Loading...
Report -1 t`I r S.on 2i a .tSZ01 Lt- 0©Oag - Global Project Values: 1% SILENT Project Name: The Adrienne Standby Hours: 24 KNIGIIT Project ID: Alarm Mins:I 5 Prepared By: Jason Sweet Derating Factor: 1.2 5808 Calculations Date: 1/2/2014 Voltage Drop Warning Threshold%: 10 Panel ID: 5808 Model: 5808 Add.Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: IT Closet Volts: 24 VDC Max Panel Current: 6.0 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts Q ° Ckt.# Circuit Name Qty Standby Alarm &Type 1000 Ft. One-Way Ohms EOL Drop 5808 5808 CTRL Panel 1 0.206 0.356 SLC-DEV Addrsbl SLC Devices 12 0.007 0.007 5860 LCD Remote Annunc 1 0.020 0.025 5824 Serial/Parallel Module 0.000 0.000 5496 Power Expander 0.000 0.000 5865-4 LED Annunciator(4G) 0.000 0.000 5865-3 LED Annunciator(3G) 0.000 0.000 5880 LED Driver Module 0.000 0.000 Other 0.000 0.000 Other 0.000 0.000 SD-Duct Duct Hsg w/Relay 0.000 0.000 5883 Relay Module 0.000 0.000 PGM-I/O#1 Notification Appl Circuit 0.000 1.064 #14 Solid 2.52 190 0.96 19.38 4.99% PGM-I/O#2 Notification Appl Circuit 0.000 0.294 #14 Solid 2.52 225 1.13 20.07 1.63% PGM-I/0#3 Notification Appl Circuit 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% PGM-I/O#4 Notification Appl Circuit 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% Aux Power *1 #of NAC's Used 0.000 0.000 Total Standby Current(Amps) 0.233 1.746 _Total Alarm Current(Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes/60 (5 Mins) Total Standby AH Required 5.582 0.145 Total Alarm AH Required Total Combined AH Required 5.73 Command Shortcuts Multiply By The Derating Factor 1.20 1 l Minimum Battery AmpHours Required 6.87 Configure Circuits I Print Page J #1. Note: A value msut be entered if ou have selected an NAC circuits as AUX Power. JJJ RECEWED 30 0 7 2014 CITY°F TII�S Cry BUILD�C D �:xic:u"� Circuit Configuration - Project Information Project Name: 0 Project ID: 0 Prepared By: 0 Date: 1/0/1900 Ckt. Number: PGM-I/O#1 Panel ID: 5808 Ckt. Name: Notification Appl Circuit I/O Use: Notification Appi Circuit Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 6 System Sensor SR 15 0.000 0.066 0.000 0.396 4 System Sensor P2R 15 0.000 0.079 0.000 0.316 2 System Sensor P2R 75 0.000 0.176 0.000 0.352 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 1.064 Ckt. Number: PGM-I/O#2 Panel ID: 5808 Ckt. Name: Notification Appl Circuit I/O Use: Notification Appi Circuit V Qty Device Current Draw Each Current Draw Total Standby Alarm _ Standby _ Alarm 2 System Sensor P2R 15 0.000 0.079 0.000 0.158 8 System Sensor 0.000 0.017 0.000 0.136 Unused 0.000 a 0.000 0.000 0.000 Unused 0.000 _. 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.294 Ckt. Number: PGM-I/O#3 Panel ID: 5808 Ckt. Name: Notification Appl Circuit I/O Use: Notification Appl Circuit v Qty Device Current Draw Each Current Draw Total _ Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 _ 0.000 0.000 0.000 Totals 0.000 0.000 INTELLIKNIGHT MODEL 5808 FIRE ALARM CONTROL PANEL IntelliKnight® Model 5808 ill ;,. Single Loop Addressable K r • Fire Alarm Control System A. The convenience of an addressable fire alarm control panel in a cost effective ,i 1 easy to use package. 0 IntelliKnight Model 5808 is a 127 point class leading single loop addressable fire alarm control/communicator system that provides you with the revolutionary value and performance of addressable sensing technology combined with exclusive, built-in digital communication, distributed intelligent power, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-446-6444, or in Minnesota, call 763-493-6435. Description • Built-in RS-232 interface for The IntelliKnight 5808 performs drift programming via PC. compensation and calibration checks • Built-in Form C trouble relay rated at on each of the sensors in the system. 2.5 amps at 24 VDC. The basic IntelliKnight 5808 system • Two built-in Form C programmable can be enhanced by adding modules relays rated at 2.5 amps at 24 VDC. such as the Model 5860 Remote Approvals: Annunciator, the Model 5824 UL Listed/ NFPA 72 – ''' Serial/Parallel Interface(for printing -Central Station system reports), and an Intelligent -DACT Power Module. The Model 5808 also -Local Protective features a powerful built-in dual line fire Signalling System communicator that allows for reporting -Water Deluge of all system activity to a remote • Releasing Service monitoring location. _ it Features Specifications • Up to 127 addressable points. Primary AC. 120 VRMS at 50/60 hz, • Uses standard wire—no shielded or 2.75A twisted pair required. Total Accessory Load: 6A at 24 VDC Lam • Built-in digital communicator. 