Specifications "FPS 2-012— Oo t Cs
�la� a SW DL -hafl + /00
14795 S.W. 72nd t DELTA PORTLAND, OR 97224
PHONE 503-620-4020
-FIRE INC. CCBIt 641674 1058 0CT
CITY OF TIGARD
B
DfNG DIVISION
Pactrust Business Center
Indio Inc.
DATA SUBMITTAL
FOR
FIRE PROTECTION SYSTEM
•
SHOP DRAWING AND SUBMITTAL REVIEW
D CONFORMS TO DESIGN C MCEPT
U =FORMS TO DESIGN CONCEPT EXCEPT AS NOTED
NONCONFOININ4,WINE AND RESUBMIT
O
REVIEWED
THIS SUBPQTTA& HAS BSI NEVEM rat OMAN. mMFORE+ANCE
WITH THE DESDGN CONCEPT OF THE PIt)W AND GENBTAL COMPLIANCE
WITH THE D*ORMATION G1YB1 N THE CONTRACT DOCUMENTS. ANY
ACTION 9 15 SUIUEtT TO THE REQUIREMENTS OF THE IMAMS,
SPECIFICATIONS AND APPEICAI E CODES,ALL OF WHICH HAVE PRIORITY
OVER THIS SUBMITTAL. CONTRACTOR IS iIESFONSTBtE FOR QUALITY
DIMENSIONS(WHICH SHALL BE CONFIRMED AND CORRELATED AT THE
OD SITE), FABRICATION PROCESSES AND TECHNIQUES OF
CONSTRUCTION, COORDINATION OF THE WORK WITH THAT OF AU.
OTHER TRADES AND THE SATISFACTORY PERFORMANCE OF THE MAX_
PacTnj st
DE-. /0/2
October 23, 2012
125049
FIRE PROTECTION CONTRACTORS
D 14795 S.W. 72 Avenue
PORTLAND, OR 97224
PHONE 503-620-4020
• FIRE, INC. CCB# 64 74 1058
S •rin kit e r e a s
FIRE PROTECTION CONTRACTORS
Bulletin 014 Rev. F
co
Re1iabI ModLiEies cp
QuicStany
Model Fl FR56 Sprinkler Types
Standard Upright o ,; -
Standard Pendent �� --~
Conventional ;, 40 1
Vertical Sidewall
Horizontal Sidewall � °
Model F1FR56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP Upright Pendent
Horizontal Sidewall
Model Fl FR56 Concealed Sprinkler Types -
Standard Pendent
OA .
a it
Listing & Approvals
1. Underwriters Laboratories Inc. and Certified for
Canada(cULus). A
2. Factory Mutual Approvals (FM) Vertical Sidewall Conventional
3. Loss Prevention Council (LPCB, UK)
4. VdS Schadenverhutung GmbH
UL Listing Category x£
Sprinklers, Automatic&Open (VNIV)
C e___•_.e4 jk
- Quick Response Sprinkler j , t l' IF.
Product Description
Reliable Models F1FR56 Series Sprinklers are quick re-
sponse sprinklers which combine the durability of a Stan- Horizontal Sidewall Recessed
dard sprinkler with the attractive low profile of a decorative Pendent/F1/F2
sprinkler.
The Models F1FR56 Series Recessed automatic sprin-
klers utilize a 3.0 mm frangible glass bulb. These sprin- ' "'=- ,.
klers have demonstrated response times in laboratory tests r • , N.,T
which are five to ten times faster than standard response t volt
sprinklers. This quick response enables the Model F1FR56
P q P
- k It. . 'Series sprinklers to apply water to a fire much faster than -.._°;, ...A`
standard sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount Recessed Recessed
of special fluid hermetically sealed inside a precisely manu- Horizontal Sidewall Pendent/FP
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response. Application
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can Quick response sprinklers are used in fixed fire protec
be seen as a small bubble. As heat is applied, the liquid tion systems: Wet, Dry, Deluge or Preaction. Care must be
expands,forcing the bubble smaller and smaller as the liq exercised that the orifice size, temperature rating, deflec-
uid pressure increases. Continued heating forces the liquid
tor style and sprinkler type are in accordance with the lat-
to push out against the bulb, causing the glass to shatter, est published standards of the National Fire Protection As-
sociation or the approving Authority Having Jurisdiction.
ute the discharging water. Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model Fl FR56 Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal Thread Nominal K Factor Sprinkler Approval Sprinkler IdenSfication Number
(SIN)
Orifice Size Height Organization
• US Metric Upright r Pendent
Standard-Upright(SSU)and pendent Deflectors Marked to Indicate Position
1/2"(15mm) 1/2"NPT(R1/2) 5.6 80 2.25"(57mm) 1,2,3,4 RA142501 J RA1414 0x2)
Conventional-Install in Upright or Pendent Position
15mm1'1 1/2"NPT(R'/2) 5.6 80 57mm 3,4 RA1475
(1)cULus listed corrosion resistant(Polyester coated)sprinkler.
(2)Polyester coated FM approved sprinkler.
33 0
:. r -
Upright Pendent Conventional
Model Fl FR56 Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Sprinkler Identification Number
• Orifice Size US Metric Height (SIN)
1"(15mm) 1/2" NPT(R1/2) 5.6 80 2.25"(57mm) RA1414
(" Refer to escutcheon data table for approvals and dimensions.
2 5/6"DIA. [66.7mm]
1 1/4•HOLE Du. HOLE IN CEILING
~ (572mm]
r 75/16"DM
2 5/16"0L4. [58.7mm]
F (49.2mmj CUP
___=_a L==t'_==—
r I 1
7"K 1/2•REDUCER I _ _ I 1"X I/2 REDUCER
TURN COLLAR
UNTIL TIGHT
AGAINST SPRINKLER I I I I
WRENCH BOSS \1 III
///�/7J 1 r -l 1 `\ -- /
-I—�� 1 t_„=�I.1=.1_.7 FACE OF FITTING ro('1 CEILING
(11 CE/UNG DIMENSION
AD/us7MEN llp`o !111/1//%L 1 t FACE OF G
I`i II 'IiI 1 "&Ilid ONIp1W.,ION(1J 4 (J2mmJ IM I
L (J , /. A r)
ADJUSTMENT
1 27/31-D9L 014FGO7 ••-— -• --
(72.2mmJ 074Fa01
• L (1)REFER TO F1 k F2 ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS (IJ REFER TO FP ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
Model F1FR56/F1 or F2 Model F1FR56/FP
2.
