FIRE PROTECTION
EQUIPMENT SUBMITTAL
tqco Worldwide
Contacts www.tyco-fire.com
Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE -_
The TYCO Series TY-FRB Sprinklers f`r •-••s"'. i'V►
Description described herein must be installed and °t
maintained in compliance with this doc-
The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable
Upright(TY313)and Pendent(TY323) standards of the National Fire Protec- t
Sprinklers described in this data sheet tion Association,in addition to the stan- : I I !
are quick response,standard coverage, dards of any other authorities having .j t
decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair i
sprinklers designed for use in light or the performance of these devices. �'-
ordinary hazard,commercial occupan- -i
ties such as banks, hotels,and shop- The owner is responsible for maintain-
ping malls. ing their fire protection system and - 4i*.
devices in proper operating condition.
The recessed version of the Series TY- The installing contractor or sprinkler
FRB Pendent Sprinkler,where applica- manufacturer should be contacted with
ble, is intended for use in areas with a any questions.
finished ceiling.This recessed pendent `
sprinkler uses one of the following: i
Sprinkler
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust- Identification .�,
ment up to 5/8 inch (15,9 mm)from i .�
the flush pendent position. Number (SIN)
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT
ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT ; ...
the flush pendent position. ,o.
The adjustment provided by the Technical
Recessed Escutcheon reduces the Finishes
accuracy to which the fixed pipe drops Data Sprinkler: Natural Brass,Chrome
to the sprinklers must be cut. Plated,Pure White(RAL 9010)and
Intermediate level versions of Series Approvals Signal White(RAL 9003).
TY FRB
Intermediate are described is UL and C-UL Listed Recessed Escutcheon:White Coated,
Sprinklers FM and VdS Approved Chrome Plated,or Brass Plated
Technical Data Sheet TFP357. Sprin- CE Certified
kler guards and shields are described Physical Characteristics
in Technical Data Sheet TFP780. Maximum Working Pressure Frame Bronze
175 psi(12.1 bar) Button Brass/Copper
250 psi(17.2 bar)` Sealing Assembly Stainless
The maximum working pressure of 250 psi Steel w/TEFLON
(17.2 bar)only applies to the listing by Un-
Bulb Glass
derwriters Laboratories,Inc.(UL). Compression Screw Bronze
Deflector Bronze
IMPORTANT
Coefficient
Always refer to Technical Data K=5.6 GPM/psi1/2(80,6 LPM/barli2)
Sheet TFP700 for the `INSTALLER Temperature Rating
WARNING" that provides cautions 135°F(57°C)
with respect to handling and 155`F(68°C)
installation of sprinkler systems and 175°F(79°C)
components. Improper handling and 200°F(93°C)
installation can permanently damage 286°F(141°C)
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 4 JANUARY 2013 TFP172
TFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
6* ....... — _ 1
5
•�� 7/16' ■
_ (11,1 mm) _ i mr
4 NOMINAL j 2" I
MAKE-IN (50,8 mm)
2 r /eiiD 1 q 2" 1-3/8"3 � (50,8 mm) (34,9 mm) I 'kr
1 _� WRENCH
1/2 NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
�, Operation Installation
WRENCH RECESS
The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor,
expands when exposed to heat.When Upright(TY313)and Pendent(TY323)
{USE ONLY the rated temperature is reached,the Sprinklers must be installed in accor-
END'A") fluid expands sufficiently to shatter the dance with this section.
glass bulb, allowing the sprinkler to
activate and water to flow. General Instructions
FIGURE 2 Do not install any bulb-type sprinkler if
W-TYPE 6 the bulb is cracked or there is a loss
SPRINKLER WRENCH Design of liquid from the bulb.With the sprin-
kler held horizontally,a small air bub-
WRENCH Criteria ble should be present. The diameter
of the air bubble is approximately 1/16
RECESS The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and
Upright(TY313) and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C)
�,y� Sprinklers are intended for fire protec- temperature ratings.
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or should be obtained by applying amin-
Approval agency(such as, UL Listing min-
imum to maximum torque of 7 to 14
OP-1
is based on the requirements of NFPA ft:lbs. (9,5 to 19,0 Nm). Higher levels
�.. 13,and FM Approval is based on the of torque can distort the sprinkler Inlet
requirements of FM's Loss Prevention with consequent leakage or impairment
PUSH WRENCH of the sprinkler.
Data Sheets).Only the Style 15 or Style
IN ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for
ENGAGEMENT NT for recessed pendent installations. insufficient adjustment in the Escutch-
WITH SPRINKLER
WRENCHING AREA eon Plate by under-or over-tightening
the sprinkler.Re-adjust the position of
FIGURE 3 the sprinkler fitting to suit.
W-TYPE 7 RECESSED Upright and Pendent Sprinklers
SPRINKLER WRENCH The Series TY-FRB Upright and Pen-
dent Sprinklers must be installed
in accordance with the following
instructions.
