Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Plans
6-27-14 , APPLICABLE CODES RECEIVED 4 .I '. , , PARTIAL LIST OF APPLICABLE CODES , AUG 4 20M r �t4'`9' GENERAL NOTES DUCT CONSTRUCTION HVAC NOTES AS OF JANUARY 1 , 2011 pp��Q�1YOuFTIIGAnR�/Dyy $ r WWLU11iGUfllRIVr' C TOO' 1. SIMILAR REQUIREMENTS, AS STATED IN THESE GENERAL NOTES AND HVAC NOTES, MAY ALSO APPEAR IN THE GENERAL CONDITIONS AND A.MINIMUM DUCTWORK GAGES, JOINTS, REINFORCING, AND BRACING SHALL CONFORM TO THE 1. ALL HVAC EQUIPMENT SHALL COMPLY WITH THE OEESC. 2010 OREGON STRUCTURAL SPECIALTY CODE (OSSC) EXPIRES: 30JUN16 SPECIFICATIONS. SUCH SIMILAR AND CORRESPONDING NOTES IN THE GENERAL CONDITIONS AND SPECIFICATIONS TAKE PRECEDENCE OVER FOLLOWING TABLES. HOODS, PLENUMS, AND CASTINGS SHALL NOT BE LIGHTER THAN THE (2009 INTERNATIONAL BUILDING CODE) THESE GENERAL NOTES AND HVAC NOTES. WHEN THESE GENERAL NOTES AND HVAC NOTES ARE MORE STRINGENT, THEN THEY SHALL DUCT GAGE LISTED IN TABLE 2 FOR CORRESPONDING DIMENSIONS. ADDITIONAL BRACING 2. CONTRACTOR SHALL INSTALL PER PLAN. SUBMIT SHOP DRAWINGS 2011 OREGON ELECTRICAL SPECIALTY CODE (OESC) PREVAIL. SHALL BE PROVIDED TO PREVENT OBJECTIONABLE PANEL VIBRATION. FOR APPROVAL PRIOR TO INSTALLATION. CONTRACTOR SHALL (2008 NATIONAL ELECTRICAL CODE) VERIFY THE EXACT CEILING SPACE AND INTERCHANGE THE DUCT 2010 OREGON MECHANICAL SPECIALTY CODE (OMSC) 2. SCOPE: THE CONTRACTOR SHALL FURNISH ALL MATERIALS, LABOR, EQUIPMENT, TRANSPORTATION, SCAFFOLDING, AND SERVICES NECESSARY B.PROVIDE LONGITUDINAL SEAMS OF THE GROOVED SNAP LOCK AND STANDING, SEALED AND SIZE TO FIT THE CEILING SPACE WITHOUT ADDITIONAL COST TO (2009 UNIFORM MECHANICAL CODE) FOR COMPLETION OF THE CODES AND REGULATIONS: ALL MATERIALS AND WORK SHALL CONFORM TO THE LATEST ADOPTED EDITIONS OF TAPED, OR SEALED SPIRAL OR CONTINUOUSLY WELDED. FOR EXHAUST DUCT, TAPING MAY BE THE DISTRICT. 0 THE OREGON MECHANICAL SPECIALTY CODE, OREGON RESIDENTIAL SPECIALTY CODE, OREGON PLUMBING SPECIALTY CODE, AND NATIONAL OMITTED. 2 01 1 OREGON PLUMBING SPECIALTY CODE (OPSC) _Z ELECTRIC CODE, AND ALL OTHER APPLICABLE CODES AND REGULATIONS, INCLUDING OREGON ENERGY EFFICIENCY CODE. ALL MATERIALS AND 3. EXHAUST TERMINATION SHALL BE MINIMUM 10'-0" AWAY FROM, OR (2009 UNIFORM PLUMBING CODE) EE WORK SHALL MEET THE APPROVAL OF THE LOCAL JURISDICTION AND THE FIRE MARSHAL. WHERE THE DRAWINGS AND SPECIFICATIONS TABLE 1 - SHEET METAL THICKNESS FOR CIRCULAR DUCTS AND FLAT-OVAL 3'-0" ABOVE, ANY OUTSIDE AIR INTAKE, OPERABLE WINDOWS,AND 2010 OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC) w INDICATE MORE RESTRICTIVE REQUIREMENTS, THE DRAWINGS AND SPECIFICATIONS SHALL GOVERN, BUT NOTHING IN THE DRAWINGS AND (FOR STATIC PRESSURES LISTED) DOORS. THEY SHALL ALSO BE 10'-0" MINIMUM ABOVE GRADE. 2010 OREGON FIRE CODE Z SPECIFICATIONS SHALL BE INTERPRETED AS AUTHORITY TO VIOLATE ANY CODE OR REGULATION. (2009 INTERNATIONAL FIRE CODE) C5 GAGE THICKNESS 4. ALL PIPES AND DUCTS SHALL BE SUPPORTED AND BRACED PER W 3. PERMITS, LICENSEES, AND FEES: THE CONTRACTOR SHALL PAY FOR ALL PERMITS, 2" WATER COLUMN DIAMETER OF DUCT HORIZONTAL GIRTH "SMACNA" GUIDELINES. d (0 4. SYMBOLS AND ABBREVIATIONS: IF THE CONTRACTOR IS UNSURE OF ANY SYMBOLS OR ABBREVIATIONS ON THE DRAWINGS, THE CONTRACTOR MAXIMUM S.P. MAXIMUM MAXIMUM JOINTS 13 2 SHALL NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK. ROUND / OVAL DIAMETER SUPPORT DISTANCE CL 26 / 24 UP TO 9° 10' 2" SLIP 5. NATURE OF THE DRAWINGS: FOR THE PURPOSE OF CLARITY AND LEGIBILITY, THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC. ALTHOUGH SIZES PARTIAL LIST OF APPLICABLE STANDARDS z !-Z AND LOCATION OF EQUIPMENT ARE DRAWN TO SCALE WHEREVER POSSIBLE, THE CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL OF THE 26 / 24 9" - 14" 8' 4" - 0 § CONTRACT DOCUMENTS, AND VERIFY THIS INFORMATION BEFORE ORDERING, FABRICATING, OR INSTALLING OF ANY MATERIALS. NFPA 13 AUTOMATIC SPRINKLER SYSTEMS 2010 EDITION W 3 O z 24 / 22 14" - 23" 8' 4" NFPA 14 STANDPIPE SYSTEMS 2007 EDITION a NFPA 17 DRY CHEMICAL EXTINGUISHING SYSTEMS 2002 EDITION Q i F- 6. FIELD VERIFICATION: ALL EXISTING STRUCTURES, EQUIPMENT, DUCTWORK, PIPING, AND CONDUIT ARE NOT SHOWN IN THESE DRAWINGS. BEFORE z ,. n BIDDING AND BEFORE BEGINNING ANY WORK, THE CONTRACTOR SHALL THOROUGHLY EXAMINE AND VERIFY ALL EXISTING CONDITIONS, POINTS OF NFPA 17A WET CHEMICAL SYSTEMS 2002 EDITION cc > W CONNECTION, SIZES, LOCATION, INTERFERENCES, ETC. ALL NECESSARY ADJUSTMENTS REQUIRED TO FACILITATE THE NEW INSTALLATION SHALL C.CONSTRUCTION DETAILS