- Model Fl FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
' Nominal Nominal K Factor Sprinkler Approval Sprinkler
Orifice Thread Size US Metric Height Organizations Identification
Numbers(SIN)
'h"(15mm) 1/2" NPT(R1/2) 5.6 8.0 2.25"(57mm) 1,2,3,4
RA1485
15mm 'h"NPT(R1/2) 5.6 8.0 2.25"(57mm) 40)
")LPC Approval is for pendent position only.
Sprinkler Type Deflector to Ceiling Distance
(Min. -Max.)
ipit
Upright 4"(102mm) 12"(305mm)
Pendent 4"(102mm)-12"(305mm)
Vertical Sidewall
Model Fl FR56 Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW
Installation Wrench: Model D Sprinkler Wrench
Installation Data: Horizontal Sidewall
Nominal K Factor Sprinkler Approval Organizations
Height and Type of Approval Sprinkler
Nominal Orifice Thread Size Identification
US Metric Light Hazard Ordinary Numbers(SIN)
Hazard
1/2"(15mm) 1/2"NPT(R1/2) 5.6 80 2.63"(67mm) 1,2 1 RA1435
FACE OF FITTING(1)
TO FACE OF CEILING
DIMENSION 1 1/4"MIN.
2 1/4"HOLE DLA. [31.8mm] 4"-12"
�. (57.2mm] 1/B" [101.6mm-304.8mm]
(3.2mmJ CEILING TO
1"X 1/2"REDUCER DEFLECTOR
-II%
WV _ _ �_
a - r L
C -f1�
1 15/16"DLA. l I I II
(49.2mm] 1-i 1 I II - �4 2 27/32"DN.
L I`-'----1---i -1--.Al [72.2mm]
1111 All
Horizontal Sidewall l i
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER `\.
WRENCH BOSS. II
- -.I La-ADJUSTMENT
ot,W50J4
(1) REFER TO ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
• (2) FM APPROVED FOR 4" - 6"(101.6MM - 152.41,114 CEILING TO DEFLECTOR.
Note: For Recessed HSW Sprinklers use installation wrench GFR2.
3.
Model Fl FR56 Quick Response Concealed Pendent Sprinklers
: Installation Wrench: Model RC1 Sprinkler Wrench
Technical Data:
Nominal "K" Factor Thread Temp. Rating Max. Bulb Sprinkler
Orifice Size Model Ambient Color Approvals Identification
US Metric Sprinkler Cover Temp Number(SIN)
'/z"(15mm) 5.6 80 '/" NPT F1FR 135°F/57°C 135°F/57°C 100°F/38°C Orange 1,2 RA1414
1/2"(15mm) 5.6 80 1/2" NPT F1FR 155°F/68°C 135°F/57°C 100°F/38°C Red 1, 2,4111 RA1414
1/2"(15mm) 5.6 80 '/2" NPT F1FR 175°F/79°C 165°F/74°C 100°F/38°C Yellow 1,2 RA1414
1/2"(15mm) 5.6 80 1/2"NPT F1FR 200°F/93°C 165°F/74°C 100°F/38°C ' Green 1,2 RA1414
(')For VdS only= 155°F/68°C Norbulb and 1/2"[12,7mm]adjustment.
7-x 1/2"REDUCING
TEE OR ELBOW ---°----..
I"x 1/2"REDUCING
-- s—
m
Tr-------- TEE OR ELBOW
-- •—•----fN—'———'-------X44--'--- ---—..n. �.._..--
1--1 i r--,— 2 5/8"DIA. --._..11 I •ll — —2 5/16"DIA — HOLE IN CEILING —,---1 _— 2 5/8`01A.
2 5/16"DIA — HOLE IN CEILING
CUP -_�� I J—
l'V•ul 1 1/2"MAX. CUP ��—�� 4
p I _-- ' 1 1 2"MAX.
,f I I FACE OF FITTING C!Z-1l /
NI H �1 TO FACE OF CEILING ---•- ( I FACE OF FITTING
T,-;T;� DIMENSION I'� �l TO FACE OF CEILING
�. ; j..:,*,;;. :i 1T ::-...CEILING ! { `111�i1 _. D!M£0SION`Iii— CEILING \\. %�� -11111 ii
1/2" MAX. 15/16" 5/16"MAX. �^ 3/4"
COVER ADJUSTMENT COVER ADJUSTMENT
COVER PLATE— COVER PLATE— I t
ASSEMBLY 3 5/16" DIA. t ASSEMBLY 3 5/16"DIA.