Step 1.Install Pendent sprinklers in the
- pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
TFP172
Page 3 of 4
Step 3.Tighten the sprinkler into the 2-7/8"DIA.
sprinkler fitting using only the W-Type (73,0 mm)
6 Sprinkler Wrench(Figure 2).With ref-
erence to Figure 1, apply the W-Type 6 2-1/4"DIA. •
. Sprinkler Wrench to the wrench flats. FACE OF — (57,2 mm)
Torque sprinklers 7 to 14 ft:lbs.(9,5 to SPRINKLER
19,0 Nm). FITTING
5/8"(15,9 mm)
Recessed Pendent Sprinklers i \ - FLUSH
The Series TY-FRB Recessed Pendent 3/8±5/16" —_1 I i
Sprinklers must be installed in accor- (9,517,9 mm) 14 s 'v +dance with the following instructions. f J l
Step A.After installing the Style 15 or Mir 1/8" j I
MOUNTING
Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm)
kler threads, and with pipe-thread -----— i
sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8'(34,9 mm)
hand-tighten the sprinkler into the TY-FRB PLATE
3/4"(19,1 mm)
sprinkler fitting.
Step B.Tighten the sprinkler into the FIGURE 4
sprinkler fitting using only the W-Type SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
7 Recessed Sprinkler Wrench (Figure WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
3).With reference to Figure 1,apply the RECESSED ESCUTCHEON
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque 2-7/8"DIA.
sprinklers 7 to 14 ft.-Ibs. (9,5 to 19,0 (73,0 mm)
Nm). FACE OF
Step C.After ceiling installation and fin- SPRINKLER — 2-1/4"DIA.
ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm)
Closure over the Series TY-FRB Sprin-
kler and push the Closure over the 5/16±1/4" 1/2"(12,7 mm)
Mounting Plate until its flange comes in (7,9±6,4 mm)
contact with the ceiling. t =
FLUSH
Care and t I Maintenance MOUNTING I
1/8"
SURFACE - (3,2 mm)
The TYCO Series TY-FRB,5.6 K-factor, ------- T
Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
Sprinklers must be maintained and ser- TY-FRB PLATE
viced in accordance with this section. 7/8"(22,2 mm)
Before closing a fire protection system FIGURE 5
main control valve for maintenance SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
work on the fire protection system WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
that it controls, obtain permission to RECESSED ESCUTCHEON
shut down the affected fire protection
systems from the proper authorities Modified sprinklers must be replaced. of the National Fire Protection Associa-
and notify all personnel who may be Sprinklers that have been exposed to tion (e.g., NFPA 25), in addition to the
affected by this action. corrosive products of combustion, but standards of any other authorities hav-
Absence of the outer piece of an have not operated,should be replaced ing jurisdiction. Contact the installing
escutcheon, which is used to cover if they cannot be completely cleaned contractor or sprinkler manufacturer
a clearance hole, can delay sprinkler by wiping the sprinkler with a cloth or regarding any questions.
operation in a fire situation. by brushing it with a soft bristle brush. Automatic sprinkler systems are rec-
The owner must assure that the sprin- Care must be exercised to avoid dam- ommended to be inspected, tested,
klers are not used for hanging any age to the sprinklers- before, during, and maintained by a qualified Inspec-
objects and that the sprinklers are only and after installation.Sprinklers dam- tion Service in accordance with local
cleaned by means of gently dusting aged by dropping, striking, wrench requirements and/or national codes.
with a feather duster;otherwise, non- twist/slippage, or the like, must be
operation in the event of a fire or inad- replaced. Also, replace any sprinkler
vertent operation may result. that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Sprinklers which are found to be leak- Section.)
ing or exhibiting visible signs of corro- The owner is responsible for the
sion must be replaced. P
Automatic sprinklers must never be inspection,testing,and maintenance of
P their fire protection system and devices
painted, plated, coated, or other- in compliance with this document,as
wise altered after leaving the factory. well as with the applicable standards
TFP172
Page 4 of 4
P/N* 77 - XXX - X - XXX
SPRINKLER TEMPERATURE
• FINISH RATINGS
SIN 1 NATURAL BRASS 135 135°F(57°C)
370 5.6K UPRIGHT(1/2-NPT) TY313 4 SIGNAL WHITE(RAL 9003) 155 155-F(68"C)
371 5.6K PENDENT(1/2-NPT) TY323 3 PURE WHITE(RAL 9010)" 175 175°F(79°C)
•Use suffix•I"for ISO 7-1 connection; 9 CHROME PLATED 200 200`F(93°C)
for example,77-370-4-175-I
Eastern Hemisphere sales only 286 286°F(141°C)
TABLE A
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
—PART NUMBER SELECTION-
Ordering
Procedure
Contact your local distributor for avail-
ability.When placing an order,indicate
the full product name and Part Num-
ber(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB (SIN), K=5.6,
(Upright or Pendent) Sprinkler Quick
Response, (specify) temperature rat-
ing,(specify)finish, P/N(Table A).
Recessed Escutcheon
Specify:Style 15 Recessed Escutcheon
with(specify')finish, P/N(specify")
Specify:Style 20 Recessed Escutch-
eon with(specify')finish,P/N(specify")
•Refer to Technical Data Sheet TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700
Copyright®2013 Tyco Fire Products,LP. All rights reserved. two
TEFLON is trademark of The DuPont Corporation.