6 amps at 24 VDC of power-limited notification power fl • Central station reporting by Point or p by Zone. Standby Current: 206 mA • Supports Class B (Style 4)and Class Alarm Current: 356 mA Model 5808 A(Style 6)configuration for SLC. Notification circuits: 3 amps of Telephone Requirements: • Distributed, intelligent power. power-limited power per circuit at 24 FCC Part 15 and Part 68 approved • Drift compensation. VDC. • 13 pre-programmed output Auxiliary power circuits: 3 amps of Type of Jack: RJ31X (two required) cadences, (including ANSI-3.41), and power-limited power per circuit at 24 4 programmable outputs. VDC. • Notification circuits can be configured Mechanical Specifications: as 2 Class A(Style Z)or 4 Class B (Style Y), or auxiliary power for Flush Mount resettable, constant, or door holder Dimensions: power. 14.5"W x 24.75"H x 3.5"D • Built-in annunciator with 80-character (36.8W x 62.9H x 8.73D cm) LCD display. Overall • RS-485 bus provides communication Dimensions: to system accessories. 16"W x 26.4"H x 4.65"D SILENT • Up or Down load programming, (40.6 x 67 x 11.8 cm) KNIGHT event history, or detector status via Weight: 28 lbs. (12.8 kg) remote or direct connection. Color: Red INTELLIKNIGHT FIRE ALARM CONTROL PANEL • SLC Sensor Devices Intelligent SLC Modules 5496 Intelligent Power Module Model SD505-APS Model SD500-AIM The Model 5496 is a 6 amp.notification power Addressable photoelectric smoke detector. Dry Contact Input Module. Designed to used expander that provides Model SD505-AIS with normally open dry contacts. Mounts in a four additional power- I 4 inch square electrical box. It features an limited notification Addressable ionization smoke detector. indicator LED to show alarm status and a Model SD505-AHS coverplate. appliance circuit outputs. Addressable heat sensor. Model SD500-MIM 5865-3 and 5865-4 Model SD505-6AB Mini Dry Contact Input Module.A miniature Remote LED Six inch base designed for use with detector version of the addressable input module Annunciator head models SD505-APS, SD505-AIS and which is designed to be used with pull Features 30 Programmable LEDs(15 red SD505-AHS. stations and other normally open dry contact and 15 yellow)outputs and piezo sounder. Model SD505-ADH inputs where a smaller size is desired. The 5865-4 adds a silence and reset switch Duct Housing. Detects smoke in HVAC Model SD500-ARM to the package. ducts. Use with SD505-APS or SD505-AIS. Addressable Relay Module. Features 2 5883 Relay Board SD505-ADHR/DTS Form C output relays,designed to mount on Features 10 General purpose Form C a 4 inch square electrical box. Provides relays. Used with 5880 module. Addressable Duct smoke detector with built- indicator LED to show output status and 5824 Serial/Parallel Gateway in relay module detects products of comes with a coverplate. combustion present in air moving through an Module HVAC system. Provides form C alarm Model SD500-LED Has one parallel and one RS-232 serial port contact.The SD505-ADHR is compatible An LED driver capable of driving 80 LEDs for connecting any standard IBM-compatible with the SD505-DTS,which provides remote through the SLC loop. Up to 40 SD500- printer to the IntelliKnight system. Interfaces annunciation and testing capabilities for the LEDs can be used per system. with building control system. SD505-ADHR. Use with SD505-APS or S_-BUS Accessories SKSS Silent Knight Software SD505-AIS. The following items listed are devices that Suite Model SD500-PS connected to the IntelliKnight's RS-485 Bus Addressable Pull Station with visible LED. 5860 Remote Fire Annunciator 5660 Up Down Load Software The 5860 features the same 80 character User-friendly,WindowsTM software for backlit LCD display keypad and firefighter's remote programming of the IntelliKnight keyswitch as the 5820.The system can be panel using a PC. fully programmed and operated from any 5670 Facility Management remote annunciator. 5880 LED/I0 Module Software Powerful end-user software allows viewing Features 40 LED outputs, 8 normally open of detector status and event history via dry contact inputs and one piezo output. modem or direct connection. ion *• 113500-LED III. rik" Al 414 4 _an NI MO II an !MM--._ , I I I __ .L -'-a S.l� — o. 50500)NM 40505A1,S SD50SAII MM l M•.-II•W • • . —+• w- n•nw I I • I soeewn r i I ow i4*_ I us.n•Seep m 0 as w 0. _...._._..