FOR RECTANGULAR SHEET METAL DUCTS FOR LOW-PRESSURE NFPA 90A STANDARD FOR THE INSTALLATION OF A/C & VENTILATING SYSTEM 2012 EDITION W 1- o � BE MADE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. SYSTEMS - VELOCITIES NOT EXCEEDING 2,000 FEET PER MINUTE: NFPA 72 NATIONAL FIRE ALARM CODE (CALIFORNIA AMENDED) 2010 EDITION fn o 13-- OZ (NOTE SEE UL STANDARD 1971 FOR "VISUAL DEVICES") W a m m . V 1. FOR PRESSURES IN EXCESS OF 2 INCHES WATER COLUMN, DUCT WALL s i m 7. DISCREPANCIES: THE CONTRACTOR SHALL BRING TO THE ATTENTION OF THE ARCHITECT, IN WRITING, ANY DISCREPANCIES BETWEEN EXISTING THICKNESS SHALL BE 2 GAGES HEAVIER THAN SET FORTH IN THIS TABLE. NFPA 80 FIRE DOOR AND OTHER OPENINGS PROTECTIVE 2007 EDITION il i 3 CONDITIONS AND THE CONTRACT DOCUMENTS, AND ANY CONFLICTS WITHIN THE CONTRACT DOCUMENTS. THIS SHALL BE DONE PRIOR TO THE 2. DUCT SPECIFICATIONS SHOWN BELOW ARE APPLICABLE WHEN DUCTS LARGER THAN 18 NFPA 2001 CRRIEAN AGE4NTIAFIRE EXTINGUISHING COVERING SYSTEMS 2008 EDITION ■ $ € START OF CONSTRUCTION IN EACH AREA SO ANY NECESSARY CLARIFICATIONS CAN BE ISSUED. INCHES ARE CROSS-BROKEN. WHERE CROSS BREAKING IS NOT PROVIDED, DUCT WALL flfl • • • • 8. SUBMITTALS: THE CONTRACTOR SHALL MAKE SUBMITTALS ON EQUIPMENT AND OTHER ITEMS REQUIRING SUBMITTALS, AND SHALL RECEIVE THICKNESS SHALL BE 2 GAGES HEAVIER ON DUCTS 19 INCHES TO 60 INCHES WIDE APPROVALS ON THE SUBMITTALS, PRIOR TO PURCHASE OR INSTALLATION. UNLESS LONGITUDINAL STANDING SEAMS ARE FURNISHED. 9. COORDINATION: PRIOR TO FABRICATION AND INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING HIS OR HER WORK TABLE 2 - MINIMUM METAL GAGES WITH ALL LOCATIONS OTHER AND OF LEVATIONS INCLUDES COORDINATING AND OTHER EQUIPMENT. IT INCLUDES COORDINATING MINIMUM GAGE MAX. SIDE, DUCT PERMISSIBLE GIRTH HORIZONTAL SUPPORT SYMBOLS AND ABBREVIATIONS SYMBOLS AND ABBREVIATIONS in WITH THE ELECTRICAL CONTRACTOR FOR ELECTRICAL REQUIREMENTS OF ALL MECHANICAL EQUIPMENT. THE CONTRACTOR SHALL COORDINATE THICKNESS GROSS JOINTS & LONGITUDINAL MAXIMUM CC THE LOCATION OF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES WITH THE ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL LIGHTING STEEL / ALUMINUM DIMENSIONS SEAMS DISTANCE W W LAYOUT AND ARCHITECTURAL ROOM ELEVATIONS. 26 / 24 UP TO 12" DRIVE-SLIP, PLAIN S-SLIP, 10' SA IIIIIaI SUPPLY AIR PLENUM CROSS-UP DIRECTION EDB ENTERING DRY BULB < F- Q N OR 1" POCKET LOCK EER ENERGY EFFICIENCY RATIO 10. WORK SCHEDULING AND INTERRUPTIONS: THE CONTRACTOR SHALL OBTAIN WRITTEN APPROVAL FROM THE OWNER BEFORE BEGINNING WORK W N RA IIIIIIII RETURN MR PLENUM CROSS DOWN DIRECTION IN ANY EXISTING AREA, OR BEFORE WORKING ON ANY EXISTING EQUIPMENT. THE CONTRACTOR SHALL INDICATE TO THE OWNER, THE (n 24 / 22 13" 18" DRIVE SLIP, PLAINS SLIP, 10' N. PARTICULAR AREA IN WHICH WORK WILL BE DONE AND THE PARTICULAR EQUIPMENT TO BE WORKED ON ALONG WITH THE DURATION OF ESP EXTERNAL STATIC PRESSURE W Z TIME ANY SYSTEM WILL BE OUT OF SERVICE. SUCH WORK WILL BE SCHEDULED IN SUCH A MANNER SO AS NOT TO DISRUPT PRESENT 1" POCKET LOCK 0 CO SA OPERATIONS, IF POSSIBLE. FOR INTERRUPTION OF PRESENT OPERATIONS, THE CONTRACTOR SHALL OBTAIN A LETTER OF APPROVAL FROM �><m"'mII� SUPPLY AIR PLENUM CROSS UP DIRECTION EWB ENTERING WET BULB 0 Z O THE OWNER, CITING AREAS, DATES, HOURS OF THE DAY, AND DURATION INTERRUPTION IS TO TAKE PLACE. MINIMUM GAGE MAX. SIDE, DUCT PERMISSIBLE GIRTH HORIZONTAL SUPPORT X O THICKNESS GROSS JOINTS & LONGITUDINAL MAXIMUM RA II I I� II RETURN AIR PLENUM CROSS-DOWN DIRECTION EXIST EXISTING J 0 0- STEEL / ALUMINUMDIMENSIONS SEAMS DISTANCE 0 I- 2 Z X 11. CONSTRUCTION BARRIERS AND PASSAGES: THE CONTRACTOR SHALL PROVIDE ADEQUATE BARRICADES AND PROTECTIVE DEVICES _ -� FLA FULL LOAD AMPERES CD - Z 0 SEPARATING CONSTRUCTION AREAS. TEMPORARY PASSAGES SHALL BE PROVIDED AS REQUIRED. 24 / 22 19" 30" HEMMED S-SLIP, 1" BAR 10' CD � CEILING DIFFUSER, 2 WAY W Z I- C SLIP, OR 1" POCKET LOCK ON HP HORSEPOWER, HEAT PUMP n = Z j <L 12. DEMOLITION: THE CONTRACTOR SHALL DEMOLISH AND REMOVE EXISTING CONSTRUCTION AS NECESSARY TO INSTALL NEW CONSTRUCTION AS 5' CENTERS. -_ HZ HERTZ Q W > C� SHOWN. CD CEILING DIFFUSER, 4 - WAY KW KILOWATT H fn HEMMED S SLIP, 1" SLIP, OR 1" POCKET LOCK ON 5' CENTERS CM 13. SALVAGE: THE OWNER RESERVES THE RIGHT TO SALVAGE ANY EQUIPMENT AND/OR MATERIALS AFTER REMOVAL BY THE CONTRACTOR. ALL WITH 1" X 1" X 1/8" ANGLES ON i LAT LEAVING AIR TEMPERATURE REMAINING ITEMS REMOVED BY THE CONTRACTOR SHALL BE REMOVED FROM THE SITE AND DISPOSED BY THE CONTRACTOR. CENTER