'JIKIF16i® SPRINKLER WATER
TECHNICAL DATA SHIELDS AND GUARDS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
1. DESCRIPTION
Viking Model A-1, B-1, and C-1 Sprinkler Water Shields and Guards are used in conjunction
with Viking frame style '/7" or 3/4" NPT (15 mm or 20 mm BSP) upright or pendent sprinklers
where allowed by the approvals. (Refer to the Approval Chart on page 130g.) The guards are
hard-wire cages designed to encase the sprinklers and protect them from mechanical damage.
They are recommended for areas where sprinklers are installed at a low elevation and/or near
a high degree of human or mechanical activity.
Water shields protect the sprinklers'heat-sensing operating element from water spray discharge t IMP '
from sprinklers located at a higher elevation.Viking frame style sprinklers with Model B-1 or C-1
Water Shields are converted to intermediate level/rack storage sprinklers. They may be used Model A-1 Sprinkler Guard
in any application where water shielding is required, such as in-rack sprinkler systems, under
grating, on pilot sprinklers for deluge systems, and outdoors as a weather shield. - - --_,_
2. LISTINGS AND APPROVALS
FM Approved: Class 2091
NYC Approved: MEA 89-92-E, Volume 12 and Calendar Number 219-76-SA, Bulletin No. 26,
Vol. LXIX !t of
VdS Approved: Certificate G4920022
Warning: Products represented on this page and manufactured after 1998 have no UL Model B-1 Upright Water Shield
Listing. and Guard Assembly
See the Approval Chart on page 130g for FM, NYC, and VdS Approvals.
3. TECHNICAL DATA l
Specifications:
Model A-1, B-1, and C-1 Sprinkler Viking Technical Data may be found on
Guards: Dimensions: 2-5/16" (58.7
mm) diameter, 2-1/4" (57.2 mm) high. The Viking Corporation's Web site at
Available since 1982. http://www.vikinggroupinc.com.
Model B-1 Sprinkler Water Shield: The Web site may include a more recent
edition of this Technical Data Page. Model C-1 Pendent Water
Dimensions: 4-3/8" (111.1 mm) diam- Shield and Guard Assembly
eter, 0.0359" (0.91 mm) thick.
Available since 1984. j ��
Model C-1 Sprinkler Water Shield: Dimensions: 3-1/2" (88.9 mm) diameter, 0.0359" (0.91 .
/ VIKING\
mm) thick.Available since 1986. non. c-i
Material Standards:
0 (T)
Sprinkler Guards: UNS-G10100 Bright Basic Steel Wire
Water Shields: UNS-G10080 Cold Rolled Steel \
Ordering Information: (Also refer to the current Viking price list.) \\ �/
Order water shields and guards using the appropriate part number for the thread size required. Model C-1 Pendent Water Shield
1. To order the Model A-1 Sprinkler Guard, specify Part No. 05446A, for either 1/2" or 3/4" (15 _
mm or 20 mm).
2.To order the Model B-1 Upright Water Shield and Guard Assembly, specify: Part No. 05866A, ., ..
for either%" or 3/4" (15 mm or 20 mm).
Viking Model C-1 Pendent Sprinkler Water Shields and Guard may be ordered separately or as
a package. However, the Model C-1 Guard cannot be used without Model C-1 Water Shield.
3.To order the Model C-1 Pendent Sprinkler Water Shield and Guard package, specify:
A. Part No. 06509A, 1/" (15 mm), or
B. Part No. 06682A, 3/4" (20 mm).
4. To order the Model C-1 Pendent Water Shield only, specify: Model C-1 Pendent Guard
A. Part No. 06467B, 1/2" (15 mm), or Figure 1
B. Part No. 06656B, 3/4" (20 mm).
Form No. F_061289 Replaces page 130e-h dated February 26, 2010.
(Replaced Part Nos 10138 and 06661B with 12986 and 12978)
Sprinkler 130f February 7, 2013
CR
TECHNICAL DATA SPRINKLER WATER
SHIELDS AND GUARDS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
_ Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
5.To order the Model C-1 Pendent Guard only (for use with the Model C-1 Water Shield), specify Part No. 06471A.
NOTE: Model A-1, B-1, and C-1 Sprinkler Water Shields and Guards are NOT designed to be used on sprinklers installed
in recessed escutcheons.
Sprinklers must be ordered separately. Refer to the appropriate sprinkler Technical Data Page.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches: Part No. 10896W/B (available since 2000) or 05000CW/B (no longer available).