CO Worldwide
Contacts www.tyco-fire.com
Series RFII — 5.6 K-factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick & Standard Response, Standard Coverage
General stallation or finish. The tip of the Pro-
tective Cap can be used to mark the _
Description center of the ceiling hole into plaster
p board or ceiling tiles by gently push-
The TYCO Series RFII 5.6 K-factor, ing the ceiling product against the Pro-
"Royal Flush II" Concealed Pendent tective Cap. When ceiling installation
Sprinklers Quick Response (3 mm is complete, the Protective Cap is re-
bulb) and Standard Response (5 mm moved and the Cover Plate/Retainer ,
Assembly is installed. —°`
bulb), are decorative sprinklers featur- Y
ing a flat cover plate designed to con- As an option, the Series RFII Standard
ceal the sprinkler.These sprinklers are Response(5-mm bulb)"Royal Flush II"
optimal for architecturally sensitive ar- Concealed Pendent Sprinklers can be
eas such as hotel lobbies,office build- fitted with a silicone Air and Dust Seal.
•
ings,churches,and restaurants. (Refer to Figure 5.) The Air and Dust TY3531 (3 mm Bulb) is UL Listed,
Seal is intended for sensitive areas C-UL Listed, VdS Approved (Certif-
Each sprinkler includes a Cover Plate/ icate No. G4090007), and NYC Ap-
Retainer Assembly and a Sprinkler/ where it is desirable to prevent air and proved (MEA 353-01-E) as Quick
Support Cup Assembly. The separa- dust from the area above the ceiling to Response.
ble, two-piece assembly design pro- pass through the cover plate.
vides the following benefits: • TY3531 (3 mm Bulb) is FM and
NOTICE LPCB Approved (Ref. No. 094a/10)
• Allows installation of the sprinklers The Series RFII Concealed Pendent Approved as Standard Response.
and pressure testing of the fire pro- Sprinklers described herein must be Factory Mutual and LPCB do not
tection system prior to installation p
installed and maintained in oomph-
of approve any concealed sprinklers
a suspended ceiling or applica- ance with this document and with the
for quick response.
tion of the finish coating to a fixed a licable standards of the National •
ceiling. Fe Protection Association, in addi- TY3551 (5 mm Bulb) is UL Listed,
C-UL Listed, FM Approved, LPCB
• Permits the removal of suspended Lion to the standards of any authori- Approved (Ref. No. 094a/9), and
ceiling panels for access to building ties having jurisdiction. Failure to do so NYC Approved (MEA 353-01-E) as
service equipment without having may impair the performance of these Standard Response.
to first shut down the fire protection devices.
system and remove sprinklers. Approvals for Air and Dust Seal
The owner is responsible for maintain UL and C UL Listed for use with the
• Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de RFII Standard Response Concealed
vertical adjustment to allow a mea- vices in proper operating condition. p
sure of flexibility in determining the The installing contractor or sprinkler Sprinkler(TY3551).
length of fixed piping to cut for the manufacturer should be contacted Maximum Working Pressure
sprinkler drops. with any questions.
Maximum 250 psi (17,3 bar) by UL,
The Series RFII Sprinklers are shipped C-UL, and NYC
with a Disposable Protective Cap.The Sprinkler
Protective Cap is temporarily removed p Maximum 175 psi (12,1 bar) by FM,
during installation and replaced to help Identification VdS,and LPCB
protect the sprinkler during ceiling in- Temperature Rating
Number (SIN) 155°F(68°C)Sprinkler with
IMPORTANT 139`F(59°C) Plate
Always refer to Technical Data TY3531 — 3 mm bulb
Sheet TFP700 for the "INSTALLER TY3551 — 5 mm bulb 200`F(93'C) Sprinkler with
WARNING" that provides cautions 165°F(74°C)Plate
with respect to handling and instal- Technical Discharge Coefficient
lation of sprinkler systems and corn-
K=5.6 GPM/psi12(80,6 LPM/bar'z)
ponents. Improper handling and in- Data
stallation can permanently damage Adjustment
a sprinkler system or its components Sprinkler Approvals 1/2 inch(12,7 mm)
and cause the sprinkler to fail to Approvals apply only to the service
operate in a fire situation or cause it conditions indicated in the Design Cri- Finishes
to operate prematurely. teria section. See the Ordering Procedure section.
