Loading...
Specifications �PS 201 -- Oo rt Li WYATT FIRE PROTECTION, INC. 9095 SW Burnham Street; Tigard, Oregon 97223 PHONE (503)684-2928 The Adrienne 7148 SW Gonzaga Street Tigard, Oregon Revision #1 - 12/11/2013 FIRE PROTECTION HYDRAULIC CALCULATIONS CHECKED OR COMPLETED BY: I2./i. /3 MARC A.WALTER, NICET IV #74783 TUALATIN VALLEY WATER DISTRICT Test #: 868 FIRE HYDRANT FLOW TEST REPORT Hydrant it #: 2S1W01A40H50 Location: 7070 SW GONZAGA ST. Date: 8/31/2009 Test made by: HERB & KEVIN Witness: Time: 11:00 Project name: Discharge coefficient: .54816 Inside dia. of outlet = 4.5 inches Pitot reading = 41 psi Pitot 2 = 0 psi Observed flow rate = 2119.5 gpm Flow method: HOSE MONSTER Static pressure: 110 psi Residual pressure: 80 psi 01 Flow at 20psi residual pressure (calculated): 3836 gpm Location map: To be attached to test report and to show which hydrants were used to monitor residual pressure and flow. Gage information: Static and residual pressure gage: 120997-20 Pitot gage: 9864E1 Hydrant information: Hydrant!D Year Make Notes Flow hydrant: 2S1W01A40H50 1999 WATEROUS see map for location Read hydrant: 2S1W01A39H50 2000 WATEROUS see map for location Remarks: The mapping, flow or pressure information contained herein reflects conditions on the date and time of the test_ Tualatin Valley Water District makes no representation as to the system's ability to meet specific fire flow requirements. Future system capability may differ from the flows reported herein because of subsequent modifications to the district's system and/or because flow and pressure may vary by time of day and season. Test gage callibration information available upon request. V r' N r c_ '-Crrl BEVELAND I 1 ST . • .- TITERYs 1 r 8"GV ,_, P0 I I Laic. : &134/e)9 f 1 .• .. C. � � e4*: I 2 997-2G I I !j" 1 e k{ot..5+er g ( r w� 1 i 1 ii GONZAGA ST. 1 a� f 1 :'CV, ` DI h ^; *PA.,n04 GV 1 Zs Ftd� 1 -y 1 I si • a 2 V:k.- rA5 I ba 1999 il Ai ^'' 1 Li I I > 1 1 < y '-. N HAMPTON m m 1 112BFV *? GVN/C(17 -- -- -- -- I _ '� II 'Fl- 1 .IV �„ /2111 ' t SPRINKLER SYSTEM ANALYSIS (IMPERIAL) CALCULATION #1 Contractor : WYATT FIRE PROTECTION, INC Company Address : 9095 SW Burnham St. ; Portland, OR 97223 PAGE: 1 OF 8 DATE: 11 . 20 . 2013 JOB NAME : THE ADRIENNE ADDRESS : 7148 SW Gonzaga Street * Tigard * Oregon Description:Covered Parking DESIGNER : M. Walter, SET Authority : Tualitin Valley Fire District CONTRACT #13-862-WF REF. TO DRAWING #FP2 . 0 HAZARD DESCRIPTION: Ordinary Hazard Group I CALCULATION CRITERIA: - TOTAL AREA : 1002. 0 SQ. FT. DENSITY : 0 . 150 USGPM/SQ. FT. Max.AREA/SPRINKLER : 120. 0 SQ. FT. #- OF SPRINKLER : 9 Min. Safety : 0 PSI SYSTEM REQUIREMENT: - Node System Hose Hydrant Total Pressure GPM GPM GPM GPM PSI 131 181 . 85 0 . 00 250 . 00 431 . 85 80 . 56 SOURCE INFORMATION: - SUPPLY STATIC PRESSURE RESIDUAL PRESSURE RESIDUAL FLOW 131 110 . 00 PSI 80 . 00 PSI 2119 . 5 GPM FIRE PUMP RATING: PUMP PRESSURE FLOW SPRINKLER K= 5. 60 OVERHEAD PIPE C= 120/140 UNDERGROUND C= 140 TOTAL SAFETY = 27 . 86 PSI Below Supply FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 1 .mdb THE ADRIENNE • • Ground Floor - Parking 125 - System Pressure 80.56 PSI Demand @ Base: 181 .85 GPM Flow @ Supply: 431 .85 GPM 100 — i50 GPM Hose Source Supply • cn 75 a) L U) a) ^L 0 50 Demandl 25 0 212424 636 848 1060 1272 1484 1696 1908 2120 2331 Flow(GPM) WYATT FIRE PROTECTION, INC SPRINKLER SYSTEM ANALYSIS (IMPERIAL) JOB NAME: THE ADRIENNE FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 1 .mdb NODE ELEVATION PRESSURE DISCHARGE WASTAGE FT. PSI GPM % 101 11 . 0 10. 33 18 . 0 0 . 0 102 11 . 5 10. 37 103 11 . 5 11. 73 104 11 . 0 10 . 76 18 . 4 2 . 1 105 11 . 5 10 . 81 106 11 . 0 10 . 70 18 . 3 1 . 7 107 11 . 5 10 . 75 108 11. 5 12 . 15 109 11. 0 11 . 14 18 . 7 3. 8 110 11. 5 11 . 20 111 11 . 0 12 . 04 19. 4 7 . 9 112 11 . 5 12 . 12 113 11 . 5 13. 69 114 11 . 0 12 . 53 19. 8 10 . 1 115 11 . 5 12 . 63 116 11 . 0 15. 01 21 . 7 20 . 5 117 11 . 5 15. 16 118 11 . 5 17 . 09 119 11 . 0 15 . 62 22 . 1 22 . 9 120 11 . 5 15. 78 121 11 . 0 20 . 48 25. 3 40 . 8 122 11 . 5 20 . 76 123 11. 5 23. 33 124 11. 5 37 . 51 125 10 . 0 55. 34 126 10 . 0 65. 34 127 10 . 0 67 . 61 128 0 . 5 73. 12 129 0 . 0 73. 46 130 0 . 0 80 . 46 131 0 . 0 80. 56 250 . 0 HOSE JOB NAME: THE ADRIENNE FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 1 .mdb :PE NODE FLOW DIA. LENGTH FRICTION PRESSURE To. No. GPM IN. FT. PSI/FT. PSI 101 QN=18 . 0 L=0 . 6 PT=10 . 33 K=5 . 60 • D=1 . 080 F=2 . 3 0 . 093 PF=0 . 27 V=6. 31 FT=E PE=-0 . 23 C=120 . 00 102 QP=18 . 0 LT=2 . 9 PT=10 . 37 Pv=0 . 27 102 QN=0 . 0 L=8 . 8 PT=10 . 37 K=0 . 00 D=1 . 080 F=5. 8 0 . 093 PF=1 . 36 V=6. 31 FT=T PE=0 . 00 C=120 . 00 103 QP=18 . 0 LT=14 . 6 PT-11 . 73 Pv=0 . 27 104 QN=18 . 4 L=0 . 6 PT=10 . 76 K=5. 60 D=1 . 080 F=2 . 3 0 . 097 PF=0 . 28 V=6. 44 FT=E PE=-0 . 23 C=120 . 00 105 QP=18 . 4 LT=2 . 9 PT=10 . 81 Pv=0 . 28 105 QN=0. 0 L=3. 7 PT=10 . 81 K=0 . 00 D=1 . 080 F=5. 8 0. 097 PF=0 . 92 V=6. 44 FT=T PE=0 . 00 C=120. 00 103 QP=18 . 4 LT=9. 5 PT=11 . 73 Pv=0 . 28 103 QN=0 . 0 L=9. 3 PT=11 . 73 K=0 . 00 D=1 . 639 F=0 . 0 0 . 045 PF=0 . 42 V=5. 53 FT=0 PE=0 . 00 C=120 . 00 108 QP=36. 4 LT=9. 3 PT=12 . 15 Pv=0 . 21 106 QN=18 . 3 L=0 . 6 PT=10 . 70 K=5. 60 D=1 . 080 F=2 . 3 0 . 097 PF=0 . 28 V=6. 42 FT=E PE=-0 . 23 C=120 . 00 107 QP=18 . 3 LT=2 . 9 PT=10. 75 Pv=0 . 28 107 QN=0 . 0 L=8 . 8 PT=10 . 75 K=0 . 00 D=1 . 080 F=5. 8 0 . 097 PF=1 . 41 V=6. 42 FT=T PE=0 . 00 C=120 . 00 108 QP=18 . 3 LT=14 . 6 PT=12 . 15 Pv=0 . 28 109 QN=18 . 7 L=0 . 6 PT=11 . 14 K=5 . 60 D=1. 080 F=2 . 3 0 . 100 PF=0 . 29 V=6. 55 FT=E PE=-0 . 23 C=120. 00 110 QP=18 . 7 LT=2 . 9 PT=11 . 20 Pv=0 . 29 110 QN=0 . 0 L=3 . 7 PT=11 . 20 K=0 . 00 D=1 . 080 F=5. 8 0 . 100 PF=0 . 95 V=6. 55 FT=T PE=0 . 00 C=120 . 00 108 QP=18 . 7 LT=9. 5 PT=12. 15 Pv=0 . 29 108 QN=0 . 0 L=9. 3 PT=12 . 15 K=0 . 00 D=1. 639 F=0 . 0 0 . 165 PF=1 . 54 V=11 . 16 FT=0 PE=0 . 00 C=120 . 00 113 QP=73 . 4 LT=9. 3 PT=13 . 69 Pv=0 . 84 JOBkNAMB: THE ADRIENNE FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 1 .mdb :PE NODE FLOW DIA. LENGTH FRICTION PRESSURE 1o. No. GPM IN. FT. PSI/FT. PSI 111 QN=19. 4 L=0 . 6 PT=12 . 04 K=5 . 60 ' D=1 . 080 F=2 . 3 0 . 108 PF=0 . 32 V=6. 81 FT=E PE=-0 . 23 C=120 . 00 112 QP=19. 4 LT=2 . 9 PT=12 . 12 Pv=0 . 31 112 QN=0 . 0 L=8 . 8 PT=12 . 12 K=0 . 00 ' D=1. 080 F=5. 8 0 . 108 PF=1 . 57 V=6. 81 FT=T PE=0. 00 C=120 . 00 113 QP=19. 4 LT=14 . 6 PT=13. 69 Pv=0 . 31 114 QN=19. 8 L=0 . 6 PT=12 . 53 K=5. 60 3 D=1 . 080 F=2 . 3 0 . 112 PF=0. 33 V=6. 95 FT=E PE=-0 . 23 C=120 . 00 115 QP=19. 8 LT=2 . 9 PT=12 . 63 Pv=0 . 32 115 QN=0 . 0 L=3. 7 PT=12 . 63 K=0. 00 E D=1 . 080 F=5. 8 0 . 112 PF=1 . 06 V=6. 95 FT=T PE=0 . 00 C=120 . 00 113 QP=19. 8 LT=9. 5 PT=13. 69 Pv=0 . 32 113 QN=0 . 0 L=9. 3 PT=13. 69 K=0 . 00 i D=1 . 639 F=0 . 0 0 . 366 PF=3. 40 V=17 . 13 FT=0 PE=0 . 00 C=120 . 00 118 QP=112 . 7 LT=9. 3 PT=17 . 09 Pv=1 . 98 116 QN=21 . 7 L=0 . 6 PT=15. 01 K=5. 60 3 D=1 . 080 F=2 . 3 0 . 132 PF=0 . 39 V=7 . 60 FT=E PE=-0 . 23 C=120 . 00 117 QP=21 . 7 LT=2 . 9 PT=15. 16 Pv=0 . 39 117 QN=0 . 0 L=8 . 8 PT=15. 16 K=0 . 00 D=1 . 080 F=5. 8 0 . 132 PF=1 . 93 V=7 . 60 FT=T PE=0 . 00 C=120 . 00 118 QP=21 . 7 LT=14 . 6 PT=17 . 09 Pv=0 . 39 119 QN=22 . 1 L=0 . 6 PT=15. 62 K=5. 60 3 D=1 . 080 F=2 . 3 0 . 137 PF=0 . 40 V=7 . 75 FT=E PE=-0 . 23 C=120 . 00 120 QP=22 . 1 LT=2 . 9 PT=15. 78 Pv=0 . 40 120 QN=0 . 0 L=3. 7 PT=15 . 78 K=0 . 00 a D=1 . 080 F=5 . 8 0 . 137 PF=1 . 30 V=7 . 75 FT=T PE=0 . 00 C=120 . 00 118 QP=22 . 1 LT=9. 5 PT=17 . 09 Pv=0 . 40 118 QN=0 . 0 L=9. 3 PT=17 . 09 K=0 . 00 l D=1 . 639 F=0 . 0 0. 672 PF=6. 24 V=23. 80 FT=0 PE=0 . 00 C=120 . 00 123 QP=156. 5 LT=9. 3 PT=23. 33 Pv=3 . 81 JOB, NAML: THE ADRIENNE FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 1 .mdb :PE NODE FLOW DIA. LENGTH FRICTION PRESSURE 1o. No. GPM IN. FT. PSI/FT. PSI 121 QN=25. 3 L=0 . 6 PT=20 . 48 K=5 . 60 • D=1 . 080 F=2 . 3 0 . 176 PF=0. 52 V=8 . 88 FT=E PE=-0 . 23 C=120 . 00 122 QP=25. 3 LT=2 . 9 PT=20 . 76 Pv=0 . 53 122 QN=0 . 0 L=8 . 8 PT=20 . 76 K=0 . 00 D=1 . 080 F=5. 8 0 . 176 PF=2 . 57 V=8 . 88 FT=T PE=0 . 00 C=120 . 00 123 QP=25. 3 LT=14 . 6 PT=23. 33 Pv=0 . 53 123 QN=0 . 0 L=11 . 6 PT=23. 33 K=0 . 00 3 D=1 . 639 F=4 . 4 0 . 888 PF=14 . 18 V=27 . 65 FT=E PE=0 . 00 C=120 . 00 124 QP=181 . 8 LT=16. 0 PT=37 . 51 Pv=5 . 15 124 QN=0. 0 L=32 . 5 PT=37 . 51 K=0 . 00 I D=2. 104 F=32 . 8 0 . 263 PF=17 . 17 V=16. 78 FT=2E2T PE=0 . 65 C=120 . 00 125 QP=181 . 8 LT=65. 3 PT=55. 34 Pv=1 . 89 125 QN=0 . 0 L=1 . 0 PT=55. 34 K=0 . 00 i D=2 . 469 F=0 . 0 0 . 001 PF=10. 00 V=12 . 19 FT=F, 10 PE=0 . 00 C=120 . 00 126 QP=181 . 8 LT=1 . 0 PT=65. 34 Pv=1 . 00 r 126 QN=0 . 0 L=0 . 8 PT=65. 34 K=0. 00 i D=2 . 469 F=18 . 0 0 . 121 PF=2 . 27 V=12 . 19 FT=ET PE=0. 00 C=120 . 00 127 QP=181 . 8 LT=18 . 8 PT=67 . 61 Pv=1 . 00 127 QN=0 . 0 L=7 . 0 PT=67 . 61 K=0 . 00 7 D=2. 703 F=10 . 9 0 . 078 PF=1 . 39 V=10 . 17 FT=B PE=4 . 12 C=120 . 00 128 QP=181 . 8 LT=17 . 9 PT=73. 12 Pv=0 . 70 128 QN=0 . 0 L=75. 0 PT=73. 12 K=0 . 00 3 D=6. 280 F=58 . 4 0 . 001 PF=0 . 13 V=1 . 88 FT=L4S PE=0 . 22 C=140 . 00 129 QP=181 . 8 LT=133. 4 PT=73. 46 Pv=0 . 02 129 QN=0 . 0 L=1 . 0 PT=73 . 46 K=0 . 00 ) D=6. 280 F=0 . 0 0 . 001 PF=7 . 00 V=1 . 88 FT=F, 7 PE=0 . 00 C=140 . 00 130 QP=181 . 8 LT=1 . 0 PT=80 . 46 Pv=0 . 02 130 QN=0 . 0 L=30 . 0 PT=80 . 46 K=0 . 00 D=6. 280 F=66. 2 0 . 001 PF=0 . 09 V=1 . 88 FT=LGT PE=0 . 00 C=140 . 00 131 QP=181 . 8 LT=96. 2 PT=80 . 56 Pv=0 . 02 :LEND = Standard 45 degree elbow QN = Normal flow discharge = Standard 90 degree elbow QP = Flow; in; pipe = 'Long turn degree elbow D = Pipe inside diameter = Standard tee L = Pipe length = Butterfly valve F = Fitting equivalence =Gate valve FT = Fitting type = Check valve LT = Total length = Alarm valve PT = Total node pressure = Dry pipe valve PF = Pressure friction loss = Deluge valve PE = Pressure elevation loss = Pre-action valve K = Sprinkler K-factor = Back flow preventer V = Velocity x = Constant pressure x in PSI C = C-factor for fitting F PV = Velocity pressure SIGNIFICANT HYDRAULICAL NOTES: iximum velocity of 27 . 65 FT/SEC at pipe 23 )st remote sprinkler @ node 101 • ∎ , • 1 SPRINKLER SYSTEM ANALYSIS (IMPERIAL) CALCULATION #2r1 Contractor : WYATT FIRE PROTECTION, INC Company Address: 9095 SW Burnham St. ; Portland, OR 97223 ' PAGE: 1 OF 8 DATE: 12 . 11 . 2013 JOB NAME : THE ADRIENNE ADDRESS : 7148 SW Gonzaga Street * Tigard * Oregon Description: Residential Unit - Revision #1 DESIGNER : M. Walter, SET Authority : Tualitin Valley Fire District CONTRACT #13-862-WF REF. TO DRAWING #FP2 . 2 HAZARD DESCRIPTION: Residential NFPA 13 CALCULATION CRITERIA: - TOTAL AREA : 438 . 1 SQ. FT. DENSITY : 0 . 100 USGPM/SQ. FT. Max.AREA/SPRINKLER : 228 . 0 SQ. FT. #- OF SPRINKLER : 4 Min. Safety : 0 PSI SYSTEM REQUIREMENT: - Node System Hose Hydrant Total Pressure GPM GPM GPM GPM PSI 131 104 . 62 0. 00 100 . 00 204 . 62 101 . 95 SOURCE INFORMATION: - SUPPLY STATIC PRESSURE RESIDUAL PRESSURE RESIDUAL FLOW 131 110 . 00 PSI 80 . 00 PSI 2119. 5 GPM FIRE PUMP RATING: PUMP PRESSURE FLOW SPRINKLER K= 4 . 90 OVERHEAD PIPE C= 150/120/140 UNDERGROUND C= 140 TOTAL SAFETY = 7 . 65 PSI Below Supply FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 2 Rev 1 .mdb THE ADRIENNE • Third Floor- Residential Unit - Revision 1 125 - System Pressure 101.95 PSI Demand @ Base: 104.62 GPM Flow @, Supply: 204.62 GPM IN100 GPM Hose 100 Source Supply 75 a. a_ L ^L 50 r Demand1 25 0 212424 636 848 1060 1272 1484 1696 1908 2120 2331 Flow(GPM) '�` . t WYATT FIRE PROTECTION, INC SPRINKLER SYSTEM ANALYSIS (IMPERIAL) JOB NAME: THE ADRIENNE FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 2 Rev 1 .mdb NODE ELEVATION PRESSURE DISCHARGE WASTAGE FT. PSI GPM % 127 10 . 0 89. 39 128 0 . 5 94 . 65 129 0 . 0 94 . 91 130 0 . 0 101. 92 131 0 . 0 101. 95 100 . 0 HOSE 201 34 . 3 21 . 65 22 . 8 0 . 0 202 34 . 8 21. 81 203 34 . 3 22 . 41 23. 2 1 . 7 204 34 . 8 23. 12 205 34 . 8 25. 43 206 34 . 8 33. 14 207 34 . 3 32 . 40 27 . 9 22 . 3 208 34 . 8 32 . 73 209 34 . 8 36. 79 210 34 . 8 41. 53 211 34 . 8 45. 27 212 34 . 3 39. 30 30. 7 34 . 7 - 213 34 . 8 39. 74 - 214 34 . 8 41 . 68 215 34 . 8 59. 18 216 34 . 8 72 . 10 217 34 . 8 76. 28 218 24 . 5 81 . 76 219 11. 5 88 . 60 JOBb AML: THE ADRIENNE FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 2 Rev 1 .mdb :PE NODE FLOW DIA. LENGTH FRICTION PRESSURE lo. No. GPM IN. FT. PSI/FT. PSI 201 QN=22 . 8 L=0 . 5 PT=21 . 65 K=4 . 90 • D=1 . 101 F=3. 9 0 . 087 PF=0 . 39 V=7 . 68 FT=E PE=-0 . 23 C=150 . 00 202 QP=22 . 8 LT=4 . 5 PT=21 . 81 Pv=0 . 40 202 QN=0 . 0 L=15 . 1 PT=21 . 81 K=0 . 00 D=1 . 101 F=0 . 0 0 . 087 PF=1 . 32 V=7 . 68 FT=0 PE=0 . 00 C=150 . 00 204 QP=22 . 8 LT=15. 1 PT=23 . 12 Pv=0 . 40 203 QN=23. 2 L=0 . 5 PT=22 . 41 K=4 . 90 D=1. 101 F=10 . 0 0. 090 PF=0 . 95 V=7 . 82 FT=T PE=-0 . 23 C=150 . 00 204 QP=23. 2 LT=10 . 5 PT=23. 12 Pv=0 . 41 204 QN=0 . 0 L=3. 3 PT=23. 12 K=0 . 00 D=1 . 101 F=3. 9 0 . 320 PF=2 . 31 V=15 . 50 FT=E PE=0 . 00 C=150 . 00 205 QP=46. 0 LT=7 . 2 PT=25. 43 Pv=1 . 62 205 QN=0 . 0 L=14 . 1 PT=25. 43 K=0 . 00 D=1 . 101 F=10 . 0 0 . 320 PF=7 . 71 V=15. 50 FT=T PE=0. 00 C=150 . 00 206 QP=46. 0 LT=24 . 1 PT=33. 14 Pv=1 . 62 207 QN=27 . 9 L=0 . 5 PT=32 . 40 K=4 . 90 D=1 . 101 F=3. 9 0 . 127 PF=0 . 57 V=9. 40 FT=E PE=-0 . 23 C=150 . 00 208 QP=27 . 9 LT=4 . 5 PT=32 . 73 Pv=0 . 59 208 QN=0. 0 L=3. 3 PT=32 . 73 K=0. 00 D=1 . 101 F=0. 0 0 . 127 PF=0 . 42 V=9. 40 FT=0 PE=0 . 00 C=150 . 00 206 QP=27 . 9 LT=3. 3 PT=33. 14 Pv=0 . 59 206 QN=0 . 0 L=10 . 1 PT=33 . 14 K=0 . 00 D=1 . 394 F=4 . 8 0 . 244 PF=3. 65 V=15. 53 FT=E PE=0. 00 C=150 . 00 209 QP=73. 9 LT=15. 0 PT=36. 79 Pv=1 . 62 209 QN=0 . 0 L=9. 8 PT=36. 79 K=0 . 00 D=1. 394 F=9. 7 0 . 244 PF=4 . 74 V=15. 53 FT=T PE=0 . 00 C=150 . 00 210 QP=73. 9 LT=19. 4 PT=41 . 53 Pv=1 . 62 210 QN=0 . 0 L=5. 7 PT=41 . 53 K=0 . 00 l D=1 . 394 F=9. 7 0 . 244 PF=3. 74 V=15. 53 FT=T PE=0 . 00 C=150 . 00 211 QP=73. 9 LT=15. 3 PT=45 . 27 Pv=1 . 62 JOBa N4;Mg: THE ADRIENNE FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 2 Rev 1 .mdb :PE NODE FLOW DIA. LENGTH FRICTION PRESSURE ]o. No. GPM IN. FT. PSI/FT. PSI 212 QN=30 . 7 L=0 . 5 PT=39. 30 K=4 . 90 ' D=1 . 101 F=3. 9 0 . 151 PF=0. 68 V=10 . 35 FT=E PE=-0 . 23 C=150 . 00 213 QP=30 . 7 LT=4 . 5 PT=39. 74 Pv=0 . 72 213 QN=0 . 0 L=2 . 8 PT=39. 74 K=0 . 00 D=1 . 101 F=10 . 0 0. 151 PF=1 . 94 V=10 . 35 FT=T PE=0 . 00 C=150 . 00 214 QP=30 . 7 LT=12 . 8 PT=41 . 68 Pv=0 . 72 214 QN=0 . 0 L=13. 7 PT=41 . 68 K=0 . 00 3 D=1. 101 F=10 . 0 0 . 151 PF=3. 59 V=10 . 35 FT=T PE=0 . 00 C=150 . 00 211 QP=30. 7 LT=23. 7 PT=45. 27 Pv=0 . 72 211 QN=0 . 0 L=20. 3 PT=45. 27 K=0 . 00 ! D=1 . 394 F=9. 7 0 . 464 PF=13. 91 V=21 . 99 FT=T PE=0 . 00 C=150 . 00 215 QP=104 . 6 LT=30 . 0 PT=59. 18 Pv=3. 25 215 QN=0 . 0 L=23 . 0 PT=59. 18 K=0 . 00 i D=1 . 394 F=4 . 8 0 . 464 PF=12. 92 V=21 . 99 FT=E PE=0. 00 C=150 . 00 216 QP=104 . 6 LT=27 . 8 PT=72 . 10 Pv=3. 25 216 QN=0 . 0 L=4 . 2 PT=72 . 10 K=0 . 00 i D=1. 394 F=4 . 8 0 . 464 PF=4 . 18 V=21. 99 FT=E PE=0 . 00 C=150 . 00 217 QP=104 . 6 LT=9. 0 PT=76. 28 Pv=3. 25 217 QN=0. 0 L=10 . 4 PT=76. 28 K=0. 00 D=2 . 104 F=0. 0 0 . 094 PF=0 . 98 V=9 . 65 FT=0 PE=4 . 49 C=120 . 00 218 QP=104 . 6 LT=10 . 4 PT=81 . 76 Pv=0 . 63 218 QN=0 . 0 L=13. 0 PT=81 . 76 K=0 . 00 3 D=2 . 104 F=0 . 0 0 . 094 PF=1 . 22 V=9 . 65 FT=0 PE=5 . 62 C=120 . 00 219 QP=104 . 6 LT=13. 0 PT=88 . 60 Pv=0 . 63 219 QN=0 . 0 L=1 . 5 PT=88 . 60 K=0 . 00 3 D=2. 104 F=0 . 0 0 . 094 PF=0 . 14 V=9. 65 FT=0 PE=0 . 65 C=120 . 00 127 QP=104 . 6 LT=1. 5 PT=89. 39 Pv=0. 63 127 QN=0 . 0 L=7 . 0 PT=89. 39 K=0 . 00 D=2 . 203 F=8 . 2 0 . 076 PF=1 . 15 V=8 . 81 FT=B PE=4 . 12 C=120 . 00 128 QP=104 . 6 LT=15. 2 PT=94 . 65 Pv=0 . 52 JOB16-NMA: THE ADRIENNE FILE: C: \FireAcad\dwgl\Wyatt Fire\The Adrienne\Adrienne Calc 2 Rev 1 .mdb :PE NODE FLOW DIA. LENGTH FRICTION PRESSURE 1o. No. GPM IN. FT. PSI/FT. PSI 128 QN=0 . 0 L=75. 0 PT=94 . 65 K=0 . 00 ` D=6. 280 F=58 . 4 0 . 000 PF=0 . 05 V=1 . 08 - FT=L4S PE=0 . 22 C=140 . 00 129 QP=104 . 6 LT=133 . 4 PT=94 . 91 Pv=0 . 01 129 QN=0 . 0 L=1 . 0 PT=94 . 91 K=0. 00 ' D=6. 280 F=0. 0 0 . 000 PF=7 . 00 V=1 . 08 FT=F, 7 PE=0 . 00 C=140 . 00 130 QP=104 . 6 LT=1. 0 PT=101 . 92 Pv=0 . 01 130 QN=0 . 0 L=30 . 0 PT=101 . 92 K=0 . 00 3 D=6. 280 F=66. 2 0. 000 PF=0 . 03 V=1 . 08 FT=LGT PE=0 . 00 C=140 . 00 131 QP=104 . 6 LT=96. 2 PT=101 . 95 Pv=0 . 01 - ;GEND = Standard 45 degree elbow QN = Normal flow discharge = Standard 90 degree elbow QP = Flow; in; pipe = Fong turn degree elbow D = Pipe inside diameter = -Standard tee L = Pipe length = Butterfly valve F = Fitting equivalence = Gate valve FT = Fitting type = Check valve LT = Total length = Alarm valve PT = Total node pressure = Dry pipe valve PF = Pressure friction loss = Deluge valve PE = Pressure elevation loss = Pre-action valve K = Sprinkler K-factor = Back flow preventer V = Velocity x = Constant pressure x in PSI C = C-factor for fitting F PV = Velocity pressure SIGNIFICANT HYDRAULICAL NOTES: iximum velocity of 21 . 99 FT/SEC at pipe 16 )st remote sprinkler @ node 201 WYATT FIRE PROTECTION, INC. 9095 SW Burnham Street; Tigard, Oregon 97223 PHONE (503)684-2928 dr: TU co PROF �N G'NE: '• The Adrienne 5. 7148 SW Gonzaga Street Tigard, Oregon 9 • ON U(S'g 2p01 .OYO. LYVER9. I RENEWAL:DEC.31,20 FIRE PROTECTION SEISMIC CALCULATIONS • CHECKED OR COMPLETED BY: "'•-�, I I zo 3 MARC A.WALTER, NICET IV #74783 Tol-Brace Seismic Calculations Wyatt Fire Protection Project Address: The Adrienne 9095 SW Burnham St Tigard,OR 97223 COOPER 13-Line TOLCO 7148 SW Gonzaga Street (503)684-2928 Tigard, Oregon CCB #64077 Job# 13-862-WF Calculations based on 2010 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 40' 0" (12.19 m) Tolco Component Fig. Number Adjusted Load 0" (2.13 m Fig.1000 Clamp 1425 lbs(646 kg) 7 Maximum Brace Length 7' " ( j Bracing Material 1" SCh.40 Fig.980 Universal Swivel 1955 lbs(887 kg) Angle from Vertical 450 Min. 