Report "PS 20■'3- 0003 l l 55 5 ) -4-to l l Blvd RECEIVED DEC 26 2012 CITY OF TIGARD BUILDING DIVISION 11(O Western States Fire Protection Co. Protecti, 4cie4 agd Proftertet a subsidiary of API Group, Inc.C' MATERIAL SUBMITTAL SAINT JAMES APARTMENTS BUILDING F 11155 SW Hall Blvd. Tigard, Oregon 97223 WSFP Job No. LM0027 APIO Table of Contents • Description 1. RELIABLE Model RFC43 Concealed Residential Sprinkler 2. RELIABLE Model Fl Res 49 Recessed Pendent 3. BLAZEMASTER CPVC Pipe 4. SPEARS CPVC Fire Sprinkler Fittings 5. AMES CO.Series 2000B Double Check Valve Assembly 6. SYSTEM SENSOR WFDTH Waterflow Detector 7. POTTER PBA-AC Alarm Bell 8. AFCON Hangers Western States Fire Protection Co. 2_torectuc91'uied a€ w ie Bulletin 006 Rev D Relliabld Model RFC43 (SIN RA0612) cc Model RFC49 (SIN RA0616) -- Flat Concealed Residential Sprinklers A Concealed Residential - - Sprinkler engineered for a r minimum design density '" • of 0.05 gpm/ft2 with low GPM requirements. Features • 1 . Very low water flow requirements. 2. '/2" (13mm) Total adjustment. 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) 2. NYC MEA 258-93-E UL Listing Categories Residential Automatic Sprinklers UL Guide Number VK KW Product Description Model RFC43 and RFC49 Concealed Residential Sprinklers The RFC43 and RFC49 are UL Listed Residential Sprinklers are fast response residential fusible solder link automatic to be installed in the residential portions of any occupancy in sprinklers. Residential sprinklers differ from standard accordance with NFPA 13, 13R, & 13D. sprinklers primarily in their response time and water The RFC43 and RFC49 can reduce the need for precise distribution patterns, cutting of drop nipples. The threaded cover plate assembly Model RFC43 and RFC49 sprinklers discharge water in a can be adjusted without tools to fit accurately against the hemispherical pattern below the sprinkler deflector. ceiling. The fire protection system need not be shut down to Residential distribution patterns are higher and generally adjust or remove the cover plate assembly. contain a finer droplet size than standard sprinkler patterns. The combination of speed of operation and high discharge Application and Installation pattern required for residential sprinklers has demonstrated, The RFC43 and RFC49, for residential installations, use a in fire testing, an ability for controlling residential fires, and 165°F(74°C)fusible solder link in a tuning fork style sprinkler thereby providing significant evacuation time for occupants. frame with a drop-down deflector. This assembly is recessed The RFC43 and RFC49 Sprinklers provide the best form of into the ceiling and concealed by a flat cover plate. The cover • fire protection by combining an attractive appearance and plate is attached to the skirt, using 135°F (57°C) ordinary 1/2"(13mm)of cover adjustment for ease of installation. The temperature classification solder. When the ceiling small diameter cover plate is easily and positively attached temperature rises,the solder holding the cover plate releases and blends into the ceiling,concealing the most dependable the cover allowing the deflector to drop into position and fire protection available, an automatic sprinkler system. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 exposing the sprinkler inside to ceiling temperature. The should be taken to prevent damage to the sprinkler. DO NOT subsequent operation of the solder link opens the waterway WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP and causes the deflector to drop into position to distribute the ASSEMBLY. MODEL RFC43 AND RFC49 CONCEALED discharging water in a hemispherical pattern below the SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F sprinkler deflector. Any adjustment of thread engagement RATED COVERS. between the cover plate and cup will assure that the Cover assemblies provide up to Y" (13mm) of drop-down deflector is properly located below the ceiling. adjustment.Turn the cover clockwise until the flange is in The residential distribution pattern contains a finer droplet size contact with the ceiling. For the push-on/thread-off option, than a standard sprinkler, and the pattern produces the cover assembly is pushed onto the cup and final significantly higher wall wetting. adjustment is made by turning the cover clockwise until the After a 2 5/8 inch diameter hole is cut in the ceiling, the skirt flange makes full contact with the ceiling. Cover sprinkler is to be installed with the Model FC Wrench. When removal requires turning in the counter-clockwise direction. installing a sprinkler, the wrench is first positioned into the In ceilings that have a plenum space above the sprinkler, sprinkler/cup assembly and around the hexagonal body of the plenum space may have neutral or negative the sprinkler frame. The Wrench must bottom out against the pressurization but must not be positively pressurized. Inspect cup in order to ensure proper, safe installation. The sprinkler all sprinklers after installation to ensure that the gap between is then tightened into the pipe fitting. When inserting or the cover plate and ceiling and the 4 slots in the cup are all removing the wrench from the sprinkler/cup assembly, care open and free from any air flow impediment. Temperature Rating Sprinkler Cover Plate Max.Ambient Temp. 165°F/74°C 135°F/57°C 100T/38°C installation Data: RFC43 (SIN RAO6 12) Minimum Required Thread Size K Sprinkler Maximum Minimum Sprinkler Discharge inch(mm) Factor Spacing Distance Distance between - ft. (m) to Wall ft. (m) sprinklers,ft.(m) Flow Press. gpm(Lpm) psi(bar) 1"(15mm) 4,3 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 12(45) 7.8(0.54) Y"(15mm) 4.3 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 9.1 (0.63) 1/2"(15mm) 4.3 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 9.1 (0.63) 1/2"(15mm) 4.3 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 18(68) 17.5(1.21) '/b"(15mm) 4.3 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 21 (79) 23.8(1.64) Note: 1 bar= 100 Kpa Installation Data: RFC49 (RA0616) Minimum Required Thread Size K Sprinkler Maximum Minimum Sprinkler Discharge inch(mm) Factor Spacing Distance Distance between ft.(m) to Wall ft. (m) sprinklers,ft.(m) Flow Press. gpin(Lpm) psi(bar) j 1/2"(15mm) 4,9 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 13(49) 7.0(0.48) 1/2"(15mm) 4.9 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 7.0(0.48) 1/2"(15mm) 4.9 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 7.0(0.48) '/z"(15mm) 4.9 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 17(64.3) 12.0(0.83) Y"(15mm) 4.9 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 20(75.7) 16.7(1.14) Note: 1 bar= 100 Kpa FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035. 2. Maintenance Model RFC43 and RFC49 Concealed Sprinklers should be 135°F(57°C). Cover plate assembly shall consist of a brass inspected quarterly and the sprinkler system maintained in cover plate and copper alloy retainer flange allowing a 1/2" accordance with NFPA 25. Do not clean sprinklers with soap cover plate adjustment. Any secure engagement between and water, ammonia or any other cleaning fluids. Remove the cover plate and the cup will assure that the drop-down dust by using a soft brush or gentle vacuuming.Remove any deflector is properly located below the ceiling. A plastic • sprinkler cover plate assembly which has been painted(other protective cap shall be provided and factory installed inside than factory applied) or damaged in any way. A stock of the sprinkler cup to protect the drop-down sprinkler deflector spare sprinklers should be maintained to allow quick from damage, which could occur during construction before replacement of damaged or operated sprinklers. Prior to the cover plate is installed. Standard cover finish: [Chrome] installation, sprinklers should be maintained in the original [White][Specialty-specify]. Residential concealed sprinklers cartons and packaging until used to minimize the potential for shall be Reliable Model RFC43, SIN RA0612(Bulletin 006)or damage to sprinklers that would cause improper operation or Model RFC49, SIN RA0616(Bulletin 006). non-operation. Model RFC43 and RFC49 Residential Ordering Information Cover Plate Finishes M Concealed Sprinkler Specification Specify: Standard Finishes Sprinklers shall be cULus Listed low flow residential 1. Sprinkler Model Chrome concealed sprinklers with drop-down deflector and 2. Cover Plate Finish White adjustable flat cover plate engineered for a minimum design 3. Thread-On or density of 0.05 gpm/ft'. Sprinkler frame and deflector shall be Push On Feature Special Application of bronze frame construction having a 1/2" NPT thread. Finishes Thermal element shall consist of an approved black-painted Bright Brass beryllium-nickel fusible solder link with symmetric lever mechanism, maintaining a Teflon-coated Belleville spring Black Plating washer and machined brass cap water seal assembly Black Paint containing no plastic parts. Sprinkler K-factor shall be nominal Off White 4.3(62.4), having a 7/16" orifice.Temperature rating shall be Satin Chrome Ordinary 165°F (74°C); cover plate temperature rating to be "' Other colors and finishes available. Consult factory for details. Note: Paint or any other coatings applied over the factory finish will void all approvals and warranties. i 1" x 1/2" REDUCING TEE OR ELBOW 1 _b— II T III L_ r J 4" [65.7mm] D/A. 2 (58.7mm] DIA - HOLE IN CEILING 1 L= J CUP rs. — ■M■ 2" /50.8mm] MAX. •*`� I!11I ' FACE OF FITTING � ` " TO FACE OF CEILING �v DIMENSION r CEILING iiiiiii T ii—■� i" [12.7mm] MAX. J . I I J COVER ADJUSTMENT 3i" D/A I 3/16' �� COVER PLATE [84.1mm] f [4.8mm] BOOn ASSEMBLY SPRINKLER oosrcoi COVER PLATE: 1/2" [12.7mm] ADJUSTMENT 3. Reliable. . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Supertrol electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances,whenever applicable. Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by: The Reliable Automatic Sprinkler Co.,Inc. ®Recycled H eu au'd (800)431-1588 Sales Offices Paper (800)848-6051 Sales Fax (914)829-2042 Corporate Offices Revision lines indicate updated or new data www.reliablesprinkler.com Internet Address E.G.Printed in USA. 12/06 P/N 9999970261 Bulletin 135 Rev. H w Reliable ® Model Fl Residential Sprinklers for Design Density of .05 gprnfft2 Model Fl Res Sprinklers engineered for the lowest flows to meet the minimum design density of.05 gpm/ft2 '► 4 Types: r1 _ 1. Fl Res 30 Pendent 2. Fl Res 30 Recessed Pendent/F2 3. Fl Res 30 Recessed Pendent/FP Fl Res 30, 49, 58&76 Fl Res 30,49,58&76 4. Fl Res 49 Pendent Recessed Pendent/Fl Recessed Pendent/FP 5. Fl Res 49 Recessed Pendent/F1 6. Fl Res 49 Recessed Pendent/FP 7. Fl Res 58 Pendent 8. Fl Res 58 Recessed Pendent/F1 9. Fl Res 58 Recessed Pendent/FP 10. Fl Res 76 Pendent 11. F1 Res 76 Recessed Pendent/F1 12. Fl Res 76 Recessed Pendent/FP 13. Fl Res 30 CCP Pendent Fl Res 30, 49,58&76 Fl Res 44&58 14. Fl Res 49 CCP Pendent CCP Pendent Recessed HSW/F2 15. Fl Res 58 CCP Pendent 16. Fl Res 76 CCP Pendent 17. Fl Res 44 HSW 18. Fl Res 44 Recessed HSW/F2 19. Fl Res 58 HSW 20. Fl Res 58 HSW Recessed HSW/F2 21. F1 Res 44 SWC Fl Res 44 SWC Listings & Approvals The 3mm glass-bulb pendent sprinklers permit the effi- 1. Listed by Underwriters Laboratories Inc.and cient use of residential water supplies for sprinkler cover- UL Certified for Canada (cULus) age in residential fire protection design. 2. NYC MEA 258-93-E The low flow Fl Res sprinklers are specially engineered Slope Ceiling Approvals: Refer to Bulletin 035 for fast thermal response to meet the sensitive fire protec- Sprinklers for .10 Density: Refer to Bulletin 176 tion application needs of the latest residential market stan- dards (UL 1626 Standard). Upon fire conditions, rising UL Listing Category heat causes a sprinkler's heat-sensitive glass-bulb to shat- Residential Automatic Sprinkler ter, releasing the waterway for water flow onto the deflector, UL Guide Number evenly distributing the discharged water to control a fire. VKKW Technical Data: Patents • Thermal Sensor: Nominal 3mm glass-bulb US Patent No. 6,516,893 applies to the • Sprinkler Frame : Brass Casting Model Fl Res 49&58 Pendent Sprinklers • Sprinklers' Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi Product Description • Thread Size: 1/2" NPT(R1/2) Model Fl Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are • K-Factor: 3.0(Actual)- Fl Res 30 Pendent Sprinkler fast response sprinklers combining excellent durability, 4.9(Actual)-F1 Res 49 Pendent Sprinkler high sensitivity glass-bulb and low profile decorative de- 5.8 (Actual)-Fl Res 58 Pendent&HSW Sprinkler sign. The Fl Res Horizontal Sidewall sprinklers(Figs. 5, 6 7.6(Actual)-Fl Res 76 Pendent Sprinkler & 7) are equally attractive when above ceiling piping can 4.4(Actual) F1 Res 44 HSW Sprinkler not be used. • Density: Minimum 0.05 gpm/ft2 The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application Installation Model Fl Res Sprinklers are used for Residential Fire Pro- Models Fl Res sprinklers are to be installed as shown. tection according to UL 1626 Standard*. Be sure that ori- Model F1, F2 and FP Escutcheons, illustrated herewith, fice size, temperature rating, deflector style and sprinkler are the only recessed escutcheons to be used with Model type are in accordance with the latest published standards Fl Res sprinklers. Use of any other recessed escutcheon of The National Fire Protection Association or the approving will void all approvals and warranties. For installing Model _ authority having jurisdiction. Fl Res Pendent sprinklers use only the Model D sprinkler • Model Fl Res 30 Recessed Pendent/F2 • Model Fl Res 30, 49,58&76 Pendent • Model Fl Res 49,58&76 Recessed Pendent/Fl l Q.a # t , Fl escutcheon, 3/4" (19mm)adjustment (r 1 . I / .,/� REDUCE TURN COLLAR LAME � f CNI AGAINST SPRINKLER MRENCN BOSS. r j 1 EASE Of MT/.ID ---• B___.- --111 r- CEILING A'NENSKIM - �i?/// !/I6-IS/I6(Fl ESCUTCNf G�.. 1Y �,��,#Y+� !/16-11/16(F?15CU2HFGY,: 1 .::L OWE l� I!Ilil I�///. ct 1 �- Fig. 1 Fig. 2 Wrench; for installing Models Fl Res Recessed Pendent, Escutcheon*, Fl or F2, Data: CCP& SWC sprinklers use only the Model GFR2 sprinkler Face of fitting wrench; for installing Model Fl Res Recessed HSW sprin- Type Adjustment "A" to ceiling klers use only the Model GFR2 Sprinkler Wrench. Use of Inch(mm) Inch(mm) Inch(mm) wrenches other than those specified may damage these Min=3/ (19.1) 3/16-15/16 sprinklers. Install Fl Res 44 with a ceiling to deflector dis- Fl 3/4(19.0) Max.=1'/2"(38.1) (4.7-24.0) tance of 4" - 12". Flow arrow on deflector must point away M;n,.I6/16°(23.8) 3116 "I,6 from near wall and "Top" marking must face ceiling. F2 1/2(12.7) Max.=11/2"(38.1) (4.7 17.4) •Note:Escutcheons Fl or F2 may be used with Model Fl Res 49,58&76 Recessed Pendent Sprinkler . 2. Technical Data: Fl Res 30 Pendent and Recessed Pendent Thread Nominal Orifice Sprinkler Max. Max. Actual Sprinkler Size Inch(mm) Temp.Rating Pressure Ambient Temp. K Length °F °C psi(bar) °F °C Factor Inch(mm) 1/2"(R1/2)NPT "/5."(8.2) 175 68 175(12) 100 38 3.0 2.25(57) Deflector-to-ceiling Maximum 1" (25mm)to 4"(100mm) Max' Flow Pressure Sprinkler Identification Sprinkler Spacing ft(m) gpm(Lpm) psi(bar) Number(SIN) 12 x 12(3,6 x 3,6) 8(30.3) 7.0(0,48) R3511 14 x 14(4,3 x 4,3) 10(37.8) 11 (0,76) Technical Data: Fl Res 49 Pendent and Recessed Pendent. Thread Nominal Orifice Sprinkler Max. Max. Actual Sprinkler Size Inch(mm) Temp.Rating Pressure Ambient Temp. K Length °F °C psi(bar) °F °C Factor Inch(mm) 1/2"NPT 7/6"(11) 155 68 175(12) 100 38 4.9 2.25(57) (R'/z) 175 79 150 66 _ Deflector-to-ceiling Deflector-to-ceiling Maximum 1" (25mm)to 4" (100mm) Maximum 4" (100mm)to 8" (203mm) Max. Sprinkler Max. Sprinkler Sprinkler Flow Pressure Sprinkler Flow Pressure Identification gpm(Lp m) p si(bar) (SIN) Spacing 9P (Lp m) Psi(bar) Number(SIN) ft(m) ft(m) 12 x 12(3,6 x 3,6) 13(49) 7.0(0,48) 12 x 12(3,6 x 3,6) 15(57) 9.4(0,65) 14 x 14(4,3 x 4,3) 13(49) 7.0(0,48) 14 x 14(4,3 x 4,3) 16(60.5) 10.6(0,73) 16 x 16(4,9 x 4,9) 13(49) 7.0(0,48) R3516 16 x 16(4,9 x 4,9) 17(64.3) 12.0(0,83) R3516 18 x 18(5,5 x 5,5) 17(64.3) 12.0(0,83) 18 x 18(5,5 x 5,5) 19(72) 15.0(1,0) 20x20(6,1 x6,1) 20(75.7) 16.7(1,14) 20x20(6,1x6,1) 22(83.2) 20.2(1,4) *Note:The Fl Res 49 pendent and recessed pendent residential sprin- klers can be installed per NFPA 13 in beamed ceilings meeting the following criteria: 1.Maximum beam depth=7"(178mm) 2.Beam spacing at or greater than 7.5 ft.(2.3m)on center. Technical Data: Fl Res 58 Pendent and Recessed Pendent. Thread Nominal Orifice Sprinkler Max. Max. Actual Sprinkler Temp.Rating Pressure Ambient Temp. Length Size Inch(mm) °F °C psi(bar) °F °C K Factor Inch(mm) /z"NPT 1/2''(13) 155 68 175(12) 100 38 5.8 2.25(57) (R1/2) 175 _ 79 150 66 Max. Sprinkler Flow Pressure Ceiling-to-Deflector Sprinkler Spacing gpm(Lpm) psi(bar) Inch(mm) Identification ft(m) Number(SIN) 12 x 12(3,6 x 3,6) 16(61) 7.6(0,53) _14 x 14(4,3 x 4,3) 16(61) 7.6(0,53) 16 x 16(4,9 x 4,9) 16(61) 7.6(0,53) (25-1- 100) R3513 18 x 18(5,5 x 5,5) 19(72) 10.8(0,75) 20x20(6,1 x 6,1) 22(83.3) 14.4(1,0) 3. Technical Data: Fl Res 76 Pendent and Recessed Pendent Thread Nominal Orifice Sprinkler Max. Max. K Sprinkler Temp.Rating Pressure Ambient Temp. Length • Size Inch(mm) •F °C psi(bar) °F •c Factor Inch(mm) 3/4"NPT 155 68 100 38 (R'/z) "/32"(13.5) 175 79 175(12) 150 66 7.6 2.25(57) Max. Flow Pressure Sprinkler Identification Sprinkler Spacing gpm(Lpm) psi(bar) Number(SIN) ft(m) 12 x 12(3,6 x 3,6) 21 (79.5) . 7.6(0,53) 14 x 14(4,3 x 4,3) 21 (79.5) 7.6(0,53) 16 x 16(4,9 x 4,9) 21 (79.5) 7.6(0,53) R7618 18 x 18(5,5 x 5,5) 21 (79.5) 7.6(0,53) 20 x20(6,1x 6,1) 23(87.1) 9.2(0,63) _- • Model Fl Res 30,49,58&76 CCP Pendent • Model Fl Res 30, 49, 58&76 Recessed Pendent/FP : "4„,,. .„, . , . ..*.. _ . ... .. _ . U 4 w' X FP push-on/thread-off escutcheon 2 5/'C'O✓ _�_ ) I _____ - r " ;' .. n„ouc£R A.' CEILING - \ .ms ._ - -� \, _- �_ 1/4•131.5mm] a � '� MAX. FACE OF FITTING i QI TO FAC£ OF CEILING aLL4 �I AdOr ,1� �illl— l,i� A[L Oi lm NL ,, 11111 ' i� DIMENSION - r�o or ttnmc COVER ADJUSTMENT HEIGHT �. t 03^,0) - *. �/ n "1 . 3 5/16”DIA. 135FGO4D — [84.1mm] Fl RES 30, 49, 58 & 76 CCP PEND. Fl RES 49 PENDENT/FP Fig. 3 Fig. 4 . Note:The Fl Res 76 will use a 1" x 3/4" reducer. 4. Technical Data: Fl Res 30 CCP Pendent and Recessed Pendent/FP Thread Nominal Sprinkler CCP Assembly Max. Max. K Sprinkler Size Orifice Temp.Rating . Temp.Rating Pressure Ambient Temp. Factor Length Inch(mm) °F °C °F , °C psi(bar) °F °C Inch(mm) 1/2"NPT 21/64"(8.2) 155 68 135 57 175(12) 100 38 3.0 2.25(57) (R'/2) Max. Flow Pressure I Sprinkler Identification Sprinkler Spacing gpm(Lpm) psi(bar) Number ft(m) (SIN) 12 x 12(3,6 x 3,6) 8(30.3) 7.0(0,48) R3511 14 x 14(4,3 x 4,3) 11 (41.6) 13.4(0,92) Technical Data: Fl Res 49 CCP Pendent and Recessed Pendent/FP CCP Nominal Sprinkler Asse bly Max.Temp, Pressure Max. Sprinkler CCP Options Data: Thread Orifice Temp. Ambient K Length "A" Size Inch Rating Temp. Factor Inch Cover Adjustment CCP Height (mm) °F °C Rating 0 psi(bar) °F °C (mm) Inch(mm) Inch(mm) /z(RN�T '/,e"(11) 155 68 135 57 175(12) 100 38 4.9 2.25(57) %,( ( (7.9 ) 3/4 (19) Max. Sprinkler FP Data"A": Sprinkler Spacing Flow Pressure Identification "A" ft(m) gpm(Lpm) psi(bar) Number(SIN) FP Position Inch(mm) 12 x 12(3,6 x 3,6) 13(49) 7.0(0,48) Max.Recessed 7/16(1 1) 14 x 14(4,3 x 4,3) 13(49) 7.0(0,48) _ Min. Recessed 75/16(24) 16 x 16(4,9 x 4,9) 14(53) 8.2(0,56) R3516 Note: Sprinklers shown in Fig. 3 and Fig. 4 18 x 18(5,5 x 5,5) 18(68.1) 13.5(0,93) are not suitable for installation in cell- 20 x 20(6,1 x 6,1) 20(75.7) 16.7(1,14) ings which have positive pressure in the space above. Technical Data: Fl Res 58 CCP Pendent and Recessed Pendent/FP Thread Nominal Sprinkler CCP Assembly Max. Max. K Sprinkler Size Orifice Temp.Rating Temp.Rating _ Pressure Ambient Temp. Factor Length Inch(mm) °F °C °F °C psi(bar) °F °C Inch(mm) 1/2"NPT (R1/2) 1/2"(13) 155 68 135 57 175(12) 100 38 5.8 2.25(57) - Max. Sprinkler Identification Flow Pressure Sprinkler Spacing gpm(Lpm) psi(bar) Number ft(m) (SIN) 12 x 12(3,6 x 3,6) 16(61) 7.6(0,53) _. 14 x 14(4,3 x 4,3) 16(61) 7.6(0,53) 16 x 16(4,9 x 4,9) 16(61) 7.6(0,53) R3513 18 x 18(5,5 x 5,5) 19(72) 10.8(0,75) 20x20(6,1 x 6,1) 22(83.3) 14.4(1,0) Technical Data: Fl Res 76 CCP Pendent and Recessed Pendent/FP Thread Nominal Sprinkler CCP Assembly Max. Max. K Sprinkler Orifice Temp.Rating Temp.Rating Pressure Ambient Temp. Length Size Inch(mm) °F °C °F °C psi(bar) °F °C Factor Inch(mm) 3/4"NPT "/32"(13.5) 155 68 135 57 175(12) 100 38 7.6 2.25(57) (R3/4) 175 79 150 66 Max. Flow Pressure Sprinkler Identification Sprinkler Spacing (Lpm) p si(bar) Number gpm(Lp m ft(m) (SIN) 12 x 12(3,6 x 3,6) 21 (79.5) 7.6(0,53) 14 x 14(4,3 x 4,3) 21 (79.5) 7.6(0,53) . 16 x 16(4,9 x 4,9) 21 (79.5) 7.6(0,53) R7618 18 x 18(5,5 x 5,5) 22(83.3) 8.4(0,58) 20 x 20(6,1 x 6,1) 25(94.6) 10.8(0,74) 5. • Model F1 Res 44&58 HSW " FACE OF FITTING TO WALL DIMENSION 1 7/4" MIN. [31.8mrr J - 2 1/4"HOLE DIA. A" [57.2mm] 1/8" CEILING TO [3.2mm] DEFLECTOR 7"X 7/2"REDUCER DIMENSION n1-p 1 15/76"DIA. 1„.w I 1. [49.2mmJ --- IMO I' 4 2 27/32"DIA. nni .