Report CC Z K a b00(-440
�
30\ e L j
COMcheck Software Version 3.8.0
Mechanical Compliance Certificate
Oregon Energy Efficiency Specialty Code
Section 1: Project Information
Project Type:Alteration
Project Title : Infocus
Construction Site: Owner/Agent: Designer/Contractor:
7301 SW KABLE IN
Tigard,OR 97224
Section 2: General Information
Building Location(for weather data): Sherwood,Oregon
Climate Zone: 4c
Section 3: Mechanical Systems List
Quantity System Type&Description
1 HVAC System 1:Heating:Heating equipment(Other),Gas,Capacity 105 kBtu/h/Cooling:Cooling equipment
(Rooftop Package Unit),Capacity 37 kBtu/h,Efficiency: 13.00 SEER,Air-Cooled Condenser/Single Zone
1 HVAC System 2:Heating:Heating equipment(Other),Gas,Capacity 150 kBtu/h/Cooling:Cooling equipment
(Rooftop Package Unit),Capacity 50 kBtu/h,Efficiency: 13.00 SEER,Air-Cooled Condenser/Single Zone
Section 4: Requirements Checklist
In the following requirements,the relevant code section reference is shown in[].'+'denotes that more details exist in the specified code
section.
Requirements Specific To: HVAC System 1 :
w 1. [503.2.3+]Equipment meets minimum efficiency: Rooftop Package Unit: 13.0 SEER
2. [503.3.1 +]Supply air economizers shall be provided on each cooling system and are capable of providing 100-percent outdoor air,
even if additional mechanical cooling is required to meet the cooling load of the building.Systems provide a means to relieve excess
outdoor air during economizer operation to prevent overpressurizing the building.
L$'Exception: Cooling equipment less than 54,000 Btu/hr total cooling capacity.The total capacity of all such units without
/'` economizers shall not exceed 240,000 Btu/hr per building area served by one utility meter or service,or 10 percent of its total
installed cooling capacity,whichever is greater.That portion of the equipment serving dwelling units and guest rooms is not
included in determining the total capacity of units without economizers.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
Li 3. [503.3.2]Hydronic system controls,Hydronic systems of at least 300,000 Btu/h design output capacity supplying heated and chilled
water to comfort conditioning systems include controls that meet the requirements of Section 503.4.3.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
Requirements Specific To: HVAC System 2 :
1. [503.2.3+]Equipment meets minimum efficiency: Rooftop Package Unit: 13.0 SEER
u 2. [503.3.1 +]Supply air economizers shall be provided on each cooling system and are capable of providing 100-percent outdoor air,
even if additional mechanical cooling is required to meet the cooling load of the building.Systems provide a means to relieve excess
outdoor air during economizer operation to prevent overpressurizing the building.
le-Exception: Cooling equipment less than 54,000 Btu/hr total cooling capacity.The total capacity of all such units without
economizers shall not exceed 240,000 Btu/hr per building area served by one utility meter or service,or 10 percent of its total
installed cooling capacity,whichever is greater.That portion of the equipment serving dwelling units and guest rooms is not
included in determining the total capacity of units without economizers.
Project Title: lnfocus Report date: 08/18/14
Data filename:\\SERVER1\RedirectedFolders\brute\My Documents\vangaurd EMS.cck Page 1 of 5
Location in plans/specs where compliance can be identified(enter NA if not applicable)
it 3. [503.3.2]Hydronic system controls.Hydronic systems of at least 300,000 Btu/h design output capacity supplying heated and chilled
water to comfort conditioning systems include controls that meet the requirements of Section 503.4.3.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
Generic Requirements: Must be met by all systems to which the requirement is applicable:
A 1. [503.2.1 +]Calculation of heating and cooling loads. Design loads are determined in accordance with the procedures described in the
ASHRAE/ACCA Standard 183.Alternatively,design loads have been determined by an approved equivalent computation procedure.
wALLj 2. [503.2.1.1 +]Packaged Electric Equipment.Specified packaged electrical equipment has a heat pump as the primary heating source.
U Exception:Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities.
Location in plans/specs where compliance can be identified(enter NA if not applicable)
X.3. [503.2.2+]Equipment and system sizing.Heating and cooling equipment and systems capacity do not exceed the loads calculated in
accordance with Section 503.2.1.
U Exception: Required standby equipment and systems provided with controls and devices that allow such systems or equipment to
operate automatically only when the primary equipment is not operating.
U Exception: Multiple units of the same equipment type with combined capacities exceeding the design load and provided with
controls that have the capability to sequence the operation of each unit based on load.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
( (4. [503.2.3+]HVAC Equipment Performance Requirements. Reported efficiencies have been tested and rated in accordance with the
/�` applicable test procedure.The efficiency has been verified through certification under an approved certification program or,if no
certification program exists,the equipment efficiency ratings are supported by data furnished by the manufacturer.
X5. [503.2.4.1 +]Thermostatic Controls.The supply of heating and cooling energy to each zone is controlled by individual thermostatic
controls that respond to temperature within the zone.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
lily(-l 6. [503.2.4.1.1]Heat pump supplementary heat.Heat pumps having supplementary electric resistance heat have controls that,except
��CC during defrost,prevent supplementary heat operation when the heat pump can meet the heating load.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
7. [503.2.4.2]Set point overlap restriction.Where used to control both heating and cooling,zone thermostatic controls provide a
temperature range or deadband of at least 5°F(2.8°C)within which the supply of heating and cooling energy to the zone is capable of
being shut off or reduced to a minimum.
