Report &p200g-00367q 50I Dant )1,d0-th City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 November 14, 2008 RE: TENANT IMPROVEMENT Project Information T I GARD Building Permit: BUP2008-00369 Construction Type: 2B Address: 7501 SW Dartmouth Rd. Occupancy Type: M Area: 95299 Sq. Ft. Stories: 1 Name: Winco Sprinkled: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition and the 2007 Oregon State Fire Code 1) Suspended ceiling to be installed as per ASCE 7 or Oregon State Interpretation. 2) All improvements made to the building shall be inspected prior to covering. 3) Make approved set of plans available for all inspections. 4) A total of 25% of the cost of the project shall go towards removing architectural barriers (accessibility). 5) All framing shall conform to accepted engineering standards. FIRE LIFE AND SAFETY / GENERAL The main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. Sec. 1008.1.8.3 All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. Sec. 1008.1.8 Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Sec. 1011.1 Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 '/4 hours of illumination in case of primary power loss. Sec. 1006.3 FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress illumination shall be provided with a second source of power in case of primary power loss. Amended Construction Documents: Work shall be installed in accordance with the approved construction documents, and any changes made during construction that are Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard-or.gov • TTY Relay: 503.684.2772 not in compliance with the approved construction documents shall be resubmitted for approval as an amended set of construction documents. OSSC 106.4 Work Commencing Before Permit Issuance: Any person who commences any work on a building or structure before obtaining the necessary permits shall be subject to an investigation fee equal to the permit fee that shall be in addition to the required permit fees. OSSC 108.4 Inspections: Construction or work for which a permit is required shall be subject to inspection by the building official and such construction or work shall remain accessible and exposed for inspection purposes until approved. Approval as a result of an inspection shall not be construed to be an approval of a violation of the provisions of this code or of other laws or ordinances of the jurisdiction. Inspections presuming to give authority to violate or cancel the provisions of this code or of other laws or ordinances of the jurisdiction shall not be valid. OSSC 109.1 Approval Required: Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the building official. The building official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the building official. OSSC 109.6 Use and Occupancy: No building or structure shall be used or occupied, and no change in the existing character, use or occupancy classification of a building or structure or portion thereof shall be made until the building official has issued a certificate of occupancy for such change in character, use or occupancy, therefore, as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. OSSC 