-.J �` viii All 1J� TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS. I • Model Fl Res 44&58 Recessed HSW/F2 1/2"[73mm] I J5fFO6—D ADJUSTMENT Fl RES 58 & 44 HSW/F2 Fig.5 ' ' • / iI F2 escutcheon, • 1/2" (13mm)adjustment Technical Data: Fl Res 44 HSW& HSW/F2 Escutcheon, F2, Data: Max. Face of Fitting Nominal Sprinkler Max. Sprinkler Adjustment Thread Ambient K Type to wall Size Orifice Temp.Rating Pressure Tem . Factor Length Inch(mm) Inch(mm) Inch(mm) , °F ,C psi(bar) o f roc Inch(mm) 'h '/2(13) 3[t6 ,y16 (R'/2) 3/8"(10) 175 79 175(12) 150 66 4.4 2.45(62) (4.7- 17.4) Max. Ceil in to Sprinkler Temp. Flow Pressure Sprinkler Sprinkler Spacing Rating Identification ft(m) Deflector 'F('C) gpm(Lpm) psi(bar) Number(SIN) Inch(mm) 12 x 12(3,6 x 3,6) 155(68) 175(79) 12(45,4) 7.5(0,52) 14 x 14(4,3 x 4,3) 155(68) 175(79) 14(53,0) 10.2(0,71) 16 x 16(4,9 x 4,9) 4-6 155(68) 175(79) 16(60,6) 13.3(0,92) 16 x 18(4,9 x 5,5) (101 -152) 155(68) 175(79) 18(68,1) 16.8(1,16) 18 x 18(5,5 x 5,5) 155(68) 175(79) 19(72,0) 18.7(1,29) 16 x 20(4,9 x 6,1) 155(68) 175(79) 23(87,1) 27.4(1,89) R3531 12 x 12(3,6 x 3,6) 155(68) 175(79) 14(53,0) 10.2(0,71) 14 x 14(4,3 x 4,3) 155(68) 175(79) 16(60,6) 13.3(0,92) 16 x 16(4,9 x 4,9) 6 12 155(68) 175(79) 17(64,4) 15.0(1,04) 16 x 18(4,9 x 5,5) (152 305) 155(68) 175(79) 20(75,7) 20.7(1,43) 16 x 20(4,9 x 6,1) 155(68) 175(79) 23(87,1) 27.4(1,89) 6. Technical Data: F1 Res 58 HSW& HSW/F2 Escutcheon, F2, Data: Max. Adjustment Face of Fitting Thread Nominal Sprinkler Max. Ambient K Sprinkler Type Inch(mm) to wall Size Orifice Temp.Rating Pressure Temp. Factor Length Inch(mm) Inch(mm) ,F ,C psi(bar) ,F ,C Inch(mm) 3/ "/16 F2 '/2(13) to '/2 (4.7 17.4) (R'/2) '/2"(13) 175 79 175(12) 150 66 5.8 2.45(62) Max. "A" Sprinkler Temp. Flow Pressure Sprinkler Sprinkler Spacing Ceiling to Deflector Rating Identification v. ft(m) Inch(mm) °F(°C) gPm(Lpm) psi(bar) Number(SIN) 12 x 12(3,6 x 3,6) 155(68) 175(79) 16(60,6) 7.6(0,53) 14 x 14(4,3 x 4,3) 155(68) 175(79) 18(68,2) 9.7(0,67) 16 x 16(4,9 x 4,9) (101- 52) 155(68) 175(79) 21 (79,5) 13.2(0,91) 16 x 18(4,9 x 5,5) 155(68) 175(79) 25(94,7) 18.6(1,28) 16 x 20(4,9 x 6,1) 155(68) 175(79) 29(109,8) 25(1,73) R3533 12 x 12(3,6 x 3,6) 155(68) 175(79) 22(83,3) 14.4(1,0) 14 x 14(4,3 x 4,3) 6-12 155(68) 175(79) 22(83,3) 14.4(1,0) 16 x 16(4,9 x 4,9) (152-305) 155(68) 175(79) 26(98,4) 20.1 (1,39) 16 x 18(4,9 x 5,5) 155(68) 175(79) 31 (117,4) 28.6(1,97) • Model Fl Res 44 SWC j 4" 12" f101.60mm To I I/4'[3I.75mmJ Mooimum 504.8OmmJ )4) face OT F'Hing PUSH ON COYER, THEN TO WOO Dimension TURN TO A0./UST UNTIL TIGHT AGAINST WALL. 1"X f/2"Reduce, %' Ro ommen0e0 1--' WOO Hole 2 5/16" 2 5/8n (5874mm] l �.—_ la= ,7 5/16" (66.68 mJ DiO. l �I DB I l- - [84.IImmJ /il �-� jr'O. TURN COLLAR'UNTIL' ' l I �" TIGHT AGAINST SPRINKLER WRENCH BOSS. 12f/22" (42.07mm] I.SSo:07 -+ 1/2'1,22.70' 7 �..r� AOjusfinen, F1 RES 44 SWC Fig. 6 Technical Data: Fl Res 44 SWC Nominal Sprinkler Cover Max. Max. Sprinkler Thread Temp. Ambient K Size Orifice Temp.Rating Rating Pressure Temp. Factor Length Inch(mm) ,F ,C °F ,C psi(bar) ,F ,C Inch(mm) 1/2"NPT 3/8"(10) 155 68 135 57 175(12) 100 38 4.4 2.45(62) (R1/2) "A" Max. Sprinkler Ceiling to Flow Pressure Sprinkler Spacing Identification ft(m) Deflector gpm(Lpm) psi(bar) Number(SIN) Inch jmm) - 12 x 12(3,6 x 3,6) 13(49,2) 8.7(0,60) 14 x 14(4,3 x 4,3) 14(53,0) 10.2(0,71) 16 x 16(4,9 x 4,9) (101 -52) 17(64,3) 15.0(1,1) 16 x 18(4,9 x 5,5) 19(71,8) 18.7(1,13) 16 x 20(4,9 x 6,1) 23(87,1) 27,4(1,89) R3531 • 12 x 12(3,6 x 3,6) 14(52,9) 10.2(0,71) 14 x 14(4,3 x 4,3) 6-12 15(56,7) 11.7(0,81) 16x 16(4,9x4,9) (152-305) 18(68,1) 16.8(1,16) • 16 x 18(4,9 x 5,5) 20(75,6) 20.7(1,43) 7. Maintenance Model Fl Res 30, 49, Fl Res 58, Fl Res 76 and Fl Res 44 be a steel, two-piece escutcheon [with 1/2" adjustment (Model Sprinklers should be inspected quarterly, and the sprinkler sys- F2)][with 3/4'adjustment(Model F1)] [of push-on and thread off tern maintained in accordance with NFPA 25, 13, 13D,and 13R. design with 1"adjustment(Model FP)].Standard finish shall be Do not clean sprinkler with soap and water,Ammonia or any oth- [brass][bright chrome] [white painted]. Residential recessed er cleaning fluids. Remove dust by using a soft brush or gentle pendent sprinklers shall be Reliable[Model Fl Res 30,49&58 vacuuming.Remove any sprinkler which has been painted(oth- Recessed Pendent/F1] [Model Fl Res 30, 49&58 Recessed er than factory applied)or damaged in any way.A stock of spare Pendent/F2][Model Fl Res 30,49&58 Recessed Pendent/FP] sprinklers should be maintained to allow quick replacement of SIN R3511,R3516&R3513(Bulletin 135). damaged or operated sprinklers. Prior to installation, sprinklers Model Fl Res 30,49&58 CCP Pendent(Concealed) should remain in the original cartons and packaging until used. Sprinklers shall be [cULus listed] [New York City MEA Ap- This will minimize the potential for damage to sprinklers that could proved(258-93-E)]low flow residential concealed sprinklers en- cause improper operation or non-operation. gineered to provide a minimum design density of 0.05 gpm/ft2 Model Fl Res 30, 49 & 58 Pendent over the listed coverage area. Listed flows as specified by the Sprinkler Specifications manufacturers technical data sheets are to be used.Residential Sprinklers shall be [cULus listed] [New York City MEA Ap- sprinklers shall be installed in conformance with the manufac- proved (258-93-E)] low flow residential pendent sprinklers en- turer's installation guidelines and the applicable installation stan- gineered to provide a minimum design density of 0.05 gpm/ft2 dard. Where pendent residential sprinklers are installed under over the listed coverage area. Listed flows as specified by the sloped ceilings having a pitch from[4/12]to[8/12],the sprinklers manufacturer's technical data sheets are to be used. Residential shall be listed for such use. Sprinkler frame and deflector shall sprinklers shall be installed in conformance with the manufac- be of bronze frame construction having a 1'NPT thread. Water turer's installation guidelines and the applicable installation stan- seal assembly shall consist of a Teflon-coated Belleville spring dard. Where pendent residential sprinklers are installed under washer with top-loaded extruded or cold head cup with 3 mm sloped ceilings having a pitch from[4/12]to[8/12],the sprinklers glass bulb containing no plastic parts,and having a temperature shall be listed for such use. Deflector-to-ceiling distance listing rating of 155°F(68°C). Cover plate assembly shall consist of a shall be 1"to 8" maximum. Sprinkler frame and deflector shall brass cover plate and copper alloy retainer flange. Method of be of bronze frame construction having a 1'NPT thread. Water attaching the cover plate to the sprinkler cup shall be a push- seal assembly shall consist of a Teflon-coated Belleville spring on and thread-off design allowing a 1/2"cover plate adjustment. washer with top-loaded extruded or cold head cup with 3 mm Cover plate temperature rating shall be 135°F(57°C). A plastic glass bulb containing no plastic parts,and having a temperature protective cap shall be provided and factory installed inside the rating of[155°F(68°C)] [175°F(79°C)]. Sprinklers shall have a sprinkler cup to protect the sprinkler from damage,which could nominal K-factor of 3.0, 4.9 and 5.8. Standard finish: [Bronze] occur during construction before the cover plate is installed. [Chrome-plated][White Polyester][Special finish-specify].Resi- Standard cover plate finish: [White] [Custom Color-specify]. ]. dential pendent sprinklers shall be Reliable Model Fl Res 30,49 Concealed pendent sprinklers shall be Reliable Model Fl Res &58,SIN R3511,R3516&R3513(Bulletin 135). 30,49&58 CCP,SIN R3511,R3516&R3513(Bulletin 135). Model Fl Res 49&58 Recessed Pendent/F1, Model Fl Res 44 Horizontal Sidewall Model Fl Res 30,49&58 Recessed Pendent/F2, Residential Sprinkler Specifications Model Fl Res 30,49&58 Recessed Pendent/FP Sprinklers shall be [cULus Listed] [New York City MEA Ap- Sprinklers shall be [cULus Listed] [New York City MEA Ap- proved(258-93-E)]low flow residential horizontal sidewall sprin- proved (258-93-E)] low flow residential recessed pendent klers engineered to provide a minimum design density of 0.05 sprinklers engineered to provide a minimum design density gpMft2 over the listed coverage area. Listed flows as speci- of 0.05 gpm/ft2 over the listed coverage area. listed flows as fied by the manufacturer's technical data sheets are to be used. specified by the manufacturer's technical data sheets are to be Residential sprinklers shall be installed in conformance with the used. Residential sprinklers shall be installed in conformance manufacturer's installation guidelines and the applicable instal- with the manufacturer's installation guidelines and the applica- lation standard. Where horizontal sidewall residential sprinklers ble installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from[4/12]to are installed under sloped ceilings having a pitch from [4/12] [8/12],the sprinklers shall be listed for such use.Sprinkler frame to [8/12], the sprinklers shall be listed for such use. Deflector- and deflector shall be of bronze frame construction having a'h" to-ceiling distance listing shall be 1" to 8" maximum. Sprinkler NPT thread. Water seal assembly shall consist of a Teflon-coat- frame and deflector shall be of bronze frame construction hav- ed Belleville spring washer with top-loaded extruded or cold ing a 1" NPT thread. Water seal assembly shall consist of a head cup with 3 mm glass bulb containing no plastic parts,and Teflon-coated Belleville spring washer with top-loaded extruded having a temperature rating of [155°F (68°C)] [175°F (79°C)]. or cold head cup with 3 mm glass bulb containing no plastic Sprinklers shall have a nominal K-factor of 4.4(62.8). Standard parts,and having a temperature rating of[155°F(68°C)] [175°F finish: [Bronze] [Chrome-plated] [White Polyester] [Special fin- (79°C)]. Sprinklers shall have a nominal K-factor of 3.0, 4.9& ish-specify]. Residential horizontal sidewall sprinklers shall be 5.8. Standard finish:[Bronze][Chrome-plated][White Polyester] Reliable Model Fl Res 44,SIN R3531 (Bulletin 135). [Special finish-specify]. Recessed escutcheon assembly shall 8. Model Fl Res 44 Recessed Model Fl Res 76 CCP Pendent (Concealed) Horizontal Sidewall Sprinkler Sprinklers shall be [cULus Listed] low flow residential Use description for the Model Fl Res 44 horizontal side- concealed sprinklers engineered to provide a minimum wall sprinkler with the following