4. INSTALLATION
NOTE: Viking Model A-1, B-1, and C-1 Sprinkler Water Shields and Guards are not available factory pre-assembled with the sprin-
klers. They must be ordered separately and then field installed onto the Viking frame style sprinklers.
Refer to the appropriate Viking sprinkler Technical Data Page for warnings and additional installation instructions.Then install units
according to the following steps:
A. MODEL A-1 SPRINKLER GUARD
Viking frame style sprinklers must be installed on the system prior to adding the Model A-1 Sprinkler Guards onto the sprinklers.
After the sprinklers are installed:
1. Remove the retaining ring from the Model A-1 Sprinkler Guard.
2. Spread and hold the two bracket halves at the base of the guard just enough to place the guard over the deflector and wrench
boss of the sprinkler.
CAUTION: Excessive spreading of the guard may break the weld.
3. With the sprinkler inside the sprinkler guard, orient the guard with the heavy wire base parallel to the sprinkler wrench boss. The
two halves of the bracket should grip the sprinkler in the slot between the wrench boss and the threads.
4. Press the retaining ring over the guard and toward the base of the sprinkler until the ring snaps firmly into the depressions pro-
vided on each of the six wire members of the guard.
a.To remove, reverse the instructions. If the sprinkler must also be removed, follow the system instructions and notify appropri-
ate personnel.
B. MODEL B-1 UPRIGHT SPRINKLER WATER SHIELD AND GUARD ASSEMBLY
The Model B-1 Upright Water Shield and Guard are available as a welded assembly only.Viking frame style upright sprinklers must
be installed on the system prior to installing the Model B-1 Upright Water Shield and Guard Assembly onto the sprinklers.After the
sprinklers are installed:
1. Position the retaining ring against the water shield.
2. Spread and hold the two bracket halves at the base of the guard just enough to place the guard over the deflector and wrench
boss of the sprinkler.
CAUTION: Excessive spreading of the guard may break the weld.
3. With the sprinkler inside the sprinkler guard, orient the guard with the heavy wire base parallel to the sprinkler wrench boss.The
two halves of the bracket should grip the sprinkler in the slot just below the wrench boss, and above the threads.
4. Press the retaining ring down until it slides into the notches in the six wire members of the guard.
To remove, reverse the instructions. If the sprinkler must also be removed, follow the system instructions and notify appropriate
personnel.
C. MODEL C-1 PENDENT SPRINKLER WATER SHIELDS AND GUARDS
The Model C-1 Pendent Water Shields can be installed with or without the Model C-1 Guard. However,the Model C-1 Guard cannot
be installed without the Model C-1 Water Shield. To install Model C-1 Pendent Water Shields:
1. Thread the Viking frame style pendent sprinkler into the shield. The concave surface of the shield should face the sprinkler
deflector.
2. Apply a small amount of pipe-joint compound or tape to the external threads of the sprinkler only, taking care not to allow a
build-up of compound in the sprinkler inlet.
3. Install the sprinkler unit on the piping using the standard sprinkler wrench. DO NOT use the shield to start or thread the sprinkler
into the fitting.
Viking frame style pendent sprinklers and Model C-1 Water Shields must be installed on the system prior to installing the Model
C-1 Guard onto the sprinkler. If the Model C-1 Guard is used:
1. Remove the retaining ring from the guard.
2. Place the Model C-1 Guard over the sprinkler.
3. Spread each half of the cage slightly and gently push the cage onto the shield retainer until it snaps into place.
CAUTION: Excessive spreading of the cage may break the weld.
1
February 7, 2013 Sprinkler 130g
NIKING.
SPRINKLER WATER
TECHNICAL DATA SHIELDS AND GUARDS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
_ Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
Approval Chart
i----Temperature KEY
Model A-1 Sprinkler Guard,and Upright i Finish
Intermediate Level/Rack Storage Sprinklers A1X4- Escutcheon(If applicable)
with Model B-1 Water Shield and Guard Assembly .
Nominal Listings and Approvals'
Base Part Sprinkler Maximum Thread Size Overall Length (Refer also to Design
SIN ' K-Factor Criteria on 130h.