U Exception:Thermostats requiring manual change over between heating and cooling modes.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
X 8. [503.2.4.3]Optimum Start Controls.Each HVAC system has controls that vary the start-up time of the system to just meet the
temperature set point at time of occupancy.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
[503.2.4.4+]Off-hour controls.Each zone is provided with thermostatic setback controls that are controlled by either an automatic time
clock or programmable control system.
Li Exception:Zones that will be operated continuously.
U Exception:Zones with a full HVAC load demand not exceeding 6,800 Btu/h(2 kW)and having a readily accessible manual shutoff
switch.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
r 10. [503.2.4.5+]Shutoff damper controls.Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers.
/" U Exception:Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
11. [503.2.4.6+]Freeze Protection and Snow melt system controls. Freeze protection systems,such as heat tracing of outdoor piping and
'Vit.._ heat exchangers,including self-regulating heat tracing,include automatic controls capable of shutting off the systems when outdoor air
temperatures meet code criteria.
Location in plans/specs where compliance can be identified(enter NA if not applicable)
tiyiL1 12. [503.2.4.8]Separate air distribution systems.Zones with special process temperature requirements and/or humidity requirements are
served by separate air distribution systems from those serving zones requiring only comfort conditions;or shall include supplementary
control provisions so that the primary systems may be specifically controlled for comfort purposes only.
Project Title: Infocus Report date: 08/18/14
Data filename:\\SERVER1\RedirectedFolders\bruce\My Documentslvangaurd EMS.cck Page 2 of 5
u Exception: [503.2.4.8+]Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for
process temperature and humidity control.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
t l 13. [503.2.4.9]Humidity control. If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a
/ zone or zones,a humidity control device is provided.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
Adip 14. [503.2.4.9.1]Humidity control.Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce
relative humidity in excess of 30 percent.Where a humidity control device is used for dehumidification,it is set to prevent the use of
fossil fuel or electricity to reduce relative humidity below 60 percent.
L] Exception: Hospitals,process needs,archives,museums,critical equipment,and other non-comfort situations with specific humidity
requirements outside this range.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
A U 15. [503.2.4.9.2]Humidity control.Where a humidity control device exists it is set to maintain a deadband of at least 10%relative humidity
IL- where no active humidification or dehumidification takes place.
1 Exception: Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system
efficiency is 10 percent higher than required in section 503.2.3,HVAC equipment performance requirements.
Location in plans/specs where compliance can be identified(enter NA if not applicable),
p 16. [503.2.5]Ventilation.Ventilation,either natural or mechanical,is provided in accordance with Chapter 4 of the International Mechanical
Code.Where mechanical ventilation is provided,the system has the capability to reduce the outdoor air supply to the minimum
required by Chapter 4 of the International Mechanical Code.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
via] 17. [503.2.5.1 +]Demand controlled ventilation(DCV).DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger
than 150 ft2 for multiple zone systems.
LJ Exception:Systems with energy recovery complying with Section 503.2.6
Lj Exception:Spaces less than 750 ft2(69.7 m2)where an occupancy sensor turns the fan off,closes the ventilation damper,or closes
the zone damper when the space is unoccupied.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
WO 18. [503.2.5.2+]Kitchen hoods. Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code.
[7 Exception: Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems.
• Exception: Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
hrtC] 19. [503.2.5.3+]Enclosed parking garage ventilation controls.In Group S-2,enclosed parking garages used for storing or handling
automobiles employs automatic carbon monoxide sensing devices.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
j 20. [503.2.6+]Energy recovery ventilation systems. Individual fan systems that have both a design supply air capacity of 5,000 cfm or
greater and a minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system.
L Exception:Where energy recovery systems are prohibited by the International Mechanical Code.
• Exception:Systems serving spaces that are not cooled and are heated to less than 60°F.
LI Exception:Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy.
• Exception:Type 1 kitchen exhaust hoods.
❑ Exception:Cooling systems in climates with a 1-percent cooling design wet-bulb temperature less than 64°F(18°C).
u Exception:Systems requiring dehumidification that employ series-style energy recovery coils wrapped around the cooling coil when
the evaporative coil is located upstream of the exhaust air stream.
L] Exception:Systems exhausting toxic,flammable,paint exhaust,corrosive fumes,or dust.
U Exception: Laboratory fume hood systems that include qualifying features.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
r�f 21. [503.2.7+]Duct and plenum insulation and sealing.All supply and return air ducts and plenums are insulated with the specified
�
`t insulation.When located within a building envelope assembly,the duct or plenum is separated from the building exterior or
unconditioned or exempt spaces by a minimum of R-8 insulation.All ducts,air handlers and filter boxes are sealed.Joints and seams
comply with Section 603.9 of the International Mechanical Code.
Project Title: Infocus Report date: 08/18/14
Data filename:\\SERVER11RedirectedFolders\brute\My Documents\vangaurd EMS.cck Page 3 of 5
❑ Exception:When located within equipment.