110.1 American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Respectfully, Dan Nelson Senior Plans Examiner (503) 718-2436 dann @tigard-or.gov • MICHAEL K. BROWN Registered Professional Structural Engineer ce\o" In Partners With 4Vy— Structural Engineers I- d CCIRE N(lv ��` �@��IA` Elder Street, Suite 100 Ay `' Ce `v Boise, Idaho 83705 ENGINEERING CP 1 w` ,ZAN1 Ph. (208) 386-9170 � � Fax (208) 386-9076 ����� www.core-engineering.net STRUCTURAL DESIGN CALCULATIONS FOR WINCO FOODS STORE NO. 23 7500 DARTMOUTH RD TIGARD, OR CORE ENGR JOB # B08-664 DESIGN INFORMATION: USED 2006 IBC,ALLOWABLE STRESS DESIGN MEZZANINE: -OFFICE DEAD: 70 PSF -OFFICE LIVE: 50 PSF -OFFICE PARTITION: 20 PSF SEISMIC DESIGN CATEGORY: D SEISMIC PARAMETERS: -Ss: 94.4% RUG7Uq 34.0% -SDS: tt PROF q� 70.6% �G N 4 39.0% 9 cF,OREGON cv �_ 102 fit-47NGS\--E,ktb EXPIRATION WinCo—Tigard, OR Conterminous 48 States 2006 International Building Code Zip Code= 97223 Spectral Response Accelerations Ss and S1 Ss and S1 = Mapped Spectral Acceleration Values Site Class B - Fa= 1.0 ,Fv= 1.0 Data are based on a 0.05 deg grid spacing Period Centroid Sa (sec) (g) 0.2 0.944 (Ss, Site Class D) 1.0 0.340 (51, Site Class D) Period Maximum Sa (sec) (g) 0.2 0.971 (Ss, Site Class D) 1.0 0.347 (S1, Site Class D) Period Minimum Sa (sec) (g) 0.2 0.907 (Ss, Site Class D) 1.0 0.334 (S1, Site Class D) Conterminous 48 States 2006 International Building Code Zip Code = 97223 Spectral Response Accelerations SMs and SM1 SMs=FaSs and SM1 = FvS1 Site Class D - Fa= 1.122 ,Fv= 1.721 Period Sa (sec) (g) 0.2 1.059 (SMs, Site Class D) 1.0 0.584 (SM1, Site Class D) Conterminous 48 States 2006 International Building Code Zip Code = 97223 SDs = 2/3 x SMs and SD1 =2/3 x SM1 Site Class D - Fa= 1.122 ,Fv= 1.721 Period Sa (sec) (g) 0.2 0.706 (SDs, Site Class D) 1.0 0.390 (SD1, Site Class D) \I *... / CORE . ENGINEERING 3501 West Elder Street,Suite 100 Boise,Idaho 83705 Ph.208 386-9170-Fax 208 386-9076 Structural Engineers www.core-engineering.net ' JOB NAME /(-, / ; JOB NO. z / BY DATE ',/'j:;/'-'i` SHEET OF ■ 1, . • '\j 4- e'.° tzl •C' . ...' ,-, ,.._,., - 72/1- ..'W,.. .ti■1 0 ' '' i - 7 •'q ( 01,7e..,. L'3' D.-7r(:. ■+I t ' r . Q , .i . i .t c''-` i ) a....--- ( „ii-o; / ,..r- i t/ .4.... ) , /I/ .:..// r i J.„ r.i .. - ,. - _ -, , .) 5) ,. , /0 1.)•- i Cf.....4. e J.\) .) nee ) S-'(1 f I,'121 0,i ...; -- .6:'C)iff • 2 ,- 1-' --- --;o. i' 42- '----.''' PAT 9 c.-' —1- ■.: .:, - (—CA-Ii .., - /6. -Ci ;' ., ._ • .. , 7. ,I ---— ), -.5::' '14 -:\I ` g' ' ---,'( )) —; (r ,.' 1/6 i..._ - ij ...) ) ip i-) ) .... .14,, ., ... ... .,-) ./. ,,'.. P-(../,---. ..." '`,7/) • -)\‘ " .. ...)..-, . , . ..\ \ - ' 2/ IC (tie; fi/Ar, 7 fe.,1, i/.,-,/,/ , -.., :-) ......,e6r- ii, ,f..,, 6. -• ,,,.....I ,..z_ ,, •, _• I. - re'l Title: Job# Dsgnr: Date: 10:28AM, 15 JUL 08 • Description: Scope: Rev: 580002 j User:KW-0 05725.Ver5.8.0,I-Dec.2003 Rigid Diaphragm Torsional Analysis Page 1 L(c)1983-2003 ENERCALC Engineering Software tigard calcs.ecw:Calculations Description Original Forces to Interior Masonry Shear walls General Information 1 Y-Y Axis Shear 67.46 k Min.X Axis Ecc 5.00 % X Axis Center of