'Calculation Based on CONCENTRIC Loading 'Please Note:These calculations are for Tolco components only.Use of any other components voids these calculations and the listing of the assembly. Least Rad.of Gyration 0.42„ (11 mm) Assembly Detail L/R Value 200 Max Horizontal Load 1310 lbs(594 kg) TOLCO FIG. 980 UNIVERSAL SWAY BRACE Force Factor(Cp) 0.5 ATTACHMENT .; STEEL PIPE LATERAL BRACE • Fastener Information Fastener Orientation NFPA Type B Maximum Load 216 lbs (98 kg) TOLCO FIG. 1000 FAST CLAMP Diameter 3/8in. _ �• Length tin. - Type Wedge Anchor(3000psi 14 ht-Weight Concrete - Metal Decking) Brace Identification on Plans SB1 Orientation of Brace Lateral Braced Pipe: 2”Threadable Thinwall Load Information Size and Type of Pipe Total Length Total Calculated Load 2"Threadable Thinwall(50.8 mm) 40ft(12.2 m) 84 lbs(38 kg) 1"Threadable Thinwall(25.4 mm) 60ft(18.3 m) 54 lbs(24 kg) Percentage added for Fittings and Sprinklers 15% 21 lbs(9.53 kg) Total Adjusted Load of all pipe within Zone of Influence 160 lbs(73 kg) {Tol-Brace Version 7} Tol-Brace Seismic Calculations The Adrienne Job # 13-862-WF COOPER B-Line TOLCO 7148 SW Gonzaga Street Brace Identification SB1 Brace Type (Per NFPA#13) NFPA Type B Braced Pipe 2"Threadable Thinwall Spacing of Brace 40'0" (12.19 m) Orientation of Brace Lateral Bracing Material 1" Sch.40 Maximum Brace Length 7' 0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 3/8in. x 2in. Wedge Anchor(3000 psi Light-Weight Concrete- Me Length of Fastener 2in. Summary of Pipe within Zone of Influence 2"Threadable Thinwall(50.8 mm) 40ft(12.2 m) 1"Threadable Thinwall(25.4 mm) 60ft(18.3 m) Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 160 lbs (73 kg) Material Capacity 1310 lbs (594 kg) Fastener Capacity 216 lbs (98 kg) Fig.1000 Clamp 1425 lbs (646 kg) Fig.980 Universal Swivel 1955 lbs (887 kg) Structural Member Concrete Deck Calculations prepared by M. Walter, SET The description of the Structual Member is for informational purposes only. Tol-Brace software calculates the brace assembly only,not the structure is is attached to. Calculated with Tol-Brace 7 visit us at www.tolco.com Tol-Brace Seismic Calculations Wyatt Fire Protection Project Address: The Adrienne 9095 SW Burnham St • Tigard,OR 97223 COOPER B-Line ®TOLCO 7148 SW Gonzaga Street (503)684-2928 Tigard, Oregon CCB#64077 Job# 13-862-WF Calculations based on 2010 NFPA Pamphlet#13 Brace Information Tolco Brace Components Maximum Spacing 80'0" (24.38 m) Tolco Component Fig. Number Adjusted Load Maximum Brace Length 7' 0" (2.13 m) Fig.4LA(Long)Clamp 707 lbs(321 kg) Bracing Material 1" Sch.40 Fig.980 Universal Swivel 1955 lbs(887 kg) Angle from Vertical 45° Min. *Calculation Based on CONCENTRIC Loading *Please Note:These calculations are for Tolco components only.Use of any Least Rad.of Gyration 0.42" (11 mm) other components voids these calculations and the listing of the assembly. Assembly Detail L/R Value 200 Max Horizontal Load 1310 lbs (594 kg) NUNS TOLCO F10 Pro Force Factor(Cp) 0.5 UMVERBAL SWAY BRACE ATTACHMENT .A Fastener Information BRACE PIPE • Fastener Orientation NFPA Type B B-LINE ITOLCO HO ALA "MAINE"SWAY • BRACE ATTACHMENT �i Maximum Load 216 lbs(98 kg) C9 Diameter 3/8in. j A Length tin. Type Wedge Anchor(3000 psi Light-Weight Concrete - Metal Decking) Brace Identification on Plans SB2 Orientation of Brace Longitudinal Braced Pipe:2"Threadable Thinwall Load Information Size and Type of Pipe Total Length Total Calculated Load 2"Threadable Thinwall(50.8 mm) 80ft(24.4 m) 169 lbs(77 kg) • Percentage added for Fittings and Sprinklers 15% 25 lbs(11.34 kg) Total Adjusted Load of all pipe within Zone of Influence 194 lbs(88 kg) {Tot-Brace Version 7} Tol-Brace Seismic Calculations The Adrienne Job # 13-862-WF COOPER B-Line ®TOLCO 7148 SW Gonzaga Street Brace Identification SB2 Brace Type (Per NFPA#13) NFPA Type B Braced Pipe 2"Threadable Thinwall Spacing of Brace 80'0" (24.38 m) Orientation of Brace Longitudinal Bracing Material 1" Sch.40 Maximum Brace Length 7' 0" (2.13 m) Slenderness Ratio used for Load Calculation 200 True Angle of Brace for Calculation 45° Type of Fastener 3/8in. x 2in. Wedge Anchor(3000 psi Light-Weight Concrete- Me Length of Fastener 2in. Summary of Pipe within Zone of Influence 2"Threadable Thinwall(50.8 mm) I 80ft(24.4 m) Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of InfluencE 194 lbs (88 kg) Material Capacity 1310 lbs(594 kg) Fastener Capacity 216 lbs (98 kg) ▪ Fig.4LA(Long) Clar 707 lbs (321 kg) Fig.980 Universal Swivel 1955 lbs (887 kg) • Structural Member Concrete Deck Calculations prepared by M. Walter, SET *The description of the Structual Member is for informational purposes only. Tol-Brace software calculates the brace assembly only,not the structure it is attached to. Calculated with Tol-Brace 7 visit us at www.tolco.com 201,3 - 1-i9 WYATT FIRE PROTECTION, INC. 9095 SW Burnham Street; Tigard, Oregon 97223 PHONE (503)684-2928 The Adrienne 7148 SW Gonzaga Street Tigard, Oregon FIRE PROTECTION EQUIPMENT SUBMITTAL f � The Adrienne 7148 SW Gonzaga Street Tigard,Oregon FIRE PROTECTION EQUIPMENT SUBMITTAL INDEX PRODUCT MAKE MODEL I DESCRIPTION 1. SPRINKLERS TYCO Series TY-FRB Quick Response SSU SIN#TY3131 Bronze Finish TYCO Series TY-FRB Quick Response SSP SIN#TY3231 Chrome w/Chr Recessed Esc or Chr w/Chr 2-Piece Esc TYCO Series TY-FRB Quick Response HSW SIN#TY3331 Bronze Finish TYCO Series LFII Residential SSP SIN#TY2234 White w/White Recessed Esc 2. PIPING ALLIED Dynaflow,Black Steel,ASTM A-795 ALLIED Dynathread,Black Steel,ASTM A-135 3. PIPE FITTINGS SMITH COOPER Ductile Iron,Grooved,ASTM A536 SMITH COOPER Cast Iron,Threaded,ASME B16.4 SMITH COOPER Ductile Iron,Threaded,ASTM A536 4. HANGERS COOPER B-LINE Figure 200 Band Hanger Ring COOPER B-LINE Figure ATR All Thread Rod COOPER B-LINE Figure 65 C-Type Beam Clamp COOPER B-LINE Figure ATR All Thread Rod COOPER B-LINE Figure B3367 Retaining Strap AFCON Figure 510 CPVC Dbl Strap AFCON Figure 511 CPVC Side Mount Strap AFCON Figure 513 CPVC Sgl Strap AFCON Figure 514 CPVC Offset Hanger AFCON Figure 515 CPVC Dbl Offset Hanger 5. SEISMIC EQUIP COOPER B-LINE Figure 4L Longitudinal Attachment COOPER B-LINE Figure 980 Sway Brace Attachment COOPER B-LINE Figure 1000 Sway Brace Attachment 6. VALVES AMES Model C400 Reduced Pressure BFP AGF Model 1000 TestanDrain FPPI Bronze Ball Valve FPPI Bronze 3-Way Valve FPPI TrimFit Grooved Butterfly Valve 7. ELECTRICAL DEVICES POTTER Model VSR Waterflow Detector POTTER Model PBA 6"Electric Bell 8. MISCELLANEOUS FPPI 300#Sprinkler Gauge FPPI Sprinkler Cabinet FPPI Identification Signs FPPI 401 2-Piece Escutcheons FPPI Recessed Sprinkler Coverage Plate **The above listed items are the proposed equipment to be used on this project,however we reserve the right to use an'equivalent'product or manufacturer at our discretion. I . ttico Worldwide Contacts www.tyco-fire.com Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General spheres.Although corrosion-resistant coated sprinklers have passed the - -- - Description standard corrosion tests of the appli p cable approval agencies,the testing is .. The TYCO Series TY-FRB, 2.8, 4.2, not representative of all possible cor- - 5.6, and 8.0 K-factor, Upright, Pen- rosive atmospheres. Consequently, •-� dent, and Recessed Pendent Sprin- it is recommended that the end user klers described in this data sheet are be consulted with respect to the suit- f """ quick response, standard coverage, ability of these coatings for any given decorative 3 mm glass bulb-type spray corrosive environment. The effects of _ sprinklers designed for use in light or ambient temperature,concentration of . -' - _ _ • ordinary hazard,commercial occupan- and gas/chemical velocity, __ cies such as banks, hotels,and shop- should be considered,as a minimum, ping malls. along with the corrosive nature of the chemical to which the sprinklers will be The recessed version of the Series TY- exposed. FRB Pendent Sprinkler,where applica- An intermediate level of the Series TY ble,is intended for use in areas with a tama finished ceiling.This recessed pendent FRB Pendent Sprinklers is detailed - . sprinkler uses one of the following: in Technical Data Sheet TFP356, and Sprinkler Guards are detailed in Tech- • A two-piece Style 10 (1/2 inch NPT) nical Data Sheet TFP780. or Style 40(3/4 inch NPT) Recessed Escutcheon with 1/2 inch(12,7 mm)of NOTICE —` recessed adjustment or up to 3/4 inch . _.�. (19,1 mm)of total adjustment from the The Series TY-FRB Concealed Pendent ,� flush pendent position,or a Sprinklers described herein must be installed and maintained in compliance • A two-piece Style 20 (1/2 inch NPT) with this document and with the appli- or Style 30(3/4 inch NPT) Recessed cable standards of the National Fire Sprinkler Escutcheon with 1/4 inch(6,4 mm)of Protection Association, in addition to recessed adjustment or up to 1/2 inch the standards of any authorities having Identification (12,7 mm)of total adjustment from the jurisdiction. Failure to do so may impair flush pendent position. the performance of these devices. Number (SIN) The adjustment provided by the The owner is responsible for maintain- Recessed Escutcheon reduces the ing their fire protection system and TY1131: Upright 2.8K, 1/2-NPT accuracy to which the fixed pipe drops devices in proper operating condition. TY1231: Pendent 2.8K, 1/2-NPT to the sprinklers must be cut. The installing contractor or sprinkler TY2131: Upright 4.2K, 1/2-NPT Corrosion-resistant coatings, where manufacturer should be contacted with TY2231: Pendent 4.2K, 1/2"NPT applicable, are utilized to extend the any questions. TY3131: Upright 5.6K, 1/2-NPT life of copper alloy sprinklers beyond TY3231: Pendent 5.6K, 1/2-NPT that which would otherwise be obtained TY4131: Upright 8.0K, 3/4-NPT when exposed to corrosive atmo- TY4231: Pendent 8.0K, 3/4-NPT TY4831: Upright* 8.0K, 1/2-NPT TY4931: Pendent* 8.0K, 1/2°NPT IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. 'Eastern Hemisphere Sales Only Page 1 of 10 MARCH 2013 TFP171 4 • TFP171 Page 2 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 7 - Bushing TIT-T-T-m, = 7 7/16" l I / ■1' �� 3 ' (11,1 mm) 1 — MOAKE NL 2 1/4" �� r 2 Ø—� (57,2 mm) ��� (55,6 mm) • l 1-9/16" 4 . (39,7 mm) . )F' 5 1/2"NPT** f WRENCH STYLE 10 or 20 P-7/8"(73,0 mm)DIA --.- FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - iiinpress2ion is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly ew Deflector. special request. PLATE SEATING 4 - Bulb 6 - ector* SURFACE 1 th 7/16" 3 (11,1 mm)NOMINAL 2-3/16" ����-� A i MAKE-IN (55,6 mm) �� 2-3/16" 1 1/2" ��� 1 4 (55,6 mm) 1 (38,1 mm) �— I ;7=� 5 \ tl • 1 .. SI .. `ir........ 6* 1/2" NPT** t WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS 4.2 K-FACTOR, 1/2 INCH NPT 1 4 . TFP171 Page 3 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector* PLATE SEATING SURFACE ciLo iTlr7TRR�; 1 0 7/16" •c(11,1 mm) -- NOMINAL -� 2-3/16" ��� � INIH MAKE-IN (55,6 mm) 2-3/16" , IF 112..2-3/16"1/2" 4l0 1 4 I (55,6 mm) (38,1 mm) f1 f1 5 6* 1/2" NPT** t WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 1/2" 9 1 � 3 (12,7 mm) ri � 'f� NOMINAL 111 f 2-5/16" � 1r-II =� 2 `=� MAKE-IN I (58,7 mm) r r . /mm I Ii 1-9/16" I �lf I 4 (57,2 ) (39,7 mm) ■ r_ 5 3/4"NPT** I WRENCH STYLE 30 or 40 6 FLATS RECESSED 2-7/8"(73,0 mm)DIA UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR, 3/4 INCH NPT 4 • TFP171 Page 4 of 10 CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 1 3 - Sealing 6 - Deflector * "ff Assembly 7/16" 2-1/4 4 f 3 4 - Bulb (11,1 mm) N i 1 (57,2 mm) ;/i� 4 2 NOMINAL MAKE-IN I * Temperature rating is r�� 2-3/16" 1-9/16" 4 indicated on Deflector. (55,6 mm) i i (39,7 mm) . r��5 ** Pipe thread connections \ „-_ _.��,-,1.-_ * per ISO 7-1 can be 1 6 provided on special 1/2" NPT** I WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT Technical Design the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Data Criteria Series TY-FRB Upright and Pendent Approvals The TYCO Series TY-FRB, 2.8, 4.2, Sprinklers UL and C-UL Listed 5.6, and 8.0 K-factor, Upright, Pen- The Series TY-FRB Pendent and FM, LPCB,and NYC Approved dent,and Recessed Pendent Sprinklers Upright Sprinklers must be installed Refer to Table A and B for complete are intended for fire protection sys- in accordance with the following tems designed in accordance with the instructions. approval information including 9 corrosion-resistant status. standard installation rules recognized Step 1.Install Pendent sprinklers in the . by the applicable Listing or Approval pendent position. Install upright sprin- Maximum Working Pressure agency (such as, UL Listing is based klers in the upright position. Refer to Table C. on the requirements of NFPA 13, and Step 2. With pipe-thread sealant FM Approval is based on the require- applied to the pipe threads, hand Discharge Coefficient ments of FM's Loss Prevention Data K=2.8 GPM/psi1I2 (40,3 LPM/bar"2) Sheets). Only the Style 10, 20, 30, or tighten the sprinkler into the sprinkler K=4.2 GPM/psi112 (60,5 LPM/bar1/2) 40 Recessed Escutcheon,as applica- fitting. K=5.6 GPM/psi112 (80,6 LPM/bar1/2) ble,is to be used for recessed pendent Step 3. Tighten the sprinkler into the K=8.0 GPM/psi112 (115,2 LPM/bar1/2) installations. sprinkler fitting using only the W-Type 6 Sprinkler Wrench(Figure 14).With refer- Temperature Rating installation ence to Figures 1 through 5,apply the Refer to Table A and B. W-Type 6 Sprinkler Wrench to the sprin- The TYCO Series TY-FRB, 2.8, 4.2, kler wrench flats. Finishes 5.6,and 8.0 K-factor, Upright,Pendent, Sprinkler: Refer to Table A and B. and Recessed Pendent Sprinklersmust Series TY-FRB Recessed Pendent Recessed Escutcheon:White Coated, be installed in accordance with this Sprinklers Chrome Plated,or Brass Plated. section. The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor- Physical Characteristics General Instructions dance with the following instructions. Frame Bronze Do not install any bulb-type sprinkler if Button Brass/Copper the bulb is cracked or there is a loss Step A.After installing the Style 10,20, Sealing Assembly Beryllium of liquid from the bulb.With the sprin- 30, or 40 Mounting Plate, as applica- Nickel w/TEFLON kler held horizontally, a small air bub- ble,over the sprinkler threads and with Bulb Glass ble should be present. The diameter pipe-thread sealant applied to the pipe Compression Screw Bronze of the air bubble is approximately 1/16 threads,hand-tighten the sprinkler into Deflector Copper/Bronze inch(1,6 mm)for the 135°F(57°C)and the sprinkler fitting. Bushing(K=2.8) Bronze 3/32 inch(2,4 mm)for the 286°F(141°C) Step B. Tighten the sprinkler into the Operation temperature ratings. sprinkler fitting using only the W-Type ~ A leak-tight 1/2 inch NPT sprinkler joint 7 Recessed Sprinkler Wrench (Figure The glass bulb contains a fluid that shold be obtained by applying a min- 15). With reference to Figures 1 to 4, expands when exposed to heat.When imum to maximum torque of 7 to 14 apply the W Type 7 Recessed Sprinkler the rated temperature is reached, the ft.l-bs. (9,5 to 19,0 Nm). Higher levels Wrench to the sprinkler wrench flats. fluid expands sufficiently to shatter the of torque can distort the sprinkler Inlet Step C. After ceiling installation and glass bulb, allowing the sprinkler to with consequent leakage or impairment finishing,slide on the Style 10,20,30, activate and water to flow. of the sprinkler. or 40 Closure over the Series TY-FRB Do not attempt to compensate for Sprinkler and push the Closure over the insufficient adjustment in the Escutch- Mounting Plate until its flange comes in eon Plate by under-or over-tightening contact with the ceiling. • . TFP171 Page 5 of 10 SPRINKLER FINISH(See Note 5) K BULB LIQUID NATURAL CHROME SIGNAL*** FACTOR TYPE TEMPERATURE COLOR BRASS PLATED WHITE 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY1231) and 175°F(79°C) Yellow 1,2,3,4 UPRIGHT ° ° 200 F 93 C (TY1131) ( ) Green 286°F(141°C) Blue 135°F(57°C) Orange 2.8 RECESSED 1 1/2"NPT PENDENT 155°F(68°C) Red (TY1231)* 175°F(79°C) Yellow Figure 6 200°F(93°C) Green 1,2,4 135°F(57°C) Orange RECESSED ° ° 155 F(68°C) Red PENDENT ( ) (TY1231)** 175°F(79°C) Yellow Figure 7 — 200°F(93°C) Green 135°F(57°C) Orange — PENDENT 155°F(68°C) Red (TY2231) and 175°F(79°C) Yellow UPRIGHT (TY2131) 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 4.2 RECESSED 1/2"NPT PENDENT 155°F(68°C) Red 1,2 (TY2231)* 175°F(79°C) Yellow Figure 8 200°F(93°C) Green 135°F(57°C) Orange RECESSED ° ° 155 F 68 C PENDENT ( ) Red (TY2231)** 175°F(79°C) Yellow Figure 9 200°F(93°C) Green NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. "Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT) 1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only.Listings and approvals apply to color(Special Order). N/A:Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS • TFP171 Page 6 of 10 SPRINKLER FINISH(See Note 8) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME SIGNAL*** LEAD FACTOR COLOR BRASS PLATED WHITE COATED 135°F(57°C) Orange PENDENT (TY3231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,3,5 UPRIGHT 200°F(93°C) Green (TY3131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 N/A 1/2'NPT (TY3231) Figure 10 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,4,5 N/A (TY3231) Figure 11 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT (TY4231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5 UPRIGHT 200°F(93°C) Green (TY4131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 8.0 PENDENT 175°F(79°C) Yellow 1,2,5 N/A 3/4"NPT (TY4231)* Figure 12 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,5 N/A (TY4231) Figure 13 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT 155°F(68°C) Red 8.0 (TY4931) 1/2"NPT and 175°F(79°C) Yellow 1,2,4,5,6 1,2,5 UPRIGHT 200°F(93°C) Green (TY4831) 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. *Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. **Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT) 1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only.Listings and approvals apply to color(Special Order). N/A:Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS • • TFP171 Page 7 of 10 _ SPRINKLER FINISH K TYPE NATURAL CHROME SIGNAL LEAD FACTOR BRASS PLATED WHITE COATED PENDENT(TY1231) and 2.8 UPRIGHT(TY1131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY1231) PENDENT(TY2231) and UPRIGHT(TY2131) 4.2 175 PSI(12,1 BAR) N/A 1/2"NPT RECESSED PENDENT(TY2231) PENDENT(TY3231) 175 PSI and UPRIGHT(TY3131) 250 PSI(17,2 BAR) (12,1 BAR) 5.6 OR 175 PSI(12,1 BAR) 1/2"NPT RECESSED (SEE NOTE 1) PENDENT(TY3231) N/A PENDENT(TY4231) 175 PSI and (12,1 BAR) UPRIGHT(TY4131) 8.0 -3/4"NPT 175 PSI(12,1 BAR) - RECESSED N/A • PENDENT(TY4231) 8 0 PENDENT(TY4931) 175 PSI 1/2"NPT and 175 PSI(12,1 BAR) (12,1 BAR) UPRIGHT(TY4831) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE Care and corrosive products of combustion,but tion Service in accordance with local have not operated,should be replaced requirements and/or national codes. Maintenance if they cannot be completely cleaned Care must be exercised to avoid dam- by wiping the sprinkler with a cloth or age to the sprinklers -before, during, The TYCO Series TY-FRB must be by brushing it with a soft bristle brush. and after installation.Sprinklers dam- maintained and serviced in accordance Care must be exercised to avoid dam- aged by dropping, striking, wrench with this section. age to the sprinklers- before, during, twist/slippage, or the like, must be Before closing a fire protection system and after installation.Sprinklers dam- replaced. Also, replace any sprinkler main control valve for maintenance aged by dropping, striking, wrench that has a cracked bulb or that has lost work on the fire protection system twist/slippage, or the like, must be liquid from its bulb. (Ref. Installation that it controls, obtain permission to replaced. Also, replace any sprinkler Section). shut down the affected fire protection that has a cracked bulb or that has lost Initial and frequent visual inspections of systems from the proper authorities liquid from its bulb. (Ref. Installation random samples are recommended for and notify all personnel who may be Section.) corrosion-resistant sprinklers to verify affected by this action. The owner is responsible for the the integrity of the