� _ I SW RN•y Welt Mosul.I r A fOMb�01w OM# NNI l w*NS .ONMRM , 3. . [ 4 Imi+ wwq•.y. ru bra 4rt•r .Nrw,• r•vww qtt' SILENT KNIGHT 0 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763-493-6435 FORM#350386, Rev. 9/01 FAX: 763-493-6475 World Wide Web: http://www.silentknight.com Copyright©2001 Silent Knight SYSTEM SENSOR'� 4 to Selectable Output • ' • Notification Devices SpectrAlert'Advance selectable-output horns,strobes, and horn/strobes are rich with features guaranteed to cut installation times and maximize profits. Sr CCIEIert A D V A N C E The SpectrAlert Advance series of notification appliances is Features designed to simplify your installations,with features such as:plug in Plug-in design designs,instant feedback messages to ensure correct installation of individual devices,and eleven field-selectable candela settings for •Same mounting plate for wall-and ceiling-mount units wall and ceiling strobes and horn/strobes. •Shorting spring on mounting plate for continuity check before installation More specifically,when installing Advance products,first attach a universal mounting plate to a four-inch square,four-inch octagon or •Captive mounting screw double-gang junction box.The two-wire mounting plate attaches to •Tamper resistance capability a single gang junction box. •Field selectable candela settings on wall and ceiling units:15,15/75, Then,connect the notification appliance circuit wiring to the SEMS 30,75,95,110,115,135,150,177,185 terminals on the mounting plate. •Automatic selection of 12 or 24 volt operation at 15 and 15/75 candela Finally,attach the horn,strobe or horn/strobe to the mounting plate Outdoor wall and ceiling products by inserting the product's tabs in the mounting plate's grooves.The device will rotate into position,locking the product's pins into the •Outdoor products rated from 40°to 151°F mounting plate's terminals.The device will temporarily hold in place -Minimal intrusion into the back box with a catch until it is secured with a captured mounting screw. SpectrAlert Advance products allow you to choose: •Horn rated at 88+dbA at 16 volts •12 or 24 volts •Rotary switch for tone selection •At 24 volts,15,15/75,30,75,95,110,115,135,150,177 or 185 .3 horn volume settings candela by way of rear-mounted slide switch and front viewing window •Electrically compatible with existing SpectrAlert products •Horn tones and volume by way of rotary switch The SpectrAlert Advance series includes outdoor notification Agency Listings appliances.Outdoor strobes and horn/strobes(two wire and four wire)are available for wall or ceiling.Outdoor horns are available for SIGNALING T 7125.1653:186(Indoor strobes) wall only.All System Sensor outdoor products are rated between A , 7175-1653:187(outdoor strobes) I.O 7125-1653:188(ho,,VsUobes) minus 40 degrees Fahrenheit and 151 degrees Fahrenheit in wet or USTEG APPROVED approv/d I'..-,?.' 7125-1653189 Morro) dry applications. h. MEM52-05-E SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance horns,strobes and horn/strobes shall mount to a standard 4 x 4 x 11-inch back box,4-inch octagon back box or double-gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 1k-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance products,when used with the Sync•Circuit- Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC,or full-wave rectified,unfiltered power supply.Strobes and horn/strobes shall have field-selectable candela settings including 15,15/75,30,75,95,110,115, 135,150,177,185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn/Strobe Combination The horn/strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn/strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three-pattern and a non-temporal(continuous) pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn/strobe models shall operate on a coded or non-coded power supply. Outdoor Products SpectrAlert Advance outdoor horns,strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 151 degrees Fahrenheit.The products shall be listed for use with a System Sensor outdoor/weatherproof back box with half inch and three-fourths inch conduit entries. Synchronization Module The module shall be a System Sensor Sync•Circuit listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn/strobe models over a single pair of wires.The module shall mount to a 49(6 x 4916 x 2k-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) K Series Operating Temperature -40°F to 151°F(-40°C to 66°C) Humidity Range 10 to 93%non-condensing(indoor products) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12DC/FWR or regulated 24DC/FWR1 Operating Voltage Range' 8 to 17.5 V(12V nominal)or 16 to 33 V(24 nominal) Input terminal wire gauge 12 to 18 AWG Ceiling mount dimensions(including lens) 6.8-diameter x 2.5-high(173 mm diameter x 64 mm high) Wall mount dimensions(including lens) 5.61 x 4.71N x 2.5D(142 mm L x 119 mm W x 64 mm D) Horn dimensions 5.61 x 4.7'W x 13'D(142 mm L x 119 mm Wx33 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time varying power source that is used on some power supply and panel outputs. 