Mass 71.15 ft X-X Axis Shear 62.40 k Min.Y Axis Ecc 5.00 % Y Axis Center of Mass 10.93 ft ...Shears are applied on each axis separately Max X Dimension 141.00 ft Max Y Dimension 27.75 ft Wall Data il Label Thickness Length Height Wall Xcg Wall Ycg Wall Angle Wall End E in ft ft ft ft deg CCW Fixity 1 7.625 27.750 10.670 12.250 13.875 90.0 Fix-Pin 1.0 2 7.625 27.750 10.670 51.083 13.875 90.0 Fix-Pin 1.0 3 7.625 27.750 10.670 56.083 13.875 90.0 Fix-Pin 1.0 4 7.625 27.720 10.670 114.083 13.875 90.0 Fix-Pin 1.0 5 7.625 27.750 10.670 141.000 13.875 90.0 Fix-Pin 1.0 6 7.625 141.000 10.670 70.500 0.000 0.0 Fix-Fix 1.0 Calculated Wall Forces Load Location for Maximum Forces Direct Shears k Torsional Shears k Final Max. 1 Label Wall Shear X ft Y Length Thick Length Thick k 1 -10.738 0.000 13.342 0.000 4.217 -0.003 17.559 2 -10.738 0.000 13.342 0.000 1.600 -0.003 14.942 3 -10.738 0.000 13.342 0.000 1.264 -0.003 14.606 4 3.362 0.000 13.322 0.000 0.827 0.001 14.149 5 3.362 0.000 13.342 0.000 1.395 0.001 14.737 6 0.000 12.286 -62.257 0.000 0.014 0.018 -62.257 ` Summary X Distance to Center of Rigidity 74.838 ft Controlling Eccentricities&Forces from Applied Y-Y Shear Y Distance to Center of Rigidity 0.032 ft Xcm+(Min%MaxX)-X-cr = 3.362 ft Torsion= 226.79 k-ft Xcm-(Min%*MaxX)-X-cr = -10.738 ft Torsion= -724.40 k-ft X Accidental Eccentricity 7.050 ft Controlling Eccentricities&Forces from Applied X-X Shear Y Accidental Eccentricity 1.388 ft Ycm+(Min%*MaxY)-Y-cr = 12.286 ft Torsion= 766.62 k-ft Ycm-(Min%*MaxY)-Y-cr = 9.511 ft Torsion= 593.46 k-ft 1)1 Title: Job# Dsgnr: Date: 10:28AM, 15 JUL 08 • Description : Scope: Rev: 580002 User:KW-o605725•Vet 5.8.0.1-oeo-2003 Rigid Diaphragm Torsional Analysis Page 2 (01983-2003 EPERCALC Engineering Software tigard cales.ecw:Calculations Description Original Forces to Interior Masonry Shear walls Sketch&Diagram 1) 2 3) •) 5) Wall:1 at[12.3,13.9 WR 3.9 Wall: at 1U.1,13.9) Wall:S nt(1N.0,13.9) • L=2T.8,T=1.3,Ht=1t�.T L= 227 i L=2T.T,To1.3,Htv10.T 1a2T.9,T=1.3,Htc10.T T P1.3 S.P11.1T (6) • Title: Job# Dsgnr: Date: 10:43AM, 15 JUL 08 • Description: Scope: Raw: 580002 oser:KW-0055N5.Ver CE 0 Rigid Diaphragm Torsional Analysis Page 1 () ngineeri g Software tigard calcs.ecw:Calculations Description Forces to Interior Masonry Shear walls w/new opening General Information -- - - Y ill -Y Axis Shear 67.46 k Min.X Axis Ecc 5.00 % X Axis Center of Mass 71.78 ft X-X Axis Shear 62.40 k Min.Y Axis Ecc 5.00 % Y Axis Center of Mass 10.80 ft ...Shears are applied on each axis separately Max X Dimension 141.00 ft Max Y Dimension 27.75 ft Wall Data Label Thickness Length Height Wall Xcg Wall Ycg Wall Angle Wall End E in ft ft ft ft deg CCW Fixity -- - - J 1 7.625 17.750 10.670 12.250 8.875 90.0 Fix-Pin 1.0 2 7.625 27.750 10.670 51.083 13.875 90.0 Fix-Pin 1.0 3 7.625 27.750 10.670 56.083 13.875 90.0 Fix-Pin 1.0 4 7.625 27.720 10.670 114.083 13.875 90.0 Fix-Pin 1.0 5 7.625 27.750 10.670 141.000 13.875 90.0 Fix-Pin 1.0 6 7.625 141.000 10.670 70.500 0.000 0.0 Fix-Fix 1.0 7 7.625 6.830 10.670 12.250 24.330 90.0 Fix-Pin 1.0 Calculated Wall Forces Load Location for Maximum Forces Direct Shears k Torsional Shears k