Page 1 of 4 MARCH 2013 TFP181
TFP181
Page 2 of 4
Physical Characteristics 1/2^NPT / SEALING
Frame Bronze , ASSEMBLY
. Support Cup Chrome ,
Plated Steel Guide Pins Stainless Steel FRAME y ��Deflector Bronze 1 1 CAP
Compression Screw Brass + I
Bulb Glass ���
Cap Bronze or Copper SUPPORT
Sealing Assembly Beryllium
Nickel w/TEFLON CUP WITH ( BULB
Cover Plate Brass ROLL FORMED
Retainer Brass THREADS
Ejection Spring Stainless Steel —
Design COMPRESSION
SCREW
GUIDE �_►
Criteria PINS(2) i =
The TYCO Series RFII 5.6 K-factor, _—_ DEFLECTOR
"Royal Flush II" Concealed Pendent (DROPPED
Sprinklers are intended for fire protec- DEFLECTOR , ' POSITION)
tion systems designed in accordance -r -r '
with the standard installation rules rec-
ognized by the applicable Listing or SPRINKLER/SUPPORT CUP
Approval agency;for example,UL List- ASSEMBLY
ing is based on NFPA 13 and VdS Ap- I
proval is based on the CEA 4001. THREAD INTO I RETAINER
For more information on LPCB and SUPPORT 0 i WITH THREAD
CUP UNTIL 0 ` DIMPLES
VdS Approvals,contact Tyco Fire Pro- MOUNTING
tection Products at the following office: SURFACE IS EJECTION
Enschede, Netherlands FLUSH WITH SPRING
Telephone:31-53-428-4444 CEILING
• Fax:31-53-428-3377
• The Series RFII Concealed Pendent ' ----
Sprinklers are only listed and approved
with the Series RFII Concealed Cover /
Plates having a factory applied finish. SOLDER J COVER
TABS(3) COVER PLATE/RETAINER PLATE
NOTICE ASSEMBLY
Do not use the Series RFII in applica- FIGURE 1
Lions where the air pressure above MODEL RFII CONCEALED SPRINKLER
the ceiling is greater than that be- ASSEMBLY
low. Down drafts through the Sprin-
kler/Support Cup Assembly can delay Installation Do not attempt to compensate for in-
sprinkler operation in a fire situation. sufficient adjustment in the Sprinkler
The TYCO Series RFII 5.6 K-factor, by under-or over-tightening the Sprin-
Oeration "Royal Flush II" Concealed Pendent kler/Support Cup Assembly.Re-adjust
p Sprinklers must be installed in accor- the position of the sprinkler fitting to
When exposed to heat from a fire, the dance with this section. suit.
Cover Plate, normally soldered to the General Instructions Step 1. Install the sprinkler only in the
Retainer
the three rpoint , falls away to Do not install any bulb-type sprinkler if of thenspr nklern I
perpend c lar to the
expose se l . p pPo p the bulb is cracked or there is a loss mounting surface.
Assembly. of liquid from the bulb.With the sprin- Step 2.Remove the Protective Cap.
The Deflector — supported by the kier held horizontally, a small air bub- Step 2.Remove the Protective Cap.
Guide Pins — then drops down to its ble should be present. The diameter Step 3. With pipe thread sealant ap-
operational position. of the air bubble is approximately 1/16 plied to the pipe threads, hand-tighten
inch (1,6 mm)for the 155°F(68°C)and the sprinkler into the sprinkler fitting.
The glass bulb contains a fluid that ex- 3/32 inch(2,4 mm)for the 200°F(93°C) Step 4. Wrench-tighten the sprinkler
ex-
pands when exposed to heat. When temperature ratings. using only the RFII Sprinkler Wrench.
the rated temperature is reached, the (Refer to Figure 3.) Apply the RFII
fluid expands sufficiently to shatter the A leak-tight 1/2 inch NPT sprinkler joint Sprinkler Wrench to the Sprinkler as
glass bulb,activating the sprinkler and should be obtained by applying a min- shown in Figure 3.
allowing water to flow. imum to maximum torque of 7 to 14 Step 5. Replace the Protective Cap
. ft.-lbs. (9,5 to 19,0 Nm). Higher levels by pushing it upwards until it bottoms
of torque can distort the sprinkler In- out against the Support Cup. (Refer
let with consequent leakage or impair- to Figure 4.)The Protective Cap helps
ment of the sprinkler. prevent damage to the Deflector and
TFP181
Page 3 of 4
FACE OF CLEARANCE HOLE CLEARANCE
SPRINKLER DIAMETER - ' HOLE
- FITTING DIMENSION C
SPRINKLER 1j - ' J 1=�
SUPPORT CUP e
ASSEMBLY I li,,1/2
"(12,7 mm) ' r THREADED It '%4i �D ADJUSTMENT ll I■I
FACE i4 o ------_--
OF CEILING,
RETAINING RING \ '""'� "'i
MOUNTING / I i i ���/
SURFACE / el 1 FIGURE 4
�J �� DISPOSABLE PROTECTIVE CAP
I ‘.\--J , ____...--.. • MIL.
Arms during ceiling installation and/or
finish. You can also use the Protective
I i r---T 1-r-J Cap to locate the center of the clear-
3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE ance hole by gently pushing the ceiling
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER material up against the center point of
REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY the Protective Cap.
COVER PLATE COVER PLATE NOTICE
-PROFILE DEPTH DIAMETER As long as the Protective Cap remains
DIMENSION B DIMENSION A in place, the system is considered
A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) "Out of Service".
Step 6.After the ceiling has been com-
B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) pleted with the 2-1/2 inch(63,5 mm)di-
ameter clearance hole and in prepa-
FIGURE 2 ration for installing the Cover Plate/
SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Retainer Assembly, remove and dis-
card the Protective Cap.Verify that the
Deflector moves up and down freely.
-� If the Sprinkler is damaged and the
j=lt FRAME iy=il Deflector does not move up and down
ARM i% freely, replace the entire Sprinkler.