modifications: Replace design density of 0.05 gpm/ft2 over the listed coverage "horizontal sidewall sprinkler" with "recessed horizontal area. Listed flows as specified by the manufacturer's sprinkler." Add: Recessed escutcheon assembly shall be technical data sheets are to be used. Residential sprin- a steel, two-piece escutcheon with ' "adjustment(Model klers shall be installed in conformance with the manufac- F2). Standard finish shall be[brass][bright chrome] [white turer's installation guidelines and the applicable instal- painted] [Special finish- specify]. Residential recessed lation standard. Sprinkler frame and deflector shall be horizontal sidewall sprinklers shall be Reliable Model Fl of bronze frame construction having a 3/4" NPT thread. Res 44/F2, SIN R3531 (Bulletin 135). Water seal assembly shall consist of a Teflon-coated Bel- Model Fl Res 76 Pendent leville spring washer with machined or cold head cup with Sprinklers shall be [cULus Listed] low flow residential 3 mm glass bulb containing no plastic parts, and having pendent sprinklers engineered to provide a minimum de- a temperature rating of 155°F(68°C). Cover plate assem- sign density of 0.05 gpm/ft2 over the listed coverage area. bly shall consist of a brass cover plate and copper alloy Listed flows as specified by the manufacturer's technical retainer flange. Method of attaching the cover plate to the data sheets are to be used. Residential sprinklers shall sprinkler cup shall be a push on and thread off design be installed in conformance with the manufacturer's in- allowing a /z' cover plate adjustment. Cover plate tern stallation guidelines and the applicable installation stan perature rating shall be 135°F (57°C). A plastic protec dard. Sprinkler frame and deflector shall be of bronze tive cap shall be provided and factory installed inside the frame construction having a 3/4" NPT thread. Water seal sprinkler cup to protect the sprinkler from damage, which assembly shall consist of a Teflon coated Belleville spring could occur during construction before the cover plate washer with machined or cold head cup with 3 mm glass is installed. Standard cover plate finish: [White] [Custom bulb containing no plastic parts, and having a tempera- Color-specify]. 1. Concealed pendent sprinklers shall be ture rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers Reliable Model Fl Res 76 CCP, SIN R7618 (Bulletin 135). shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special fin- Finishes (1) ish-specify]. Residential pendent sprinklers shall be Reli- able Model Fl Res 76, SIN R7618 (Bulletin 135). Standard Finishes • Model Fl Res 76 Recessed Pendent/F1, Sprinkler Fl,F2,FP Cover Plates Model Fl Res 76 Recessed Pendent/F2, Escutcheons Model Fl Res 76 Recessed Pendent/FP Bronze Brass White Painted Chrome Plated Bright Chrome Plated Chrome Sprinklers shall be [cULus Listed] low flow residential White and Black Polyester White Painted recessed pendent sprinklers engineered to provide a Coated minimum design density of 0.05 gpm/ft2 over the listed Special Application Finishes coverage area. Listed flows as specified by the manu- Fl,F2, lecturer's technical data sheets are to be used. Residen- Sprinkler Escutcheons Cover Plates tial sprinklers shall be installed in conformance with the • manufacturer's installation guidelines and the applicable Bright Brass Bright Brass Bright Brass Black Plated Black Plated Black Plated installation standard. Sprinkler frame and deflector shall Black Paint Black Paint Black Paint be of bronze frame construction having a 3/4" NPT thread. Off White Off White Off White Water seal assembly shall consist of a Teflon-coated Bel- Satin chrome Satin Chrome Satin Chrome leville spring washer with machined or cold head cup with (1)Other finishes and colors are available on special order. 3 mm glass bulb containing no plastic parts, and hay- Consult factory for details. ing a temperature rating of[155°F(68°C)] [175°F(79°C)]. Note: Paint or any other coating applied over the factory finish will void Sprinklers shall have a nominal K-factor of 7.6. Standard all approvals and warranties. finish: [Bronze] [Chrome-plated] [White Polyester] [Spe- cial finish- specify]. Recessed escutcheon assembly Ordering Information shall be a steel, two-piece escutcheon [with 1/2" adjust- Specify: ment (Model F2)] [with 3/4" adjustment (Model F1)] [of 1. Sprinkler Model push-on and thread off design with 1/2" adjustment (Mod- 2. Sprinkler Type el FP)]. Standard finish shall be [brass][bright chrome] 3. Temperature Rating [white painted]. Residential recessed pendent sprinklers 4. Sprinkler Finish shall be Reliable [Model Fl Res 76 Recessed Pendent/ 5. Escutcheon Finish Fl] [Model Fl Res 76 Recessed Pendent/F2] [Model Fl 6. Cover Plate Finish Res 76 Recessed Pendent/FP] SIN R7618(Bulletin 135). 9. Reliable. . . For Complete ProtectiOfl Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gaugesldentification signs • Electrical sprinkler alarm switches • Fire department connection • Water flow detectors The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States.Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. ® Recycled Paper iabl Reld (800)431-1588 Sales Offices (800)848-6051 Sales Fax Corporate Offices Revision lines indicate updated or new data • (914)829 2042 www.reliablesprinkler.com Internet Address EG.Printed in U.S.A 09/10 P/N 9999970235 , . VIKING „,....... , • SupplyNet® i • BlazeMaster* CPVC Pipe Technical Features r) •Sizes Available(Nominal) :3/4" (DN20) through 3"(DN80) pipe diameters, with a Standard Dimension Ratio(SDR)of 13.5 as specified in ASTM F442. •Environmental Specifications : Indoor use only. Maximum Ambient Tem- perature : 150°F(65°C) ^ • Hazen-Williams C Value : 150 t J •Pressure Data :Working Pressure : 175 PSI (12.1 bar)at 150°F(65°C) •Specifications : _ • • Meets NFPA 13, 13R and 13D standards for light hazard occupancies. -0 • Pipe complies with ASTM F442. • Approved for National Sanitation Foundation (NSF) potable water rD services. • Complies with ANSI/NSF Standard 61 for health effects. ® ®®u ( ";, VdS NSF. • CPVC Pipe from Viking SupplyNet complies to NSF cell class 23547 LISTED �., 4 • a �J (demonstrated highest structural properties). CPVC Pipe Physical Data r N rage LD. Approvals Part Number ` in, metric inch,. mil (inc .. h/mm) , length(lb/kg) (ft/m) 3/4" DN20 1.050 26,670 0.874/22,199 2.52/ 1,14 15/4,6 34HPIPE 1" DN25 1.315 33,401 1.101 /27,965 3.93/ 1,78 15/4,6 1 HPIPE 11/4" DN32 1.660 42,164 1.394/35,408 6.27/2,84 15/4,6 cULus,FM, 114HPIPE 11/2" DN40 1.900 48,260 1.598/40,589 8.22/3,73 15/4,6 LPCB,VDS, 112HPIPE 2" DN50 _ 2.375 60,325 2.003/50,876_ 12.89/5.85 15/4,6 NSF 2HPIPE 21/2" DN65 2.875 73,000 2.423/61,500 18.86/8,55 15/4,6 212HPIPE 4 N 3" DN80 3.500 88,900 2.950/74,900 28.01 /12,71 15/4,6 3HPIPE Nominal Pipe Size Actual Outside Diameter Average I.D. Weight per 10'(4.6m) Length inch metric inch 1 mm ' '°'�-�° length(Ib/kg) (ft/m) Approvals Part Number lia; Adit—iim—iiiiimiim "a IS 3/4" DN20 1 1.050 26,670 0.874/22,199 1.68/0,76 10/ 3,05 34HPIPE10 1" DN25 1.315 33,401 1.101 /2Z965 2.62/ 1,19 10/3,05 1 HPIPE10 1 1/4" DN32 1.660 42,164 1.394/35,408 4.18/ 1,90 10/3,05 cULus, FM, 114HPIPE10 11/2" DN40 1.900 48,260 1.598/40,589 5.48/2,49 10/3,05 LPCB,VDS, 112HPIPE10 2" DN50 2.375 60,325 2.003/50,876 8.59/3,90 10/3,05 NSF 2HPIPE10 21/2" DN65 2.875 73,000 2.423/61,500 12.57/5,70 10/3,05 212HPIPE10 3" DN80 3.500 88,900 2.950/74,900 18.67/8,47 10/3,05 3HPIPE10 Note:CPVC Pipe is produced in SDR 13.5 Dimensions in accordance with ASTM F442.Standard Dimension Ratio is the ratio of the outside pipe diameter to the wall thickness of the pipe. IMPORTANT:Installers should receive thorough hands-on training in the proper methods of assembly and installation of CPVC products. On-site training is available at no charge from Viking SupplyNet. Participants in the training program will receive a special card acknowledging their attendance. In addition to receiving proper training,installers must always consult the Manufacturer's in Design and Installation Guide before any installation project is commenced. N pS . Worldwide Fire Protection www.vikinggroupinc.com BlazeMasterb pipe produced by Ftarvel Mapes.Inc for Viking SupplyNet.Refer to Manufacturers daUSheet Specifications subject to change without nonce VIKING SupplyNet' CPVC Pipe CPVC Pipe Product Specifications Corrosion resistance CPVC fire sprinkler pipe,when installed in strict accordance with the manufacturer's design and installation instructions,are UL and C-UL Listed by Underwriters Laboratories for use in the following: •Light Hazard occupancies as defined in the Standard for Installation of Sprinkler Systems,NFPA 13. •Residential occupancies up to and including four stories in height as defined by NFPA 13R. •Residential occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings,NFPA13D. •Installation of private fire service mains and their appurtenances,NFPA 24. CPVC fire sprinkler pipe from Viking SupplyNet shall be employed in wet pipe systems only and are not listed for outdoor use. CPVC pipe must never be used in a system using compressed air or other gases. • CPVC pipe from Viking SupplyNet also carries the following enhanced listings and approvals: •Tt •According to UL Listing(UL 1821) •Can be flush at return air plenums rD •Mechanical cut-in tee&crosses concealed with Grinnell figure 730 fittings •Mechanical cut-in tee&crosses exposed with Grinnell figure 730 fittings •Exposed system risers NFPA 13D, 13R •Exposed basement NFPA 13D(solid wood joist) •Extended coverage(exposed) •20'spacing on pendent in lieu of 15' • 18'spacing on sidewall in lieu of 14' •Use with combustible concealed sprinklers •Tyco attic sprinkler head(to protect the floor below) •Tyco attic sprinkler head with wet system piping(teed main and ndge installation) •Exposed sidewall sprinkler Listing for exposed pipe&fittings •24'extended coverage sidewall sprinkler. 