LINE BETWEEN. LAV LAVATORY r 14. PROTECTION, REPAIR, AND RESTORATION OF EXISTING: THE CONTRACTOR SHALL PROTECT AND REPAIR ADJACENT EXISTING SURFACES, HEMMED S-SLIP, 1" BAR SLIP, CD O CEILING DIFFUSER, ROUND AREAS, PIPING, AND EQUIPMENT WHICH MAY BE DAMAGED AS A RESULT OF DEMOLITION AND/OR NEW WORK. CONTRACTOR SHALL OR 1" POCKET LOCK ON 10' CENTERS LDB LEAVING DRY BULB NOT DEMOLISH OR ALTER ANY WORK WHICH IS NOT PART OF THIS CONTRACT WITHOUT WRITTEN PERMISSION OF THE OWNER. WITH CROSS BREAK 1" STANDING SEAM ON 5' CENTERS. SWS SIDEWALL SUPPLY REGISTER LWB LEAVING WET BULB 15. PROTECTION AND REPAIR OF NEW WORK: THE CONTRACTOR TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE MATERIALS BEFORE, MBH THOUSAND BRITISH THERMAL UNITS PER HOUR SHEET TITLE DURING AND AFTER INSTALLATION. IN THE EVENT OF DAMAGE, THE CONTRACTOR SHALL IMMEDIATELY REPAIR ALL DAMAGED AND DEFECTIVE , MECHANICAL BUTTON PUNCH SNAP-LOCK SEAMS, LOCKFORMER, OR EQUAL, SHALL ONLY BE PERMUTED MFR MANUFACTURER WORK TO THE APPROVAL OF THE ARCHITECT AND AT NO ADDITIONAL COST TO THE OWNER. ON 20 AND 22 GAGE GALVANIZED STEEL DUCTS. FOR ALUMINUM DUCT, BUTTON PUNCH RR "'� RETURN REGISTER NOTES SNAP LOCK IS NOT PERMUTED. � I MCA MAXIMUM CURRENT AMPACITY 16. MATERIALS: ALL MATERIAL, EQUIPMENT, FIXTURES, ETC. SHALL BE NEW, UNLESS OTHERWISE NOTED, AND OF THE BEST GRADE OF THE ER •• V V EXHAUST REGISTER MFS MAXIMUM FUSE SIZE RESPECTIVE KIND, FREE FROM ALL DEFECTS. ANY MATERIAL, ARTICLE OR PIECE OF EQUIPMENT OTHER THAN THAT INDICATED SHALL NOT BE D. FERROUS ANGLES AND STRUCTURAL MEMBERS AND JOINING COLLARS SPECIFIED FOR THE USED UNLESS APPROVED IN WRITING BY THE ENGINEER, AND ANY CHANGES IN MECHANICAL, ELECTRICAL AND/OR OTHER SYSTEMS REQUIRED CONSTRUCTION AND SUPPORT OF DUCTWORK AND PLENUMS SHALL BE PRIMED WITH ONE SWS -...- I- SIDE WALL SUPPLY REGISTER MOCP MAXIMUM OVERCURRENT PROTECTION DUE TO SUCH SUBSTITUTION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, AND AT NO ADDITIONAL COST TO THE OWNER. HEAVY COAT OF ASPHALT ALUMINUM PAINT BEFORE INSTALLATION OR FABRICATION. THE NFPA NATIONAL FIRE PROTECTION ASSOCIATION METAL SURFACE SHALL BE THOROUGHLY CLEANED BEFORE APPLICATION OF THE PAINT. SWR ter_ I- SIDE WALL RETURN GRILLE 17. MATERIALS UNIFORMITY: MATERIALS FOR SIMILAR USE SHALL BE OF THE SAME TYPE AND MANUFACTURER, UNLESS OTHERWISE SPECIFIED. GALVANIZING MAY BE PROVIDED INSTEAD OF PAINTING. INSTALLED DUCT HANGER RODS (N) NEW CONCEALED IN FURRED CEILINGS AND WALLS IS NOT REQUIRED TO BE PRIMED OR PAINTED. CD CD CONDENSATE DRAIN OBD OPPOSED BLADE DAMPER REUSE OF DOCUMENTS E. BROKEN PLACES IN GALVANIZED COATING SHALL BE ACID WASHED AND THEN 18. SEALING OF OPENINGS: ALL FLOOR, WALL, AND CEILING OPENINGS REQUIRED FOR PIPES, DUCTS, CONDUITS, AND SIMILAR ITEMS SHALL BE COMPLETELY SOLDERED OVER OR PAINTED WITH GALVANIZING PAINT, DEVCON Z OR ZRC RL RL REFRIGERANT LIQUID LINE OSA OUTSIDE SUPPLY AIR SEALED; UNLESS OTHERWISE PROTECTED WITH A TWO-HOUR FIRE RESISTIVE ENCLOSURE (ONE-HOUR FOR ONE-HOUR BUILDINGS). COLD GALVANIZING COMPOUND. This document, and the ideas RS RS REFRIGERANT SUCTION LINE QTY QUANTITY and designs incorporated, as an 19. STRUCTURAL MEMBERS: UNLESS SPECIFICALLY SHOWN ON THESE PLANS NO STRUCTURAL MEMBER SHALL BE CUT, NEITHER DRILLED NOR F. S-TYPE OR DRIVE-SLIP TYPE GIRTHS OR LONGITUDINAL SEAMS SHALL NOT BE instrument of professional NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE ARCHITECT. FURNISHED FOR DUCTWORK INSTALLED OUTDOORS OR MOUNTED ON ROOFS. PROVIDE Q ROOM THERMOSTAT RLA RATED LOAD AMPERES service is the property of ANGLE-REINFORCED GOVERNMENT LOCK ONLY. Western Design Group, RA RETURN AIR and is not to be used, in whole 20. WIRING: RESPONSIBILITY DISTINCTION: THE GENERAL CONTRACTOR SHALL SUPERVISE THE FOLLOWING WIRING RESPONSIBILITY DISTINCTION. BDD \ I BACKDRAFT DAMPER or in part,for any mason without CONTROL LOW VOLTAGE WIRING AND CONNECTION SHALL BE BY MECHANICAL CONTRACTOR. LINE VOLTAGE WIRING, CONDUIT, DISCONNECT G. BROKEN PLACES IN GALVANIZED COATING SHALL BE ACID WASHED AND THEN RTU ROOFTOP UNIT the written authorization of SWITCHES, AND CONNECTION SHALL BE BY ELECTRICAL CONTRACTOR. COMPLETELY SOLDERED OVER OR PAINTED WITH GALVANIZING PAINT, DEVCON Z OR ZRC MVD 1 MANUAL VOLUME DAMPER Western Design Group, Inc. COLD GALVANIZING COMPOUND. SA SUPPLY AIR 21. PLUMBING DISTINCTION: CONDENSATE DRAIN PIPING AND FINAL CONNECTION TO EQUIPMENT UNITS SHALL BE BY PLUMBING POC POINT OF CONNECTION SEER SEASONAL ENERGY EFFICIENCY RATIO CONTRACTOR. POD tO POINT OF