corrosion-resistant Absence of the outer piece of an inspection,testing,and maintenance of material of construction. Thereafter, escutcheon, which is used to cover their fire protection system and devices annual inspections per NFPA 25 should a clearance hole, can delay sprinkler in compliance with this document,as suffice. operation in a fire situation. well as with the applicable standards Inspections of corrosion-resistant P • of the National Fire Protection Associa- Sprinklers sprinklers are recommended at close Sprinklers which are found to be leak- tion (e.g., NFPA 25), in addition to the p ing or exhibiting visible signs of corro- standards of any other authorities hav- range, instead of from the floor level sion must be replaced. ing jurisdiction. Contact the installing per NFPA. Inspection at close range contractor or sprinkler manufacturer can better determine the exact sprin- Automatic sprinklers must never be p kler condition and the long-term integ- painted, plated, coated, or other- regarding any questions. rity of the corrosion-resistant material, wise altered after leaving the factory. Automatic sprinkler systems are rec- which can be affected by the corrosive Modified sprinklers must be replaced. ommended to be inspected, tested, conditions present. Sprinklers that have been exposed to and maintained by a qualified Inspec- . I TFP171 Page 8 of 10 2-7/8"DIA. _ 2-7/8"DIA. - 5/811/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7 mm 1/2±1/8" ( mm) (15,9±6,4 mm) "1/4"(6,4 mm) (12,7±3,2 mm) 1/4 (6,4 mm 2-1/4"DIA. 2-1/4"DIA. ( mm) / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" _ / 1/8" (3,2 mm) ,iH( (3,2mm) l P77 . _14 MOUNTING I SURFACE qv SURFACE �• I • CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 6 FIGURE 7 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. _ 2-7/8"DIA. _ 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7 mm 1/211/8" ( mm) (15,9±6,4 mm) "1/4 1/4"(6,4 mm) (12,7±3,2 mm) (6,4 mm 2-1/4"DIA. 2-1/4"DIA. ( mm) / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" / 1/8" (3,2 mm) (3,2 mm) '1-! MOUNTING 10r MOUNTING SURFACE SURFACE r CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT . • TFP171 Page 9 of 10 2-7/8"DIA. _ 2-7/8"DIA. 5/811/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7 mm 1/231/8" ( mm) (15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) (6,4 mm 2-1/4"DIA. 2-1/4"DIA. 1/4"( mm) / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING I 1/8"(3 ,2 mm) (3,2 mm) MO\UNTINdG 7/- L i l,_-I 47 iv, ■ MOUNTING 1Ip 111. .. SURFACE _;_ SURFACE +II ' CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 2-7/8"DIA. _ 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) • (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" (3,2 mm) / (3,2 mm) >r -r yr I a • % -77-/� �- ird MOUNTING II�MOUNTING �. SURFAC .SURFACE CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 12 FIGURE 13 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 INCH NPT 8.0 K-FACTOR, 3/4 INCH NPT Cl WRENCH RECESS WRENCH RECESS (END"A" USED FOR sFr ...../..../ 1/2" NPT MODELS) WRENCH RECESS (END"B"USED FOR PUSH WRENCH 3/4"NPT MODELS) IN TO ENSURE ENGAGEMENT - WITH SPRINKLER WRENCHING AREA FIGURE 14 FIGURE 15 W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED WRENCH SPRINKLER WRENCH TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C) 331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 155 155°F(68°C) (RAL9010)' 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F(79°C) (RAL9003) 341 4.2K PENDENT(1/2"NPT) TY2231 7 LEAD COATED 200 200°F(93°C) 370 5.6K UPRIGHT(1/2"NPT) TY3131 9 CHROME PLATED 286 286°F(141°C) 371 5.6K PENDENT(1/2"NPT) TY3231 X JET BLACK (RAL9005)" 390 8.0K UPRIGHT(3/4"NPT) TY4131 'Eastern Hemisphere sales only. Available in only 2.8K,4.2K,and 8.0K,155°F(68°C)and 200°F(93°C); 391 8.0K PENDENT(3/4"NPT) TY4231 requires lead time to manufacture. 360 8.0K UPRIGHT(1/2"NPT) TY4831' 361 8.0K PENDENT(1/2"NPT) TY4931' TABLE D SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB(Specify SIN), (specify K-factor), (specify Pendent or Upright) Sprinkler (specify) tempera- ture rating, (specify)finish or coating, P/N(specify from Table D). Recessed Escutcheon: Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify*) finish, P/N (specify*). Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. *Refer to Technical Data Sheet TFP770. GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446(Telephone+1-215-362-0700 Copyright C 2013 Tyco Fire Products,LP. All rights reserved. t Co TEFLON is trademark of The DuPont Corporation. . . CO Worldwide Contacts www.tyco-fire.corn Series TY-FRB — 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General tamed when exposed to corrosive at- mospheres. Although corrosion resis- Descr� tion tant coated sprinklers have passed the p standard corrosion tests of the appli- The Series TY-FRB, 5.6 K-factor, Hor cable approval agencies,the testing is izontal and Vertical Sidewall Sprin- not representative of all possible cor- .. - - klers described in this data sheet rosive atmospheres. Consequently, it / j is recommended that the end user be 111 are quick response -standard cover- , • IA age, decorative 3 mm glass bulb type consulted with respect to the suitabil- �� spray sprinklers designed for use in ity of these coatings for any given cor- ,;:, light and ordinary hazard, commer rosive environment.The effects of am- cial occupancies such as banks, ho- bient temperature, concentration of �f tels,shopping malls,etc.They are de chemicals,and gas/chemical velocity, signed for installation along a wall or should be considered, as a minimum, the side of a beam and just beneath a along with the corrosive nature of the smooth ceiling.Sidewall sprinklers are chemical to which the sprinklers will commonly used instead of pendent or be exposed. upright sprinklers due to aesthetics or NOTICE building construction considerations, - where piping across the ceiling is not The Series TY-FRB Sprinklers de- desirable. scribed herein must be installed and � The recessed version of the Series maintained in compliance with this / TY-FRB Horizontal Sidewall Sprin- document, as well as with the appli- fl kler is intended for use in areas with cable standards of the National Fire a finished wall. It uses a two-piece Protection Association, in addition to # 11111 III Style 10 Recessed Escutcheon with the standards of any other authorities 0: . 1/2 inch(12,7 mm)of recessed adjust- having jurisdiction. Failure to do so ment or up to 3/4 inch(19,1 mm)of to- may impair the performance of these i �---' tal adjustment from the flush sidewall devices. • position, or a two-piece Style 20 Re- The owner is responsible for maintain- cessed Escutcheon with 1/4 inch (6,4 ing their fire protection system and - mm) of recessed adjustment or up to devices in proper operating condition. 1/2 inch (12,7 mm)of total adjustment The installing contractor or sprinkler from the flush sidewall position. The manufacturer should be contacted adjustment provided by the Recessed with any questions. Technical Escutcheon reduces the accuracy to which the fixed pipe nipples to the Sprinkler Data sprinklers must be cut. Corrosion resistant coatings, where Identification Approvals applicable, are utilized to extend the UL and C-UL Listed. life of copper alloy sprinklers beyond Numbers FM, LPCB,and NYC Approved. that which would otherwise be ob- (Refer to Table A for complete approv- TY3331 -Horizontal al information including corrosion re- TY3431 -Vertical sistant status.) IMPORTANT Maximum Working Pressure Always refer to Technical Data Refer to Table B. Sheet TFP700 for the "INSTALLER WARNING" that provides cautions Discharge Coefficient with respect to handling and instal- K=5.6 GPM/psi112(80,6 LPM/bar1i2) lation of sprinkler systems and com- Temperature Ratings ponents.Improper handling and in- Refer to Table A. stallation can permanently damage a sprinkler system or its compo- Finishes nents and cause the sprinkler to fail Sprinkler: Refer to Table A. to operate in a fire situation or cause Recessed Escutcheon:Signal or it to operate prematurely. Pure White,Chrome Plated,or Brass Plated. Page 1 of 6 MARCH 2013 TFP176 • • TFP176 Page 2 of 6 1 Frame DEFLECTOR Installation 2 - Button HAT ` 5 4i17'diD.d'e The Series TY-FRB,5.6 K-factor, Hori- 3 - Sealing —Ai, zontal and Vertical Sidewall Sprinklers Assembly ( must be installed in accordance with 4 - Bulb ►y �,�� this section. 5 Compression General Instructions Screw 6 - Deflector* 6*/ 4 2 3 1 Do not install any bulb type sprin- kler if the bulb is cracked or there is WRENCH 1/2"** m (14,3 mm) FLATS NPT a loss of liquid from the bulb.With the 9/1 sprinkler held horizontally, a small air I bubble should be present. The diam- . �' / eter of the air bubble is approximately il pr. �7■ / } rill I 1/16 inch(1,6 mm)for the 135°F(57°C) �'O`� + ~�I I' to 3/32 inch (2,4 mm) for the 286°F 11 (141°C)temperature ratings. m' - A leak tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 1-13/16" 7/16" to 14 ft.-lbs. (9,5 to 19,0 Nm). A maxi- ~(46,0 mm) (11,1 mm) f mum of 21 ft.-lbs.(28,5 Nm)of torque CENTERLINE NOMINAL may be used to install sprinklers with OF SPRINKLER MAKE-IN 1/2 NPT connections. Higher levels of WATERWAY torque may distort the sprinkler and 1-1/2" cause leakage or impairment of the –(38,1 mm) sprinkler. *Temperature rating Do not attempt to make-up for insuf- is indicated on - 2-3/16" ~ Deflector. (55,6 mm)— ficient adjustment in the escutcheon ESCUTCHEON plate by under-or over-tightening the STYLE sprinkler. Readjust the position of the ** Pipe P thread ■ 10 or 20 PLATE SEATING sprinkler fitting to suit. • connections per RECESSED SURFACE ISO 7-1 can be ESCUTCHEON I Series TY-FRB Horizontal and li provided on Vertical Sidewall Sprinkler special request. _.� Installation ,a111 71 2-7/8"DIA. I The Series TY-FRB Horizontal and (73,0 mm) r411111 Vertical Sidewall Sprinklers must be installed in accordance with the fol- lowing instructions. Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal po- sition with their centerline of waterway perpendicular to the back wall and parallel to the ceiling.The word "TOP" FIGURE 1 on the Deflector is to face towards the 5.6 K-FACTOR QUICK RESPONSE ceiling. SERIES TY-FRB HORIZONTAL SIDEWALL(TY3331)SPRINKLERS Vertical sidewall sprinklers are to be installed in the pendent or upright po- Physical Characteristics sition with the arrow on the Deflector Design pointing away from the wall. Frame Bronze Button Brass/Copper Criteria Step 2. With pipe thread sealant ap- Sealing Assembly Beryllium plied to the pipe threads, hand tighten Nickel w/TEFLON The Series TY-FRB,5.6 K-factor, Hori- the sprinkler into the sprinkler fitting. Bulb Glass zontal and Vertical Sidewall Sprinklers Step 3. Tighten the sprinkler into the Compression Screw Bronze are intended for fire protection sys sprinkler fitting using only the W-Type HSW Deflector Bronze terns designed in accordance with the 6 Sprinkler Wrench (Ref. Figure 5), W- VSW Deflector Copper standard installation rules recognized With reference to Figure 1 or 2,the W- by the applicable Listing or Approval Type 6 Sprinkler Wrench is to be ap- Oeration agency (e.g., UL Listing is based on plied to the wrench flats. p the requirements of NFPA 13, and FM The glass bulb contains a fluid which Approval is based on the requirements expands when exposed to heat.When of FM's Loss Prevention Data Sheets). - the rated temperature is reached, the Only the Style 10 or 20 Recessed Es- fluid expands sufficiently to shatter cutcheon,as applicable, is to be used the glass bulb, allowing the sprinkler for recessed horizontal installations. to activate and water to flow. V • TFP176 Page 3 of 6 Series TY-FRB Recessed *Temperature ** Pipe thread 1 - Frame 4 - Bulb 7 - Ejection Horizontal Sidewall Sprinkler rating is connections 2 - Button 5 - Compression Spring Installation indicated on per ISO 7-1 can 3 - Sealing Screw The Series TY-FRB Recessed Hori- Deflector. be provided on Assembly 6 - Deflector* zontal Sidewall Sprinklers must be special request. installed in accordance with this ARROW MUST section. POINT AWAY �4 ilit Step A. Recessed horizontal sidewall 7/16" FROM AND BE s • prinklers are to be installed in the ESCUTCHEON (11,1 mm) PERPENDICULAR O horizontal position with their center- PLATE SEATING NOMINAL TO THE BACK 4 line of waterway perpendicular to the SURFACE 1/2** MAKE-IN WALL SURFACE back wall and parallel to the ceiling. The word "TOP"on the Deflector is to 6* face towards the ceiling. + — J �$._ 40 Step B.After installing the Style 10 or I FLOW'°`—5 20 Mounting sprinkler 0 ounting Plate over the sp e threads,hand tighten the sprinkler into 2-3/16" du �� 2-3/16" I 4 the sprinkler fitting. (55,6 mm) i ' (55,6 mm) yr Step C. Tighten the sprinkler into the 1-1/2" \ / If 2 sprinkler fitting using only the W-Type (38,1 mm) 1 WRENCH II ._. •••• 7 7 Recessed Sprinkler Wrench (Ref. FLATS 3 Figure 6). With reference to Figure z�•�s _ i ¢• 1, the W-Type 7 Recessed Sprinkler 1 Wrench is to be applied to the sprin- SHOWN SHOWN CROSS kler wrench flats. PENDENT UPRIGHT SECTION Step D. After the ceiling has been in- FIGURE 2 - stalled or the finish coat has been ap- 5.6 K-FACTOR QUICK RESPONSE plied, slide on the Style 10 or 20 Clo- SERIES TY-FRB VERTICAL SIDEWALL(TY3431)SPRINKLERS sure over the Series TY-FRB Sprinkler and push the Closure over the Mount- . if they cannot be completely cleaned The owner is responsible for the in- tacPlate until its flange comes in con- by wiping the sprinkler with a cloth or spection, testing, and maintenance tact with the ceiling. by brushing it with a soft bristle brush. of their fire protection system and de- Care must be exercised to avoid darn- age vices in compliance with this docu- Care and to the sprinklers -before, during, ment, as well as with the applicable standards of the National Fire Pro- Maintenance and after installation. Sprinklers dam- aged by dropping, striking, wrench tection Association (e.g., NFPA 25), in The Series TY-FRB,5.6 K-factor, Hori- twist/slippage, or the like, must be addition to the standards of any oth- zontal and Vertical Sidewall Sprinklers replaced. Also, replace any sprinkler er authorities having jurisdiction. The p that has a cracked bulb or that has installing contractor or sprinkler man- must be maintained and serviced in ufacturer should be contacted relative accordance with this section. lost liquid from its bulb. (Ref. Installa- tion Section). to any questions. Before closing a fire protection sys- It is recommended that automatic tern main control valve for mainte- The owner must assure that the sprin- sprinkler systems be inspected, test- nance work on the fire protection sys- klers are not used for hanging of any ed, and maintained by a qualified In- tern that it controls,permission to shut objects; otherwise, non-operation in spection Service in accordance with down the affected fire protection sys- the event of a fire or inadvertent op local requirements and/or national tern must be obtained from the prop- eration may result. codes. er authorities and all personnel who Frequent visual inspections are rec- may be affected by this action must ommended to be initially performed be notified. for corrosion resistant coated sprin- Absence of an escutcheon, which is klers, after the installation has been used to cover a clearance hole, may completed,to verify the integrity of the delay the time to sprinkler operation in corrosion resistant coating. Thereaf- a fire situation. ter, annual inspections per NFPA 25 should suffice; however, instead of in- Sprinklers that are found to be leaking specting from the floor level,a random or exhibiting visible signs of corrosion sampling of close-up visual inspec- must be replaced. tions should be made, so as to better - Automatic sprinklers must never be determine the exact sprinkler condi- painted, plated, coated or other- tion and the long term integrity of the wise altered after leaving the factory. corrosion resistant coating, as it may Modified sprinklers must be replaced. be affected by the corrosive condi- - Sprinklers that have been exposed to tions present. corrosive products of combustion,but have not operated,should be replaced • • TFP176 Page 4 of 6 y 5/8±1/4" e�' - (15,9±6,4 mm) MOUNTING FACE OF / WRENCH RECESS SPRINKLER (END"A" USED FOR SURFACE FITTING 1/2" NPT MODELS) 4 CLOSURE FIGURE 5 W-TYPE 6 SPRINKLER WRENCH �` 2-7/8"DIA. M (73,0 mm) SERIES I.� 2.1/4"DIA. WRENCH Ty-FRB 'lam., iliT (57,2 mm) RECESS MOUNTING M PLATE I% 4 1/8" (3,2 mm) PUSH WRENCH 1-1/4"(31,8 mm) 3/4"(19,1 mm) IN TO ENSURE 3/4"(19,1 mm) ~ 1/4"(6,4 mm) ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 FIGURE 6 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER W-TYPE 7 RECESSED WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT SPRINKLER WRENCH STYLE 10 RECESSED ESCUTCHEON 1/2±1/8" (12,7±3,2 mm) MOUNTING FACE OF SURFACE '`-- SPRINKLER FITTING 4 CLOSURE A I ,,._ 2-7/8"DIA. SERIES Ii,- II (73,0 mm) TY FRB IIIII (57,21 mm) MOUNTING 1 PLATE I '� ' /1 1/8" (3,2 mm) 1-1/4"(31,8 mm) 1/2"(12,7 mm) 1"(25,4 mm) 1/4"(6,4 mm) FIGURE 4 " SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON TFP176 Page 5 of 6 SPRINKLER FINISH(See Note 11) K TYPE TEMP. BULB NATURAL CHROME SIGNAL LEAD COATED LIQUID BRASS PLATED WHITE*** 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 175°F(79°C) Yellow 1,2,3,4,9, 10 1,2,3,9 1,2,3,9 (TY3331) 200°F(93°C) Green 286°F(141°C) Blue 5.6 RECESSED 135°F(57°C) Orange 1/2" HORIZ. 155°F(68°C) Red NPT SIDEWALL — 1,2,4,9,10 1,2,9 N/A (TY3331)* 175°F(79°C) Yellow Figure 3 200°F(93°C) Green RECESSED 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 1,2,3,4,9 N/A (TY3331)** 175°F(79°C) Yellow Figure 4 200°F(93°C) Green VERTICAL 135°F(57°C) Orange SIDEWALL 155°F(68°C) Red 5.6 (TY3431) 1/2" Installed 175°F(79°C) Yellow 5,6,7,8,9 5,6,7,9 NPT Pendent ° ° 200 F 93 C or ( ) Green Upright 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.(UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 2. Listed by Underwriters Laboratories Inc.for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007a/04)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5. Listed by Underwriters Laboratories,Inc.as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies. 8. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06&007a/04)as Quick Response Sprinklers. 9. Approved by the City of New York under MEA 354-01-E. 10. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resis- tant Sprinklers.Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. •Installed with Style 10(1/2"NPT)3/4"Total Adjustment Recessed Escutcheon. **Installed with Style 20(1/2"NPT)1/2"Total Adjustment Recessed Escutcheon. "*Frame and deflector only.Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS TFP176 Page 6 of 6 SPRINKLER FINISH K TYPE NATURAL BRASS CHROME PLATED WHITE POLYES- LEAD COATED TER HORIZONTAL SIDEWALL 250 PSI(17,2 BAR) 175 PSI(12,1 BAR)or ( ) 175PSI(12,1 BAR) 5.6 RECESSED HORIZ. 