Li Exception:When the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15°F
(8°C).
r22. [503.2.7.1.1 +]Low-pressure duct systems.All longitudinal and transverse joints,seams and connections of low-pressure supply and
return ducts are securely fastened and sealed with welds,gaskets,mastics(adhesives),mastic-plus-embedded-fabric systems or
tapes installed in accordance with the manufacturer's installation instructions.
Li Exception:Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2
inches w.g.pressure classification.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
23. [503.2.7.1.2+]Medium-pressure duct systems.All ducts and plenums designed to operate medium-pressure are insulated and sealed
in accordance with Section 503.2.7.Pressure classifications specific to the duct system are clearly indicated on the construction
documents.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
ti/L4 24. [503.2.7.1.3+]High-pressure duct systems. Ducts designed to operate at high-pressure are insulated and sealed in accordance with
Section 503.2.7. In addition,ducts and plenums are leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
x}-25. [503.2.8+]Piping Insulation.All pipes serving space-conditioning systems(hot water piping for heat systems,chilled water,refrigerant,
/�' and brine piping systems,and steam piping)are insulated as specified by this section.
LI Exception:Pipe insulation is not required for factory-installed piping within HVAC equipment.
Li Exception: Pipe insulation is not required for piping that conveys fluids having a design operating temperature range between 60°F
and 105°F.
❑ Exception: Piping within room fan-coil(with AHRI440 rating)and unit ventilators(with AHRI840 rating).
Exception: Pipe insulation is not required for runout piping not exceeding 4 ft in length and 1 in.in diameter between the control
valve and HVAC coil.
u 26. [503.2.9.1 +]Air system balancing. Each supply air outlet and zone terminal device is equipped with means for air balancing in
accordance with the requirements of IMC 603.17.Discharge dampers intended to modulate airflow are prohibited on constant volume
fans and variable volume fans with motors 10 horsepower.
Location in plans/specs where compliance can be identified(enter NA if not applicable(:
Al) 27. [503.2.9.2]Hydronic system balancing.Individual hydronic heating and cooling coils are equipped with means for balancing and
��-- pressure test connections.
Location in plans/specs where compliance can be identified(enter NA if not applicable(..
}�28. [503.2.9.3+]Manuals.The construction documents require that an operating and maintenance manual be provided to the building
�-` owner by the mechanical contractor.See long description for specifications.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
/6 29. [503.2.10+]Air System Design and Control.Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets
the provisions of Sections 503.2.10.1 through 503.2.10.2.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
.c1/6_11 30. [503.2.10.1 +]Allowable fan floor horsepower. Each HVAC system at fan system design conditions does not exceed the allowable fan
system motor nameplate hp(Option 1)or fan system bhp(Option 2)as shown and calulated in requirement details.
L] Exception: Hospital and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure
relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power
limitation.
L_] Exception: Individual exhaust fans with motor nameplate horsepower of 1 hp or less.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
Ark_ 31. [503.2.10.2+]Motor nameplate horsepower.For each fan,the selected fan motor is no larger than the first available motor size greater
than the brake horsepower(bhp).
Li Exception:For fans less than 6 bhp,where the first available motor larger than the brake horsepower has a nameplate rating within
50 percent of the bhp,selection of the next larger nameplate motor size is allowed.
U Exception:For fans 6 bhp and larger,where the first available motor larger than the bhp has a nameplate rating within 30 percent of
the bhp,selection of the next larger nameplate motor size is allowed.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
A/6j 32. [503.2.10.3.1]Large Volume Fan Systems.Fan systems over 8,000(7 m3/s)cfm without direct expansion cooling coils that serve
single zones reduce airflow based on space thermostat heating and cooling demand.A two-speed motor or variable frequency drive
Project Title: Infocus Report date: 08/18/14
Data filename:11SERVER1 1RedirectedFolders\bruce\My Documents\vangaurd EMS.cck Page 4 of 5
reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the
International Mechanical Code,whichever is greater.
[] Exception: Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific
humidity levels or supplying an exhaust system.
Location in plans/specs where compliance can be identified(enter NA if not applicable).
33. [503.2.10.3.2+]All air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at ARI
conditions greater than or equal to 110,000 Btu/h that serve single zones have their supply fan operation controlled according to code
specific requirements.
[] Exception: Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific
humidity levels or supplying an exhaust system.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
k_U 34. [503.2.10.4]Series fan-powered terminal unit fan motors. Fan motors for series fan-powered terminal units are
electronically-commutated motors and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard
MG 1-2006 at full load rating conditions.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
/060 35. [503.2.11]Heating outside a building.Systems installed to provide heat outside a building are radiant systems.Such heating systems
are controlled by an occupancy sensing device or a timer switch,so that the system is automatically deenergized when no occupants
are present.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
q j j0 36. [503.2.12]Hot Gas Bypass Limitation.For cooling systems<=240 kBtu/h,maximum hot gas bypass capacity is no more than 50%
total cooling capacity.