2.P S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. A05-0195-002 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela Range 15/75 142 148 77 81 Temporal Medium 44 49 58 69 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 _ 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela Range 150 NA NA 246 220 Coded Low 40 46 52 50 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-wire Horn/Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-temporal High 141 152 91 100 116 176 201 221 229 Non-temporal Medium 133 145 75 85 102 163 187 207 216 Non-temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-temporal High 142 161 103 112 126 181 203 221 229 Non-temporal Medium 134 155 85 95 110 166 189 208 216 Non-temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-wire Horn/Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-temporal High 255 270 303 309 Non-temporal High 233 248 275 281 Non-temporal Medium 242 259 293 299 Non-temporal Medium 219 232 262 267 Non-temporal Low 238 254 291 295 Non-temporal Low 214 229 256 262 Horn Tones and Sound Output Data Rotary Horn and Horn/Strobe Switch Settings Horn and Horn/Strobe Output(dBA) Setting Repetition Rate dB Level Switch 8-17.5 Volts 16-33 Volts 1 Temporal horn High Position Sound Pattern dB DC FWR DC FWR 2 Temporal horn Medium 1 Temporal High 78 78 84 84 3 Temporal horn Low 2 Temporal Medium 74 74 80 80 4 Normal horn High 3 Temporal Low 71 73 76 76 5 Normal horn Medium 4 Non-temporal High 82 82 88 88 6 Normal horn Low 5 Non-temporal Medium 78 78 85 85 7` Externally coded High 6 Non-temporal Low 75 75 81 81 8• Externally coded Medium 7" Coded High 82 82 88 88 9• Externally coded Low 8" Coded Medium 78 78 85 85 9` Coded Low 75 75 81 81 'Settings 7,8,and 9 are not available on 2-wire horn/strobe. n05-0395-002 • • SpectrAlert Advance Dimensions 14------4.7" lo�_ Dia. '. 'I II Dia. ® � ; - r 2.5" `: iftillio•-4141"*. 5.6" _ I I. :.\ri 0 .= —'• 4_2.5"--. SpectrAlert Advance Ordering Information Model Description Model Description Wall Horn/Strobes Ceiling Horn/Strobes(cont'd.) P2R*' 2-wire Hom/Strobe,Standard cdt,Red PC2W*' 2-wire Horn/Strobe,Standard cd,White P2RH* 2-wire Horn/Strobe,High cd,Red PC2WH*' 2-wire Horn/Strobe,High cd,White P2RK* 2-wire Horn/Strobe,Standard cd,Red,Outdoor PC4R 4-wire Horn/Strobe,Standard cd,Red P2RHK* 2-wire Horn/Strobe,High cd,Red,Outdoor PC4RH 4-wire Horn/Strobe,High cd,Red P2W* 2-wire Horn/Strobe,Standard cd,White PC4RK 4-wire Horn/Strobe,Standard cd,Red,Outdoor P2WH* 2-wire Horn/Strobe,High cd,White PC4RHK 4-wire Horn/Strobe,High cd,Red,Outdoor P4R* 4-wire Horn/Strobe,Standard cd,Red PC4W 4-wire Horn/Strobe,Standard cd,White P4RH* 4-wire Horn/Strobe,High cd,Red PC4WH 4-wire Horn/Strobe,High cd,White P4RK 4-wire Horn/Strobe,Standard cd,Red,Outdoor Ceiling Strobes P4RHK 4-wire Horn/Strobe,High cd,Red,Outdoor SCR* Strobe,Standard cd,Red P4W* 4-wire Horn/Strobe,Standard cd,White SCRH* Strobe,High cd,Red P4WH* 4-wire Horn/Strobe,High cd,White SCRK Strobe,Standard cd,Red,Outdoor Wall Strobes SCRHK Strobe,High cd,Red,Outdoor SR' Strobe,Standard cd,Red SCW"' Strobe,Standard cd,White SRH*' Strobe,High cd,Red SCWH*' Strobe,High cd,White SRK Strobe,Standard cd,Red,Outdoor Horns SRHK Strobe,High cd,Red,Outdoor HR Horn,Red SW* Strobe,Standard cd,White HRK Horn,Red,Outdoor SWH* Strobe,High cd,White HW Horn,White Ceiling Horn/Strobes Accessories PC2R* 2-wire Horn/Strobe,Standard cd,Red BBS-2 Back Box Skirt,Wall,Red PC2RH* 2-wire Horn/Strobe,High cd,Red BBSW-2 Back Box Skirt,Wall,White PARK 2-wire Horn/Strobe,Standard cd,Red,Outdoor BBSC-2 Back Box Skirt,Ceiling,Red PC2RHK 2-wire Horn/Strobe,High cd,Red,Outdoor BBSCW-2 Back Box Skirt,Ceiling,White Notes: •Add"-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2R-P t Add"-SP"to model number for"FUEGO'marking on cover,e.g.,P2R-SP t"High cd,"refers to strobes that include 135,150,177,and 185 candela settings.'Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings. Th SYSTEM 02006 System Senses _ SENSOR 3825 Ohio Avenue•St.Charles,IL 60174 aoa,a p *y�loo any notice v:rt:,,:tm:etsheet , Phone:800-SENSOR2•Fax:630-377-6495 current°od"information,395-0"9"06.11 "90 0`""dd° ` A05-0395-002.7/06•f1659 *Th, SYSTEM SENSOR® Mini-Horns The SpectrAlert•Advance series of mini-horn sounders are designed to simplify installations to provide "" (j primary and secondary signaling for fire and security _, 4 applications. SPECTWert A d V A N C E Features The MHR and MHW mini-horns operate at 12 and 24 volts and are •12 and 24V operation ideal for hotel,motel or residential fire system applications,where a smaller notification device is desired.The mini-horns offer high •High and low volume settings and low volume settings,and temporal or non-temporal tones. The •Temporal and non-temporal tones horns can be mounted to single gang back boxes for aesthetically •Mounts to single gang back box sensitive applications. Synchronization is also provided when using the MDL module. •Compatible with MDL sync module •Mechanically and electrically compatible with PA400 series The MHR and MHW mini-horns can operate between 32 and 120 Mini-Alert-sounders degrees Fahrenheit from a regulated DC or full-wave rectified, unfiltered power supply.They are listed to Underwriter's Laboratories Standard UL 464 for fire protective signaling systems. Agency