■SPRINKLER / SPRINKLER /
1/2" ADJUSTMENT 5/1 6" ADJUSTMENT 01"40:
Figure 1 Figure 2
Installation Aid
A protective cap is included for use during installation. Sprinkler with a threaded Model CCP cup which is fac-
• important: The F1FR56 Sprinkler with Model CCP cover tory attached to the sprinkler. The assembly is complet-
plate is not an FM Approved combination. ed by the installation of the attractive, low profile, 135°F
Installation (57°C) or 165°F (74°C) rated Model CCP push on cover
Quick response sprinklers are intended for installation plate assembly. The cover plate and sprinkler cup as-
as specified in NFPA 13. Quick response sprinklers and semblies are joined using a cover plate skirt with flexible
standard response sprinklers should not be intermixed. tabs for threaded engagement. A choice of two cover
The Model F1FR56 Recessed Quick Response Sprin- plate assemblies provide either 1/2" (13mm)or 5/16" (8mm)
klers are to be installed as shown.The Model Fl or F2 Es- of cover adjustment.
cutcheons illustrated are the only recessed escutcheons Do not install these sprinklers in ceiling which have
to be used with the Model F1FR56 Sprinklers. The use positive pressure in the space above.
of any other recessed escutcheon will void all approvals After a 25/6" (67mm) diameter hole is cut in the ceil-
and negate all warranties. ing, the sprinkler is easily installed with the Model RC1
When installing Model Fl FR56 Sprinklers, use the Mod- Wrench. A Teflon* based thread sealant should be
el D Sprinkler Wrench. Use the Model GFR2 Wrench for applied to the sprinkler threads only. The Model RC1
installing F1FR56 Recessed Pendent Sprinklers. Any Wrench is then used to engage the sprinkler wrenching
other type of wrench may damage these sprinklers. surfaces and to install the sprinkler in the fitting. When
NOTE: A leak tight 1/2" NPT (R1/2) sprinkler joint can inserting or removing the wrench from the sprinkler/cup
be obtained with a torque of 8-18 ft-lbs(10,8-24,4 N-m). assembly, care should be taken to prevent damage to
Do not tighten sprinklers over maximum recommended the sprinkler. DO NOT WRENCH ON ANY OTHER PART
torque. It may cause leakage or impairment of the sprin- OF THE SPRINKLER. The cover plate is then pushed
- klers. onto the cup. Final adjustment is made by hand turning
The Model Fl FR56/CCP Concealed Sprinkler uses the the cover plate until the skirt flange makes full contact
1" orifice, 1/2" NPT (R1/2), 135°F (57°C), 155°F (68°C), with the ceiling. Cover plate removal requires turning in
175°F (79°C) or 200°F (93°C) Model F1FR56 Pendent the counter clockwise direction.
*DuPont Registered Trade Mark
4.
After installation, inspect all sprinklers to ensure that Sprinkler Types
there is a gap between the cover plate and ceiling and Standard Upright
that the four cup slots are open and free from any air flow Standard Pendent
impediment to the space above. Conventional
Concealed cover plate/cup assemblies are listed only Recessed Pendent
for use with specific sprinklers. The use of any other con- Vertical Sidewall
cealed cover plate/cup assembly with the Model Fl FR56 Horizontal Sidewall
Pendent Sprinkler or the use of the Model CCP Concealed Recessed Horizontal sidewall
cover plate assembly on any sprinkler with which it is not Concealed pendent
specifically listed my prevent good fire protection and will
void all guarantees, warranties, listings and approvals. Maximum Working Pressure
Glass bulb sprinklers have orange bulb protectors to 175 psi (12 bar)
minimize bulb damage during shipping, handling and 100% Factory tested hydrostatically to 500 psi (34.5 bar)
installation. REMOVE THIS PROTECTION AT THE TIME Finishes (1)
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR
FIRE PROTECTION. Removal of the protectors before this Standard Finishes
time may leave the bulb vulnerable to damage. RASCO Sprinkler Escutcheon L Cover plate
Bronze Brass
wrenches are designed to install sprinklers when covers Chrome Plated Chrome Chrome
are in place. REMOVE PROTECTORS BY UNDOING THE White Polyester Plated White
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE Coated(4)(5) White Painted
THE PROTECTORS. Special Application Finishes
Sprinkler Escutcheon Cover plate
Temperature Ratings Bright Brass(3) Bright Brass Bright Brass
Sprinkler Black Plated Black Plated Satin
Max.Ambient Black Paint Black Paint Off White
Classification , Temperature Temp. Bulb Color Off White(2) Off White Black Paint
°C °F Satin Chrome Satin Chrome Black Plated
Ordinary 57 135 100°F(38°C) Orange (1) Other finishes and colors are available on special order.
Ordinary 68 155 100°F(38°C) Red Consult the factory for details.
Intermediate 79 175 150°F(66°C) Yellow (2) cULus Listed only.
Intermediate 93 200 150°F(66°C) Green (3) 200°F(93°C)maximum.
High(1) 141 286 225°F(107°C) Blue (4) cULus listed"corrosion resistance"applies to SIN Numbers
("Not available for recessed sprinklers. RA1425(Upright)and RA1414(Pendent)in standard black or white.
(5) FM Approvals finish as"Polyester coated"applies to SIN Number
Escutcheon Data (1) RA1414(Pendent)in standard black or white.
Faced
Esaicheon Approvals Adjustment Ceding W U Ordering Information
Model Dknension
Dimension Specify:
Fl 1,3,4 Max Recess 11/2"(38.1m) 3/16"-15/16' 1. Sprinkler Model
MiRecess 3/4"(19.1m) (5rrm-24mm) 2. Sprinkler Type
F2 1,2,3,4 Max Recess 11"(38.1mm) 3/16'-"/16 3. Orifice Size
min Recess 1"(25rrm) (arm 17m) 4. Deflector Type
FP Push onl Max Recessed 7/16"(11m) 11/2" (38.1 mm)
Thread-off 1,4 Min Recessed 75/16(24mm) 1"(25.4mm) 5. Temperature Rating
(1)SIN:RA1435-cULus and FM permits use with Fl or F2 escutcheons for light 6. Sprinkler Finish
hazard only. 7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Maintenance 9. Cover plate Model
The Models F1FR56 and F1FR56 Recessed Sprinklers 10. Cover plate Thread size
should be inspected quarterly and the sprinkler system 11. Cover plate Temperature
maintained in accordance with NFPA 25. Do not clean 12. Cover plate Adjustment
sprinklers with soap and water, ammonia or any other 13. Cover plate Finish
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler which has Note:When Model F1FR56 Recessed sprinklers are ordered,the sprin-
been painted (other than factory applied) or damaged klers and escutcheons are packaged separately.