Location in plans/specs where compliance can be identified(enter NA if not applicable):
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building plans,
specifications and other calculations submitted with this permit application.The proposed mechanical alteration project has been designed to
meet the Oregon Energy Efficiency Specialty Code,Chapter 8,requirements in COMcheck Version 3.8.0 and to comply with the mandatory
requirements in the Requirements Checklist. [t
1('.L�1�1SlL %"SfEC ioNJ •f1� �. � / �! � / 4f' �/
Name-Title Signature Date
Project Title: Infocus Report date: 08/18/14
Data filename: \\SERVER11RedirectedFolders\brute\My Documents\vangaurd EMS.cck Page 5 of 5
AA^^��
'vce__ ZO •r
Li - OOLitto
---701 Kabit t_L1
STRUCTURAL CALCULATIONS
FOR
IN FOCUS
OREGON BUSINESS PARK III
7301 S.W. KABLE LANE #900, BLDG. H (PTR #222)
PORTLAND, OR 97224
-- ROOF MECHANICAL UNITS --
O.p PROF
, 12,187
ri y.,
4 OR- ON 0`i0 ✓Gt y t5. 032?ti4, . NOW-\
(I EXPIRES:12/31/14 I
Contents
Details A-C D1 -D3
Gravity Calculations GI -G2
Lateral Calculations LI -L2
Contact Person: John E Nordling,PE Enclosures El -E6
NORDLING Proj. No.: 14-306
IN STRUCTURAL ROOF ME CH UNITS
. 115C ENGINEERS, LLC PAC TRUST
6775 SW 111th,Suite 200•Beaverton OR.97008 Date:AUG 2014 By: JEN Sheet No.: COVER
• G
,.
. 'Let t'. 0 ittz P k:1
e
co
r3'_9. - t
r__—, 1D — • I ..I ( i $ 1013- Va,,c (14, f 7 {a.'
0 .S 1/2 I CU. BA. 6 3/4 _IS I :— r---� l
l O 1 ` J I I
01-----1 R - ....
r I
Z 3 1 9 , I "1
II
7 6 BAVgI .0"-:1 • 0 .. ... n drr�� 014k...1`�4 le. 1�•t °P no B' t "_) T
r
.. ....' ti:Yc3; (yt ;4"(vMa t— _S_ !fir"
.... I 1 1
_ _CANT. I - Hi® x 25 1/2 I '/4 x 24 .. .. ;�.i �`` : .e
.
,4,,o 0
I W
"cl) I t
1 1
IP all
:I,
x 2S L/2 j- - -r�!4 x 24
I I NI' 600 C)--- 1 I
e
sQ 0 . ,
I I .I-
\J�
kl-
.
1 1
Of r
II
-1.
--r MI!
��ED PROFFsji
' V
ck. y12
IRE
O
�i ' ( �j� 1 v acv i$ •' Cj Chat r- 0 . .
yN f. NORC)"-
I EXPIRES:12/31/14 j I
NORDLING Proj. No.: 14-306 fl STRUCTURAL
IN FOCUS
ROOF MECH UNITS
ENGINEERS, LLC PAC TRUST
6775 SW 111th.Suite 200'Beaverton OR,97008 Date:AUG 2014 By:JEN Sheet No.: (DI
4 . -
:. p� ..
1:
iii ..._•
V !F°
GC.:4,3% .: 1 I . . .:_ . . . 42 . .
, . .
III Fr:
L___•__: _ :. i -: • '• •••:• • 1 . . •
• . •'t'`i?it..Wk: - .= ....
: •
2y.4.`.ot. �: 04.144 tic e*C.
•
- .. . : ).''t"46. • . ...i f ,.-04'.. 416.. : .-
•
•
svvi 044P-,...... teri."-----"7
g 7- � -�% � Q ED PR OFF
�. thlaa 1/4A31tr GiRa3 21 9
•
' ..REG'A
0 5 :,,:,,,,,,,,,,„.„. ,.., tr, ,.�
EXPIRES: 12/31/14 I I
. .
--- • NORDLING Proj. No.: 14-306
n5STRUCTURAL ROOF ME H UNITS
ENGINEERS, LLC PAC TRUST
6775 SW 111th.Suite 200•Beaverton OR.97008 Date:AUG 2014 By:JEN Sheet No.: D Z
-MECHANICAL UNIT
,--UNIT BASE RAIL
�J.
•12 x 3/4' SCREW
8' x 8' x 16ga STRAP,
ONE EACH SIDE
"12 x 3' SCREW SELF
A
MECHANICAL UNIT O TAPPING SCREW
0
"12 WOOD SCREWS XI2' o/c CURB I I
LEVELING CURB f FLASHING 4 ROOFING
rX
-- --------------------
_ � r
4x8 W/ SIMPSON °U46'
4x8 W/ SIMPSON 'U46'—} EACH END
EACH END PROF
NEF`/49
L v�
(E) GL GIRDER ,87
•
•
ORE •
DETAIL
5.
CyN " Nog
I EXPIRES:12/31/14
NORDLING Proj. No.: 14-306
IN FOCUS
• STRUCTURAL ROOF MECH UNITS
4._Awar ENGINEERS, LLC PAC TRUST
6775 SW 111th.Suite 200•Beaverton OR.97008 Date:AUG 2014 By: JEN Sheet No.:D3
•
' DAwa 4hr toil*K K . .. . .- ...
s •�
. tfa.w .
