111311111b111111011 thermostat• System supports Edge® Thermidistat"° or standard
` n1131111` 11011 thermostat controls
Bill Reliability
INj,IlJ 111111��Il
• Pur on® refrigerant - environmentally sound, won't
✓ deplete the ozone layer and low lifetime service cost.
® Comfort • Scroll compressor
• Internal pressure relief valve
Puron. SERIES • Internal thermal overload
• Filter drier
Carrier's Air Conditioners with Puron® refrigerant provide a • Balanced refrigeration system for maximum reliability
collection of features unmatched by any other family of Durability
equipment. The 24ABB has been designed utilizing Carrier's WeatherArmor'" protection package:
Puron refrigerant. The environmentally sound refrigerant allows
you to make a responsible decision in the protection of the earth's • Solid,durable sheet metal construction
ozone layer. • Dense wire coil guard available
(3-phase units come standard with dense wire coil
NOTE: Ratings contained in this document are subject to guard)
change at any time. Always refer to the AHRI directory •
(www.ahridirectory.org) for the most up-to-date ratings Baked-on,complete outer coverage, powder paint
information. Applications
• Long-line-up to 250 feet(76.20 m)total equivalent
length, up to 200 feet (60.96 m) condenser above
evaporator,or up to 80 ft.(24.38 m)evaporator above
condenser(See Longline Guide for more information.)
• Low ambient (down to -20°F/-28.9°C)) with
accessory kit
MODEL NUMBER NOMENCLATURE
1 2 3 4 5 6 7 8 9 10 11 12 13
N N A A A/N N N N A/N NN A/N N N
2 4 A B B 3 3 6 A 0 0 3 0
Product Product Tier Major SEER Cooling Variations Open Open Voltage Series
Series Family Series Capacity
3=208/230-1 0—
24=AC A=RES AC El=Comfort B=Puron 3=13 SEER 1.000 Btuh A=Dense Grille 0=Not 0=Not 5=208/230-3 Original
(nominal) W=Wide Grille Defined Defined 6=460/3 Series
1 =575/3
1;) E
TM
Puron. ti.��CERTIFIED,. "'›cn
C PI us
the environmentally sound refrigerant 0
Use of the AHRI Certified
CD
CI TM Mark indicates a !+=
CO manufacturer's ++
m participation in the CD
Q program For verification fJ ,
Q of certification for individual
N products,go to ISO 9001
www.ahridirectory.org.
OMI-SAI Global
STANDARD FEATURES
•17
Feature 18 24 30 36 42 48 60
Puron Refrigerant X X X X X X X
SEER 13 13 13 13 13 13 13
Scroll Compressor X X X X X X X
Field Installed Filter Drier X X X X X X X
Front Seating Service Valves X X X X X X X
Internal Pressure Relief Valve X X X X X X X
Internal Thermal Overload X X X X X X X
Long Line capability X X X X X X X
Low Ambient capability with Kit X X X X X X X
Dense Grille(standard on 3—Phase only) X X X X X
X= Standard
2
PHY'ICAL DATA
UNIT SIZE SERIES 16-33 ' 24-33 30-31,51 36-34 36-51,61, 42-30,50, 48-34 48-81,61, 80-34 60-52,62,
11 60 11 12
Operating Weight lb(kg) 107 110 111 144 141 190 181 186 199 198
(48.5) (50.0) (50.3) (65.3) (64.0) (86.2) (82.1) (84.4) (90.3) • (89.8)
Shipping Weight lb(kg) 130 134 136 169 170 218 217 224 232 230
(60.0) (60.8) (61.7) (76.7) (77.1) (98.9) (98.4) (101.6) (105.2) (104.3)
•
Compressor Type Scroll
REFRIGERANT Puron®(R-410A)
Control TXV(Puron®Hard Shutoff)
Charge lb(kg) 3.50 3.80 4.10 5.51 5.34 5.84 7.37 7.00 8.80 8.00
(1.6) (1.7) (1.9) (2.5) (2.4) (2.7) (3.3) (3.2) (4.0) (3.6)
COND FAN Propeller Type,Direct Drive
Air Discharge Vertical
Air Oty(CFM) 1792 2218 1 2218 2954 2954 3167 3365 3365 3365 1 3365
Motor HP 1/12 1/10 1/10 1/4 1/4 1/5 1/4 1/4 1/4 • 1/4
Motor RPM 1100 1100 1100 1100 1100 1100 1100 1100 800 1100
COND COIL
Face Area(Sq ft) 8.40 8.40 9.80 13.13 13.13 17.25 19.40 19.40 12.93 15.09
Fins per In. 20 25 25 25 25 25 25 25 20 20
Rows 1 1 1 1 1 1 1 1 2 2
Circuits 3 3 3 3 3 4 5 5 5 6
VALVE CONNECT.(In.ID) m
Vapor 3/4 3/4 3/4 7/8 7/8 7/8 7/8 7/8 7/8 7/8 CO
Liquid 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Q
.qt-
REFRIGERANT TUBES"(In.OD) N
Rated Vapor* 3/4 7/8 7/8 1-1/8
Max Liquid Linet 3/8
*Units are rated with 25 ft(7.6 m)of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
t See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables.