Listings �FrT� ■ØMEAQ 4 LISTED APPROVED approved (mil MEA7-07{ 7135-1653196 SpectrAlert°Advance Mini-Horn Specifications Architectural/Engineering Specifications Mini-horns shall be a System Sensor Model MHR or MHW capable of operating at nominal 12 or 24VDC and shall mount to a deep single gang back box.Mini- • horn shall be listed to Underwriter's Laboratories Standard UL464 for fire protective signaling systems.Mini-horns shall operate between 32 and 120 degrees Fahrenheit from a regulated DC,or full-wave rectified,unfiltered power supply.When used with the Sync•Circuit-Module,12-volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Physical Specifications Dimensions 4.61 x 2.9W x.45-D Weight 2.67 oz Operating Temperature Range 32°F to 120°F(0°C to 49°C) Mounting Surface:deep single-gang back box(2W deep) Flush:Standard 4-x 4-back box Electrical Specifications Input Terminals 12 to 18 AWG Nominal Voltage Regulated 12DC/FWR or regulated 24DGFWR Operating Voltage 8-33 Operating Voltage with MDL 9-33 UL Sound Output and Current Draw Data Sounder Output(dBA) Switch Setting Pattern Output Level 8-17.5 VDC 8-17.5 VFWR Nominal 12 VDC Nominal 12 VFWR 16-33 VDC 16-33 VFWR 1 Temporal High 68 67 71 70 78 76 2 Temporal Low 66 65 69 68 76 75 3 Non-temporal High 72 71 75 74 80 79 4 Non-temporal Low 70 69 73 72 78 77 Sounder Current Draw(mA MIS) 8-17.5 Volts 16-33 Volts Switch Position Sound Pattern Volume DC FWR DC FWR 1 Temporal High 12 10 17 15 2 Temporal Low 10 9 14 13 3 Non-temporal High 22 17 29 25 4 Non-temporal Low 17 13 21 19 Ordering Information Part No. Description MHR Mini-Horn,Red MHW Mini-Horn,White " SYSTEM 02009 System Sensor �� SENSOR 3825 Ohio Avenue•St.Charles,IL 60174 Radictspedflo0wsssubjecttodump.MwutndknYisitsystensenwrt9m for Phone:800-SEN50R2•Fax:630-377-6495 ""entp1Oduct Hammon.Ydidingthe6isi'FSO10r"isdis sheet A050414-001•12/09.02266 INTELLIKNIGHT ACCESSORY Model SD500-AIM . Addressable Input Module j lit '. R And ' Model SD500-MIM t k. Miniature Input Module ht .. N IntelliKnight's addressable contact monitor modules combine fast response with pin-point location ID. A combination that saves lives and property. The SD500-AIM and SD500-MIM are addressable input modules for use with Silent Knight's IntelliKnight fire control panel. The SD500-AIM and SD500-MIM are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. The SD500-AIM addressable input module mounts to a 4"-square box. The SD500-MIM mini input module fits inside a single gang box. The modules are supervised, single input contact monitors. Using an EOL resister, they monitor for alarm contact closures and for open circuit wiring fault conditions. The SD500-AIM and SD500-MIM offer a compact design for adaptability and pleasing aesthetics as well as easy installation and stable operation—a flexible solution for all your fire protection needs. Model SD500-AIM and SD500-MIM Input Modules The addressable input modules expand the flexibility of the IntelliKnight system by allowing the use of contact type inputs. Typical [1 +� applications include manual pull stations and water flow switches. —* 0�. Features • Operates on Class A (Style 6 & -- — b- Style 7) or Class B (Style 4)SLC Loop. 505U-AIM IDISHIll • Single contact monitor. Operation Specifications • Up to 127 modules per SLC loop. Each addressable input module is Operating Voltage: 24 VDC • SD500-MIM mounts in a single programmed with a unique SLC Standby Current: 0.55 mA loop address. The module gang box. supervises the wiring to the contact Alarm Current: 0.55 mA • SD500-AIM mounts in a with an End Of Line (EOL) resistor. Ambient Temperature: 32°F to 120°F . 4"-square or double gang If a fault occurs in the wiring, the (0°C to 49°C) electrical box, and has an module alerts the FACP. Mounting: SD500-AIM attractive ivory cover plate. double gang box or 4"-square electrical • SD500-AIM/MIM are DIP switch box programmable. • Accepts up to 14 gauge wire. 3D single gang ang box • Both modules UL 864 listed; comply with NFPA 72 SILENT • 2500 ft max. wiring distance from input module to contact. ` KNIGHT • CSFM listed. ft INTELLIKNIGHT ACCESSORY Model SD500-AIM and SD500-MIM Addressable Input and Mini Input Modules °11,4:111 Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable input modules Silent Knight SD500-AIM or SD500-MIM. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight 5820XL fire panel. The SD500-MIM shall fit inside a single gang electrical box. The SD500-AIM shall be supplied with a plastic cover and shall be suitable for mounting to a 4"-square or double gang electrical box. The SD500-AIM addressable input module must provide a monitor LED that is visible from outside the cover plate. Model SD500.AW FRC•T vIE* BACK v1Elr SWIM • • pao. • ' I / 0 • Model S1)500-MIM - e WI" U • glIPAPPLA I a 1 SILENT KNIGHT • 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 612-493-6435 FORM#350231, Rev. 01/00 FAX: 612-493-6475 World Wide Web: http://www.silentknight.com Copyright©2000 Silent Knight INTELLIKNIGHT ACCESSORY Model SD500-ARM A Addressable Relay Module ; ! i I Place relay applications anywhere on the • ,� IntelliKnight loop with the SD500-ARM • Addressable Relay Module. The SD500-ARM is an addressable device that adds great flexibility to the IntelliKnight system. Providing two Form C contacts rated at 2.0 amps © 30 VDC or .6 amp @ 120 VAC. The SD500-ARM allows you to control a wide variety of normally open and normally closed applications, including elevator recall, door closing, fan operation, and auxiliary notification. And, because the relay module is addressable, these applications can be located at any point in the signaling line circuit. Like other IntelliKnight SLC devices, the SD500-ARM is compact for adaptability and pleasing aesthetics. Combine this with the features you've come to expect from Silent Knight fire protection devices—easy installation and stable operation—and it adds up to a flexible solution for all your fire protection needs. Model SD500-ARM Features Addressable Relay Module • Two sets of Form C contacts. • The SD500-ARM provides two Contacts are rated at 2A @ 30 Form C contacts rated at 2A © VDC or .6A @ 120 VAC. C!�' 30 VDC or .6A @ 120 VAC. • Up to 127 relays can be used on l ° These contacts can be used for each SLC loop. • virtually any normally open or Relay programming is normally closed application. completely flexible—can be Model SD500-ARM mapped to zone conditions. • Polling LED visible through Specifications Operation cover plate. • UL listed, complies with NFPA Contact Rating: Form C Each relay module is 72. 2A @ 30 VDC programmed with a unique SLC • CSFM approved .6A @ 120 VAC loop address. When an event • MEA Approved, 429-92-E, Vol. 9 that controls the relay module Standby Current .55 mA occurs, the relay is triggered by Alarm Current: .55 mA the IntelliKnight panel. Ambient 32°F to 120°F Temperature (0°C to 49°C) itpSILENT Mounting 4-square electrical box KNIGHT INTELLIKNIGHT ACCESSORY • Model SD500-ARM Addressable Relay Module • Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable relay modules, Silent Knight SD500-ARM. The modules shall be UL listed compatible with Silent Knight's Intelliknight 5820XL fire panel. The relay module must provide two Form C dry contacts rated at 2.0 amps at 30 VDC or .6 amp at 120 VAC. The relay module must be suitable for mounting in a standard 4-square electrical box and must include a plastic cover plate. The relay module board must provide an LED that is visible from the outside of the cover plate. The relay must be fully programmable for such applications as are required by the installation. FRONT VIEW • 0 C • 0 0 cps, • V j • - • • • 4-718' 1/4' • 1' Model SD500-ARM Addressable Relay Module Dimensions ftli SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 612-493-6435 FORM#350218,Rev. 11/99 FAX 612-493-6475 World Wide Web: http://www.silentknight.com Copyright©1999 Silent Knight INTELLIKNIGHT ACCESSORY SD500-PS and SD500-PSDA Addressable Pull-Station 'try t / 3 IntelliKnight's addressable pull stations combine fast response with pin-point location ID. The SD500-PS and SD500-PSDA are a single action or dual action addressable manual fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SD500-PS/PSDA provides a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. The SD500-PS/PSDA mounts to a single gang box and features a rugged metal construction that lasts and lasts. Combine all this with the features you've come to expect from Silent Knight- easy installation and stable operation - and it adds up to a flexible solution for all your fire protection needs. Model SD500-PS 8 SD500-PSDA • Reflective label makes it easier Addressable Pull Station to locate in low light p i Operation 4 The SD500-PS is a single action r v LL addressable fire pull station, and The SD500-PS/PSDA single action the SD500--PSDA is a dual action pull stations are operated by a pull addressable fire pull station. The on the front pull cover of the SD500-PS/PSDA feature rugged station. A plunger switch, wired to metal construction A terminal strip a self contained addressable on back of the pull station allows module, is released as the pull interconnection of the pull station to station opens to initiate the alarm. the SLC of an IntelliKnight control Once operated, the cover hangs panel. The SD500-PS/PSDA is down and can be seen up to 100 1' 11? designed for indoor use in non- feet away. The pull station is reset explosive environments. The by returning the front cover to the normally open initiating point normal upright position and contacts are gold-plated to avoid relocking the station with a reset t j R risk of corrosion. The