DISCONNECTION SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS DATE ISSUE 22. GENERAL CONTRACTOR DISTINCTION: REDWOOD SLEEPERS OR PLATFORMS FOR ROOF MOUNTED EQUIPMENT UNITS, DUCT PENETRATIONS AND NATIONAL ASSOCIATION XX.XX.XX PRELIM CUTTING AND PATCHING SHALL BE BY GENERAL CONTRACTOR, UNLESS OTHERWISE NOTED ON PLAN. SD ® SMOKE DETECTOR 009P61/4-- l O\13\ l SP STATIC PRESSURE XX.XX.XX PERMIT 23. MANUFACTURER'S INSTALLATION RECOMMENDATIONS: ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT AD ACCESS DOOR MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL FITTINGS, OFFSETS, TRANSITIONS, DAMPERS, VALVES AND OTHER DEVICES REQUIRED TA TRANSFER AIR CITY OP 1'IGARD FOR A COMPLETE WORKABLE INSTALLATION. AFF ABOVE FINISHED FLOOR TG TRANSFER GRILLE REVIEWED FOR CODE COMPLIANCE ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND Approved: [ 4-- 24. AIR BALANCING: THE CONTRACTOR SHALL CONDUCT AN AIR BALANCE OF THE HVAC SYSTEMS TO ACHIEVE THE AIR FLOWS INDICATED ON AIR CONDITIONING ENGINEERS TYP TYPICAL OTC: THE DRAWINGS. THE CONTRACTOR SHALL SUBMIT A COMPLETE AIR BALANCE REPORT FOR APPROVAL. THE AIR BALANCE REPORT SHALL CONFORM TO AABC STANDARDS AND SPECIFICATIONS. THE REPORT SHALL INCLUDE THE FOLLOWING: BFF BELOW FINISHED FLOOR U/C UNDERCUT DOOR Permit its Me". A -('� " A) AIR QUANTITIES AT EACH REGISTER. BTUH BRITISH THERMAL UNITS PER HOUR U.O.N. UNLESS OTHERWISE NOTED Address: (G�(( ___ 00/1%6E. -<0 B) STATIC PRESSURE READINGS AT INLET AND DISCHARGE OF EACH AIR HANDLING SYSTEM AND AT INLET OF EACH EXHAUST AIR Suite#: SYSTEM. CFM CUBIC FEET PER MINUTE UTR UP THRU ROOF B Dates ate- C) COOLING AND HEATING SUPPLY AND RETURN AIR TEMPERATURES AT EACH AIR CONDITIONING UNIT. COP COEFFICIENT OF PERFORMANCE V VOLT 25. TESTING AND OPERATION: THE CONTRACTOR SHALL TEST, ADJUST, AND PLACE IN PROPER OPERATING CONDITION ALL SYSTEMS DRY BULB 0 i VTR VENT THRU ROOF INSTALLED UNDER THE WORK OF THIS CONTRACT. OFFICE COPY DX DIRECT EXPANSION WB WET BULB 26. OPERATION AND MAINTENANCE MANUALS: THE CONTRACTOR SHALL SUBMIT FOUR SETS OF OPERATING AND MAINTENANCE MANUALS TO • THE OWNER UPON COMPLETION OF THE PROJECT. EA EXHAUST AIR W.C. WATER COLUMN 27. AS-BUILT DRAWINGS: THE CONTRACTOR SHALL MAINTAIN ACCURATE AS-BUILT DRAWINGS DURING CONSTRUCTION AND SHALL SUBMIT EAT ENTERING AIR TEMPERATURE 0 PHASE, DIAMETER THEM FOR APPROVAL UPON COMPLETION OF INSTALLATION. DRAWN BY BKG 28. WARRANTY: IN ADDITION TO EQUIPMENT WARRANTIES, THE CONTRACTOR SHALL FURNISH A WRITTEN WARRANTY AGAINST DEFECTS IN (E) EXISTING CHECKED BY JLT MATERIALS AND WORKMANSHIP FOR ONE YEAR AFTER OWNER'S ACCEPTANCE OF THE PROJECT. THE WARRANTY SHALL INCLUDE LABOR AND MATERIALS FOR REPAIR OF DAMAGE TO, OR REPLACEMENT OF, ANY PART OF DEFECTIVE OR DAMAGED EQUIPMENT OR ITEM. JOB # : 29. THE SEISMIC ANCHORAGE OF MECHANICAL AND ELECTRICAL EQUIPMENT SHALL CONFORM TO 2009 IBC. ANCHORAGE DETAILS FOR ' ,. ., ROOF/FLOOR MOUNTED EQUIPMENT SHALL BE SHOWN ON PLANS. SCALE: AS NOTED SHEET NUMBER M 1 a 0 1 r�+l PACKAGED ROOFTOP HEAT PUMP UNIT SCHEDULE DIFFUSER SCHEDULE DIFFUSER SCHEDULE �►$4!ifir r r AIR FLOW NECK PANEL AIR FLOW NECK PANEL MARK MFR MODEL DAMPER REMARKS MARK MFR MODEL DAMPER REMARK1 INDOOR FAN COOLING HEATING POWER SUPPLY CFM SIZE SIZE I CFM SIZE SIZE } T� MIN. OSA EAT EAT AMB. WOGI R MARK CONDITION LOCATION 1 ESP MTR. (( ) 'F DB 'F 'F DB TOTAL SENSIBLE OUTPUT ELECTRIC DESIGN EQUIPMENT NOTES CD-1 400-600 KRUEGER RM1 12"0 22"0 MANUAL 1,2,3 1 RR-1 600 KRUEGER 56490 12"X12" 24°X24" MANUAL 1,2,3 ; C�'li�� IN WG. BHP BTUH BTUH SEER (BTUH) (KW) �' VOLT PH Hz MCA MOCP j 1 9 - CD-2 350 KRUEGER 51240 12"X12" 15"X15" OBD 1,2,3 1 RR-2 550 KRUEGER S580 16"X16" 18"X18" OBD 1,2,3 EXISTING ROOF 2,800 0.5 1.5 1000 80.0 67.0 95 90.5 65.6 1150 208 3 60 51 70 TRANE SPCC-8756-A 1 CD-3 300 KRUEGER 51240 12"X12" 24"X24" MANUAL 1,2,3 ' ER-1 100-160 KRUEGER S80 10"X10" 12"X12" 1,2,3 CD 11.. P NT TO MATCH THE COLOR OF CEIUNG/SOFFIT. SPLIT SYSTEM HEAT PUMP UNIT SCHEDULE 2. FURNISH AND INSTALL PROPER DUCT TRANSlON COLLAR. <r 3. FURNISH AND INSTALL DUCT EXTRACTOR. w LU INDOOR FAN COOUNG HEATING POWER SUPPLY Z MIN. OSA EAT EAT AMB. ,WOG R MARK CONDITION LOCATION ESP MTR. (CFM) •F DB 'F WB 'F DB TOTAL SENSIBLE SEER OUTPUT ELECTRIC LBS. DESIGN EQUIPMENT NOTES w CFIJI IN WG. BHP BTUH BTUH (BTUH) (KW) VOLT PH Hz MCA MOCP w OWING ROOF 59.0 54.5 208 3 60 23.5 40 LENNOX HP23-653 p ® EX EC - _ 0 I ® EXISTING 1,500 400 80.0 67.0 95 59.0 54.5 z w 3 O 0 Q EXHAUST FAN SCHEDULE § il w a ; F SYM MANUF./MODEL CONDITION LOCATION AREA SERVED TYPE CFM PRESSURE RPM DRIVE MOTOR OPER. WT. REMARKS HOOD INFORMATION LOCATED ON THIS SHEET w m U HP VOLT FOR COORDINATION PURPOSES ONLY. ANY ?