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or oper-
ated sprinklers. Prior to installation, sprinklers should be
maintained in the original cartons and packaging to mini-
mize the potential for damage to sprinklers that would
• cause improper operation or non-operation.
5.
- Reliable. . . For ProtectiOn
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
. • Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gaugesldentification signs
• Electrical sprinkler alarm switches • Fire department connection
• Water flow detectors
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. ® Recycled
(80000))4381-6105858 Sales Offices
Paable aper per
(8 848-6051 Sales Fax Revision lines indicate updated or new data.
(914)829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A 02/11 P/N 9999970300
Bulletin 153 Rev.L
co
Model F3 c
®
Dry Sprinklers c
r—
Features --- -'
1. The Model F3 Sprinkler utilizes Belleville Spring I 0 fi,
1
Closure Technology
2. Styles available for Model F3 Dry Sprinklers:
• Pendent
• Recessed Pendent
• Concealed
• Horizontal Sidewall j
• Recessed Horizontal Sidewall
ir -
3. 11/2"" (38mm) escutcheon adjustment on pendent l
sprinkler. `'
4. 1/2" (13mm)escutcheon adjustment on recessed sprin- Pendent Pendent/HB
kler with push-on/thread-off FP Model escutcheon (See Fig. 1) (See Fig. 2)
ring. _
5. 3/8" (9.5mm) cover plate adjustment on concealed
sprinkler with push-on/thread-off CCP cover.
6. Attractive appearance. Employs 5mm frangible glass
bulb and galvanized nipple.
7. Lengths available to accommodate installation di-
mensions from 2" - to - 48" (51mm - to- 1219mm), in
I
1/4" (6mm) increments.
8. Available in a variety of plated and painted finishes.
Ra ;
9. Polyester Coated Corrosion Resistant Sprinklers. -
U.S. Patent Numbers 5,775,431 and 5,967,240. Recessed FP Pendent Concealed
(See Fig. 3) (See Fig. 4)
Approvals
1. Listed by Underwriters Laboratories Inc. and UL
Certified for Canada(cULus).
Style Response Sprinkler Hazard �`'` ,,
System Type _ "...,::�€
Pendent 'r 4,,,,
Recessed Pendent
CCP Concealed Wet Pipe Light
(R5314) Standard Dry Pipe Ordinary
Horizontal Sidewall All Preaction
Recessed Horizontal Sidewall Horizontal Sidewall Horizontal FP Sidewall
(R5334)
2. Certified by FM Approvals (See Fig. 5) (See Fig. 7)
Style Response Sprinkler Hazard
System Type
Pendent Light
Recessed Pendent Wet Pipe Ordinary,
CCP Concealed Standard Dry Pipe Groups
(R5314) All Preaction 1&2 �
Horizontal Sidewall Wet Pipe
Recessed Horizontal Sidewall Standard Dry Pipe Light i',
(R5334) All Preaction
3. NYC MEA 258-93-E
4. LPCB Approved, CE listed 0832-CPD-2006
Horizontal Sidewall/HB
(See Fig. 6)
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F3 Dry Pendent Sprinkler
"A" Dim. 2"to 48"(51mm to 1219mm)in 14"(6mm)increments
- Finishes',, Standard Temperature Ratings
Sprinkler Escutcheon Sprinkler Max.
- I Bronze Brass(51 Classification Temperature Ambient Bulb Color
Chrome Plated Chrome Plated Rating Temp.
White Polyester(4) White Ordinary 135°F (57°C) 100°F (38°C) Orange
. Lead Plated(2) Ordinary 155°F (68°C) 100°F (38°C) Red
Wax Coated[2][3) Intermediate[1) 175°F (79°C) 150°F (66°C) Yellow
Wax Over Lead(2)(3) Intermediate 200°F (93°C) 150°F (66°C) Green
(1)Other finishes and colors are available on special order.Consult factory High 286°F(141°C) 225°F(107°C) _ Blue
for details. Sprinkler can and escutcheon fabricated of brass for better weather
(2)155°F(68°C)to 200°F(93°C)rating only. resistance in exterior applications.
(3) 212°F(100°C) brown wax may be used on 286°F(141°C)sprinklers
when maximum ceiling temperatures do not exceed 150°F(66°C). [']Listed and Certified only by cULus.
14) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
(5)Not available for HB escutcheons. Inlet Protrusion Elevated
Above Inside R«
bust Protn.yon Ele«ted F
Above er:de One } I _
F-- --1 i [-- _ =.OA
___ -r,ll�o,1:::: _^g Syelem Tee
`—_ 1‘--*eh.. ip
et«n r« ■■
M� 'A'Dkeees.n 2 1/2•[63.5mm] t'NPT
Adjustment Range Da.Mob Cai'ILp //
2 t/e'Ma. 1•NPf -t/2'[-tz.7mm]] E«u!n«n obsmm]
•A•n.,t Ren [.in Cm] +1/2'(+tx.7mm]
Ad -6 Renge Mob in CNllry IIII
-1/4' -6.35mm] t/z•[t z.7mm]
+1 1/0 [+31.75rnm] ,43/..ob. 1 l/2•[3e.t0mm] I -- Eeootn«n la].
[42.47mm] 'I�I total Aeluetmenl LClling 1'[25.4
s«Intl«Can 1r i c..on93 r 1 1/4•[31.75mm] Escutcheon total rnn
Escutcheon ---.. I 1/4•[6.35mm] Escueneon Ad].
Ceieng, i2---'L'Tn,-I U Escutcheon
Sprinkler Can Nominal Position MIEN-- Adjustment of Escutcheon
Nominal Position 1-,/4•[31.7Smm] 1 S/e-
e Escutcheon III �II i s/6• Namina gild on 001
[41.3mm]
1/0(6.35mm]
Prolruebn
[55.eemm)
2 13/64• 1371r048
3•[76.20mm]
DIA IOSml-0 Do.
