Loading...
Report COSCO FIRE PROTECTION, INC. PS 2013^cx I 11800 NE 95th STREET, SUITE 240 1O33 w 8("C 1pUr9 VANCOUVER,WA 98682 HYDRAULIC CALCULATIONS FOR RED LOBSTER #457 - TIGARD SERVICE AREA FILE NUMBER: PD5119-1 DATE: SEP 19, 2013 -DESIGN DATA- OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP I DENSITY: . 15 gpm/sq. ft . AREA OF APPLICATION: 900 sq. ft . COVERAGE PER SPRINKLER: 120 sq. ft . NUMBER OF SPRINKLERS CALCULATED: 14 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 280 . 6 gpm TOTAL WATER REQUIRED (including hose) : 530 . 6 gpm FLOW AND PRESSURE (Q BOR) : 280 . 6 gpm @ 63.0 psi . SPRINKLER ORIFICE SIZE: 1/2 inch/5 . 6 K NAME OF CONTRACTOR: HALEY CONSTRUCTION DESIGN/LAYOUT BY: JEFF HALSTEAD AUTHORITY HAVING JURISDICTION: CITY OF TIGARD CONTRACTOR CERTIFICATION NUMBER: 67508 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 380812802) HRS SYSTEMS, INC. J,41 7750. PEA 1 . 0 ,'( • • RE VR10 ��P`' Y 0 EXPIRATION DATE:12/31/14 1 • , SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 9/19/2013- HOME\PD 5113 RED LOBSTER #457 - TIGARD\CALCS\PD5119-1 .SDF ! JOB TITLE: Red Lobster #457 - Tigard WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS . @ PRESS . C4? DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 101 . 0 98 . 0 2293 .3 100 .8 530 . 6 69 . 0 , Required pressure is 31 . 8 psi (32%) less than available pressure. AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 530. 6 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 280 .6 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) HD1 8 . 0 K= 5 . 60 10 .3 18 . 0 HD2 8 . 0 K= 5 . 60 10 .6 18 .2 HD3 8 . 0 K= 5 . 60 11 .6 19 . 1 HD4 8 . 0 K= 5 . 60 11 .6 19. 1 HD5 8 . 0 K= 5 . 60 10.7 18 . 3 HD6 8 . 0 K= 5 . 60 11.7 19 . 2 HD7 8 . 0 K= 5 . 60 12 .3 19 . 6 HD8 8 . 0 K= 5 . 60 12 .6 19 . 9 HD9 8 . 0 K= 5 . 60 11 .9 19 .3 HD10 8 . 0 K= 5 . 60 15 . 8 22 . 2 HD11 8 . 0 K= 5 . 60 15 .5 22 . 1 HD12 8 . 0 K= 5 . 60 14 . 9 21 . 6 HD13 8 . 0 K= 5 . 60 15 .8 22 . 3 HD14 8 . 0 K= 5 . 60 15 .0 21 . 7 1 10 .0 - - - - 11 .5 - - - 2 10 . 0 - - - - 12 .1 - - - 3 10 . 0 - - - - 12 . 8 - - - 4 10 . 0 - - - - 13 .4 - - - 5 10 . 0 - - - - 12 .3 - - - 6 10 . 0 - - - - 13 .5 - - - 7 10 . 0 - - - - 13 .8 - - - 8 10 . 0 - - - - 14 .2 - - - 9 10 . 0 - - - - 14 .9 - - - 10 10 . 0 - - - - 14 .6 - - - _ 11 10 . 0 - - - - 13 .3 - - - 12 10 . 0 - - - - 14 .3 - - - 13 9 . 0 - - - - 18 .2 - - - . 14 9 . 0 - - - - 18 .4 - - - 15 9 . 0 - - - - 17 .2 - - - 16 10 . 0 - - - - 18 .0 - - - 17 10 . 0 - - - - 19 .3 - - - 18 10 . 0 - - - - 17 .0 - - - 19 10 . 0 - - - - 17 . 9 - - - T1 10 . 0 - - - - 14 . 9 - - - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 PATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-1 .SDF JOB TITLE: Red Lobster #457 - Tigard NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) T2 ' 10 . 0 - - - - 16 . 3 - - - T4 10 . 0 - - - - 22 . 0 - - - B1 9 . 0 - - - - 17 . 9 - - - B2 ' 9 . 0 - - - - 18 . 5 - - - B3 9 . 0 - - - - 19 . 8 - - - B4 9 . 0 - - - - 23 . 0 - - - M1 9 . 0 - - - - 35 . 9 - - - M2 9 . 0 - - - - 50 . 6 - - - RT 9 . 0 - - - - 54 . 5 - - - BF1 3 . 6 - - - - 57 . 9 - - - BF2 3 .6 - - - - 61 . 9 - - - RB 1 . 0 - - - - 63 . 0 - - - SOURCE 0 . 0 SOURCE 69 . 0 280 . 6 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-1.SDF ` JOB TITLE: Red Lobster #457 - Tigard PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. _ NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -18 . 0 1 .049 PL 17 . 00 PF 2 . 0 . HD1 8 . 0 5 . 6 10 . 3 18 . 0 6 . 7 120 FTG E PE -0 . 9 1 10 . 0 0 . 0 11 . 5 0 . 0 0.107 TL 19 . 00 PV Pipe: 2 -18 . 0 1 . 049 PL 6 . 00 PF 0 . 6 1 10 . 0 0 . 0 11 . 5 0 . 0 6 . 7 120 FTG ---- PE 0. 0 2 10 . 0 0 . 0 12 . 1 0 . 0 0 . 107 TL 6 . 00 PV Pipe: 3 -18 .2 1 . 049 PL 17 . 00 PF 2 .4 HD2 8 . 0 5 . 6 10 . 6 18 . 2 6 . 8 120 FTG T PE -0 . 9 2 10 . 0 0 . 0 12 . 1 0 . 0 0 .110 TL 22 . 00 PV Pipe: 4 -36 .2 1.380 PL 6 . 00 PF 0 . 6 2 10 . 0 0 . 0 12 . 1 0 . 0 7 . 8 120 FTG ---- PE 0 . 0 3 10 . 0 0 . 0 12 . 8 0 . 0 0 . 103 TL 6 . 00 PV Pipe: 5 -19 . 1 1 . 049 PL 17 . 00 PF 2 . 0 HD3 8 . 0 5 . 6 11 . 6 19 . 1 7 . 1 120 FTG ---- PE -0 . 9 3 10 . 0 0 . 0 12 . 8 0 . 0 0 . 119 TL 17 . 00 PV Pipe : 6 -55 .3 1 .380 PL 3 . 75 PF 2 . 2 3 10 . 0 0 . 0 12 . 8 0 . 0 11 . 9 120 FTG T PE 0 . 0 T1 10 . 0 0 . 0 14 . 9 0 . 0 0 .225 TL 9 . 75 PV Pipe: 7 37 .4 1 .380 PL 8 .25 PF 1 . 6 T1 10 . 0 0 . 0 14 . 9 0 . 0 8 . 0 120 FTG T PE 0 . 0 4 10 . 0 0 . 0 13 .4 0 . 0 0 . 109 TL 14 . 25 PV Pipe: 8 -19 . 1 1 . 049 PL 17 . 00 PF 2 . 6 HD4 8 . 0 5 . 6 11 . 6 19 . 1 7 . 1 120 FTG T PE -0 . 9 4 10 . 0 0 . 0 13 .4 0 . 0 0 .119 TL 22 . 00 PV Pipe: 9 18 . 3 1 . 049 PL 10 . 00 PF 1 . 1 4 10 . 0 0 . 0 13 .4 0 . 0 6 . 8 120 FTG ---- PE 0 . 0 5 10 . 0 0 . 0 12 . 3 0 . 0 0 . 111 TL 10 . 00 PV Pipe: 10 -18 .3 1 . 049 PL 17 . 00 PF 2 .4 HD5 8 . 0 5 . 6 10 . 7 18 . 3 6 . 8 120 FTG T PE -0 . 9 5 10 . 0 0 . 0 12 . 3 0 . 0 0 .111 TL 22 . 00 PV Pipe: 11 -92 . 7 1 . 610 PL 1 . 00 PF 2 . 5 T1 10 . 0 0 . 0 14 . 9 0 . 0 14 . 6 120 FTG T PE 0 . 4 _ B1 9 . 0 0 . 0 17 . 9 0 . 0 0 .276 TL 9 . 00 PV Pipe : 12 -19 . 2 1 . 049 PL 17 . 00 PF 2 . 6 . HD6 8 . 0 5 . 6 11 . 7 19 .2 7 . 1 120 FTG T PE -0 . 9 6 10 . 0 0 . 0 13 . 5 0 . 0 0. 120 TL 22 . 00 PV Pipe: 13 -19 .2 1 . 049 PL 0 . 50 PF 0 . 3 6 10 . 0 0 . 0 13 . 5 0 . 0 7 . 1 120 FTG E PE 0 . 0 7 10 . 0 0 . 0 13 . 8 0 . 0 0 . 120 TL 2 . 50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 ,DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-1 .SDF JOB TITLE: Red Lobster #457 - Tigard PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) - Pipe: 14 -19 .2 1 . 049 PL 9 . 00 PF 1 . 1 7 10 . 0 0 . 0 13 . 8 0 . 0 7 . 1 120 FTG ---- PE 0 . 0 9 10 . 0 0 . 0 14 . 9 0 . 0 0 . 120 TL 9. 00 PV Pipe: 15 -19 . 6 1 . 049 PL 17 . 00 PF 2 . 8 HD7 8 . 0 5 .6 12 .3 19 . 6 7 . 3 120 FTG T PE -0 . 9 8 10 . 0 0 . 0 14 .2 0 . 0 0 . 126 TL 22 . 00 PV Pipe: 16 -19 . 6 1 . 049 PL 0 . 50 PF 0 .7 8 10 . 0 0 . 0 14 .2 0 . 0 7 . 3 120 FTG T PE 0 . 0 9 10 . 0 0 . 0 14 . 9 0 . 0 0 . 126 TL 5 . 50 PV Pipe: 17 -38 . 8 1 . 380 PL 5 . 75 PF 1 .4 9 10 . 0 0 . 0 14 . 9 0 . 0 8 . 3 120 FTG T PE 0 . 0 T2 10 . 0 0 . 0 16 . 3 0 . 0 0 . 117 TL 11 . 75 PV Pipe: 18 39 .2 1 . 380 PL 8 .25 PF 1 . 7 T2 10 . 0 0 . 0 16 .3 0 . 0 8 .4 120 FTG T PE 0 . 0 10 10 . 0 0 . 0 14 .6 0 . 0 0 . 119 TL 14 .25 PV Pipe: 19 -19 . 9 1 . 049 PL 17 . 00 PF 2 . 8 HD8 8 . 0 5 . 6 12 . 6 19 . 9 7 .4 120 FTG T PE -0 . 9 10 10 . 0 0 . 0 14 . 6 0 . 0 0 .129 TL 22 . 00 PV Pipe: 20 19 . 3 1 .380 PL 10 . 00 PF 0 . 3 10 10 . 0 0 . 0 14 . 6 0 . 0 4 . 1 120 FTG ---- PE 0 . 0 12 10 . 0 0 . 0 14 . 3 0 . 0 0 . 032 TL 10 . 00 PV Pipe: 21 -19 . 3 1 . 049 PL 17 . 00 PF 2 . 3 HD9 8 . 0 5 . 6 11 . 9 19 .3 7 . 2 120 FTG E PE -0 . 9 11 10 . 0 0 . 0 13 . 3 0 . 0 0 .122 TL 19 . 00 PV Pipe: 22 -19 .3 1 . 049 PL 2 . 50 PF 0 . 9 11 10 . 0 0 . 0 13 . 3 0 . 0 7 .2 120 FTG T PE 0 . 0 12 10 . 0 0 . 0 14 .3 0 . 0 0 . 122 TL 7 . 50 PV Pipe: 23 -78 . 0 1 .610 PL 1 . 00 PF 1 . 8 T2 10 . 0 0 . 0 16 . 3 0 . 0 12 .3 120 FTG T PE 0 .4 B2 9 . 0 0 . 0 18 . 5 0 . 0 0 .200 TL 9 . 00 PV Pipe: 24 -22 .2 1 . 049 PL 16 . 00 PF 2 . 8 HD10 8 . 0 5 . 6 15 . 8 22 .2 8 . 3 120 FTG E PE -0 .4 13 9 . 0 0 . 0 18 . 2 0 . 0 0 . 158 TL 18 . 00 PV Pipe : 25 -22 . 2 1 . 049 PL 5 . 50 PF 1 . 7 13 9 . 0 0 . 0 18 .2 0 .0 8 . 3 120 FTG T PE 0 . 0 B3 9 . 0 0 . 0 19 .8 0 . 0 0 . 158 TL 10 . 50 PV Pipe: 26 43 . 7 1 .380 PL 4 .25 PF 1 . 5 B3 9 . 0 0 . 0 19 . 8 0 . 0 9 .4 120 FTG T PE 0 . 0 14 9 . 0 0 . 0 18 .4 0 . 0 0 . 145 TL 10 . 25 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-1.SDF JOB TITLE: Red Lobster #457 - Tigard PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe : 27 -22 . 1 1 .049 PL 16 . 00 PF 3 .3 HD11 8 . 0 5 .6 15 . 5 22 . 1 8 .2 120 FTG T PE -0 .4 14 9 . 0 0 . 0 18 .4 0 . 0 0 . 156 TL 21 . 00 PV Pipe: 28 21 . 6 1.049 PL 8 . 00 PF 1 .2 14 9 . 0 0 . 0 18 .4 0 . 0 8 . 0 120 FTG ---- PE 0 . 0 15 9 . 0 0 . 0 17 . 2 0 . 0 0 . 150 TL 8 . 00 PV Pipe: 29 -21 . 6 1 .049 PL 16 . 00 PF 2 . 7 HD12 8 . 0 5 . 6 14 . 9 21 .6 8 . 0 120 FTG E PE -0 .4 15 9 . 0 0 . 0 17 .2 0 . 0 0 .150 TL 18 . 00 PV Pipe: 30 -21 . 7 1. 049 PL 17 . 00 PF 2 . 9 HD14 8 . 0 5 . 6 15 . 0 21 . 7 8 . 0 120 FTG E PE -0 . 9 18 10 . 0 0 . 0 17 . 0 0 . 0 0 . 151 TL 19 . 00 PV Pipe: 31 -21 . 7 1 .049 PL 2 . 50 PF 1 . 0 18 10 . 0 0 . 0 17 . 0 0 . 0 8 . 0 120 FTG 2E PE 0 . 0 19 10 . 0 0 . 0 17 . 9 0 . 0 0 . 151 TL 6 . 50 PV Pipe : 32 -21 . 7 1. 049 PL 9 . 00 PF 1 .4 19 10 . 0 0 . 0 17 . 9 0 . 0 8 . 0 120 FTG ---- PE 0 . 0 17 10 . 0 0 . 0 19 . 3 0 . 0 0 . 151 TL 9 . 00 PV Pipe : 33 -22 .3 1 .049 PL 17 . 00 PF 3 . 0 HD13 8 . 0 5 . 6 15 . 8 22 . 3 8 .3 120 FTG E PE -0 . 9 16 10 . 0 0 . 0 18 . 0 0 . 0 0. 159 TL 19 . 00 PV Pipe: 34 -22 . 3 1 . 049 PL 3 . 50 PF 1. 3 16 10 . 0 0 . 0 18 . 0 0 . 0 8 . 3 120 FTG T PE 0 . 0 17 10 . 0 0 . 0 19 . 3 0 . 0 0 . 159 TL 8 . 50 PV Pipe : 35 -43 . 9 1. 380 PL 12 . 25 PF 2 . 7 17 10 . 0 0 . 0 19 .3 0 . 0 9 .4 120 FTG T PE 0 . 0 T4 10 . 0 0 . 0 22 . 0 0 . 0 0 . 147 TL 18 . 25 PV Pipe: 36 -43 . 9 1 .610 PL 1 . 00 PF 0 . 6 T4 10 . 0 0 . 0 22 . 0 0 . 0 6 . 9 120 FTG T PE 0 .4 B4 9 . 0 0 . 0 23 . 0 0 . 0 0. 069 TL 9 . 00 PV Pipe : 37 -92 . 7 2 . 157 PL 9 . 75 PF 0 . 6 B1 9 . 0 0 . 0 17 . 9 0 . 0 8 . 1 120 FTG - --- PE 0 . 0 B2 9 . 0 0 . 0 18 . 5 0 . 0 0 . 066 TL 9. 75 PV Pipe: 38 -170 . 8 2 . 157 PL 6 . 50 PF 1 . 3 B2 9 . 0 0 . 0 18 . 5 0 . 0 15 . 0 120 FTG ---- PE 0 . 0 B3 9 . 0 0 . 0 19 . 8 0 . 0 0 .205 TL 6 . 50 PV . Pipe : 39 -236 . 7 2 .157 PL 8 . 50 PF 3 . 2 B3 9 . 0 0 . 0 19 . 8 0 . 0 20 . 8 120 FTG ---- PE 0 . 0 B4 9 . 0 0 . 0 23 . 0 0 . 0 0 . 376 TL 8 . 50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 PATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-1 .SDF JOB TITLE: Red Lobster #457 - Tigard PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) - Pipe: 40 -280 . 6 2 . 157 PL 13 . 00 PF 12 . 9 B4 9 . 0 0 . 0 23 . 0 0 . 0 24 . 6 120 FTG T PE 0 . 0 M1 9 . 0 0 . 0 35 . 9 0 . 0 0 . 515 TL 25 . 00 PV Pipe: 41 -280 . 6 2 . 157 PL 16 . 58 PF 14 . 7 M1 9 . 0 0 . 0 35 . 9 0 . 0 24 . 6 120 FTG T PE 0 . 0 M2 9 . 0 0 . 0 50 .6 0 . 0 0 . 515 TL 28 . 58 PV Pipe: 42 -280 . 6 2 . 157 PL 1 .42 PF 3 . 8 M2 9.0 0 . 0 50 . 6 0 . 0 24 . 6 120 FTG E PE 0 . 0 RT 9. 0 0 . 0 54 . 5 0 . 0 0 . 515 TL 7 .42 PV Pipe: 43 -280 . 6 2 . 635 PL 5 .42 PF 1 . 1 RT 9 . 0 0 . 0 54 . 5 0 . 0 16 . 5 120 FTG ---- PE 2 . 3 BF1 3 . 6 0 .0 57 . 9 0 . 0 0 . 194 TL 5 .42 PV Pipe: 44 FIXED PRESSURE LOSS DEVICE BF2 3 . 6 0 . 0 61. 9 0 . 0 4 . 0 psi, 280 . 6 gpm BF1 3 . 6 0 . 0 57 . 9 0 . 0 Pipe : 45 -280 .6 2 .635 PL 0 .29 PF 0 . 1 BF2 3 . 6 0 . 0 61. 9 0 . 0 16 .5 120 FTG ---- PE 1 . 1 RB 1 . 0 0 . 0 63 . 0 0 . 0 0 . 194 TL 0 . 29 PV Pipe : 46 -280 . 6 4 .220 PL 253 .46 PF 5 . 5 RB 1 . 0 0 . 0 63 . 0 0 . 0 6 .4 140 FTG 3E2TG PE 0 .4 SOURCE 0 . 0 SRCE 69 . 0 (N/A) 0 . 015 TL 375 .46 PV • NOTES (HASS) : (1) Calculations were performed by the HASS 8 .4 computer program under license no. 380812802 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0 . 001 gpm and a maximum imbalance at any node of 0 . 067 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 24 . 6 ft/sec at pipe 42 . (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report . (5) Available pressure at source node SOURCE under full flow conditions is 100 . 75 psi compared to the minimum required pressure of 20 . 00 psi . SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE : 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-1.SDF ' JOB TITLE: Red Lobster #457 - Tigard (6) PIPE FITTINGS TABLE Pipe Table Name: COSCO.PIP PAGE: A MATERIAL: Sch40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v NPTee F 45e11 1 . 049 2 . 00 5 . 00 2 . 00 5 . 00 6 . 00 1 . 00 10 . 00 10 . 00 5 . 00 1 . 00 1 . 380 3 . 00 6 . 00 2 . 00 7 . 00 6 . 00 1. 00 10 . 00 10 . 00 6 . 00 1 . 00 1 . 610 4 . 00 8 . 00 2 . 00 9 . 00 6 . 00 1 . 00 10 . 00 10 . 00 8 . 00 2 . 00 PAGE : B MATERIAL: Sch10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v NPTee F 45e11 2 . 157 6 . 00 12 . 00 3 . 00 14 . 00 8 . 00 1 . 00 12 . 00 12 . 00 12 . 00 2 . 00 2 . 635 8 . 00 17 . 00 6 . 00 19 . 00 10 . 00 1. 00 14 . 00 14 . 00 17 . 00 3 . 00 PAGE: U MATERIAL: D-Iron HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVa BFV GateVa NPTee 45e11 F 4 .220 17 . 00 34 . 00 10 . 00 37 . 00 20 . 00 3 . 00 34 . 00 6 . 00 0 . 00 0 . 00 • b o W H [t] WATER SUPPLY ANALYSIS H 120.0 Static: 101.00 psi Resid: 98 .00 psi Flow: 2293 .3 gpm w LEGEND L H .. 10 1 Available pressure iv N 100.80 psi @ 530.6 gpm N a N w 1 2 Required pressure Cr 0 100.0 — 0 68.99 psi @ 530.6 gpm rmr X G A. Source Supply Curve - - C B. System Demand Curve nro A Yk H U A Ul Z U1 H G H r E 80.0 pzi H M m P • t7 m R 2 w r H E a W 3 s H x s 60.0 m U > R r E J H ( 40.0 H zy p > K s m 1 ci H / V] n r C) 20.0 U) / ro d U' H �o B ' H ro 0.0 — — — cW n U m "n -14 .7 I E I I 600 900 1200 1500 1800 2100 2400 2700 3000 FLOW (GPM) (Note: Dashed Lines indicate extrapolated values from Test Results) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-1 .SDF JOB TITLE : Red Lobster #457 - Tigard WATER SUPPLY CURVE 108+ 1 1 *\0\\\\\\\\\\\\\\\\\\\\ 99+ * <-98 . 0 psi @ 2293 gpm 1 Flow Test Point 1 1 90+ 1 1 1 81+ 1 1 1 P 72+ R 1 X E 1 S 1 S 63+ U 1 R 1 E 1 54+ ( 1 P 1 S I 45+ 1 1 1 36+ 1 1 1 27+ 1 1 1 18+ LEGEND 1 1 X = Required Water Supply 1 68 . 99 psi @ 530 . 6 gpm 9+ " 0 = Available Water Supply " 1 100 . 80 psi @ 530 . 6 gpm 1 0++-+---+----+ + + + + + + 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) 4 COSCO FIRE PROTECTION, INC. / 11800 NE 95th STREET, SUITE 240 VANCOUVER,WA 98682 HYDRAULIC CALCULATIONS FOR RED LOBSTER #457 - TIGARD SEATING AREA - UPRIGHTS FILE NUMBER: PD5119-2 DATE: SEP 19, 2013 -DESIGN DATA- OCCUPANCY CLASSIFICATION: LIGHT HAZARD DENSITY: . 10 gpm/sq. ft . AREA OF APPLICATION: 1020 sq. ft . COVERAGE PER SPRINKLER: 100 sq. ft . NUMBER OF SPRINKLERS CALCULATED: 11 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 171 . 2 gpm TOTAL WATER REQUIRED (including hose) : 271 . 2 gpm FLOW AND PRESSURE (Q BOR) : 171 . 2 gpm (4) 38.6 psi SPRINKLER ORIFICE SIZE: 1/2 inch/5 . 6 K NAME OF CONTRACTOR: HALEY CONSTRUCTION DESIGN/LAYOUT BY: JEFF HALSTEAD AUTHORITY HAVING JURISDICTION: CITY OF TIGARD CONTRACTOR CERTIFICATION NUMBER: 67508 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 380812802) HRS SYSTEMS, INC. -P 9 7750. PE , RE 0 v�,9N 10 ,LSO Q`' SPRY t 0,�F. EXPIRATION DATE:12/31/14 I A SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-2 .SDF JOB TITLE: Red Lobster #457 - Tigard WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS . @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 101 . 0 98 . 0 2293 . 3 100 .9 271 .2 41 .2 Required pressure is 59 . 7 psi (59%) less than available pressure. AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 271 .2 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 171 .2 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) HD15 15 .3 K= 5 .60 7 . 0 14 . 8 HD16 15 . 3 K= 5 . 60 8 . 0 15 . 9 HD17 15 . 3 K= 5 . 60 7 . 0 14 . 8 HD18 15 .3 K= 5 . 60 8 .0 15 . 9 HD19 15 .3 K= 5 . 60 7 . 0 14 .8 HD20 15 .3 K= 5 . 60 8 . 1 15 . 9 HD21 15 . 3 K= 5 . 60 7 .2 15. 0 HD22 15 . 3 K= 5 . 60 8 .2 16 . 1 HD23 15 .3 K= 5 . 60 7 .5 15 . 3 HD24 15 . 3 K= 5 . 60 8 . 6 16 .4 HD25 15 .3 K= 5 . 60 8 . 5 16 . 3 T5 15 .3 - - - - 8 .6 - - - T6 15 . 3 - - - - 8 .6 - - - T7 15 . 3 - - - - 8 .6 - - - T8 15 .3 - - - - 8 .8 - - - T9 15 . 3 - - - - 9. 1 - - - T10 15 . 3 - - - - 10 . 3 - - - B5 14 . 0 - - - - 9 . 7 - - - B6 14 . 0 - - - - 9 .7 - - - B7 14 . 0 - - - - 9 .7 - - - B8 14 . 0 - - - - 9 .9 - - - B9 14 . 0 - - - - 10 .3 - - - B10 14 . 0 - - - - 11 . 0 - - - M1 9 . 0 - - - - 23 .2 - - - M2 9 . 0 - - - - 29 . 1 - - - M3 14 . 0 - - - - 12 .8 - - - M4 14 . 0 - - - - 11 .9 - - - . M5 11 . 5 - - - - 11. 9 - - - M6 11 . 5 - - - - 11 . 0 - - - M7 11 . 5 - - - - 11 . 0 - - - M8 11 . 5 - - - - 11 . 8 - - - M9 24 . 8 - - - - 6 .8 - - - M10 14 . 0 - - - - 12 .0 - - - RT 9 . 0 - - - - 30 . 7 - - - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-2 .SDF JOB TITLE: Red Lobster #457 - Tigard NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) BF1 3 . 6 - - - - 33 .4 - - - BF2 3 . 6 - - - - 37 .4 - - - RB 1 . 0 - - - - 38 . 6 - - - SOURCE 0 . 0 SOURCE 41 .2 171 .2 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 , DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-2 .SDF l JOB TITLE: Red Lobster #457 - Tigard PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. _ NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -14 . 8 1 .049 PL 14 .17 PF 1 . 1 . HD15 15 . 3 5 . 6 7 . 0 14 . 8 5 . 5 120 FTG ---- PE 0 . 0 HD16 15 . 3 5 . 6 8 . 0 15 . 9 0 .075 TL 14 . 17 PV Pipe: 2 -30 . 7 1.380 PL 0 . 79 PF 0 . 5 HD16 15 .3 5 . 6 8 . 0 15 . 9 6 . 6 120 FTG T PE 0 . 0 T5 15 .3 0 . 0 8 . 6 0 . 0 0 . 076 TL 6 . 79 PV Pipe: 3 -30 . 7 1 .380 PL 1 .29 PF 0 . 6 T5 15 . 3 0 . 0 8 . 6 0 . 0 6 . 6 120 FTG T PE 0 . 6 B5 14 . 0 0 . 0 9 . 7 0 . 0 0 .076 TL 7 .29 PV Pipe: 4 -14 . 8 1 . 049 PL 14 . 17 PF 1 . 1 HD17 15 . 3 5 . 6 7 . 0 14 . 8 5 . 5 120 FTG ---- PE 0 . 0 HD18 15 . 3 5 . 6 8 . 0 15 . 9 0 . 075 TL 14 . 17 PV Pipe : 5 -30 . 7 1 .380 PL 0 . 79 PF 0 . 5 HD18 15 . 3 5 . 6 8 . 0 15 . 9 6 . 6 120 FTG T PE 0 . 0 T6 15 . 3 0 . 0 8 . 6 0 . 0 0. 076 TL 6 . 79 PV Pipe: 6 -30 . 7 1 .380 PL 1 . 29 PF 0 . 6 T6 15 . 3 0 . 0 8 . 6 0 . 0 6 . 6 120 FTG T PE 0 . 6 B6 14 . 0 0 . 0 9 . 7 0 . 0 0 . 076 TL 7 . 29 PV Pipe: 7 -14 . 8 1 . 049 PL 14 . 17 PF 1 . 1 HD19 15 . 3 5 . 6 7 . 0 14 . 8 5 . 5 120 FTG ---- PE 0 . 0 HD20 15 . 3 5 . 6 8 . 1 15 . 9 0 . 075 TL 14 . 17 PV Pipe: 8 -30 . 7 1 .380 PL 0 . 79 PF 0 . 5 HD20 15 . 3 5 . 6 8 . 1 15 . 9 6 . 6 120 FTG T PE 0 . 0 T7 15 . 3 0 . 0 8 . 6 0 . 0 0 . 076 TL 6 . 79 PV Pipe : 9 -30 . 7 1 .380 PL 1 .29 PF 0 . 6 T7 15 . 3 0 . 0 8 . 6 0 . 0 6 . 6 120 FTG T PE 0 . 6 B7 14 . 0 0 . 0 9 . 7 0 . 0 0 .076 TL 7 .29 PV Pipe: 10 -15 . 0 1 . 049 PL 14 . 17 PF 1 . 1 HD21 15 . 3 5 .6 7 . 2 15 . 0 5 . 6 120 FTG ---- PE 0 . 0 HD22 15 .3 5 .6 8 .2 16 . 1 0 . 076 TL 14 . 17 PV Pipe: 11 -31 . 0 1 . 380 PL 0 . 79 PF 0 . 5 HD22 15 . 3 5 . 6 8 .2 16 . 1 6 . 