12"drop, 155°F sprinkler head • 18'extended coverage sidewall sprinkler, 12"drop, 165°F sprinkler head • 16'extended coverage sidewall sprinkler, 12"drop, 175°F sprinkler head • 14'standard coverage sidewall sprinkler, 12"drop,200°F sprinkler head •Factory Mutual Approved' •Factory Mutual Approval exposed •Factory Mutual Approval above drop-in ceilings •Factory Mutual Approval exposed w/Soffi-Steel soffiting covering system •LPCB Approval •VDS Approval The above data is based on UL and FM reported Listings and Approvals as of 11/30/05. New and enhanced listings and approvals are being pursued. Always check with the appropriate Listing and Approval agency for details on current listing parameters. S CPVC pipe also meets all applicable standards for pressure rated application as required in ANSI-NSF Standard 14 and complies with ANSI-NSF Standard 61 for health effects and are marked with the NSF-pw end us marking. All CPVC fire sprinkler pipe shall be Listed by Underwriters Laboratories for wet pipe systems,and shall carry a rated working pressure of 175 psi @ 150°F(12 bar @ 65.5°C). The FM Approval is limited to use in wet pipe fire protection sprinkler systems for light hazard occupancies in both concealed and exposed applications with certain restrictions. Piping must always be installed in strict accordance to the manufacturer's System Design and Installation Manual,including product storage and handling,joining methods,supporting and bracing,expansion and contraction allowance and testing,etc. National Fire Protection Association (NFPA)Standards 13, 13D,and 13R must be referenced for design and installation requirements in conjunction with the installation instructions. All CPVC fire sprinkler pipe from Viking SupplyNet is manufactured in the USA by an ISO 9001 certified manufacturer. All CPVC pipe shall be packaged immediately after its manufacture to prevent damage and shall be stored indoors after production,at the manufacturing site,until shipped from the factory. The pipe shall bear the logo of the listing agencies,and shall carry the National Sanitation Foundation(NSF)seal of approval for potable water applications. CPVC products are intended for use in areas where the maximum ambient temperature does not exceed 150°F(65.5°C). If the ambient tem- perature is expected to exceed this limitation,refer to the manufacturer's System Design and Installation Manual for additional information on methods to reduce the pipe exposure temperatures. CPVC pipe is not intended to be installed in outdoor applications. CPVC pipe is intended to be used in wet pipe systems only and have not been investigated for use in dry pipe systems. Special installation and design criteria relative to pipe hanger spacings,piping and sprinkler restraint,sprinkler temperature rating,piping locations,testing procedures and friction loss charac- teristics are specified in the manufacturer's installation instructions provided with the pipe. The manufacturer's installation instructions should be reviewed and the Authority Having Jurisdiction consulted before installation. Worldwide Fire Protection www.vikinggroupinc.com BlazrMaster'pipe pronucec by.Ntvel f'lastfcs.ne la Vil.fny SupplyNet Hele1 to Manulacturer s°ataslteer Spenteanons subject to manse wit�uut nnli<r FlameGuardni CPVC FIRE SPRINKLER PIPING PRODUCTS ■S' TEE Socket x Socket x Socket • • F.- H lot— pi L Part Number Size G H L M Approx.Wt.(Lbs.) - 4201-007 3/4 17/32 1-9/16 3-1/8 1-5/16 .11 4201-010 1 25/32 1-13/16 3-5/8 1-5/8 .19 4201-012 1-1/4 7/8 2-1/8 4-1/4 1-31/32 .28 4201-015 1-1/2 1-3/16 2-9/16 5-1/8 2-11/32 .65 4201-020 2 1-13/32 2-15/16 5-7/8 2-7/8 1.00 4201-025 2-1/2 1-19/32 3-11/32 6-11/16 3-17/32 1.81 4201-030 3 2-1/16 3-15/16 7-7/8 4-3/16 3.02 REDUCING TEE Socket x Socket x Socket I+--►r M 1 M MO M2 H1 NG2 H H2 L Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx.Wt. (Lbs.) 4201-102 3/4x3/4x1 27/32 11/16 27/32 1-27/32 1-27/32 1-27/32 3-11/16 1-13/32 1-23/32 1-13/32 .21 4201-125 1x3/4x314 21/32 13/16 5/8 1-25/32 1-13/16 1-5/8 3-7/16 1-17/32 1-5/16 1-5/16 .16 4201-126 1x314x1 3/4 1-7/8 1-3/32 1-27/32 2-31/32 1-31/32 3-13/16 1-23/32 1-23/32 1-13/32 .26 4201-131 1x1x3/4 21/32 13/16 21/32 1-25/32 1-13/16 1-25/32 3-9/16 1-5/8 1-5/16 1-5/8 .16 4201-157 1-1/4x 1x3/4 11/16 1-1/32 11/16 1-15/16 2-1/32 1-13/16 3-25/32 2-3/32 1-13/32 1-23/32 .32 4201-158 1-1/4x1x1 3/4 1 7/8 2 2-1/16 2 4 2 1-11/16 1-5/8 .26 4201-159 1-1/4x1x1-1/4 15/16 31/32 1 2-3/16 2-7/32 2-3/32 4-9/32 2-3/32 2-3/32 1-23/32 .42 4201-167 1-1/4x1-1/4x3/4 21/32 1 21/32 1-29/32 2 1-29/32 3-13/16 2 1-5/16 2 .22 4201-168 1-1/4x1-1/4x1 13/16 1 13/16 2-1/16 2-1/8 2-1/16 4-3/32 1-31/32 1-5/8 1-31/32 .25 4201-169 1-1/4x1-1/4x1-1/2 1-1/8 15/16 1-1/8 2-3/8 2-11/32 2-3/8 4-3/4 2-3/32 2-11/32 2-3/32 .51 4201-201 1-1/2x1-1/4x3/4 11/16 1 1/4 2-1/16 2 1-15/16 4 2-5/16 1-3/8 2-1/16 .41 4201-202 1-1/2x1-1/4x1 27/32 1-1/32 1 2-7/32 2-5/32 2-1/4 4-15/32 2-5/16 1-11/16 2-1/16 .42 4201-210 1-112x1-1/2x3/4 23/32 1-1/16 23/32 2-3/32 2-1/32 2-3/32 4-3/16 2-5/16 1-3/8 2-5/16 .38 4201-211 1-1/2x1-1/2x1 13/16 1-3/16 13/16 2-3/16 2-1/4 2-3/16 4-3/8 2-11/32 1-23/32 2-11/32 .41 _ 4201-212 1-1/2x1-1/2x1-1/4 1 1-1/8 1 2-3/8 2-11/32 2-3/8 4-13/16 2-11/32 2-3/32 2-11/32 .48 ' 4201-213 1-1/2x1-112x2 1-5/16 1-1/8 1-5/16 2-11/16 2-21/32 2-11/16 5-3/8 2-11/32 2-27/32 2-11/32 .72 MADE IN THE U.S.A. 2 FlameGuardTM CPVC FIRE SPRINKLER PIPING PRODUCTS SPEARS 90° ELL Socket x Socket G al H iiir. 1.---M—.1 Part Number Size G H M Approx.Wt.(Lbs.) - 4206-007 3/4 9/16 1-1/2 1-5/16 .07 4206-010 1 3/4 1-5/8 1-5/8 .11 4206-012 1-1/4 7/8 2-1/8 2 .18 4206-015 1-1/2 1-5/32 2-17/32 2-11/32 .25 4206-020 2 1-13/32 2-29/32 2-7/8 .63 4206-025 2-1/2 1-5/8 3-7/16 3-7/16 1.17 4206-030 3 1-29/32 3-23/32 4-3/16 1.80 SIDE OUTLET ELL Socket x Socket x Socket . 1.1111RL . en M H Part Number Size G H M Approx.Wt.(Lbs.) 4213-007 3/4 27/32 1-19/32 1-5/16 09 4213-010 1 3/4 1-7/8 1-5/8 .17 REDUCING 90° ELL Socket x Socket H1 G1 G re-mfi H I mrr F4-M-Id Part Number Size G G1 H H1 M M1 Approx.Wt.(Lbs.) 4206-131 1x3/4 21/32 13/16 1-3/4 1-25/32 1-19/32 1-9/32 .11 MADE IN THE U.S.A. 6 . ( FlameGuardT"" CPVC FIRE SPRINKLER PIPING PRODUCTS ) ■SPE 45° STREET ELL Spigot x Socket J� H1 �1 \ H -+I PIPE O.D. 1~ Part Number Size H H1 J J1 M1 Approx.Wt.(Lbs.) 4227-010 1 1-1/2 1-5/16 1/2 1/4 1-5/8 .10 4227-012 1-1/4 1-25/32 1-9/16 9/16 11/32 1-31/32 .15 4227-015 1-1/2 2-1/32 2-1/8 19/32 25/32 2-11/32 .29 4227-020 2 2-5/16 1-15/16 25/32 13/32 2-7/8 .44 CROSS Socket x Socket x Socket x Socket t---AI I�1 t � L_— H11 M -- -- - Lt 4---i I-- G k-H-• L .- Part Number Size G G1 H H1 L L1 _ M Approx.Wt.(Lbs.) 4220-007 3/4 5/8 5/8 1-21/32 1-21/32 3-5/16 3-5/16 1-13/32 22 4220-010 1 1-11/16 1-11/16 1-5/8 1-5/8 3-1/4 3-1/4 1-5/8 .23 4220-012 1-1/4 1-1/8 1-1/8 2-3/8 2-3/8 4-3/4 4-3/4 2-3/32 .65 4220-015 1-1/2 1-7/32 1-7/32 2-5/8 2-5/8 5-1/4 5-1/4 2-11/32 .87 4220-020 2 1-1/2 1-1/2 3 3 6 6 3 1.43 - 4220-025 2-1/2 1-23/32 1-23/32 3-13/32 3-13/32 6-13/16 6-13/16 3-1/2 2.17 ■ 4220-030 3 2-1/16 2-1/16 3-15/16 3-15/16 7-7/8 7-7/8 4-1/8 3.12 MADE IN THE U.S.A. 10 SPEARS Flame Guard TM CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCING CROSS Socket x Socket x Socket x Socket r--►rM1 rj�_1 H1 1 L1 Rir- H L Part Number Size G G1 H H1 L L1 M M1 Approx.Wt.(Lbs.) 4220-131 1x3/4 7/8 5/8 2 1-5/8 4 3-1/4 1-27/32 1-1/2 .35 4220-167 1-1/4x3/4 1-1/16 - 23/32 2-1/16 , 1-31/32 4-3/32 3-31/32 2-1/16 1-13/32 .35 COUPLING Socket x Socket -_1_ . i----_---17 .____. ____ . I^I 1. _.ILf._N Part Number Size L M N Approx.Wt.(Lbs.) 4229-007 3/4 2-1/8 1-5/16 3/16 .05 4229-010 1 2-3/16 1-5/8 3/32 .08 4229-012 1-1/4 2-19/32 2 3/32 .13 4229-015 1-1/2 2-31/32 2-1/2 11/32 .32 4229-020 2 3-1/8 2-7/8 1/8 .46 4229-025 2-1/2 3-13/16 3-9/16 7/16 .70 4229-030 3 4 4-3/16 1/4 .89 11 SPEARS®MANUFACTURING COMPANY SPEARS Flame Guard TM CPVC FIRE SPRINKLER PIPING PRODUCTS FEMALE ADAPTER Metal Thread Insert Style Socket x Fipt F_ ......_ i M --- - M1 L _JI LN t L Part Number Size L M M1 N Approx.Wt.(Lbs.) 4235-007 3/4 2 1-13/32 1-3/8 5/16 .23 4235-010 1 2-9/32 1-11/16 1-11/16 15/32 .25 4235-012 1-1/4 2-3/8 2-3/32 2-1/16 13/32 .35 4235-015 1-1/2 2-9/16 2-3/8 2-7/16 7/16 .23 4235-020 2 2-11/16 2-7/8 3-1/32 15/32 .31 FEMALE ADAPTER Special Reinforced Plastic Thread Style Socket x SR Fipt M ---- M1 L _...............A 1� ._.1 Part Number Size L M M1 N Approx.Wt.(Lbs.) 4235-007SR 3/4 1-7/8 1-13/32 1-3/8 1/8 .09 4235-010SR 1 1-23/32 1-23/32 1-15/16 3/32 .21 4235-012SR 1-1/4 2-5/16 2-1/8 2-1/16 3/16 .20 13 SPEARS®MANUFACTURING COMPANY FlameGuardTM CPVC FIRE SPRINKLER PIPING PRODUCTS ) SPG i_j 7 FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Socket x SR Fipt 1 M WI 1 III M1 LS 1 ---N L Part Number Size L M M1 N Approx.Wt.(Lbs.) 4235-101SR 3/4x1/2 1-29/32 1-13/32 1-3/16 7/32 .07 4235-130SR 1x1/2 2-7/32 1-23/32 1-3/16 13/32 .10 4235-131SR 1x3/4 2-3/32 1-3/4 1-3/8 1/4 .13 I FEMALE SPRINKLER HEAD ADAPTER I Special Reinforced Plastic Thread Style w/Backup Wrench Flats Socket x SR Fipt -t M -- Is M1 M=Flat-to-Flat Dimension • • N aL Part Number Size L M M1 N Approx.Wt.(Lbs.) W4235-101SR 3/4x112 2-9/32 1-13/32 1-3/16 17/32 .09 W4235-130SR 1x1/2 2-9/32 1-3/4 1-3/16 13/32 .12 MADE IN THE U.S.A. 14 ffl ( FlameGuardTM CPVC FIRE SPRINKLER PIPING PRODUCTS FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread w/Metal Thread Start Socket x SR Fipt M — — — 'Ji1 II N j.1--L Part Number Size L M M1 N Approx.Wt.(Lbs.) Z4235-101SR 3/4x1/2 1-7/8 1-3/8 1-7/16 3/16 .08 Z4235-130SR 1x1/2 2-1/32 1-23/32 1-7/16 5/32 .17 SPIGOT FEMALE ADAPTER Metal Thread Insert Style Spigot x Fipt . F It 1 PIPE M1 . O.D. - - u 1 N--I .II- 1 L '. Part Number Size L M1 N Approx.Wt.(Lbs.) 4278-007 3/4 2-1/16 1-3/8 15/32 13 4278-010 1 2-13/32 1-23/32 19/32 .23 SPIGOT FEMALE ADAPTER Special Reinforced Plastic Thread Style Spigot x SR Fipt PIPE ------_ • M1 O.D. L 1 Part Number Size L M1 N Approx.Wt.(Lbs.) 4278-007SR 3/4 1-15/16 1-3/8 11/32 .08 4278-010SR 1 2-1/4 1-23/32 13/32 .13 15 SPEARS®MANUFACTURING COMPANY ES-A-2000B Series 2000B • A M E S Double Check Valve Assemblies FIRE&WATERWORKS • Sizes: 1/2" —2" (15—60mm) Features • • • • Ease of maintenance with only one cover . . 2"20008 HC • Top entry (50mm) • Replaceable seats and seat discs • Modular construction • Compact design • 12"-2" (15-50mm)Cast bronze body construction • Top mounted ball valve test cocks 1/4 (20mm) • Low pressure drop • No special tools required Series 2000B Double Check Valve Assemblies shall be installed at referenced cross-con- • 1/2"-1" (15-25 mm) have nections to prevent the backflow of polluted water into the potable water supply. Only tee handles those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation,frequency of Available Models testing or other installation requirements. Suffix: These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are • B Quarter turn ball valves approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. LBV- less ball valves LH - locking handle ball valves(open Specifications position) A Double Check Valve Assembly shall be installed at each noted location. The assembly SH- stainless steel ball valve handles shall consist of two positive seating check modules with captured springs and rubber seat HC- 2/2" inlet/outlet fire hydrant fitting discs.The check module seats and seat discs shall be replaceable. Service of all internal (2" valve) components shall be through a single access cover secured with stainless steel bolts.The assembly shall also include two resilient seated isolation valves and four top mounted, re- Prefix: silient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 U- union connections and AWWA Std. C510.Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.Assembly shall be an Ames Company Series 2000B. Pressure — Temperature. Temperature Range: 33°F-140°F Approvals (5°C-60°C) ae ti� s ,�o\/<A,Maximum Working Pressure: 175psi p' c us (12.06 bar) ` 1015 B64.5 '/n"-2" (LBV Models Only) Standards Approved by the Foundation for Cross-Connection Control and Hydraulic Research at AWWA Std. C510, IAPMO PS31 the University of Southern California. LBV models not listed. Horizontal and vertical "flow up" approval on all sizes. Job Name Contractor Job Location Approval • Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Dimensions - Weights < A Milk M • . Ni 4 1 --.I.- Imii'"�-_.=_ 1 moo . F \ / E-H-).- I Suffix HC - Fire Hydrant Fittings dimension"A"=231/2"(594mm) G SIZE(DN) DIMENSIONS WEIGHT A B C F G H I in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 1/2 15 10 254 4% 117 27/6 62 5 127 33/s 85 25/6 59 216 52 4.5 2 3/4 20 111/8 282 4 102 31/4 79 6'/6 157 37/6 87 21/8 54 15/6 33 5 2.3 1 25 131/4 337 51/2 130 4 102 71/2 191 33/6 85 1116 43 11146 43 12 5.4 11/4 32 163/s 416 5 127 35/6 84 . 91/2 241 5 127 3 76 2 50 15 6.8 11/2 40 163/4 425 4'/6 124 31/2 89 9'/a 248 513/6 148 31/4 79 2116 68 15.86 7.2 2 50 191/2 495 61/4 159 4 102 133/8 340 61/6 156 31/46 87 2116 68 25.75 11.7 Strainer sold separately Capacities kPa psi 1 II As compiled from documented Foundation for Cross-Connection Control 96 14 �a (32mm) and Hydraulic Research at the University of Southern California lab tests. m 83 12 co `Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) 0 69 10 55 8 12 kPa psi " (15mm) 41 6 ..„...... ..............................0.07--. co 83 121 I I I I I y 28 4 _ O 09 5 5 '8 _ a 1 0 0 [ 1 1 I I 1 I f I f m 41 6 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm to 14 2 AP 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm d 0 0 _ 5 7.5 10 15 fps • 0 2 4 6 8 10 12 gpm 1.5 2.3 3.0 4.6 mps AP 0 7.6 15.2 22.8 30.4 38 45.6 Ipm Flow Rate 5 7.5 10 fps 1.5 2.3 3.0 mps kPa psi 11/21" (40mm) Flow Rate 83 12_ _ -- kPa psi 3/4" (20mm) N 69 10 a 152 22 * o 55 8 o 124 18 ` 41 6 m 96 14 y 14 4 n 14 2 r ' 69 10 d 0 0 a • 41 6 Apo 10 20 30 40 50 60 70 80 90 100 110 120 gpm O. 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 14 2 - 5 7.5 10 15 tps 0 5 10 15 20 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps AP 0 19 38 57 76 95 114 133 152 171 190 Ipm Flow Rate 7.5 15 tps 2.3 4.6 mps kPa psi 21I (50mm) Flow Rate w 83 12 kPa psi 1" (25mm) p 69 10 N 110 16 ' 55 8 _1• 83 12 d 41 6 55 y • 55 8 8 28 4 0 N In d 14 2 41 6 a D 0 a d 28 4 ��. Cl. 14 2 ' 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 Ipm 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm 5 7.5 10 15 fps AP 0 19 38 57 76 95 114 133 152 171 190 209 228 1pm 1.5 2.3 3.0 4.6 mps 5 7.5 10 15 fps Flow Rate 1.5 2.3 3.0 4.6 mps Flow Rate IMPORTANT:inquire with governing authorities for local installation requirements. A M E S IS0 9001 FIRE&WATERWORKS A Division of Watts Regulator Company www.amesfirewater.com CERTIFIED 1427 North Market Blvd. • Suite #9 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 ES-A-20008 0521 ©Ames Co.2005 * SYSTEM SENSOR' WFDTH Waterflow Detector The System Sensor WFDTH Retard T-Tap Waterflow Detector is designed for primary signaling in residential systems and fits within 2x4 stud wall construction. Features The WFDTH fits any tee that has a 1"NPT branch,including:1",11/4", •Residential sprinkler systems 11/2",and 2"NPT threaded ferrous and brass tees;1",11/4",13W and 2" copper sweat tees;Central,Spears',and Victaulic•brand 1"CPVC tees; • •Sealed retard mechanism and 11/2"polybutylene tees. •Visual switch activation • •Rugged,dual SPDT switches enclosed in a durable terminal block Design.The design of the WFDTH makes it easy to install and simple to maintain.It can be mounted in the vertical or horizontal • Easy to install and maintain design position.Two conduit openings permit easy attachment to the local •Vertical or horizontal mount alarm system.The retard mechanism and switch assembly are field- •Field replaceable retard mechanism and switch assembly replaceable. •Twelve different flexible paddles Features.Twelve different flexible paddles fit 1",11/4",11/2",and 2" •Durable,tamper resistant enclosure tees.Sizes are marked clearly on the paddle for ease of installation. •Two conduit openings Plastic paddles slip over the actuating lever and are securely fastened with one screw.The handy depth gauge insures the proper •Handy depth gauge installation depth and clearance of the detector to the tee. ▪Accommodates up to 12 AWG wire •100%synchronization fires alarm panel and local bell Construction.The WFDTH includes a durable and tamper resistant simultaneously enclosure.Its sealed retard assures that the delay mechanism is not contaminated by dust and dirt when the cover is removed.The long lasting cover completely encloses the electrical components to further keep out dust and dirt.Improved self-guiding security screws and removal tools make detectors resistant to tampering and simplify field maintenance. Agency Listings UL 0T LISTED approved AMMO Crib:+ 7770.1653:114 167-93-E 3033305 WFDTH Specifications Architectural/Engineering Specifications • Model shall be a WFDTH as manufactured by System Sensor.T-tap waterflow detectors shall be installed on a tee that has a 1"NPT branch including:l,1 W, 111",or 2"threaded ferrous or brass tee;1-2"copper sweat tees;Central,Spears',and Victaulic•brand 1"CPVC tees;or 11/2"polybutylene tee as designated on the drawings and/or as specified herein.Detectors shall mount on any clear pipe span of the appropriate size,either a vertical or horizontal run at least 6"from any • fittings or valves which may change water direction,flow rate,or pipe diameter or no closer than 24"from a valve or drain.Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 250 psi.The retard t-tap detector shall be a sealed mechanical pneumatic unit with visual indication of actuation.The actuation mechanism shall include a polyethylene vane inserted through the tee fitting and connected by a mechanical linkage to the delay mechanism.Outputs shall consist of dual SPDT switches(Form C contacts).Two conduit entrances(one of which is a knockout type)for standard fittings of commonly used electrical conduit shall be provided on the detectors.A grounding provision is provided.WFDTH is listed by Underwriters Laboratories for indoor use. Physical/Operating Specifications Static Pressure Rating 250 PSI(max.) Operating Temperature Range 32°F to 120°F(0°C to 49°C) Maximum Surge 18 FPS Enclosure Rating UL listed for indoor use Triggering Threshold 4-10 GPM Cover Tamper Switch Canadian models only,factory installed Bandwidth(Flow Rate) Overall Dimensions, 4.5"H x 3.55-W x 67"L Service Use Automatic Sprinkler:NFPA 13 Installed (11.4cm H x 9cm W x 17cm L) One or Two Family Dwelling:NFPA 13D Residential Occupancies up to 4 Stories:NFPA 13R National Fire Alarm Code:NFPA 72 Contact Ratings Two sets of SPDT(Form C) Shipping Weight 2.6 lbs.(1.2 kg.) 10.0 A @ 125/250 VAC 2.5A @24VDC Compatible Tee Threaded ferrous and brass tees,copper Warranty 3 years Fittings sweat tees,CPVC tees,and polybutylene tees Conduit Entrances Two openings for 1/2"conduit. U.S.Patent Numbers 3,845,259;4,782,333;5,213,205 Flactrirnl Connections Delay Adjustment Dial vcaw� inwjwaan�ona vier NOTE:COMMON AND B-NO out is UL-LISTED SSM24-X CONNECTIONS WILL CLOSE Delay e°o A•!N SE"b COMPATIBLE SSV120-X WHEN VANE IS DEFLECTED,I.E., �`.n� v CONTROL PANEL WHEN WATER IS FLOWING.DUAL adjustment /?0 0 +r<,,` SWITCHES PERMIT dial \1 POWER APPLICATIONS TO BE COMBINED it' °�24VDC OR- I ON A SINGLE DETECTOR. Q 1 120VAC SUGGESTED EOL CONTACT RATINGS INrrIA LOOP _ 1224VDC 2.5 AMPS � LOOP RESISTOR 5/ 50 V 20 AMPS ,4 SCHEMATIC OF ANC �' INDIVIDUAL NOTE:Retard time may exceed 90 seconds. SWITCH IN coM Adjust and verify that time does not exceed 90 seconds. i `' i`' - `A I' i CONDITION FLOW" d_eN° A &WD66N0 A � BREAK WIRE AS Q ••SNRCH I 111-NO SWITCH 2 I^yaj SHOWN FOR V1� ..eo .o.r�At SUPERVISION OF ,r m turn. wM."AT.1 `l/ CONNECTION.DO •Ij11.i iti• LT Imo A.. NOT ALLOW 4■'WZIWI IMP M L°' STRIPPED WIRE 0 ten) (i=w0 LEADS TO EXTEND BEYOND SWITCH HOUSING.DO NOT Irl —M LOOP WIRES. Ordering Information UL Model No. ULC/Canadian Model No. Description WFDTH WFDTHA Waterflow Detector,Fits 1,11/4",11/",2-ferrous and brass threaded tees;1,11/:,,11/,2"copper sweat tees;1-CPVC tees;and 111'polybutylene tees Accessories A77-01-02 Replacement terminal block for WFDTH S07-66002 Replacement tamper screws for covers of WFDTH PRK9 Replacement paddle kit-12 paddles for WFDTH(see WFDW Replacement tamper proof wrench for cover of WFDTH for sizes included) WFDTH A3008-00 Replacement retard mechanism C58-0009-000 Replacement metal cover Spears'is a registered trademark of the Spears Manufacturing Company.Victaulic-is a registered trademark d the Mctaulk Company of America. • *� SS YSTEM 02010 System Sensor. 3825 Ohio Avenue•St.Charles,IL 60174 Aoductspecir subject to change withannaace.Vsitsntemu nprmmfa �� SENSOR Phone:800-SENSOR2-Fax:630-377-6495 current :duct information,including the latest`ersi°nof this data sheet. A05-0341-008.7/10./2451 • . P POTTER BELLS The Symbol of Protection PBA-AC & MBA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) t Voltages Available: 24VAC 120VAC 12VDC(10.2 to 15.6)Polarized 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm 6 General Signaling 4.0 Burglar Alarm Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWG stranded wires ® DC Bells-Terminal strip * Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA126 1750070 .12A 85 76 8(200) 12VDC MBA128 1750080 .12A 90 77 10(250) 12VDC MBA1210 1750060 .12A 92 78 6(150) 24VDC MBA246 1750100 .06A 87 77 8(200) 24VDC MBA248 1750110 .06A 91 79 10(250) 24VDC MBA2410 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 I0(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing. In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-I.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5400776-REV Y PAGE I OF 2 5/08 P POTTER BELLS The Symbol of Protection PBA-AC &MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. 