Number Style Pressure pg )
NPT BSP U.S. metric' Inches mm FM' NYC' VdS6
Standard Response Standard Orifice
12986 VK100 Upright 175 psi 1/2" 15 mm 5.6 80.6 2-3/16 56 B1 - -
10233 VK145 Upright 175 psi 1/2" 15 mm 5.6 80.6 2-3/16 56 B1 - A2
Standard Response Large Orifice
10141 VK200 Upright 175 psi 3/4" 20 mm 8.0 115.2 _ 2-5/16 _ 59 B1 - -
Standard Response Fusible Link
05557 VK108 Upright 175 psi 1/2" 15 mm 5.6 80.6 2-3/16 56 Cl D1 -
05514 VK204 Upright 175 psi . 3/4" 20 mm 8.0 115.2 2-5/16 59 C1 D1 -
Quick Response Glass Bulb
12978 VK300 Upright 175 psi 1/2" 15 mm 5.6 80.6 2-3/16 56 B2 B1 -
06665B VK350 Upright 175 psi 3/4" 20 mm 8.0 115.2 2-5/16 59 B2 B1 -
Conventional
10227 VK118 Conventional 175 psi 1/2" 15 mm 5.6 80.6 2-3/16 ' 56 -- - A2
Model A-1 Sprinkler Guard,and Pendent intermediate Level/Rack Storage Sprinklers with Model C-1 Water Shield and Guard'
Standard Response Standard Orifice Models A-1 and C-1 Model C-1 only
10139 VK102 Pendent 175 psi 1/2" 15 mm 5.6 80.6 2-3/16 56 B1 - A2
Standard Response Large Orifice
10142 VK202 Pendent 175 psi 3/4" 20 mm 8.0 115.2 2-5/16 59 B1 - -
Standard Response Fusible Link
05508 VK110 Pendent 175 psi 1/2" 15 mm 5.6 80.6 2-3/16 56 C1 D1 -
05516 VK206 Pendent 175 psi 3/4" 20 mm 8.0 115.2 2-5/16 59 -- D1 -
Quick Response Glass Bulb
06662B VK302 r Pendent 175 psi 1/2" 15 mm 5.6 80.6 2-1/4 58 B2 B1 -
06666B VK352 Pendent 175 psi 3/4" 20 mm 8.0 - 115.2 2-3/8 60 B2 B1 -
Conventional
10227 VK118 Conventional 175 psi 1/2" 15 mm 5.6 80.6 2-3/16 56 -- - A2
Approved Temperature Ratings
A- 155°F(68°C),175°F(79°C),200°F(93°C),286°F(141 °C),and 360°F(182°C) Approved Finishes
B- 135°F(57°C), 155°F(68°C), 175°F(79°C),200°F(93°C), and 286°F(141 °C) 1 -Brass
C- 165°F(74°C) and 286°F (141 °C) 2-Brass and Chrome-Enloy''
D- 165°F (74°C),220 °F(104°C), 286°F(141 °C), and 360°F(182°C)
E- 155 °F (68 °C)
Footnotes
'Base part number shown. For complete part number, refer to Viking's current price schedule.
''Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
'This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
'FM Approved for protection of occupancies described in the FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins.
- 'Model A-1 Sprinkler Guard and Model B-1 Water Shield and Guard Assembly are accepted for use, New York City Board of Standards and Appeals,
Calendar Number 219-76-SA. Model B-1 and Model C-1 Sprinkler Water Shields and Guards are accepted for use, City of New York Department of
Buildings, MEA 89-92-E, Vol. 12, with temperature ratings of 135°F(57°C), 155°F (68°C), 175°F(79 °C), 200°F (93 °C), and 286 °F(141 °C).
6 The Model A-1 Sprinkler Guard has no VdS Approval.
'Model C-1 Intermediate Level/Rack Storage Sprinklers with the Model C-1 Sprinkler Guard have the same FM Approvals and acceptance for use by
New York City Department of Buildings as those without the Model C-1 Sprinkler Guard.
Sprinkler 130h February 7, 2013•
'.jII(II'1Gi® SPRIN kTECHNICAL DATA SS ND GUARDS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
IMPORTANT NOTES
Viking Model A-1, B-1,and C-1 Sprinkler Water Shields and Guards are used in( Refer conjunction the A with Viking
Chart on page 130 or 3/4" NPT (15 mm
or 20 mm BSP) upright or pendent sprinklers where allowed by the app
Products represented on this page and manufactured after 1998 have no UL Listing.
Model A-1, B-1 and C-1 Sprinkler Water Shields and Guards are NOT designed to be used on sprinklers installed in recessed escutcheons.
WARNING:Viking products accordance with recognized ainstallat on standards. requirements
from thefst approving
any alteration to the sprinkler after it
to v installed in a plating, coating,or modification, may render the sprinkler inoperative and will nul-
lify the factory including,but not limited to: painting ,p 9� g.
lify the approval and any guarantee made by The Viking Corporation.