/ \ Do not attempt to modify or repair a
damaged sprinkler.
SUPPORT / _ Step 7. When installing an Air and
- CUP i Dust Seal, refer to Figure 5; otherwise,
_ _ i i proceed to Step 8. To attach the Air
■s- it . and Dust Seal, verify the angle of the
= ��4 outside edge of the seal is oriented ac-
cording to i cording to Figure 5. Start the edge of
-_- - --
0
the Retainer in the grooved slot of the
7/8"(23 mm) Air and Dust Seal and continue around
SQUARE the retainer until the entire Air and Dust
Seal is engaged.
"..:"F-J-1-_--
�-` Step 8. Screw on the Cover Plate/
ALIGN Retainer Assembly until the Retainer
ARROWS WITH /r' 1 i (shown in Figure 2)or the Air and Dust
FRAME ARMS Seal (shown in Figure 5) contacts the
'l al ceiling. Do not continue to screw on
i i the Cover Plate/Retainer Assembly
ACCEPTS \ `� ' so that it lifts a ceiling panel out of its
0 1/2"SOCKET \ r normal position. If you cannot engage
DRIVE \ the Cover Plate/Retainer Assembly
FIGURE 3 with the Support Cup or you cannot
RFII SPRINKLER WRENCH engage the Cover Plate/Retainer As-
sembly sufficiently to contact the ceil-
ing, you must reposition the Sprinkler
Fitting.
TFP181
Page 4 of 4
Care and SUPPORT SPRINKLER FACE OF ORIENT
CUP CEILING ��SEAL
Maintenance — BEVEL AS
j=tom _ COVER ). SHOWN
i The TYCO Series RFII 5.6 K-fac-
1 j� '
tor, "Royal Flush II" Concealed Pen- PLATE
dent Sprinklers must be maintained
; RETAINER — )
and serviced in accordance with this `� �, ASSEMBLY
section. _ _
Before closing a fire protection system ``� ' - I
main control valve for maintenance At owl ! � AIR
work on the fire protection system that
AND DUST
it controls, obtain permission to shut •— �_—• LIP OF COVER SEAL
down the affected fire protection sys- RETAINER PLATE
tern from the proper authorities and FIGURE 5
notify all personnel who may be affect- OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551)
ed by this action.
Absence of the Cover Plate/Retainer If you must remove a sprinkler, do not Ordering
Assembly can delay sprinkler opera- reinstall it or a replacement without re-
tion in a fire situation. installing the Cover Plate/Retainer As- Procedure
When properly installed, there is a As-
sembly. If a Cover Plate/Retainer As-
nominal 3/32 inch(2,4 mm)air gap be sembly becomes dislodged during Contact your local distributor for
tween the lip of the Cover Plate and the service,replace it immediately. availability. When placing an order,
ceiling,as shown in Figure 2. The owner is responsible for the in- indicate the full product name.
spection, testing, and maintenance of
This air gap is necessary for proper their fire protection system and devic- Sprinkler/Support Cup Assembly
operation of the sprinkler. If the ceil- es in compliance with this document, Specify: Series RFII SIN),
ing requires repainting after sprinkler p p Y (specify Sprin-
installation, ensure that the new paint as well as with the applicable stan- K=5.6, "Royal Flush II" Pendent Sprin-
does not n, ensure
off any that
the air gap. dards of the National Fire Protection kiers (specify) temperature rating and
Association(e.g., NFPA 25), in addition (specify)finish,P/N(specify).
Do not pull the Cover Plate relative to to the standards of any other authori-
the Enclosure.Separation may result. ties having jurisdiction. Contact the in- 155°F(66°C1 200°F(93°C)
S rinklers which are found to be leak- stalling contractor or sprinkler manu- TY3531 51-792-1-155 51-792-1-200
p facturer regarding any questions. TY3551 51-790-1-155 51-790-1-200
ing or exhibiting visible signs of corro-
sion must be replaced. Automatic sprinkler systems should be Separately Ordered Cover Plate/
inspected,tested,and maintained by a Retainer Assembly:
Automatic sprinklers must never be qualified Inspection Service in accor-
painted, plated, coated, or other- dance with local requirements and/or Specify: (temperature rating from be-
wise altered after leaving the factory. national code. low) Series RFII Concealed Cover
Modified sprinklers must be replaced. Plate with(finish),P/N(specify).
Sprinklers that have been exposed to 139°F(59°C)(a) 165°F(74°C)(b)
corrosive products of combustion,but Grey White
have not operated,should be replaced (RAL9002) 56-792-0-135 56-792-0-165
if they cannot be completely cleaned Brass 56-792-1-135 56-792-1-165
by wiping the sprinkler with a cloth or Pure White(c)
by brushing it with a soft bristle brush. (RAL9010) 56-792-3-135 56-792-3-165
Care must be exercised to avoid dam- Signal White
(RAL9003) 56-792-4-135 56-792-4-165
age to the sprinklers - before, during, Jet Black
and after installation. Sprinklers dam- (RAL9005) 56-792-6-135 59-792-6-165
aged by dropping, striking, wrench Brushed
twist/slippage, or the like, must be re- chrome 56-792-8-135 56-792-8-165
placed.Also,replace any sprinkler that Chrome 56-792-9-135 56-792-9-165
has a cracked bulb or that has lost Custom 56-792-X-135 56-792-x-165
liquid from its bulb. (Ref. Installation (a) For use with 155°F(68°C)sprinklers.