•rye °..... ' ' ; . : U4 4,C, 'T•
- giti. —
awe
' -04, .jpg, . • - .. - • •• - -. . • , . v i.:-.7.-_-.45-,:-)
. . 44 6.
:
. . . ing„., :...... .: .., 7.. :.....:.: .. .
E .
- •
:.._ B ..: ... .* 4 R
0 .. ' ... • ... . ..
.:. . ... ...... . -.. -:..$0" ..::ti■S UN.: 4.1■5(•..... .11' :Iva° )1•4ils;V
•
•
..Gam:... : . : : I.: 6 LIN**. (c°Z::-.:.
•
•
•
./. A
• NORDLING Pro;. No.: 14-306
IN STRUCTURAL ROOF ME CH UN TS
ENGINEERS, LLC PAC TRUST
6775 SW 111th.Suite 200•Beaverton OR.97008 Date:AUG 2014 By: JEN Sheet No.: G 1
' Nordling Structural Engineers, LLC
6775 SW 111th #200
Beaverton, OR 97008
Date:08115114 Page:
MULTI-SPAN TIMBER BEAM DESIGN
IN FOCUS-ROOF MECHANICAL UNITS
A-(SL+DL) A.(MECH) A-(COMB)
GENERAL DATA - 1 3 5
All Spans Simple Support?? : YES
Spans Length ft : 24.25 24.25 24.25
End Fixity: Pin:Pin Pin:Pin Pin:Pin
Beam Width in : 2.500 2.500 2.500
Beam Depth in : 16.50 16.50 16.50
CALCULATED VALUES -OK- -OK- -OK-
Fb-Modified Allow. psi : 2664.0 2664.0 2664.0
fb-Actual. psi : 2177.3 251.2 2425.9
F'v-Modified Allow. psi : 207.0 207.0 207.0
fv(actual)" 1.5 psi : 108.6 14.7 123.3
Moment @ Left k-in : 0.0 0.0 0.0
Moment @ Right kin : 0.0 0.0 0.0
Max.Mom.@ Mid-Span k-in : 247.0 28.5 275.2
X-Dist ft : 12.12 6.14 12.12
Shears: Left k : 3.39 0.40 3.79
Right k : -3.39 -0.40 -3.80
Reaction @ Left DL k : 0.97 0.00 0.97
LL k : 2.42 0.40 2.82
Total k : 3.39 0.40 3.79
Reaction @ Right DL k : 0.97 0.00 0.97
LL k : 2.42 0.40 2.83
Total k : 3.39 0.40 3.80
Max.Defl.@ Mid Span in : -1.293 -0.163 -1.457
X-Dist ft : 12.12 12.12 12.12
DESIGN DATA
Le:Unsupported Length ft : 0.00 0.00 0.00
Fb:Basic Allowable psi : 2400.0 2400.0 2400.0
Fv:Basic Allowable psi : 180.0 180.0 180.0
Elastic Modulus ksi : 1800 1800 1800
Load Duration Factor 1.15 1.15 1.15
APPLIED LOADS
Use Live Load on This Span ? Yes Yes Yes
Uniform DL plf : 80.0 0.0 80.0
LL plf : 200.0 0.0 200.0
Point DL # :
LL # : 400.00 400.00
X-Dist. ft : 6.00 6.00
Point DL # :
LL # : 400.00 400.00
X-Dist. ft. : 18.50 18.50
QUERY VALUES
Location ft : 0.00 0.00 0.00
Shear # : 3.39 0.40 3.79
Moment k-in : 0.00 0.00 0.00
Deflection in : 0.000 0.000 0.000
6
V4.4B2(c) 1983-95 ENERCALC Bruce W.Kenny,KW060914SL-A
2010 ASCE 7 Standard
Location 45°24'32.5"N Ss and SI=Mapped Spectral Acceleration Values
122°45'0.46" W 7301 SW Kahle Ln,Tigard,OR 97224
Ground Motion Ss 0.938 Si 0337
Occupancy Category H Site Coefficients Fa 1.12
Site Class D F� 1.73
Importance Factor 1.00
Height of Structure 20.0 ft SMS Fa* Ss 1.055
SMI F,. * Si 0.582
Design Category(SDC) D
SOS (2/3)SMS 0.703
Sol (2/3)SMI 0.388
Air Side HVAC
ap 2.50 Rp 6.00
FP MIN= 0.3 SDS WP
F'p= 0.4 aPRSo, •IPC1+2•h�•W = 0.211 wP->* 0.7 0.148
n
Rp
FP MAX= 1.6 SDS IP WP
z= 20.0 ft ASD = 1.13 Wp->* 0.7 0.788
Fp= 0.35 Wp->*0.7 0.246
z= 24.0 ft Eq= 0.279W+0.2 SDS W
Fp= 0.40 Wp->*0.7 0.279 W :W eight of Unit
se Af I}}fH � 16117; 7.'rs .":
Wind Speed : 120 mph Exposure: B
Height of Structure 20'-0" assume Af<0.1 Bf::Force increase factor x=1.9
qz: 23.24 psf kz: 0.70
Unit Weight 750 lbs Cost: 0.85 Ka: 0.90
