GAS PIPE CALCULATIONS JTUvN 22 4 2014
Based on 2010 OMSC Table C402.4(3) C1 i tw�o r ���11
Schedule 40 Metallic Pipe,2.0 PSI Inlet Pressure �ILOI�P`i 'vN
GAS INPUT DELIVERY
EQUIPMENT BTU PRESSURE
EXISTING GP-9 115,000 2 PSI
EXISTING GP-10 115,000 2 PSI
NEW UH-1 45,000 2 PSI
TOTAL LOAD 275,000 2 PSI
LONGEST RUN 175'
GAS PIPE SIZING BASED ON 2 PSI DELIVERY AT 200'
SIZE MAX. CAPACITY
1" 566,000
1/2" 136,000
I.•.
New t./1-1- I
LENNOX GAS UNIT HEATERS/DUCT FURNACES
LF24
ENGINEERING DATA COMPACT GAS-FIRED UNIT HEATER - HORIZONTAL
Steady-State Efficiency - up to 81%
Input - 30,000 to 75,000 Btuh
Bulletin No.210108
IIIIIPIIIIIIIIIIMIIIIIIIIIIIIIIII".1.1------r— 41W‘ 2:1,•-•-,.,
November 2003
Supersedes Apnl 2000
,,.,...,, Mall. ti.'
_-;.,.,. 00110"1
N 44
i k a CESKM ny i 410
iii fib
tIlir° .-.,--. ,_
•
"4-ATIFII°
MODEL NUMBER IDENTIFICATION
LF24 - 045A - P
L Gas Type
Unit Type (blank)=Natural Gas
LF=Unit Heater P=LPG/Propane Gas
Aluminized Steel Heat Exchanger
Nominal Gas Heat Input
Series 30=30,000 Btuh(8.8 kW)
45=45,000 Btuh(13.2 kW)
60=60,000 Btuh(17.6 kW)
75=75.000 Btuh(22.0 kW)
FEATURES
CONTENTS APPROVALS
Dimensions Page 4 Units certified by CSA International for use with natural or LPG/
Features Pages 1-2 propane gas(optional kit required for LPG/Propane conversion).
High Altitude Information Page 2 Units are approved for vertical or horizontal venting.
Installation Clearances Page 3 EQUIPMENT WARRANTY
Maximum Vent Connector Lengths Page 3 Aluminized steel heat exchanger-limited warranty for ten years.
Model Number Identification Page 1 Solid-state ignition module-limited warranty for three years in
Optional Accessories Page 2 residential applications,one year in non-residential applications.
Specifications Page 3 All other covered components have a imited warranty for one year.
Refer to the Lennox Equipment Limited Warranty certificate in-
APPLICATIONS cluded with the equipment for details.
Horizontal unit heaters are low profile, compact in design and CABINET
easy to install. Constructed of pre-painted heavy gauge cold rolled steel.
Steady State Efficiencies of up to 81%. Inside cabinet insulation keeps outer cabinet surface tempera-
Ideal for economical heating systems in garages and non-con- tures low_
fined living spaces. Adjustable louvers are furnished on cabinet for control of air flow
Shipped completely assembled with controls factory installed direction.
and wired. Wiring junction box is conveniently located inside unit cabinet.
Hanging brackets are shipped loose for field installation. Contains all electrical and safety controls.
Each unit is test operated at the factory to ensure proper opera- Hanging brackets for suspending unit are furnished for field
tion and dependability. installation.
Installer has only to locate unit,make unit gas supply,electrical Unit may be turned over to change gas,electrical and flue posi-
connections and mount thermostat to complete the installation. tions. See dimension drawing.
Visit us at www.lennox.com
For the latest technical information,www.davenet.com
NOTE-Due to Lennox'ongoing committment to quality,Specifications,Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation,adjustment,alteration,service or maintenance can cause property damage or personal injury.
®2003 Lennox Industries Inc.
Installation and service must be performed by a qualified installer and servicing agency.
FEATURES
HEATING SYSTEM
24 volt redundant combination gas control valve combines a Inshot Burners
manual main shutoff valve, pressure regulation and automatic Aluminized steel inshot burners provide efficient trouble free op-
electric valve(dual)into one compact combination control. eration.
Solid-state electronic direct spark ignition control provides posi- Burner venturi mixes air and gas in correct proportion for proper
tive main burner ignition. combustion.