Fig. 1 Fig. 2
Note: The sprinkler can protrudes 1/4" when escutcheon is in nominal Note: The sprinkler can protrudes 11/4"when escutcheon is in nominal
position. Escutcheon adjustment provides 1/4"(-6mm)to+11/4" position. Escutcheon adjustment provides-1/2"(-12.7mm)to+1/2"
(+32mm)"A"dimension adjustment range. (+12.7mm)"A"dimension adjustment range.
Sprinkler Guard: Model C-2
Sprinkler Installation Wrench: Model G3 Sprinkler Wrench
Sprinkler Identification Number(SIN): R5314
Model F3 Dry Pendent FP Recessed Sprinkler
"A"Dim. 31/2"to 48"(89mm to 1219mm)in 1/4"(6mm)increments Inlet Protrusion Elevated -rr~T----i•---y-f- ___5p,
Above Inside Pipe Rq , ,
Finishes
Sprinkler Escutcheonr_, r_ti ==j
Bronze Brass ? == system Tee
Chrome Plated Chrome Plated mr.■—•
White Polyester(2) White NPT
(1)Other finishes and colors are available on special order.
Consult factory for details.Cu remainds unfinished. 2 1/2•oia. IIII
rY Cup a•Dimension [63.wmm]
Only the escutcheon will contain desired finish. Adjustment Range Hole in Ceiling
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or [t6.5mm] 2 19/64'Dta.
White. [58.34mm]
Standard Temperature Ratings —Nominal Position Sprinkler
of Escutcheon Cup Assembly
I Sprinkler Max.
Classification Temperature Ambient Bulb Color + +rCeiltng' Escutcheon
Rating Temp. `— El i ll►_ ceiling
Ordinary 135°F (57°C) 100°F (38°C) Orange 1/e[6.35mm] i
1°/Ordinary 155°F (68°C) 150°F (66°C) Red Esa°tans°°Adjustment
ntermediate(2) 175°F (79°C) 150°F (66°C) Yellow Escutcheon m Adjustment 3 7/32•oia.
[61.76mm] -..-
Intermediate 200°F (93°C) 150°F (66°C) Green 1/2•[12.7omm]-
- High(1) 286°F(141°C) 225°F(107°C) Blue To1ol Adjustment 153CCO2-C
Sprinkler cup and FP Escutcheon fabricated of steel and recommended Fig. 3
for interior applications. Note: Do not install the Model F3 Dry Pendent Recessed Sprinkler in
. (l)Listed and Certified Only by LPCB and cULus. ceilings which have positive pressure in space above.
[2]Listed and Certified Only by cULus.
Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number(SIN): R5314
2.
Model F3 Dry Pendent Concealed Sprinkler
"A"Dim. 372"to 48"(89mm to 1219mm)in 1/4"(6mm)increments net Protrusion Elevated == r�T----t----T" a,
(1) (Z) Above Inside Pips HH,
CCP Cover Plate ' F•nishes 1
Standard Finishes Special Application Finishes == r'; r.....,_` p`==_'
Chrome Plated Bright Brass Plated ,== , system Tee
White Black Plated ma
Black Paint fl 1-NPT
Off White
2 1/r Dia.
'H'
Satin Chrome "A"Dimension [63.50mr^j
Adjustment Range Hde in C.iling
11'Utilizes the 1/2"cover plate with 3/8"total adjustment. t 3/16"
(2)Other finishes and colors are available on special order. [t4.76rnmj 2 19/64"Dia.
Consult factory for details. [5e•34mmj
Standard Temperature Ratings of Coverplate Nominal Position Sprinkler
I Sprinkler Max.
Cup Assembly
Cover Plate '------ _� A`°.a.°..
Classification Temperature Ambient • ailing.Q.
Rating Temp.Rating Temp. L.---...LI�1pi c«linyg�
Ordinary 135°F (57°C) 135°F (57°C) 100°F (38°C) 3/76'14.76 mm] MililV
Cove slats Adjustment
Ordinary 155°F (68°C) 135°F (57°C) 100°F (38°C)
3/16•[4.76mm]
Intermediate(1) 175°F (79°C) 165°F (74°C) 150°F (66°C) Coverplate Adjustment 3 5/16"Dia.
Intermediate 200°F (93°C) 165°F (74°C) 150°F (66°C) 3/6"[9.53mm] [64.13mm]
High(1) 286°F(141°C) 165°F (74°C) 150°F (66°C) Total Adjustment 53sco3-c
Sprinkler cup fabricated of steel and CCP Cover Plate fabricated of Fig. 4
brass and recommended for interior applications. Note:Do not install the Model F3 CCP Pendent Concealed Sprinkler in
ceilings which have positive pressure in the space above.
[')Listed and Certified only by cULus.
Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number(SIN): R5314
Model F3 Dry Horizontal Sidewall Sprinkler
"A"Dim. 2"to 48"(51mm to 1219mm)in 1/4"(6mm)increments
Finishes['] Standard Temperature Ratings
Sprinkler Escutcheon Sprinkler Max.
I Bronze Brass(5) Classification Temperature Ambient Bulb Color
Chrome Plated Chrome Plated Rating Temp.
White Polyester(41 White Ordinary 135°F (57°C) 100°F (38°C) Orange
Lead Plated(2) Ordinary 155°F (68°C) 100°F (38°C) Red
Wax Coated(2)(3) Intermediate(1) 175°F (79°C) 150°F (66°C) Yellow
Wax Over Lead(21(3) Intermediate 200°F (93°C) 150°F (66°C) Green
'11 Other finishes and colors are available on special order. High 286°F(141°C) 225°F(107°C) Blue
Consult factory for details. Sprinkler can and escutcheon fabricated of brass for better weather
- (2) 155°F(68°C)to 200°F(93°C)rating only. resistance in exterior applications.
(3)212°F(100°C)brown wax may be used on 286°F(141°C)sprinklers
when maximum ceiling temperatures do not exceed 150°F(66°C). "]Listed and Certified only by cULus.