1 Fig.3 A.C.BELLS WHITE(LN) WHITE(OUT) (230) r �, I FROM CONTROL O 6" I I PANEL OR (I�) I o I PRECEDING BELL .40 BLACK(IN) , BLACK(OUT) �T CAUTION: WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. _..j 2 11/16" (68) DWG T161 NOTES: I.WHEN USING AC BELLS,TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL, 2.END•OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS. DWG ntr3 Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP Box has one threaded 1/2"/2"conrinn rni is nrr ri, - VIII - �`' III 5 3/4- O — 3(3/ (127) 1, To Next a (146) Device or End-of-Line 4 L— illur, ip Resistor J 3/8" _...i 1 (R6) (41)41) 4 1/4" (108) Installation DWG r,77,2 1. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and I not less than 6"below the ceiling. _ -.7 : 2. Remove the gong. 3. Connect wiring(see Fig.3). T / 4. Mount bell mechanism to backbox(bell mechanism must be mounted with the striker pointing down). / 5. Reinstall the gong(be sure that the gong positioning pin,in the /\ mechanism housing,is in the hole in the gong). / 6. Test all bells for proper operation and observe that they can 1313 - be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). Failure to install striker down will prevent bell from operating. PRINTED IN USA MFG.#5400776-REV Y PAGE 2 OF 2 5/08 X000 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 511 SIDE MOUNT C.P.V.C. - COPPER HANGER 0 SIZE-3/4"thru 2"pipe. MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. Side view-For LISTINGS- Drawings Below c!us EX 4231,EX 2551 �� FUNCTION- Hanger on C.P.V.0 and Copper pipe. INSTALLATION-Per N.F.P.A. 13, 13R and 13D on Q Q top or bottom of beam.Space by pipe type FASTENERS-UL Listed per NFPA 13. 0 in WOOD: �� CPVC pipe-#905 screw- no pre-drill. ; Copper pipe-#905 screw- no pre-drill. �� in STEEL: __ CPVC pipe- 1/4"or•#14 Tek Screw. Copper pipe- 1/4"or#14 Tek Screw. FEATURES *Offset edge eliminates abrasion. *Retainer dimples secure hanger to pipe during installation. *Required AFCON#905 screw has 5/16"hex head- included. Hanger-Wood Stud ORDERING-Part#and pipe size. Hanger-Metal Stud • CAD 4/04 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 513 C.P.V.C. - STEEL - COPPER HANGER a SIZE-3/4"thru 2"pipe. MATERIAL-Carbon Steel. Hanger FINISH -Mil.Galvanized. LISTINGS- 111111.111115 c�us EX 4231,EX 2551 FUNCTION-To support horizontal piping- C.P.V.C. ,Copper or Steel. Restrainer Tab up=Hanger. Tab down=Restrainer. INSTALLATION- Per N.F.P.A. 13, 13R and 13D on Mr Stabilize-Only side or top of beam. Space by pipe type. FASTENERS-UL Listed per NFPA 13. , " in WOOD: CPVC pipe-#905 screw-no pre-drill. Copper pipe-#905 screw-no pre-drill. f�rl Steel pipe- 1/4"xl 1/2"lag screw-no pre-drill. in STEEL: CPVC pipe- 1/4"or#14 Tek Screw. Copper pipe- 1/4"or#14 Tek Screw. Steel pipe- 1/4"or#14 Tek Screw. FEATURES *Offset edge eliminates abrasion. * Required AFCON#905 screw has 5/16"hex head- included. ORDERING-Part#and pipe size. Drawing A *Also listed as a hanger/restrainer combination. Install per drawing A. l '1040 CAD 5/04 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 514 OFFSET C.P.V.C. - STEEL - COPPER 40 HANGER •1111.111: SIZE-3/4"thru 2"pipe. MATERIAL-Carbon Steel. FINISH-Mil.Galvanized.. _ ` C LISTINGS- ink EX 4231,EX 2551 =� PATENT-No.6,648,278. FUNCTION- To support horizontal piping-C.P.V.C.,Copper or Steel. Hanger and restrainer in listed mounting positions on vertical,top horizontal and bottom horizontal surfaces. 010 Provides horizontal restraint on vertical piping. INSTALLATION- Per N.F.P.A 13, 13R and 13D.Space by pipe type. Install on wood,concrete or steel. Snap over pipe then squeeze strap back allowing pipe to slide freely. o - o • p Use#906 backing nut when#905 threads are exposed on minimum 4 3/8"or thicker wood web-see drawing. • FASTENERS-in wood and steel UL Listed per NFPA 13 4 WOOD: CPVC pipe-#905 screw-no pre-drill. Copper pipe- #905 screw- no pre-drill. Steel pipe- 1/4"xl 1/2"lag screw- no pre-drill. Mr, 11 Thru 5/8"gypsum board- 1/4"x 2"lag screw. STEEL:min.20 GA. CPVC pipe- 1/4"or#14 Tek Screw. Copper pipe- 1/4"or#14 Tek Screw. Steel pipe- 1/4"or#14 Tek Screw. CONCRETE:per NFPA 13- load used to size fasteners 5(wt)22501bs. —wt ea.fastener FEATURES ■ * 1 1/2"Offset. *3/4"and 1"pipe size made with common center-line. *Leg design produces superior strength. =MU *Offset edge eliminates abrasion. *Required AFCON#905 screw has 5/16"hex head- included ORDERING-Part#and pipe size. AFCON#906 sold separately. I. CAD 1/06 BPS 2013-40o p- Dan Nelson 1 I 1 55 1,1A/ 4-'Ct 1 ( GM) From: Darrell Fluit <Darrell.Fluit @wsfp.us> . Sent: Friday, March 22,2013 8:42 AM To: Mark VanDomelen; Dan Nelson Cc: Bryan Kelley ' Subject: St James Apartments - Bldg F Attachments: WSFP - calc domestic demand.pdf Mark/ Dan, Attached please find a revised hydraulic calculation reflecting the additional domestic demand for those two buildings per Fixture Unit Load Tables in NFPA 13R. The system still works with the added demand, so it appears that the system as installed should be okay. Thanks, Darrell Fluit 971.409.3248 • 1 Annex A Explanatory Material Page 2 of 7 Table A.6.6.5(b) Total Estimated Domestic Demand Total Demand For Systems For Systems with Predominately with Predominately Flush Tanks Flush Valves Total Fixture Load Units [from Table A.6.6.5(a)] gpm L/min gpm L/min 1 3 11.25 — — 2 5 18.75 — — 5 10 37.5 15 56 10 15 56 25 94 20 20 75 35 13 35 25 94 45 169 50 30 113 50 187 70 35 131 60 225 100 45 169 70 262 150 55 200 80 300 200 65 244 90 337 250 75 261 100 375 350 100 375 125 469 500 125 469 150 562 750 175 656 175 656 1000 200 750 200 750 1500 275 1031 275 1031 2000 325 1219 325 1219 3500 500 1875 500 1875 A.6.7.2 These connections should be installed so that the valve can be opened fully and for a sufficient . time period to ensure a proper test without causing water damage. The test connection should be designed and sized to verify the sufficiency of the water supply and alarm mechanisms. A.6.7.3 These connections should be installed so that the valve can be opened fully and for a sufficient time period to ensure a proper test without causing water damage. The test connection should be designed and sized to verify the sufficiency of the water supply and alarm mechanisms. I A.6.7.4 The fire department connection should be connected to the system riser. For single systems, it http://www.nfpa.org/codesonline/document.asp?action=load&scope=0&path=NFPA/codes... 3/21/2008 Annex A Explanatory Material Page 1 of 7 A.6.6.5 Table A.6.6.5(a) and Table A.6.6.5(12) can be used to determine a domestic design demand. Using Table A.6.6.5(a),the total number of water supply fixture units downstream of any point in the piping serving both sprinkler and domestic needs is determined. Using Table A.6.6.5(bI,the appropriate total flow allowance is determined and added to the sprinkler demand at the total pressure required for the sprinkler system at that point. Table A.6.6.5(a) Fixture Load Values Facility Type Unit Private Facilities(those within individual dwelling units) Bathroom group with flush tank(including lavatory,water closet,and bathtub with shower) 6 Bathroom group with flush valve 8 Bathtub 2 Dishwasher 1 Kitchen sink 2 Laundry trays 3 Lavatory 1 Shower stall 2 Washing machine 2 Water closet with flush valve 6 Water closet with flush tank 3 Public Facilities Bathtub 4 Drinking fountain 0 Kitchen sink 4 Lavatory 2 Service sink 3 Shower head 4 Urinal with 1 in.(25.4 mm)flush valve 10 Urinal with Yi in.(19 mm)flush valve 5 Urinal with flush tank 3 Washing machine [8 lb(3.63 kg)] 3 Washing machine [16 lb(7.26 kg)] 4 Water closet with flush valve 10 Water closet with flush tank 5 httn://www.nfna.ore/codesonline/document.asp?action=load&scope=0&oath=NFPA/codes... 3/21/2008 . . z .u. 4,- 6_z NE* -2: Flvs- 1-114 um P 0, til,"a a° ADDED 556-PM foR alsTrw, 0" DonEST it PIP1 WI- To BLOIS,%Or% L:1TALPAc:u51 51 yIL ELL AI 1:TA0AE:ii:4;311 4(t)(i1)0Toirrfc.f 1- 1 ,. I • I. • ; , I ' ' '- r''" -1.- '; CA _.--:—- 1 ---.-: • .—— T . I .-_.- —17. •' i -' 117, . . 2 , ... ',_, ■__1..4 ::,1, -.-. TRES E 'TWO 1 ) a 7 e 4, guile IM&S 0,/18INEo z: . r -, .._.-, .- • 4'el.' 17LrASE REf€F2 To ..."'76In%/1............ 60' 41/4 A TTA-ci-lEb "MVIS Et w HYDRAULIC CALcuLATI e r4 5 NNIEST E1214 5 TATEs ReE PizO-T ECTIO ts1 CO. 13B% FIR STeEtr,- ScirrE 13 oREGot) CAT4 i oR 91045 illi[Hydraulic Summary Job Number:LM0027 Report Description. Residential Job Job Number ' Design Enyinser 1M0027 Job Neme .-_. _.� SIMeGerootkonArc.ns.Number St James Apartments-BUILDING F CCB 104570 Metro 4003 11155 SW Hall Blvd. City of Tigard Add1°2 Job Sdareuildnp --- Tigard,Oregon 97223 2nd Floor Address 3 -- Doering Awn. - LM0027.cad System 'Remote Area(s) Most Dem.nen1 Spnntle Deo +OuOuO.nu Jo0 Sum. 4.3 K-Factor 12.01 at 7.800 Residential Hose Afire ant Al Source - Needy ---- --- Ned Acoconen 0.00 0.050gpmlft' 900.00ft2(Actual 332.12ft2) P 9lborri Hose Suppbes Number Or Spnrdeem Cewul.l.d _--_ Ce.sesp PM EgInis Node Flow(gpm) 4 100.00ft2 Hose At Node 3 55.00 Aa4OOeek Rawls Prawn.Fe,Reno.N.110 Ardecel To Most RemoteNe Right:48.563 Toter Hoee Streams ----— --- 55.00 Sysl.m Fbeo DeMee— TOM Y,'M.r R.lun.dfln Jltlnp Hawed.beer 106.53 106.53 hiewmws.Predawn Unbtls„>in Leaf 0.000 Meenum v.loate Anal*Grouts _ 17.37 between nodes 54 and 58 M:pmum Vsloo0 under Ground v.v....p..1;e'w.t Ppn 'Nu'eeu.po 01Dry Pipes 1096.00gal Supplies Hose Flow Static Residual Flow Available @ Total Demand I Required Safety Margin Node I (gpm) (Psi) I (psi) (9pm) f (Psi) (9Pm) (Psi) (psi) 1- i. _ 78.000 _ 63 000 I 1901.00 - 77_927 I 106.53 ( 53.114 24.813 Contractor • Conn error N,ml.., CanoM New LM0027 Darrell Fluit PM/Designer .em e M Coraect°, Phone EMeneren Western States Fire Protection Co. 503.657.5155 223 Addrew 1 -- FAX 13896 Fir Street,Suite B 503.657.5182 Address Oregon City,OR 97045 darrell.fluit @wsfp.us - ,n.ea.. www.wsfp.com A�y©M.E.P.CAD,Inc. AutoSPRINKO VR8 v8 1.11 03/22/2013 8.27 13AM Page 1 lj*auIøc.Ana1y3is . .1 Job Number:LM0027 Report Description:Residential Pipe Type_ Diameter Flow _ Velocity _ HWC _ Friction Loss _ Length 'Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length (Summary Upstream I Total Length s• Route 1 DR 1.1010 12.01 4.05 150 __0.026483 _ 4'-53 Pf 0.383 101 8'-0 12.01 4.3 7.800 Sprinkler, 10'-0 Pe -0.217 74 8'-6 7.966 E(5'-0),T(5'-0) 14'-5'Y Pv BL - 1.1010 24.07 8.11 150 0.095872 7'-1 Pf 0.871 74 8'-6 12.06 7.966 Flow(q)from Route 2 2'-0 Pe 62 8'-6 8.837 2Tr(1'-0) 9'-1 Pv BL 1.1010 36.89 12.43 150 0.211212 _ 12'-0 Pf 2.746 62 8'-6 12.82 8.837 Flow(q)from Route 3 1'-0 Pe 58 8'-6 11.583 Tr(1'-0) 13'-0 Pv BL __ 1.1010 51.53 17.37 150 0.391928 i 20'-11+x5 Pf 12.525 58 8'-6 11.583 - 11'-0 Pe 0.000 54 8'-6 24.108 2T(5'-0),Tr(1'-0) 31'-111/�Pv BL _ _1.5980 51.53 8.24 150 0.063869_ 24'-3 Pf 3.401 54 8'-6 24.108 29'-0 Pe 6.506 15 5'-6 34.016 2EE(2'-0),2T(8'-0),E(7'-0), 53'-3 Pv cplg(1'-0),Tr(1'-0) BL 1.6100 51.53 8.12 120 _ 0.093058 I 3'-1 Pf 5.286 15 5'-6 34.016 'Pe 1.333 13 2'-5 40.635 BFP(-5.000) 3'-j Pv BL ___. 