� QUESTIONS SHALL BE ANSWERED BY CAPTIVE ? EF AIRE OFFICE OF SOUTHERN CALIFORNIA. (714) COOK GN-144 NEW CEILING WOMEN'S RESTROOM INUNE 100 0.5 1100 DIRECT 1/6 120/10 20 7 U iiii Q CABINET / / 957-1500. FINISHED BACK �� - THIS SIDE FRONT © COOK GN-144 NEW CEIUNG MEN'S RESTROOM CABINET 100 0.5 1100 DIRECT 1/6 120/10 20 7 1/4" I] IY EF viv COOK 135 VCR NEW ROOF PIZZA HOOD R001 1,200 0.625 1,159 BELT 1/4 120V/10 135 1,2,3,4,5,6 w Q W w Field Cut (e I-- < M A 14" Diameter < IZ D N 1. PROVIDE 9.5" fNGH VENIFD ROOF CURB WITH VENT DCWNDER. Exhaust D LU a 2. PROVDE ALUMINUM GREASE TUBE AND GREASE TERMINATOR. Riser 3. PROVIDE EXPLOSION PROOF MOTOR. �nj Z 4. PROVDE 5. PROVIDE HINGED DISCONNECT BASE 3" V � ce 6. INTERLOCK WITH KITCHEN HOOD. O 0 If C7 Q 7. INTERLOCK WITH LKIHT SWITCH. U.L. Listed Incandescent Light ~ Z Fixture-High Temp Assembly O - I 0 HOOD INFORMATION w z ~ ° cC � _ za MAX. EXHAUST PLENUM HOOD CONFIG. !v] Z ���nn HOOD MODEL LENGTH COOKING TOTAL RISER(S) HOOD END TO LU V NO. TEMP. EXH. CFM WIDTH LENG. DNA. CFM S.P. CONSTRUCTION END ROW Q (- 3624 " 600 14" 1200 -0.253" 430 SS N 1 6' 0.00 1200 ALONE ALONE �- ND-2 Deg. Where Exposed 6' o.00'Nom./6' 0.00`OD C FIRE SUPPRESSION FURNISH AND INSTALL UL-300 LISTED S ON S STEM PLAN VIEW - Hood # 1 HOOD INFORMATION 6' 0.00" LONG 3624ND-2 SHEET TITLE FILTER(S) LIGHT(S) UTILITY CABINETS) FIRE HOOD FIELD CUT EXHAUST RISER 3• MECHANICAL HOOD FIRE SYSTEM ELECTRICAL SWITCHES NO. TYPE QTY. HEIGHT LENGTH QTY. TYPE WIRE LOCATION SYSTEM HANGING SCHEDULES GUARD TYPE SIZE MODEL # QUANTITY PIPING WGHT INCANDESCENT LIGHT FIXTURE-HIGH TEMP 2 16" 16" 257 HANGING ANGLE ASSEMBLY, INCLUDES CLEAR THERMAL AND 1 SS Baffle with Handles 2 Incandescent Light Fixt NO YES LBS SHOCK RESISTANT GLOBE (L55 FIXTURE) 5/16• 16* SS BAFFLE WITH dpill . • HOOD 0 PTI 0 N S HANDLES AND HOOK ,gr, - REUSE document,and OF DOCUMENTS the ideas and designs incorporated,as an HOOD OPTION \--I This NO. 24• NOM. 1 FINISHED BACK- ISL/REV INSTALL 72.00" Long ': instrument of professional service is the property of , Western Design Group,Inc. • and is not to be used,in whole 2010 OREGON MECHANICAL VENTILATION REQUIREMENT 1 % or in part,for any reason without the written authorization of i I Western Design Group,Inc. UNIT ROOM AREA AREA PERSONS NO. OF CFM PER CFM O.A. S.A. O.A. NOTES FINISHED BACK NO. NO. S.F. SERVED PER 1000 S.F. PEOPLE PERSON PER S.F. REQUIRED PROVIDED PROVIDED DATE ISSUE IAC-1 441 BOH 10 4 7.5 0.18 112 600 175 B GREASE DRAIN XX.XX.XX PRELIM 424 KITCHEN 10 3 7.5 0.18 80 700 200 WITH REMOVABLE XX.XX.XX PERMIT 402 CORRIDOR/RESTROOMS 0 0 0 0.06 25 200 25 TOTAL 909 7 217 1500 400 A NOTES: A BALANCE UNIT OUTSIDE AIR TO 26% B SPACES COMMUNICATE 2010 OREGON MECHANICAL VENTILATION REQUIREMENT c UNIT ROOM AREA AREA PERSONS NO. OF CFM PER CFM O.A. S.A. O.A NOTES NO. NO. S.F. SERVED PER 1000 S.F. PEOPLE PERSON PER S.F. REQUIRED PROVIDED PROVIDED c 00 AC-4 1054 DINING 70 74 7.5 0.18 745 2800 1000 B TOTAL 1054 74 745 2800 1000 A NOTES: A BALANCE UNIT OUTSIDE AIR TO 36% B SPACES COMMUNICATE DRAWN BY BKG CHECKED BY JLT JOB # : I I I I - SCALE: AS NOTED SHEET NUMBER SECTION VIEW - MODEL 3624ND-2 M2 . O ■ , �,r/ OUTSIDE AIR '- (SEE SCHEDULES) V/0/14z ` •,� (I CRC. Bala. '!v SECURE TO 2" WIDE ACOUSTICAL m ' CO ` TO STRUCTURE ABOVE METAL STRAPS FLEXIBLE DUCT �i�_ T �� 6 FT. LONG 0 MANUF. TO PROVIDE INTERNAL CIRCUIT . VOLUME DAMPER LINE SUPPLY AIR DUCT SUPPLY RETURN VOLTAGE = BREAKER. "+-*-• . -,.. (E) ROOF CURB. . • • 45° 1111111111111111011■ / FLEXIBLE CONNECTION. CEILING ®m U\ SOUND LINER, TYPICAL. STRUCTURE z TYPICAL. RETURN AIR PLENUM. VERIFY SIZE SHEET METAL EXHAUST v v W SUPPLY AIR PLENUM. IN THE FIELD. DUCT W 1 1 P R Z RETURN AIR DUCT. SIZE TO MATCH I SUPPLY AIR DUCT. z L CEILING DIFFUSER / CEILING SEE SHEET M-5 EXISTING RETURN AIR PLENUM. ®® LOW 110lTAGE (; W FOR SIZE. i 0© 1 1 1 1 1 1 1 ® O. C� 1. RETURN AIR REGISTER INSTALLATION SIMILAR DUCT SMOKE DETECTOR. O Y 0 E2 INTERLOCK WITH RESPECTIVE AC ) I 1 � 1 � 1 � � E 2. ALL DUCT INSULATION SHALL HAVE A FLAME FOR AUTOMATIC SHUTDOWN. / - i I \ / 1 1 1 1 1 1 1 0 _ SPREAD OF NOT MORE THAN 25 AND A -j Z SMOKE-DENSITY NOT EXCEEDING 50 PER KEYNOTE: (N) 24°X17" IR f---FROG O MN VERIFY EXACT WIRING PER 0 (N) DUCT TRANSITION. SECTION 605.0, CMG. CONTRACTOR SHALL FURNISH AND INSTALL MANUFACTURER'S INSTRUCTION U) Z A Y" STAINLESS STEEL MESH SCREEN OVER (N) 1" DUCT LINER. CEILING BEFORE INSTALLATION. w `3 THE RETURN PLENUM OPENING. (N) TURNING VANES. O O i Q SCALE SCALE SCALE SCALE J CEILING DIFFUSER DETAIL NONE 0 ROOF TOP UNIT NONE EXHAUST FAN DETAIL NONE OD RTU CONTROL DIAGRAM w o 1/4" DIA. SET SCREW 1" x 1/8" W 1- Z GALVANIZED STRAP 0 SPOTWELD I "16 GAUGE GALVANIZED Z BDE ■ STRAP MINIMUM HANGER SIZES FOR ROUND DUCT • CIRCUIT I 1/4 INCH LESS THAN I SECTION A-A HANGER MAXIMUM WIRE 0I • • • • O BREAKER--{ DUCT DIAMETER RATED DIA SPACING DIA. ROD STRAP 3/8" SQUARE ROD END BEARING FASTENER. 