1/2 SIDEWALL(TY3331) (SEE NOTE 1) N/A NPT VERTICAL SIDEWALL 175 PSI(12,1 BAR) (TY3431) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories,Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE B MAXIMUM WORKING PRESSURE P/N 57 -XXX-X-XXX I I S/N Sprinkler TEMPERATURE RATING 378 HORIZONTAL SIDEWALL TY3331 1 Natural Brass 375 VERTICAL SIDEWALL TY3431 3 Pure White(RAL 9010)' 135 135°F(57°C) 155 155°F(68°C) 4 Signal White(RAL9003) 175 175°F(79°C) X Jet Black(RAL9005)" 200 200°F(93°C) 7 Lead Coated 286 286°F(141°C) 9 Chrome Plated 'Eastern Hemisphere sales only Available in 155°F (68°C) or 200°F(93°C)temperature rat- ing only. TABLE C PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS Ordering Recessed Escutcheon: Specify:Style(10 or 20) Recessed Es- Procedure cutcheon with (specify") finish, P/N (specify"). Contact your local distributor for avail- ability. When placing an order, indi- cate 'Refer to Technical Data Sheet TFP770. the full product name and Part Sprinkler Wrench: Number(P/N). Sprinkler Assemblies with NPT Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Thread Connections: Specify: W-Type 7 Sprinkler Wrench, Specify: Series TY-FRB(specify SIN), P/N 56-850-4-001. (specify K-factor), (specify) Horizontal Sidewall or Vertical Sidewall Sprinkler, Standard Response, Standard Cov- erage, (specify) temperature rating, (specify) finish or coating, P/N (spec- ify from Table C) GLOBAL HEADQUARTERS I 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. tqCO ti,iD Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Pendent Wet Pipe and Dry Pipe Systems General Escutcheon reduces the accuracy to which the pipe drops to the sprinklers Description must be cut. The Series LFII Residential Sprinklers The TYCO RAPID RESPONSE Series have been designed with heat sensi- LFII Residential Pendent and Recessed tivity and water distribution charac- ' Pendent Sprinklers(TY2234)are deco- teristics proven to help in the control rative, fast response, frangible bulb of residential fires and to improve the sprinklers designed for use in residen- chance for occupants to escape or be tial occupancies such as homes,apart- evacuated. ments, dormitories, and hotels. When aesthetics and optimized flow charac- Dry Pipe System Application teristics are the major consideration, The Series LFII Residential Pendent - the Series LFII Residential Sprinklers and Recessed Pendent Sprinklers (TY2234) should be the first choice. offers a laboratory approved option for The Series LFII Residential Sprinklers designing dry pipe residential sprinkler are intended for use in the following systems, whereas, most residential The owner is responsible for main- scenarios: sprinklers are laboratory approved for taming their fire protection system and wet systems only. devices in proper operating condition. • wet and dry pipe residential sprin- Through extensive testing, it has been The installing contractor or sprinkler kler systems for one-and two-family determined that the number of design manufacturer should be contacted with dwellings and mobile homes per any questions. sprinklers (hydraulic design area) for NFPA 13D the Series LFII Residential Pendent and • wet and dry pipe residential sprinkler Recessed Pendent Sprinklers(TY2234) Sprinkler systems for residential occupancies need not be increased over the number up to and including four stories in of design sprinklers(hydraulic design Identification height per NFPA 13R area)as specified for wet pipe sprinkler • wet and dry pipe sprinkler systems systems,as is accustomed for density/ Number (SIN) area sprinkler systems designed per for the residential portions of any NFPA 13. TY2234 occupancy per NFPA 13 Consequently, the Series LFII The recessed version of the Series Residential Sprinklers offer the features LFII Residential Sprinklers is intended of non-water filled pipe in addition to for use in areas with finished ceilings. not having to increase the number of It employs a two-piece Style 20 design sprinklers (hydraulic design Recessed Escutcheon. The Recessed area) for systems designed to NFPA Escutcheon provides 1/4 inch (6,4 13, 13D, or 13R. Non-water filled pipe mm) of recessed adjustment or up to will permit options for areas sensitive 1/2 inch (12,7 mm) of total adjustment to freezing. from the flush ceiling position. The adjustment provided by the Recessed NOTICE The Series LFII Residential Pendent and Recessed Pendent Sprinklers(TY2234) IMPORTANT described herein must be installed and Always refer to Technical Data maintained in compliance with this Sheet TFP700 for the "INSTALLER document and the applicable stan- WARNING" that provides cautions dards of the National Fire Protection • with respect to handling and instal- Association, in addition to the standards lation of sprinkler systems and of any authorities having jurisdiction. components. Improper handling and Failure to do so may impair the perfor installation can permanently damage mance of these devices. a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 APRIL 2013 TFP400 TFP400 . Page 2 of 6 7/16"(11,1 mm) 1/2„ ESCUTCHEON Components: NOMINAL NPT PLATE SEATING 2-7/8"DIA. 1 - Frame MAKE IN SURFACE (73,0 mm) 2 - Button 1 3 - Sealing Assembly 1 $64 4 Bulb 1 ._ ________- 5 Screwression 2 2- /4" I■r 6 Deflector' ,..,.1, i (57,2 mm) ∎M 1Ip 4 I ' 1-5/8" 11111 STYLE 20 413 mm WRENCH RECESSED *Temperature 5 jai . I FLATS ■ ESCUTCHEON rating is �.� _ it 6*indicated on Deflector. CROSS SECTION PENDENT RECESSED PENDENT FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) 2-7/8"DIA. Gl _ 7/16±1/8" (73,0 mm) 1/2"(12,7 mm) (11,1±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) WRENCH RECESS FACE OF (57,2 mm) (END"A" USED SPRINKLER MOUNTING FOR TY2234) FITTING PLATE '.../ .41 FIGURE 3 W-TYPE 6 ����' ��� SPRINKLER WRENCH f,//i. ■fir 1 � , MOUNTING t WRENCH SURFACE IP 1/8" RECESS (3,2 mm) CLOSURE TY2234 1-3/8"(34,9 mm) i 1-1/8"(28,6 mm) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER .."..' (TY2234) PUSH WRENCH IN TO ENSURE Technical Temperature Rating ENGAGEMENT 155°F(68°C)or 175°F(79°C) WITH SPRINKLER Data Finishes WRENCHING AREA Natural Brass FIGURE 4 Approvals Pure or Signal White W-TYPE 7 RECESSED UL Listed for use with wet pipe and Chrome Plated SPRINKLER WRENCH dry pipe systems Physical Characteristics C-UL Listed for use only with wet pipe Frame Brass systems Button Copper NSF Certified to NSF/ANSI 61 Sealing Assembly Beryllium Nickel w/TEFLON For details on these approvals,refer Bulb(3 mm) Glass to the Design Criteria section. Compression Screw Bronze Maximum Working Pressure Deflector Bronze 175 psi(12,1 bar) Ejection Spring Stainless Steel Discharge Coefficient K=4.9 GPM/psi112(70,6 LPM/bar1/2) TFP400 . Page 3 of 6 Operation Hydraulic Design Installation (NFPA 13) The glass bulb contains a fluid that For systems designed to NFPA 13, The TYCO RAPID RESPONSE expands when exposed to heat.When the number of design sprinklers is Series LFII Residential Pendent the rated temperature is reached,the to be the four most hydraulically and Recessed Pendent Sprinklers fluid expands sufficiently to shatter the demanding sprinklers.The minimum (TY2234) must be installed in accor- glass bulb, allowing the sprinkler to required discharge from each of the dance with this section: activate and flow water. four sprinklers is to be the greater of the following: General Instructions Design • The flow rates given in Tables A Do not install any bulb type sprin- or B as a function of temperature kler if the bulb is cracked or there is a Criteria rating and the maximum allowable loss of liquid from the bulb. With the coverage area. sprinkler held horizontally,a small air The TYCO RAPID RESPONSE • A minimum discharge of 0.1 gpm/ft2 bubble should be present.The diam- Series LFII Residential Pendent over the "design area" comprised eter of the air bubble is approximately and Recessed Pendent Sprinklers 1/16 inch(1,6 mm). (TY2234)are UL and C-UL Listed for of the four most hydraulically installation in accordance with this demanding sprinklers for actual A leak-tight 1/2 inch NPT sprinkler section. coverage areas protected by the joint should be obtained by applying four sprinklers. a minimum-to-maximum torque of 7 Residential Sprinkler Design Guide to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher P 9 The number of "design sprinklers" When conditions exist that are specified in NFPA 13 for wet pipe levels of torque can distort the ge or outside the scope of the provided systems is to be applied when kler Inlet with consequent leakage or criteria, refer to the Residential designing dry pipe systems. impairment of the sprinkler. Sprinkler Design Guide TFP490 for Do not attempt to compensate the manufacturer's recommendations Dry Pipe System Water Delivery for insufficient adjustment in an that may be acceptable to the local When using the Series LFII Residential Escutcheon Plate by under- or over- authority having jurisdiction. Sprinklers(TY2234)in dry pipe sprin- tightening the sprinkler.Re-adjust the kler systems, the time for water position of the sprinkler fitting to suit. System Types delivery must not exceed 15 seconds Per the UL Listing, wet pipe and dry for the most remote operating Series LFII Residential Pendent pipe systems may be utilized. Per the sprinkler. Sprinklers C-UL Listing, only wet pipe systems The Series LFII Residential Pendent may be utilized. Obstruction to Water Distribution Sprinklers must be installed in accor- Refer to Technical Data Sheet TFP485 Sprinklers are to be located in accor- dance with the following instructions. for the use of residential sprinklers in dance with the obstruction rules Step 1. Install pendent sprinklers in residential dry pipe systems. of NFPA 13D, 13R, and 13 as appli- the pendent position with the deflector cable for residential sprinklers as parallel to the ceiling. Ceiling Types well as with the obstruction criteria Smooth flat horizontal, or beamed, or described within the Technical Data Step 2. With pipe thread sealant sloped, in accordance with the 2013 Sheet TFP490. applied to the pipe threads, hand- Edition of NFPA 13D, 13R, or 13 as tighten the sprinkler into the sprinkler applicable. Operational Sensitivity fitting. Sprinklers are to be installed with a Step 3. Tighten the sprinkler into Hydraulic Design deflector-to-ceiling distance of 1-1/4 to the sprinkler fitting using only the (NFPA 13D and 13R) 4 inches. W-Type 6 Sprinkler Wrench (Figure For systems designed to NFPA 3). With reference to Figure 1, apply 13D or NFPA 13R, the minimum Sprinkler Spacing the W-Type 6 Sprinkler Wrench to the required sprinkler flow rates are The minimum spacing between sprin- wrench flats. given in Tables A and B as a func- klers is 8 feet (2,4 m).The maximum tion of temperature rating and the spacing between sprinklers cannot Series LFII Residential Recessed maximum allowable coverage areas. exceed the length of the coverage Pendent Sprinklers The sprinkler flow rate is the minimum area(Table A or B)being hydraulically The Series LFII Residential Recessed required discharge from each of the calculated(e.g.,maximum 12 feet for a Pendent Sprinklers must be installed total number of"design sprinklers"as 12 ft.x 12 ft.coverage area,or 20 feet in accordance with the following specified in NFPA 13D or NFPA 13R. for a 20 ft. x 20 ft.coverage area). instructions. The number of "design sprinklers" specified in NFPA 13D and 13R for wet Step A. Install recessed pendent pipe systems is to be applied when sprinklers in the pendent position with designing dry pipe systems. the deflector parallel to the ceiling. Step B. After installing the Style 20 Mounting Plate over the sprinkler - threads and with pipe thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. (Continued on Page 5) TFP400 Page 4 of 6 . WET PIPE SYSTEM Minimum Flow and Residual Pressurelb,c) Max. Coverage Ordinary Temp.Rating Intermediate Temp.Rating Area(a) 155°F(68°C) 175°F(79°C) Minimum Deflector to Installation Spacing Ft.x Ft. Flow Pressure Flow Pressure Ceiling Type Ft. (m x m) GPM PSI GPM PSI (m) (L/min) (bar) (L/min) (bar) 12 x 12 13 7.0 13 7.0 Smooth (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings 1-1/4 to 14x14 13 7.0 13 7.0 inches nc (4,3 x 4,3) (49,2) (0,48) (49,2) (0,48) hee s Recessed Beamed using Style 20 16 x 16 13 7.0 13 7.0 Ceilings per Escutcheon or 8 (4,9 x 4,9) (49,2)49,2) (0,48)0,48) (49,2) (0,48)0,48 NFPA 13D non-recessed r2.t 18 x 18 17 12.0 17 12.0 or 13R per NFPA 13D, (5,5 x 5,5) (64,3) (0,83) (64,3) (0,83) 1-1/4 to 1-3/4 13R,or 13 inches below 20 x 20 20 16.7 20 16.7 bottom of (6,1 x 6,1) (75,7) (1,15) (75,7) (1,15) beam. (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Minimum Flow and Residual Pressure(b,c) Coverage Ordinary Temp.Rating Intermediate Temp.Rating Area(a) 155°F(68'C) 175`F(79`C) Minimum Ft.x Ft. Deflector to Installation Spacing (m x m) Flow Pressure Flow Pressure Ceiling Type Ft. GPM PSI GPM PSI (m) (L/min) (bar) (L/min) (bar) 12 x 12 13 7.0 13 7.0 Smooth (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings to 14 x 14 14 8.2 14 8.2 (4,3 x 4,3) (53,0) (0,57) (53,0) (0,57) 4 inches s Recessed using le 16 x 16 15 9.4 15 9.4 Beamed EscutchSteyon 20 or 8 (4,9 x 4,9) (56,8) (0,65) (56,8) (0,65) Ceilings per non-recessed (2,4) NFPA 13D per NFPA 13D, 18 x 18 18 13.5 18 13.5 or 13R 13R,or 13 (5,5 x 5,5) (68,1) (0,93) (68,1) (0,93) 1-1/4 to 1-3/4 inches below 20 x 20 21 18.4 21 18.4 bottom of (6,1 x 6,1) (79,5) (1,27) (79,5) (1,27) beam. (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA a TFP400 Page 5 of 6 Step C. Tighten the sprinkler into the The owner is responsible for the sprinkler fitting using only the W-Type 7 inspection, testing, and mainte- Recessed Sprinkler Wrench(Figure 4). nance of their fire protection system With reference to Figure 1, apply the and devices in compliance with this W-Type 7 Recessed Sprinkler Wrench document, as well as with the appli- to the sprinkler wrench flats. cable standards of the National Fire Step D. After the ceiling has been Protection Association (e.g., NFPA installed or the finish coat has been 25), in addition to the standards of any applied, slide on the Style 20 Closure authorities having jurisdiction.Contact over the Series LFII Residential the installing contractor or sprinkler Sprinkler and push the Closure over the manufacturer regarding any questions. Mounting Plate until its flange comes in Automatic sprinkler systems are contact with the ceiling. recommended to be inspected, tested,and maintained by a qualified Care and Inspection Service in accordance with local requirements and/or national Maintenance codes. The TYCO RAPID RESPONSE Series Ordering LFII Residential Pendent and Recessed Pendent Sprinklers(TY2234)must be Procedure maintained and serviced in accordance with this section: Contact your local distributor for Before closing a fire protection system availability. When placing an order, main control valve for maintenance indicate the full product name and Part work on the fire protection system that Number(P/N). it controls, permission to shut down Sprinkler Assembly the affected fire protection system Specify: Series LFII (TY2234), K=4.9, must be obtained from the proper Residential Pendent Sprinkler, authorities and notify all personnel (specify)temperature rating, (specify) who may be affected by this action. finish, P/N (specify). Absence of the outer piece of an 155°F(68°C) escutcheon, which is used to cover Natural Brass P/N 51-201-1-155 a clearance hole, can delay sprinkler Pure White(RAL 9010)' P/N 51-201-3-155 operation in a fire situation. Signal White(RAL 9003) P/N 51-201-4-155 Chrome Plated P/N 51-201-9-155 The owner must assure that the 175°F(79°C) sprinklers are not used for hanging Natural Brass P/N 51-201-1-175 any objects and that the sprinklers Pure White(RAL 9010)' P/N 51-201-3-175 are only cleaned by means of gently Signal White(RAL 9003) P/N 51-201-4-175 dusting with a feather duster; other- Chrome Plated P/N 51-201-9-175 wise, non-operation in the event of 'Eastern Hemisphere sales only. a fire or inadvertent operation may result. Recessed Escutcheon Sprinklers which are found to be Specify: Style 20 Recessed leaking or exhibiting visible signs of Escutcheon with(specify*)finish, P/N (specify'). corrosion must be replaced. Automatic sprinklers must never be *Refer to Technical Data Sheet TFP770. painted, plated, coated, or other- wise altered after leaving the factory. Sprinkler Wrench Modified sprinklers must be replaced. Specify: W-Type 6 Sprinkler Wrench, Sprinklers that have been exposed to P/N 56-000-6-387. corrosive products of combustion,but have not operated,should be replaced Specify: W-Type 7 Sprinkler Wrench, if they cannot be completely cleaned P/N 56-850-4-001. by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprinklers damaged by dropping, striking,wrench twist/slippage,or the like, must be replaced.Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) • TFP400 Page6of6 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. -tgG.o TEFLON is trademark of The DuPont Corporation. Dyna-Flow® High Strength Steel Pipe The original high-strength lightwall sprinkler pipe with hydraulics superior to Schedule-10. Dyna-Flow pipe is the"original"high- Specifications strength lightwall sprinkler pipe.Dyna- Flow has outstanding hydraulic NPS Nominal I.D. Wt. Wt.(H20 Filled) Pcs/ WVLift(21') WI/Lift(24') Wt/Lift(25') capabilities and is recognized as the In;mm In:mm Lbs/Ft:Kg/m Lbs/Ft;Kg/m Lift Lbs;Kg Lbs;Kg Lbs;Kg most popular alternative to Schedule-10 1" 1.191 0.830 1.31 91 1,586 1,812 1,888 pipe.Lightweight,easy to cut and easy 25 30.3 1.2 1.95 91 719 822 856 to handle for installation.Dyna-Flow is a 11/4" 1.536 1.059 1.87 61 1,356 1,550 1,615 valuable addition to any fire protection 32 39.0 1.6 2.78 61 615 703 733 system. 