REFRIGERANT PIPING LENGTH LIMITATIONS
Liquid Line Sizing and Maximum Total Equivalent Lengthst for Cooling Only Systems with Puron®Refrigerant:
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and
outdoor units.
See Table below for liquid line sizing and maximum lengths:
Maximum Total Equivalent Length
Outdoor Unit BELOW Indoor Unit
Liquid AC with Puron Refrigerant Maximum Total Equivalent Lengtht: Outdoor unit BELOW indoor
Size Liquid Line Line Vertical Separation ft(m)
Connection Diam. 0-5 6-10 11-20 21-30 31-40 41-50 51-60 61-70 71-80
w/TXV (0-1.5) (1.8-3.0) (3.4-6.1) (6.4-9.1) (9.4-12.2) (12.5-15.2) 1 (15.5-18.3) (18.6-21.3) (21.8-24.4)
018 1/4 150 150 125 100 100 75
AC with 3/8 5/16 1 250* 250* 250* 250* 250* 250* 1 250* i 225* 150
Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
024 1/4 75 75 75 50 50 -- -- -- --
_
AC with 3/8 5/16 250* 250* 250* 250* 250* 225* 175 125 100
Puron 3/8 t 250* 250* 250* 250* 250* 250* 250* 250* 250*
030 1/4 30 -- -- -- -- --
c) AC with 3/8 5/16 175 225* 200 175 125 100 75 -- --
m Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
CO
Q AC w6th 3/8 5/16 175 150 150 100 100 100 75 -- --
CN Puron 3//8 250* 250* 250* 250* 250* 250* 250* 250* 250*
T
042 5/16 125 100 L 100 75 75 50 -- -- --
AC with 3/8 - • - - .
Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 150
048
AC with 3/8 3/8 250* 250* 250* 250* 250* 250* 1 230 1 160 --
Puron
060 !
AC with 3/8 3/8 250* 250* 250* 225* 190 150 110 -- --
Puron
* Maximum actual length not to exceed 200 ft(61 m)
t Total equivalent length accounts for losses due to elbows or fitting.See the Long Line Guideline for details.
--=outside acceptable range
Maximum Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
Liquid AC with Puron Refrigerant Maximum Total Equivalent Lengtht: Outdoor unit ABOVE Indoor
Size Liquid Line Line Vertical Separation ft(m)
Connection Diam. 25 26-50 51-75 76-100 101-125 126-150 151-175 176-200
w/TXV (7.6) (7.9-15.2) (15.5-22.9) (23.2-30.5) (30.8-38.1) (38.4-45.7) (46.0-53.3) (53.6-61.0)
018 1/4 175 250* 250* 250* 250* 250* 250* 250*
AC with 3/8 5/16 250* 250* 250* 250* i 250* 250* 250* 250*
Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250*
024 1/4 100 125 175 200 225* 250* 250* 250*
AC with 3/8 5/16 250* 250* 250* 250* 250* 250* 250* 250*
Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250*
030 1/4 30 -- -- -- --
AC with 3/8 5/16 250* 250* 250* 250* 250* 250* 250* 250*
Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250*
036 5/16 225* 250* 250* 250* 250* 250* 250* 250*
AC with 3/8
Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250*
042 5/16 175 200 250* 250* 250* 250* 250* 250*
AC with 3/8
Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250*
048
AC with 3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
Puron
060
AC with 3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
Puron
*Maximum actual length not to exceed 200 ft(61 m)
t Total equivalent length accounts for losses due to elbows or fitting.See the Long Line Guideline for details.