Unit Height 36" Cf: 1.30 Kn: 1.00
Unit Length 84" x: 1.9
Unit Width 48"
Curb Height 14" WP: 48.8 psf
P: 615 lbs -ASD
T= 615 lbs * (14"+36"/2)/48"
- 0.6* 750 lbs/2
= 185 lbs Net Uplift
NORDLING Proj. No.: 14-306
IN STRUCTURAL ROOF ME CH UNITS
ENGINEERS, LLC PAC TRUST
6775 SW loth.Suite 200 Reuverton OR.97008 Date=AUG 2014 By: TEN Sheet No. L1
49
D� VEQ
100 lbs
W:
150 lbs
Height 36" Weight 750 lbs
Length 84"
Width 48"
Curb 14"
VEQ= 0.279* 7501bs+0.2*0.703*750 lbs
= 209 lbs+106 lbs
VEQ
209 lbs
T= 209 lbs *(14" +36"/2)/48"
+ 1061bs/2
- 0.6* 7501bs/2
G: 33 Ibs = -33 lbs [0 Net Uplift]
V=209 lbs
(4) STEEL BRACKETS W/ *12 SCREWS TO
ROOF CURB 4 "12 SCREWS TO UNIT BASE
RAIL. _ok_
*12 912' o/c SCREWS FROM CURB TO
FRAMING BELOW. _ok_
- -- NORDLING Proj. No.: 14-306
C UNITS
STRUCTURAL
ROOF MECH NTI'S
ENGINEERS, LLC PAC TRUST
6775 SW 111th,Suite 200 Beaverton OR.97008 Date:AUG 2014 By:JEN Sheet No.: L2
Lennox Industries Inc. - Product Submittal
Table of Contents
System ID Qty Model Description
•��_ _�,--- .��_--yeas.�-. _-s -t —^--r_ - �„f ..._. Sra-`<� - - ---
-ac 7:i Wes'==c,--' "”.-=-.a`__ _, d E =}c Pr 4
RTU-4 TON 1 KGA048S4D PKGGE/4 TONI150KBI460-3
Project: 081114KHO1 IN FOCUS Last Changed:C18565ACO
Quote: 4400061218 IN FOCUS Prepared On:2014-08-11
Page 1 of 13 Phone:800-575-2473
Lennox Industries Inc. - Product Submittal
System ID:RTU-3 TON
Package Model:KGA036S4D Description:PKGGE/3 TON/105KB/460-3
HEATING PERFORMANCE
Unit Type Packaged Gas Gas Supply Connection 0.50 (in.)
Electric
WE Highlnput 105000 (Btuh) H/E Heat Rise 64.8 (°F)
WE HighOutput 84000 (Btuh) AFUE/ThermalEff 80
System HeatOutput 84000 (Btuh) Number of Heating Stages
Gas Supply Pressure 7 (in.WC)
COOLING PERFORMANCE
Refrigerant R-410A Number Compressors 1
AR1 EER 10.7 Number of Cooling Stages
ARI SEER 13.0 Condensate Drain Size 1.00 (in.)
ARI Total Power 3400 (W)
AR!GrossTotalCool 37500 (Btuh)
ARI NetTotalCool 36000 (Btuh)
Tube/Fin Refrigerant Charge 8 LBS.5 OZ.
SUPPLY FAN PERFORMANCE
SupplyFan NomPower 0.50 (hp) Air Filter Qty 4
Supply Fan Type CAV Direct Drive Air Filter Length 16.0 (in.)
Air Filter Width 20.0 (in.)
Air Filter Thickness 2.0 (in.)
ELECTRICAL
Voltage 460V 3Ph SupplyFan FLA 1.5 (amp)
Frequency 60 (Hz) CondensingUnit FLA 1.1 (amp)
System MCA 11.0 (amp) CondenserFan Power 250 (W)
System MOCP 15 (amp)
Compressors RLA 5.8 (amp)
Cooling FLA Total 8.4 (amp)
Unit Oper Range-Nom Voltage +1-10%
DIMENSIONS
Cabinet Width 47.0 (in.) Downflow Supply Length 18.0 (in.)
Cabinet Length 83.3 (in.) Downflow Supply Width 20.0 (in.)
Cabinet Height 36.4 (in.) Downflow Return Length 11.0 (in.)
Total Weight 604 (lb) Downflow Return Width 29.0 (in.)
SOUND
Outdoor Sound Rating 75 ((lb)
Project 081114KHO1 IN FOCUS Last Changed:C18565.ACO
Quote: 4400061218 IN FOCUS Prepared On:2014-08-11
Page 2 of 13 Phone:800-575-2473
Lennox Industries Inc. - Product Submittal
System ID:RTU-3 TON
Package Model:KGA036S4D Description:PKGGE/3 TON/105KB/460-3
DIMENSIONS-INCHES(MM)
CORNER WEIGHTS CENTER OF GRAVITY
Model AA BB CC DO EE FF
No.