10" DN. 12' ONE 12 GA. 1/4" 1" x 22 GA. ___ 2541016-0m1 m DN. 3.7 m ONE 2.75 mm 6.4 mm 25.4 x 0.85 mm 24" MAX LIGHTING 1 , 3/8" SQUARE ROD GASKET CENTERLINE OF r- CENTERLINE OF CIRCUIT. I g 11 1 \ 8" OR ONE 8 GA 1/4" 1" x 22 GA. THERMOSTAT, - A THERMOSTAT, © ___J I I mm 3.172'm ONE 4.27 mm 6.4 mm 25.4 x 0.85 mm IXCI SWITCH, SWITCH, IA OUTLET, j �- OUTLET, NI9II I \ 24 INCH DIA MAX. 19-24" 12' TWO 10 GA. 1/4" 1" x 22 GA. Ce <cc (Y) Q CONTROL. a CONTROL. n A A (WIRE HANGERS 610 mm 3.7 m TWO 3.51 mm 6.4 mm 25.4 x 0.85 mm < Z D N I I ' NOT PERMUTED) D I'M a N 1 I I l GASKET >- G W u) r . M ce FINISHED FINISHED \ I I O I I / INDICATING HANDLE 0 Z ° 0 il I: , t FLOOR. NOTES: 0 Z j I L 1. FOR HANGERS SIZE AND SPACING, TABLE ABOVE. J 0 0 0 PLAN � � � z .. v©© NOTE: REGULATOR � PLAN 2. FOR UPPER ATTACHMENT TO BUILDING, SEE DETAIL L/M-2. W 0 - I 0 LOCK DAMPER DURING AIR BALANCE AND MARK QUAD' TO RECORD AIR BALANCE POSITION. PROVIDE "HAT" 3. FOR NON-GREASE DUCT INSTALLATION ONLY. ' Z Z Q I.I.. SECTION AT QUADRANT FOR ALL EXTERNALLY INSULATED DUCTWORK. PROVIDE FLUORESCENT COLORED MARKERS AT ALL VOLUME DAMPER LOCATIONS. = Z Q (E) THERMOSTAT LOCATION Sc ® EXHAUST FAN CONTROL WIRING SCALE MANUAL VOLUME DAMPER SCALE ® ROUND DUCT SUPPORT DETAIL SCALE Q w 0 I NODE NONE E NONE NONE I- CO ' 4f > N HANGER STRAPS 16,, KEY NOTES: o �� RECTANGULAR DUCT HANGER MINIMUM SIZE DUCT C 60" MAX. DURODYNE WELDED _ 0 14"0 EXH. DUCT. WITH "THERMAL O GREASE DUCT SHALL BE MAXIMUM PAIR OF PAIR OF PAIR OF PAIR OF HEAD PIN TYP .0.4.-.. CERAMICS" FlREMASTER DUCT CONSTRUCTED WITH MINIMUM 16 HALF OF 10 FT. SPACING 8 FT. SPACING 5 FT. SPACING 4 FT. SPACING ( ) ♦•���4.4• WRAP. SEE SHEET M-4 FOR GAUGE GALVANIZED SHEET METAL DUCT �1 j ENTIRE INSIDE DUCT WITH WELDED SEAMS. PERIMETER WIRE/ WIRE/ WIRE/ WIRE/ `g FURTHER DETAIL. STRAP ROD STRAP ROD STRAP ROD STRAP ROD ....._ SURFACE SPRAYED SHEET TITLE �!.•:. CONTRACTOR SHALL SLOPE THE WITH ADHESIVE VERTICAL EXHAUST • EXHAUST AIR DUCT NO LESS MECHANICAL >zc P/2=30" 1"x22 10 GA. 1"x22 10 GA. 1"x22 12 GA. 1"x22 12 GA. '=j, THAN Y4" PER LINER FOOT. EXHAUST DUCT - DISCHARGE DETAILS GA. (.135") GA. (.135") GA. (.106") GA. (.106") n r.G. cite ;�•.�\ N6 `� s!..: 1 0 r ' ::::::::: °o. . ,,,..... ii FlOgi :II . ; z.sp a A ' 1,1i1 f ' ii,o2 4) itr ittilii 0101 Irk, o TOY . if „ , _ 1. 0 . ,, c.,... . $ / ..... cs I( - al 1 rill 51 ii / i ;- I ' � I : ; J 0 71/4 id ' vie; % I Ilti Tt - - - - . 0 lr • I 8 § r ' 17D....__„: 7,, I -. 1. „_. , tr! lik et li 7 ' '. r4*- : 1, I i -, 14!: ,-_ % r ", , . Els va— • ozR fr.' ° " V... Y , 1-;a 04/124, 7" '1 :- - H rj : -. 1 • Pni , 3115 00 . .. 11191 ' 3 i 1 i FS 1 0 . . illr ; i . p I v 31 4 -...-- 1 . . ii 0 1 '1, .1 q ; 0 ,, ei o 0 gli 14 1 1 - Le o ;; 0 0 RdidiliWO � . � _ fie N \-**1 o �'_ F a€ . e """""" m , .. 0 ,..„ 7jH H ,, ,. e ... .. V. C p irsi ra ; ,�I 4. 1 1 . 1: : : 9 . , 1 , „ , . , B 9 fr! 1 . � if B qgill ij re MiNP3-91 liQi itif rs4 411f Ai i g i Nom' 11 " Q t ,11 Idni i 1 iiir i ft 1 V.1,: : :: i3i, . , i> . . • if g al Qr ' N'' ' 14:1i.4' i -1 klii.! ,: E - Wjai. ..: . .... 0 * KL ' 4 `j 4: 2 : 0 i di 1 i nu ; 'iiiti1 T n ,.,„:, 8 F:1 .:, 4 : , .1*.,7,4..:: . 00 : § I , ill' -.1 'ii .q, -En F3 ifillifiliflaillippilainyjilMiltilliliplifliii 'J'1ll'9 tqb t o :S e. ; ti et * : III ti 1LT .1 111111101# il Whielligilliiiguilidili II P3 I 11111 111 I i 121.1114 Whig Atli 11/1111111g )211 ii X*) 1- iri a 1 14141141/ rid /1 If tl 1 11" milill ir wt, hit If 1 , 11 iiiiii, t! !ill I, ! 1111 If afilli„ 1 . il 21 '41 1 I 1 ii f [wiz 1141 /nil 11 1 itgi 'f infl Oil ' I WI I 1 1 1 t rw" ! osil t! I fill il 1 0 t il 1 1 I ii I Ca NI 4 t mi al )0 r j � Q�il��, i�$a eye i Ett' eeil ' a} e,�t� � re ; P�J�I1i��}�l?� g iy(t� � I� � ��' :8= tg� � •� �e�� a�i� pe� €i�ags� ��. l ip�111ijli ����f �il � � . a{ �@. �r iF17I� �` e 1 ���F t i � J [�� � � ���� ' ��6�� f} t - ° �sE° ►9°ti¢i � °e �tIr` t i. � � P6 �; �t ;Ilgg etg `�(l ie$}t f� p �1r�+'�B�}Z . 9ei��8 i[r �4! !