-- =outside acceptable range
4
ELECTRICAL DATA
UNIT SIZE- OPER VOLTS* COMPR FAN MAX FUSE**or
VOLTAGE, V/PH MCA CKT BRK AMPS
' SERIES MAX MIN LRA RLA FLA
18-33 56.6 9.4 0.50 12.3 20
24-33 60.8 11.2 0.77 14.8 25
30-31 64.0 12.8 0.77 16.8 25
•- 36-34 208/230/1 253 197 70.0 14.2 1.40 19.2 30
42-30 112.0 17.9 1.10 23.5 40
48-34 93.0 18.3 1.40 24.3 40
60-34 125.0 22.1 1.40 29.0 50
30-51 58.0 8.3 0.77 11.2 20
36-51 71.0 10.5 1.40 14.5 20
42-50 208/230-3 253 187 88.0 13.5 1.10 18.0 30
48-51 83.1 13.1 1.40 17.8 30
60-52 110.0 16.0 1.40 21.4 30
36-61 38.0 5.6 0.70 7.7 15
42-60 44.0 6.0 0.60 8.1 15
48-61 460-3 506 414 41.0 6.1 0.70 8.3 15
60-62 52.0 7.8 0.70 10.5 15
36-11 36.5 3.8 0.50 5.3 15
48-11 575-3 532 518 33.0 4.4 0.50 6.0 15
60-12 38.9 5.7 0.50 7.6 15 co
*Permissible limits of the voltage range at which the unit will operate satisfactorily. m
lb
**Time-Delay fuse. Q
FLA -Full Load Amps •:t
LRA -Locked Rotor Amps cv
MCA-Minimum Circuit Amps
RLA -Rated Load Amps
NOTE: Control circuit is 24-V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
A-WEIGHTED SOUND POWER LEVEL
STANDARD TYPICAL OCTAVE BAND SPECTRUM(dBA,without tone adjustment)
UNIT SIZE RATING
dBA 125 250 500 1000 2000 4000 8000
24ABB318-33 72 53.5 59.5 63.5 67.0 63.5 59.0 52.5
24ABB324-33 73 50.5 61.0 67.0 68.0 65.0 60.0 55.0
24ABB330-31,51 74 55.0 63.5 68.5 68.5 65.5 61.0 54.0
24ABB336-34 73 53.0 61.0 67.0 69.0 65.5 63.0 55.5
24ABB336-51,61,11 75 59.5 63.0 68.5 70.0 65.5 61.5 53.5
24ABB342-30,50,60 78 57.5 65.0 71.0 73.0 70.5 67.5 62.5
24ABB348-34 77 54.0 67.5 71.5 71.5 69.5 67.0 61.5
24ABB348-51,61,11 80 58.5 67.5 73.5 75.0 70.5 67.5 64.5
24ABB360-34 79 57.5 67.0 72.0 75.0 72.5 68.0 61.0
24ABB360-52,62,12 79 59.5 69.5 72.5 73.5 71.0 68.0 63.5
NOTE: Tested in accordance with AHRI Standard 270-2008(not listed in AHRI).
A-WEIGHTED SOUND POWER LEVEL WITH SOUND SHIELD
STANDARD TYPICAL OCTAVE BAND SPECTRUM(dBA,without tone adjustment)
UNIT SIZE RATING
dBA 125 250 500 1000 2000 4000 8000
24A8B318-33 71 55.5 60.5 64.0 66.0 63.0 58.5 52.0
24ABB324-33 73 53.0 62.0 67.5 68.0 65.0 60.0 53.5
24ABB330-31,51 73 55.5 64.0 68.0 67.0 64.0 60.0 52.5
24ABB336-34 73 54.5 61.5 66.5 68.5 65.0 61.5 52.5
24ABB336-51,61,11 74 59.5 63.0 68.0 69.5 65.0 60.5 50.5
24ABB342-50,60 77 57.5 65.0 70.5 72.0 70.0 67.0 62.0
24ABB348-34 77 54.0 68.0 71.5 71.5 69.0 66.5 61.0
24ABB348-51,61,11 79 60.5 67.5 73.5 74.5 71.0 68.0 63.5
24AB8360-34 79 57.5 68.0 72.5 74.5 72.5 68.0 60.5
24ABB360-52,62,12 78 60.5 69.5 72.5 73.0 71.0 67.5 61.5
NOTE: Tested in accordance with AHRI Standard 270-2008(not listed in AHRI).