Base Max. Base Max. Base Max. Base Max. Base Max. Base Max.
lbs. lea lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg bs. kg in. mm in. mm iL mm ii. rrtrn
024 92 42 113 52 112 51 128 58 180 82 207 94 148 67 183 83 38-1/2 978 40 1016 18 457 18 457
030 92 42 114 52 112 51 129 58 180 82 207 94 149 68 183 83 38-1/2 978 40 1016 18 457 18 457
ir- 036 92 42 114 52 012 51 129 59 181 82 208 94 149 68 184 83 38-1/2 978 40 1016 18 457 18 457
048 99 45 123 56 120 55 139 63 193 88 223 102 159 72 197 90 38-1/2 978 40 1016 18 457 18 457
060 104 47 128 58 126 57 145 68 203 92 233 106 167 78 206 94 38-1/2 978 40 1016 18 457 18 457
072 1 2 1 5 5 l 4 3 6 6 1 4 7 6 7 1 6 2 7 4 2 3 7 1 0 8 2 5 1 1 1 9 1 2 3 1 1 0 5 3 8.1/2 978 40 1016 18 457 18 457
090 '188 78 195 88'183 83 212 96 727 103 263 119 203 95 241 109 47 1194 47 1194 21 533' 21 -533
Base Unit•The ont wdh Aendard heat exchanger NO OPr 10NS.
Max.Unit-The urq Mil ILL OPTIONS Best led(Kph InpA Heat&cha ger.Emromeer..k.)
5.5la ,Rt# 18
AA I (2I9) 88
II7(178)
79 R N BOTTOM 8(102)
t r
BOTTOM (70I6) ,,�J�/+Of
47(119Z m111 OPENING
t} GRAVITY \\`� i1
BASE X y Mu072 T I
FF C J
1,;(7).°-
�S8
5.98
co 1..., _..I cc
min BOTTOM • EE
(677) CONDENSATE
OUTLET BOTTOM POWER ENTRY
3X6(76X203)
TOP VIEW(Base)
f' („15 3)� r x 83-, (2115)02A two 072 4 85 4 l4(24431090 I
o 9 1 PI 11111
�o g$
o s e F FLUE/VENT T _ELECTRICAL I J
g GAS 11
\\ �NIPT
o CONrEESATE / 1 1!III
d -rn (BTHER SOS) A3
{� A �� -12 TS
h(25) f I a (,40) 1381 I ll' (25)
1100 L_I L—J 00J • 3/ `).^, r —1 i
I�47(17$) {ti73) )
_ BASE LIFTING HOLES 85-144(2165)024 thru 072 BASE__}
EN D VIEW
(For rigging) 95-tU(2456)Ow BASE
SIDE VIEW
11
19.18 1818 (r' .�.
(4%) X467) 1 I 2 p17
I:II III 1011 I'''hi II I I:1 I (72�
1111 III
11 III II Hill.. ■11111r ..
FORl41FT SLOTS 7-Y2 HORIZONTAL HORIZONTAL (2
IF Boner EEnd)d I>'� SUPPLY OPENING OPENING (140)
lritai Economizer)
BACK VIEW
Project 0811140101 IN FOCUS Last Changed:C18565.ACO
Quote: 4400061218 IN FOCUS Prepared On:2014-08-11
Page 4 of 13 Phone:800-575-2473
E3
Lennox Industries Inc. -Product Submittal
System ID:RTU-4 TON
Package Model:KOA048S4D Description:PKGGE/4 TON/150KB/460-3
HEATING PERFORMANCE
Unit Type Packaged Gas Gas Supply Connection 0.50 (in.)
Electric
HIE LowInput 105000 (Btuh) H/E Heat Rise 69.4 (°F)
WE LowOutput 85500 (Btuh) AFUE/ThermalEff 82
HIE Highlnput 150000 (Btuh) Number of Heating Stages 2
H/E HighOutput 120000 (Btuh) Gas Supply Pressure 7 (in.WC)
System HeatOutput 120000 (Btuh)
COOLING PERFORMANCE
Refrigerant R-410A Number Compressors 1
ARl EER 11.0 Number of Cooling Stages 1
AR1 SEER 13.0 Condensate Drain Size 1.00 (in.)
ARI Total Power 4400 (W)
ARI GrossTotalCool 50000 (Btuh)
ARI NetTotalCool 48000 (Btuh)
Tube/Fin Refrigerant Charge 8 LBS. 10 OZ.
SUPPLY FAN PERFORMANCE
SupplyFan NomPower 0.50 (hp) Air Filter Qty 4
Supply Fan Type CAV Direct Drive Air Filter Length 16.0 (in.)
Air Filter Width 20.0 (in.)
Air Filter Thickness 2.0 (in.)
ELECTRICAL
Voltage 460V 3Ph SupplyFan FLA 1.5 (amp)
Frequency 60 (Hz) CondensingUnit FLA 1.1 (amp)
System MCA 11.0 (amp) CondenserFan Power 250 (W)
System MOCP 15 (amp)
Compressors RLA 6.2 (amp)
Cooling FLA Total 8.8 (amp)
Unit Oper Range-Nom Voltage +/- 10%
DIMENSIONS
Cabinet Width 47.0 (in.) Downflow Supply Length 18.0 (in.)
Cabinet Length 83.3 (in.) Downflow Supply Width 20.0 (in.)
Cabinet Height 36.4 (in.) Downflow Return Length 11.0 (in.)