�; l lt��6leifiiji �8t$ . �O' E��i`yd��i �s[iIEB �ee [ H9 ( �d �iel� iE i. �I 4:, 1411111=q111� �It �i�ftii�•7a� �=��� g�# i� '�+#al ' ad[��� 6 d�li �E 3adi�& t... , et1 !t`1 ;r �8� t i �� T .t��;` � i �� • ��t� �P 6��31'Icri3�� 11 , . .� •r�l i0i -:`I� $H!' tK���lil°j a �a9€ ��t :r B. t [ � (�r�. g t. �� g -��{Bd ,Ba[ i!i} �r7 �1 �! � e a tie li � �r [Hl�� icz r}li i114111111111111111� ��rF � ��1�;� c E [9 . � . + jij�.. . � i 6 e;;11; 1111111111111111111.111111111111101W111111/10111401111111 tt !e°�i �. {{ . � f �!_} r �{i ` 3 .t8 Z. �g a � i� {9r [IF 1 } �t��E�}BIF� yt� t €rd IFet�l*�' �}3 � �[Ei � r HiPt ! ri�S 1 }�i. li � t I•p �Q] jir e i � t r � 'I�f i 1l � s a t g lt ,1���ae .Y1Rt�I liii li g r �igliplwigi tj S � �� i�1 f}H`t gS� �a{ {!fl{ Q �g �.yjlo�l ¢i ��j ti7 [�`��plrli�Igiittsll 1��!en�ola B'¢�1i91t � ;' i � E� � �yg9 !' Sr r �� 5 �al�ilp� 1 •� P1111111 1 . jItlH � 1� ° � 1F . s (�l a'i;�•� 1 Inlr 1 .1r� �� i # H �� � r II1��� ��°' :� `! ��iE,� i ivi It 111 it{ 11�1� � E 11: erlifrOiliskilli ji ' B I Ifiti I �I(tIIFt 11111111111111q1111 ;t � ji 11111111Iff� i ,tifi1�411llt i I ; ft�l1:f/f � fff9 � � €ia�• 1 [ l, 19 . 1611 •e } 3 lirli OW 1I i i' III, 9 s € i 1 ia I itsl t i It lid 111111iii i P P= ifS r [1'i nF1 ii ` E } [ i ' Y A 3 - ! P i, q . . i11011,11[11 1 /011/11 jigifIlIg64111 R 111/0 1 4411111111111 11111111e111141111111;1111111T1 � i 1}ilk il i . (IBWiIt } H � {11 i1 � i' Ps it1t� 8 ' i t 'lF� 1 l[l °�" g j{. (� 81:5 } ia l } T l � 11140111 4'}I tralige Og ill ph !t t ! 1 ill i ' r il 3 II [s : 11114111, � 4y,i j . h{p �111 t [`1 �as ioil d � ili i te � i � a ; 1 lt! � i if $ E� f � 2111. k s 11. ii I�� � + 1110111111 111111111 /11j1/I411111 / & }f[ sk` ji te t i1"1 il' , 1 H 1 4x1t[1 �,i ,sd{�jt/11zr0i$[� r�tt 1111111111 Mil 4# lialli Iii ill 11 ;�� I € 1 yp 1� �jll � }� i :�40� ni� f ��p � $ ; � ji1 1i I, pi III�� F i; � ( t� � j 0 e l apg li iiP6E[iett td lni! 6iii rii [ Ii(litig;f !liiei� wr 1 fil[wa1 fillifiligliniai"1" 411" 11g"11111111011111" � 1Islifig`tt111111� ( gPe &q ;gq6I9g # F� I111-4 H � 1 � g 101 Mil lill lifIliiil1r 11R e I c i 1l �i s!° �l :: 1 f c Iiill# I 1111111111141111111111111 E 1 I 4� ai 11111114 7tiB lsi 1 , 1 1 1 9 i`` r e ( rli i t fat i t !milt f }, ( 1 I �' i111111111111111111 1141 , t Ifi i i i II Pities I'd i iitif t t; It g m 0 0 � � o is ° t # 1 - a ' HaN PIEOLOGY 0 WESTERN DESIGN GROUP ', K � m � $ � P � gi� a�t �I� o Sy WASHINGTON SQUARE 01 7 'AI' a q y U3 -- - TENANT IMPROVEMENT Suite Vancouver,.,�.m 'po � y } g m 10112 SW WASHINGTON SQUARE RD �°�"v�°°" ifigN„ ' ! y � m " � 'g ' e ( m i TIGARD, OR 97223 IN CONSULTATION WITH: RIDGE ENGINEERING 6-27- . litftil' iili HVAC NOTES lillerr� 1. CONTRACTOR SHALL PAINT ALL EXPOSED DUCTWORK AND DIFFUSERS. PLEASE SEE ARCHITECTURAL DRAWINGS FOR COLOR. 4 TO 2. CONTRACTOR SHALL INSTALL THE DUCTWORK AS HIGH AS POSSIBLE. i►. : : *- L UN1 B 3. EXHAUST AIR DUCTS SHALL BE EQUIPPED WITH BACK-DRAFT DAMPERS. : 4. TURBINE UPDRAFT EXHAUST FANS SHALL BE HINGED AND CHAINED FOR CLEANING OF VERTICAL DUCT. 5. DUCT OPENINGS AND OTHER RELATED MR DISTRIBUTION OPENINGS SHALL BE COVERED DURING CONSTRUCTION. 6. PROVIDE THE BUILDING OWNER OR REPRESENTATIVE WITH DETAILED OPERATING AND MAINTENANCE 0 INSTRUCTIONS AND COPIES OF GUARANTIES/WARRANTIES FOR EACH SYSTEM. O&M INSTRUCTIONS SHALL Z BE CONSISTENT WITH OSHA REQUIREMENTS AND OTHER RELATED REGULATIONS. CC 7. AN INTERLOCKING SWITCH WILL BE PROVIDED BETWEEN HOOD EXHAUST AND MAKE UP AIR SYSTEM. w 8. THE EXHAUST HOOD WILL BE PROVIDED WITH 100% MECHANICAL MAKE-UP MR AND AN INTERLCOKING z ELECTRICAL SWITCH. 0 Z w w O Fe KEY » NOTES ce Q NEW 1411 GREASE DUCT UP THROUGH ROOF TO EF-3. SEE SHEET 11-6 FOR CONTINUATION. Z C9 © 14'0 16 GAUGE GALVANIZED SHEET METAL DUCT WITH WELDED SEAMS UP THROUGH ROOF TO EF-3. w O SEE SHEET M-6 FOR CONTINUATION. 14'4 EXHAUST MR DUCT SHALL BE FIRE WRAPPED. SEE SHEET o F= M-4 FOR FIRE WRAP INSTALLATION. SEE DETAIL M/M-3. ZZ J CONTRACTOR SHALL INSTALL THE DIFFUSER AT THE SAME HEIGHT THE SURROUNDING FIXTURES. w u © EIGFIT AS LIGHT H- Z 0 O 16"X16" SUPPLY AND 24'X14' RETURN AIR PLENUMS. CONTRACTOR SHALL FURNISH AND INSTALL 1' t V SOUND LINER. z © 24"X16' OSA INTAKE WITH MOTORIZED DAMPER. • i • 0 BALANCE TO 1,800 CFM. 0 mill • • • • 0 BALANCE TO 1,100 CFM. Q CONTRACTOR SHALL CONNECT GALVANIZED SHEET METAL DUCT DIRECTLY ONTO AIR TERMINAL DEVICE. NO FLEXIBLE CONNECTION. N' Ce 0 E IS11NG. Co FURNISH AND INSTALL Y4' SCREEN MESH OVER RETURN PLENUM OPENING. LU LU LU 0 ROOF. CI SHORTEN DUCT DROPS FROM AC-3 AND RECONNECT BRANCH DUCTS TO AVOID HOOD EXHAUST Ce F- Q M DUCTWORK. < W = N ,_- CD FURNISH AND INSTALL 1' SOUND UNER. SEE DETAIL K/M-3. r>.. a w Cl) N TO T-STAY SERVING AC 111 U. -+ IX ^ IX r� ® CONNECT EXHAUST DUCTWORK FROM EF-1 AND EF-2 TO EXISTING EXHAUST OPENING. V C > Z Nu ��� n � 0 2 Zoo Ce f:°O°°01 -I∎ „._,. � H� :-1 3■-1 ° THIS NOTE NOT USED. O o 101 - r� r� t/ ® OaZO.1 IIh1�0 4 I u ! 