Section.) (b) For use with 200°F(93°C)sprinklers.
Exercise care to avoid damage to (c) Eastern Hemisphere sales only.
sprinklers before, during, and after in- Sprinkler Wrench
stallation.Replace sprinklers damaged Specify: RFII Sprinkler Wrench,
by dropping, striking, wrench twisting, P/N 56-000-1-075.
wrench slipping, or the like. Also, re-
- place any sprinkler that has a cracked Air and Dust Seal
bulb or that has lost liquid from its Specify:Air and Dust Seal,
bulb.(Refer to the Installation section.) P/N 56-908-1-001.
GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
Copyright®2013 Tyco Fire Products,LP. All rights reserved. Vi ico
TEFLON is trademark of The DuPont Corporation.
Dyna-Thread® - M-COAT®
Submittal Data Sheet
O Full Line Sch-40 Replacement Dyna-Thread—M-COAT Specifications
Dyna-Thread"'-M-Coati sprinkler pipe represents an engineering NPS Nominal I.D. Wt. Wt.(H20 Filled) CRR CRR
. advancement for the spunkier pipe industry.It combines the safety In;mm In;mm Lbs/Ft kg/m Lbs/Ft;kg/m Unthreaded Threaded
and longevity of traditional Sch-40 pipe with quality and superior 1" 1.080 1.330 1.75 11.39 1.00
hydraulic advantages. 25 27.4 2.0 2.60 — - -
1'/4" 1.408 1.870 2.54 9.50 1.00
O Comparison to Schedule 40 32 35.8 2.8 3./8 — — _
1'/2" 1.639 2.290 3.22 9.14 1.00
Dyna-Thread4.-M-CoatC inside diameter is up to 3.6%larger than Sch-40 40 41.6 3.4 4.79 - -
giving it superior hydraulics.Also,when used in combination with Dyna- 2" 2.104 3.050 4.57 8.41 1.00
Flow-M-Coat pipe,down sizing often occurs.Dyna-Thread is fully listed and 50 53.4 4.5 6.80 — -
approved UL,ULC,and FM for fire sprinkler applications.The life expectancy -
of Dyna-Thread-M-Coat and Sch-40 are equal based on the calculated wall ® c®
thicknesses per UL.The consistent quality of steel used to make Dyna-Thread- APPROVED
M-Coat facilitates smooth threading and lower maintenance costs.The exterior
of Dyna-Thread-M-Coat is protected by a clean,durable mill coating for ® American Made
extended shelf life and easy paint application.With its increased strength Manufactured at one of 3 U.S.Facilities and is available
and lighter weight, Dyna-Thread-M-Coat reduces installation fatigue and through distributors in the USA,Canada,Mexico,and
is ideal for retro-fit applications.Corrosion Resistance Ratio(CRR)is a UL Latin America.
(Underwriters Laboratory)term for the estimated life expectancy of a pipe joint.
= This is based on the calculated wall thickness at the base of the first exposed ®Specifications &Approvals
thread,assumed to be the weakest point of the pipe length.Dyna-Thread-
M-Coat and Sch-40 have the same calculated wall thicknesses at this point Dyna-Thread-M-Coat pipe is manufactured to meet:ASTM A
and are both assigned the same CRR of 1.00. 135,Type E Grade A,and is in compliance with hiFPA-13.All
sizes of Dyna-Thread-M-Coat are rated at 300 psi working
0 Comparison to L.W.T. Pipe pressure.Dyna-Thread-M-Coat is UL and ULC Listed for wet,
More wall thickness at the thread(CRR=1.00)gives Dyna-Thread-M-Coat dry and pre-action sprinkler systems and FM Approved for
better life expectancy than lightwall threadable pipe joints.Dyna-Thread- use in wet systems.Dyna Thl ead-M-Coat is approved for all
M-Coat is approved for standard hanger spacing(15 ft.O.C.),can be used as threaded couplings and welded outlets and is suitable for all
earthquake sway bracing,and is safe to use as drops.Dyna-Thread-M-Coat roll grooved,and plain end fittings.(See listing information).
is safer to weld on than many zinc coated lightwall threadable pipe products.
Dyna-Thread-M-Coat is more widely accepted than lightwall threadable
where Sch-40 is specified.
Project: Sprinkler Contractor: Date:
Engineer: Specification Reference: System Type:
Locations: Comments:
Ponied Customer Service:(800)882-5543 Fax:(800)659-7730 www.alliedtube-sprinkler.com
• 16100 5 Lathrop Ave • 1 1350 Norcom Rd. • 2525 N 27th Ave.