IMPORTANT Always refer to Bulletin Form
i Handling t edition
ap-
propriate sprinkler data page.Viking sP k e s are designed to be installed accordance with the latest
of Viking technical data, the latest standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-
tions, and also with the provisions of governmental codes, ordinances, hazard standards whenever
holicable. he
use of certain types of sprinklers may be limited due to occupancy and
Jurisdiction prior to installation.
4. Slide the retaining ring onto the cage by pressing up until it locks into the notches on each of the six wire cage members.
To remove, reverse these instructions. Before removing the sprinkler and water shield, follow the system instructions and remove
_ the system from service. Notify appropriate personnel prior to removing the system from service.
5. OPERATION
Refer to the sprinkler techical data page for the sprinkler model used. Water shields protect the sprinklers' heat-sensing operating
element from water spray discharge from sprinklers located at a higher elevation.The Sprinkler Guard is a hard-wire cage designed
to encase the sprinkler and protect it from mechanical damage.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection,Testing and Maintenance requirements.
7. AVAILABILITY
Viking sprinkler water shields and guards are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Replaces page 130e-h dated February 26, 2010.
Form No. F_061289 (Replaced Part Nos 10138 and 06661B with 12986 and 12978)
RECEIVED
June 28, 2013 c rp 1 6 2014 Sprinkler 11q
NIKINGirr MICROMATIC®AND
TECHNICAL DATA MicromaticHP® STANDARD
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
• Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
1. DESCRIPTION
Viking Micromatie' and MicromaticHP" Standard Response Upright and
Conventional (Old Style) Sprinklers are small, thermosensitive, glass-bulb
spray sprinklers available in several different finishes, temperature rat- i •
ings, and K-Factors to meet design requirements. The special Polyester, II 1
Polytetrafluoroethylene (PTFE), and Electroless Nickel PTFE (ENT) coatings i,' t.:
can be used in decorative applications where colors are desired. In addition,
these coatings have been investigated for installation in corrosive atmospheres ::"71;f1 ti's�"i;
and are listed/approved as corrosion resistant as indicated in the Approval l '
Chart. (Note: FM Global approves the ENT coating as corrosion resistant. FM
Global has no approval classification for PTFE and Polyester coatings as corro-
sion resistant.) - '
Viking standard response sprinklers may be ordered and/or used as open sprin-
klers (glass bulb and pip cap assembly removed) on deluge systems. Refer to
Ordering Instructions on page 11r.
2. LISTINGS AND APPROVALS
�� os cULus Listed: Category VNIV
FM FM Approved: Classes 2001, 2002, and 2016
NYC Approved: MEA 89-92-E, Volumes 3 and 12
VdS‘ ABS Certified: Certificate 04-HS407984B-PDA
• VdS Approved: Certificates G4060055, G4980001, G4980003, G4980004, G4980006, and G4980008
LPCB LPC Approved: Ref. No. 096e/06
E CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40137,
O 0786-CPD-40142, 0786-CPD-40177, and 0786-CPD-40182
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008
NOTE: Other International approval certificates are available upon request.
Refer to Approval Chart 1 and Design Criteria on pages 11t-u for cULus Listing requirements, and refer to Approval Chart 2 and
Design Criteria on page 11v for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 1997. Viking Technical Data may be found on
Minimum Operating Pressure: 7 psi (0.5 bar)* The Viking Corporation's Web site at
Maximum Working Pressure: Sprinklers VK021 and VK124 are rated for http://www-vikinggroupinc.com.
use with water working pressures ranging from the minimum 7 psi The Web site may include a more recent
(0.5 bar) up to 250 psi (17 bar)for high-pressure systems. High-pres- edition of this Technical Data Page.
sure (HP) sprinklers can be identified by locating "250" stamped on
the deflector.All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar)wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: Refer to the Approval Charts
Nominal K-Factor: Refer to the Approval Charts
Glass-bulb fluid temperature rated to-65 °F (-55 °C)
Overall Length: Refer to the Approval Charts
"cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi(0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 09993, 12986, 10227, and 10233. Brass UNS-C84400 for all other
sprinklers.
Form No. F_080106 Replaces page 11q-v, dated June 11, 2013.