(4) cULus Listed as a Corrosion Resistant sprinkler in standard Black or
White.
(5)Not available for HB escutcheons.
1 /2• 38.10mm - 1"[25.4mm]
[ l I Total Adjustment --_----------Ceiling-------
Total Adjustment [-
r Ceiling i --- - r
iI i-r----------------i- 7/2•[12.7mm] T
1 I c T Escutcheon Adjustment •~ 4"[101.60mm] Min.
L.-J 4"[101.60mm] Min. 1/2"[12.7mm] 12"[304.80mm] Mon.
I ,/4"[3,.75mm] 12•[304.80mm] Max. Escutcheon Adjustment-six
Escutcheon Adjustment 2 3/32"
r i. 1/4"[6.35mm] System Tee [53.16mmj
System Tee I Escutcheon Adjustment 1"NPT i -
," NPT t ,
I h 1 2 3/32' }r \-1-----.,,
\-1' --- ' I [53.18mm] IF I a f�-,J1�{�RIIIIIIIII 2-1J/64" 3_1/2.
IIIII I_---'--I -a . . 3 Oia �::::i..._.. .,-- [55.--°' E utcheon II'' D1 O' Escutcheon Dia.
hnhIIIllrI f� [76.20mm] 7 `�
if--1' 2 1/2" Dia.
``� -7- 1 [63.51mm]
2 1/8" Dia. - • Hole Wall 1-1/4"[31.75mm] Nominal
[53.98mm] i I�3•J Protrusion
Hole in Wall 1/4"[6.35mm] prmkler Con
Sprinkler Can Protrusion .-"A'Dimension Escutcheon
P Adjustment(+
Range 1/2"[ 12.7mm] Nominal Position
v "A"Dimension ,� of Escutcheon
Adjustment Nominal Position - 1/5"[-12.7mm]
15s1204-0 Range - 1/4" [-6.35mm] of Escutcheon
rsr/cnr_a + I 1/4 [+31.75mm]
Fig. 5 Fig. 6
Note: The sprinkler can protrudes 1/4" when escutcheon is in nominal Note: The sprinkler can protrudes 11/4"when escutcheon is in nominal
position. Escutcheon adjustment provides 1/4"(-6mm)to+11/4" position. Escutcheon adjustment provides-1/2"(-12.7mm)to+1/2"
(+32mm)"A"dimension adjustment range. (+12.7mm) "A"dimension adjustment range.
Sprinkler Installation Wrench: Model G3 Sprinkler Wrench
Sprinkler Identification Number(SIN): R5334
3.
Model F3 Horizontal FP Recessed Sidewall Sprinkler
"A"Dim. 1372"to 48"(89mm to 1219mm)in 1/4"(6mm)increments (— Ceiling
_ Finishes`1'
Sprinkler Escutcheon lr
3/32"
Escutcheon I [35.7mm]
Bronze Brass IT 4• 101.6mm Min.
Cup o I *6"€152 4mm�Moe.
Chrome Plated Chrome Plated System Tee i;;
' White Polyester(2) White
1'NPT
11'Other finishes and colors are available on special order, }-__ _r- i�_
Consult factory for details.
1 tL_
(2) cULus Listed as a Corrosion Resistant sprinkler in standard Black or "� 3 7/32"Dia
IIII Q1-- [7/32' ,
White. i'% 1- I _ I 1
2 1/2' Dia.
Sprinkler's can and FP Escutcheon are fabricated of steel and recom- [[63.5mm]] 13; Nominal Position
H
in wall Of Escutcheon
mended for interior applications. 2 19/84'Dia.
[58.3mm] Escutcheon Adju[6.35]
I
stment
Standard Temperature Ratings Adjustment Range Escutcheon Adjustment
153F503-E 31/4' 1/4'[6.35]
Sprinkler Max. (±6.35] Escutcheon Adjustment
Classification Temperature Ambient Bulb Color ., Factory Mutual (FM)
. ■" - 8" for Underwriters Laboratories (UL)
Rating Temp.
Fig. 7
Ordinary 135°F (57°C) 100°F (38°C) Orange Note: Do not install the Model F3 Dry Horizontal Recessed Sidewall
Ordinary 155°F (68°C) 100°F (38°C) Red
Intermediate(1) 175°F (79°C) 150°F (66°C) Yellow Sprinkler in walls which have positive pressure in their side
Intermediate 200°F (93°C) 150°F (66°C) Green space.
High(1) 286°F(141°C) 225°F(107°C) Blue • Recessed Horizontal Sidewall sprinklers are listed by cULus
for installation of min. 4" (100mm) - to - max. 6" (150mm)
(')Listed and Certified Only by LPCB or cULus. below ceiling, and FM approved for installation of min. 4"
(100mm)-to-max. 12"(306mm).
Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number(SIN): R5334
Technical Data Ordering Information
Orifice Size: 1/2" (15mm) Specify:
Thread size: 1" NPT per ANSI B2.1 1. Sprinkler Type (select one):
Working Pressure: 175 psi (12 bar) (a) Model F3 Dry Pendent
. Nominal K Factor-US/(Metric): 5.6/(80) (b) Model F3 Dry Pendent/HB
Product Description (c) Model F3 Dry Recessed Pendent
Reliable Model F3 Dry Sprinklers are standard response (d) Model F3 Dry Concealed Pendent
sprinklers utilizing a durable 5mm frangible glass bulb. (e) Model F3 Dry Horizontal sidewall
Model F3 Dry Sprinklers are intended for use in dry and pre- (f) Model F3 Dry Horizontal sidewall/HB
action systems and in areas subjected to freezing tempera- (g) Model F3 Dry Recessed Horizontal Sidewall
tures, such as freezers and unheated portions inside and 2. Sprinkler Temperature Rating.
outside buildings. 3. Sprinkler Finish.