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)
UNIT SIZE-VOLTAGE&SERIES REQUIRED SUBCOOLING°F(°C)
18-33 10(5.6)
24-33 10(5.6)
30-31,51 10(5.6)
36-34 12(6.7)
36-51,61,11 14(7.8)
42-30,50,60 10(5.6)
48-34,51,61,11 15(8.3)
60-34 15(8.3)
60-52,62,12 10(5.6)
n
24ABB3
DIMENSIONS - ENGLISH
ELECTRICAL(NT SERIES AC A B C D E F 0 K L M N P OPERATING SIPPING SMITING
WEIGHT Ibsl'WEIGHT (6s) DIMENSIONS IL x W x HI
24488316 2.3 X 0 0 0 23 1/8' 25 5/16' 3 3/4' 3/1' 4 7/16' 18 1116• 1 13/16' 2 13/16' 112' 16 112• 15' 12' 101 130 25 1/4' x 25 1/4' X 29 7/8'
24A68324 1,3 X 0 0 0 23 1/8" 25 5/16' 3 3/1' 3/4' 4 7/16' 18 1/16' 7 13/16" 2 13/16' 112' 16 112' 15' 12' 110 134 25 1/4' X 25 1/4' X 29 7/8'
24488330 1 X 0 X 0 23 1/8" 28 11/16' 3 3/4' 3M' 4 1/16' 18 1/16" 7 13/16' 2 13/16' 1/2" 16 1/2' 15' 14' 111 136 25 1/4' x 25 114' x 33 1/4'
24488336 1 X X X X 25 3/4' 32 5/16" 3 7/8' 7/8' 4 7/16' 21 1/4' 9 1/8' 2 15/16' 5/8' 14 114' 10 1/2' 16' 141 170 27 718' X 21 1/6' X 36 5/8'
24488336 4 X 0 0 0 25 314' 32 5/16' 3 7/8' 7/8' 4 7/16' 21 1/1' 9 1/8' 2 15/16' 5/8' 14 1/4' 10 1/2' 16" 144 169 27 7/8' X 21 1/8' X 36 5/8'
24488342 0 X 0 X X 31 3/16' 32 5/16' 3 7/8' 7/8' 6 9/16' 24 11116' 9 1/8' 2 15/16" 5/8' 15 3/4' 16 1/4" 13 3/4' 190 218 33 3/8' X 33 3/8' X 36 5/8'
24488348 1 X X X X 31 3/16• 35 3/4' 3 7/8' 7/8' 6 9/16' 24 11/16' 9 1/8' 2 15/16' 5/8' 16 3/8' 15 3/8' 15 1/4' 186 224 33 3/8' X 33 3/8' X 40•
24488348 3,4 X 0 0 0 31 3/16' 35 3/4' 3 7/8' 7/8" 6 9/16- 24 11/16" 9 1/8' 2 15/16' 5/8' 16 3/8' 15 3/8" 15 1/4' 181 217 33 3/8' X 33 3/8" X 40'
24488360 2 X 0 0 0 31 3/16' 25 1/2" 3 1/8' 7/8' 6 9/16' 24 11/16' 9 118' 2 15/16' 5/8" 14 1/8' 15 3/8' 11 3/8" 190 226 33 3/8' X 33 3/8' X 29 7/8'
24486360 2 0 X X X 31 3/16' 28 15/16' 3 7/8' 7/8' 6 9/16" 24 11116" 9 1/8' 2 15/16' 5/8' 16" 15 1/2' 12 3/4' 198 230 33 3/8' X 33 3/8' X 33 1/4"
24488360 4 X 0 0 0 31 3/16' 28 15/16' 3 7/8' 7/8' 6 9/16' 24 11/16" 9 1/8' 2 15/16" 5/8' 16' 15 112' 12 3/4' 199 232 33 3/8' X 33 3/8' X 33 1/4'
X .
p g p D _ NO
A
So.
