Report iLC 20/3- Oo/7 7
-7 7 Oa 3)or-t-mo0+11
Portland General Electric Company
11/19/12 /PGE/
N /
CONTACT: Eric Jeter- Pacland Eng.
PHONE: (503)659-9500
CUSTOMER NAME: Walmart Stores Inc. - Retail Outlet Store 1 1--
ADDRESS: 700 SW Dartmouth Street, Tigard, Or., 97223
770c,
i
SDPM/ENGR: Ralph N. Reisbeck, SDPM yy(' WR: 678995
PHONE: (503) 570-4409
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
TRANSFORMER DATA PAD MOUNT? YES
XFMR Impedance (%): 5.32 % 3-PH SUBMERSI YES
TRANSFORMER SIZE: 1500 KVA XFMR? NO
Secondary VOLTAGE (L to L): 480 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 170 Feet WIRE SIZE
Number of SECONDARY RUNS: 7 Run(s)of: 350 OX UG
Secondary WIRE Resistance R: 0.0600 Ohms/1000'
Secondary WIRE Reactance X: 0.0330 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 0 Feet WIRE SIZE
Number of Service RUNS: 7 Run(s)of: 350 OX UG M
Service WIRE Resistance R: 0.0600 Ohms/1000'
Service WIRE Reactance X: 0.0330 Ohms/1000'
MAXIMUM FAULT CURRENT*: 28,179 Amps 11L71/YIftrE"
*Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating
Based on a panel size of 1600 .. f
To Print This Page: "Ctrl M" and choose "Print 3-Phase Data -