TUBE&CONDUIT' Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009
"'°"`OF=}'� ■r? e2013 Atkore International,Inc.All Rights Reserved.STP-53-4M-1301
Cn
= .
y cue
. £f+`1 k•'`F r k�lmf
' i
OZ
1' r 1'a`s'0E*' ' '� •{ i�T N•Al•gi4 y 'z 't ! .+ „ 11, 4), '$� F. v@• ,'a' 4i? . ,r N �,;� �ir4s 3rx +
M w S A� at «7r l .,W><♦ l Vt '1,.r_•pmi
l',..',/
' 1 'y r QT #.11; , r! t _ ,�_ S ; Ais t�k .4,.* ' .;4 F
'MCI A J;y T r-.7.
Plitil: . f; , 0„, , • , •, . 0
14 t t f a IJc: t! .T y'. ?
= .):,..- ',
'�'S St S v-.� A''.'".017,21,',41-0-;'f' Ss s s
''S !" r 1 x..af;r i . S c++ c -l+�c-,cu^ 't+. . »s_: '4!
y�., 4 ..�s ft` ¢ .:+ d a� "Z"7 r ! -U��y 17s•i:.
k
At • + t`A'E
lilli sv�"§e w ,+.° ,yy < 1 .; `Y ,
,tom* s
as f'^ �' ,�, . r r ;3�' •4
MIMI
tr T .f s r f!V.'.
rya'
k,
Cid '
CZ
SMCODFEi
I N T E R N A T I O N A L•
Ductile Iron Threaded Fittings
Specifications
• 4> branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi
• Rated to 300 WSP
Ductile iron castings conform to ASTM A536 C US
• LISTED
• Fitting dimensions conform to ASME B16.3
• Bushings and plugs conform to ASME B16.14 41>
• Fittings are 100% air tested APPROVED
• NPT threads on all fittings conform to ASME B1.20.1
• Independent lab verification that fittings meet applicable chemical&physical properties
• Manufacturing facilities are ISO 9001:2008 and ISO 14001
Temperature Working Pressure, Nonshock psiG
Degrees F 300# Class Threaded Fittings
-20 to 100 500
150 500
200 480
250 460
300 440
350 420
400 400
450 380
500 360
550 340
600 320
650 300
•
Dail le trot [1 r lass Q . .t .
c (20US
APPROVED
LISTED
- A Fig. 35E 3- 90'Elbow
<r -� Size A Packing Weight
� in Part Number
in inner Master lb
/f(i } x3_"'!. . 1/2 35E 3004 1.13 100 200 0.2
\.'.. .. -�q 3/4 35E 3006 1.31 70 140 0.3
r- ' , ' A 1 35E 3010 1.50 40 80 0.5
- �t R' 1-114 35E 3012 1.75 25 50 0.8
1-1/2 35E 3014 1.94 18 36 1.1
2 35E 3020 2.25 10 20 1.8
2-1/2 35E 3024 2.70 4 8 3.2
Fig. 35RE3- 90°Reducing Elbow
B Size A B Packing Weight
"_-' `r,= (-) Part Number
in in in Inner Master lb
3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3
,,r, ry `% 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4
1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4
1-1/4 x 112 35RE3012004 1.34 1.53 35 70 0.5
1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6
1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7
1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6
1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7
1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8
1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0
2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0
2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0
2 x 1 35RE3020010 1.73 2.02 16 32 1.2
2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3
:j
1 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5
h( 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2
2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5
•f
Fig. 35F 3-45°Mew
Size Part Number A Packing Weight
-• in in Inner Master lb
� 12 35F 3004 0.88 150 300 0.2
� • 314 35F 3006 0.98 80 160 0.3
#10 1 35F 3010 1.13 40 80 0.5
1-1/4 35F 3012 1.29 25 50 0.7
I - A
1-1/2 35F 3014 1.44 20 40 1.0
�' 2 35F 3020 1,69 10 20 1.6
2-1/2 35F 3024 1.95 4 8 2.7
Fig. 35T 3- Tee
• Size Part Number A Packing Weight
in in Inner Master lb
A 1/2 35T 3004 1.13 80 160 03
" 3/4 35T 3006 1.31 30 60 0.5•€f � � girl� 1 35T 3010 1.50 25 50 0.7
1,' •'' `=-1' 1-1/4 35T 3012 1.75 10 20 1.1
A A 1-12 35T 3014 1.94 10 20 1.5
2 35T 3020 2.25 6 12 2.4
2-1/2 35T 3024 2.70 4 8 4.3
111 SMITH-COOPER INTERNATIONAL* • TOLL FREE 1410-766-0076 • FAX k323)5'40--1456 • WA\NV.smithcO)per.cum
FDLCJ _ www.tolco.com
NIBCO Revision 12/18/2008
Fig. 200 - "Trimline" Adjustable Band Hanger 0USLISTED
Fig. 200R (Import) - "Trimline" Adjustable Band Hanger
w/Retainer Ring "
Size Range — 1/2" thru 8" pipe �±
Material — Carbon Steel, Mil. Galvanized to G90
. specifications .�..�r ��-�
Function — For fire sprinkler and other general piping --
purposes. Knurled swivel nut design permits hanger
adjustment after installation. ---
Features — 1
• (1/2" thru 2") Flared edges ease installation for i B
, B ( I
all pipe types and protect CPVC plastic pipe // ; - ,► i //
from abrasion. Captured design keeps adjusting A ;i' ) f;
nut from separating with hanger. Hanger is eas- t 1 , /
ily installed around pipe. A
• (21/2" thru 8") Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed. Fig.200 1"-2" Fig.200 21/2"-8"
Approvals — Underwriters' Laboratories listed
(1/2" thru 8') in the USA(UL)and Canada(cUL) 4,L-
for steel and CPVC plastic pipe and Factory Mutual - -
Engineering Approved (3/4" thru 8"). Conforms to �U1_.