7 120 FTG T PE 0 . 0 T8 15 . 3 0 . 0 8 .8 0 . 0 0 . 077 TL 6 . 79 PV Pipe: 12 -31 . 0 1 .380 PL 1 . 29 PF 0 . 6 • T8 15 . 3 0 . 0 8 . 8 0 . 0 6 . 7 120 FTG T PE 0 . 6 B8 14 . 0 0 . 0 9 . 9 0 . 0 0 .077 TL 7 .29 PV Pipe : 13 -15 .3 1. 049 PL 14 . 17 PF 1 . 1 HD23 15 . 3 5 . 6 7 . 5 15 .3 5 . 7 120 FTG --- - PE 0 . 0 HD24 15 . 3 5 . 6 8 . 6 16 .4 0 . 079 TL 14 . 17 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 .DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-2 .SDF JOB TITLE: Red Lobster #457 - Tigard PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) - Pipe: 14 -31 . 7 1 . 380 PL 0 . 79 PF 0 . 5 HD24 15 . 3 5 . 6 8 .6 16 .4 6 . 8 120 FTG T PE 0 . 0 T9 15 .3 0 . 0 9 .1 0 . 0 0 . 080 TL 6 . 79 PV Pipe: 15 -31 . 7 1 .380 PL 1 . 29 PF 0 . 6 T9 15 . 3 0 . 0 9 . 1 0 . 0 6 . 8 120 FTG T PE 0 . 6 B9 14 . 0 0 . 0 10 .3 0 . 0 0 . 080 TL 7 . 29 PV Pipe: 16 -16 . 3 1 . 049 PL 14 . 96 PF 1 . 8 HD25 15 .3 5 . 6 8 . 5 16 . 3 6 . 1 120 FTG T PE 0 . 0 T10 15 .3 0 . 0 10 . 3 0 . 0 0 . 089 TL 19 . 96 PV Pipe: 17 -16 . 3 1 .380 PL 1 . 29 PF 0 . 2 T10 15 .3 0 . 0 10 .3 0 . 0 3 . 5 120 FTG T PE 0 . 6 B10 14 . 0 0 . 0 11 . 0 0 . 0 0 . 023 TL 7 .29 PV Pipe: 18 6 . 5 2 . 157 PL 6 . 12 PF 0 . 0 B5 14 . 0 0 . 0 9 . 7 0. 0 0 . 6 120 FTG ---- PE 0 . 0 B6 14 . 0 0 . 0 9 .7 0. 0 0 . 000 TL 6 . 12 PV Pipe: 19 -24 . 2 2 . 157 PL 7 . 00 PF 0 . 0 B6 14 . 0 0 . 0 9 . 7 0 . 0 2 . 1 120 FTG ---- PE 0 . 0 B7 14 . 0 0 . 0 9 . 7 0 . 0 0 . 006 TL 7 . 00 PV - Pipe: 20 -55 . 0 2 .157 PL 7 . 00 PF 0 . 2 B7 14 . 0 0 . 0 9 . 7 0 . 0 4 . 8 120 FTG ---- PE 0 . 0 B8 14 . 0 0 . 0 9 . 9 0 . 0 0 .025 TL 7 . 00 PV Pipe: 21 -86 . 0 2 .157 PL 7 . 00 PF 0 .4 B8 14 . 0 0 . 0 9 . 9 0 . 0 7 . 6 120 FTG ---- PE 0 . 0 B9 14 . 0 0 . 0 10 . 3 0 . 0 0 . 058 TL 7 . 00 PV Pipe: 22 -117 . 7 2 . 157 PL 7. 00 PF 0 . 7 B9 14 . 0 0 . 0 10 .3 0. 0 10 . 3 120 FTG ---- PE 0 . 0 B10 14 . 0 0 . 0 11 . 0 0. 0 0 . 103 TL 7 . 00 PV Pipe: 23 -134 . 1 2 . 157 PL 7 . 50 PF 1 . 0 B10 14 . 0 0 . 0 11 . 0 0 . 0 11 . 8 120 FTG ---- PE 0 . 0 M10 14 . 0 0 . 0 12 . 0 0 . 0 0 . 131 TL 7 . 50 PV Pipe: 24 -149 . 9 2 . 157 PL 4 . 79 PF 0 . 8 M10 14 . 0 0 . 0 12 . 0 0 . 0 13 . 2 120 FTG ---- PE 0 . 0 M3 14 . 0 0 . 0 12 . 8 0 . 0 0 . 161 TL 4 . 79 PV Pipe: 25 21 .3 1 . 682 PL 39 . 29 PF 0 . 9 M3 14 . 0 0 . 0 12 . 8 0 . 0 3 . 1 120 FTG 2T PE 0 . 0 M4 14 . 0 0 . 0 11 . 9 0 . 0 0 . 015 TL 59 .29 PV Pipe : 26 21 . 3 1 .682 PL 55 . 38 PF 1 . 1 M4 14 . 0 0 . 0 11 . 9 0 . 0 3 . 1 120 FTG 2ET PE 1 . 1 M5 11 . 5 0 . 0 11 . 9 0 . 0 0 . 015 TL 75 . 38 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-2 .SDF JOB TITLE: Red Lobster #457 - Tigard PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe : 27 21 . 3 1 .682 PL 39 . 29 PF 0 . 9 M5 11 .5 0 . 0 11 . 9 0 . 0 3 . 1 120 FTG 2T PE 0 . 0 M6 11 .5 0 . 0 11 . 0 0 . 0 0 .015 TL 59 .29 PV Pipe : 28 -15 . 9 2 . 157 PL 2 . 92 PF 0 . 0 M6 11 . 5 0 . 0 11 . 0 0 . 0 1 .4 120 FTG T PE 0 . 0 M7 11 . 5 0 . 0 11 . 0 0 . 0 0 . 003 TL 14 . 92 PV Pipe: 29 37 . 1 2 . 157 PL 8 . 96 PF 0 .3 M6 11 . 5 0 . 0 11. 0 0 . 0 3 . 3 120 FTG 2E PE -1.1 B5 14 . 0 0 . 0 9 . 7 0 . 0 0. 012 TL 20 . 96 PV Pipe: 30 -15 . 9 1 . 682 PL 48 .42 PF 0 . 8 M7 11 . 5 0 . 0 11 . 0 0 . 0 2 . 3 120 FTG 4E2T PE 0 . 0 M8 11 . 5 0 . 0 11 . 8 0 . 0 0 . 008 TL 88 .42 PV Pipe: 31 -15 . 9 1 . 682 PL 64 .33 PF 0 . 8 M8 11 . 5 0 . 0 11 . 8 0 . 0 2 .3 120 FTG 2E2T PE -5 . 8 M9 24 . 8 0 . 0 6 . 8 0 . 0 0 . 008 TL 94 . 33 PV Pipe : 32 -15 . 9 1 .682 PL 36 .42 PF 0 . 5 M9 24 . 8 0 . 0 6 . 8 0 . 0 2 . 3 120 FTG 2ET PE 4 . 7 M10 14 . 0 0 . 0 12 . 0 0 . 0 0 .008 TL 56 .42 PV Pipe: 33 -171 . 2 2 . 157 PL 28 . 17 PF 8 . 3 M3 14 . 0 0 . 0 12 . 8 0 . 0 15 . 0 120 FTG 2E PE 2 .2 M1 9 . 0 0 . 0 23 . 2 0 . 0 0 .206 TL 40 . 17 PV Pipe: 34 -171 .2 2 . 157 PL 16 . 58 PF 5 . 9 M1 9 . 0 0 . 0 23 . 2 0 . 0 15 . 0 120 FTG T PE 0 . 0 M2 9 . 0 0 . 0 29 . 1 0 . 0 0 .206 TL 28 . 58 PV Pipe : 35 -171 . 2 2 .157 PL 1 .42 PF 1 . 5 M2 9 . 0 0 . 0 29 . 1 0 . 0 15 . 0 120 FTG E PE 0 . 0 RT 9 . 0 0 . 0 30 . 7 0 . 0 0 .206 TL 7 .42 PV Pipe : 36 -171 . 2 2 .635 PL 5 .42 PF 0 .4 RT 9 . 0 0 . 0 30 . 7 0 . 0 10 . 1 120 FTG ---- PE 2 . 3 BF1 3 . 6 0 . 0 33 .4 0 . 0 0 . 078 TL 5 .42 PV Pipe : 37 FIXED PRESSURE LOSS DEVICE BF2 3 . 6 0 . 0 37 .4 0 . 0 4 . 0 psi, 171 .2 gpm BF1 3 . 6 0 . 0 33 .4 0 . 0 Pipe: 38 -171 . 2 2 . 635 PL 0 . 29 PF 0 . 0 BF2 3 . 6 0 . 0 37 .4 0 . 0 10 . 1 120 FTG ---- PE 1 . 1 RB 1 . 0 0 . 0 38 . 6 0 . 0 0 . 078 TL 0 . 29 PV Pipe : 39 -171 . 2 4 .220 PL 253 .46 PF 2 . 2 RB 1 . 0 0 . 0 38 . 6 0 . 0 3 . 9 140 FTG 3E2TG PE 0 . 4 SOURCE 0 . 0 SRCE 41 . 2 (N/A) 0 . 006 TL 375 .46 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 ;DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-2 .SDF JOB TITLE: Red Lobster #457 - Tigard NOTES (HASS) : (1) Calculations were performed by the HASS 8 .4 computer program under license no. 380812802 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0 . 002 gpm and a maximum imbalance at any node of 0 . 063 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 15 . 0 ft/sec at pipe 35 . (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report . (5) Available pressure at source node SOURCE under full flow conditions is 100 . 88 psi compared to the minimum required pressure of 20 . 00 psi . (6) PIPE FITTINGS TABLE Pipe Table Name: COSCO. PIP PAGE: A MATERIAL: Sch40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet •(in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v NPTee F 45e11 1 . 049 2 . 00 5 . 00 2 . 00 5 .00 6 . 00 1 . 00 10 . 00 10 . 00 5 . 00 1 . 00 1 . 380 3 . 00 6 . 00 2 . 00 7 . 00 6 . 00 1 . 00 10 . 00 10 . 00 6 . 00 1 . 00 PAGE: B MATERIAL: Sch10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v NPTee F 45ell ' 1 . 682 5 . 00 10 . 00 3 . 00 11 .00 8 . 00 1 . 00 12 . 00 12 . 00 10 . 00 2 . 00 . 2 . 157 6 . 00 12 . 00 3 . 00 14 .00 8 . 00 1 . 00 12 . 00 12 . 00 12 . 00 2 . 00 2 . 635 8 . 00 17 . 00 6 . 00 19 .00 10 . 00 1 . 00 14 . 00 14 . 00 17 . 00 3 . 00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-2 .SDF JOB TITLE: Red Lobster #457 - Tigard PAGE: U MATERIAL: D-Iron HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVa BFV GateVa NPTee 45e11 F 4 .220 17 . 00 34 . 00 10 . 00 37 . 00 20 . 00 3 . 00 34 . 00 6 . 00 0 . 00 0 . 00 o > w H M WATER SUPPLY ANALYSIS H •• Static: 101. 00 psi Resid: 98.00 psi Flow: 2293 .3 gpm H 120.0 r' LEGEND to H .. 1 \ Available pressure xi n� 100.94 psi @ 271.2 gpm • H r 100.0 1 2 Required pressure 41.22 psi @ 271.2 gpm Uri X G A. Source Supply Curve - - N U) B. System Demand Curve n d V A 1 H U P n Ul r G r r i0 t11 E 80.0 I ;v Ht+]• m P w 0 FC tq to R w r H n ot1 E Q. m s H x S 60.0 M• U U R mr E J H 2 f Z ( 40.0 H p > k s cn 1 0 H / U) n r n 20.0 m ro L7) u, r B r N ro 0.0 CnXt O m hn -14.7 600 900 1200 1500 1800 2100 2400 2700 3000 FLOW (GPM) (Note: Dashed Lines indicate extrapolated values from Test Results) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 • DATE: 9/19/2013 HOME\PD 5119 RED LOBSTER #457 - TIGARD\CALCS\PD5119-2 .SDF JOB TITLE: Red Lobster #457 - Tigard WATER SUPPLY CURVE 108+ 0\\\\\\\\\\\\\\\\\\\\\\ 99+ * <-98 . 0 psi @ 2293 gpm Flow Test Point 90+ 81+ P 72+ R E I S I S 63+ U R I E I 54+ ( I P S I I 45+ ) I X 36+ 27+ 18+ LEGEND " I X = Required Water Supply 41 .22 psi @ 271 . 2 gpm 9+ I 0 = Available Water Supply " 100 . 94 psi @ 271 .2 gpm 0++-+---+----+ + + + + + + 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) • S Z o t 3- Do■ ` S COSCO o3� svJ �recnbuo f •••..•• Fire Protection Fire Protection and Life Safety Specialists MATERIAL SUBMITTAL FOR Red Lobster #457 10330 SW Greenburg Road Tigard, Oregon 97223 COSCO Fire Protection Inc. Job # 24PD5119 2501 SE Columbia Way Suite 100 Vancouver,WA 98661 Phone:360-883-6383 Fax: 360-883-6390 Toll Free:800-983-6383 • Material Submittal Red Lobster #457 Tigard, Oregon Item Manufacturer Model Size Comments Sprinklers QR Upright Viking VK300 %"/5.6 K 155° F & 200° F, Brass QR Pendent Viking VK302 %"/5.6 K 155° F, Chrome QR Dry Pendent Viking VK176 1/2"/5.6 K 200° F & 286° F, Chrome Valves Double Check Ames C300BFG 2%7" With tampers, bypass Detector Assembly meter with TVWD sending unit TestanDrain AGF 1011 1/4" With pressure relief Pipe & Fittings . Grooved Pipe State Pipe &Supply Schedule 10 11/4" -6" Or equal Screwed Pipe State Pipe &Supply Schedule 40 1" - 2" Or equal Grooved Fittings Victaulic Varies 1 Y" -8" Or equal D.I. Threaded Fittings Smith Cooper Varies 1" - 2" Or equal Electrical Devices Flow Switch Potter VSR-2Y2 2%" Or equal Hangers Sidewinder for wood Speedy Products SWG 20 Vertical Sammy Speedy Products GST 20 Hanger Ring Afcon Fig. 300 1" - 6" Or equal Seismic Bracing In-line Clamp Tolco Fig. 4A EQ Ear Tolco Fig. 980 Fast Clamp Tolco Fig. 1000 January 22, 2010 Sprinkler 51a MICROFAST®AND _ luNG TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 - Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Microfast" and MicrofastHP`' Quick Response Upright and Conventional (Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several different finishes, temperature ratings, and K-Factors to �"� meet design requirements. The special Polyester and Teflon"' coatings can be used in decorative applications where colors are desired. In addi- tion, these coatings have been investigated for installation in corrosive atmos- pheres and are cULus listed as corrosion resistant as indicated in Approval , Chart 1. (Note: FM Global has no approval classification for Teflon`' and Polyester coatings as corrosion resistant.) • 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approved: Classes 2002 and 2020 NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984B-PDA VdS Approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020 LPC Approved: Ref. No. 096e/03, TE30401, and TE30872 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, and 0786-CPD-40171 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on pages 51c-d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 51e for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres- http://www.vikinggroupinc.com. sure(HP) sprinklers can be identified by locating "250" stamped on The Web site may include a more recent the deflector.All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page. maximum 175 psi (12 bar)wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: Refer to the Approval Charts *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06661B, 06766B, 07060, and 12281. Brass UNS-C84400 for all other sprinklers. Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 06661B and 12281. Copper UNS-C19500 for Sprinklers 06665B, 06764B, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Form No. F 080488 Replaces page 51a-e, dated April 25, 2008. (Updated for Sprinkler 14817. Added VdS to Sprinklers 06665B, 06764B, and 14817. Updated FM Approvals and split the Approval Charts to separate UL Listing requirements from FM Approval requirements. Changed the metric K-factor for K4.2 sprinklers to 57.) Sprinkler 51b January 22, 2010 MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Teflon'Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon`'Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order Microfasr and MicrofastHP®Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass =A, Chrome-Enloy"= F, White Polyester= M-/W, Black Polyester= M-/B, and Black Teflon'= N Temperature Suffix(°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK300 with a 1/2" thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 06661 BAB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000) Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern - to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast`'and MicrofastHP°'Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification _ Temperature Rating' Ceiling Temperature2 Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F(38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy', White Polyester, Black Polyester, and Black Teflon" Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon`' Footnotes • The sprinkler temperature rating is stamped on the deflector. Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. - Refer to specific installation standards. s The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e.These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment.For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only Note that the spring is exposed on sprinklers with Polyester and Teflon"' coatings. • January 22, 2010 Sprinkler 51c MICROFASP AND TECHNICAL DATA MicrofastHP® QUICK NIKING RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 - Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) Temperature KEY Microfast®and MicrofastHP'5Quick Response fir—Finish Upright and Conventional Sprinklers AIX4-Escutcheon(if applicable) Maximum 175 PSI(12 bar)WWP Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals' SIN (Refer also to Design Criteria on page 51d.) Number' NPT BSP U.S. metric2 Inches mm cULus4 NYC' VdS LPCB (E 0 Upright-Standard Orifice 06661B VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- -- -- -- 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- -- A3 A3 B3" B313 Conventional-Standard Orifice 06766B VK310 1/2" 15 mm 5.6 80.6 2-3/16 56 A3 A3 -- A3 _ B3" B3" Upright-Large Orifice 06665B VK350 3/4" -- 8.0 115.2 2-5/16 59 A2 A2 A3 A3 _ B3" -- 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2 A2 A3 A3 B311 -- 06764B VK350 1/2" 15 mm 8.0 115.2 2-5/16 59 A2 A2 _ A3 -- -- -- Conventional-Large Orifice 06768B VK354 3/4" 20 mm 8.0 115.2 2-5/16 59 A2 A3 - A3 B3" -- Upright-Small Orifice1' 0671781° VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 A2 A2 -- -- -- -- 06719B7° VK327 1/2" 15 mm 4.2 57 2-3/16 56 A2 A2 -- -- --06931B1° VK327 -- 10 mm 4.2 57 2-3/16 56 -- -- A3 -- C112 -- Maximum 250 PSI(17 bar)WWP Upright-Standard Orifice Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals' SIN (Refer also to Design Criteria on page 51d.) Number' NPT BSP U.S. metric2 Inches mm cULus4 NYC8 VdS LPCB (E 12281 VK315 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- -- -- -- Upright-Small Orifice' 1228610 VK340 1/2" 15 mm 2.8 40.3 2-3/16 56 A2 _ A2 -- - -- I -- Approved Temperature Ratings Approved Finishes A- 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 1 Brass and Chrome Enloy 286 °F(141°C) 2-Brass,Chrome-Enloy®,White Polyester56, Black Polyester'6, B- 155 °F(68 °C), 175 °F(79 °C), 200 °F(93°C), and 286 °F(141°C) and Black Teflon C 155 °F(68°C) 3 - Brass, Chrome-Enloy®, White Polyester", and Black Polyester5.6 Footnotes 'Base part number is shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. a Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5cULus Listed as corrosion resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 'Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA. 8 Accepted for use, City of New York Department of Buildings,MEA 89-92-E, Vol. 16. e Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or - internally galvanized. 10The sprinkler orifice is bushed. " (E Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. • '2(E Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40131. '3 O MED Certified, Standard EN 12259-1,EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. Sprinkler 51d January 22, 2010 MICROFAST°AND NIKIING TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com DESIGN CRITERIA- UL (Also refer to Approval Chart 1 on page 51c) cULus Listing Reauirements: Microfast and MicrofastHP"'Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers,or old style(conventional)sprinklers. • Designed for use in Light and Ordinary Hazard occupancies (exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to the installation guidelines for old style(conventional)sprinklers. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Protective Wrench Sprinkler Flat , Cap 10896 (P5) Figure 1: Standard Sprinkler Wrench 10896W/B January 22, 2010 Sprinkler 51e MICROFAST®AND NIKING TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) Temperature KEY Microfast-' Quick Response Upright Sprinklers � Finish Al x f-Escutcheon(it applicable) Maximum 175 PSI(12 bar)WWP Base Part SIN Thread Size Nominal K-Factor Overall Length FM Approvals' Number' NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria below.) Standard Orifice 06661B VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 _ A2 Large Orifice 06665B VK350 3/4" -- 8.0 115.2 2-5/16 59 A2 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2 Small Orifice' 0671786 VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Approved Finishes Approved Temperature Ratings 1 - Brass and Chrome-Enloy° A- 135 °F(57 °C), 155 °F (68 °C), 175 °F (79°C), 200°F(93 °C), and 286 °F(141°C) 2 - Brass, Chrome-Enloy`'', White Polyesters, and Black Polyesters Footnotes 'Base part number is shown. For complete part number, refer to Viking's current price schedule. - 'Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the FM Approvals available at the time of printing.Check with the manufacturer for any additional approvals. FM Approved as quick response Non-Storage pendent sprinklers. For specific application and installation requirements, reference the latest appli- cable FM Loss Prevention Data Sheets(including Data Sheet 2-0). Other colors are available on request with the same Approvals as the standard colors. °The sprinkler orifice is bushed. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Approval Reauirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-Storage upright sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements,hydraulic design,ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. I THIS PAGE INTENTIONALLY LEFT BLANK Form No. F_080488 Replaces page 51a-e, dated April 25, 2008. (Updated for Sprinkler 14817. Added VdS to Sprinklers 06665B, 06764B, and 14817. Updated FM Approvals and split the Approval Charts to separate UL Listing requirements from FM Approval requirements. Chanaed the metric K-factor for K4.2 sprinklers to 57.1 October 8, 2010 Sprinkler 41a NIKING MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Microfast' and MicrofastHP`' Quick Response Pendent Sprinklers are small, thermosensitive,glass-bulb spray sprinklers available in several different finishes and temperature ratings and K-Factors to meet design requirements.The special Polyester and Teflon'coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive at- 9 9 •.;:acs:. t, mospheres and are cULus listed as corrosion resistant as indicated in the Approval ;« , Chart. (Note: FM Global has no approval classification for Teflon'and Polyester coat- ings as corrosion resistant.) ar 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV - - FM Approved: Class 2020 NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984C-PDA VdS Approved: Certificates G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021 LPC Approved: Ref. Nos. 096e/03 and 096e/04 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40130, and 0 786-CPD-40170 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on page 41d for cULus Listing requirements and refer to Approval Chart 2 and Design Criteria on page 41e for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres- http://www.vikinggroupinc.com. sure (HP) sprinklers can be identified by locating "250" stamped on The Web site may include a more recent the deflector. All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page. maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: Refer to the Approval Charts "cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06662B and 12282. Brass UNS-C84400 for all other sprinklers. Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 06662B, 06666B, and 06765B. Copper UNS- C19500 for Sprinkler 12282. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Form No F_081296 Replaces page 41a-f, dated May 7, 2010. (Clarified FM Approval.) Sprinkler 41b October 8, 2010 MICROFAST°AND VIKING TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com For Teflon"Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon'Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order Microfast"'and MicrofastHP`'Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler fin- ish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass=A, Chrome-Enloy`"'= F, White Polyester= M-/W, Black Polyester= M-/B, and Black Teflon`'= N Temperature Suffix(°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 2867141° = G For example, sprinkler VK302 with a 1/2" thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 06662BAB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for Coated and/or Recessed Sprinklers: Part No. 12144W/B*(available since 2003) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool** Part No. 15915 (available since 2010.) NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W/B. *A'A"ratchet is required(not available from Viking). **Allows use from the floor by attaching a length of 1"diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F 051808. Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Wrench The Viking Microfast°'and MicrofastHPP"Quick Response Pendent Plats Sprinklers are available through a network of domestic and Protective international distributors. See The Viking Corporation web site for cgo 'I�∎ab,�1' Sprinkler the closest distributor or contact The Viking Corporation. Cap 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. 10896 -- / Figure 1: Standard Sprinkler Wrench 10896W/B • October 8, 2010 Sprinkler 41c MICROFASP AND TECHNICAL DATA MicrofastHP® QUICK . NIKING RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature2 Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy"', White Polyester, Black Polyester, and Black Teflon`'? Corrosion-Resistant Coatings': White Polyester, Black Polyester, and Black Teflon`' Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and Teflon"coatings. 1 I I I I ■ I +.... � III �N \ I k .+71 1! illIt IN'1N lllk INIf y 1! Ir Sprinkler- Wrench 12144W/B for installing coated NW and/or recessed pendent sprinklers N , Carefully slide the t with rotective cas. -_ L wrench sideways r ;1 around the protective cap, ensuring engage— L,`. `' s rient with the sprinkler im wrench flats. i=i 400 1/2" ratchet is required (not available from Viking) Figure 2: Wrench 12144W/B for Coated and/or Recessed Pendent Sprinklers Sprinkler 41d October 8, 2010 MICROFAST®AND VIKING TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) Temperature KEY Microfast® and MicrofastHP®Quick Response Pendent Sprinklers A 7J F Escutcheon(i!applicable) Maximum 175 PSI(12 bar)WWP Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No.' NPT BSP U.S. metric2 Inches mm cULus` NYC' VdS LPCB C E Q Standard Orifice 06662B VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A1X,B1Y A1X,B1Y A3 A3X, B3Y C3X, E3Y11 C3X, E3Y13 Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 AI X, B1Y AI X,B1Y A3 A3X C311 -- 06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 AI X,B1Y A1X,B1Y A3 -- -- -- Small Orifice' 06718B9 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 AI X,B1Y AI X, B1Y -- -- -- -- 06720B9 VK331 1/2" 15 mm 4.2 57 2-1/4" 58 A1X,B1Y AI X,B1Y -- -- -- -- 06932B VK331 -- 10 mm 4.2 57 2-3/8" 60 -- -- A3 -- G212 -- Maximum 250 PSI(17 bar)WWP Standard Orifice Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No' NPT BSP U.S. metric2 Inches mm cULus` NYC10 VdS LPCB C E 0 12282 VK317 1/2" 15 mm 5.6 80.6 2-1/4" 58 AI X,B1Y A1X -- -- -- -- Maximum 250 PSI(17 bar)WWP Small Orifice' 1229010 VK342 1/2" 15 mm 2.8 40.3 2-3/16" 56 AI X, B1Y A1X -- -- -- -- Approved Temperature Ratings A-135°F(57°C), 155°F(68°C), 175°F(79°C),200°F(93°C), Approved Escutcheons and 286°F(141 °C) Approved Finishes X - Standard surface-mounted escutcheon or B- 135°F(57°C), 155°F(68°C), 175°F(79°C),and 200°F 1 - Brass, Chrome-Enloy`, White the Viking Microfasf' Model F-1 Adjustable (93°C) Polyester6J, Black Polyester", Escutcheon C- 155°F(68°C), 175°F(79°C), 200 °F(93°C),and 286°F and Black Teflon" (141 °C) Y - Standard surface-mounted escutcheon or D 135°F(57°C), 155°F(68°C), 175°F(79°C),and 286°F 2-Brass and Chrome-Enloy"' the Viking Microfast` Model F-1 Adjustable (141 °C) 3 - Brass, Chrome-Enloy, White Escutcheon or recessed with the Viking E- 155°F(68°C), 175°F(79°C),and 200°F(93°C) Polyester',and Black Polyester' Micromatic" Model E-1 or E-2 Recessed F- 155°F(68°C), 175°F(79°C),and 286°F(141 °C) Escutcheon G- 155°F(68°C) Footnotes ' Base part number is shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. 'Listed by Underwriters Laboratories Inc. for use in the U.S.and Canada. 'Accepted for use,City of New York Board of Standards and Appeals, Calendar Number 219-76-SA. 6 cULus Listed as corrosion resistant. 'Other colors are available on request with the same Listings and Approvals as the standard colors. 'Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. 'The sprinkler orifice is bushed. ',Accepted for use,City of New York Department of Buildings, MEA Number 89-92-E,Vol. 16. " L t Certified,Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. 12 CE Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40130 and 0786-CPD-40170. " 0 MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. October 8, 2010 Sprinkler 41 e MICROFAST°AND TECHNICAL DATA MicrofastHP QUICK RESPONSE PENDENT - 14 I KI NG SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 - Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com DESIGN CRITERIA- UI. (Also refer to Appr `""`'4" - cULus Listing Requirements: Microfast"'and MicrofastHPSi Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies (exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Ceiling Opening Size: 2-5/16' (58,7 mm) minimum 2-1/8' 2-1/2' (63.5 mm) maximum (54 mm) 1/2' (15 mm) -F-1 LIF..— -----■11111 Illig `I I 1 ta91aIL\�■ ` Imlite 2-1/4' 1-3/4' 4 1-5/8' (58 mm) (44.5 mm) 2' 1-1/2' (38.1 mm)..._ie / <50,8 mm) 110 Minimum (41 chin) = Maximum Installed with a ..... l Pendent Sprinkler standard 1/8' surface- 06662B (VK302) mounted escutcheon. Installed with a Microfast Model F-1 Adjustable Escutcheon Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon 2-1/8' Ceiling Opening Size: 2-1/8' (54 mm) 2-5/16' (58.7 mm) minimum (54 mm) 2-1/2' (63.5 mm) maximum n is i t�■ �! mil 1r `= .• �� MM. �Imly I.�b�I +- 1-3/4' a 1-1/8° (28.6 mm) T (44,5 mm) Minimum 2' !_, 1-1/8' (28.6 mm) i (50.8 mm) Minimum Maximum Maximum f 1 r Installed with a Micromatic • Model E-1 Recessed Escutcheon Installed with a thread on Model E-2 Recessed Escutcheon Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons Sprinkler 41f October 8, 2010 MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 �Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) ---- Temperature KEY Microfast®Quick Response Pendent Sprinklers 1+--Finish Maximum 175 PSI(12 bar)WWP A1X4 Escutcheon(if applicable) Sprinkler SIN Thread Size Nominal K-Factor Overall Length FM Approvals' Base Part No. NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria below.) Standard Orifice 06662B VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A2X,B2Y Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 A1X,B1Y Small Orifice4 06718B6 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 A1X Approved Escutcheons Approved Temperature Ratings Approved Finishes X-Standard surface-mounted escutcheon or the Viking A-135°F(57°C, 155 155°F(68°C , 175 175°F(79°C, Microfast®Model F-1 Adjustable Escutcheon ( ) ( ) ( ) 1 -Brass and Chrome-Enloy® 200°F(93°C),and 286°F(141 °C) 2 grass,Chrome Enloy ,White Polyesters, Y - Standard surface-mounted escutcheon or the B-135°F(57°C),155°F(68°C), 175°F(79°C), and Black Polyesters Viking Microfast®Model F-1 Adjustable Escutcheon - and 200°F(93°C) or recessed with the Viking Micromatic®Model E-1 or E-2 Recessed Escutcheon Footnotes Base part number is shown. For complete part number,refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. ^FM Approved as standard response control mode standard spray Non-storage sprinklers.For specific application and installation requirements,refer- ence the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). s Other colors are available on request with the same Listings and Approvals as the standard colors. 6 The sprinkler orifice is bushed. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Approval Reauirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-storage standard spray pendent sprinklers as indicated in the FM Approval Guidet. For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheets 2-0 and 8-9).FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements, hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. tSprinklers VK302 and VK352 are also FM Approved as quick response Rack Storage standard spray pendent sprinklers. Refer to technical data page 131a-e for Intermediate Level In-Rack Sprinklers. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations, and also with the provisions of governmental codes,ordinances,and standards, whenever applicable. Form No. F_081296 Replaces page 41a-f, dated May 7, 2010. (Clarified FM Approval.) October 25, 2010 Sprinkler 105a TECHNICAL DATA QUICK RESPONSE DRY PENDENT SPRINKLERS . NHKING The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Quick Response Dry Pendent Sprinklers are thermosensitive spray sprinklers suit- able for use in areas subject to freezing.The sprinklers are designed for dry systems and preaction systems where it is necessary to prevent water or condensation from entering the drop nipple before sprinkler operation.They may also be installed in spaces subject to freezing and supplied from a wet system in an adjacent heated area. Viking Quick Response Dry Pendent Sprinklers are available in various finishes and tem- perature ratings to meet design requirements. The special Polyester coating has been investigated for installation in corrosive atmospheres and is cULus listed as corrosion resistant as indicated in Approval Chart 1. (Note: FM Global has no approval classification for Polyester coatings as corrosion resistant.) A ,tom NOTE: When installed in some corrosive environments, the Polyester finish may , _ change color. This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such. All sprinklers installed in corrosive environments should be replaced or tested as described in NFPA 25 on a more frequent basis. 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approved: Classes 2013 and 2015 NYC Approved: MEA 89-92-E Volume 15 Refer to Approval Chart 1 and Design Criteria on page 105d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 105e for FM Approval requirements that must be followed. 3. TECHNICAL DATA Viking Technical Data may be found on Specifications: The Viking Corporation's Web site at Minimum Operating Pressure: 7 psi (0.5 bar) http://www.vikinggroupinc.com. Maximum Working Pressure: 175 psi (12 bar). Factory tested pneumatically to The Web site may include a more recent 100 psi (6.89 bar) edition of this Technical Data Page. Thread size: 1" NPT or 25 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric")for all listed and approved lengths. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to-65 °F (-55 °C) Material Standards: Frame Casting: Brass UNS-C84400 Deflector: Brass UNS-C26000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Compression Screw: Brass UNS-C36000 Pip Cap: Brass UNS-C31400 or UNS-C31600 Pip Cap Adapter: Brass UNS-C36000 Orifice: Copper UNS-C22000 or UNS-C11000 Tube: ERW Hydraulic Steel Tube Support (Internal): Stainless Steel UNS-530400 Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish Barrel End and Threads: QM Brass Sleeve (for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800 Escutcheon Materials: Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800 Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080 Form No. F_031793 Replaces page 105a-f, dated August 12, 2010. (Revised sprinkler materials.) Sprinkler 105b October 25, 2010 VIKING TECHNICAL DATA QUICK RESPONSE DRY PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 - Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Dry Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish, the appropriate suffix for the temperature rating, and then the suffix for the length ("A" dimension) to sprinkler base part number. Order in a specific length noted as the "A" dimension. The "A" dimension is the distance from the face of the fitting (tee) to the desired finished surface of the ceiling. These sprinklers are listed and approved in lengths from 1-1/2"to 45-1/2"(38.1 mm to 1,156 mm)for the adjustable standard style,3"to 47"(76.2 mm to 1,194 mm)for the plain barrel style,and 3-1/4"to 47-1/2"(82.5 mm to 1,207 mm)for the adjustable recessed style. Lengths exceeding the standard lengths are available,with no approvals,on a"made-to-order"basis: Recessed Dry Pendent up to 65-1/2"(1,664 mm).Adjustable Standard Dry Pendent up to 63-1/2"(1,613 mm). Plain Barrel Dry Pendent up to 65" (1,651 mm). Contact the manufacturer for more information. Finish Suffix: Brass =A, Chrome-Enloy®= F, and White Polyester= M-/W Temperature Suffix(°F/°C): 155"/68° = B, 175°/79° = D, 200°/93° = E, 286°/141° =G For example, sprinkler VK176 with a Chrome finish and a 155 °F/68 °C temperature rating, and "A" length of 10" = Part No. 08383U FBI 0. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Wrench Sprinkler Wrenches: Flat A. Standard Wrench: Part No. 07297W/B (available since 1991) j�rxu.:llNl��j Protective B. Wrench for recessed sprinklers: Part No. 07565W/B** Sprinkler - (available since 1991) O■ I Shield **A'/2"ratchet is required(not available from Viking). '`w Sprinkler Guard: Chrome,with no listings or approvals, for installation - on dry pendent sprinklers made after May 1994 only (Part No. 08954). -'- Replacement Escutcheons: A.Adjustable Standard Dry Escutcheon: Base Part No. 07741 B. Recessed Dry Escutcheon Cup: Base Part No. 05459A VIKING 07297 O 4. INSTALLATION Refer to appropriate NFPA Installation Standards. Figure 1: Standard Sprinkler Wrench 07297W/B 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the internal parts to open the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector,forming a m....... uniform spray pattern to extinguish or control the fire. --- Sprinkler Wrench 6. INSPECTIONS,TESTS& MAINTENANCE 07565W/B, K must be Refer to NFPA 25 for Inspection, Testing and used for installing P 9 recessed dry Maintenance requirements. sprinklers ura•r.MI eI f1Ill rs :rrr 7. AVAILABILITY `�' The Viking Quick Response Dry Pendent Srink- - Step 2:wrench upward press g p ry p `� ��i the turnrslich upward and ',i ler is available through a network of domestic 1 j� slightly to ensure and international distributors. See The Viking -- engagement with the -- - Corporation web site for the closest distributor sprinkler wrench flats. or contact The Viking Corporation. Step 1, carefully ""A 1/2' ratchet is - slide the wrench required (Not avail- sideways around the able from Viking.) 8. GUARANTEE sprinkler deflector. For details of warranty, refer to Viking's current • list price schedule or contact Viking directly. Figure 2: Wrench 07565W/B for Adjustable Recessed Dry Pendent Sprinklers October 25, 2010 Sprinkler 105c TECHNICAL DATA QUICK RESPONSE DRY PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature2 Ordinary 155 °F (68 00) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy®(patents pending), and White Polyester Corrosion-Resistant Coating": White Polyester in all temperature ratings Footnotes The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply,depending on fire loading,sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant Polyester coating has passed the standard corrosion test required by the approving agencies indicated in Approval Chart 1.These tests cannot and do not represent all possible corrosive environments. Note:This coating is NOT corrosion proof. Prior to installation,verify through the end-user that the coating is compatible with or suitable for the proposed environment. Polyester coating is applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester coatings. °When installed in some corrosive environments,the Polyester finish may change color.This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such. All sprinklers installed in corrosive environments should be replaced or tested as described in NFPA 25 on a more frequent basis. For 'A' Dimension: 1. Determine the distance from the face of the tee to the finished ceiling. 