Final Max. Label Wall Shear X ft Y Length Thick Length Thick k 1 -15.925 0.000 7.377 0.000 4.172 -0.002 11.549 J 2 -15.925 0.000 14.582 0.000 3.565 -0.005 18.147 3 -15.925 0.000 14.582 0.000 2.962 -0.005 17.544 4 -15.925 0.000 14.560 0.000 -4.024 -0.005 14.560 5 -15.925 0.000 14.582 0.000 -7.274 -0.005 14.582 - 6 0.000 12.157 -62.260 0.000 0.016 0.050 -62.260 7 -15.925 0.000 0.935 0.000 0.529 -0.002 1.464 1 Summary X Distance to Center of Rigidity 80.655 ft Controlling Eccentricities&Forces from Applied Y-Y Shear Y Distance to Center of Rigidity 0.031 ft Xcm+(Min%*MaxX)-X-cr = -1.825 ft Torsion= -123.10 k-ft Xcm-(Min%*MaxX)-X-cr = -15.925 ft Torsion= -1,074.29 k-ft X Accidental Eccentricity 7.050 ft Controlling Eccentricities&Forces from Applied X-X Shear Y Accidental Eccentricity 1.388 ft Ycm+(Min%*MaxY)-Y-cr = 12.157 ft Torsion= 758.57 k-ft Ycm-(Min%*MaxY)-Y-cr = 9.382 ft Torsion= 585.41 k-ft 01 Title: Job# Dsgnr: Date: 10:43AM, 15 JUL 08 • Description: Scope: LkRw: 680002 - -- -- --_-_------ _ User:KW-0806725,Ver 6.8.0,1-Deo-2003 Rigid Diaphragm Torsional Analysis Page 2 1 (0983-2003ENERCALC Engineering Sof tware tiger dcalcs.ecw:Calculations Description Forces to Interior Masonry Shear walls w/new opening 1 Sketch & Diagram II 17) 0 2 ) 4) 5) LW6u.L 87 Ti2.32403. 1) LWa7.:8t,T 3l 89 t.7 V jr 9 a aza w2: .Tt e 1.4 Ht313)T W 78,T-1e 1:Clin • 1.14 3,6 ao.7 (6) t'.sj ___A DRE . ENGINEERING 3501 West Elder Street,Suite 100 Boise,Idaho 83705 Ph.208 386-9170-Fax 208 386-9076 Structural Engineers www.core-engineering.net - JOB NAME ✓0;,1`O 7!" 7 JOB NO. BY ',t DATE SHEET OF i.--i„ ",'-±:` (,( Cyr. , ,�. ;)e, `,riC,_� /ekG( g , Tv GJq!Ij J r, 121, ,. • 1 _;, -(17)(2 x(3.83) - 1T, 7q,',5,' 01)-1tolk (.w oly,0•144, of F v = ,c, ,, ; /5-09 7 r✓ '?.)cb "7/1 ..--- 7,/ , o K ✓ r .;. .. / -. j C\ :y b{ K i„0 - 7/3 ( fi ' ,y ,F (,'V(),6 7') .4-`;Izc� �(I.Y,101+/*j(/2)( ) _ 73,a` ✓ 1r - /2Z 4" 123.2 . /22_ . 14,*4v/l 7 " /V, -7:c - b' 7 - , no u a�!'ell I�r�f. 44/l r2si '- 4,,,j/ 3 y 5 1 - J�,�t/7 � K v / 12(20(` .43\ • l-).(�sr < � --0 k. I/"". ,/< - ,1'f l:'-,k ��.-F) /93.6 k' eT i . ry ely , A \ __A CORE . ENGINEERING 3501 West Elder Street,Suite 100 Boise,Idaho 83705 Ph.208 386-9170-Fax 208 386-9076 Structural Engineers www.core-engineering.net JOB NAME -t i 0 JOB NO. -7: BY Ci---- DATE rr SHEET OF t- a11 ' 1 10a a r. `Ca ., to , = 77,,,,, , ,-, (nJ c ,-,.,CI nt. (,MR Loo - L --:?" f p: CI yc,. ) cr /D:! -n = C lii0 -'JV:,4 '" r'j-_ ,t -c. 1 • =l c o Mr�t , 6n(l1cl SNr'`.:,+ti>,t'(. rUcs.C� DY\ �0-+11:7 5� c+i + .r Fn 7 0'C`l 7.U6, • 5p17 �- Z)A. ?` / I tyrkx - z 5 i fi,�,� 156# c'` e 71Z,, J Y z x 31 I �- ��.`/� /i,3 / r� f/Z , �- 5' YD/�� ALA /G?- = z o vo -te - o% e--------- .i a:6176/ , t (_ 4) I CORE _dA .,;„ ENGINEERING 3501 West Elder Street,Suite 100 Boise,Idaho 83705 Ph.208 386-9170-Fax 208 386-9076 Structural Engineers www.core-engineering.net • JOB NAME i r/C7ct"L'\• JOB NO. /30CI—(2671-/ BY DATE SHEET OF �\\ �Ohes C.) cc(F %y &,--77-7✓ is -4,—c..r f 2 c, L . 3O 'f 3t 7- ' -. 1.--„, I 1 f 2' IC' nkr - 7 ' 5 ri V 11 - f),(,/– r)' ///7 ,-- 7 - - 'r l `1. C.) �ZC:)Y l — l L 7.11/2( • e ( ,i 5X X1 w / //>• p1f 1