(ENT finish is now approved as corrosion resistant.)
p
Sprinkler 11r June 28, 2013
MICROMATICP'AND
NiluNG® TECHNICAL DATA MicromaticHP® STANDARD
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
Deflector:Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 12986 and 12993. Copper UNS-C19500 for Sprinklers 10141,
10169, 10174, 10220, and 10233. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 09995, 10191, 10192, 10218, and 10219): Brass UNS-C36000
Bulb: Glass, nominal 5 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap for Sprinkler 09993: Brass UNS-C31400 or UNS-C31600. Pip Cap and Insert Assembly for all other Sprinklers: Copper
UNS-C11000 and Stainless Steel UNS-S30400
Pip Cap Attachment(for Sprinklers 09995, 10192, and 10218): Brass UNS-C36000
For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap- ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order Micromatic® and MicromaticHP' Standard Response Upright and Conventional Sprinklers by first adding the appropriate
suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass =A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and Black PTFE = N, Wax Coated = C,
Wax Over Polyester=V-/W, ENT= JN
Temperature Suffix(°F/°C): 135°/68° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, 212°/100° = M, 286°/141° = G, 360°/182° = H,
500°/260°= L, OPEN =Z(PTFE only).
For example, sprinkler VK100 with a 1/2" thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12986AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the"Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/B (available since 2000)
B. Wrench for wax-coated sprinklers: Part No. 13577W/B" (available since 2006)
"A'/2"ratchet is required(not available from Viking).
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A(available since 1971)
B. Twelve-head capacity: Part No. 01725A(available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection,Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Micromatic® and MicromaticHP® Standard Response Upright and Conventional Sprinklers are available through a
network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The
Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
•
•
June 28, 2013
Sprinkler 11s
R, MICROMATIC®AND
TECHNICAL DATA MicromaticHP® STANDARD
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
. Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal
•�lassifcation Maximum Ambient •
Temperature Rating' Ceiling Temperature2 Bulb Color
Ordinary 135 `F (57 °C) 100 °F (38 'C)
Orange
Ordinary 155°F (68 °C) 100 °F (38 °C)
Red
Intermediate 175 °F (79 °C) 150 °F(65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F(65 °C) Green
Intermediate 212 °F (100 °C) 150 °F(65 °C)
Green
High 286 °F(141 °C) 225 °F (107 °C) Blue
Extra High 360 °F(182 °C) 300 °F (149 °C) Mauve
Ultra High' 500 °F (260°C) 465 °F (240 °C) Black
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black PTFE in all temperature ratings. ENT in all tempurature
ratings except 135 °F (57 °C). Wax-Coated Brass and Wax over Polyesters for sprinklers with the following temperature ratings:
135 °F(57 °C) Off-White Wax 155 °F (68°C) Lt. Brown Wax 175 °F (79 °C) Brown Wax
200 °F(93 °C) Brown Wax 212 °F (100 °C)Dk. Brown Wax6 286 °F (141 °C) Dk. Brown Wax°
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
z Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction.
-Refer to specific installation standards.
'Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above ,.---
(149°C).Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149°C),
response time may be severely retarded.
"The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These
tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only.
Note that the spring is exposed on sprinklers with Polyester,ENT,and PTFE coatings.For PTFE coated open sprinklers only,the waterway is coated.
For ENT coated sprinklers,the waterway is coated.
"Wax Over Polyester is unavailable for Sprinklers VK021 and VK124.
6 Wax melting point is 170°F(76°C)for 212°F(100°C)and 286°F(141 °C)temperature rated sprinklers.
Wrench
Protective
Sprinkler
5 79a7 if
Flat
10896 m�
Figure 1:
Standard Sprinkler Wrench 10896W/B
r
i
Sprinkler 11t June 28, 2013
NIIKING 8 MICROMATIC®AND
TECHNICAL DATA MicromaticHP® STANDARD
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
- Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
Approval Chart 1 (UL) ----- Temperature KEY
Micromatic5'and MicromaticHP°Standard Response Upright and Conventional Sprinklers ai--. Finish
Maximum 175 PSI(12 bar)WWP „; A1XF Escutcheon(ii applicable)
Base Part Thread Size Nominal K-Factor Overall Length J Listings and Approvals'
Number' SIN (Refer also to Design Criteria on page 11u.)