Total Weight 641 (lb) Downflow Return Width 29.0 ujn�
SOUND
Outdoor Sound Rating 75 (db)
Project: 081114KHO1 IN FOCUS Last Changed:C18565.ACO
Quote: 4400061218 IN FOCUS Prepared On:2014-08-11
Page 8 of 13 Phone:800-575-2473
1
Lennox Industries Inc.-Product Submittal
System ID:RTU-4 TON
,Package Model:KGA048S4D Description:PKGGE/4 TON/150KB/460-3
DIMENSIONS-INCHES(MM)
CORNER WEIGHTS CENTER OF GRAVITY
Model AA BB CC DO EE FF
No.
Base Max. Base Max. Base Max. Base Max. Base Max. Base Max.
lbs. kg lbs. kg lbs. kg Ls. kg lbs. kg lbs. kg lbs. kg lbs. kg In. mm i1. mm in. mm in. mm
024 92 42 113 52 112 51 128 58 180 82 207 94 148 67 183 83 38-1/2 978 40 1016 18 457 18 457
03) 92 42 114 52 112 51 129 58 180 82 207 94 149 68'183 83 38.12 978 40 1016 18 457 18 457
036 92 42 114 52 112 51 129 59 181 82 203 94 149 68 184 83 38-12 978 40 1018 18 457 18 457
048 99 45 123 56 120 55 139 63 193 88223 102 159 72 197 90 38.12 978 40 1016 18 457 18 457
/1' 060 104 47 128 58 126 57 145 66 203 92 233 106 167 76 206 94 38-1/2 978 40 1016 18 457 18 457
/ 072 121 55 143 66 147 67 162 74 237 108261 119 195 89 231 105 33-1/2 978 40 1016 18 457 18 457
t$0 168 76 195 88 183 83 212 96.227-103 263 119 203 95 241 109 47 1194 47 1194 21 533 21 533
Base lint-The ant with standard hose.r dnrg.r NO OPTIONS.
M a x.Unto The lid N t h ALL OPTIONS I rsOled(HO Ingt Heal Exchanger.Em mammas ow)
&t __1B•iM 18
(143) a 11 )413).�tI1457)
�� (279) I 1 BB
7 O BOTTOM 5002)
RETUP RLN y 1` �.
..^
AMINO /�BOTTOM (508) ENER ' „me�
47( 192}( n AIR Y VT �S%�•
/OPEN PG'
BASE
25-311(654)
I M4(96)02
„36.34(964)090~
_ 65,51_9 ` ( } 6f2
(168)j \ (241)
Do T CC
. 2612
III���"""(573)—~CONDENSATE
OUTLET OUTLET BOTTOM POWER ENTRY
3XI(76X203)
+ �.J TOP VIEW(Base)
{
1 (1143) .I 83.1.4(211115)0246 09a 072
0
4 1
o g$ 0 I 1 I 'ill!'
2 ELECTRICAL I II
aS� s o F FLUE/YEN TT INLET
^e $� \ GAS iii°= —" CONDENSATE \\e INLET I ,III 1
r` {EITHER SIDE)
e.— OUTLET
-.1.-1125) I I E 1 1140] (56 I I I' h(n)
100 L] 1-1 001 1 3-112(19) Q.0 r-1 O i Oofl
L4!(1192) 7(673 1 )
BASE LIFTING NOLES
(For'woo ,e 85 V4 1(2 02a Lhn10T2 BASE
END VIEW 93-114(za96)°9°easE
SIDE VIEW
11
1942 163+8 m'
___ (430) (467) 11.11 12—(51)
(I11IIIII
I� imll
11 III II 11 20 (737)
illl; �IIII (sae)
caz• .....11 i∎w asimer .e
7
FORIOJTSLOTS a.a HORIZONTAL HORIZONTAL 5.7n
(Front Blower nd)l (140) OPENINaGR ROPENINNGR III)
(Wtloul Ecv onizer)
BACK VIEW
Project 081114KH01 IN FOCUS Last Changed:C18565.ACO
Quote: 4400061218 IN FOCUS Prepared On:2014-08-11
Page 10 of 13 Phone:800-575-2473
ES
Lennox Industries Inc. - Product Submittal
System ID:RTU-3 TON
Package Model:KGA036S4D Description:PKGGE/3 TON/105KB/460-3
HYBRID ROOF CURBS FOR-024 THRU-072 DOWNFLOW UNITS—DOUBLE DUCT OPENING
- +-1.75
I
rJ/ 2X4NAILER
OR 2 X 3 NAILER
8
° TOP EDGE
•
CAT NO. DIM A
11F50 8.00
171 :• . .FLANGE
11'51 14.00 AS1EN OR
1.75 LOCKING TAB
11132 18.00 NNW
SECTION AA
SCALE 0.250
DETAIL A
11F53 24.04
WALE 0.125
72.75 7/
t75 7Q..,.
3:.176
1
41.50 INF
A
i r
1•
t Milrff
ri
Z.1214 15.13 10.13
-z DETAIL A
Project 081114KH01 IN FOCUS Last Changed:C18565.ACQ
Quote: 4400061218 IN FOCUS Prepared On:2014-08-11
Page 5 of 13 Phone:800-575-2473