Environments wherein dry sprinklers are employed can 4. Cover Plate/FP Escutcheon Finish.
be corrosive. For this reason, Model F3 Sprinklers have a 5. Length: "A" Dimension(face of tee to face of ceiling or
special wax fillet placed in the gap between the cup that wall) in 1/4" (6.4mm) increments.
supports the bulb and the wrenching boss.This wax will not 6. Model F3 Dry Pendent (a) is available without sprin-
interfere with the operation of the sprinkler, and it prevents kler can and escutcheon.
contaminents from entering the internal portion of the drop Note:
nipple.The wax must not be removed. 1. The "A" dimension is based on a nominally gauged
Operation pipe thread "make-up" of .600" (15mm) per ANSI
The glass bulb consists of an accurately controlled amount B2.1 [7 '/2 threads approximately].
of special fluid hermetically sealed inside a precisely manu 2. All platings and paintings are decorative and intend-
factured glass capsule. When the temperature increases ed for interior use.
sufficiently due to a fire, the bulb shatters allowing operat- 3. Acceptable appearance in conditions such as park-
- ing parts to clear the waterway. This enables the inlet seal ing garages is generally provided with bronze sprin-
to release air or water and subsequently, cause water flow kler, brass cup and escutcheon for the Model F3 Pen-
over the deflector in a uniform spray pattern, controlling or dent only.
' extinguishing the fire.
4.
General Installation Instructions Maintenance
Model F3 dry sprinklers must be installed only in stan- The Model F3 Dry Sprinklers should be inspected quar-
dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125) terly and the sprinkler system maintained in accordance
pipe tees in the horizontal position,even at branch line ends. with NFPA 25. Do not remove the factory applied thermally
They should not be installed into elbows or pipe couplings sensitive wax fillet between the bulb supporting cup and the
located on drop nipples to the sprinklers.For these and other wrenching boss. Do not replace this wax with a substitute
fittings including CPVC,the dry sprinkler should be installed substance.An Alternate substance may interfere with proper
into a fitting to allow protrusion into the fitting in accordance operation of the sprinkler. Do not clean sprinklers with soap
with the diagrams. The "A" dimension of the dry sprinkler, and water, ammonia or any other cleaning fluids. Remove
which extends into the freezers or a freezing zone from wet dust by using a soft brush or gently vacuuming. Remove
pipe systems,should be selected to provide,as a minimum, any sprinkler which has been painted(other than factory ap-
the specified lengths in inches shown in Fig.8. plied) or damaged in any way. A stock of spare sprinklers
Caution; should be maintained to allow quick replacement of darn-
Do not install Model F3 Dry sprinklers into CPVC adapter aged or operated sprinklers. Prior to installation, sprinklers
fittings or tees that have an internal obstruction. This will should be maintained in the original cartons and packaging
damage the sprinkler and/or the fitting. Refer to Fig. 9 until used to minimize the potential for damage to sprinklers
During installation, the following steps must be followed: that would cause improper operation or non-operation.
1. Cut the specified size hole (see illustrations) for the
sprinkler in the ceiling or wall directly in line with the
tee.
2. Apply pipe joint compound to the 1" (25mm) pipe
threads and install sprinkler using the Model G3 or
G3 R/C Sprinkler Wrench as specified.
3. Install the Model FP push-on /thread-off escutcheon
or CCP cover plate if required.
Note: Installation of the Model F3 Sprinklers is not recom-
mended in copper pipe systems, as this may reduce the
life expectancy of the sprinklers.
Model F3 Concealed and Recessed
Installation Instructions
• The Model G3 R/C Wrench (Fig. 10) is designed to
locate on the wrenching pads of the Recessed sprin-
kler while centering in the cup. A standard 1/2" drive
ratchet may be used to drive this wrench. Figures 11
and 12 show sequentially the insertion of the wrench.
First, the wrench, with its jaws above the sprinkler de-
flector, is moved laterally until centered with the cup.
Then raise the wrench inside the cup until its jaws
engage the sprinkler's square wrenching pads (Fig.
12). To remove the wrench, follow this procedure in
reverse order. Care should be taken to avoid striking
the deflector with the wrench.
• Model G3 Wrench (Fig. 13) is used for installation of
Pendent and Horizontal sidewall sprinklers.
• Glass bulb sprinklers have orange bulb protectors
to minimize bulb damage during shipping, handling
and installation. REMOVE THIS PROTECTION AT THE
TIME THE SPRINKLER SYSTEM IS PLACED IN SER-
VICE FOR FIRE PROTECTION. Removal of the pro-
tectors before this time may leave the bulb vulnerable
to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PRO-
TECTORS BY UNDOING THE CLASP BY HAND. DO
NOT USE TOOLS TO REMOVE THE PROTECTORS.
5.
•
RECOMMENDED EXPOSED MINIMUM BARREL LENGTH BASED ON AMBIENT TEMPERATURE IN THE PROTECTED AREA
(STANDARD DRY PENDENT SPRINKLER SHOWN)
INSTALL 1 INCH NPT THREADED
END OF DRY PENDENT SPRINKLER
• WET PIPE INTO THE 1 INCH NPT SIDE OUTLET
EXPOSED BARREL OF A MALLEABLE IRON TEE FITTING
AMBIENT AMBIENT TEMPERATURE r` , OERCANSI IRON 16.3 (CLASS 15 )FITTING
TEMPERATURE --- r - I�'--- PER ANSI 16.4 (CLASS 125) ONLY,
OF PROTECTED 40T/4'C I 50'F/10'C I 60T/16T ' 1
AREA.AT THE -h-- -J—--4—-
EXPOSED MINIMUM BARREL LENGTH•• !• ,I , li
DISCHARGE END (FACE OF TEE TO TOP OF CEILING In 'I
OF THE SPRINKLER ( ) Iw=== ,Ls,1 17--L J ==
IN. (MM) IN. (MM) IN. (MM) 1 L IF HUMIDITY AND TEMPERATURE DIFFERENTIAL
40'F (4'C) 0 0 0 =----=.---- CAUSES CONDENSATION ON THE EXPOSED DRY
30'F (-1'C) 0 0 0 SPRINKLER, CONSIDER WRAPPING THE EXPOSED
BARREL WITH INSULATION. FOAM INSULATING
TAPE OR EQUIVALENT.