2. Round to the nearest 1/2' (12.7 mm) between 1-1/2' and 45-1/2' (38.1 mm and 1,156 mm). NOTE: The deflector will be located approximately 3-7/16' (87.3 mm) below the ceiling. with 1' (25.4 rim) upward and 1' (25.4 mm) downward adjustment. Deflector at minimum distance below ceiling. NOTE: To To locate the deflector at the minimum distance below the ceiling, with 1 --- no downward adjustment Minimum ceiling opening f 2-7/16' available, order the A (61.9 mm) dry 1-3/4' (44.5 mm). y pendent sprinkler Maximum ceiling opening Minimum 1' (25.4 mm) shorter diameter: 2-1/4' (57 mm). than the 'A' dimension. ._. 13/16' 1 1 =£ NOTE: Finished J (20.6 mm) To locate the deflector Ceiling at the maximum distance 4-7/16' below the ceiling, with 1-1/2' Sleeve finish (112.7 mm) no downward adjustment (38.1 mm) matches escutcheon. Maximum available, order the diameter dry pendent sprinkler 3-1/16' 1' (25.4 mm) longer (77.8 rim) than the 'A' dimension. Deflector at maximum distance below ceiling. Figure 3: Adjustable Standard Dry Pendent Sprinkler Sprinkler 105d October 25, 2010 TECHNICAL DATA QUICK RESPONSE DRY PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) Temperature KEY Quick Response Dry Pendent Sprinklers Finish Maximum 175 PSI(12 bar)AMP MX. Escutcheon(f applicable) Sprinkler SIN Style Thread Size Nominal K-Factor2 Order Length Increment Listings and Approvals° Base Part No.' (Refer also to Design Criteria below.) NPT BSP U.S. metric' Inches mm cULus5 NYC' VdS LPCB CE 08383U Adjustable 1" -- 5.6 80.6 1/2" 12.7 Al Al -- -- -- -- VK176 16457U Standard -- 25 mm -- 80.6 1/2" 12.7 Al -- -- -- -- 08385U Adjustable -- j 1,' : -- 5.6 80.6 1/4" 6.35 B2 B2 -- -- -- -- 16453U VK180 Recessed -- 25 mm -- 80.6 1/4" 6.35 B2 08387U Plain 1" -- 5.6 80.6 1/2" 12.7 A3 A4 -- -- -- -- VK172 16455U Barrel -- 25 mm 80.6 1/2" 12.7 A3 -- -- Approved Temperature Ratings Approved Finishes and "A" Dimensions A- 155 °F (68 °C), 175 °F (79°C), 200 °F (93 °C), 1 -Chrome-Enloe or White Polyester'sprinkler with a Chrome-Enloe or White Polyester Sleeve and 286°F(141 °C) and Escutcheon with"A"dimensions 1-1/2"to 45-1/2"(38.1 mm to 1,156 mm) B 155 °F (68 °C), 175 °F 79°C and 200 °F 2-Chrome-Enloe or White Polyester with"A"dimensions 3-1/4"to 47-1/2"(82.5 mm to 1,207 mm) 3-Chrome-Enloy®, Brass,or White Polyester' with"A"dimensions 3"to 47"(76.2 mm to 1,194 mm) (93°C) 4-Chrome-Enloy®or Brass with "A"dimensions 3"to 47"(76.2 mm to 1,194 mm) Footnotes ' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 K-Factor applies for standard lengths("A" Dimensions indicated above). Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa, divide the metric K-factor shown by - 10.0. 'This chart shows the listings and approvals available at the time of printing.Other approvals may be in process. Check with the manufacturer for any additional approvals. 5 Listed by Underwriter's Laboratories for use in the U.S. and Canada. 5 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E.Vol. 15. 'cULus Listed as corrosion resistant. DESIGN CRITERIA - UL (Also refer to Approval Chart 1 above.) NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-BI tees.When selecting other CPVC fittings, contact Viking Technical Services. cULus Listing Requirements: Standard Dry Pendent Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies. • The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page DRY1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. October 25, 2010 Sprinkler 105e TECHNICAL DATA QUICK RESPONSE DRY PENDENT SPRINKLERS . NIKING, The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) f Temperature KEY Quick Response Dry Pendent Sprinklers +f- Finish Maximum 175 PSI(12 bar)WWP Al X4-Escutcheon(if applicable) Sprinkler Base SIN S le Thread Size Nominal K-Factor2 Order Length Increment FM Approvals' Part No.1 NPT BSP U.S. metric' Inches mm (Refer also to Design Criteria below.) 08383U 1" -- 5.6 80.6 1/2" 12.7 Al 16457U VK176 Adjustable Standard -- 25 mm -- 80.6 1/2" 12.7 Al 08385U 1" -- 5.6 80.6 1/4" 6.35 B2 16453U VK180 Adjustable Recessed -- 25 mm -- 80.6 1/4" 6.35 B2 08387U 1" -- 5.6 80.6 1/2" 12.7 A3 16455U VK172 Plain Barrel -- 25 mm -- 80.6 1/2" 12.7 A3 Approved Temperature Ratings Approved Finishes and "A" Dimensions A- 155°F(68°C), 175°F(79°C),200°F(93°C), 1 - Brass, Chrome-Enlor, or White Polyester sprinkler with a Brass, Chrome-Enloy® or White Polyester Sleeve and Escutcheon with"A"dimensions 1-1/2"to 45-1/2"(38.1 mm to 1,156 mm) and 286°F(141 °C) 2-Brass,Chrome-Enloym,or White Polyester with"A"dimensions 3-1/4"to 47-1/2"(82.5 mm to 1,207 mm) B-155°F(68°C), 175°F(79°C),and 200°F(93°C) 3-Brass,Chrome-Enloy®, or White Polyester with"A"dimensions 3"to 47"(76.2 mm to 1,194 mm) Footnotes I Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 K-Factor applies for standard lengths("A" Dimensions indicated above). 'Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa, divide the metric K-factor shown by 10.0. a This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any ad- ditional approvals. DESIGN CRITERIA -FM (Also refer to Approval Chart 2 above.) NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-BI tees.When selecting other CPVC fittings, contact Viking Technical Services. FM Approval Reauirements: The Dry Pendent Sprinklers in the Approval Chart above are FM Approved as quick response Non-storage standard spray sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets(includ- ing 2-0) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT:Always refer to Bulletin Form No. F 091699 -Care and Handling of Sprinklers.Also refer to page DRY1-3 for general care, installation,and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data,the appropriate standards of NFPA, FM Global, LPCB,APSAD,VdS or other simi- lar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. $ 0 4 00 I -.. - l- For "A' Dimension I. Determine the distance �- ■ 1 from face of tee to _� ,T-For 'A' Dimension the finished ceiling. A 2. Round to nearest 1/4" A 1. Determine the Minimum ceiling opening: (6,35 mm) between distance from 9 P 9' \ Outside the face of the 2-1/8' (54 rim) diameter. 3-1/4' (82.5 mm) and 47-1/2' (1,207 mm). diameter, N. tee to the base Maximum ceiling opening: 1-5/16' ii, of the sprinkler. 9 P 9' (33.4 mm) 2. Round up to the 2-1/2' (63.5 mm) diameter. NOTE: Sprinkler will be (same as next hi hest 1/2' recessed approximate., 1' (25 mm) g 5/16' (7.9 mm) above (12.7 mm) incre- Schedule ment between 3' - the finished ceiling wit4' 40 pipe). (76.2 mm) and . Adjustment: 5/8' (15.8 mm) vertical 47' (1,194 mm). 5/16' (7.9 mm)-. 1 -f=- ,-V......a.�.. ...... adjustment available. 5/16' (7.9 mm)- ��■ it..∎ .;;:::»:. s (::%----I Finished ceiling 1. 1-5/8' Minimum, 1' (25.4 mm)- i t. (48.3 rim) Maximum: 1-5/8' (42.1 mm) 1 3-1/16' (779 nn)-- '�' Figure 4: Adjustable Recessed Dry Pendent Sprinkler Figure 5: Plain Barrel Dry Pendent Sprinkler Sprinkler 105f October 25, 2010 VIKING TECHNICAL DATA QUICK RESPONSE DRY PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Ambient Exposed Barrel Install 1 inch NPT threaded Temperature Ambient Temperature end of dry pendent sprinkler Deflector at of Protected 40'F/4 LI50 Ffl0'CI60 F/16 C — into the 1 inch NPT outlet minimum distance Areal! et the Exposed Minimum Barrel - below ceiling Discharge End Lengths, Face of Tee `)of a malleable Iron tee fitting 9 Y per ANSI B 16.3 (Class 150) to Top of Ceiling / P ` Up to 2' (50.8 mm) of the Sprinkler In (m) In.(m) In(m) or cast iron threaded tee fitting adjustment available. 40•F (4'C) 0 0 0 4 ', per ANSI 16.4 (Class 125) only. 30•F (-1•C) 0 0 0 I M Note: 20'F ( 7'C) 4 (100) 0 0 Minimum ceiling opening diameter, 1-3/4' (44.5 mm) = To locate the 10•1 (-12•C) 8 (203) 1 (25.4) 0 _,(Exposed, deflector at the Barrel) / Maximum ceiling opening diameter: ,-, minimum distance 0'F (-18'C) 12 (305) 3 (76) 0 2-1/4' (57 mm). 2-7/16' below the ceiling, -lo•F (-23'C)14 (356) 4 (102) 1 (25.4) , •i• (61.9 mm) with no upward -20'F (-29'C)14 (356)6 (152) 3 <76) Seal the clearance Minimum adjustment avail- /-30•F (-34'0 16 (406)8 (203)4 (102) space around the I I able, order the sprinkler to avoid leak- dry pendent sprink- -40'F (-40•C)18 (457)8 (203)4 (102) p ler 1' (25.4 mm) -50'F (-46'C)20 (508)IO (254)6 (152) 6 iiFRi age of air into the iii shorter than the -60'F ( 51'C)20 (508)10 (254)6 (152) / ® 1316' protected area and 'A' dimension. J (2m) consequent formation � Ceiling — of condensate around the frame, which could Note: inhibit operation or To locate the /1 1/2' (38.1 mm) I Sleeve finish cause premature opera- 4-7/16' deflector at the matches tion. Refer to Figure maximum distance diameter 7 below. (112.7 mm) below the ceiling, escutcheon Maximum If humidity and temp- with t downward P- ndJustment avnil- 3 1/16' erature differential able, order the (Protected Area) causes condensation I dry pendent sprink- _ (77.8 mm) on the exposed dry ler 1' (25.4 mm) sprinkler, consider longer than the wrapping the exposed Deflector at 'A' dimension. barrel with insulation, maximum distance foam insulating tape, below ceiling or equivalent. *The protected area refers to the area below the ceiling. The ambient temperature is the temperature at the discharge end of the sprinkler. For protected area temperatures that occur between the values listed, use the next cooler temperature. wwThe minimum required barrel length is not the same as the 'A' dimension. Refer to Figures 3-5 for the 'A' dimension. NOTE, Exposed minimum barrel lengths are inclusive up to 30 mph wind velocities. Figure 6: Dry Pendent Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area (Adjustable Standard Dry Pendent Sprinkler is Shown) ■ ....., Seal Part No. 13864 �__ ■ (or equivalent method) Seal IIIII=1 411 OM • Clearance 11111111r Insulated Opening III Ceiling ■ I I A II Dry Sprinkler Seal on the Dry Sprinkler Seal Within the Ceiling Exterior of the Ceiling Figure 7: Dry Sprinkler Seal (Adjustable Standard Dry Pendent Sprinkler is Shown) Form No F_031793 Replaces page 105a-f, dated August 12, 2010. (Revised sprinkler materials.) ES-A-C300/C300N Colt Series C300/C300N A M E S FIRE&WATERWORKS'' Double Check Detector Assemblies Sizes: 21/2 — 10" (65 —250mm) AP% ,41011C30O6FG 11,71r C3000SY op; - 2. e Features The Colt C300/C300N Double Check Detector Assemblies are used to prevent backflow of pollutants, that are objectionable but not toxic, from • Extremely Compact Design entering the potable water supply system.The Colt C300/C300N may be • 70% Lighter than Traditional installed under continuous pressure service and may be subjected to Designs backpressure. The Colt C300/C300N is used primarily on fire line • 304 (Schedule 40) Stainless Steel sprinkler systems when it is necessary to monitor unauthorized use of Housing &Sleeve water. For use in non-health hazard applications. • Groove Fittings Allow Integral Pipeline Adjustment Specifications • Patented Tri Link Check Provides The Colt C300/C300N Double Check Detector Assemblies shall consist Lowest Pressure Loss Unmatched Ease of Serviceability of two independent Tri-Link Check modules within a single housing, • sleeve access port, four test cocks and two drip tight shutoff valves. Tri- • Available with Grooved Butterfly Link Checks shall be removable and serviceable, without the use of Valve Shutoffs special tools. The housing shall be constructed of 304 (Schedule 40) • May be Used for Horizontal, stainless steel pipe with groove end connections. Tri-Link Checks shall Vertical or N Pattern Installations have reversible elastomer discs and in operation shall produce drip tight • Replaceable Check Disc Rubber closure against the reverse flow of liquid caused by backpressure or backsiphonage. The bypass assembly shall consist of a meter, which registers in either gallon or cubic measurement, a double check valve assembly and required test cocks. Assembly shall be a Colt C300/C300N as manufactured by the Ames Company. Job Name Contractor Job Location Approval Engineer Contractor's P.O. No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Configurations Available Models • Horizontal Suffix: • Vertical up OSY- UUFM outside stem and yoke resilient • "N" pattern horizontal seated gate valves BFG- UUFM grooved gear operated butterfly valves Materials with tamper switch • Housing&Sleeve: 304(Schedule 40)Stainless Steel - • Elastomers: EPDM, Silicone and Buna `N' Pressure — Temperature • Tri-Link Checks: Noryl®, Stainless Steel Temperature Range: 33°F- 140°F (5°C-60°C) Maximum Working Pressure: 175psi (12 bars) • Check Discs: Reversible Silicone or EPDM • Test Cocks: Bronze Body Nickel Plated • Pins&Fasteners: 300 Series Stainless Steel • Springs: Stainless Steel Dimensions — Weights a tI!J ?m III 1■1 4 C(open) AAN, It%. .� i t*wL . .r c „1.11!!,1 H 1 A ] F C300/C300N SIZE(ON) DIMENSIONS WEIGHT A COSY) D G H I J P C300 C300N in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kas. lbs. kos. 21/2 65 31 787 163/8 416 31% 89 291/6 738 22 559 15%2 393 813/6 223 133/16 335 139 63 147 67 3 80 3111/6 805 181/2 479 3'%6 94 301/4 768 223/4 578 17% 435 93/6 233 14' 368 159 72 172 78 4 100 3311/6 856 223/4 578 4 102 33 838 24 610 181/2 470 915/16 252 153/16 386 175 79 198 90 6 150 44 1118 301/2 765 512 140 443/4 1137 333/4 857 233/16 589 13'/16 332 19 483 309 140 350 159 8 200 50 1270 373/4 959 6"/6 170 54% 1375 405/8 1032 277/6 697 1511/16 399 213/6 538 494 224 569 258 10 250 571/2 1460 453/4 1162 83/16 208 66 1676 50 1270 32' 826 175/6 440 24 610 795 361 965 438 Pt w Tr.. x I I C_ Pi I J -um ! y ,, ,, CII)• 117 ' -':•1 -F • 'BOIL! + A 1. [ _ H - _ I 1 —_ P --- C300BFG/C300NBFG 0 SIZE(DN) DIMENSIONS WEIGHT A C D G H I J P C3008FG C300N8FG in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. lbs. kgs. 21/2 65 28 711 8 203 3% 89 291/2 759 22 559 1415/6 379 813/16 223 13 330 70 32 78 35 3 80 28% 724 85/16 211 3'1/6 94 3011/6 779 223/4 578 15'/6 392 93/6 233 131/2 343 68 31 81 37 4 100 293/6 741 815/6 227 3"A6 94 _3115/6 811 24 610 161/4 412 915/6 252 14 356 75 34 98 44 - 6 150 36'% 927 10 254 5 127 433/6 1097 333/4 857 1911/6 500 131/6 332 14% 368 131 59 171 78 8 200 43 1092 121/4 311 6% 165 511/6 1297 405/8 1032 235/16 592 1511/6 399 183/6 462 275 125 351 159 Noryl®is a registered trademark of General Electric Company. Approvals ID c 0 us SP® 44114> Approved . 1048 Listed B64.4 28S6 For additional approval information please contact the factory or visit our website at www.amesfirewater.com Capacity UL/FM Certified Flow Characteristics Flow characteristics collected using butterfly shutoff valves. See literatue S-Colt-2001300 for gate valve flow characteristics * = Rated Flow " = UL Tested Horizontal Vertical N - Pattern kPa psi 21/2" 6 * ** kPa psi * ** 96 14 83 12 N 83 12 - - - N 69 10 • • - — _ v H 69 10 -- - -- 55 8 -- _ +- }-- , - ,H 55 8 • , _ 41 6 _ —�- ' _ 28 4 —_ — — _ ' 28 4 14 2 - - -- 14 2 0 0 — - 0 0 0 50 100 150 200 250 300 350 gpm 0 300 600 900 1200 1500 gpm 0 190 380 570 760 950 1140 1330 Ipm 0 1140 2280 3420 4560 5700 Ipm 15 fps 15 fps 4.6 mps 4.6 mps kPa psi 3,. * ** kPa psi 8.. ** 83 12 83 12 N 69 10 . . H 69 10 1 ' H V 55 8 _ N 55 8 — i 41 6 41 6 n I- 28 4 \ _�.i 28 4 r• 14 2 14 2 --- 0 0 0 0 0 100 200 300 400 500 gpm 0 500 1000 1500 2000 2500 gpm 0 380 760 1140 1520 1900 Ipm 0 1900 3800 5700 7600 9500 Ipm 15 fps 15 fps 4.6 mps 4.6 mps 4" 10" kPa psi * ** kPa psi * ** 165 24 83 12 138 20 69 10 N 110 16 - — H 55 8 83 12 — 41 6 v 55 8 �.�\ !r 28 4 �' 28 4 - 14 2 0 0 -- 0 0 0 100 200 300 400 500 600 700 800gpm _, 0 380 760 1140 1520 1900 2280 2660 3040 Ipm 0 500 1000 1500 2000 2500 3000 3500 gpm 15 fps 0 1900 3800 5700 7600 9500 11400 13300 Ipm 4.6 mps fps • mps IMPORTANT:INQUIRE WITH GOVERNING AUTHORITIES FOR LOCAL INSTALLATION REQUIREMENTS • For Technical Assistance Call Your Authorized Ames Agent. Telephone# Fax# HEADQUARTERS:Ames Fire and Waterworks 1427 North Market Blvd..Suite#9,Sacramento,CA 95834 916 928-0123 916 928-9333 t 4,, Edwards,Platt&Deely,Inc. 271 Royal Ave.,Hawthorne,NJ 07506 973 427-2898 973 427-4246 - t m Edwards,Platt&Deely,Inc. 368 Wyandanch Ave.,North Babylon,NY 11703 631 253-0600 631 253-0303 z uJ W.P. Haney Co.,Inc. 51 Norfolk Ave.,South Easton.MA 02375 508 238-2030 508 238-8353 RMI Glenfield Bus.Ctr.,2535 Mechanicsville Tpk.,Richmond,VA 23223 804 643-7355 804 643-7380 v c The Joyce Agency,Inc. 8442 Alban Rd.,Springfield,VA 22150 703 866-3111 703 866-2332 .°113. Vernon Bitzer Associates,Inc. 980 Thomas Drive,Warminster,PA 18974 215 443-7500 215 443-7573 Q WMS Sales,Inc.