NPT I BSP _ U.S. I metric' Inches I mm cULus4 I_ NYC' I VdS I LPCB I (("I 013
Upright-Standard Orifice
12986 VK100 1/2" 15 mm_ 5.6 80.6 2-3/16 56 Al, B4, C5, D3, F6 See Footnote 7. — — -- —
10233 VK145 1/2" 15 mm_ 5.6 _ 80.6 2-3/16 56 _ -- -- A2 A2, B4 A2 E2
10174 VK145 -- 15 mm_ 5.6 - 80.6 2-3/16 _ 56 -- — A2 A2, B4 -- — -
12993 VK100 -- _15 mm_ 5.6 80.6 _ 2-3/16 56 Al, B4, C5, D3, F6_ Al, B4,C5 -- _ -- __ -- --
Upright-Large Orifice
1022014 VK200 1/2" 15 mm 8.0 115.2 2-3/8 60 Al, B4, C5, D3, F6 Al, B4 A2 — E3 E3
10141 VK200 3/4" .20 mm 8.0 115.2 2-5/16 _ 59 Al, B4, C5, D3, F6 Al, B4, C5 A2 A2 E3 E3
10169 VK200 -- 20 mm 8.0 115.2 2-5/16 59 Al, B4,C5, D3, F6 — A2 A2 E3 E3
Upright-Small Orifice'
1021810 VK001 1/2" 15 mm 2.8 _ 40.3 2-3/16 56 Al, B4, C5 See Footnote 7. — -- -- --
1021910 VK002 1/2" 15 mm 4.2 _ 57 2-3/16 56 Al, B4, C5 See Footnote 7. — -- — --
1019110 VK002 — 15 mm 4.2 57 2-3/16 56 Al, B4, C5 — -- -- _ -- --
1019210 VK001 -- 15 mm _ 2.8 1 40.3 2-3/16 56 Al, B4, C5 -- — -- -- --
Conventional-Standard Orifice
10227 VK118 1/2" 15 mm 5.6 80.6 2-3/16 56 Al, B4 _ Al,B4 A2 A2, B4 A2 E2
10172" _VK118 -- 15 mm 5.6 _ 80.6 _ 2-3/16 56 A1, B4 -- _ -- A2, B4 -- —
Conventional-Large Orifice
10228 VK120 3/4" 20 mm 8.0 115.2 2-5/16 _ 59 Al, B4 Al,B4 A2 A2 E3 E2
10168" VK120_ -- 20 mm 8.0 115.2 2-5/16 _ 59 Al, B4 — A2 A2 E3 E3
Maximum 250 PSI (17 bar)WWP
Upright-Standard Orifice
09993 1 VK124 1 1/2" 115 mm I 5.6 1 80.6 I 2-1/4 1 58 ] Al, D3 I See Footnote 7. I -- I -- I -- I —
Upright-Small Orifice'
099959 I VK021 1 1/2" 115 mm I 2.8 1 40.3 I 2-1/4 _I 58 1 Al I See Footnote 7 I -- I -- 1 — I —
Approved Temperature Ratings
A- 135°F (57 °C), 155 °F(68 °C), 175 °F (79 °C),200 °F (93 °C), 286 °F Approved Finishes
(141 °C),and 360°F(182°C) 1 -Brass, Chrome,White Polyesters, Black Polyesters, and Black PTFE6
B- 135°F (57°C), 155°F(68°C), 175°F(79°C),and 200°F(93°C) 2-Brass, Chrome,White Polyester, and Black Polyester
C-286°F(141 °C) 3-Brass and Chrome
D-500°F (260°C)6 4-Wax-Coated Brass and Wax over Polyesters
E - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), and 5- 200 °F (93 °C) High-Temperature Wax Coating (corrosion resistant);
360°F(182°C) maximum ambient temperature allowed at ceiling= 150°F(65 °C)
F- 155°F (68°C), 175°F(79°C),200°F(93°C),286°F(141 °C), 360 °F 6-ENT'
(182 °C), and 500°F(260°C)8
Footnotes
'Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
'Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada.
5 cULus Listed as corrosion resistant.
6 Upright sprinklers Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E,Vol. 12. Conventional sprinklers accepted for
use,City of New York Department of Buildings, MEA Number 89-92-E,Vol. 3.
7 Meets New York City requirements,effective July 1, 2008.
8 Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above
300°F (149°C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F(149 °C),
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
'Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems
only.Exception:4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.
_ 10The sprinkler orifice is bushed.
"Sprinklers 10168 and 10172 are available on special order.
12((Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40137, 0786-CPD-40142, 0786-CPD-40177, 0786-CPD-40182, 0832-
CPD-2001,and 0832-CPD-2003.
1' O MED Certified, Standard EN 12259-1,EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
14 The 1/2"NPT Large Orifice Sprinkler is Listed and Approved for retrofit only.
•
I
June 28, 2013 Sprinkler 11u
MICROMATIC®AND
TECHNICAL DATA MicromaticHP® STANDARD
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
• Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
PESIGN CRITERIA- UL
(Also refer to Approval Chart 1 on page 11t)
cULus Listing Requirements:
Micromatic®and MicromaticHP®Standard Response Upright and Conventional Sprinklers are cULus Listed as indicated in the Approval Chart 1 for
installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers,or old style(conventional)sprinklers.