SD500- key. The reset keys are the same PS/PSDA has been tested by UL keys used on Silent Knight for compliance to the requirements enclosures. of the Americans with Disabilities The SD500-PS/PSDA includes a ACT (ADA). status LED which blinks, indicating Features that the addressable module is communicating with the loop. The • UL Listed status LED lights continuously SD500-PS • CSFM listed during an alarm. A dip switch on • ADA compliant the addressable module is used to • Key reset (Same key as Silent set the unique address. Knight enclosures) Specifications • Surface mount back box Operating Voltage: 24VDC available Standby Current: .55mA • Terminals - accept up to 14 Alarm Current: 55mA Ambient Temperature: 32°F to 120°F gauge wire (0°C to 49°C) SILENT • Extremely easy to operate Mounting: Single gang KNIGHT • Corrosion-resistant gold-plated box - contacts. Optional Red Surface Mount Box PS-SMBB INTELLIKNIGHT ACCESSORY SD500-PS and SD500-PSDA Addressable Pull-Station Engineering Specifications Manual pull station shall be addressable Module SD500-PS/SD500-PSDA. Equipment shall be made of 14 gauge C.R.S.(Cold Rolled Steel), painted with a red enamel . The label shall contain the words Fire Alarm and be made of a reflective material embossed text 3/8 inches tall. Operating instruction shall be clearly visible on the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, the key shall match the control panel. Manual station shall contain four terminal blocks with two connected to the addressable module and two connect to the SLC loop. Manual station shall provide data to the control panel with an ID address programmed by dip switch settings . Manual stations shall be Underwriters Laboratories Inc. listed and installed within the limits defined in the American Disabilities Act. L --- r.�[v `,Y , `�♦ +� a w ... _gyro ter.ww • - ,10 l 1 �� ��� Wiring • I Mounting to Single Mounting to Optional Gang Electrical Box Surface Mount Box rt 1111111111111111111111111110 - -! SD500-PSDA,,,,t, ,,,,, ., • •• l - "Unlarl Installing SD500-LK �� I Dimensions •«■. :mu- itiiSILENT KNIGHT 4 ,, 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763-493-6435 FORM#350342, Rev. 09/02 FAX: 763-493-6475 World Wide Web: http://www.silentknight.com Copyright©2002 Silent Knight INTELLIKNIGHT ACCESSORY i, Addressable . Photoelectric Type . Ill Smoke Detector ` ., Detect smoldering fires quickly and get help fast ,e, 4, .. ,.......,,, 1 with IntelliKnight® photoelectric smoke detectors. IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505-APS photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds are wasted in determining location of an alarm. The SD505-APS compensates automatically for contamination in the environment. And detector testing is simple—even from a remote site. Like other IntelliKnight detector models, the SD505-APS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505-6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight smoke detectors—easy installation, stable operation, RF/transient protection, and vandal-resistant locking—and it adds up to a flexible solution for all your fire protection needs. Model SD505-APS The light received is converted into Anal /Addressable an electronic signal. Under normal conditions, the status LED blinks , Photoelectric Type approximately every 15 seconds, Smoke Detector indicating that the head is The SD505-APS is particularly communicating with the loop. The LED lights continuously during the suited to detecting dense smoke typical of fires involving materials alarm period. such as soft furnishings, plastic, Features foam or other similar materials • Low profile, 2 inches, including which tend to smolder and produce base SD505-APS Smoke Detector large visible particles. Simple and reliable addressing •The detector features automatic without mechanical switches Specifications compensation for contamination Operating Voltage: 17-41 VDC P Automatic compensation for and a simple detector calibration sensor contamination Current Consumption: test procedure that can be run from Built-in fire test feature Standby: .55 mA the panel or remotely (using the Alarm: .55 mA WindowsTM based downloading • Simple detector calibration g testing through the control panel Ambient Temperature: 32°F to 100°F software). or remotely through a (0°c to 5o°c) . Operation WindowsTM based computer Mounting: 4"Square,4"OCT, software. Single gang mud The SD505-APS units made up of ring an LED light source and a silicon • Vandal-resistance locking Relative Humidity: 85% photo diode receiving element. In a features noncondensing normal standby condition, the • Field cleanable Sensitivity: 0.88%-3.57%FT receiving element receives no light • UL listed, meets NFPA 72 Ch 7 from the pulsing light source. In the Air Velocity: 500-4000 FPM P 9 9 requirements event or fire, smoke enters