(Main office) 9580 County Rd.,Clarence Center,NY 14032 716 741-9575 716 741-4810 Billingsley&Associates,Inc. 2728 Crestview Ave.,Kenner,LA 70062-4829 504 602-8100 504 602-8106 Billingsley&Associates,Inc. 478 Cheyenne Lane,Madison,MS 39110 601 856-7565 601 856-8390 c, Mid-America Marketing,Inc. 203 Industrial Dr.,Birmingham,AL 35211 205 879-3469 205 870-5027 45 m Mid-America Marketing,Inc. 1364 Foster Avenue,Nashville,TN 37210 615 259-9944 615 259-5111 (o W Mid-America Marketing,Inc. 5466 Old Hwy.78,Memphis,TN 38118 901 795-0045 901 795-0394 Smith&Stevenson Co.,Inc. 4935 Chastain Ave.,Charlotte,NC 28217 704 525-3388 704 525-6749 Wager Company 702-B Industry Rd.,Longwood,FL 32750 407 834-4667 407 831-0091 Watts 2861-B Bankers Industrial Drive,Atlanta,GA 30360 770 209-3310 770 447-4583 s c HydroSource 8182 Chagrin Rd.,Chagrin Falls,OH 44023 440 247-9150 440 247-6719 t c Mid-Continent Marketing Services Ltd. 1724 Armitage Ct.,Addison, IL 60101 630 953-1211 630 953-1067 o Soderholm&Associates,Inc. 7150 143rd Ave.N.W.,Anoka,MN 55303 763 427-9635 763 427-5665 0 Z0 Stickler&Associates 333 North 121 St.,Milwaukee,WI 53226 414 771-0400 414 771-3607 Hugh M.Cunningham,Inc. 13755 Benchmark,Dallas,TX 75234 972 888-3808 972 888-3838 =To Mack McClain&Associates 11132 South Towne Square,Suite 202,St.Louis,MO 63123 314 894-8188 314 894-8388 =- Mack McClain&Associates,Inc. 1450 NE 69th Place,Ste.56 Ankeny,IA 50021 515 288-0184 515 288-504 o aci Mack McClain&Associates,Inc. 15090 West 116th St.,Olathe,KS 66062 913 339-6677 913 339-9518 0)U OK!Sales,Inc. 2200 Blue Creek Dr.,Norman,OK 73026 405 360-6161 405 360-0092 Phoenix Marketing,Ltd. 2416 Candelaria N.E.,Albuquerque,NM 87107 505 883-7100 505 883-7101 Cisco 1738 Neville Street,Orange,CA 92865 714 921-9228 714 921-0442 c Delco Sales.Inc. 111 Sand Island Access Rd., Unit 1-10,Honolulu,HI 96819 808 842-7900 808 842-9625 it Hollabaugh Brothers&Associates 6915 South 194th St.,Kent,WA 98032 253 867-5040 253 867-5055 N Hollabaugh Brothers&Associates 3028 S.E.17th Ave.,Portland,OR 97202 503 238-0313 503 235-2824 N P I R Sales,Inc. 3050 North San Marcos Place,Chandler,AZ 85225 480 892-6000 480 892-6096 3 Preferred Sales 31177 Wiegman Road,Hayward,CA 94544 510 487-9755 510 476-1595 Rep Masters,Inc. 6255 Dexter St.,Commerce City,CO 80022 303 286-7575 303 286-7576 Watts Industries(Canada)Inc. (Watts Regulator Co.Division) 5435 North Service Road,Burlington,Ontario L7L 5H7 905 332-4090 905 332-7068 D.C.Sales,Ltd. 10-6130 4th St.S.E.,Calgary,Alberta T2H 2A6 403 253-6808 403 259-8331 D.C.Sales,Ltd. 11420 142 Street,Edmonton,Alberta T5M 1V1 780 496-9495 780 496-9621 Hydro-Mechanical Sales,Ltd. 3700 Joseph Howe Dr.,Ste. 1 Halifax,Nova Scotia B3L 4H7 902 443-2274 902 443-2275 -a Hydro-Mechanical Sales,Ltd. 297 Collishaw St.,Ste.7(shipping)Moncton,New Brunswick E1C 9R2 506 859-1107 506 859-2424 C Hydro-Mechanical Sales,Ltd. 85 Tolt Rd.,St.Phillips,Newfoundland A1B 3M7 709 895-0090 709 895-0091 co Le Groupe B.G.T.,Inc. 23 du Buisson,Pont Rouge,Quebec G3H 1X9 418 832-2800 418 873-2505 U Le Groupe B.G.T.,Inc. 86 des Enterprises#208,Boisbriand,Quebec J7G 2T3 450 434-9010 450 434-9848 Mar-Win Agencies,Ltd. 1333 Clifton St.,Winnipeg,Manitoba R3E 2V1 204 775-8194 204 786-8016 Northern Mechanical Sales P.O.Box 280(mailing) 163 Pine St.(shipping),Garson,Ontario P3L 156 705 693-2715 705 693-4394 Palser Enterprises,Ltd. 1885 Blue Heron Dr.,#4,London,Ontario N6H 5L9 519 471-9382 519 471-1049 RAM Mechanical Marketing 1301 Winnipeg St.,Regina,Saskatchewan S4R 1K2 306 525-1986 306 525-0809 RAM Mechanical Marketing 510 Ave.M South,Saskatoon,Saskatchewan S7K 2K9 306 244-6622 306 244-0807 0423 Walmar Mechanical Sales 24 Gurdwara Rd.,Nepean,Ontario K2E 8B5 613 225-9774 613 225-0673 A A M E S IS0 9001 FIRE&WATERWORKS A Division of Watts Regulator Company www.amesfirewater.com CERTIFIED ' 1427 North Market Blvd. • Suite #9 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 ES-A-C300/C300N 0306 ©Ames Co.2003 Printed in U.S.A. MODEL 1011 -, TE TAN Az. 3/4- 1 r. 11/4" 11/2" I � TEP 00 ji.tAil Ad 11,04 .10 v aw l lR • pica na mo+[x•w�� 116 040, fffJttr`Jt`I ti!t USA PATENT AND OTHER PATENTS PENDING The AGF Manufacturing Inc.Model 1011 Matches All The Features And Benefits Of Our Model 1000 by Providing Both The Test Function And The Express Drain Function In A Multistory Installation,With The Added Feature Of An Integral Model 7000 Pressure Relief Valve With Drainage Piping. J Available In A Full Range Of Sizes From 3/4"To 2", NPT & BSPT,With All Specifiable Orifice Sizes 3/8", 7/16", 1/2" 17/32",5/8" (ELO),& 3/4" (ESFR). a The Model 1011 Complies With The Requirements Of NFPA 13, 13R,& 13D,Which Stipulate A Pressure Relief Valve Be Installed On All Gridded Systems And Downstream Of All Pressure Reducing Valves. J The Model 1011 Is A Single Handle Ball Valve That Is Lightweight And Compact,Which Includes A Tamper Resistant Test Orifice, Integral Tamper Resistant Sight Glass,And Is 300 PSI Rated. a The Included UL/FM Model 7000 Pressure Relief Valve Features A Flushing Handle And Is Factory Set At 175 PSI,Other Pressure Settings Are Also Available. J Designed To Relieve Excess System Pressure Caused By Surges Or Temperature Changes As Well As Solve The Difficult Problem Of Providing The Relief Valve With A Drainage-Piping Outlet. is The Unit Comes Shipped In A Semi-Assembled State With The Relief Valve And The Bypass Drain Ports Plugged.This Is Done To Ease Pressure Testing The System. our New qutoc visit us 9Q ■• on the Internet Si) at 8/01 MODEL 1011 APDRAIN. ® ® MODEL 1011 (UL LISTED/FM APPROVED) BRONZE BALL VALVE MODEL 7000 (UL LISTED/FM APPROVED) PRESSURE RELIEF VALVE FACTORY SET AT 175 PSI WITH OTHER SETTINGS AVAILABLE. FRONT VIEW - MODEL 1011 PLAN VIEW INLET A P. E 1 jii€ U I ~D _ ` I ■• H 1� TO DRAIN IIIIIP Iu From the February 1 , 1999 Edition of NFPA 13: Chapter 4-1.2 Requires ALL GRIDDED SYSTEMS be provided with a relief valves Chapter 5-14.1.2.3 Requires a relief valve be installed downstream of all pressure-reducing valves ORIFICE SIZES AVAILABLE -3/8, 7/16, 1/2, 17/32, ELO(5/8)', ESFR(3/4)' DIMENSIONS- INCHES OVERALL LENGTH 1011 1011 SIZE A B C D E F G H MATERIAL LIST 3/41 7 9/16" 1 1/2" 2 3/16" 3 5/8" 3 3/8" 1 13/16" 4 9/i6" 6 3/8" 191.30mm 37.58mm 55.65mm 93.23mm 85 88mm 45.30mm 117.12mm 162.42mm PART: MATERIAL: 1" 7 9/16" 1 1/2" 2 3/16" 3 5j8" 3 3/8" 1 13/16" 4 9/18" 6 3/8" 191.30mm 37.58mm 55.65mm 93.23mm 85.88mm 45.30mm 117.12mm 162.42mm HANDLE STEEL 1 1/4" 7 15/160 1 11/16" 2 9/16" 4 1/4"" 3 5/16" 1 15/16" 5 9/16" 5 1/2" STEM ROD BRASS 201mm 42.70mm 65.36mm 108.36mm 82.84mm 50.89mm 141.39mm 192.28mm BALL C.P.BRONZE BODY BRONZE 1 1/2" 8 15/16" 1 13/16" 3 1/4" 5 1/16" 3 7/8" 2 5/8" 8 1/a" 10 7/8" VALVE SEAT IMPREGNATED TEFLON 2 226.68mm 45.50mm 81.50mm 127mm 99.18mm 66.97mm 206.63mm 273.60mm INDICATOR PLATE STEEL 2" 8 15/16" 1 13/16" 3 1/4" 5 1/16" 3 7/8" 2 5j8" 8 1/4" 10 7/8" RELIEFVALVE BRONZE 226.68mm 45.50mm 81.50mm 127mm 99.18mm 66.97mm 206.63mm 273.60mm BYPASS TITBINGS BRASS BYPASS TUBING NYLOBRAID 'Available on 1 1/4"to 2"size units only T ELO/ESFR IS UL LISTED&FM APPROVED 1"/4 ELO/ESFR IS UL LISTED UL LISTING EX4019(N)&EX4533(N) AGF MANUFACTURING COMPANY JOB NAME: - 100 Quaker Lane Malvern,PA 19355 USA ARCHITECT: Telephone:(610)240-4900 1 ENGINEER: Fax:(610)240-4906 • www.testandrain.com MADE IN U.S.A. CONTRACTOR: • State Pipe & Supply, Inc. THIS INFORMATION PROVIDED IS BASED ON ASTM GUIDELINES FOR WELDED PIPE . SPECIFICATIONS AND ASTM REQUIREMENTS. ACTUAL PIPE AND MATERIAL TEST REPORTS PROVIDED WOULD MEET OR EXCEED THESE GUIDELINES. TEST REPORTS WOULD PROVIDE SPECIFIC AND ACTUAL DETAILS CONCERNING THE MECHANICAL AND CHEMICAL PROPERTIES OF THE ACTUAL PIPE,AS WELL AS ADDITIONAL TESTS RESULTS REQUIRED BY ASTM. SCHEDULE 10 ** Black and Galvanized Steel ERW Pipe Pipe Size Test Pressure Nominal O.D. I.D. Weight/Foot psi 1" 1.315 1.097 1.410 700 1-1/4" 1.660 1.442 1.810 1200 1-1/2" 1.900 1.682 2.090 1200 2" 2.375 2.157 2.640 2300 2-1/2" 2.875 2.635 3.530 2500 3" 3.500 3.260 4.340 1290 4" 4.500 4.260 5.620 1000 5" 5.563 5.295 7.780 1010 6" 6.625 6.357 9.300 1020 8"" 8.625 8.249 16.960 780 *`8"wall thickness is 0.188, not SCH10 or 0.148"wall thickness. COMPOSITION AND PROPERTIES Chemical and mechanical properties requirements are as prescribed by applicable ASTM standards edition January 2006. Chemical Requirements, Percent(Product) C Mn P S Other Specification Grade max max max max ASTM A53 A 0.250 0.950 0.05 0.045 1 Residual elements max:Cu-0.40,Ni-0.40,Cr-0.40,Mo-0.15 and V-.08. These live elements combined shall not exceed 1%. Mechanical Properties-Tensile Requirements Strength-psi. Yield Tensile Specification Grade Min Max Min Max ASTM A53 _ A _ 30,000 - 48,000 - NOTE: Elongation requirements vary with nominal area of test specimen and specified minimum tensile strength of the steel grade. 9615 S. Norwalk Blvd., Santa Fe Springs,CA 90670 • (562)695-5555 ' FAX: (562) 692-1054 •www.statepipe.com • State Pipe & Supply, Inc• THIS INFORMATION PROVIDED IS BASED ON ASTM GUIDELINES FOR WELDED PIPE . SPECIFICATIONS AND ASTM REQUIREMENTS. ACTUAL PIPE AND MATERIAL TEST REPORTS PROVIDED WOULD MEET OR EXCEED THESE GUIDELINES. TEST REPORTS WOULD PROVIDE SPECIFIC AND ACTUAL DETAILS CONCERNING THE MECHANICAL AND CHEMICAL PROPERTIES OF THE ACTUAL PIPE,AS WELL AS ADDITIONAL TESTS RESULTS REQUIRED BY ASTM. SCHEDULE 40 Black and Galvanized Steel ERW Pipe Pipe Size Test Pressure Nominal O.D. I.D. Weight/Foot psi 1" 1.315 1.049 1.680 700 1-1/4" 1.660 1.380 2.270 1200 1-1/2" 1.900 1.610 2.720 1200 2" 2.375 2.067 3.660 2300 2-1/2" 2.875 2.469 5.800 2500 3" 3.500 3.068 7.580 2220 4" 4.500 4.026 10.800 1900 5" 5.563 5.047 14.630 1670 6" 6.625 6.065 18.990 1520 - 8" 8.625 7.981 28.580 1340 - COMPOSITION AND PROPERTIES Chemical and mechanical properties requirements are as prescribed by applicable ASTM standards edition January 2006. Chemical Requirements, Percent(Product) C Mn P S Other Specification Grade max max max max ASTM A53 A 0.250 0.950 0.05 0.045 1 Residual elements max:Cu-0.40,Ni-0.40,Cr-0.40,Mo-0.15 and V-.08. These live elements combined shall not exceed 1%. Mechanical Properties-Tensile Requirements Stren th-psi. Yield Tensile Specification Grade Min Max Min Max ASTM A53 A 30,000 - 48,000 - NOTE: Elongation requirements vary with nominal area of test specimen and specified minimum tensile strength of the steel grade. 9615 S. Norwalk Blvd., Santa Fe Springs,CA 90670 • (562) 695-5555 • FAX: (562)692-1054 • www.statepipe.com FireLock EZTM Rigid Coupling °OU © [LPCB VdS SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 009 (UL, FM) • STYLE 009V(UL, FM, VdS, LPCB) t,f :"'=A . The FireLock EZ Style 009 and Style 009V couplings are rigid,installation-ready couplings for r ` /� fire protection pipe joining. The coupling's unique design eliminates loose parts,insures consis- 4. p tent installation and provides substantial gains in productivity. IMPORTANT 11 FireLock EZ Style 009 and Style 009V couplings are recommended for use ONLY on fire protection systems. PATENTED STYLE 009 LISTINGS/APPROVALS tt§ The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Pipe Size Pressure Rating-psi Pipe Size Pressure Rating-psi Pipe Size Pressure Rating-psi Sch. Inches 5 11/4-2 175 175 ' 175 EZT 11/4-2 300 300 300 MT 1%-2 300 300 300 10,40 115-4 300 300 300 FF 1 V4-4 300 300 300 MLT 114-2 300 300 300 BLT 114-2 300 300 300 FLF 1 r14-4 N/A N/A 300 ST 1 V4-2 N/A N/A 300 DF 114-4 300 300 300 FLT 114-2 N/A N/A 300 STF 1 Y.-4 N/A N/A 300 DT 114-2 300 300 300 FLTL 114-2 N/A N/A 300 TF 214-4 N/A N/A 300 EF 114-4 175 175 175 GL 114-2 300 300 300 WLS 1 r'A-2 300 300 300 EL 11 -2 300 300 300 G5 114-2 175 175 175 WST 1 r'A-2 175 175 175 ET40 114-2 300 300 300 G7 1'/A-2 300 300 300 XL _ 114-2 1 300 300 300 EZF 3-4 300 300 300 MF 1 Vu-4 300 300 ! 300 STYLE 009V LISTINGS/APPROVALS t#§ Pipe Schedule Size Pressure Rating ri Nominal Size p Inches mm VdS LPC UL FM INI 76.1 mm — — 16 Bar 16 Bar 232 psi 232 psi 1Vi-4,76.1mm 16 Bar 16Bar —32-100 232 psi 232 psi 11 _ — 16Bar 20.7 Bar 32 232 psi 300 psi 1 Vz — _ 16 Bar 20.7 Bar 40 232 psi 300 psi 10,40 2 _ _ 16 Bar 20.7 Bar 50 232 psi 300 psi 3 _-- 16Bar 20.7 Bar_ 80 232 psi 300 psi 4 1 16 Bar 20.7 Bar 100 232 psi 300 psi t Listed/Approved for wet and dry pipe systems(>-40°F/-40°C).For rigid pipe connections in systems operating below 0°F/-18°C Victaulic recommends Style 005 FireLock rigid couplings with Grade"L"silicone gaskets. #Please refer to the Victaulic Field Installation Handbook(1-100)for details concerning when supplemental lubrication is required. §Style 009V couplings are VdS and LPC approved to 16 Bar/232 psi for wet and dry fire protection systems. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect -- Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. •Cta U I I C REV H ;c, ,,, 1 IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS 1 U.OU FireLock EZTM Rigid Coupling STYLE 009(UL, FM) STYLE 009V(UL, FM,VdS, LPCB) STYLE 009 DIMENSIONS Max. Max. Allow. Work. End Pipe End 0 Bolt/Nut Aprx. Size Press.* Load" Sep.t No -Size Dimensions-Inches/mm Wgt.Ea. _ Actual Pre-assembled Y F.-Z-1 final Outside (Stab in ? 'Size Dia. condition) Joint Assembled pp hes Inches psi Lbs. Inches Lbs. , . - 'rim mm kPa N mm Inches x Y x Y 2 kg j1 ►'1 1/. 1.660 300 649 0.10 2-a/e x 2 3.13 4.93 2.86 4.83 1.93 1.5 � 32 42.4 2068 2888 2.54 80 125 73 123 49 0.7 1 1.900 300 851 0.10 2-e/s x 2 3.38 5.16 3.11 5.07 1.86 1.7 40 48.3 2068 3787 2.54 86 131 79 129 47 0.8 STYLE 009 PRE-ASSEMBLED 2 2.375 300 ' 1329 0.12 2 'K x 21/2 3.88 5.81 3.59 5.68 1.86 1.9 (STAB IN CONDITION) 50 60.3 2068 5914 3.05 99 148 91 144 47 0.9 21 2.875 300 1948 0.12 4.38 6.21 4.08 6.10 1.87 2.0 V Z 65 73.0 2068 8668 3.05 2-3/e x 215 111 158 104 155 48 0.9 i 3 3.500 300 2886 0.12 2_'/a x 2 yi 5.06 6.68 4.73 6.43 1.90 4.3 80 88.9 2068 12842 3.05 129 170 120 163 48 2.0 .:.riflivall . a OA r! ! 4 4.500 300 4771 0.17 100 114.3 2068 21230 4.32 2-% x 21/2 6.46 8.64 6.00 8.34 2.10 2.3 164 220 152 212 53 1.0 Num, . '@ t Refer to notes below. STYLE 009 JOINT ASSEMBLED STYLE 009V DIMENSIONS Max. Max. Allow. Work. End Pipe End @ Bolt/Nut Aprx. Size Press.' Load* Sep.t No.-Size Dimensions--Inches/mm Wgt.Ea. Pre.assembled !N (Stab in nche condition) Joint Assembled s Inches psi Lbs. Inches Lbs. mm mm Pa N mm Inches X Y X Y Z kg � ►i 1 Y. 1.660 300 649 0.10 2_M10 x 57 3.14 4.84 2.85 4.65 1.91 1.6 J_ 32 42.4 2068 2888 2.54 80 123 72 118 49 0.7 1 Yz 1.900 300 851 0.10 2-M10 x 57 3.34 5.06 3.13 4.85 1.92 1.7 40 483 2068 3787 2.54 85 129 80 123 49 0.8 STYLE 009 PRE-ASSEMBLED 2 2.375 300 1329 0.12 2-M10 x64 3.91 5.66 3.61 5.47 1.94 2.1 (STAB IN CONDITION) 50 60.3 2068 5914 3.05 99 144 92 139 49 0.9 3.000 300 1948 0.12 4.57 6.46 4.17 6.18 1.96 2.3 Y r-Z 76.1 mm 76.1 2068 8668 3.05 2 M10 x64 116 164 106 157 50 1.1 3 3.500 300 2886 0.12 2-M10 x64 5.15 7.12 4.73 6.67 1.94 2.6 1:,flitalt‘ , 80 88.9 2068 12842 3A5 131 181 120 169 49 1.2 I� ` I �'� 4 4.500 300 4771 0.17 2 M10 x64 6.39 8.74 6.05 8.46 2.11 4.6 J _ 100 1143 2068 21230 4.32 162 . 222 154 215 54 2.1 * Working Pressure and End Load are total,from all internal and external loads, based on STYLE 009 JOINT ASSEMBLED standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications. See pages 3 and 4 of this document for Listed/Approved ratings on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. t The allowable pipe separation dimension shown is for system layout purposes only. FireLock EZ couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. @ Number of bolts required equals number of housing segments. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. gCtau'ge 10.60 2 REV H IPS CARBON STEEL PIPE—FIRE PROTECTION PRODUCTS 1 V.OV FireLock EZTM Rigid Coupling STYLE 009(UL, FM) STYLE 009V(UL, FM,VdS, LPCB) MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Housing Coating: • Orange enamel(North America) • Red enamel (Europe) Optional Coatings: • Hot dipped galvanized Gasket: • Grade"E"EPDM(Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited,and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services within the rated working pressure. Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. www.victaulic.com jctaulic' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.02007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. REV H 10.603 • • . . - : •;• •, ;•. t 111.011 FireLock EZTM Rigid Coupling STYLE 009(UL, FM) STYLE 009V(UL, FM,VdS, LPCB) GENERAL NOTES NOTE:When assembling FireLock EZ couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009 and Style 009V couplings, use FireLock No.006 end caps containing the"EZ" marking on the inside face or No.60 end caps containing the"QV EZ"marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V couplings. INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. 131111111111111111111111111111111 WCAS-78KHHG For complete contact information,visit www.victaulic.com 10.60 3999 REV H UPDATED 11/2007 iCtaUI•C' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 10.60 CARBON STEEL PIPE- GROOVED COUPLINGS V • . V ■ Reducing Coupling 0 © ® 0 LPCB ; SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 750 The Style 750 Reducing Coupling permits direct reduction on the piping run. Designed '" to replace two couplings and a reducing fitting,the Style 750 features a special reducing , gasket for pressure responsive sealing.A steel washer which prevents telescoping of the smaller pipe inside the larger pipe during vertical systems assembly is available upon request. %�I Skis imi Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-4542. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. . Housing Coating:Orange enamel • Optional: Hot dipped galvanized and others Gasket:(Specify choice*): • Grade"E" EPDM (All other sizes) EPDM(Green color code). Temperature range-30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code). Temperature range-20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional:Assembly Washer:Galvanized,carbon steel Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.O 2017 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ictau1ic' RFV I 06.08 1 CARBON STEEL PIPE-GROOVED COUPLINGS UO.U8 Reducing Coupling STYLE 750 DIMENSIONS Max.Work Allow.Pipe Bolt/Nutd Approx. Size Pressure' Max.End Load' End Sep.t Deflect.Fr.C., No-Size Dimensions-Inches/mm Wgt.Each ..a.�...-..- - .