1'/2" 1.728 1.667 2.71 61 2,135 2,440 2,542 Superior Hydraulics 40 43.9 2.5 4.03 61 968 1107 1153 2" 2.203 2.104 3.79 37 1,634 1,868 1,946 With an inside diameter of up to 11% 50 56.0 3.1 5.64 37 741 847 883 larger than Schedule-40 and up to 7% 212" 2.703 2.564 5.10 30 1,615 1,846 1,923 larger than Schedule-10, Dyna-Flow 65 68.7 3.8 7.59 30 733 837 872 pipe hydraulics are exceptional.Larger 3" 3.314 3.387 7.18 19 1,351 1,544 1,608 I.D.s enable Dyna-Flow,and related 80 84.2 5.0 10.69 19 613 700 729 components,to be down-sized within the 4" 4.310 4.473 10.86 19 1,784 2,039 2,124 system,thus increasing the potential for 90 109.5 6.7 16.16 19 809 925 963 job cost savings.For complete Hazen- Williams charts,refer to"Dyna-Flow Hydraulic Data Tables." Coatings & Fabrication Specifications & Approvals Additional Benefits Dyna-Flow products are coated with Dyna-Flow/Super Flo pipe is manufac- • Lightweight and easy to install, an environmentally approved and tured to meet ASTM A-795 Type E, resulting in more efficient use of your specially formulated modified-acrylic or Grade A and is in compliance with freight and labor dollars. water-based coating.This durable coating NFPA-13 and NFPA-14.All sizes of is paintable.The black coating acts as Dyna Flow/Super Flo are UL Listed,FM • Provides stability needed to comply with an excellent primer and is resistant to Approved and ULC Listed. standard hanger spacing weathering and U.V.degradation from (15 ft O.C.)per NFPA. outdoor storage. ® 4> ® • Available in Standard lengths for your Metallurgical properties provide excellent Listed Approved Listed convenience,or can be ordered in fabrication characteristics for end prep custom lengths upon approval. Dyna-Flow/Super Ho is UL/ULC Listed finishes,welding and roll grooving. for use with roll grooved,plain-end • Fast cutting and welding,as well as There is no special process or equipment couplings,and welded joints for wet,dry, easy roll grooving and end preparation. needed for fabrication and installation. preaction and deluge systems.It is FM • Available in Factory roll grooved form The internal surface of all black Allied Approved for roll grooved,plain-end,and for quicker shop turnaround. Tube&Conduit Fire Sprinkler pipe welded joints for wet systems.Refer to products up to 4.5000"in diameter is appropriate documentation for up-to-date • Clean,durable mill coating provides coated with our new Antibacterial listing and approval information. Dyna- longer"shelf life"and acts as an Formula,"ABF'. In scientific laboratory Flow/Super Flo is now available"hot- excellent primer for custom paint test,ABS proved to have superior dip"galvanized and has been specifically applications. - resistance to microbial colonization of approved by FM for dry systems uses. pipe walls,thereby delaying or possibly preventing the onset of Microbiologically - Influenced corrosion(MIC)when the First Sprinkler System is first installed. ���0 allied 16100 S. Lathrop•Harvey, IL 60426 Customer Service: \�/ 11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882-5543 a vita!part of your world TUBE 8 CONDUIT 2525 N. 27 th Ave. • Phoenix,AZ 85009 Fax 708-339-1806 S2 - 3 r Dyna-Thread ® . Full Line Sch-40 Replacement Dyna-Thread' offers the life expectancy of Sch-40 with superior hydraulics and greater value. Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry.It combines the safety and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages. Comparison to Schedule 40 Comparison to L.W.T. Pipes • Dyna-Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread to 3.6%larger than Sch-40 giving it weight,Dyna-Thread reduces (CRR=1.00)gives Dyna-Thread superior hydraulics.And,when used installation fatigue and is ideal for better life expectancy than lightwall in combination with Dyna-Flow pipe, retro-fit applications. threadable pipe joints. down sizing often occurs. Corrosion Resistance Ratio(CRR)is a • Unlike lightwall threadable pipe, • Dyna-Thread is fully listed and UL(Underwriters Laboratory)term for Dyna-Thread has no thread gauge approved by UL,ULC,and FM for the estimated life expectancy of a pipe warning. fire sprinkler applications. joint.This is based on the calculated wall thickness at the base of the fast • byna-Thread is approved for • The life expectancy of Dyna-Thread standard hanger spacing(15 ft. and Sch-40 are equal based on the exposed thread,assumed to be the weakest point of the pipe length.Dyna- U.C.),can be used as earthquake calculated wall thicknesses per UL. Thread and Sch-40 have the same sway bracing, and is safe to use as • The consistent quality of steel used to calculated wall thicknesses at this point drops. make Dyna-Thread facilitates smooth and are both assigned the same CRR of • Dyna-Thread is safer to weld on. threading and lower maintenance 1.00. costs • Dyna-Thread is more widely accepted than lightwall threadable • The exterior of Dyna-Thread is The internal surface of all black Allied where Sch-40 is specified. protected by a clean,durable mill Tube&Conduit Fire Sprinkler pipe coating for extended shelf life and products up to 4.5000"in diameter is easy paint application. coated with our new Antibacterial Formula,"ABF".In scientific laboratory test,ABS proved to have superior Specifications & Approvals resistance to microbial colonization of el ® 010 pipe walls,thereby delaying or possibly preventing the onset of Super 40/Dyna-Thread pipe is manufactured to meet:ASTM A-135, Listed Approved Listed Microbiologically Influenced corrosion Grade A and is in compliance with (MIC)when the First Sprinkler System IvFPA-13.All sizes of Super 40/Dyna- is first installed. mead are rated at 300 psi working pressure.Super 40/Dyna-Thread is UL Specifications and ULC Listed for wet,dry deluge and pre-action sprinkler systems and FM NPS Nominal I.D. Wt. WI.(H20 Filled) PeW WIILift(2V) MLitt(24') Wglift(25') Approved for use in wet systems. Super In;mm In:mm Lbs/Ft;Kg/m Lbs/Ft;Kg/m Litt Lbs;Kg Ctrs:Kg lbs.Kg 40/Dyna-Thread can be"hot-dip" 1" 1.080 1.330 1.75 70 1955 2234 2327 galvanized to meet FM requirement for 25 27.4 2.0 2.60 70 887 1013 1056 dry systems. Super 40/Dyna-Thread is 11/4' 1.408 1.870 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 35.8 2.8 3.78 51 908 1038 1081 welded outlets and is suitable for all - 11/i 1.639 2.290 3.22 44 2115 2418 2519 roll-grooved,and plain-end fittings. 40 41.6 3.4 4.79 44 959 1097 1143 (See listing information). 2" 2.104 3.050 4.57 30 1921 2196 2287 50 53.4 4.5 6.80 30 871 996 1037 //—�' ■ 16100 S. Lathrop• Harvey, IL 60426 Customer Service: tIL�CO \-/ allied 16100 Norcom Rd. • Philadelphia, PA 19154 (800) 882-5543 a vital poi t of you, wdild TUBE&CONDUIT 2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708-339-1806 S3 - 3 SMITHCOOPERR. I N T E R N A T I O N A L • CORPORATE OFFICE TEL(800)766-0076 LOCAL(323)890-4455 FAX(323)890-4456 W W W.SMITHCOOPER.COM 400tiofor ites Or • Zr 1.0' fiROO\ Grooved Couplings & Fittings • SMrrHCooPiEi ® I N T E R N A T I O N A L GROOVED COUPLINGS & FITTINGS TABLE OF CONTENTS Lightweight Couplings 1-2 Concentric Reducers & Reducing Tees 10 Standard Weight Couplings 3-4 Threaded Mechanical Tees 11-12 Reducing Couplings 5 Grooved Mechanical Tees 13 Hinged Flange Adapters 6 Strap Tees 14 Short Radius Fittings 7 Adapter Elbow 15 Drain Cap 7 C00PLET3 Adapter Nipples. 16 Drain Elbow 7 Standard Roll Groove Specifications 17 Standard Radius Elbows 8 Standard Cut Groove Specifications 18 Tee 9 UL Listed/FM Approved Sprinkler Pipe Cross 9 and Warranty Information 19 Caps 9 Installation Instructions 20 Grooved x Flange Adapter 9 Housing •Ductile Iron Conforming to ASTM A536 Coating •Orange Paint •Hot Dipped Galvanized Conforming to ASTM A153 Hardware •Electroplated Track Bolts Conforming to ASTM A183 with a minimum tensile strength of 110,000 psi • 100%Magnetic Particle Inspection of Each Bolt Gaskets •Grade E EPDM(Green Stripe) Temperature Range:—30°F(-34°C)to+230°F(+110°C) •Grade T Nitrite(Orange Stripe) Temperature Range:—20°F(-29°C)to+180°F(+82°C) Grooves •Dimensions to AWWA C606 All COOPLOKTM Grooved products c®us UL Listed and FM Approved. LISTED APPROVED SMITH-COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX(323) 890-4456 • www.smithcooper.com t 0(, It)h 500 Series Lightweight Flexible Couplings /ice. • 11011 . \N. c � us -� 14 Ir�MI lli __ _ r APPROVED ILIA , Fr; P_. - i Fig. 65LF& 66LF-Lightweight Flexible Couplings C B Part Number Max Pipe Max Working Dimensions Pipe Size Pipe OD End Gap Pressure A B C Bolt Size Deflection Weight Painted GaIv IN/mm IN/mm IN/mm PSI/bar IN/mm IN/mm IN/mm IN/mm Degrees LB/kg 1-1/4 1.66 1/8 500 2.58 4.09 1.85 3/8" x 2 1.2 65113012 66LF3012 2 1'` 32 42.2 3.2 34.5 65.5 103.9 47.0 M10 x 52 0.5 1-1/2 1.900 1/8 500 2.85 4.37 1.85 3/8"x 2 1.3 651F3014 611F3014 1.9" 40 48.3 3.2 34.5 72.4 111.0 47.0 M10x52 0.6 2 2.375 1/8 500 3.37 4.8 1.85 3/8" x 2-1/2 1.7 65LF3020 66LF3020 2 0 50 60.3 3.2 34.5 85.6 121.9 47.0 M10 x 60 0.8 2-1/2 2.875 1/8 500 3.88 5.28 1.85 3/8"x2-1/2 1.9 651F3024 66113024 2.3° 65 73.0 3.2 34.5 98.6 134.1 47.0 M10 x 65 0.9 3 3.500 1/8 500 4.4 5.91 1.85 3/8"x 2-1/2 2 1 65LF3030 661.F3030 2.0` 80 88.9 3.2 34.5 111.8 150.1 47.0 M10 x 65 0.9 4 4.500 1/4 500 5.75 7.44 2.01 1/2" x 3-1/4 3.6 65LF3040 66113040 2.2° 100 114.3 6.4 34.5 146.1 189.0 51.1 M12 x 80 1.6 5 5.563 1/4 500 6.79 9.13 2.01 5/8"x 3-3/4 5.1 65LF3050 66113050 1.8- 125 141.3 6.4 34.5 172.5 231.9 51.1 M16 X 95 2.3 6 6.625 1/4 500 7.95 10.31 2.01 5/8"x 3-3/4 6.0 65LF3060 66113060 1.6° 150 168.3 6.4 34.5 201.9 261.9 51.1 M16 X 95 2.7 8 8.625 1/4 500 10.8 13.07 2.52 3/4" X 5-1/4 10.6 65113080 66113080 1.4: 200 219.1 6.4 34.5 274.3 332.0 64.0 M19 X 110 4.8 NOTES: 1.All bolts and gaskets identified by SCI logo. 2. 100% Magnetic particle inspection of each bolt. Each bolt has a minimum tensile strength of 110,000 psi. 3. Gaskets are pre-lubricated. 4. Gasket Grade E EPDM(green stripe): • Temperature range:-30°F(-34°C)to+230°F(+110°C). ' 5. Gasket Grade T Nitrile(orange stripe): • Temperature range:-20°F(-29°C)to+180°F(+82°C). . 6. See Installation Instructions on Page 20. 7. SMITH-COOPER Warranty(see page 19)only applies to assemblies made up using gaskets, housings, and bolts with the<>.logo. c Ous SMITH-COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX(323) 890-4456 • www.smithcooper.com . 1 . • 0(,,,1d)h 500 Series Lightweight Rigid Couplings B a 'i: cous • hi - -T- - A F APPROVED C Fig. 65LR & 66LR-Lightweight Rigid Couplings Part Number Max Pipe Max Working Dimensions Pipe Size Pipe OD End Gap Pressure A B C Bolt Size Weight Painted Galv IN/mm IN/mm IN/mm PSI/bar IN/mm IN/mm IN/mm IN/mm LB/kg -1 r 4 1.660 1/8 500 2.66 4.09 1 85 3/8. x 2 1 2 65LR3012 6603012 32 42.2 3.2 34.5 67.6 103.9 47.0 M10 x 52 0.5 1-1/2 1.900 1/8 500 2.93 4.37 1.85 3/8"x 2 1.3 65LR3014 66LR3014 40 48.3 3.2 34.5 74.4 111.0 47.0 M10 x 52 0.6 2 2.375 1/8 500 3.44 4.8 1.85 3/8x2-1/2 1.7 65LR3020 66LR3020 50 60.3 3.2 34.5 87.4 121.9 47.0 M10 x 60 0.8 2-1/2 2.875 1/8 500 3.96 5.28 1.85 3/8" x 2-3/4 1.9 65LR3024 66LR3024 65 73.0 3.2 34.5 100.6 134.1 47.0 M10 x 65 0.9 3 3.500 1/8 500 4.55 5.91 1.85 3/8"x 2-3/4 2.1 65E113030 66E63030 80 88.9 3.2 34.5 115.6 150.1 47.0 M10 x 65 1.0 4 4.500 1/4 500 5.83 7.28 2.01 3/8"x 2-3/4 3.6 65LR3040 66ER3040 100 114.3 6.4 34.5 148.1 184.9 51.1 M10 x 65 1.6 5 5.563 1/4 500 6.87 8.62 2.01 1/2"x3-3/4 5.1 65LR3050 66LR3050 125 141.3 6.4 34.5 174.5 218.9 51.1 M12 x 95 2.3 6 6.625 1/4 500 8.03 9.76 2.01 1/2" x 3-1/4 6.0 651R3060 66LR3060 150 168.3 6.4 34.5 204.0 247.9 51.1 M12 x 95 2.7 8 8.625 1/4 500 10.16 12.52 2.52 5/8" x 4-1/2 10.6 65LR3080 66LR3080 200 219.1 6.4 34.5 258.1 318.0 64.0 M16 x 120 4.8 NOTES: 1. All bolts and gaskets identified by SCI logo. 2. 100% Magnetic particle inspection of each bolt. Each bolt has a minimum tensile strength of 110,000 psi. 3. Gaskets are pre-lubricated. 4. Gasket Grade E EPDM(green stripe): •Temperature range:-30°F(-34°C)to+230°F(+110°C). ' 5. Gasket Grade T Nitrite(orange stripe): • Temperature range:-20°F(-29°C)to+180°F(+82°C). . 6. See Installation Instructions on Page 20. 7. SMITH-COOPER Warranty(see page 19)only applies to assemblies made up using gaskets, housings, and bolts with the ® logo. c®w SMITH-COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX(323) 890-4456 • www.smithcooper.com 2 . . , .l I)(.!.1.0k 500 Series Reducing Couplings B Vii , 7,0502 C ID us Inim.- l1 ilif, 4�41:41(..... .4,_ . _,.- / r 'MI a A I 410, APPROVED I�I p IL ,', IIIT aN All .7 r Fig. 65RC& 66RC-Reducing Couplings Part Number Max Pipe Max Working Dimensions Pipe Size End Gap Pressure A B C Bolt Size Deflection Weight Painted Galv IN/mm IN/mm PSI/bar IN/mm IN/mm IN/mm IN/mm Degrees LB/kg 2 x 1-1/2 1/8 300 3.43 4.88 1.85 3/8x2-1/4 1.9 65RC3020014 66RC3020014 2.0' 50 x 40 3.2 20.7 87.1 124.0 47.0 M10 x 57 0.9 2-1/2 x 2 1/8 300 3.98 5.35 1.85 3/8x2-1/2 2 3 65RC3024020 66RC3024020 1.5` 65x50 3.2 20.7 101.1 135.9 47.0 M10x64 1.0 3 x 2 1/8 300 4.59 6.34 1.85 3/8x2-112 3.1 65RC3030020 66RC3030020 1.8° 80x50 3.2 20.7 116.6 161.0 47.0 M10x64 1.4 3 x 2-1/2 1/8 300 4.51 6.34 1.85 3/8x2-1/2 2 9 65RC3030024 66RC3030024 - .- - - - 1.8` 80x65 3.2 20.7 114.6 161.0 47.0 M10x64 1.3 4 x 2 1/4 300 5.83 7.52 2.01 1/2 x 3 4.8 65RC3040020 66RC3040020 1.2 100x50 6.4 20.7 148.1 191.0 51.1 M12x76 2.2 4 x 2-1/2 1/4 300 5.83 7.52 2.01 1/2 x 3 4.8 65RC3040024 66RC3040024 1.2 100x65 6.4 20.7 148.1 191.0 51.1 M12x76 2.2 4 x 3 1/4 300 5.83 7.52 2.01 1/2 x 3 4.4 6511C3040030 66RC3040030 1.2° 100x80 6.4 20.7 148.1 191.0 51.1 M12x76 2.0 6 x 4 1/4 300 7.99 10.35 2.01 5/8 x 3-3/4 9 65RC3060040 66RC3060040 0.9° 150 x 100 6.4 20.7 202.9 262.9 51.1 M16 x 95 4.1 8 x 6 1/4 300 10.12 13.15 2.48 5/8 x 3-3/4 14.6 65RC3080060 66RC3080060 0.8° 200 x 100 6.4 20.7 257.0 334.0 63.0 M19 x 108 6.6 NOTES: 1. All bolts and gaskets identified by SCI logo. 2. 100% Magnetic particle inspection of each bolt. Each bolt has a minimum tensile strength of 110.000 psi. 3. Gaskets are pre-lubricated. 4. Gasket Grade E EPDM(green stripe): • Temperature range:-30°F(-34°C)to+230°F(+110°C). 5. Gasket Grade T Nitrite (orange stripe)available: • Temperature range:-20°F(-29°C)to+180°F(+82°C). - 6. See Installation Instructions on Page 20. 7. SMITH-COOPER Warranty(see page 19)only applies to assemblies made up using gaskets, housings, and bolts with the 4. logo. c Ous SMITH-COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX(323) 890-4456 • www.smithcooper.com 5 . . (p . iA)h 500 Series Hinged Flange Adapter ( „ ,Ill I' tb 0,r C0US S APPROVED ..." 410 Yg4 �� • ~.I . _ A . - Cf Fig. 65FH& 66FH-Hinged Flange Adapter Part Number Max Working Dimensions Flange Bolt Number Pipe Size Pipe OD Pressure A B C Size of Flange Weight Painted Galv IN/mm IN/mm PSI/bar IN/mm IN/mm IN/mm IN/mm Bolts LB/kg 2 2.375 300 6.00 4.75 0.75 5/8 x 3 3 6 65F113020 66F H3020 4 50 60.3 20.7 152.4 120.7 19.1 M16 x 76 1.6 2-1/2 2.875 300 7.00 5.50 0.88 5/8 x 3 3 6 65F113024 66F113024 4 65 73.0 20.7 177.8 139.7 22.4 M16 x 76 1.6 3 3.500 300 7.50 6.00 0.94 5/8 x3 4.8 65FH3030 66FH3030 4 . 80 88.9 20.7 190.5 152.4 23.9 M16 x 76 2.2 4 4.500 300 9.00 7.50 0.94 5/8 x 3 6.6 65F H3040 613F H3040 8 100 114.3 20.7 228.6 190.5 23.9 M16 x 76 3.0 6 6.625 300 11.00 9.50 1.00 3/4 x 3-1/2 8.4 65FH3060 66FH3060 8 150 168.3 20.7 279.4 241.3 25.4 M19 x 89 3.8 8 8.625 300 13.50 11.75 1.12 3/4x3-1/2 14.3 85F H3080 B6FH3080 8 200 219.1 20.7 342.9 298.5 28.4 M19 x 89 6.4 NOTES: 1. All bolts and gaskets identified by SCI logo. 2. 100% Magnetic particle inspection of each bolt. Each bolt has a minimum tensile strength of 110,000 psi. 3. Gaskets are pre-lubricated. 4. Gasket Grade E EPDM(green stripe): •Temperature range:-30°F(-34°C)to+230°F(+110°C). 5. Gasket Grade T Nitrile(orange stripe): • Temperature range:-20°F(-29°C)to+1807(+82°C). 6. Matches class 125/150 flange dimensions. 7. See Installation Instructions on Page 17. 8. SMITH-COOPER Warranty(see page 19)only applies to assemblies made up using gaskets, housings, and bolts with the 0 logo. Cus SMITH-COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX(323) 890-4456 • www.smithcooper.com t I)( . L()hk 500 Series Short Radius Grooved Fittings (, •,Ivo c0us 411110P • APPROVED 111 1 - II 1 • ii1 _II II' - . I 0. / .I -1"NPT %IT A 0,,, ■■ DRAIN I -� I-- A I.-A-i 1 B,I 1"NPT DRAIN 90° Elbow Tee Drain Cap Drain Elbow Fig. 65ES & 66ES- 90°Elbow, Short Radius Fig. 65TS & 66TS- Tee, S_h_ ort Radius Part Number Nominal Actual Part Number Nominal Actual Pipe Size Pipe OD A Weight Pipe Size Pipe OD A Weight Painted GaIv IN IN/mm IN/mm LB/kg Painted GaIv IN/mm IN/mm IN/mm LB/kg 65E83020 66E83020 2 2.375 2 75 1.7 2 2.375 2.75 2.4 65783020 66183020 50 60.3 69.9 0.8 50 60.3 69.9 1.1 65E83024 66E83024 2-1/2 2 875 3.00 3.1 65783024 66T83024 2-1/2 2 875 3.00 3.6 65 73.0 76.2 1.4 65 73.0 76.2 1.6 65E83030 66E83030 3 3.500 3.38 4.0 3 3.50U 3.38 5.3 65783030 66183030 80 88.9 85.9 1.8 80 88.9 85.9 2.4 65E83040 66E83040 4 4.500 4.00 6.5 4 4.500 4.00 8.7 65183040 66183040 100 114,3 101.6 2.9 100 114.3 101.6 3.9 65E83050 66E83050 5 5.563 4.88 12.6 65783050 66183050 5 5.563 4.88 15.7_ 125 141.3 124.0 5.7 125 141.3 124.0 7.1 65ES3060 66E83060 6 6.625 5.50 18.3 6 6.625 5.50 22.7 65783060 66783060 150 168.3 139.7 8.2 150 168.3 139.7 10.2 65E83080 66E83080 8 8.625 6.81 25.5 65783080 66783080 8 8.625 6.94 38.7_ 200 219.1 173.0 11.5 200 219.1 176.3 17.4 500 Series Grooved Fittings w/ Drains Fig. 65DC& 66DC-Drain Cap Fig. 65DE & 66DE-Drain Elbow Part Number Nominal Actual Part Number Nominal Actual Pipe Size Pipe OD A Weight Pipe Size Pipe OD A B C Weight Painted Galv IN IN/mm IN/mm LB/kg Painted Galv IN/mm IN/mm IN/mm IN/mmIN/mm LB/kg 650C3020 660C3020 2 2.375 0.88 0.6 650E3020 668E3020 2 2.375 3.25 2.76 1.30 2.1 50 60.3 22.4 0.3 50 60.3 82.6 70.1 33.0 0.9 650C3024 660C3024 2-1/2 2.875 0.88 1.0 658E3024 660E3024 2-1/2 2.875 3.75 2.70 68 5.2 65 73 22.4 0.5 65 73.0 95.3 68.6 42.7 2.3 65DC3030 660C3030 3 3.500 0.88 1.2 658E3030 660E3030 3 3.500 4.25 2.70 2.10 5.5 88.9 88.9 22.4 0.5 80 88.9 108.0 68.6 53.3 2.5 650C3040 660C3040 4 4.500 1.00 2.5 650E3040 660E3040 4 4.500 5.00 2 75 2.60 8.8 100 114.3 25.4 1.1 100 114.3 127.0 69.9 66.0 4.0 5 5.563 1.00 4.6 6 6.625 6.50 2.75 3.65 18.7 65E3050 660C3050 - 125 141.3 25.4 2.1 65DE3060 6611E3060 150 168.3 165.1 69.9 92.7 8.4 650C3060 660C3060 6 6.625 1.00 6.1 650E3080 660E3080 8 8.625 7 75 2.75 4.57 28.6 150 168.3 25.4 2.7 200 219.1 196.9 _ 69.9 116.1 12.9 5DC3080 660C3080 8 8.625 20 13.1 6 200 219.1 30.5 5.9 c Ous SMITH-COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX(323) 890-4456 • www.smithcooper.com 7 �t of—1,0K 1,(l h UL Listed/FM Approved Sprinkler Pipe and Warranty Information '1)yl Sc!COOPLOKTM Grooved Couplings are UL Listed and FM Approved c (21 us for use on the following types of sprinkler pipe:* APPROVED PIPE NAME MANUFACTURER Dyna-Thread®, Central-Thread®, XL®, XL-II®, Dyna-Flow®, Allied Tube and Conduit Corp. Super 40®, Super-Flo®,TL®, Central 7®, BLT® Eddylite®, Eddy Flow®, Eddy Thread 40® Bull Moose Tube Co. Gal-7® IDOD Systems Co. EZ-Flow® Northwest Pipe & Casing Co. WLS®, Mega-Flow®, Mega-Thread®, MLT®, GL® Wheatland Tube Company Steady Flow®, Steady Thread® Welded Tube Corp. Fire-Flo®, EZ-Thread® Youngstown Tube Co. Tex-Flow® Tex-Tube International SPSF® Yieh Phui Enterprise Co. Ltd. *NOTE.Includes any manufacturer of Schedule 10 or Schedule 40 steel pipe. Check www.SmithCooper.corn for updated list of UL Listed/FM Approved sprinkler pipe manufacturers. • WARRANTY AND LIMITATIONS OF LIABILITY SMITH-COOPER INTERNATIONAL(SCI)warrants to its initial purchaser only,that its products which are delivered to this initial purchaser will be of the kind described in the order or price list and will be free of defects in workmanship or material for a period of five years from the date of delivery to our initial purchaser. Should any failure to conform to this warranty appear within five years after the date of the initial delivery to our initial purchaser,SCI will,upon written notification thereof and substantiation that the goods have been stored,installed,maintained and operated in accordance with recognized engineering and piping practices and industry standards,correct such defects by suitable repair or replacement(which alternative shall be at the discretion of SCI)of product at SCI's own expense upon return of the defective part to SCI. In the event that SCI elects to replace the defective product,SCI shall pay up to$50 per defective product for total cost of replacement. In the event of multiple claims, such payment shall be no greater than$1,000 for each installation project. This warranty applies only during normal use that meets the above referenced conditions of installation and operation and is absolutely void if the product has been damaged after purchase or it it has been misused,repaired,altered or modified in any manner whatsoever. SCI shall not warranty any of its products if any portion of the product including without limitation,any component,gasket,housing or bolt has been modified,altered,remanufactured or replaced in any manner by any customer, user of the product or third party. Correction of non-conformities,in the manner and for the period of time provided above,shall constitute fulfillment of all liabilities of SCI to our initial purchaser,with respect to the goods,whether based on contract,negligence,strict tort,or otherwise. It is the intention of SCI that no warranty of any kind,whether expressed or implied shall pass through our initial purchaser to any other person or corporation. No returns will be allowed unless prior written permission of SCI is first obtained. Buyers shall be responsible for all costs of transportation as well as a restocking charge. This warranty is exclusively for the benefit of the initial purchaser of this product from SCI and,except to the extent prohibited by applicable law,the foregoing warranty is in lieu of all other warranties,express or implied,including but not limited to warranties of fitness or merchantability. LIMITATIONS OF LIABILITY:SCI shall not under any circumstances be liable for special or consequential damages such as,but not limited to damage to loss of other property or equipment,loss of profits or revenue,cost of capital,cost of purchased or replacement goods,claims of customers of our initial purchaser,any labor cost for repair or replacement of the product or damage caused by the product. The remedies of our initial purchaser,and all others,set forth herein are exclusive,and the liability of SCI with respect to same shall not,except as expressly provided herein,exceed the price of the SCI products on which such liability is based. DISCLAIMER:Smith-Cooper International cannot be held responsible for omissions or errors in this catalog. Please refer to www.smithcooper.com for current information. cOuz SMITH-COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX(323) 890-4456 • www.smithcooper.com 19 . . • as Iron Threaded Fittings -401`.