the • CSFM approved detector and light is reflected from • the smoke particles to the receiving MEA approved SILENT element. o t KNIGHT INTELLIKNIGHT ACCESSORY Model SD505-APS Addressable Photoelectric Type Smoke Detector Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector Silent Knight SD505-APS. The combination detector head, and twist-lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight 5820XL fire panel. The base shall permit direct interchange with Silent Knight SD505-AIS Ionization Smoke Detector, or SD505- AHS Heat Detector. Base shall be the appropriate twist-lock base SD505-6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SD505-APS shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. Diameter=5-15/16" Diameter=3-15/16" - N N 4‘7 5: if h - 2 inches, 0 O o Height including base imonati 91EN1 O Model SD505-6AB Detector Base Model SD505-APS Detector Head (front view) (front view) itSILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 612-493-6435 FORM#350225, Rev.01/00 FAX: 612-493-6475 World Wide Web: http://www.silentknight.com Copyright©2000 Silent Knight INTELLIKNIGHT ACCESSORY Addressable Heat Detector ti t IntelliKnight® addressable heat detectors combine accurate heat detection with pin-point location ID. V An essential combination for any installation. IntelliKnight heat detectors are an essential component in virtually any IntelliKnight installation. The IntelliKnight panel recognizes each detector by its specific address, so precious seconds are not wasted in determining location of an alarm. Like other IntelliKnight detector models, the SD505-AHS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505-6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight detectors—easy installation, stable operation, RF/transient protection, and vandal-resistant locking—and it adds up to a flexible solution for all your fire protection needs. Model SD505-AHS If the temperature exceeds the trip Addressable Heat Detector point (programmed at the panel), an alarm occurs. The status LED The SD505-AHS is a heat detector lights continuously during the alarm C'kV suited to virtually any commercial period. • setting. The SD505-AHS is an • absolute temperature device. This Under normal conditions, the status means that it responds in alarm if LED blinks approximately every 15 the temperature goes above the seconds, indicating that the head is trip point (programmed at the communicating with the loop. a panel). Features The SD505-AHS provides accurate • Low profile, 2 inches, including SD505-AHS Heat Detector temperature measurement data to base Specifications the fire alarm control panel. This Absolute temperature device Operating Voltage: 17 to 41 VDC •heat detector is particularly suited to environments where smoke • Simple and reliable addressing Current Consumption: detectors cannot be used because • Uses digital communication Standby: .55 mA of the presence of steam or protocol Alarm: 55 mA cooking fumes, such as in a • The SD505-AHS is UL Listed Detection Temperature • kitchen. Range: 135°F to 150°F and meets the requirements (57°C TO 65°C) outlined in NFPA 72 Inspection Operation Testing and Maintenance, Ambient Temperature: 32°F to 100°F The SD505-AHS unit is made up of (o C to 37 c) Chapter 7. an externally mounted thermistor Mounting: 4"SQR,4"OCT with a specially designed cover that CFSM listed Single gang mud protects the thermistor while • MEA listed ring allowing maximum air flow. The Rated Spacing: 70'between thermistor reads the temperature sensors on smooth ceilings. from the air it takes in. It then transmits a signal representing the SILENT temperature to the IntelliKnight panel. ` KNIGHT INTELLIKNIGHT ACCESSORY Model SD505-AHS .. Addressable Heat Detector . 1:. . (i.:. A Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable heat detector Silent Knight SD505-AHS. The combination detector head, and twist-lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight 5820XL fire panel. The base shall permit direct interchange with Silent SD505-APS Photoelectric Smoke Detector, or SD505-AIS Ionization Smoke Detector. Base shall be the appropriate twist-lock base SD505-6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset switch. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field removable when not required. Voltage and RF/transient suppression techniques shall be employed to minimize false alarm potential. Diameter=5-15/16" Diameter= 3-15/16" H M M H Ilicil 'ci friai4 // /,—.\ \1 Height= 2 inch es, ..fii4 0 p 0 9))) \./ � including base iwtcxr 0 Model SD505-6AB Detector Base Model SD505-AHS Detector Head - (Front View) (Front View) itliSILENT KNIGHT A 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 612-493-6435 FORM#350229, Rev. 01/00 FAX: 612-493-6475 World Wide Web: http://www.silentknight.com Copyright©2000 Silent Knight