-... -... ____ ...,-. . Nominal Per 1 Pipe 1 1 , Size psi Lbs. Cplg. In./Ft. Lbs. Inches/mm kPa N Inches/mm Deg. mm/m Inches x AO Z kg 2 1 350 500 0-0.07 0.20 3.38 5.28 1.88 2.7 50 x 25 2410 2225 0-1.8 0'-57' 17 2-3/8 x 2 85 134 48 1.2 11 350 1000 0-0.07 0.20 3.38 5.28 1.88 2.0 40 2410 4450 0-1.8 0'-57' 17 2-3/8 x 2 85 134 48 1.0 244 2 500 2215 0-0.07 0.16 4.00 5.93 1.88 3.1 65 x 50 3450 9850 0-1.8 0'-47' 14 2-3/8 x 2 102 151 48 1.4 76.1 mm x 2 350 1550 0-0.07 0.16 4.38 6.63 1.88 4.6 50 2410 6900 0-1.8 0°-47' 14 2 1/2 x 214 111 168 48 2.1 3 2 350 1550 0-0.07 0.13 4.75 7.13 1.88 4.9 80 x 50 2410 6900 0-1.8 0'-39 11 2-44 x 214 121 181 48 2.2 21 500 3250 0-0.07 0.13 4.75 7.13 1.88 4.3 65 3450 14460 0-1.8 0'-39' 11 2-Sh x 244 121 181 48 2.0 - 350 1 2275 0-0.07 0.13 4.75 7.13 1.88 4.2 88.9mm x 76.1 mm 2410 10125 0 18 0'-39' 11 2-45x214 121 181 48 1.9 4 2 350 1550 0-0.13 0.28 6.25 8.90 2.25 8.1 100 x 50 2410 6900 0-3.2 1'-19' 25 2-5/8x31' 159 226 57 3.7 215 350 2275 0-0.13 0.28 6.25 8.90 2.25 8.6 '-65 2410 10125 0-3.2 ' 19 25 2-5/8 x 344 159 226 57 3.9 _ 3 500 4810 0-0.13 0.28 6.00 8.90 2.25 6.7 80 3450 21400 0-3.2 1'-19' 25 2-5/8 x 3'/. 152 226 57 3.0 _ 350 2475 0-0.13 0.28 6.25 8.90 2.25 6.9 114.3 mm x 76.1 mm 2410 11014 0-3.2 1'-19' 25 2-5/8 x 314 159 226 57 3.1 5 4 350 5565 0-0.13 0.22 7.18 10.70 2.13 11.2 125 x 100 2410 24765 0-3.2 1'-3 19 2-14 x 41i 182 272 54 5.1 6 4 350 5565 0-0.13 0.18 8.63 11.90 2.25 16.7 150 x 100 2410 24765 0-3.2 0'-52' 15 2 44 x 41a 181 302 57 7.6 5 350 8500 0-0.13 0.18 8.31 11.90 2.25 12.9 125 2410 37825 0-3.2 0'-52' 15 2-14 x 41. 211 302 57 5.9 165.1 mm x 4 350 5565 0-0.13 0.19 8.63 11.90 2.25 15.2 100 2410 24765 0-3.2 0'-55' 16 2-14 x 444 219 302 57 6.9 8 6 350 12000 0-0.13 0.13 10.81 14.88 2.50 22.4 200 x 150 2410 53400 0-3.2 0'-38 11 2-7/8x 5 275 378 64 10.2 219.1 mm x 165.1 mm 350 1625 0-0.13 0'-38' 0.13 2-7/8 x 5 10.75 14.88 2.50 23.2 2410 0-3.2 11 273 378 64 10.5 10 8 350 20450 0-0.13 0.9 13.12 17.26 2.62 31.4 273 x 219.1 2410 0-3.2 0°-25' 8 2-1 x 545 333 438 67 14.2 Style 750 Reducing couplings should not be used with end caps(#60)in systems where a vacuum may be developed.Contact Victaulic for details. Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size.WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1'1 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by 50%for 344-31/2720-90 mm;25%for 47100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. Ix Y o �Z� Y IIr��Z ►11 ri��cir IN � LLJ l ) ` ' P �� l 1 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. Ctci U I C 06.08 2 CARBON STEEL PIPE-GROOVED COUPLINGS UO.V8 Reducing Coupling STYLE 750 FLOW DATA HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables.All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING Equiv.Pipe Equiv.Pipe Sim tce th Site Length Nemnal Nominal % Sze Stn.Dia. Size Sm.Dia. Inchec/nlm Feetlm Inches/1nm Feet/m 2 1 5.9 1 2 2.7 50 x 25 1.8 25 x 50 0.8 1% 2.0 114 2 1.9 40 0.6 40 x 50 0.6 21 2 1.9 2 2% 1.0 65 x 50 0.6 50 x 65 0.3 76.1 mm x 2 1.9 76.1 mm 1.0 50 0.6 0.3 3 2 5.5 3 3.5 80 x 50 1.7 80 1.1 21/2 3.8 4 3.0 65 1.2 100 0.9 88.9mm x 76.1 mm 3.8 2rh x 3 2.5 1.2 65 80 0.8 4 2 6.0 4 3.0 . 100 x 50 1.8 100 0.9 65 6g 76.1 mm x 88.9mm 08 3 6.0 1143 mm 3.0 80 1.8 0.9 _ 114.3 mm x 76.1 mm 6.8 x 100 5 4 3.0 4 5 3.3 125 x 100 0.9 100 x 125 1.0 6 4 6.0 6 4.6 150 x 100 1.8 150 1.4 125 1.4 165.1 mm 4.4 1611mm x 4 6.0 5 x 6 2.3 100 1.8 125 150 0.7 8 6 7.3 6 8 6.0 200 x 150 22 150 x 200 1.8 219.1 mm x 165.1 mm 223 165.1 mm x 219.1 mm 1 65 10 8 8.7 8 10 6.3 273 x 219.1 2.65 219.1 x 273 19.2 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. sctaUllc. RFV I 06.083 CARBON STEEL PIPE GROOVED COUPLINGS • • V • Reducing Coupling STYLE 750 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. III In11IllIIIINIIIIIIIIIIiullll1III WCAS-6UPKD7 For complete contact information,visit www.victaulic.com 06.08 1536 REV I UPDATED 6/2008 .CtoIUl1C` VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 06.08 CARBON STEEL PIPE GROOVED COUPLINGS I • • Flexible Coupling Q © Q LPCB VNIIPO SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 75 Style 75 is available where moderate pressures are expected or weight considerations are a factor. Up to 50%lighter in weight than the Style 77, the Style 75 coupling is recommended for service up to 500 psi/3450 kPa depending on size. Housings are cast in two identical pieces in all sizes. Hot-dip galvanized and special coatings are available for all sizes. The Victaulic standard flexible coupling offering for grade"EHP"or"T"gaskets is the Style 177 installation-ready flexible coupling. For all available sizes,the Style ��������� 177 is the standard flexible coupling Victaulic supplies in North America for piping , N. N.systems using Grade"EHP"or"T"gaskets.Contact Victaulic for further details. Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating:Orange enamel. • Optional: Hot dipped galvanized and others. Gasket: (specify choice*) • Grade"E"EPDM EPDM(Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrite Nitrile(Orange color code). Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range;except hot,dry air over+140°F/+60°C and water over +150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. NOTE:Additional gasket styles are available.Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.. iCtaul.c RFV M 06.05 1 CARBON STEEL PIPE-GROOVED COUPLINGS U O.U 3 Flexible Coupling STYLE 75 DIMENSIONS Max.Work Allow.Pipe Bolt/Nut® Approx. Size Pressure• Max.End Load• End Sep.t Deflect.Fr.Cit No-Size Dimensions-Inches/mm Wgt.Each Nominal Size Di er Per Pipe t Inches Inches psi lbs. Inches Cplg. In./Ft. L` mm mm kPa N mm Deg. mm/m Inches 1 1.315 500 680 0-0.06 0.57 2.38 427 1.77 1.3 25 33.4 3450 3025 0-1.6 2'-43' 48 2-i4 x 2 61 108 45 0.6 114 1.660 500 1080 0-0.06 0.45 2.68 4.61 1.77 1.4 32 42.2 3450 4805 0-1.6 2'-10 38 2-'/"x 2 68 117 45 0.6 T 1' 1.900 500 1420 0-0.06 0.40 2.91 4.82 1.77 1.5 40 483 3450 6320 _ 0-1.6 1'-56' 33 2-�%i x 2 74 122 45 0.6 2 2.375 500 2215 0-0A6 0.32 3.43 5.22 1.88 1.7 50 603 3450 9860 0-1.6 1'-31' 26 2-s 1/4 ex2 87 133 48 0.8 2 h 2.875 500 3245 0-0.06 0.26 3.88 5.68 1.88 1.9 65 73.0 3450 14.440 0-1.6 1'-15' 22 2-3/e x 2 98 144 48 0.9 3.000 500 3535 0-0.06 0.26 4.00 5.90 1.88 1.9 76.1 mm 76.1 3450 15730 0-1.6 1'-12 22 2-3/e x 2 102 150 48 0.9 3 3.500 500 4800 0-0.06 0.22 4.50 7.00 1.88 2.9 80 88.9 3450 21360 0-1.6 1'-2 18 2-1/2 x 244 114 178 48 1.3 31/2 4.000 500 6300 0-0.06 0.19 5.00 7.50 1.88 2.9 90 101.6 3450 28035 0-1.6 0'-54' 16 2-1/4 x 214 127 191 48 1.3 4 4.500 500 7950 0-0.13 0.34 5.80 8.03 2.13 4.1 100 114.3 3450 35380 0-3.2 1'-36' 28 2-1h x 214 147 204 54 1.9 4.250 450 6380 0-0.13 0.35 5.55 7.79 2.13 3.7 108.0 mm 108.0 3100 28395 0-3.2 1'-41' 29 2-12x70.0 141 198 54 1.7 41 5.000 450 8820 0-0.13 0.25 6.13 9.43 2.13 5.5 120 127.0 3100 39250 0-3.2 1'-26' 21 2-s/s x 314 156 240 54 2.5 5 5.563 450 10935 0-0.13 0.27 6.88 10.07 2.13 5.8 125 141.3 3100 48660 0-3.2 1'-18' 23 2-1/4 x 3 Yi 175 256 54 2.6 5.250 450 9735 0-0.13 0.28 6.55 937 2.13 6.0 133.0 mm 133.0 3100 43325 0-3.2 1'-21 24 2-16 x 82.5 166 238 54 2.7 5.500 450 10665 0-0.13 0.28 6.80 9.59 2.13 6.3 139.7 mm 139.7 3100 47460 0-3.2 1'-18' 24 2-%x3% 173 244 54 2.9 - 6.000 450 12735 0-0.13 0.21 7.38 10.48 1.88 6.2 152.4 mm 152.4 3100 56670 0-3.2 1'-12' 18 2-%x 314 187 266 48 2.8 6 6.625 450 15525 0-0.13 0.23 8.00 11.07 2.13 7.0 150 168.3 3100 69085 0-3.2 1'-5 18 2-s/e x 314 203 281 54 3.2 6.250 450 13800 0-0.13 0.24 7.63 10.49 2.13 6.8 159.0mm 159.0 3100 61405 0-3.2 1'-9' 20 2-16 x 82.5 194 266 54 3.1 8 8.625 450 26280 0-0.13 0.18 1034 13.97 2.32 12.4 200 219.1 3100 116945 0-3.2 0'-50' 14 2-3/4 x41/4 263 355 59 5.6 " Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 3/4-31/2"/20-90mm;25%for 47100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. Y ► k-zi r�:�, etip I gal F r4 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.. jctaUlla 06.05 2 REV M :;•► • •E_ IS • • ► 91.A 1s Flexible Coupling STYLE 75 WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. For complete contact information,visit www.victaulic.com 06.05 1470 REV M UPDATED 2/2011 ictaulac VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 06.05 IPS CARBON STEEL PIPE- FIRE PROTECTION PRODUCTS 1 0"04-1 VICTAULIV IS AN ISO 9001 CERTIFIED COMPANY Style 744 FireLock® Flange Adapter �/jCP/LIS with Vic-Plus TM Gasket System Gasket System PRODUCT DESCRIPTION Style 744 FireLock Flange adapter is designed for directly incorporating flanged components with ANSI CL. 125 or CL. 150 bolt hole patterns into a grooved pipe system. Sizes 2 -8"(50 - 200 mm)are hinged for easy handling with integral end tabs which facilitate assembly. '. The design incorporates small teeth inside the key shoulder I.D.to prevent rotation. ti ` Because of the outside flange dimension, FireLock Flange adapters should not be used on FireLock fittings.When wafer or lug-type valves are used adjoining a Victaulic fitting,check disc dimensions to assure proper clearance. FireLock Flange adapters should not be used as anchor points for tie-rods across nonrestrained joints. Mating rubber faced flanges,valves,etc., require the use of a FireLock Flange washer. 2-8"Sizes FireLock Flange adapters with Vic-Plus gaskets do not require lubrication.The gasket must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. _.i. Style 744 FireLock Flange Adapters with the Vic-Plusn' Gasket System are designed and • 'rU recommended for use ONLY on fire protection systems. Ali Vic-Plus Gasket System: MI= Victaulic5 now offers a gasket system which requires no field lubrication on wet pipe systems. The Vic- 1� I ��, PIusTM' System (patented) is dry,clean, and non-toxic. It reduces assembly time substantially and eliminates the mess and chance of over-lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook(1-100)for supplemental lubrication requirements. u I Illl �4> �■■, See Victaulic (Exaggerated for clarity) publication 10.01 for details. DIMENSIONS Style 744 Sealing Sizes 2-8"(50-200 mm) Surface Dimensions Size Inches/men Ytcheslmillirneters ANSI Class 125 and 150 Flange Actual Yo End w gt.• Z Nominal Outside Press.' Load' No. Bolt Each Diameter Diameter PSI Lbs. Bolts t Sae t "A" "B" Lbs. O Inimm tniean kPa N Req'd inches Nlatt 13‘111A1 W X Y Z kg Q Q 2 2.375 175 775 2.38 6.75 6.00 4.75 0.75 2.7 04 011 50 60,3 1200 3450 4 5/8 X 23/4 60 87 172 152 121 19 1,2 �/� Y W 21/z 2.875 175 1135 4 /e X 3 2.88 3.91 7.88 7.00 5.50 0.88 4.2 � n. i65 73.0 1200 5050 73 99 200 178 140 22 1 9 3 3.500 175 1685 3.50 4.53 8.44 7.50 6.00 0.94 4.8 �O O CV O' 80 88.9 1200 7500 4 18 X 3 89 115 214 191 152 24 2,2 4 4.500 175 2780 4.50 5.53 9.94 9.00 7.50 0.94 7.1 100 114,3 1200 11045 8 /8 X 3 114 141 252 229 191 24 3.2 Note:Gray area of mating face must 5 5.563 175 4250 5.56 6.71 11.00 10.00 8.50 1.00 8.3 be free from gouges,undulations or 8 3/,x 31/2 deformities of any type for effective 125 141,3 1200 18920 141 171 279 254 216 25 3,8 sealing. 6# 0 66823 1200 6030 6840 8 1/4 X 31/2 6.63 68 198 12.00 30 11.00 9.40 1.00 9.3 8# 8.625 175 10219 ' 8.63 9.94 14.63 13.50 11.75 1.13 13.9 200 219.1 1200 45475 8 /,X 3/z 219 252 372 343 298 29 6,3 'Refer to notes below. 1Total bolts required to be supplied by installer.Bolt sizes for conventional flange-to-flange connection.Larger bolts are required when Vic-Flange adapter is utilized with wafer-type valves. #Not available with Vic-Plus gasket system.Lubrication is required. NOTES Working Pressure and End Load are total,from all internal and external loads,based on standard weight steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. Style 744 FireLock Flange adapters provide rigid joints when used on pipe with standard roll or cut groove dimensions and consequently allow no linear or angular movement at the joint. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. •REGISTERED TRADEMARK OF VICTAUUC-e COPYRIGHT 2004 VICTAULIC-PRINTED IN U.S.A. 1477 REV D • Victaulic Company 01 America•Phone:1-800-PICK-VIC(1-800-742-5842)•Fax.610-250-8817•e-mail:pickvic@victaulic.com Victaulic Company of Canada•Phone:905-884-7444•Fax:905-884-9774•e-mail:viccanada@victaulic.com Victaulic Europe•Phone:32-9-381-1500•Fax:32-9-380-4438•e-mail:viceuro@victaulic.be Victaulic America Latina•Phone:610-559-3300•Fax:610-559-3608•e-mail:vical@victaulic.com eta U I i C Victaulic Asia Pacific•Phone:65-6235-3035•Fax:65-6235-0535•e-mail:vicap@victaulic.com 1 0.04 VIC-FLANGE ADAPTER NOTES The Style 744(2-8"/50-200 mm)design incorporates small teeth inside the key shoulder I.D.to prevent rotation. 2 FireLock Flange adapter should not be used on FireLock fittings.When wafer or lug-type valves are used adjoining a Victaulic fitting, check disc dimensions to assure proper clearance. 3 FireLock Flange adapters should not be used as anchor points for tie-rods across nonrestrained joints. Mating rubber faced flanges,valves,etc.require the use of a FireLock Flange washer. 4 Area A-B noted in the above drawing must be free from gouges,undulations or deformities of any type for effective sealing. s FireLock Flange adapter gaskets must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. s Flange Washers:FireLock Flange adapters require a smooth hard surface at the mating flange face for effective sealing. Some applications for which the Vic-Flange adapter is otherwise well suited do not provide an adequate mating surface.In such cases,it is recommended that a metal Flange Washer be inserted between the FireLock Flange adapter and the mating flange to provide the necessary sealing surface. Typical applications where a Flange Washer should be used are: A When mating to a serrated flange:a standard flat flange gasket should be used adjacent to the serrated flange and then the Flange Washer is inserted between the FireLock Flange adapter and the flange gasket. Et When mating to a wafer valve:where typical valves are rubber lined and partially rubber faced(smooth or not), the Flange Washer is placed between the valve and the FireLock Flange adapter. c When mating a rubber faced flange:the Flange Washer is placed between the FireLock Flange adapters and the rubber faced flange. D When mating AWWA cast flanges to IPS flanges:the Flange Washer is placed between two FireLock Flanges. The hinge points must be oriented approximately 90°to each other. If one flange is not a FireLock Flange adapter(e.g.flanged valve),then a standard flat flange gasket must be placed - adjacent to that flange and the Flange Washer inserted between the flange gasket and the FireLock • Flange adapter. E When mating to components(valves,strainers,etc.)where the component flange face has an insert: - follow the same arrangement as in Application 1. F When mating to a Series 705-W Butterfly valve, Style 744 may only be used on one side of the connection. When ordering Flange Washers,always specify product style(Style 744)and size to assure proper Flange Washer is supplied. MATERIAL SPECIFICATIONS Flange Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Coating: Black enamel • Optional: Hot dipped galvanized Bolts/Nuts: Supplied by installer Gasket: • Grade"E" EPDM-Type A Vic-Plus Gasket System A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Ap- proved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated work- ing pressure using the Grade"E"Type A Vic-Plus Gasket System,requiring no field lubrication for most installation conditions. A Standard gasket approved for dry pipe systems to-40°F(-40°C).Based on"typical'pipe surface conditions,supplemental lubricant is recommended for services instated below 0°F(-18°C)and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water.Supplemental lubrication may also be rquired on pipe with raised or undercut weld scams or pipe that has voids and/or cracks at the weld seams. This product shall be manufactured by Victaulic Company.At products to be instated in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. 2 Style 744 FireLock® Flange Adapter FireLock® Fittings LPCB Vds L L See Victaulic publication 10.01 for details • FireLock®products comprise a unique system specifically designed for fire protection . Iltr„r services. FireLock full-flow elbows and tees feature CAD-developed, hydrodynamic design,affording a shorter center-to-end dimension than standard fittings.A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Victaulic IPS-sized couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. Victaulic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Style 005 couplings. MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12. Fitting Coating: • Orange enamel. • Red Enamel in EMEA-I. • Optional: Hot dipped galvanized. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date _ Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. uctaL Id REV I 10.03 1 IPS CARBON STEEL PIPE -FIRE PROTECTION PRODUCTS 1 V.V., FireLock® Fittings DIMENSIONS CtoE I to ET- p I C<toE p p . .i,l/ ii- 11 "r"` 11 C --lb- I NO.001 NO.003 NO.002 NO.006 N .001 No.00 i `1,. 'rt`1 V1. l.. Size .I! n Nominal Actual Approx. Approx. Approx. Approx. Size Outside Diameter C to E Weight Each C to E Weight Each C to E Weight Each Thickness"T" Weight Each Inches Inches Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs. mm mm mm kg mm kg mm kg mm kg 1 V. 1.660 _ _ _ - _ 0.8 0.3 32 42.4 21 0.1 11 1.900 - - - - - 0.82 0.4 40 48.3 - - - - - 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 50 603 70 0.8 51 0.8 70 1.1 22 0.3 21/2 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 65 73.0 76 1.4 57 1.0 76 1.6 22 0.5 76.1 mm 3.000 3.00 3.30 225 2.4 - - 76.1 76 1.5 57 1.1 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 80 88.9 86 1.8 64 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 - - 108.0 102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 100 1143 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 _ 125 141.3 124 5.7 83 3.8 124 7.1 25 1.9 159mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 - - 158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 183 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3 89 5.3 140 103 25 2.7 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. .Ctalull� 10.03 2 REV IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS j V■V3 FireLock® Fittings FLOW DATA Frictional Resistance Size Equivalent Feet/meters of Straight Pipe t • Actual 02 III Nominal Outside • _ t ght Tee Size Diameter ------------------ --- Inches Inches No.001 1 No.003 mm mm 90 Elbow 45 Elbow Branch Ron 11/4 1.660 1.5 0.8 3.7 15 32 42.4 0.5 02 1.1 0.5 11/2 1.900 2.2 1.1 5.5 22 40 48.3 0.7 0.3 1.7 0.7 2 2.375 3.5 1.8 8.5 3.5 50 60.3 1.1 0.5 2.6 1.1 214 2.875 4.3 2.2 10.8 43 65 73.0 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 45 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 0.8 4.0 1.5 108mm 4.250 6.4 32 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 1143 2.1 1.0 4.9 2.1 5 5.563 85 4.2 21.0 8.5 125 141.3 2.6 1.3 6.4 2.6 159mm 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 1683 3.0 1.5 7.6 3.0 8 8.625 13.0 5.0 33.0 13.0 - 200 219.1 4.0 1.5 10.1 4.0 t The flow data listed is based upon the pressure drop of Schedule 40 pipe. www.victaulic.com �Ctaulicr VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.O 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I 10.03 3 • ..:�� • - - :• •, •:.. t wJR0/4' FireLock® Fittings GENERAL NOTES NOTE:When assembling FireLock EZ couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009/009V/009H couplings, use FireLock No.006 end caps containing the"EZ" marking on the inside face or No.60 end caps containing the"QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H couplings. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 10.03 1539 REV I UPDATED 2/2010 ctaulic+° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. \V/ 10.03 Ductile Iron . rea e Fittings ._.......,.: .• ......._....._ .,.. „, .ft ____......... _ L,.. ,... ., • ti i ile. .... ' 3 . ..., _ __. .„. .... . ,...„ , .... . ... .. .'..,_ • , _4,- i ^ • • i SMITHCOOPER I N T E R N A T I O N A L SMITH., CooPE Rs I N T E R N A T I O N A L Ductile Iron Threaded Fittings Specifications • The © branded Ductile Iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP • Ductile Iron castings conform to ASTM A536 C 03 US • Fitting dimensions conform to ASME B16.3 LISTED • Bushings and plugs conform to ASME B16.14 • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2000 and ISO 14001 Temperature Working Pressure, Nonshock PSIG Degrees F 300# Class Threaded Fittings -20 to 100 500 150 500 200 480 250 460 300 440 350 420 400 400 450 380 500 360 550 340 600 320 650 300 • • Xi` Z.) 1✓i Ductile Iron Fittings - Class 300 UL/FM I iiuv,ar PLIJ; c ® uS APPROVED - Fig. 35E 3- 90°Elbow LISTED A ~� Size Part Number A Packing Weight r IN IN Inner Master - LB 1/2 35E 3004 1.13 100 200 0.2 ± �� 3/4 35E 3006 1.31 70 140 0.3 w;'• %A 1 35E 3010 1.50 40 80 0.5 $n1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3- 90°Reducing Elbow i B Size Part Number A B Packing Weight 11111 rr IN IN IN Inner Master LB 1 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 A 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 '■■, 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 ' 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 ' 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 •' 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 ; Fig. 35F 3-45°Elbow Size Part Number A Packing Weight III A IN IN Inner Master LB , 1/2 35F 3004 0.88 150 300 0.2 3/4 35F 3006 0.98 80 160 0.3 I 14 II -� 1 35F 3010 1.13 40 80 0.5 1-1/4 35F 3012 ' 1.29 25 50 0.7 �i IA 1-1/2 35F 3014 1.44 20 40 1.0 1 _ 2 35F 3020 1.69 li/P 20 5. 1.6 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size A Packing Weight __ Part Number ah ■• IN IN Inner Master LB � i A 1/2 35T 3004 1.13 80 160 0.3 a .I 3/4 351 3006 1.31 30 60 0.5 �_M_� 1 35T 3010 1.50 25 50 0.7 moot..,.,., 1-1/4 35T 3012 1.75 10 20 1.1 A A 1-1/2 351 3014 1.94 10 20 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 1 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(3Z3)890-4456 • www.smithcooper.com J Ii Ductile Iron Fittings - Class 300 UL/FM u.rrvtIA : cel us 4401110. LISTED APPROVED Fig. 35RT3-Reducing Tee • Size A B C Weight �t101 IN Part Number IN IN IN Inner Master LB C 314 x 1/2 35RT3006004 1.20 1.20 1.22 60 Packing 1 i I 1 x 1/2 35RT3010004 1.26 1.26 1.36 30 60 0.6 1_ -� - �I 1 x 112 x 1 35RT3010004010 1.50 1.36 1.50 30 120 0.4 60 0.6 1x3/4 35RT3010006 1.38 1.38 1.45 25 50 0.6 1 x 3/4 x 3/4 35R13010006006 1.38 1.31 1.45 35 70 0.6 B A 1x3/4x1 35RT3010006010 1.50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 35RT3012004 1.34 1.34 1.53 20 40 0.8 1-1/4 x 1/2 x 1-1)4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4 x 3/4 35RT3012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4 x 1 35RT3012010 1.58 1.58 1.67 15 30 1.0 1-1/4 x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35RT3012010006 1.45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1-1/2 x 1/2 x 1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35R13014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 3/4 35RT3014006 1.52 1.52 1.75 16 32 1.1 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2 1-1/2 x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-1/2 x 1 x 1/2 35RT3014010004 1.44 1.25 1.69 20 40 0.8 - 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35RT3014010010 1.65 1.50 1.80 16 32 1.0 1-1/2 x 1 x 1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2 0 1-1/2 x 1 x 1-1/2 35RT3014010014 1.94 1.80 1.94 12 24 1.3 1-1/2 x 1-1/4 35RT3014012 1.82 1.82 1.88 12 24 1.4 U 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 C 1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0 T 1-1/2 x 1-1/4 x 1 35RT3014012010 1.65 1.58 1.80 16 32 1.1 1-1/2 x 1-1/4 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3 1-1/2 x 1-1/4 x 1-1/2 35RT3014012014 1.94 1.88 1.94 14 28 1.4 L 2 x 1/2 358T3020004 1.49 1.49 1.88 10 20 1.5 E 2 x 3/4 35RT3020006 1.60 1.60 1.97 10 20 1.6 2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4 35R13020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1/4 x 2 35RT3020012020 2.25 2.10 2.25 8 16 2.0 2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2 x 1-1/2 x 1/2 35R13020014004 1.49 1.41 1.88 10 20 1.3 2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 1.5 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee 1 Size Part Number A B C Packing Weight JOWL, I IN IN IN IN Inner Master LB • C 3/4 x 1 35BT3006010 1.45 1.45 1.37 30 60 0.6 I1111.1 1 1 x 1-1/4 35813010012 1.67 1.67 1.58 20 40 0.9 1 x 1-1/2 35BT3010014 1.80 1.80 1.65 15 30 1.0 1-1/4 x 1 x 1-1/2 35813012010014 1.88 1.80 1.82 15 30 1.2 A B 1-1/4 x 1-1/2 35BT3012014 1.88 1.88 1.82 15 30 1.3 1-1/4 x 2 35813012020 2.10 2.10 1.90 10 20 1.6 1-1/2x1-1/4x2 35BT3014012020 2.16 2.10 2.02 10 20 1.8 1-1/2 x 2 358T3014020 2.16 2.16 2.02 8 16 1.8 SMITH-COOPER INTERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.sminccooper.com lj('t1-.. g 1 uct>< a ron 'flings - ass III I MAW PLU c ® us Fig. 35CP3-Straight Coupling with Ribs LISTED APPROVED - A Size Part Number A Packing Weight IN IN Inner Master LB • 1/2 35CP3004 1.38 200 400 0.1 3/4 35CP3006 1.63 100 200 0.2 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35CP3014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3-Hex Reducing Coupling IP Size Part Number A Packing Weight ,3 _ IN IN Inner Master LB wi� A 1 x 112 1 35RC3010004 1.69 80 160 0.3 - x 314 35RC3010006 1.69 60 120 0.4 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3-Hex Bushing Size Part Number A Packing Weight B IN IN Inner Master LB 1 x 1/2 35HB3010004 1.06 180 360 0.2 1 x 3/4 35H83010006 1.06 180 360 0.1 I'll! A 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 1 1-1/2 x 1 35HB3014010 1.25 75 150 0.4 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 2 x 1 35HB3020010 1.38 40 80 0.6 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 Fig. 35SP3-Square Head Plug Size Part Number A Packing Weight IN IN Inner Master LB \ - 1/2 35SP3004 0.94 600 1200 0.07 3/4 35SP3006 1.12 350 700 0.1 f111 IA 1 35SP3010 1.25 200 400 0.1 I 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat A Size A Packing Weight �:_ Part Number fr ` ���u� IN IN Inner Master _ LB -.h 1 35U 3010 2.19 20 40 1.0 1-1/4 35U 3012 2.50 15 30 1.2 1-1/2 35U 3014 2.62 10 20 1.7 �� 2 35U 3020 3.12 6 12 2.4 kw I SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com J i�;� Ductile Iron Fittings - Class 300 UL/FM I ri+ury rrr i.'J c14) uS 4410,' Fig. 35X 3- Cross LISTED APPROVED �-)I(-A Size A Packing Weight • Part Number IN Inner Master LB we �i�.� IA IN 1 35X 3010 1.50 20 40 0.9 t l I J 1-1/4 35X 3012 1.75 12 24 1.4 __ % i ill -A 1-1/2 35X 3014 1.94 8 16 1.8 2 35X 3020 2.25 6 12 2.8 B F B Fig. 35RX3-Reducing Cross PERO Size Part Number A B Packing Weight tuI1A IN IN IN Inner Master LB 1-1/4 x 1 35RX3012010 1.67 1.58 15 30 1.7 1-1/2 x 1 35RX3014010 1.80 1.65 12 24 1.4 IA 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 Fig. 35C 3- Cap Size Part Number A Packing Weight ... IN IN Inner Master LB 1 A 1/2 35C 3004 0.87 300 600 0.1 0.1 ii. 1 3/4 35C 3006 0.97 200 400 �\ - 1 35C 3010 1.16 1 10 220 0.2 1-1/4 35C 3012 1.28 70 140 0.4 1-1/2 35C 3014 1.33 50 100 0.5 2 35C 3020 1.45 25 50 0.8 2-1/2 35C 3024 1.70 18 36 1.6 Fig. 35BC3-Beam Clamp Size A Packing Weight AI a iiim Ell IN IN Inner Master LB 3/8 358C3003 3.75 100 200 0.3 1 Part Number ■I 1/2 - 35BC3004 0.75 80 160 - 0.5 a SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Warranty and Limitations of Liability SMITH-COOPER INTERNATIONAL(SCI)warrants to its initial purchaser only,that its products which are delivered to this initial purchaser will be of the kind described in the order or price list and will be free of defects in workmanship or material for a period of five years from the date of delivery to our initial purchaser. Should any failure to conform to this warranty appear within five years after the date of the initial delivery to our initial purchaser,SCI will,upon written notification thereof and substantiation that the goods have been stored,installed,maintained and operated in accor- dance with recognized engineering and piping practices and industry standards,correct such defects by suitable repair or replacement (which alternative shall be at the discretion of SCI)of product at SCI's own expense upon return of the defective part to SCI. In the event that SCI elects to replace the defective product,SCI shall pay up to$50 per defective product for total cost of replacement. In the event of multiple claims,such payment shall he no greater than$1,000 for each installation project. This warranty applies only during normal use that meets the above referenced conditions of installation and operation and is absolutely void if the product has been damaged after purchase or if it has been misused,repaired,altered or modified in any manner whatsoever. SCI shall not warranty any of its products if any portion of the product including without limitation,any component,gasket,housing or bolt has been modified,altered,remanufactured or replaced in any manner by any customer,user of the product or third party. Correction of non-conformities,in the manner and for the period of time provided above,shall constitute fulfillment of all liabilities of SCI to our initial purchaser,with respect to the goods,whether based on contract,negligence,strict tort,or otherwise. It is the intention of SCI that no warranty of any kind,whether expressed or implied shall pass through our initial purchaser to any other person or corpora- tion. No returns will be allowed unless prior written permission of SCI is first obtained. Buyers shall be responsible for all costs of transporta- tion as well as a restocking charge. This warranty is exclusively for the benefit of the initial purchaser of this product from SCI and,except to the extent prohibited by ap- plicable law,the foregoing warranty is in lieu of all other warranties,express or implied,including but not limited to warranties of fitness or merchantability. LIMITATIONS OF LIABILITY:SCI shall not under any circumstances be liable for special or consequential damages such as,but not limited to damage to loss of other property or equipment,loss of profits or revenue,cost of capital,cost of purchased or replacement goods, claims of customers of our initial purchaser,any labor cost for repair or replacement of the product or damage caused by the product. The remedies of our initial purchaser,and all others,set forth herein are exclusive,and the liability of SCI with respect to same shall not, except as expressly provided herein,exceed the price of the SCI products on which such liability is based. ©2010 Smith-Cooper International" 34 SNSKIFIC-IERHIRITIERVERHIEDRAINDIQM.R,64 'FGUL.EIFS1EE800(1/1 f4/0007f. 'FP1'tllM32M)0944343fP 'w\wna„itathtbopapenul m aL • ,.3 ice' s C3 4?irr -Ci)4,11,R Industrial PVF :7 _ - Malleable Iron • Cast Iron • Ductile Iron Bronze Fittings Flanged Fittings Forged Steel Fittings Merchant Steel COOPLETS® Nipples Lead Free Valves Ball Gate Globe Check Butterfly Straight Stops Hose Bibbs/Sillcocks Boiler Drains Specialties • Stainless Steel 150# Fittings 3000# Forged Fittings Weld Fittings Sanitary Fittings Compression Fittings Flanges Nipples Pipe &Tubing Valves Grooved Couplings Fittings Valves COOPLET®Adapter Nipples SMITHCOOPEIR® I N T E R N A T I O N A L Toll Free 800-766-0076 Fax 323-890-4456 www.smithcooper.com 07 T na A.,rrsai ('A Atlanta nA - Var •n»linor WA rhie•arfn TT VSR P PTURVANE TYPE WATERFLOW a The Symbol of Protection ALARM SWITCH WITH RETARD UL,CUL and CSFM Listed,FM Approved,LPCBApproved,For CE Marked(EN 12259-5)/VdS Approved model use VSR-EU • - - , Service Pressure: 450 PSI(31 BAR)-UL Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)-UL Maximum Surge: 18 FPS(5.5 m/s) Contact Ratings: Two sets of SPDT(Form C) 10.0 Amps at 125/250VAC - 2.0 Amps at 30V DC Resistive ? 10 mAmps min.at 24V DC iik! Conduit Entrances: Two knockouts provided for 1/2"conduit. Individual switch compartments suitable 010 _- for dissimilar voltages. Environmental Specifications: • NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature Range: 40°F-120°F,(4.5°C-49°C)-UL • Non-corrosive sleeve factory installed in saddle. Service Use: Automatic Sprinkler NFPA-13 Specifications subject to change without notice. One or two family dwelling NFPA-I 3D Ordering Information Residential occupancy up to four stories NFPA-I 3R National Fire Alarm Code NFPA-72 Nominal Pipe Size Model Part Number 2" DN50 VSR-2 1144402 . 2 1/2" DN65 VSR-2 1/2 1144425 WA R N I N G . 3" DN80 VSR-3 1144403 • Installation must be performed by qualified personnel and in 3 1/2" - VSR-3 1/2 1144435 accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious 4" DN100 VSR-4 1144404 injury or death could result. 5" - VSR-5 1144405 • Risk of explosion.Not for use in hazardous locations. Serious 6" DNI50 VSR-6 1144406 injury or death could result. 8" DN200 VSR-8 1144408 Optional: Cover Tamper Switch Kit,stock no.0090148 CAUTION Replaceable Components:Retard/Switch Assembly,stock no. 1029030 Waterflow switches that are mon itoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air,or short retard times. General Information Enclosure The Model VSR is a vane type waterflow switch for use on wet sprinkler The VSR switches and retard device are enclosed in a general purpose, systems. It is UL Listed and FM Approved for use on steel pipe; die-cast housing. The cover is held in place with two tamper resistant schedules 10 through 40,sizes 2" thru 8"(50 mm thru 200 mm). LPC screws which require a special key for removal. A field installable approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering cover tamper switch is available as an option which may be used Information chart. to indicate unauthorized removal of the cover. See bulletin number The VSR may also be used as a sectional waterflow detector on large 5401103 for installation instructions of this switch. systems.The VSR contains two single pole,double throw,snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM(38 LPM)or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5401146-REV L PAGE 1 OF 4 3/09 VSR P POTTER VANE TYPE WATERFLOW 8 The Symbol of Protection ALARM SWITCH WITH RETARD _ Installation (see Fig. 1) . These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6"(15 cm)of a fitting which changes the direction of the waterflow or within 24" (60 cm)of a valve or drain. NOTE: Do not leave cover off for an extended period of time. Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow.Take care not to damage the non-corrosive bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque (see the chart in Fig. 1).The vane must not rub the inside of the pipe or bind in any way. A CAUTION ' Do not trim the paddle.Failure to follow these instructions may prevent the device from operating and will void the warranty. Fig. 1 Retard Adjustment DO NOT LEAVE COVER OFF FOR ,,,i.. ./ r AN EXTENDED PERIOD OF TIME The delay can be adjusted by rotating the retard adjustment knob from ��1 0 to the max setting(60-90 seconds).The time delay should be set at / '' I�1I' ill. ����♦ \�~. the minimum required to prevent false alarms 'g`\ J TIGHTEN NUTS I ..\,\-i:, <-fir +I( III ALLERNAI'ELY 4;-� I-�.--- CAUTION J,at:i I I Hole must be drilled perpendicular to the pipe and vertically centered. /` Refer to the Compatible Pipe/Installation Requirements chart for size. . Correct Incorrect ' , MOUNT ON PIPE L V/ Y, ARROW ON SADDLE \J /� O Nro,. � POINT S IN DIRECTION - -( -) d OF WATERFLOW f\ �/ 1111 - - /1' I I�1 I%I ROLL PADDLE IN OPPOSITE DIRECTION ADAPTERN ,� ADAPTER DIRECTION OF OF WATERFLOW Vi WATERFLOW \I P','gwater activates -.4 }- - 20mm s2mm MAX. device in one direction only.) DN50 ONLY IV USE(2)5180162 ADAPTERS AS SHOWN ABOVE DWG. 1116-11 [M.I.6-I F Compatible Pipe/Installation Requirements Model Nominal Pipe Nominal Pipe Pipe Wall Thickness Hole Size U-Bolt Nuts Size O.D. Schedule 10(UL) Schedule 40(UL) BS-1387(LPC) DN(VDS) Torque inch mm inch mm inch mm inch mm inch mm inch mm inch mm fl-lb n-m VSR-2 2 DN50 2.375 60.3 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 VSR-2 1/2 2.5 - 2.875 73.0 0.120 3.05 0.203 5.16 - - - - 1.25+.125/-.062 33.0±2.0 VSR-2 1/2 - DN65 3.000 76.1 - - - - 0.142 3.6 0.102 2.6 ,-VSR-3 3 DN80 3.500 88.9 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 VSR-3 1/2 3.5 - 4.000 101.6 0.120 3.05 0.226 5.74 - - - - 20 27 VSR-4 4 DNI00 4.500 114.3 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 2.00±.125 50.8±2.0 VSR-5 5 - 5.563 141.3 0.134 3.40 0.258 6.55 - - - - VSR-6 6 DN150 6.625 168.3 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5 ' • NOTE:For copper or plastic pipe use Model VSR-CF. PRINTED IN USA MFG.