Federal Specifications WW-H-171 E,Type 10 and ® �,�
Manufacturers Standardization Society SP-69, Type / ;, 41
10. _
B
Maximum Temperature — 650°F / / -
I materials I i// ' % ? ' i' B I/i'' i ```
Finish Mil. Galvanized. Stainless Steel w will
,,f- ;; /; -
be supplied with (2) hex nuts in place of a knurl nub. I r i ;- ' 1,,,,,,
Order By — Figure number and pipe size i ; -- A ;, i
Note — Figure 200R(import)with retainer ring and A
.--_- A∎
non-captured knurl nut. --_
Fig.200R 21h"-8" Fig.200R 1/2"-2"
Dimensions •Weights
Pipe Rod Size Max.Rec. Approx.
• Size Inch Metric A B Load Lbs. WtJ100
1/2 3/8 8mm or 10mm 31/2 2% 400 11
3/4 3/8 8mm or 10mm 3143 21/2 400 11
' 1 3/8 8mm or 10mm 3% 2% 400 12
11/4 3/8 8mm or 10mm 3314 21 400 13
11/2 3/8 8mm or 10mm 37/e 21 400 14
2 3/8 8mm or 10mm 41/2 3 400 15
21 3/8 10mm 5% 41/2 600 27
3 3/8 10mm 51 4 600 29
31/2 3/8 10mm 7% 51/4 600 34
4 3/8 10mm 7% 5 1000 35
5 1/2 12mm 91/2 61/4 1250 66
6 1/2 12mm 10% 63/4 1250 73
8 1/2 12mm 13% 83/4 1250 136
OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE•CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330
CUSTOMER SERVICE•800.786.5266 III
www.tolco.com
. 72g10:0
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
100
REVERSIBLE
BEAM CLAMP 3/4" MOUTH
111111101A 1,,,
All( 711—Td 3-1.1 =
SIZE-ROD:3/8" SIZE-SYSTEM PIPE: 4"max.
SIZE-ROD: 1/2" SIZE-SYSTEM PIPE: 8"max.
MATERIAL-Ductile iron.
FINISH-Plain,E.G.and H.D.G.
LISTING/APPROVAL-
Q."203-EX 2551
- FM Approved .•
FUNCTION-Attachment component of an AFCONhanger. Ail To support horizontal piping.
INSTALLATION- Per NFPA 13 and these instructions. _yam
Install on steel flange-thickness less than 3/4". _
Set bolt up or down.
ASSEMBLY/ATTACHMENT-See drawing. _
Torque-3/8"=60 inch lbs.or l/2"= 125 inch lbs.
In the absence of a torque wrench,engage set bolt finger tight then
additionally tighten 1/4 turn. _
Caution-Do not over tighten set bolt. _
FEATURES
. *Maintains CONSTANT HANGER CENTER-LINE,with set bolt
up or down.
- *Flat throat back to prevent twisting on structure during installation.
ORDERING-Part#,rod size and finish.
11/09
TOLCO _ www.tolco.com
NIBCO Revision 3/10/2010
Fig. 69 - Beam Clamp Retaining Strap Component of State of
CaliforniaOSHPDApproved OusLISTER
Seismic Restraints System
• Size Range—3/8" thru 7/8" rod by 4" thru 16" length.*
Material —Pre-Galvanized Steel
Function — To offer more secure fastening of various types
of beam clamps to beam where danger of movement might
be expected. NFPA 13 requires the use of retaining straps
with all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13 (2010) 9.3.7.1.
Important Note — Good installation practice of a retaining
strap requires that the strap be held tightly and securely to all
component parts of the assembly. Therefore a locking mech-
anism of some kind such as a hex nut or the beveled locking
slot on the TOLCOO Fig. 69R will provide a more secure
reliable installation.
Approvals — Underwriters' Laboratories listed in the
USA(UL) and Canada(cUL). Approved for use with any
listed beam clamp. Included in our Seismic Restraints
Catalog approved by the State of California Office of
Statewide Health Planning and Development(OSHPD). For
additional load. spacing and placement information relat-
ing to OSHPD projects. please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Finish — Pre-Galvanized
Order By — Figure number, type, length "B" and rod size
being used with beam clamp
I..
Note — Minimum return on Strap: 1".
ILW/IPTAIWAVAI
u'
__ „ 1
Dimensions
Type Rod Size A Hole Size B
YP
1 3/8 7/16 Specify
1/2 9/16 Specify
2 5/8 11/16 Specify
3/4 13/16 Specify
3 3/8-7/8 Specify Specify
*Longer lengths are available,consult factory. --``--r,•1,1 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330
CUSTOMER SERVICE•800.786.5266
www.tolco.com