• Spark is intermittent and occurs only when required. Burner assembly is removeable from the unit as a single component
Separate electronic flame sensor control assures safe and reli- for ease of service and each burner may be removed individually.
able operation. Limit Control
Should loss of flame occur,flame sensor controls will initiate 3 Limit control has fixed temperature setting and protects heating
attempts at re-ignition before locking out unit operation. system from abnormal operating conditions.
Combustion air inducer prepurges heat exchanger and safely Combustion Air Inducer
vents flue products. Prepurges heat exchanger and safely vents combustion products.
Pressure switch proves inducer operation before allowing gas Blower motor has sleeve bearings and is thermally protected.
valve to open. Pressure switch prevents unit operation in case of blockage of
Combustion air inducer operates only during heating cycle. combustion air inlet or flue outlet.
Tubular Aluminized Steel Heat Exchanger CONTROLS
Tubular heat exchanger is constructed of aluminized steel for su- The following controls are furnished as standard equipment:24 volt
perior resistance to corrosion and oxidation. main gas valve with 100%safety shutoff,direct spark ignition,main
Curving design of heat exchanger allows complete exposure of shutoff valve, gas pressure regulation (natural gas models),
heating surfaces to supply air stream. 115/24v transformer, low voltage terminal strip, solid-state control
Round tube surfaces create minimum air resistance and allow board with LED diagnostics,fan timer control-fan on(45 seconds-
air to surround all surfaces for excellent heat transfer. fixed)fan off(150 seconds fixed).
Compact design reduces space requirements in unit cabinet. DIRECT DRIVE FAN
Heat exchanger has been laboratory life cycle tested.
All models are equipped with efficient and quiet operating direct
drive propeller type fan with permanently lubricated fan motor.
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
LPG/PROPANE CONVERSION KIT THERMOSTAT
Conversion kit is required for field changeover from natural gas. See Thermostat bulletins in Controls section and Lennox Price
See Specifications tables. Book for a complete list of thermostats.
HIGH ALTITUDE INFORMATION
All units may be fired at full input up to 2000 ft.(610 m)above sea level.LF24-30 and LF24-60 units may be fired at full input up to 7500
ft.(2285 m). LF24-45 units may be fired at full input up to 6500 ft. (1980 m),at altitudes above 6501 ft. (1980 m)units are adjusted by
derating manifold pressure,see below.LF24-75 units installed above 2500 ft.(760 m)are adjusted by derating manifold pressure.See
table below for correct pressure. If any unit is installed at an altitude greater than 7500 ft. (2285 m)unit must be derated 4%for each
additional 1000 ft.(305 m)above 7500 ft.(2285 m).Thus,at an altitude of 8500 feet(2895 m),an LF24-75 would require an additional
derate of 4%.
NOTE-This is the only permissible derate for the units.
Manifold Pressure-in.w.c.(Pa)
Model 2500-3500 ft. 35014500 ft. 4501-5500 ft. 5501-6500 R 6501-7500 ft.
No. (760-1065 m) (1065-1370) (1370-1675 m) (1675-1980 m) (1980-2285 m)
Natural Gas LPG/Propane Natural Gas LPG/Propane Natural Gas LPG/Propane Natural(as LPG/Propane Natural Gas LPG/Propane
LF24-30 No No No No No No No No No No
LF24-60 adjustment adjustment adjustment adjustment adjustment adjustment adjustment adjustment adjustment adjustment
LF24-45 No No No No No No No No 3.4(845) 92(2287)
adjustment adjustment adjustment adjustment adjustment adjustment adjustment adjustment
LF24-75 3.5(845) 9.5(2362) 3.4(845) 9.2(2287) 3.3(820) 8.9(2212) 3.2(795) 8.6(2138) 3.1 (770) 8.3(2063)
LF24/Page 2
VN 1
SPECIFICATIONS Je
Gas Model No. LF24-30A LF24-45A LF24-60A LF24-75A
Heating
Performance Heating Capacity Input-Btuh(kW) 30,000(8.8) 45,000(13.2) 60,000(17.6) 75,000(22.0)
Heating Capacity Output-Btuh(kW) 24,300(7.1) 36,500(10.7) 48,000(14.1) 60,000(17.6)
Steady State Efficiency 81.0% 81.0% 80.0% 80.0%
Temperature rise I°F(°C) 42(23) 45(25) 55(31) 60(33)
• Connections Flue size(round)-Vertica venting 1 3(76) 1 3(76) 24(102) 2 4(102)
in.