#5401146-REV L PAGE 2 OF 4 3/09 VSR P POTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Fig.2 Fig.3 Fig.4 Switch Terminal Connections Clamping . To remove knockouts:Place screwdriver at Break out thin section of cover when Plate Terminal inside edge of knockouts,not in the center. wiring both switches from one conduit entrance. •;>r�, 11�J 6 i "- 44(.;.' OW 0,46-41 � � 1 -�� ( AWARNIN -'� \i �/�� An uninsulatted section of a single conductor should not be looped ��\� / ® `j1i�'1,+ • around the terminal and serve as two separate collections. The �_,-�j x.21,- wire must be severed,thereby providing supervision of the 1 connection in the event that the wire become dislodged from under g NOTICE J�'�, the terminal. Failure to sever the wire may render the device Do not drill into the base as this creates If`.! Ov6 1146-13 inoperable risking severe property damage and loss of life. metal shavings which can create 0 Do not strip wire beyond 3/8"of length or expose an uninsulated electrical hazards and damage the ' conductor beyond the edge of the terminal block.When using device.Drilling voids the warranty. stranded wire,capture all strands under the clamping plate. Fig.5 Typical Electrical Connections ID Notes: a POWER SOURCE _ I I. The Model VSR has two switches,one can be used to operate a central = �- II SUITABLE FOR BELL - station,proprietary or remote signaling unit,while the other contact ., 1 is used to operate a local audible or visual annunciator. ill err„ illl • —I - 2. A condition of LPC Approval of this product is that the electrical g ■• •• • • entry must be sealed to exclude moisture. ' �� � , WATERFLOW ZONE 3. For supervised circuits,see"Switch Terminal Connections" JP, E I EOLR ON FIRE PANEL Pere 1 H p • _ drawing and warning note(Fig.4). �I 5 1 naa++*42 Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction(manufacturer recommends quarterly or more frequently). If provided,the inspector's test valve shall always be used for test purposes.If there are no provisions for testing the operation of the flow detection device on the system,application of the VSR is not recommended or advisable. A minimum flow of I0 GPM(38 LPM)is required to activate this device. NOTICE Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Fig.7 Mounting Dimensions 5.56 in Fi g.8 3.50 in (141.2 mm) GREEN GROUND 2.00 in (89.0 mm) (50.8 mm) A SCREWS EW S A2.34 in � ti , p••� (59.4 mm) I) a 4, III I dr). U-BOLT NUT PIPE DIA. _ +5.25 in ��_ r�'ill �� U-BOLT WASHER ../_-•n (+133.4mm) ��IM�i` II_ IIIII'�I�II O.II II°PIPE SADDLE Flip ' )011•hl■Yr>4:':--4.76"- r•�• PIPE , , v ,4 • PLASTIC PADDLE , ov¢11�Nv_ _�•� - U-BOLT NOMINAL PIPE DIA.+1.75 in(+44.5 MM)FOR DN 50-DN 65 2-2.5 in O ow 1144.-is - NOMINAL PIPE DIA.+2.125 in(+54.0 MM)FOR DN 80-DN 200 3-8 in PRINTED IN USA MFG.45401146-REV L PAGE 3 OF 4 3/09 VSR P POTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Maintenance Inspect detectors monthly. If leaks are found, replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly,please order replacement retard switch assembly stock#1029030(see Fig.6).There is no maintenance required,only periodic testing and inspection. Retard/Switch Assembly Replacement(See Fig.6) NOTICE The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe 1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell(if applicable). 3. Identify and remove all wires from the waterflow switch. 4. Remove the(2)mounting screws holding retard/switch assembly to the base.Do not remove the(2)retard housing screws. 5. Remove the retard assembly by lifting it straight up over the tripstem. 6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 7. Re-install the(2)original mounting screws. 8. Reconnect all wires.Perform a flow test and place the system back in service. Fig.6 REMOVE(2)ORIGINAL MOUNTING SCREWS HOLDING RETARD/SWITCH ASSEMBLY TO BASE *1 I i BREAKOUTTHINSECTIONOECOVER WHEN WIRING BOTH SWITCHES FROM ONE CONDUIT ENTRANCE. (2)ORIGINAL MOUNTING I /10 CREWS I RETARD/SWITCH ASSEMBLY Amen....1111111106.14- \ . .,....ittir 7 . , , .,„ . ,r-,--,..,./..,,,,,,, loll L-- filiMmlic''!111 ' rim p �' (2)LOCATING PINS LJ I III DO NOT REMOVE i f ." /'11 (2)LOCATING PIN I a'/� � BOSSES IN BASE \ (2)RETARD HOUSING •i r i SCREWS I■ �.��1• --'I 7.,171 11 III- ' :C311121�li_. � BAS II III ' ���/� r/i 11 �1 co 44-"Ro-c-ri Pow , o DWG#1146-10 Removal of Waterflow Switch • To prevent accidental water damage,all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector,then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers,roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • • Lift detector clear of pipe. . PRINTED IN USA MFG.#5401146-REV L PAGE 4 OF 4 3/09 j a � ucr� � nucR� .... . .. .. .. .. .. , 2.,:.,....,..::.).!!., :,:e.....,..J, .,,4 � R I ;. .P Rod Screw Box Weight Case Approvals Part# item# odel• Size --� .. Descriptions Qty. (per 125) Qty rnood luf Drivr 1/4" 8018957 4016 SWG 100 1/4 X 1 25 9.38 125 e#14SW Nut Denver 1/4" 8019957 300 SWG 200 1/4 X 2 25 10.00 125 r Sidewinders and 2"Rod Sammys 3/8" 8020957 18 SWG 10 1/4 X 1 25 7.50 125 3/8" 8021957 19 SWG 20 1/4 X 2 25 8.75 125 3/8" 8022925 26 SWG 25-380 3/8 X 2-1/2 25 12.81 125 3/8" 8023925 25 SWG 30 1/4 X 3 25 10.63 125 Approvals Rod Part* Item* Model Screw Box Weight Case t e e l Sine Descriptions Qty. (per 125) Qty • 3/8" 8050957 39 SWD 10 1/4-14 X 1 25 7.50 125 3/8" 8051957 40 SWD 15 1/4-14 X 1-1/2 25 9.38 125 'art#8114910 3/8" 8052957 41 SWD 20 114-14 X 2 25 8.13 125 Item#101 3/8" 8053957 42 SWD 516 5/16-18 X 1-1/4 25 8.75 125 • 3/8" 8054957 46 SWDR 1-1/2" 1/4-20 X 1-1/2 25 906 125 t 1 3/8" 8055957 43 SWDR 1" 1/4-20 X 1 25 8.75 125 G' 3/8" 8056957 44 SWDR 516 5/16-18 X 1-1/4 25 10.31 125 - 3/8" 8057957 45 SWT 15 12-24 X 1-112 25 7.81 125 Approvals Rod Part# Item# Model Screw Box Weight Case Concrete Size Descriptions Qty. (per 125) Qty 1/4" 8062957 1900 SWC 200 5/16 X 1-1/2 25 9.38 125 3/8" 8061957 65 SWC 20 5/16 X 1-1/2 25 9.38 125 • Most Items Available in Stainless Steel NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! * Use with 3/8" Sammy Swivel Head' tor Approvals Part# Item# Model Screw Box Weight Case • 17°deflection from vertical Descriptions Qty. (per 125) Qty U.S.Patent No. WOOD 6.443,680 • Accommodates up to it• 8139957 4702 SH-GST 20 1/4 x 2 25 9.38 125 3-1/2 x 12 pitch roof tit. 8140957 4703 SH-GST 22SS 1/4 x 2 25 9.38 125 8141957 4704 SH-GST 30 1/4 x 3 25 10.94 125 , • Also available in stainless steel C"' 8142957 4705 SH-GST 36SS 1/4 x 3 25 10.94 125 • Use#14 Nut Driver(black) STEEL 8137957 4700 SH-DSTR 1 1/4-20 x 1 25 9.38 125 ' 8138957 4701 SH-DSTR 1 -SS 1/4-20 x 1 25 9.38 125 Patent SAMMY X-PRESS M Rodplre�tlY Pending Steel Screw Box Weight Case an9 Threaded Approvals Part# Item# Model Thin Gauge Memel i Ga. Descriptions Qty. (per 125) Qty. from &purltn r STEEL It peck } 2 0 22-20 8150922 500 XP 20 114-20 x 1-118 25 10.3 125 pit', Sammy X-Press 20 � 114-20 x 1-118 -� 18-16 8153922 503 XP 35 Sammy X-Press 35 25 10.3 125 Uninstalled 8151910 501 XPIT Sammy X-Press It 1 1 02 1 .SAMMY x - Installation Tool v, (Kit includes:Sleeve,Bit Receiver, Hex Wrench,and 25/64"Drill Bit) PRESS TM 8152910 502 XPDB 25/64"Drill Bit 1 0.14 1 a+igelled VERTICAL MOUNT SAMMYS SAMMYS® for Wood IliNot less nominal� Mood Flooring Product Features (tom∎ •No pre-drilling required. IJOI less than •Quick to install using the Sammy 1°"'"al Nut Driver with an 18V cordless tlriddiase(2-1121 (dept,or side drilVdriver. d veriwl mertiber) t® -I® •Saves time from traditional r Double SheeVodc methods. For.---rt use- Ceding install m .. •Reduces installation cost. Minks•,, - , matt • - . Composite/Truss •Made in the U.S.A. Consult truss manufacturer for - recommended installation point • - _ 'Pre-dolling maybe required for GST -.-------::------7—"■:...____._._._--.—________- 25-380 Toot available on page 10. L it Rod . Part' Screw . Ultimate UL Test FM Test Box Case Approvals Size Number Model Descriptions Pullout(Ibs) Load(Ibs) Load(Ibs) Qty Qty 1/4" 8002957 GST 100 1/4x1' 210(Iris•OSB) 25 125 670(3/4•Ply) 114' 8003957 GST 200 1/4 it 2" 1760(Fir) 25 125 1/4' 8004957 GST 300 1/4 it 3" 2060(Fir) 25 125 3/8' 8006957 GST.75 1/4 x 3/4' 564 (314•Ply) 25 125 3/8' 8007957 GST 10 1/4x 1" 210(7/16'OSB) 3130 25 125 670(314•Ply) _ i a-Q 3/8' 8008957 GST 20 1/4 x 2' 1760(Fir) 850 1475 25 125 EL 318" 8068925 GST 20-SS 1/4x2' 1760(Fir) 850 25 125 3/8' 8009925 GST 25-380 3/8 x 2-1/7 2113(Fir) 1500 25 125 Q 3/8" 8010957 GST 30 1/4x3• 2060(Fir) 1500 1475 25 125 #14 Black Nut Driver 3/8' 8069925 GST 30-SS 1/4 x 3' 2060 (Fir) 25 125 Pant/8113910 3/" 8011925 GST 40 1/4x4' 2180(Fir) 25 125 3/8' 8012925 GST 60 1/4 it 6' 2230 (Fir) 25 125 1/? 8013925 GST 2 114x2" 1760(Fir) 25 125 1/7 8014925 GST 2.5.380 3/8 x 2-1/2' 2113 (Fir) 25 125 1/7 8015925 GST 3 1/4x3• 2275(Fir) 25 125 1/2" 8016925 GST 4 1/4 x 4• 2180 (Fir) 25 125 1/7 8017925 GST 6 114x 6' 2230(Fir) 25 125 #14 SW Red Nut Driver Part#8114910 . ' SAMMY Swivel Heady for Wood Product Features •Eliminates distortion of threaded rod. •Saves time from traditional methods. IIIII •Accommodates up to 3 W x 12 pitch roof. •Reduces installation cost. •Allows 17°deflection from vertical. •Made in the U.S.A. Approvals Rod Part Model Screw Ultimate UL Test FM Test Min Box Size Number Descriptions Pullout(Ibs) Load(Ibs) Load hbs) Thickness Qty �✓ 318' 8139957 SH-GST 20 114 x 7 1257(Fr) 1050 1475 25 125 125 /Q Q 3/8• 8141957 SH-GST 30 1/4 x 3' 1720(Fir) 1500 1475 25 125 #14 Black Nut Driver SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into Part#8113910 contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations. For the most up to date information,visit www.sammysuperscrew.com 4 rte' 1toHs lizom \y/ 1010./) • 300 RING HANGER PI :;.;:::7;:;;....': C \ f 1 thru 4 Inch pipe 1/2 and 3/4 inch pipe LISTED FOR STEELICPVC 5 thru 8 inch pipe SIZE- 1/2 thru 8 inch pipe. MATERIAL-Carbon Steel,Mil. Galvanized to G-90 spec. IMPERIAL MAX REC. METRIC* LISTINGS- PIPE ROD LOAD LBS. PIPE ROD C©uS EX 2551 1/2 3/8 400 10 <> Approval guide-Pipe Hangers 314 3/8 400 20 10 CONFORMS WITH: Federal Specification WW-H-171 (Type 10, 1 3/8 400 25 10 Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10). 1 1/4 318 400 32 10 MAXIMUM TEMPERATURE-6500F. 1 1/2 3/8 400 or 10 FUNCTION-Pipe hanger component for use on steel,CPVC or 2 3/8 400 50 10 copper piping. INSTALLATION-Per NFPA-13, 13R and 13D. 21/2 3/8 600 65 10 FEATURES- 3 3/8 600 80 10 * Sized and listed exclusively for use with#310 Surge Restrainer. 31/2 3/8 600 10 * Band edge is offset for EASY pipe insertion. 4 3/8 1000 100 10 * Custom fit swivel nut for better retention in ring body. 5 1/2 1250 125 12 * Full length knurl on swivel nut for better grip. s 1250 ORDERING-Part#,pipe size. 1/2 200 1� 8 1/2 1250 200 _ 1? •Order Part#300m • Note: On Co pp er-Insulate pipe. Note: 1/2"Ring Hanger not<FM>approved 08/03 aFD LCD www.tolco.com NIBCO Revision 10/15/2008 Component of State of _ Fig. 4A - Pipe Clamp for Sway Bracing CaliforniaOSHPDApproved COUR LISTED Seismic Restraints System Size Range — 4" thru 8" pipe. For sizes smaller than 4" use TOLCO® Fig. 4. B Material — Carbon Steel Function — For bracing pipe against sway and seismic disturbance. Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada ; �� (cUL) 4" thru 8". Included in our Seismic Restraints Catalog approved by / 0 the State of California Office of Statewide Health Planning and Development oil (OSHPD). / Installation Instructions — The Fig. 4A is the "braced pipe" attachment ` A component of a longitudinal, lateral or riser brace assembly. It is intended to i be combined with the "bracing pipe" and TOLCO transitional and structural attachment component(s) to form a complete bracing assembly. NFPA 13 �..� D and/or OSHPD guidelines should be followed. To Install — Place the Fig. 4A over the pipe to be braced. Attach TOLCO ` transitional fitting, either Fig. 980, 910 or 909, to the clamp ears. Tighten bolts and nuts; torque requirement is a minimum of 50 ft. lbs. Transitional fit- r....„ ting attachment can pivot for adjustment to proper brace angle. C Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, pipe size and finish opp• a ir I $ (' �M o Fig. 4A - Longitudinal Brace Fig. 4A - Lateral Brace TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components,resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components, in the instance that such TOLCO®brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. Dimensions •Weights Pipe Max. Horizontal Approx. Sizes A B C D Bolt Size Design Load WtJ100 4 81/2 9/16 33/e 311A6 1/2 2015 221 5 93/4 9/16 31/e 43/8 1/2 2015 253 6 111/2 5/8 5 51/8 1/2 2015 513 8 131/4 3/4 611/46 61/8 1/2 2015 601 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737 5599•FAX: 951,737 0330 26 CUSTOMER SERVICE•800 786 5266 www.tolco.com y rD L C cj www.toico.com NIBCO Revision 4/6/2010 Fig. 980 - Universal Swivel Sway Brace Attachment c®US LISTED Size Range — One size fits bracing pipe 1" thru 2", TOLCO 12 gauge channel, and all structural steel up to 1/4" thick. , Material — Carbon Steel Component of State of California OSHPD Approved Function — Multi-functional attachment to structure or Seismic Restraints System braced pipe fitting. Features — This product's design incorporates a concen- tric attachment opening which is critical to the performance of structural seismic connections. NFPA 13 (2010) 9.3.5.8.4 indicates clearly that fastener table load values are based I 1 )\ only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. ` Installation — The Fig.980 is the structural or transitional A attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until set bolt head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals — Underwriters Laboratories Listed in the USA(UL) and Canada (cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000 , Fig. 2001 or Fig. 4A Pipe Clamp make up a sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters' Laboratories and the National Fire Protection Association (NFPA) Finish — Plain Note — Available in Electro-Galvanized finish. Order By — Figure number and finish. r Pat. #6,273,372, Pat. #6,517,030, Pat. #6,953,174, � Pat. #6,708,930, Pat. #7,191,987, Pat. #7,441,730, Pat. #7,669,806 Lateral Brace Dimensions •Weights Max. Design **Max. Design Approx. A B H* Load Lbs. Load Lbs. Wt./100 (cULus) (FM) 51/4 1 7/8 17/32 2765 2800 132 Available with hole sizes to accommodate up to 3/4" fastener. Consult factory. '* Load shown is allowable with brace installed, between 30°-90°. No reduction of load based on brace angle is required. TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does Q warrant against the failure of TOLCO®brand bracing components, in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE •CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 149 CUSTOMER SERVICE•800.786.5266 www.folco.corn iro T o L C O www.tolco.com NIBCD Revision 5/27/2008 Component of State of Fig. 1000 - "Fast Clamp" Sway Brace Attachment California OSHPD Approved Seismic Restraints System Size Range — Pipe size to be braced: 1" thru 6" Schedule 10 thru 40 IPS.* Pipe size used for bracing: 1" and 11/4" Schedule 40 c 0 US usTED I PS. " Additionally(UL) approved for use to brace Schedule 7 sprinkler pipe up to 4" (maximum horizontal design load 655 lbs.) Torque requirement 6 — 8 ft. lbs. Material — Carbon Steel Function — For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace sys- tem: Fig. 1000 is used in conjunction with a TOLCO Fig. 900 Series Fitting and joined together with bracing pipe per NFPA 13* or TOLCO OSHPD Approved Seismic Manual, forming a complete sway brace assembly. Features — Field adjustable, making critical pre-engineering of — bracing pipe unnecessary. Unique design requires no threading of bracing pipe. Can be used as a component of a 4-way riser brace. Can be used as longitudinal brace with Fig. 907. Comes assembled and individually packaged with illustrated installation instructions lrlil — sizes are clearly marked. Steel leaf spring insert provided to assure installer and inspector necessary minimum torque has been achieved. Installation — The Fig. 1000 is the "braced pipe" attachment component of a lateral sway brace assembly. It is intended to be Maximum Design Load - combined with the "bracing pipe" and TOLCO structural attach- 1" thru 4" pipe size — 2015 lbs. ment component, Fig. 980, 910 or 909 to form a complete bracing 6" size — 1265 lbs. assembly. Follow NFPA 13 and/or OSHPD guidelines. To Install — Place the Fig. 1000 over the pipe to be braced, insert bracing pipe through opening leaving a minimum of 1" extension. FM Approved Design Loads* Brace pipe can be installed on top or bottom of pipe to be braced. 1" - 21/2" - 600 lbs. Tighten hex nuts until leaf spring is flat. It is recommended that the 3" - 4" - 700 lbs. brace angle be adjusted before hex nuts are fully tightened. Approvals — Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement informa- tion relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Application Note — Position Fast Clamp and tighten two hex nuts until leaf spring flattens. A minimum of 1" pipe extension beyond the Fig. 1000 is recommended. Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Order first by pipe size to be braced, followed by pipe size used for bracing, figure number and finish. Lateral Brace TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components, in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACIUTY•1375 SAMPSON AVE •CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.786.5266 www.tolco.com