• Designed for use in Light, Ordinary,and Extra Hazard occupancies. (Small orifice sprinklers are limited to Light Hazard where allowed by the
installation standards being applied, with hydraulically calculated wet systems only.Exception:4.2K sprinklers may be installed on hydraulically
calculated dry pipe systems where piping is corrosion resistant or internally galvanized.)
• The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.For conventional sprinklers,refer to
the installation guidelines for old style(conventional)sprinklers.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor-
dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS
or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable.
Sprinkler must
13577W/Bow must tl rl
be used for
installing wax
coated sprinklers
Step 1: Carefully slide 1
the wrench sideways �-
around the deflector,
ensuring engagement .. .�. G
with the sprinkler =-',l /°_1
wrench flats. I,
[ II N:11 Hill
Wax Coated /
Upright Sprinkler
I I 1
mokA 1/2' ratchet is required Step 2: Carefully press the wrench
(not available from Viking). downward and ensure engagement
with the sprinkler wrench flats.
Figure 2: Wrench 13577W/B for Wax Coated Sprinklers
c
i
Sprinkler 11v
June 28, 2013
Nii(iNott MICROMATIC®AND
TECHNICAL DATA MicromaticHp® STANDARD
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
- Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
Approval Chart 2 (FM)
Micromatic�Standard Response Upright Sprinklers (---�Finish atom..` KEy- _.--
i Fnish
Maximum 1.7.6 PSI{12 bar) p
A X4--Esculrheon(Ifapplicable)
Base Part I SIN Thread Size Nominal K-Factor Overall Length
Number' J I I FM Approvals'
NPT BSP U.S. I metric2 I Inches I mm (Refer also to Design Criteria below.)
Standard Orifice
12986 VK100 1/2" 15 mm 5.6 80.6 2-3/16 56
10233 VK145 1/2" 15 mm 5.6 80.6 2-3/16 56 Al, C5, E6, E H7
10174 VK145 -- Al, D2, E6,, F F1
15 mm 5.6 80.6 2-3/16 56 Al, D2, Fl
12993 VK100 15 mm 5.6 80.6 2-3/16 56 -
A1, D2, F1, G4, H7
Large Orifice
10220' VK200 1/2" 15 mm 8.0 115.2 2-3/8 60
10141 VK200 3/4" 20 mm 8.0 115.2 2-5/16 59 B1, D5, Fl, H7
B1, D5, Fl, H7
10169 VK200 —
-
20 mm 8.0 115.2 2-5/16 59 131, D5, Fl, H7
Small Orifice
102186
101926 + VK001 1-- I D3, D5
15 mm 2.8 40.3 2-3/16 56
D3, D5
Approved Temperature Ratings
A- 135°F(57°C), 155°F(68°C), 175°F(79°C),200°F(93°C),212°F(100°C), Approved Finishes
286°F(141 °C), and 360°F(182°C) 1 -Brass,Chrome, White Polyester, and Black Polyester
B- 135°F(57°C), 155°F(68°C), 175°F(79°C),200°F(93°C),286°F(141 °C), 2-White Polyester and Wax-Coated Brass(corrosion resistant)
and 360°F(182°C) 3-Brass and Chrome
C-135°F(57°C), 155°F(68°C), 175°F(79°C),200°F(93°C),and 212°F(100°C) 4-Wax-Coated Brass and Wax over Polyester
D- 135°F(57°C), 155°F(68 °C), 175°F(79°C),and 200°F °
93 C
( ) 5 Wax-Coated Brass(corrosion resistant)
E-286°F(141 °C) 6 - 200 °F (93 °C) High-Temperature Wax Coating
F-500°F(260°C)5 g (corrosion
resistant); maximum ambient temperature allowed at ceiling
G- 155°F(68°C) = 150°F(65°C)
H-155°F(68°C), 175°F(79°C),200°F(93°C),286 °F(141 °C), 360 °F(182 °C), 7-ENT'
500°F(260`C)5
Footnotes
'Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
° FM Approved as standard response Non-Storage upright sprinklers. For specific application and installation requirements, reference the latest ap-
plicable FM Loss Prevention Data Sheets(including Data Sheet 2-0).
'Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above
300 °F (149°C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F(149 °C),
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
'The sprinkler orifice is bushed.
'The 1/2"NPT Large Orifice Sprinkler is Listed and Approved for retrofit only
8 FM approved as corrosion resistant.
DESIGN CRITERIA- FM
(Also refer to Approval Chart2 above.)