--- „'"1,;.4,4' • . \ g-,.... . ' • . . - • , , • , , ! i ( 1. I 1 •, ' ' - '-' —71.11...7.1"..."11°%! •i'a. ..w. _................ . --. .....41.4... ..." - N .* ,' - • - . „ .,,,,, , , . ,. .1,...,._i.•. . ••••• •• .. . _ „, . , . • -, i 4 ,.. . S. '..- .,:•-•,, , , '.:11-7. . ,0 t ,,., ,,, 10 'At■ .."" 4 4'- ' .:7. ,'.+ .;.,47. '4 '. -* •0,, r o • .Cy -_ . .; ,,...„• 1 , 4-4?-root 4,.: a 4 e SMITH , COOPFIn, INTERNATIONAL STS'UTHCOOPER® I N T E R N A T I O N A L Cast Iron Threaded Fittings Specifications • The ® branded Cast Iron threaded fittings are UL Listed and FM Approved at 300 psi • Rated to 125#WSP • Casting date on each fitting c UI us • Grey iron castings conform to ASTM A126 LISTED • Cast iron fitting dimensions conform to ASME B16.4 Class 125 • NPT threads on fittings conform to ASME B1.20.1 APPROVED • The 4> branded Cast Iron threaded fittings and are 100% Air Tested • Manufacturing facility is ISO 9001:2000 and ISO 14001 li I troll ithngs- ass 1 • rr rL��, c ® us - Fig. 37E 1 - 90° Elbow LISTED APPROVED A Size A Packing Weight //Oi..,. IN Part Number IN Inner Master LB ,••.•• 1/2 37E 1004 3 90 180 0.3 I� ---r-' 3/4 37E 1006 1 31 50 100 0.5 1 A ��Q 1 37E 1010 1.50 35 70 0.8 ���I% 1-1/4 37E 1012 1.75 20 40 1.3 1-1/2 37E 1014 1.94 15 30 1 7 2 37E 1020 2.25 7 14 2.7 2-1/2 37E 1024 2.70 4 I 8 4.3 Fig. 37RE1 - 90° Reducing Elbow . �I Size A B Packing Weight .y" IN Part Number IN IN Inner Master LB _ _ _ _ 1 _'•. - 1 x 1/2 37HE1010004 1 36 1 26 50 100 0 5 'I, 1 x 314 37RE1010006 1.45 1.38 40 80 0.7 IB 1-1/4 x 1/2 37RE1012004 1.53 1.34 32 64 0 8 I 1-1/4 x 3/4 37RE1012006 1.63 1.45 28 56 0.9 1-1/4 x 1 37RE1012010 1.67 1 58 25 50 1 0 1-1/2 x 1/2 37RE1014004 1.75 1.52 25 50 1.0 1-1/2 x 3/4 37RE1014006 1.75 1.52 20 40 1.1 1-1/2 x 1 37RE1014010 1.80 1.65 18 36 1.3 • 1-1/2 x 1-1/4 37RE1014012 1.88 1.82 14 28 1.5 2 x 1/2 37RE1020004 1.97 1.60 15 30 1.4 2 x 3/4 37RE1020006 1.97 1.60 15 30 1 6 • 2 x 1 37RE1020010 2.02 1.73 12 24 1.8 2 x 1-1/2 37RE1020014 2.16 2.02 10 20 2 3 Fig. 37F 1 - 45° Elbow A Size A Packing Weight 1�t t Part Number IN IN Inner Master LB 1 37F 1010 1.26 40 80 0.7 , 1-1/4 37F 1012 1.29 22 44 1.2 1-1/2 37F 1014 1 44 16 32 1.5 [MI 1 IA 2 37F 1020 1.69 8 16 2.6 Fig. 37T1 - Tee C A Size Part Number A Packing Weight -IN IN Inner Master LB S I !r���� A 1/2 37T 1004 1 13 6C 120 4 T =ER 3/4 37T 1006 1.31 30 60 0 7 I Ill 1 371 1010 1.50 22 40 1.1 "`�gwore 4 1-1/4 37T 1012 1.75 12 24 1.8 R 1-1/2 37T 1014 1.94 _ 16 2.4 0 A A 2 37T 1020 2.25 5 10 3.8 N Fig. 37RC1 -Hex Coupling Size Pari Number A Packing Weight IN IN Inner Master LB 1 ., 1 x lit 37RC1010004 1 69 60 120 0.5 A 1 x 314 37RC1010006 1.69 50 100 0.6 1111,H .. 2 x 1 (not hex)I 37RC1020010 2.81 I 16 32 1.5 SMITH-COOPER INTERNATIONALS • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com iir i ast ron fittings- ass I c ® us Fig. 37RT1 -Reducing Tee LISTED APPROVED 0 `_�_ Size Part Number A B Packing Weight k'eV IN IN IN IN Inner Master LB �C 1 x 1/2 37RT1010004 1.26 1.26 1.36 25 50 0.9 1 x 1/2 x 1 37 RT 1010004010 1.50 1.36 1.50 24 48 0.9 1 x 3/4 37RT1010006 1.38 1.38 1.45 22 44 1 0 �.�.,�. 1 x 3/4 x 1 37 RT 1010006010 1.50 1.45 1.50 20 40 1.0 ���� 1 x 1-1/4 37RT1010012 1.67 1 67 1.58 15 30 1.4 B A 1-1/4 x 1/2 37RT1012004 1.34 1.34 1.53 18 36 1.3 1-1/4 x 1/2 x 1-1/4 37RT1012004012 1.75 1.53 1 75 18 36 1.4 1-1/4 x 3/4 37RT1012006 1.45 1.45 1.62 15 30 1.4 1-1/4 x 3/4 x 1-1/4 37RT1012006012 1.75 1 62 1 75 15 30 1.5 1-1/4 x 1 37RT1012010 1.58 1.58 1.67 15 30 1.6 1-1/4 x 1 x 1/2 37RT1012010004 1.34 1.26 1.53 20 40 1.1 1-1/4 x 1 x 3/4 37RT1012010006 1.45 1.38 1.63 16 32 1.2 1-1/4 x 1 x 1 37RT1012010010 1.58 1.50 1.69 15 30 1.4 1-1/4 x 1 x 1-1i4 37RT1012010012 1.75 1.69 1.75 12 24 1.6 1-1/4 x 1 x 1-1/2 37RT1012010014 1.88 1.80 1.82 12 24 1 8 1-1/4 x 1-1/2 37RT1012014 1.88 1.88 1.82 10 20 2.0 1-1/2 x 1/2 37RT1014004 1.41 1.41 1.66 12 24 1.6 1-1/2 x 1/2 x 1-1/4 37RT1014004012 1.81 1.56 1.88 12 24 1.7 1-1/2 x 1/2 x 1-1/2 37RT1014004014 1.94 1.66 1.94 12 24 1.8 1-1/2 x 3/4 37RT1014006 1.52 1.52 1.75 12 24 1.8 - 1-1/2 x 3/4 x 1-1/4 37RT1014006012 1.94 1.66 1.88 12 24 1.7 1-1/2 x 3/4 x 1-1/2 37RT1014006014 1.94 1.75 1.94 12 24 1.9 1-1/2 x 1 37R11014010 1.65 1 65 1.80 10 20 1.9 . 1-1/2 x 1 x 1/2 37RT1014010004 1.44 1.25 1.69 18 36 1.3 1-1/2 x 1 x 3/4 37RT1014010006 1.50 1.44 1.75 15 30 1.4 1-1/2 x 1 x 1 37RT1014010010 1.65 1.50 1.80 12 24 1.6 1-1/2 x 1 x 1-1/4 37RT1014010012 1.82 1.67 1.88 10 20 1.8 1-1/2 x 1 x 1-1/2 37RT1014010014 1.94 1.80 1.94 8 16 2.1 1-1/2 x 1-1/4 37RT1014012 1.82 1.82 1.88 8 16 2.2 1-1/2 x 1-1/4 x 1/2 37R11014012004 1.41 1.34 1.66 15 30 1.5 1-1/2 x 1-1/4 x 3/4 37RT1014012006 1.52 1.45 1.75 12 24 1.6 1-1/2 x 1-1/4 x 1 37RT1014012010 1.65 1.58 1.80 12 24 1.8 1-1/2 x 1-1/4 x 1-1/4 37RT1014012012 1.82 1.75 1.88 10 20 2.1 1-1/2 x 1-1/4 x 1-1/2 37RT1014012014 1.94 1.88 1.94 8 16 2.3 1-1/2 x 1-1/4 x 2 37RT1014012020 2.16 2.10 2.02 6 12 2.7 1-1/2 x 2 37RT1014020 2.16 2.16 2.02 5 10 2.9 2 x 1/2 37RT1020004 1.49 1.49 1.88 8 16 2.6 C 2 x 3/4 37RT1020006 1.60 1.60 1.97 8 16 2.6 A 2 x 1 37RT1020010 1.73 1.73 2 02 6 12 2.9 s 2 x 1 x 2 37RT1020010020 2.25 2.02 2.25 5 10 3.1 2 x 1-1/4 37RT1020012 1.90 1.90 2.10 5 10 3.2 T 2x 1-1/4 x 2 37RT1020012020 2.25 2.10 2.25 5 10 3.2 I 2 x 1-1/2 37RT1020014 2.02 2.02 2.16 5 10 3.3 R 2 x 1-1/2 x 1/2 37RT1020014004 1.49 1.41 1.88 8 16 2.1 2 x 1-1/2 x 3/4 37RT1020014006 1.60 1.52 1 97 8 16 2.2 0 2 x 1-1/2 x 1 37RT1020014010 1.73 1.65 2.02 8 16 2.4 N 2 x 1-1/2 x 1-1/4 37RT1020014012 1 90 1.82 2.10 7 14 2.7 2 x 1-1/2 x 1-1/2 37RT1020014014 2.02 1.94 2.16 7 14 2.9 2 x 1-1/2 x 2 37RT1020014020 2 25 2.16 2.25 5 10 3.4 2 x 2-1/2 37RT1020024 2.60 2.60 2.39 3 6 4 6 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com u� i e ron rea a Fittings ....,,,,,. . ._ .._ . ... . .4 __ _.,.„. , _............ _.,,,,. _____. _,....t. _____ _______ , ,.. ..;., __ .. ...... . . `1l. T ■ la ` f re y ' c.la - .:.?..,,'''' Irs • kr SMITH - CooPER® I N T E R N A T I O N A L • SMITHCOOPER® I N T E R N A T I O N A L Ductile Iron Threaded Fittings Specifications • The © branded Ductile Iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP • Ductile Iron castings conform to ASTM A536 C 01 US • Fitting dimensions conform to ASME B16.3 LISTED • Bushings and plugs conform to ASME B16.14 44> • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2000 and ISO 14001 Temperature Working Pressure, Nonshock PSIG Degrees F 300# Class Threaded Fittings -20 to 100 500 150 500 200 480 250 460 300 440 350 420 400 400 450 380 500 360 550 340 600 320 650 300 • Y X111 ' Ductile Iron Fittings-Class 300 UL/FM • Ir6- c ® us LISTED APPROVED A Fig. 35E 3- 90°Elbow Size Part Number A Packing Weight w►��•�..,. IN IN Inner Master LB __ Q 1/2 35E 3004 1.13 100 200 0.2 -1 ��� 3!4 35E 3006 1.31 70 140 0.3 A 1 35E 3010 1.50 40 80 0.5 �iq 1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 35E 3024 2.70 4 8 3 2 Fig. 35RE3- 90° Reducing Elbow � ) Size Part Number A B Packing Weight 916"--"-, IN IN IN Inner Master LB 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 I •Ny 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 � A 1 x 3/4 35 R E3010006 1.38 1.45 50 100 0.4 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1,45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1 75 30 60 0.6 • 1-1/2 x 3/4 35RE3014006 1.52 1 75 25 50 0.7 1-1/2 x 1 35RE3014010 1 65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 . 2x1;2 35RE3020004 160 1.97 18 36 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2 02 16 32 1.2 D 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 U 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 C 2-1/2 x 2 35RE3024020 2.39 _ 2.60 6 12 2.5 T 1 Fig. 35F 3- 45° Elbow L Size Part Number A Packing Weight E IN IN Inner Master LB 1... 35F 3004 0.88 150 300 0.2 �� 3/4 35F 3006 0.98 80 160 0.3 -�' 1 35F 3010 1.13 40 80 0.5 `� I 1-1/4 35F3012 1.29 25 50 0.7 1-1/2 35F 3014 1.44 20 40 1 0 �� A 2 35F 3020 1.69 10 20 1.6 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size Part Number A Packing Weight IN IN Inner Master LB '.�! IA 1/2 35T 3004 1.13 80 160 0.3 • :11:Ira 3/4 351 3006 1.31 30 60 0.5 1 351 3010 1.50 25 50 0.7 r.,.,...,.,r,q 1-1/4 35T 3012 1.75 10 20 1.1 A A 1-1/2 351 3014 1.94 10 20 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 SMITH-COOPER INTERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com I • / I Ductile Iron Fittings-Class 300 UL/FM c ® us • LISTED APPROVED Fig. 35RT3-Reducing Tee _ Size Part Number A B C Packing Weight liaia IN IN IN IN Inner Master LB i C 3/4 x 1/2 35RT3006004 1.20 1.20 1.22 60 120 0.4 I1 x 1/2 35RT3010004 1.26 1.26 1.36 30 60 0.6 �= �I 1 x 1/2 x 1 35RT3010004010 1.50 1.36 1.50 30 60 0.6 1x3/4 35873010006 1.38 1.38 1.45 25 50 0.6 1 x 3/4 x 3/4 35RT3010006006 1.38 1.31 1.45 35 70 0.6 B A 1 x 3/4 x 1 35RT3010006010 1.50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 35RT3012004 1.34 1.34 1.53 20 40 0.8 1-1/4 x 1/2 x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4 x 3/4 35RT3012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4 x 1 35RT3012010 1.58 1 58 1.67 15 30 1.0 1-1/4 x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35RT3012010006 1 45 1.38 1.63 20 40 0.8 1-1/4x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1-1/2 x 1/2 x 1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1,94 12 24 1.2 1-1/2 x 3/4 35RT3014006 1 52 1.52 1.75 16 32 1.1 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 ' 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1 2 1-1/2 x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-1/2x 1 x 1/2 35RT3014010004 1.44 1.25 1.69 20 40 08 ' 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2x 1 x 1 35RT3014010010 1.65 1.50 1.80 16 32 1 0 1-1/2 x 1 x 1-1/4 35R13014010012 1.82 1.67 1.88 12 24 1.2 D 1-1/2 x 1 x 1-1/2 35RT3014010014 1.94 1.80 1 94 12 24 1.3 U 1-1/2 x 1-1/4 35RT3014012 1.82 1.82 1.88 12 24 1.4 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1 34 1.66 16 32 0.9 C 1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0 T 1-1/2 x 1-1/4 x 1 35RT3014012010 1.65 1.58 1.80 16 32 1 1 1-1/2 x 1-1/4 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3 1-1/2 x 1-1/4 x 1-1/2 35R13014012014 1.94 1.88 1.94 14 28 1.4 L 2 x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5 E 2 x 3/4 35RT3020006 1.60 1.60 1.97 10 20 1.6 2 x 1 35R13020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4 35RT3020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1/4 x 2 35RT3020012020 2.25 2 10 2.25 8 16 2.0 2x1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2 x 1-1/2 x 1/2 35RT3020014004 1.49 1 41 1.88 10 20 1 3 2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4 2 x1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 - 1.5 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1-1/2 35813020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee • Size Part Number A B C Packing Weight /OW IN IN IN IN Inner Master LB y., IC 3/4 x 1 35813006010 1.45 4 1.37 30 60 0.6 -_ I 1 x 1-1/4 35BT3010012 1.67 1 67 1.58 20 40 0.9 41, --_�_m. 1 x 1-1/2 35813010014 1.80 1.65 15 30 1.0 A B 1-1/4 x 1 x 1-1/2 35BT3012010014 1.88 1 80 1.82 15 30 1.2 1-1/4 x 1-1/2 35BT3012014 1.88 1.88 1.82 15 30 1.3 1-1/4 x 2 35813012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 35BT3014012020 2.16 2.10 2.02 10 20 1.8 1-1/2 x 2 358T3014020 2.16 2.16 2.02 8 16 1.8 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com / l Ductile Iron Fittings- Class 300 UL/FM c ® us • Fig. 35CP3-Straight Coupling with Ribs LISTED APPROVED A 0 _ Size Part Number A Packing Weight ���'��I IN IN Inner Master LB I 1/2 35CP3004 1.38 200 400 0.1 3/4 35CP3006 100 200 0.2 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 : 2.00 , 35 f 70 a 0.5 1-1/2 35CP3014 219 50 0.7 2 35CP3020 2 62 15 30 1.2 2-1/2 35CP3024 3 00 9 18 2.2 Fig. 35RC3-Hex Reducing Coupling Size Part Number A Packing Weight IN IN Inner Master LB IA 1 x 1/2 35RC3010004 1.69 80 160 0.3 1 x 3/4 35RC3010006 1.69 60 120 0.4 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 I" 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3-Hex Bushing Size Part Number A Packing Weight B IN IN Inner Master LB ( ) 1 x 1/2 35HB3010004 1.06 180 360 0.2 • 7 i !I, 1x3/4 35H83010006 1.06 180 1 360 0.1 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 111 1-1/2x 1 35HB3014010 1.25 75 150 r 0.4 D 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 U 2 x 1 35HB3020010 1.38 40 0.6 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 C 2 x 1-1/2 35HB3020014 1.38 40 0.6 T I Fig. 35SP3-Square Head Plug L Size Part Number A Packing Weight E IN IN Inner Master LB `w0, 1/2 35SP3004 0.94 600 1200 0.07 �� RC , IA 3/4 35SP3006 1.12 350 700 0.1 11` 1 �I 1 35SP3010 1.25 200 400 0.1 , 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat A Size A Packing Weight � Part Number - .�� IN IN Inner Master LB �� ' \ 35U 3010 2.19 20 40 1.0 1-14 35U 3012 2.50 15 30 1.2 1-' 2 35U 3014 2.62 10 20 1.7 N. 7.7 / 2 35U 3020 3.12 6 12 2.4 SMITH-COOPER INTERNATIONAL1 • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Ductile Iron Fittin:s-Class 300 UL/FM c ® us Fig. 35X 3- Cross LISTED APPROVED A 1< A Size A Packing Weight ;E J Part Number ili IN IN Inner Master LB ,) I �•,..M A 35X 3010 1.50 20 40 9 IN ___1___ 1-1/4 35X3012 1.75 12 24 14 NI 2 35X 3014 1.94 8 16 1 8 ,�, /� �A 2 35X 3020 2.25 6 12 2.8 �N� B B Fig. 35RX3-Reducing Cross ii ll A Size Part Number A B Packing Weight ��� II1 IN IN IN Inner Master LB , 1-114 x 1 35RX3012010 1.67 1.58 5 30 r 1-112 x 1 35RX3014010 1.80 65 12 24 1.2 1.4 A 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 nailiri Fig. 35C 3- Cap - Size Part Number A Packing Weight 1 IN IN Inner Master LB 1/2 35C 3004 0.87 300 600 0.1 0.1 D i A 3/4 35C 3006 0.97 200 1, 400 I I 1` � 1 35C 30 0 1.16 �� �227j 0.2 U 1-114 35C 3012 1.28 70 140 0.4 C 1-1/2 35C 3014 1.33 00 100 0.5 T 2 35C 3020 1.45 25 50 0.8 ' 2-1/2 35C 3024 1.70 - 18 36 1.6 -L E Fig. 35BC3-Beam Clamp ,' -Ai Size A Packing Weight Rit A� 01111 IN Part Number IN Inner Master LB _ � 3/8 35603003 0.75 100 200 0.3 0.5 1/2 35803004 0.75 80 160 0.5 y� SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Warranty and Limitations of Liability SMITH-COOPER INTERNATIONAL(SCI)warrants to its initial purchaser only,that its products which are delivered to this initial purchaser will be of the kind described in the order or price list and will be free of defects in workmanship or material for a period of five years from the date of delivery to our initial purchaser. Should any failure to conform to this warranty appear within five years after the date of the initial delivery to our initial purchaser,SCI will,upon written notification thereof and substantiation that the goods have been stored,installed,maintained and operated in accor- dance with recognized engineering and piping practices and industry standards,correct such defects by suitable repair or replacement (which alternative shall be at the discretion of SCI)of product at SCI's own expense upon return of the defective part to SCI. In the event that SCI elects to replace the defective product,SCI shall pay up to$50 per defective product for total cost of replacement. In the event of multiple claims,such payment shall be no greater than$1,000 for each installation project. This warranty applies only during normal use that meets the above referenced conditions of installation and operation and is absolutely void if the product has been damaged after purchase or if it has been misused,repaired,altered or modified in any manner whatsoever. SCI shall not warranty any of its products if any portion of the product including without limitation,any component,gasket,housing or bolt has been modified,altered,remanufactured or replaced in any manner by any customer,user of the product or third party. Correction of non-conformities,in the manner and for the period of time provided above,shall constitute fulfillment of all liabilities of SCI to our initial purchaser,with respect to the goods,whether based on contract,negligence,strict tort,or otherwise. It is the intention of SCI that no warranty of any kind,whether expressed or implied shall pass through our initial purchaser to any other person or corpora- tion. No returns will be allowed unless prior written permission of SCI is first obtained. Buyers shall be responsible for all costs of transporta- tion as well as a restocking charge. This warranty is exclusively for the benefit of the initial purchaser of this product from SCI and,except to the extent prohibited by ap- plicable law,the foregoing warranty is in lieu of all other warranties,express or implied,including but not limited to warranties of fitness or merchantability. LIMITATIONS OF LIABILITY:SCI shall not under any circumstances be liable for special or consequential damages such as,but not limited to damage to loss of other property or equipment,loss of profits or revenue,cost of capital,cost of purchased or replacement goods, claims of customers of our initial purchaser,any labor cost for repair or replacement of the product or damage caused by the product. The remedies of our initial purchaser,and all others,set forth herein are exclusive,and the liability of SCI with respect to same shall not, except as expressly provided herein,exceed the price of the SCI products on which such liability is based. ©2010 Smith-Cooper International® 84 SMMA'C ■ iTOIQLER$1E1r800106636110067f0 •F.NA S3a•3r]QS8901 56► evywavArtyrohrhopopennom 84 Pipe Hangers Fig. 200 - "Trimline" Adjustable Band Hanger (Cooper B-Line Fig. B317ONF) ®TOLCO Fig. 200F - "Trimline" Adjustable Band Hanger with Felt Lining (Cooper B-Line Fig. B317ONFF) c 0 us Fig. 200C - "Trimline" Adjustable Band Hanger with Plastic Coated (Cooper B-Line Fig. B317ONFC) LISTED Fig. 200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig.200 - 1/2"(15mm)thru 8" (200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications : Function: For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features: ,.