20'F (-TC) 4 (101) 0 0
10T (-1TC) 8 (203) 1 (25.1) 0
OT (-16'C) 12 (305) 3 (75) 0 MINIMUM (HEATED AREA) SEAL THE CLEARANCE SPACE
-10'F (-23'C) 14 (356) 4 (101) 1 (25.1) EXPOSED AROUND THE SPRINKLER TO AVOID
BARREL LEAKAGE OF AIR INTO THE PROTECTED
-20'F (-29'C) 14 (356) 6 (152) 3 (75) LENGTH AREA AND CONSEQUENT FORMATION OF
CONDENSATE AROUND THE FRAME, WHICH
-30T (-34'C) 16 (406) 8 (203) 4 (101) COULD INHIBIT OPERATION OR CAUSE
-40T (-40'C) 18 (457) 8 (203) 4 (101)
RECOMMENDED PMETHODS.SEE BELOW FOR
CLEARANCE
-50-F (-ACC) 20 (508) 10 (254) 6 (152) DIMENSION HOLE 1111.
-60T (-5rC) 20 (508) 10 (254) 6 (152)
• THE PROTECTED AREA REFERS TO THE AREA BELOW THE CEILING.
THE AMBIENT TEMPERATURE IS THE TEMPERATURE AT THE DISCHARGE
/' �/ I ���/
END OF THE SPRINKLER.
FOR PROTECTED AREA TEMPERATURES THAT OCCUR BETWEEN THE VALUES '
LISTED. USE THE NEXT COOLER TEMPERATURE. __
••THE MIN. REQUIRED BARREL LENGTH IS NOT THE SAME AS THE 'A' DIMENSION. ` I1 ESCUTCHEON
NOTE: EXPOSED MINIMUM BARREL LENGTHS ARE INCLUSIVE UP TO 30MPH CEILING 1I�O�I�
WIND VELOCITIES IN THE PROTECTED AREA. I�'IU1,/
(PROTECTED AREA)
3" DIA.
*RECOMMENDED EXPOSED MINIMUM BARREL LENGTHS ALSO APPLY TO HORIZONTAL SIDEWALL DRY SPRINKLERS*
RECOMMENDED DRY SPRINKLER SEAL ARRANGEMENTS
WET PIPE (STANDARD DRY PENDENT SPRINKLER SHOWN) WET PIPE
rt 1-, rt
II � u I s�
---tOr--i 'r--�{ - i r----inr--," -, -r--1
n- v.0
-2.--—iii I-'-t-i-IMF--` - I- - - ---ii-iii--IL'
i n un I ""' I
I --= I
r ti. L J
iM MN
(HEATED AREA) (HEATED AREA)
MINIMUM MINIMUM
EXPOSED EXPOSED
BARREL BARREL
LENGTH DECKTITE FLASHING INSIDE FACE SEAL LENGTH
(SEE ABOVE) RASCO 04003910 (SEE ABOVE)
(RECOMMENDED)
t / / ,
fAIPSMIACIIVAIPArdrAii 1 121121011151IIIII7 PArAPINIAPIVAIAIrAll 01/4121/4151/4/2 '
MI CLEARANCE HOLE
INSULATED FREEZER,
OR COOLER STRUCTURE
OR EXTERIOR FRAMING
//////// I//////� '//////// IM IMII12112121/26
_- _-
-- ■■
(PROTECTED AREA) `I�u�I+ IN COLD IAREAR (PROTECTED AREA) I IVII DRY
COLD SPRIAREA NKLER hj
Fig. 8
6.
*CAUTION*
• DO NOT INSTALL MODEL F3, MODEL F3QR OR MODEL DH56 HSW DRY SPRINKLERS INTO
CPVC ADAPTER FITTINGS OR TEES THAT HAVE AN INTERNAL OBSTRUCTION. THIS WILL
DAMAGE THE SPRINKLER AND/OR THE FITTING.
CPVC ADAPTER FITTINGS AND TEES WITH INTERNAL OBSTRUCTIONS ARE ALSO COMMONLY
FOUND DURING THE RETROFITTING PROCESS OF RELIABLE'S OLDER MODEL G3 DRY
SPRINKLERS.
INTERNAL NO
OBSTRUCTION INTERNAL
OBSTRUCTION
II4 F i
i1I,
-
_______l C FEMALE O � FEMALE �'PIPE / PIPE l �l
THREAD '� THREAD
INCORRECT CORRECT
CPVC ADAPTER CPVC ADAPTER
FITTING OR TEE FITTING OR TEE
RELIABLE MANUFACTURES A FULL-LINE OF MODEL F3-PL, MODEL F3QR-PL, AND
MODEL DH56 HSW-PL DRY SPRINKLERS THAT HAVE A SHORTER INLET FOR THESE
APPLICATIONS.
SHORTER LONGER IIII
INLET INLET
MALE MALE min"
PIPE PIPE
THREAD THREAD
MODEL F3-PL, STANDARD
MODEL F3QR-PL OR MODEL F3,
MODEL DH56 HSW-PL MODEL F3QR OR
DRY SPRINKLER MODEL DH56 HSW
DRY SPRINKLER
BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR
APPLICATION 016fg08
Fig. 9
7.
•
•
P S ,
/:.
Fig. 10-G3 R/C Wrench Fig. 11 -G3 R/C Wrench Fig. 12-G3 R/C Wrench
4
Fig. 13-G3 Wrench
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured b
The Reliable Automatic Sprinkler Co.,Inc. Recycled
(800)431 1588 Sales Offices Paper
(800)848 2051 Sales Fax
(914)829-2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A 02/11 P/N 9999970146