6 SEE DETAIL J/M-3. TYPICAL O = Q . Coil) 0 I ( I i -�I 402) SEE DETAIL H/M-3. TYPICAL ~ Ct MENS W Z Z Q 1 I WOMENS QL pr ,; _ 1102 ® Q� SEE DETAIL G/M-3. TYPICAL. = Q r / ,' RR-1 , V) W;►�• CFM SEE DETAIL E/M-3. TYPICAL 1 L?rI• ccD3T E- = • , Ii : I r 200 CFM € MINIMUM 1 DOOR UNDERCUT. CD-1 GQ►A _ 1" CD-1 IA _... i ti L1� 1 -' I�J�� O . 500 «'' V47 © � Vzi © TO T-STAT I r r��r j' SEE DETAIL A/M-3. TYPICAL SERVING 1 AC-1. i 1 2'I II 111111 I _1 -16"6 II l r-- . i 11-2. ���� �'� ' , II • ~ SHEET TITLE I I /1� , :. :rte • . �•� . .:� .�;� .;... �!.•�J,:_.:•'.!•:1'_i_._.,P,0 i_i•O L__ I CD-2 I I :ice `' cD-3 w :-e , _.-� . - UM MECHANICAL 350 CFM'01' 0 I I • 300 CFN ••4 12'f iiii- . I -�-- it= I!I - RESTROOM EXHAUST AIR CALCULATION: PLAN 160 7160 10 . ,; i 4 J 48X24 1 ' WOMEN'S RESTROOM f, ;;. AREA: 54 SQUARE FEET.I. I I KITCHEN I I I I r■I!I I CQUNG HEIGHT: 8.0 FEET. I- -I f • L__ ' �� B.O.H. 18"!1 VOLUME: 54 SQUARE FEET X 8.0 FEET = 432 CUBIC FEET. DINING I T - J ,,;; MINIMUM AIR CHANGES: 12 AIR CHANGES. CO 100 © EXHAUST CFM = VOLUME X MINIMUM AIR CHANGES 86 CFA. O e I I 60 ' /M, {'- t�+�, i 2 ` .: EXHAUST CFM FOR EF-1: 100 CFA. '' REUSE OF DOCUMENTS V 500 CFM si. 500 CFM 0 0 - - - -- - ----- --- --- - :.::•::•:•:❖:•::❖:. ------ Er CD-1 1p CD-1 12 MEN'S RESTROOM This document,and the ideas r i 4D j ABOVE AREA: 54 SQUARE FEET. and designs incorporated,as an TYPE 11 KITCHEN CEIUNG 11, CEIUNG HEIGHT: 8.0 FEET. instrument of professional HOOD.1i SEE VOLUME: 54 SQUARE FEET X 8.0 FEET = 432 CUBIC FEET. service is the properly of I SHEET$ M-2 AND/ 11I e.9 e MINIMUM AIR CHANGES: 12 AIR CHANGES. Western Design Group,Inc. L . N L J p EXHAUST CFM = VOLUME X MINIMUM MR CHANGES = 86 CFM. and is not to be used,in whole GS or in part,for any reason without 12"f® '12'0® l J 1 n EXHAUST CFM FOR EF-2: 100 CFM. the written authorization of I- - 1-i T __v I Western Design Group,Inc. I--� •I---1� � � 10". 10'+` . GREASE DUCT AIR VELOCITY CALCULATIONS: --- � o- - v DATE ISSUE D D I EXHAUST CFM REQUIRED FOR KITCHEN HOOD: 1,200 CFM m1'I^ �- �� o Q SIZE OF MANN GREASE DUCT: 1411 = 0.91 SQ. FT. XX.XX.XX PRELIM -'-- I; �- CD-2 ( 1 4. i VELOCITY OF AR INSIDE GREASE DUCT 1,200 CFM / 0.91 SQ. FT. = 1,318 FT/MIN. )Q(,)Q(,)Q( PERMIT Il- I�t t"1] O 350 CFM `=4r� 500 CFM 400 UM N 1 CD-3 • 0 CD-1 0 CD-1 I�U 1 300 CFM l KITCHEN HOOD 8c RESTROOMS MAKE UP AIR CALCULATION o �_ SUPPLY AR FROM AC-3: 1,500 CFM. (1-N% RETURN AR BACK TO AC-1: 1,100 CFM. 111 CONDITIONED MR FROM AC-1 N. de- 4. i i Fr==__ =_ i IT==_4 t THAT IS BEING USED AS MAKE I - - -nil- I - -_ ' -- 1 UP AIR: 1,500-1,100= 400 CFA. 4 L _ ==1 _=J 4 SUPPLY AR FROM AC-4: 2,800 CFM. RETURN AR BACK TO PC-4: 1,800 CFM. CONDITIONED AIR FROM AC-2 THAT IS BEING USED AS MAKE UP AIR: 2,800-1,800= 1,000 CFM. TOTAL MAKE UP AIR: 400 + 1,000 = 1.400 CFM EXHAUST FROM EF-1: 100 CFM DRAWN BY BKG EXHAUST FROM EF-2: 100 CFM CHECKED BY JLT EXHAUST FROM EF-3: 1,200 CFM TOTAL EXHAUST AIR: 1,200 + 100 + 100 = 1.400 CF'M JOB # : SCALE: AS NOTED SHEET NUMBER MECHANICAL PLAN SCALE 1 4"= 1 '-0" M5 .O . , Vi 1 r,rl Sliiinf L. T pR ` P I ,.!_.Tiant KEY NOTES: 0 O GAS WATER HEATER COMBUSTION INTAKE AND Z FLUE SHALL TERMINATE MINIMUM 24* ABOVE Fe STING PARAPET. VENT TERMINATION SHALL w EXI FACE DOWNWARD. SEE PLUMBING DRAWINGS Z FOR EXACT LOCATION. 0 z w w a o 0 Fe lY Z I- z 0 0 0 3 1= z J w o u) col— � z V O z • i 1 . • • • 0 ce w w W I— Q C'7 w a N ti * !STING W Z C) 0 0u) > 0 p ._ 0 O gym ? o (D — = 0 I I I I W _ o- ? ZQ Ce ROOF MECHANICAL = Z �<nn WELL - w5. V o .- %. Vc- . . , . . . �,, �`. Rio` 0. SHEET TITLE — MECHANICAL ,\ ROOF PLAN EF 1 I 3 ` `% I 1 , ,.... I t(E) AC-3 SERVING \\ I ADJACENT SPACE REUSE OF DOCUMENTS ■ i This document,and the ideas i and designs incorporated,as an '\ / instrument of professional service is the property of . / Western Design Group,Inc. . /' and is not to be used, in whole . , `. ,, or in part,for any reason without (E) AC-2 SERVING the written authorization of �.� ADJACENT SPACE Western Design Group, Inc. DATE ISSUE XX.XX.XX PRELIM XX.XX.XX PERMIT /-EXISTING Ank v DRAWN BY BKG CHECKED BY JLT JOB # : _ \ SCALE: AS NOTED SHEET NUMBER SCALE MECHANICAL ROOF PLAN i 4»= 1 '—O» M6 . O•. ,