� • (1/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe `'� types and protect CPVC plastic pipe from abrasion.Captured design keeps adjusting nut from separating with hanger. Hanger is easily a B installed around pipe. For hanger with non-captured nut order Fig.200S. i, • (21/2" (65mm)thru 8"(2oomm))Spring tension on nut holds it securely in s'/ \t hanger before installation.Adjusting nut is easily removed. a Approvals: Underwriters Laboratories listed(1/2"(15mm)thru 8"(2oomm)) Rg 200-1/2. I4 in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering Approved(FM)(3/4" 2omm thru 8"(2oomm)). Fg.20o-11a20o-2 Fig.ZOD21htoZOOB Y 9 9 PP ( �(� ( ) Conforms to Federal Specifications WW-H-171 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSVMSS SP-69&SP-58, _ Type 10. Maximum Temperature: 650°F(343'C) Finish: Pre-Galvanized.Stainless Steel ,-,r- - (4)materials will be supplied with (2)hex nuts iOr in P lace of a knurl nut. Order By: Figure number and pipe size .aK Designed to meet or exceed requirements of 1 r FM DS 2-0. ∎R: Fig.200 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 7311.-'. . Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) 200-1/2 1/2" (15) 3/8"-16 31/8" (79.4) 25/8" (66.7) 11 (5.0) 200-3/4 3/4" (20) 3/e"-16 31/8" (79.4) 21/2" (63.5) 11 (5.0) 200-1 1" (25) 3/8"-16 33/8" (85.7) 25/8" (66.7) 12 (5.5) 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8" (73.0) 13 (5.9) 200-11/2 11/2" (40) 3/8"-16 37/8" (98.4) 27/8" (73.0) 14 (6.4) 200-2 2" (50) 3/8"-16 41/2" (114.3) 3" (76.3) 15 (6.9) 200-21h 21/2" (65) 3/8"-16 55/8" (142.9) 41/8" (104.7) 27 (12.3) - 200-3 3" (75) 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2" (90) 3/8"-16 73/8" (187.3) 51/4" (133.3) 34 (15.6) 200-4 4" (100) 3/8"-16 73/8" (187.3) 5" (127.0) 35 (16.0) 200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" (158.7) 66 (30.2) 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 20 COOelt B-Line Threaded Accessories Fig. B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig. 103) ®TO.Cf] Fig. B3205L - Threaded Rod (right& left hand threads) Size Range: 3/8"-16 thru 3"-4 rod TL Material: Steel �� \1\�l`111 Function: Recommended for use as a hanger support in hanger assemblies. Rod is threaded on both ends with right hand threads of the length shown.Also TL1� Maximum Temperatureht750 F(399ads specify Fig. 83205E when ordering. \isr' \\\l Thread Size Finish: Plain. Contact Cooper B-Line for alternative finishes and materials. Order By: Figure number,rod size,length and finish Standard Design Load Thread Size Thread Length TL 650°F(343'C) 7501(399 c) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) 83205-3/s x'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-1/2 x'L' 1/2"-13 21/2' (63.5) 1350 (6.00) 1057 (4.70) B3205-5/8 x'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) B3205-3/4 x'1' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) B3205-7/8 x'L' 1/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) For larger sizes consult full line pipe hanger catalog. Fig. ATR - All Threaded Rod (TOLCO Fig.99&Fig. 100) iQ. Size Range: 3/8"-16 thru 11/2"-6 rod in 10'(3.05m)lengths �� n Material: Steel , Maximum Temperature: 750°F(399°C) � . �' Finish: Plain. Contact Cooper B-Une for alternative finishes and materials. ,' ,:w. „u�` Order By: Figure number,rod size,length and finish . Note: Fig.99 is cut to length all threaded rod. Fig. 100 is full length. Part No. Threads Recommended Load Approx.Wt./100 Ft. &Size Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"x'1' 20 240 (1.07) 12 (5.44) ATR 3/8"x'L' 16 730 (3.24) 29 (13.15) . ATR 1/2"x'L' 13 1350 (6.00) 53 (24.04) ATR 5/8"x'L' 11 2160 (9.60) 89 (40.37) ATR 3/4"x'L' 10 3230 (14.37) 123 (55.79) - ATR 7/8"x'L' 9 4480 (19.93) 170 (77.11) For larger sizes consult full line pipe hanger catalog. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 88 COOPER B-Line Beam Clamps Fig. 65 - Reversible Steel C-Type Beam Clamp 3/4" (19.0mm) Throat Opening CT TOLCO Fig. 65XT - Reversible Steel C-Type Beam Clamp 3/411 (19.0mm) Throat Opening (bottom of page) CO us Size Range: LISTED Fig.65 - 1/2"-13 rod sizes,and 5/8"-11 rod sizes Fig.65XT - 3/8"-16 rod size(see below) Material: Steel with hardened cup point set screw and jam nut Function: Recommended for hanging from steel beam where flange thickness does not exceed 3/4" (19.0mm). B Features: All steel construction eliminates structural deficiencies associated with casting type beam clamps. May be used on top or bottom flange of beam.(Beveled lip 101 allows hanging from top flange where clearance is limited.) May be installed with set 4.� E c screw in up or down position.Offset design permits unlimited rod adjustment by W/J/�'ra allowing the rod to be threaded completely through the clamp.Open design permits r inspection of thread engagement. F 4 I� Approvals: Underwriters Laboratories Listed in the USA(UL)and Canada(cUL). VA Exceeds requirements of the National Fire Protection Association (NFPA), pamphlet 13, ��l 3/8"-16 rod will support 1/2" (15mm)thru 4"(loom)pipe 1/2"-13 rod will support thru 8" (200mm)pipe Finish: Plain.Contact Cooper B-Lane for alternative finishes and materials. Set Screw and P Locknut Included Order By: Figure number and finish Fig. 65 Patent#4,570,885 'ca . Part Rod Size B C D E No. A in. (mm) in. (mm) in. (mm) in. (mm) .'1i 65-1/2 1/2"-13 11/2" (38.1) 3/4" (19.0) 1" (25.4) 9/1s" (14.3) 65-5/8 5/8"-11 11/2" (38.1) 3/4" (19.0) 1" (25.4) 9/16" (14.3) Part F Approx. Wt./100 No. in. (mm) Lbs. (kg) 65-1/2 11/4" (31.7) 55 (24.9) 7 65-5/a 11/4" (31.7) 55 (24.9) * Maximum loads for clamp with set screw in up or down position. Fig. 65XT-3/s - Beam Clamp .(5") C us Feature: Extruded holes allows for more thread OOP. LISTED engagement of threaded rod and set screw. 19/16" Weight: Approx.Wt./100 - 28.0 Lbs.(12.7kg) ® (�'') .,R Finish: Plain or Electro-Galvanized 3 j„...-. �Ir�l � . • Order By: Figure number and finish (ta0) �� Approvals: Underwriters Laboratories Listed V�r ` i - (cULus)and FM Approved(FM)for up to 4" j "' 100mm pipe. y.. ( )P Pe• Set Screw and / 7 T ` (a�) Locknut Included 13h.. —. Designed to meet or exceed requirements of (34.9) FM DS 2-0. �—ryl; Ir. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. illIlliMillMillMillIll . COOPER B-Line • Beam Clamps Fig. 69 - Beam Clamp Retaining Strap (Cooper B-Line B3367) ®TOLCO Size Range: 3/a"-16 thru 3/4"-10 rod CO us • 4"(101.6mm)thru 16"(406.4mm)lengths LISTED Note:longer lengths are available consult factory Material: Pre-Galvanized Steel Function: To offer more secure fastening of various types of beam clamps to beam where danger of movement might be expected. NFPA 13 requires the use of retaining straps with all beam clamps installed in earthquake areas.Satisfies requirements of NFPA 13. Important Note: Good installation practice of a retaining strap requires that the strap be held tightly and securely to all component parts of the assembly.Therefore a locking mechanism of some kind,such as a hex for the Fig.69 will provide a more secure reliable installation. 411 Approvals: Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). Approved for use with any listed beam clamp. Finish: Pre-Galvanized Order By: Figure number,length(L),and finish. Note: Minimum return on strap is 1"(25.4mm) For Use With: Any Cooper B-Line or TOLCO beam clamp. N E: U E: m 1s1 Hole Dia. D Length Part No. in. (mm) 69-3/8-L 7/16" (30.1) Specify =isi 69-1/2-L 9/16" (30.1) Specify = ow 69-518-L 11/16" (50.8) Specify 69-3/4-L 13/16" (63.5) Specify as 1�1 E 11 All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. COOPBt B-Llne Air, g10.§01 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 510 CPVC - STEEL - COPPER HANGER o J o SIZE-3/4"thru 3"pipe. MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- Sus 203-EX 4231,EX 2551 FUNCTION-To support horizontal piping-CPVC,Copper or Steel. Hanger in listed mounting positions-Top,Bottom or Side. Also,provides stability on vertical piping. INSTALLATION- Per NFPA 13, 13R, 13D and CPVC manufacturers instructions on top,bottom or side of building element.Space by pipe type. Hanger SPECIAL NOTE: When installing on CPVC sprinkler system pipe: ,III,I Verify that all assembly components are cleaned of any surface oil. FASTENERS- UL Listed per NFPA 13 o in WOOD: 3/4"-3"CPVC pipe-#905 screw-no pre-drill. 3/4"-3"Copper pipe-#905 screw-no pre-drill. 3/4"-3"Steel pipe- 1/4"x11/2"lag screw-no pre-drill. CE• O Stabilize-Only in STEEL-min. 18 GA. 3/4"-3"CPVC pipe- 1/4"or#14 Tek Screw. M- 3/4"-3"Copper pipe- 1/4"or#14 Tek Screw. 3/4"-3"Steel pipe- 1/4"or#14 Tek Screw. FEATURES *Offset edge eliminates abrasion. *Retainer dimples secure hanger to pipe during installation. *Required AFCON#905 screw has 5/16"hex head-included. ORDERING-Part#and pipe size. *CAN ALSO BE USED TO REPLACE-#500 Pipe Strap #520 Tin Strap Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners.resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products.parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind.including but not limited to loss of business or profit.when non-A FCON products have been,or are used. • CAD 1/08 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 511 SIDE MOUNT CPVC - COPPER HANGER r o 0 SIZE-3/4"thru 2"pipe. MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. Side View-For LISTING/APPROVAL- Drawings Below ergs 203-EX 4231,EX 2551 /\/ ---�/�- FUNCTION- Hanger on CPVC and Copper pipe. INSTALLATION-Per NFPA 13, 13R,13D and CPVC manufacturers instructions on top or bottom of beam. Space by pipe type SPECIAL NOTE: When installing on CPVC sprinkler system pipe: l�1� Verify that all assembly components are cleaned of any surface oil. I �/ FASTENERS-UL Listed per NFPA 13. ��J) in WOOD: 3/4"-2"CPVC pipe-#905 screw- no pre-drill. 3/4"-2"Copper pipe-#905 screw- no pre-drill. in STEEL-min. 18 GA. 3/4"-2"CPVC pipe- 1/4"or#14 Tek Screw. 3/4"-2"Copper pipe- 1/4"or#14 Tek Screw. V f FEATURES Hanger-Wood Stud *Offset edge eliminates abrasion. Hanger-Metal Stud *Retainer dimples secure hanger to pipe during installation. *Required AFCON#905 screw has 5/16"hex head- included. ORDERING-Part#and pipe size. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind.including but not limited to loss of business or profit when non-AFCON products have been.or are used. 1/08 • r o0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 513 CPVC - STEEL - COPPER HANGER 14111,.. SIZE-3/4"thru 2"pipe. hi Hanger MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. ,III LISTING/APPROVAL- cQus 203-EX 4231,EX 2551 FUNCTION-To support horizontal piping- CPVC,Copper or Steel. Tab up=Hanger. INSTALLATION- Per NFPA 13, 13R and 13D on Stabilize-Only side or top of beam. Space by pipe type. SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FASTENERS-UL Listed per NFPA 13. W- in WOOD: 1 j1 3/4"-2"CPVC pipe-#905 screw-no pre-drill. ��� 3/4"-2"Copper pipe-#905 screw-no pre-drill. 3/4"-2"Steel pipe- 1/4"xl 1/2"lag screw-no pre-drill. FEATURES *Offset edge eliminates abrasion. *Required AFCON#905 screw has 5/16"hex head- included. ORDERING-Part#and pipe size. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace.restrainer or hanger assembly Be advised the following warranty restriction will apply. DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products.parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind.including but not limited to loss of business or profit,when non-A FCON products have been,or are used. 1/08 *'t1`..`: oz P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 514 #905 #906 OFFSET 1, I C.P.V.C. - STEEL - COPPER �1. '°° HANGER . 1 Y SIZE-3/4"thru 2"pipe. , .1.,.. MATERIAL-Carbon Steel. NO FINISH-Mil.Galvanized.. LISTING/APPROVAL- �"�� O ,� • e®„ 203-EX 4231,EX 2551 �, PATENT-No.6,648,278. 11-3/411., � FUNCTION- Hanger/restrainer for horizontal pipe-C.P.V.C.,Copper or Restraint U Steel. Listed hanger in all 3 mounting positions,i.e.vertical surface and I k both top and bottom of horizontal surface. Listed restrainer providing vertical and lateral restraint. Prevents upward �� movement of pipe that supplies a pendent sprinkler below the ceiling. CO Stabilizes vertical piping by providing horizontal restraint. INSTALLATION- Per N.F.P.A 13, 13R and 13D.Space by pipe type. Install on wood,concrete or steel-See Drawings. Snap over pipe then squeeze strap back allowing pipe to slide freely. . v • 'Si. When #905 threads are exposed in wood,install#906 backing nut. d SPECIAL NOTE:When installing on CPVC sprinkler system pipe: i • Verify that all assembly components are cleaned of any surface oil. FASTENERS- 4 WOOD: UL Listed per NFPA 13 CPVC pipe-#905 screw-no pre-drill. Copper pipe- #905 screw- no pre-drill. 1�1 �1� Steel pipe- 1/4 x xl 1/2"lag screw- no pre-drill. MA__ Restraint Thru 5/8"gypsum board- 1/4"x 2"lag screw. STEEL:UL Listed per NFPA 13-min. 18 GA. CPVC pipe- 1/4"or#14 Tek Screw. Copper pipe- 1/4"or#14 Tek Screw. Steel pipe- 1/4"or#14 Tek Screw. CONCRETE:Required minimum load each fastener a =�D The higher of: 1701bs. or S(wt)12501bs, Restraint ■ FEATURES * 1 1/2"Offset-loose fit allows pipe to slide. _■� *3/4"and 1"pipe size made with common center-line. *Patented design for superior strength. 1111 *Offset edge eliminates abrasion. *AFCON#905 screw listed for wood has 5/16"hex head- included. ORDERING-Part#and pipe size. 1 Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners resulting in a listed sway brace-restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products.parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect.incidental or consequential damages of any kind.including but not limited to loss of business or profit when non-AFCON products have been.or are used. Installation Pictures ' 9/07 • . 7. 7g1OZ P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 515 DOUBLE OFFSET C.P.V.C. HANGER Cik) j ® .° 0 SIZE-3/4"and 1"pipe. r _ MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- coil. 203-EX 4231 PATENT-No.6,702,236 FUNCTION-Hanger/restrainer for horizontal CPVC pipe. INSTALLATION- Per N.P.F.A 13, 13R and 13D. SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FASTENERS-UL Listed per NFPA 13. WOOD:#904 screw- no pre-drill. STEEL: 1/4"or#14 Tek Screw in min.20 GA. FEATURES *Double 1 1/2"offset-loose fit allows pipe to slide. *Center line matches AFCON#514. *3/4"and 1"pipe size have common center-line. *Offset edge eliminates abrasion. *Required AFCON#904 screw has 3/8"hex head- included. ' ORDERING-Part#and pipe size. t� J Specific AICON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners.resulting in a listed sway brace,restrainer or hanger assembly Be advised the following warranty restriction will apply.DISCLAIMER-AFCO.N will NOT warrant against the failure of its products when used in combination with other products.parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable trader any circumstances whatsoever for any direct or indirect.incidental or consequential damages of any kind,including but not limited to loss of business or profit is hen non-A ICON products have been,or are used. Installation CAD • Pictures 8/07 Seismic Bracing Fig. 4L - Longitudinal "In-Line" Sway Brace Attachment ®TOLCO . Size Range: 2" (50mm)through 8"(200mm)IPS. (13 Material: Steel C US LISTED e Function: For bracing pipe against sway and seismic disturbance. Set Bolt 8 Hardware Included Approvals: Underwriters Laboratories Listed in the USA(UL)and •,• /T 5' Canada(cUL)2" (50mm)through 8" (200mm)pipe. - For FM Approval information refer to page 47. ��, Installation Instructions: Fig.4L is the"braced pipe"attachment . a component of a longitudinal sway brace assembly.It is intended to be combined with the "bracing pipe"and Cooper B-Line/TOLCO structural A attachment component to form a complete bracing assembly. NFPA 13 guidelines should be followed. To Install: Place the Fig.4L over the pipe to be braced and tighten B bolts.Then engage"bracing pipe" into jaw opening and tighten set bolt until head snaps off.Jaw attachment can pivot for adjustment to proper brace angle. Finish: Plain.Contact Cooper B-Line for alternative finishes and materials. � Order By: Figure number,pipe size and finish. C •: ./- 4,14. ' \,_, .,/- '� i " :..4110A IF j III 4-Way Riser Brace 1. aY .0-4.4 (plan view) Longitudinal Brace Pipe Max.Rec.Load Approx. Part Size A C D Bolt Size (cULuc) Wt./100 No. in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg) 4L-2 ® (50) 53/8" (136.5) 21/16 En 21/16" (52.4) 1/2"-13 2015 (8.96) 247 (112.0) 4L-21/2 ® (65) 67/16" (163.5) 21/2" Ea 23/4" (69.8) 1/2"-13 2015 (8.96) 253 (114.7) 41-3 ® (80) 7" (177.8) 23/4" (69.8) 31/16" (77.8) 1/2"-13 2015 (8.96) 268 (121.5) 41-4 151 (100) 81/2" (215.9) 33/8" co 311/16" (93.7) 1/2"-13 2015 (8.96) 348 (157.8) 4L-5 1111 (125) 93/4' (247.6) 37/8" (98.4) 43/8" (111.1) 1/2"-13 2015 (8.96) 380 (172.3) 4L-6 6" (150) 111/2" (292.1) ®(127.0) 51/8" (130.2) 1/2"-13 2015 (8.96) 640 (290.3) 4L-8 8" (200) 131/4" (336.5) 55/8" ma 55/8" (142.9) 1/2"-13 2015 (8.96) 728 (330.2) The loads listed are axial loads on the brace.The horizontal load capacity, H,of the brace is: H = F x sin?,where?the installation angle measured from the vertical. Cooper B-Line, Inc.'s("Cooper B-Line")seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components,resulting in a listed seismic bracing assembly.Cooper-B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty,Cooper B-line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 46 COOPER B-Line Seismic Bracing Fig.4L- Longitudinal"In-Line"Sway Brace Attachment ®TOLCO Size Range: 21/2"(65mm)through 8"(200mm)IPS. Material: Steel APPROVED Function: For bracing pipe against sway and seismic disturbance. Set Bolts Hardware Included 01..t4 Approvals: APP roved by Factory Mutual Engineering(FM),�},21/2"(65mm) through 8"(200mm)pipe. ♦,, For UL Listed information refer to page 46. NA E 10T 52 Installation Instructions: Fig.4L is the"braced pipe"attachment component of a longitudinal sway brace assembly.It is intended to be A combined with the"bracing pipe"and Cooper B-Line/TOLCO structural attachment component to form a complete bracing assembly. NFPA 13 and/or FM guidelines should be followed. To Install: Place the Fig.4L over the pipe to be braced and tighten B bolts.Then engage"bracing pipe"into jaw opening and tighten set bolt until head snaps off.Jaw attachment can pivot for adjustment to proper brace angle. Finish: Plain.Contact Cooper B-Line for alternative finishes and materials. c Order By: Figure number,pipe size and finish. Designed to meet or exceed requirements of FM DS 2-8. /lir E III 4-Way Riser Brace (plan view) Longitudinal Brace Pipe 'Max.Design Load(FM) Approx. Part Size A C D Bolt Size 300-44° 450-59° 600-74° 75°-90° Wt./100 No. in. (mm) in. (mm) in. (mm) in. (mm) lbs.l(kN) lbs./(kN) lbs./(kN) lbs./(kN) lbs. (kg) 4L-21/2 21/2' (65) 67/16" (163.5) 21/2 11 23/4" (69.8) 1/2"-13 1030(4.58) 1180(5.24) 1420(6.31) 1590(7.07) 253 (114.7) 4L-3 3" (80) 7" (177.8) 23/4" (69.8) 31/16" (77.8) 1/2"-13 1030(4.58) 1180(5.24) 1420(6.31) 1590(7.07) 268 (121.5) 4L-4 4' (100) 81/2" (215.9) 33/8" Ea 311/16" (93.7) 1/2'-13 530(2.36) 730(3.25) 890(3.96) 990(4.40) 348 (157.8) 4L-5 5" (125) 93/4" (247.6) 37/8" co 43/8" (111.1) 1/2"-13 530(2.36) 730(3.25) 890(3.96) 990(4.40) 380 (172.3) 4L-6 6" (150) 111/2" (292.1) 5" (127.0) 51/8" (130.2) 1/2"-13 530(2.36) 730(3.25) 890(3 96) 990(4.40) 640 (290.3) 4L-8 8" (200) 131/4" (336.5) 55/8" MCI 53/8" (142.9) 1/2"-13 490(2.18) 680(3.02) 830(3.69) 930(4.13) 728 (330.2) FM Approved when used with 1",11/4",11/2"or 2"Sch.40 brace pipe. FM Approved design loads are based on ASD design method. Cooper B-Line,Inc.'s("Cooper B-Line")seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components,resulting in a listed seismic bracing assembly.Cooper-B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty,Cooper B-line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. moral B-Line . . Seismic Bracing Fig. 980 - Universal Swivel Sway Brace Attachment - 3/8" to 3/4" ®TOLCO C CO US Size Range: One size fits bracing pipe 1" (25mm)thru 2"(50mm),Cooper B-Line 12 gauge(2.6mm)channel,and all structural steel up to 1/4" (31.7mm)thick. LISTED Material: Steel �. Function: Multi-functional attachment to structure or braced pipe fitting. 