Horizontal venting-residential 3 4(102) 3 4(1 02) 4 5(127) 4 5(127)
Gas Piping Size 1/2(13) 1/2(13) 1/2(13) 1/2(13)
Fan Data Number of fans 1 1 1 1
Fan Diameter-in.(mm) 10(254) 10(254) 14(356) 14(356)
Number of blades 4 4 3 3
Motor Output-hp(W) 1/20(37) 1/20(37) 1/10(75) 1/10(75)
Amps 1.7 1.7 4.1 4.1
rpm 1650 1650 1050 1050
Air Volume-cfm(Us) 535(250) 750(355) 830(390) 950(450)
r
Air throw at 8 ft.(2.4 m)mounting height-ft.(m) 25(7.6) 25(7.6) 40(12.2) 40(12.2)
Electrical Characteristics 115 volts-60 hertz-1 phase
IShipping Weight-lbs.(kg)1 package 60(27) I 63(29) I 87(40)
91 (41)
OPTIONAL ACCESSORIES- MUST BE ORDERED EXTRA
LPG/Propane Kit I 20L05 I 20L05 I 20L05
1111 I 20L05
1 2-1/8 x 3 in.(54 mm x 76 mm)diameter adaptor is furnished with unit for flue connection
22 x 4 in.(51 mm x 102 mm)diameter adaptor is furnished with unit for flue connection.
3 3 x 4 in.(76 x 102 mm)vent adaptor required(not furnished)for horizontal venting in residential applications.
44 x 5 in.(102 x 127 mm)vent adaptor required(not furnished)for horizontal venting in residential applications.
INSTALLATION CLEARANCES- IN.(MM) MAXIMUM VENT CONNECTOR LENGTHS
Maximum Length of Straight Vent Pipe
Top 1 (25) No.of Elbows fL m
Side opposite access panel 1 (25) 1 25 7.6
2 20 6.1
Access Panel Side 18(457) 3 15 4.6
Back 18(457) 4 10 3.0
5 5 1.5
Bottom 0(0) NOTES- For residential installations only,maximum permissible horizontal vent
length is five feet(1.5 m)plus one elbow.
Flue 6(152) Minimum horizontal vent length is 3 ft.(1 m).
Horizontal venting must terminate in a tee or 90°elbow
NOTE-Provide adequate clearance for servicing. Single wall vent pipe must be used for horizontal verging.
See Installation Instructions for further installation considerations. Maximum total length of vent pipe must not exceed 30 ft.(9 m).
One elbow is equivalent to 5 ft.(1.5 m)of vent pipe.
Single or double wall(type 6)vent pipe may be used for vertical venting.
•
Minimum clearance to combustible material is 6 in.(152 mm)with
single wall vent pipe.
LF24/Page 3
DIMENSIONS - INCHES(MM)
12-1/2 12-1/2
Ai lib.141
(318) (318)
6-1/2 6-112
'11/_ (165)-I". (165)
2_3/4 HANGING MOUNTING SLOTS(Typical)
. .1.1' (70) "41- BRACKETS(2) ..0,2-3/4 5/16 x 3 Inches(8 x 76 mm)
(70) ll
t \h° .
--J ` 1/2
7 — --I° (13)
� ` ■
i
AIR
---—-FLOW — —\
° f __ \ `
I 18-1/2 NOTE- Unit may be rotated 1800 top for bottom
' (470) to change gas,electrical and flue positions.
— �/ i J Hanging brackets may be installed on
/ , either top or bottom of unit.
( HEAT
EXCHANGER c ,'
..�° I
L -,
~ l
I V
�Ill IM_ 1 1
(25)
TOP VIEW
r 25 • B 1470)
(635) ELECTRICAL (470)
INLETS 1 HANGING
(25)i♦ BRACKETS(2) all
■
, .
Fill
bIll
o
• o AIR °o 0 o° FLOW T y iii _
0
C I I °o
• FLUE ADJUSTABLE
DIRECT OUTLET 6 GAS INLET SERVICE
ACCESS LOUVERS
DRIVE FAN (152) PANEL SIDE VIEW
BACK VIEW
I
Model No. LF24-30A LF24-60A
LF24-45A LF24-75A
A 12(305) 17(432)
B 5-1/2(140) 6-1/2(165)
C 4-1/4(108) 6-3/4(171)
LF24/Page 4