M AIR IN AIR
AIR DISCHARGE DISCHARGE
i I G
•o 0 _
B
FIELD CONTROL 4 !'i'S0118'CHOLE �FIELD PONFR SUPPLY CONN. AIA IN - II \\` F 0 0 i/8' HOLE NITT \
01 1/8' KNOCKOUT o \ ; %................... ,,,` •, 414 IN
03/8 ° N
LIOUID LINE CONN. P �'� ��
1 d���+ r E
/
C 3 112• _1 ' --- �a���
1 7/8' 3' may ' r 9
OD VAPOR LINE CONN. L
5/16'
IAMMUM K 1-AIR IN
(NT SIZE MOWING PAD
DIMENSIONS 0318' TIEDORN KNOCKOUTS
18.24,30 23 1/2• X 23 1/2'
121 PLACES
36 26' X 26'
18,60 31 1/2' X 31 1/2"
35' x 35'
TESTED AHRI COMBINATION RATINGS*
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates,please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Carrier database at: www.MyCarrierRatings.com
For performance data at specific application&/or design conditions with various indoor unit combinations, the
equipment performance calculator can be accessed at: http://rpmob.wrightsoft.com/
Model Number Indoor Coll Model Number Furnace Model Number Cooling Capacity EER SEER
24ABB318(A,W)33 CAP**1814A**+TDR 17,600 _ 11.0 13.0
24ABB324(A,W)33 CAP**2414A**+TDR 23,000 11.0 13.0
24ABB330(A,W)31 CAP**3014A**+TDR 27,400 11.0 13.0
24ABB330A51 CAP**3014A**+TDR 27,400 11.0 13.0
24ABB336(A,W)34 CAP**3617A**+TDR 33,800 11.0 13.0
24ABB336A11 CAP**3617A**+TDR 33,800 11.0 13.0
` 24ABB336A51 CAP**3617A**+TDR 33,800 11.0 13.0
24ABB336A61 CAP**3617A**+TDR 33,800 _ 11.0 13.0
24ABB342(A,W)30 CAP**4221A**+TDR 41,000 11.0 13.0
24ABB342A50 CAP**4221A**+TDR 41,000 11.0 13.0 CO
24ABB342A60 CAP**4221A**+TDR 41,000 11.0 13.0 CO
24ABB348(A,W)34 CAP**4821A**+TDR 46,000 11.0 13.0 Q
24ABB348A11 CAP**4821A**+TDR 46,000 11.0 13.0 N
24ABB348A51 CAP**4821A**+TDR 46,000 11.0 _ 13.0
24ABB348A61 CAP**4821A**+TDR 46,000 11.0 13.0
24ABB360(A,W)34 CAP**6024A**+TDR 57,500 11.0 13.0
24ABB360Al2 CAP**6024A**+TDR 57,500 11.0 13.0
24ABB360A52 CAP**6024A**+TDR 57,500 11.0 13.0
24ABB360A62 CAP**6024A**+TDR 57,500 11.0 13.0
* AHRI=Air Conditioning,Heating&Refrigeration Institute
EERA-Energy Efficiency Ratio-'A'conditions-80°F(26.6°C)indoor db/67°F(19.4°C)indoor wb&95°F(35°C)outdoor wb.
SEER-Seasonal Energy Efficiency Ratio
TDR- Time-Delay Relay. In most cases,only one method should be used to achieve TDR function.Using more than one method in a system may cause degradation in
performance. Use either the accessory Time-Delay Relay,KAATD0101 TDR,or a furnace equipped with TDR.Most Carrier furnaces are equipped with TDR.
NOTES:
1.Ratings are net values reflecting the effects of circulating fan motor heat.Supplemental electric heat is not included.
2.Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners.Ratings for other
combinations are determined under DOE computer simulation procedures.
3.Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.
4.Do not apply with capillary tube coils as performance and reliability are significantly affected.