FM Aoaroval Reauirements; —_
The sprinklers indicated in Approval Chart 2 are FM Approved as standard response Non-Storage upright sprinklers as indicated in the FM Approval
Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet
2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design,
ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling.
NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT:Always refer to Bulletin Form No. F_091699-Care and Handling of Sprinklers.Also refer to page SR1-3 for gen-
eral care, installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition
of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations,
and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_080106 Replaces page 11q-v, dated June 11, 2013.
(ENT finish is now approved as corrosion resistant.)
October 31, 2014
To: Viking Automatic Sprinkler Co.
3245 NW Front Ave
Portland, OR 97210
Attn: Derek Wittkopf
Project: Les Schwab Tire Center
9385 SW Greenburg Rd
Tigard, OR 97223
Subject: Warehouse Sprinkler Design Criteria
Ref: IBC 2012 edition
IFC 2012 edition
NFPA 13 2013 edition
NFPA 231D, 1998 edition
Viking Drawing FP-2, Roof Plan dated 3/29/2000—job no. OT-9607
Viking Drawing FP-3,Section&Rack Plan dated 3/29/2000—job no. OT-1128
Derek,
This is in regards to the above referenced project. Specifically,confirmation that the design criteria for
the addition of sprinklers below catwalks in the west center warehouse complies with code.
• The facility is an existing Les Schwab Tire Center with an existing dry pipe sprinkler system.The original
installation in 2000 referenced the 1998 edition of 231D as the standard for warehouse protection. The
ceiling sprinklers in the west center warehouse were designed per 231D with provision for future
racking and catwalks.Subsequently,the sprinkler design criteria for the protection of tire storage with
standard spray sprinklers has been minimally revised.Accordingly, as the west center warehouse is
similar to the adjacent, previously completed,warehouses, matching the new under catwalk sprinkler
layout and pipe sizing to the existing is legitimate and acceptable. Corroboration is as follows:
IBC(2012),sub-section 413.1 General,states;High-piled stock or rack storage in any occupancy group
shall comply with the International Fire Code.
IFC (2012),sub-section 3401.1 Scope,states: Tire rebuilding plants, tire storage and tire byproduct
facilities shall comply with this chapter, other applicable requirements of this code and NFPA 13. Tire
storage in buildings shall also comply with Chapter 32.
IFC(2012),sub-section 3208.2 Fire Protection, states, in part; Where automatic sprinklers are required,
an approved automatic sprinkler system shall be installed throughout the building or to 1-hour fire
barriers. The design and installation of the automatic sprinkler system shall be in accordance with
Section 903.3.1.1 and the IBC.
IFC(2012),sub-section 903.3.1.1 NFPA 13 sprinkler systems,states; Where the provisions of this code
require that a building or portion thereof be equipped throughout with an automatic sprinkler system in
accordance with this section,sprinklers shall be installed throughout in accordance with NFPA 13 except
• as provided in Section 903.3.1.1.1.
NFPA 231D(1998)Storage of Rubber Tires,sub-section 4-1.2,states, in part;Sprinkler discharge and
area of application shall be in accordance with Table 4-1.2(a)for%in., 17/32 in., 5/8 in., and.70 in.
sprinklers. Table 4-1.2(a), Piling Method (5), Piling Height over 12 to 20 ft, includes the following criteria
selection: 0.40 gpm/ft2 plus one level in-rack sprinklers over a 3000 ft2 area of application.
NFPA 13 (2013)Standard for the Installation of Sprinkler Systems,sub-section 18.4 Ceiling Systems,
states, in part;Sprinkler discharge and area of application shall be in accordance with one of the
following:(1) Table 18.4(a)or Table 18.4(b)for standard spray sprinklers. Table 18.4(a), Piling Method
(8), Pile Height over 12 to 20 ft, includes the following criteria selection:0.40 gpm/ft2 plus one level in-
rack sprinklers over a 3000 ft2 area of application.
The original design criteria was 0.40 gpm/ft2 plus one level in-rack sprinklers over a 3000 ft2 area of
application.The area of application was reduced to a single 2500 ft2 warehouse by use of appropriately
rated full height walls.As stated,the sprinkler design criteria for standard spray sprinklers remains
unchanged subsequent to the original construction.So,again, matching the new under catwalk
sprinklers to the previously accepted spacing and pipe sizing arrangement is legitimate and acceptable.
If you have any questions or comments please call or email.
Respectfully,
Dan McLuen, PE
Engineer
Viking Automatic Sprinkler Co.
3434 First Ave S
Seattle, WA 98134
Office: 206.622.4656
Cell: 206.200.8827
dan.mcluen @vikingsprinkler.net