1.5980 •__ 51.53 8.24 150 0.063869 6'-0+ Pf 1.344 13 2'-5 40.635 15'-0 Pe 1.915 2 -2'-0 43.894 cplg(1'-0),2E(7'-0) 21'-0+/Pv . BL 2.0670 51.53 ____ 4.93 _ 120 0.027560 309'-635 Pf 8.807 10'-0 Pe 3 -2'-0 52.701 T(10'-0) 319'-6A Pv BL - 4.2200 106.53 2.44 140 _ 0.002457 _ 64'-935 Pf 0.200 3 -2'-0 55.00 52.701 16'-81A Pe 49 -2'-0 52.901 E(16'-8%) 81'-6 Pv BL 6.2800 _ 106.53 _._ 1.10 140 0.000354 600'-O}Pf 0.213 49 -2'-0 52.901 Supply, i Pe 1 -2'-0 53.114 600'-01 Pv _` 0.00 Hose Allowance At Source 1 106.53 ✓ Route 2 DR 1.1010 12.06 4.07 _ 150 _ .0.026705 1'-8!Pf 0.312 8' 102 -0 12.06 4.3 7.871 Sprinkler, -_ 10'-0 Pe -0.217 74 8'-6 7.966 E(5'-0),T(5'-0) 1 11'-aPv o Route 3 DR 1.1010 12.82 4.32_ 150 0.029887 _I 0'-B Pf 0.164 103 8'-00----12.82 4.3 8.889 __ Sprinkler, 5'-0 Pe -0.217 62 8'-6 8.837 T(5'-0) j 5'-6 Pv *+ Route 4 DR 1.1010 14.64 4.93 _ 150 0.038198 0'-6 Pf 0.210 104 8'0 14.64 4.3 11.589 Sprinkler, 6-0 Pe -0.217 58 8'-6 11.583 T(5'-0) 6-6,Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) k C Value Multiplier I Actual Inside Diameter °B7 Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713_ 1.16 1 33 1.51 _ • • &,®M.E.P.CAD,Inc. IN AutoSPRINK®VR8 v8.1 11 03/22/2013 8:20:43AM Page 1 g (Hydraulic iAnaIOU Job Number. LM0027 Report Description.Residential Pipe Type Diameter Flow Velocity HWC Friction Loss 'Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary U tream Total Len th AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain Discharge gpm BaIV Ball Valve DR Drop BFP Backflow Preventer DY Dynamic Velocity fps BV Butterfly Valve FM Feed Main Pressure psi C Cross Flow Turn 90° FR Feed Riser Length Foot cplg Coupling MS Miscellaneous Friction Loss psi/Foot Cr Cross Run OR Outrigger HWC Hazen-Williams Constant CV Check Valve RN Riser Nipple Pt Total pressure at a point in a pipe DeIV Deluge Valve SP Sprig DPV Dry Pipe Valve ST Stand Pipe Pn Normal pressure at a point in a pipe E 90°Elbow UG Underground Pf Pressure loss due to friction between points EE 45°Elbow Pe Pressure due to elevation difference between indicated Eel 11%°Elbow points Eel 22% Elbow Pv Velocity pressure at a point in a pipe f Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GIoV Globe Valve GV Gate Valve Ho Hose Hose Hose i-iV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap M.E.P CAD, Inc. MAutoSPRINKO VR8 v8 1 11 03/22/2013 8:20 43AM Page 2 • ...... RECEIVED HMI DEC 2 6 2012 Job Number:LM0027 • Report Description:Residential '°°M00 °' ` "` LM0027 BUILDING DIVISION Job Name'. P0O00 FA% • St James Apartments-BUILDING F Mfrs 1 State CeNM1UM1ml.mnee Number 11155 SW Hall Blvd. CCB 104570 Metro 4003 Address _ _ ANI _. Tigard,Oregon 97223 City of Tigard Address 3 Job SiblBuidtng 2nd Floor Penury Mee 01Appir uce 0.050gpm/ft' 900.00ft'(Actual 332.12ft') Mom Demand,Sommer Data Nor Severna 4.3 K-Factor 12.01 at 7.800 0.00 Coverege Per Sprinkler Number Of Sprinklers Calculated 100.00ft2 4 System Pressure Demand System Flow Deemed 56.079 51.53 Total Demand Pressure Result 51.53 @ 56.079 +21.903(28.1%) Node Flow(oom) Hose Flow(apm) Static(osil Residual(osi) Identifier Pressure(psi) K-Factor(K) Flow(apm) 1 1901.00 78.000 63.000 Pip PROFt `�•<c•ENGINEER 0 1r 80785PE / ' /41 OREGON 0 cc 'LINE 301.10 ‘, moos■ ' 4REDAN\� / //s 1 ECptRESI " , 10o B j 90 - ' 80 tatic Pressure 78.000 70 • g_ 60 .1.53 @ 56.079 - 1901.00 @ 63.000 .I °i 50 t • 11 o_ 40 • a ystem demand curve rer • %". 0 . 20 O? 10 • . . SW.r , • r,,-, P;i 0 Dm]l l l l l l l l l l l l l l l l l l l l l l l l l l l 1 1 1 1 1 1 1 1 1 111111111 11 1 1 1 1 11 1 800 1000 1200 1400 1600 1800 2000 i Water flow,gpm ks,©M.E.P.CAD,Inc. ®AutoSPRINK®VR8 v8.1.11 12/21/2012 10:35:33AM Page 1 H I Hydraulic Summary` 1111 Job Number:LM0027 Report Description:Residential Job Number IJaegr Eryllr LM0027 Job Name --- SUM CYrOWNlbwrl number St James Apartments-BUILDING F CCB 104570 Metro 4003 • ACdtae I Mu - - -- 11155 SW Hall Blvd. City of Tigard AtMMw 2 Jab SmAkilldl p Tigard,Oregon 97223 2nd Floor Aedrras 3 (WIN,Noma LM0027.cad Mwt Dentwa acv S.fl*ler On Occupancy I Jab SoIM 4.3 K-Factor 12.01 at 7.800 Residential Ho.eArlo..oAt aeea - -— - -- o.ra AlwaApptratlon 0.00 0.050gpm/ft' 900.00W(Actual 332.1211') Aeifwwl How ByliM- - - Number a SP.Mera ColaWM Coverage Per SprntMr Nag Flow(aoml 4 i 100.00W AuwPew Rauw:Haws For RenaN Araya)An)eoent To Moe!mite Alp Right:51.164 Total Hose Streams 0.00 System Flow Demand Total Water Required)lncludfnp Noes Allowance) 51.53 51.53 Maamum Pressure 150t1 Low t 0.000 Ilaidaeee Wally ASea Grew.] 17.37 between nodes 54 and 58 Madman Velocity over arena Volume capacity of MM Plow Volume capauty or Dry Pipes 478.16gal Hose Flow Static Residual Flow Available @ Total Demand Required Safety Margin Node (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi) 1 78.000 63.000 1901.00 77.981 51.53 56.079 - j 21.903 Contractor Number Contact Name Contact Title LM0027 Darrell Fluit PM/Designer Name of Contractor. . Plow Exlenstoo -- - Western States Fire Protection Co. 503.657.5155 223 AA mess f FAX 13896 Fir Street,Suite B 503.657.5182 Andres] Oregon City,OR 97045 darrell.fluit@twsfp.us Address] . va.aa -- www.wsfp.00m ©M.E.P.CAD,Inc. AutoSPRINK®VR8 v8.1.11 12/21/2012 10:35:50AM Page 2 •a, .b,' IP , '�7 ' " r� Job Number:LM0027 A Report Description:Residential Actual Flow Minimum Flow K-Factor Pressure Dsvlca Wm) (gpm) V() (psi) * Sprinkler 101 12.01 12.01 4.3 7.800 Sprinkler 102 12.08 12.01 4.3 7.871 Sprinkler 103 12.82 _ 12.01 4.3 8.889 Sprinkler 104 14.84 12.97 4.3 11.589 Most Demanding Sprinkler Data • • • • L,©M.E.P.CAD,Inc. AutoSPRINKOO VR8 v8.1.11 12/21/2012 10:35.57AM Page 3 • 01 1 Node Analysis Job Number:LM0027 Report Description:Residential Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 1 -2'-0 S 56.079 51.53 101 8'-0 Spr(-7.800) 7.800 12.01 • 102 8'-0 Spr(-7.871) 7.871 12.06 103 8'-0 Spr(-8.889) 8.889 12.82 104 8'-0 Spr(-11.589) 11.589 14.64 2 -7-0 E(7'-0) 43.785 12 1'-0 _ 41.296 18 6'-11 33.182 49 -2-0 E(4'-0) 55.694 54 8'-6 T(5'-0) 24.108 58 8'-6 T(6-0),Tr(1'-0) 11.583 62 8'-6 T(5'-0),Tr(V-0) 8.837 74 8'-0 T(5'-0) 7.966 ©M.E.P.CAD,Inc. el AutoSPRINK®VR8 v8.1.11 12/21/2012 10:36:04AM Page 4 111 Job Number:LM0027 Report Description:Residential Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length MD Route 1 • DR 1.1010 _12.01 _ 4.05 150 0.026483 4'-5%z Pf 0.383 . 101 8-0 12.01 4.3 7.800 Sprinkler, 10'-0 Pe -0.217 74 8-6 7.966 E(5'-0),T(5-0) 14'-5'/a Pv BL 1.1010 24.07 8.11 150 0.095872 7'-1 Pf 0.871 74 8'-6 12.06 7.966 Flow(q)from Route 2 2'-0 Pe 62 8'-6 8.837 2Tr(1'-0) 9'-1 Pv BL 1.1010 36.89 12.43 150 0.211212 12'-0 Pf 2.746 62 8'-6 12.82 8.837 Flow(q)from Route 3 1'-0 Pe 58 8-6 11.583 Tr(1'-0) 13'-0 Pv BL 1.1010 51.53 17.37 150 0.391928 20'-11%Pf 12.525 58 8'-6 11.583 11'-0 Pe 0.000 54 8'-6 24.108 2T(5'-0),Tr(1'-0) 31'-11'/a Pv BL 1.5980 51.53 8.24 150 0.063869 22'-10 Pf 3.183 54 8'-6 24.108 27'-0 Pe 5.891 16 8-11 33.182 2EE(2'-0),2T(8'-0),E(7'-0) 49'-10 Pv BL 1.6100 51.53 8.12 120 0.093058 5'-11 Pf 5.550 16 8-11 33.182 Pe 2.564 12 1'-0 41.296 BFP(-5.000) 5'-11 Pv • BL 1.5980 51.53 8.24 150 0.063869 4'-7".4 Pf 1.189 12 1'-0 41.296 14'-0 Pe 1.299 ' 2 -7-0 43.785 2E(7'-0) 18'-7%Pv BL 1.6100 51.53 8.12 120 0.093058 119'-11'.4 Pf 11.909 • 2 -7-0 43.785 8'-0 Pe 49 -7-0 55.894 2E(4'-0) 127'-1114 Pv BL 4.2200 51.53 1.18 140 0.000641 600'-4 Pf 0.385 49 -7-0 55.694 Supply, Ps 1 -7-0 56.079 600' Pv 0.00 Hose Allowance At Source 1 51.53 •- Route 2 DR _ 1.1010 12.06 4.07 150 0.026705 1'-8 Pf 0.312 102 8-0 12.06 4.3 7.871 Sprinkler, 10'-0 Pe -0.217 74 8'-6 7.966 E(5'-0),T(5'-0) 11'-8 Pv w Routs 3 ' DR 1.1010 12.82 4.32 150 0.029887 0'-6 Pf 0.164 103 6'-0 12.82 4.3 8.889 Sprinkler, 5'-0 Pe -0.217 62 8'-6 8.837 T(5'-0) 5'-6 Pv r- Route 4 DR _ 1.1010 14.64 4.93 150 _ _ 0.038198 0'-6 Pf 0.210 104 8-0 14.64 4.3 11.589 Sprinkler, 5'-0 Pe -0.217 58 8'-6 11.583 T(5-0) 5'-6 Pv Equivalent Pipe Lengths o!Vaives and Fittings(C=120 or;Wi _ 11 IrtTrUe Multiplier r 1 Actual Inside Diameter 4 87 ( Value Of C 100 0 130 140 150 Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor .713 1.16 1 33 1 51 L©M.E.P.CAD,Inc. a AutoSPRINK®VR8 v8.1.11 12/21/2012 10:36:09AM Page 5 9I19 a l%1{j ___t�E it 3 Job Number:LM0027 Report Description:Residential Pipe Type Diameter Flow Velocity MWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length F , AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain BaIV Ball Valve DR Drop Discharge gpm BFP Backflow Preventer DY Dynamic Velocity fps BV Butterfly Valve FM Feed Main Pressure psi C Cross Flow Turn 90° FR Feed Riser Length Foot cplg Coupling MS Miscellaneous Friction Loss psi/Foot Cr Cross Run OR Outrigger HWC Hazen-Williams Constant CV Check Valve RN Riser Nipple DelV Deluge Valve Pt Total pressure at a point in a pipe SP Sprig DPV Dry Pipe Valve ST Stand Pipe Pn Normal pressure at a point in a pipe E 90°Elbow UG Underground Pf Pressure loss due to friction between points EE 45°Elbow Pe Pressure due to elevation difference between indicated Eel 1114°Elbow points Ee2 22;4°Elbow Pv Velocity pressure at a point in a pipe f Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow fig Flange FN Floating Node fT FireLock(TM)Tee • g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose H'V Hose Valve Hyd Hydrant LIE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD,Inc. AutoSPRINK®VR8 v8.1.11 12/21/2012 10:36:09AM Page 6 4 • r Job Numher.LM0027 Report Description:Residential Supply at Node 1 • 100 90— 80 Static Pressure 78.000 70 1901.00 63.000 60 51.53 56.079 - a 2 50 - 8 v 40 30 7:s stem demand curve 20 • 10 0 �iuuuwiuu I I I 1 1 1 1,1 1 1 1 I II I I I i I 1 1 111_11 1 1 . 1 1 1 1 1 1 1 1 1 ) ) ) ) ) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0200 400 600 800 1000 1200 1400 1800 1800 2000 Water flow,gpm 'Hya.ufc Graph Supply at Node 1 ' Sla,c Penrose -78.000 Reselual Pressure 63.000 @ 1901.00 Available Pressure et Time of Test 77.981 @ 51.53 g System Dan. 56.079 @ 51.53 System 0611811d(Including llun Motown,et Source) 56.079 @ 51.53 ©M.E.P.CAD,Inc. 111 AutoSPRINK®VR8 v8.1 11 12/21/2012 10:36:16AM Page 7 Job Number:LM0027 Report Description:Residential • Up le • Up < 6 • • • • • • .-. .-. • 0 jj% fE, o 0 Vii' '///j 9:0 • C M.E.P.CAD.Inc. AutoSPRINK®VR8 v8.1.11 12/21/2012 10:36:22AM Page 8