'mil a Features: This product's design incorporates a concentric attachment �. 52 opening which is critical to the performance of structural seismic connections. a NFPA 13 indicates clearly that fastener table load values are based only on 980 �� concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. ® * D Installation: Fig.980 is the structural or transitional attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined A i with the "bracing pipe" and Cooper B-Line/TOLCO"braced pipe" attachment, B Fig. 1000, 1001,2002,4L,4A or approved attachment to pipe to form a complete bracing assembly. NFPA 13 guidelines should be followed. Set Bolt To Install: Place the Fig.980 onto the "bracing pipe".Tighten the set bolt until Included the head breaks off.Attachment can pivot for adjustment to proper brace angle. Mounting Hardware Is Not Included Approvals: —Underwriters Laboratories Listed in the USA(UL)and Canada(cUL). For FM Approval information refer to page 61. . - Note: Fig.980 Swivel Attachment and Fig. 1001,1000,2002,4A or approved { attachment to pipe that make up a sway brace system of UL Listed i� attachments and bracing materials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association(NFPA) .l Finish: Plain. Contact Cooper B-Line for alternative finishes and materials. - Order By: Figure number and finish. Pat.#6,273,372, Pat.#6,517,030, Pat.#6,953,174, Pat.#6,708,930, Pat.#7,191,987, Pat.#7,441,730, Pat. #7,669,806 Fig.980 Fr iI //V Fig.4L • J ®� Lateral Brace .. ? Longitudinal Brace Part Mtg.Hdw. Mounting Hole Max.Design Approx. Number Size A B D Load(cULus) Wt./100 in. (mm) in. (mm) in. (nxn) in. (mm) in. (mm) lbs. (kg) 980-3/8 (9.5) 51/4" (133.3) 17/8" (47.6) 13/32" (10.3) 2765 (12.30) 133 (60.3) 980-1/2* BE (12.7) 51/4" (133.3) 17/8" (47.6) 17/32" (13.5) 2765 (12.30) 132 (59.7) 980-5/8 Ell (15.9) 51/4" (133.3) 17/8" (47.6) 11/16" (17.5) 2765 (12.30) 131 (59.4) 980-3/4 MI (19.0) 51/4" (133.3) 17/8" (47.6) 13/16" (20.5) 2765 (12.30) 130 (58.9) •Standard size. Cooper B-Line, Inc.'s("Cooper B-Line")seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components,resulting in a listed seismic bracing assembly.Cooper-B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty,Cooper B-line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 60 COOPER B-Une M • Seismic Bracing Fig. 1000 - "Fast Clamp" Sway Brace Attachment ®TOLCO Size Range: Pipe size to be braced: 1"(25mm)thru 4" (loomm)40 IPS.* Pipe size used for bracing: 1"(25mm)and 11/4" (32mm)Schedule 40 C (111) US IPS.*Additionally(UL)approved for use with Allied Dyna Flow sprinkler pipe LISTED 0 up to 2" as a restraint device. Maximum horizontal design load is 655 lbs. (2.91 kN)Torque requirement is 6-8 ft./lbs.(8-1ONm). For pipe sizes larger than 4"(loomm)please refer to TOLCO Fig. 1001. m Material: Steel 1. Function: For bracing pipe against sway and seismic disturbance. Features: Field adjustable,making critical pre-engineering of bracing pipe Hardware unnecessary. Unique design requires no threading of bracing pipe.Steel leaf Included spring insert provided to assure installer and inspector necessary minimum torque has been achieved. Installation: Fig. 1000 is the"braced pipe" attachment component of a lateral sway brace assembly. It is intended to be combined with the"bracing pipe"and Cooper B-Line/TOLCO structural attachment component, Fig.980, 910,909 or other approved TOLCO component to form a complete bracing „, assembly. Follow NFPA 13 guidelines. To Install: Place the Fig.1000 over the pipe to be braced,insert bracing pipe through opening leaving a minimum of 1"extension. Brace pipe can be installed on top or bottom of pipe to be braced.Tighten hex nuts until leaf spring is flat. It is recommended that the brace angle be adjusted before hex UL Listed Design Load nuts are fully tightened. 1"(25mm)thru 4"(loomm)pipe size-2015 lbs.(8.96kN) Approvals: Underwriters Laboratories Listed in the USA(UL)and Canada Schedule 10&Schedule 40 Pipe (cUL). For FM Approval information refer to page 63. *The loads listed are axial loads on the brace.The Application Note: Position Fast Clamp and tighten two hex nuts until leaf horizontal load capacity, H,of the brace is: H = F x spring flattens.A minimum of 1' pipe extension beyond the Fig. 1000 is sin?,where?is the installation angle measured recommended. from the vertical. Finish: Plain. Contact Cooper B-Line for alternative finishes and materials. Order By: Order by figure number,pipe size to be braced,followed by pipe Pipe Part Number&Approx.Wt./100 Design i Size 1"(24mm)Brace Pipe 11/4"(32mm)Brace Pipe Load in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (kN) ®® 1000-1 xi 71.6 (32.5) 1000-1 X 11/4 75.8 (34.4) 2015 (8.96) mama 1000-11/4 X 1 74.8 (33.9) 1000-11/4 X 11/4 79.1 (35.9) 2015 (8.96) ® (40) 1000-11/2 X1 77.8 (35.3) 1000-11/2 X 11/4 82.1 (37.2) 2015 (8.96) 1111 (50) 1000-2 X 1 84.1 (38.1) 1000-2 X 11/4 88.4 (40.1) 2015 (8.96) ®m 1000-21/2 X 1 90.2 (40.9) 1000-21/2 X 11/4 94.6 (42.9) 2015 (8.96) -- ® (80) 1000-3 X 1 97.3 (44.1) 1000-3 X 11/4 101.7 (46.1) 2015 (8.96) ® (90) 1000-31/2 X 1 104.0 (47.2) 1000-31/2 X 11/4 108.4 (49.2) 2015 (8.96) MI (100) 1000-4 X 1 110.3 (50.0) 1000-4 X 11/4 114.6 (52.0) 2015 (8.96) Lateral Brace Cooper B-Line, Inc.'s("Cooper B-Line")seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components,resulting in a listed seismic bracing assembly.Cooper-B-Line's warranty for seismic bracing components will be the warranty provided in Cooper B-Line's standard terms and conditions of sale made available by Cooper B-Line,except that,in addition to the other exclusions from Cooper B-Line's warranty,Cooper B-line makes no warranty relating to Cooper B-Line's seismic bracing components that are combined with products not provided by Cooper B-Line. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 62 COOalt B-Line • ES-A-C400/C400N/C400Z Colt Series C400, C400N, C400Z A M E S Reduced Pressure Zone Assemblies FIRE&WATERWORKS Sizes: 21/2" — 10" (65 —250mm) LEAD FREE* i ' t C400 OSY C411011 1111 - T T.- Features The Colt C400, C400N, C400Z Reduced Pressure Zone Assemblies • Extremely Compact Design provide protection to the potable water system from contamination • 70% Lighter than Traditional in accordance with national plumbing codes. The Colt C400, C400N, Designs C400Z are normally used in health hazard applications for protection against backsiphonage, backpressure and the fouling of either check valve. • 304 (Schedule 40) Stainless Steel Housing& Sleeve • Groove Fittings Allow Integral Specifications Pipeline Adjustment The Colt C400, C400N, C400Z Reduced Pressure Zone Assemblies shall • Patented Link Check Provides consist of two independent Link Check modules, a differential pressure Lowest Pressure Loss relief valve located between and below the two modules, two drip • Unmatched Ease of Serviceability tight shutoff valves, and required test cocks. Link Check modules and relief valve shall be contained within a sleeve accessible single housing • Available with Grooved Butterfly constructed from 304 (Schedule 40) stainless steel pipe with groove end Valve Shutoffs connections. Link Checks shall have reversible elastomer discs and in • May be Used for Horizontal or N operation produce drip tight closure against the reverse flow of liquid Pattern Installations caused by backpressure or backsiphonage. Assembly shall be Colt • Replaceable Check Disc Rubber C400, C400N, C400Z as manufactured by the Ames Company. 'The wetted surface of this product contacted by consumable water contains IMPORTANT:INQUIRE WITH GOVERNING AUTHORITIES less than 0.25%of lead by weight. FOR LOCAL INSTALLATION REQUIREMENTS Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. • *,w 'r'6'i www.amesfirewater.com - Configurations Pressure — Temperature • Horizontal Temperature Range:33°F 140°F(0.5°C-60°C) • "Z" pattern horizontal Maximum Working Pressure: 175psi(12.1 bar) • "N" pattern horizontal Note:When installing a drain line on Series C400 backflow preventer use 400/500 air gap.See ES-A-AG/EUTC for additional information. Materials • Housing&Sleeve: 304(Schedule 40)Stainless Steel Available Models • Elastomers: EPDM, Silicone and Buna'N' Suffix: • Link Checks: Noryl®, Stainless Steel NRS - non-rising stem resilient seated gate valves • Check Discs: Reversible Silicone or EPDM OSY - UUFM outside stem and yoke resilient seated • Test Cocks: Bronze Body Nickel Plated gate valves • Pins& Fasteners:300 Series Stainless Steel BFG UUFM grooved gear operated butterfly valves with tamper switch • Springs: Stainless Steel *OSY FxG - Flanged inlet gate connection and grooved outlet gate connection Noryl®is a registered trademark of SABIC Innovative Plastics-Rs". 'OSY GxF-Grooved inlet gate connection and flanged outlet gate connection Approvals 'OSY GxG- Grooved inlet gate connection and grooved outlet gate connection c,,-ow, Available with grooved NRS gate valves-consult factory' ® a ® ® Post indicator plate and operating nut available-consult factory* ASSE C US Approved *Consult factory for dimensions . c US 1013 B64.5 For additional approval information please contact the factory or visit our website at www.amesfirewater.com Dimensions — Weights Li gP� I 0. 1\J rf I`1 C(open) Ay Mak J all I, A __, le.--. . aim. C400 SIZE(ON) DIMENSIONS WEIG iT A C(OSY) C(NRS) 0 G H I J M P C400 C400N NRS OSY NRS OSY in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. lbs. kgs. lbs. kgs. lbs. kgs. • 21/2 65 31 787 163 416 91/4 238 61/2 165 291/26738 211 546 151/2 393 813/16 223 219/6 548 93A6 234 118 54 128 58 126 57 136 62 3 80 31 146 805 181/2 479 101/4 260 61146 170 301/4768 221/4 565 171/2 435 91/46 233 231/2 587 101/2 267 134 61 148 67 147 67 161 73 4 100 331/2 851 221/4 578 123A6 310 7 178 33 838 231/2 597 181/2 470 91546 252 261 673 111/46 284 164 74 164 74 187 85 187 85 . 6 150 44 1118 301 765 16 406 81/2 216 443/41137 333/4 857 233/6 589 13146 332 323/4 832 15 381 276 125 298 135 317 144 339 154 8 200 50 1270 373/4 959 191546 506 91146 246 541/21375 401/4 1032 273A6 697 15'146 399 371/2 943 17346 437 441 200 483 219 516 234 558 253 10 250 571/2 1461 451/4 1162 231346 605 11346 285 66 1676 50 1270 321 826 17546 440 463A 1178 20 508 723 328 783 355 893 405 950 431 Dimensions — Weights r Oil IIik J AIME: ,,_ i . -,. . 1 I. I 1111 [117_, 1 s I c.� _l ili �i trAl Vi_J 0 H P G C400N BFG/C400Z BFG SIZE(DN) DIMENSIONS WEIGHT G H I J M P C400N,C400Z in mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 2 65 321/2 826 21'h 546 151/2 394 91/2 241 2113/,6 555 1111/46 300 67 30 3 80 34 864 221/4 565 165/6 414 _ 101/26 256 231/4 587 121/4 308 70 32 4 100 35% 905 231/2 597 171/46 437 101546 279 2411/46 634 12% 321 87 39 6 150 46' 1181 333/ 857 2012 521 131/2 343 281/2 718 15 382 160 73 PA giul u ILA r ILA D IIUMI'�I .. i"!��;,�;: IiiIIeT r :� �: - iliWilli I I I'=.. C400 BFG SIZE(ON) DIMENSIONS WEIGHT A C 0 P mm in. mm in. mm in. mm in. mm lbs. kgs. 4 100 281/4 730 73/a 197 614 162 912 241 66 30 6 150 37 940 911/6 246 7766 189 141/4 362 122 55 Capacity - C400 BFG * = Rated Flow ** = UL Tested 4" (100 mm) 6" (150 mm) kPa psi * ** kPa psi * ** 172 25 - 110 16 . 138 20 96 14 83 12 103 15 69 10 69 10 55 8 . 41 6 34 5 28 4 14 2 - 0 0 - - 0 0 0 100 200 300 400 500 600 700 800gpm 0 200 400 600 800 1000 1200 1400 1600gpm 0 380 760 1140 1520 1900 2280 2680 30401pm 0 760 1520 2280 3040 3800 4560 5300 60601pm 15 fps 15 fps 4.6 mps 4.6 mps Capacity UUFM Certified Flow Characteristics N&Z Flow characteristics collected using butterfly shutoff valves. See literatue S-Colt-400,500 for gate valve flow characteristics * = Rated Flow ** = UL Tested Horizontal N - Pattern Z- Pattern 21/2" (65mm) 6" (150mm) kPa psi * ** kPa psi * 124 18 **124 18 - - Z 110 16 N 110 16 N 96 14 r 96 14 H 83 12 _ • '„- H 83 12 r 69 10 .� - _- -�` 69 10 z �,., --^� 55 8 ~- 55 ■8 ��� .,- 41 6 - - 41 6 '''',<* r-A 0 50 100 150 200 250 300 350 gpm 0 300 600 900 1200 1500 gpm 0 190 380 570 760 950 1140 1330 Ipm 0 1140 2280 3420 4560 5700 Ipm 15 fps 15 fps 4.6 mps 4.6 mps kPa psi 3" (80mm) 8" (200mm) . 110 16 * ** kPa psi * ** 124 18 Z 96 14 N 110 16 , a° H _ 83 12 Z 96 14 ...rr 83 12 -. 69 10 �_'= = .o_ 69 10 55 8 55 8 `ter_ .. '-----• 41 6 41 6 0 100 200 300 400 500 gpm 0 500 1000 1500 2000 2500 gpm 0 380 760 1140 1520 1900 Ipm 0 1900 3800 5700 7600 9500 Ipm 15 fps 15 fps 4.6 mps 4.6 mps 4" (100mm) 10" (250mm) kPa psi * ** kPa psi * ** 179 26 z 110 16 152 22 r J`` H 96 14 -- I 124 18 83 12 'H 69 10 96 14 � 69 10 ` 55 8 ice_r... �Y._ 41 6 41 6 28 4 - 0 100 200 300 400 500 600 700 800 gpm 0 500 1000 1500 2000 2500 3000 3500 gpm 0 380 760 1140 1520 1900 2280 2660 3040 Ipm 0 1900 3800 5700 7600 9500 11400 13300 Ipm 15 fps fps 4.6 mps mps A M E S °� CERTIFIED 9001-2008 FIRE&WATERWORKS www.amesfirewater.com , *� . A Watts Water Technologies Company USA: Backllow- Tel.(916)928-0123•Fax(916)928-9333 Control Valves- Tel.(713)943-0688•Fax(713)944-9445 Canada lel.(905)332-4090•Fax(905)33-/068 ES-A-C400/C400N/C400Z 1151 ©2012 Ames Fire&Waterworks • MODEL 1000 Ap, ® LJ AN D) ° AIRI TT a 4 I3.OR U. ES AAw" f2Jo cite wow _ P4 Wen fin USA PATENT#4741361 AND OTHER PATENTS PENDING ❑ The AGF Manufacturing Inc. Model 1000 TESTANDRAIN Provides Both The Test Function And The Express Drain Function For A Wet Fire Sprinkler System. ❑ The Model 1000 Complies With All Requirements Of NFPA-13, NFPA-13R, And NFPA-13D. ❑ The Model 1000 TESTANDRAIN Is A Single Handle Ball Valve That Is Light Weight And Compact, Includes A Tamper Resistant Test Orifice, Integral Tamper Resistant Sight Glasses, And Is 300 PSI Rated. ❑ Available In A Full Range Of Sizes From 3/4" To 2" NPT & BSPT,With All Specifiable Orifice Sizes 3/8", 7/16", 1/2", 17/32", 5/8" (ELO), & 3/4" (ESFR). ❑ The Orifice Size Is Noted On The Indicator Plate And The Valve Is Tapped For A Pressure Gauge. ❑ Locking Kit Available Which Provides Superior Vandal Resistance And Prevents Unintentional Alarm Activation. ,tit Our ew AUtOcgO ON\ on the Internet `rifo„ at www.testandrain.com 10/00 . . - - U ®L MODEL 1000 300 PSI . AG qi "L I ---- 0 I, 0 AN DI_ I a 3/4" 1" 1 1 /4" 1 1/2" 2" PLAN VIEW FRONT VIEW/VERTICAL INSTALLATION A r 1 FROM BRANCH 1• 0 11 GAUGE INLET_ � J l / PROVIDED I..D TO DRAIN �� 1 �� C I �(� 1 �" i V �- STREET EL .� col SEM FRONT VIEW/HORIZONTAL INSTALLATION T I� l�TO DRAIN STREET EL /� r'J E ,-I OR PIPE 1 MOM i -'�, TO DRAIN' • RIGHT HAND/STRAIGHT INSTALLATION .-- H- •�elliAl m - TO DRAIN I �I. o o APPROVALS: G n] J UL and ULC Listed i J FM Approved except 3/4" ORIFICE SIZE J NYC-BSA NO.720-87-SM AVAILABLE - 3/8, 7/16, 1/2, 17/32, ELO(5/8)•, ESFR(3/4)' J CA.State Fire Marshall DIMENSIONS-INCHES SIZE ` A B C D E 1 F G H 3/4 r.. 5 1/16 1/2" 2 3/16" 3 5/8" 3 3/8" 13/16 4 9/16 6 3/8" MATERIAL LIST 128mm 37.58mm 55.65mm 93.23mm 85.88mm 45.30mm 117.12mm 162.42mm 1 11 5 1/16" 1 1/2" 2 3/16" 3 5/8" 3 3j8" 1 13/16. 4 9j16. 6 3/6n 128mm 37.58mm 55.65mm 93.23mm 85.88mm 45.30mm 117.12mm 162.42mm PART: MATERIAL: 1 1/4" 1577/0mm 112 1710/r111:' 5.36m6m 108.36mm 82.841 5089mm" 11391.6m ,?2.218/m21m1 HANDLE STEEL STEM ROD BRASS 1 1� r1 6 7/16 m 1 13/161 3 1/� 5 1j16" 3 7/8" 2 5/8" 8 1/4" 10 7/8" BALL C.P.BRONZE 2 163.38mm 45.50mm 81.50mm 127mm 99.18mm 66-97mm 206.63m4m 273.60mm BODY BRONZE VALVE SEAT IMPREGNATED TEFLON 2" 6 7/16" 1 13/16" 3 1/4" 5 1/16" 3 7/8" 2 5/8" 8 1/4" 10 7/8" INDICATOR PLATE STEEL 163.38mm 45.50mm 81.50mm _ 127mm _ 99.18mm 66.97mm 206.63mm 273.60mm HANDLE LOCK SPRING STEEL 'Available on 1 1/4"to 2"size units only. "3/4"UL Listed only. 2'ELO/ESFR IS UL LISTED&FM APPROVED 1 1/4'ELO/ESFR IS UL LISTED UL LISTING EX4019 AGF MANUFACTURING INC. JOB NAME: 100 Quaker Lane •,:∎,:•,:: ; ARCHITECT: Malvern,PA 19355 USA - Telephone:(610)240-4900 ENGINEER: Fax:(610)240-4906 www.testandrain.com MADE IN U.S.A. CONTRACTOR: • Full Port Ball Valve, Forged Brass FPPI� U VU Lc L'sted FM App ro v ed Description .0••0 FPPI's complete line of TrimFit Forged Brass", Full Port Ball Valves feature forged 'f components machined to exacting specifications. Listed for fire sprinkler systems for trim, test or drain applications, our Full Port Ball Valves are rated 600 PSI for sizes 1/2" - 1'/z" IPS and 300 PSI for the 2" size. Each valve is complete with plastic 104) coated valve handle marked as required by UL. Blow out proof stem. Installation Specifications Installation practices consistent with those of the fire sprinkler industry are appropriate for the installation of this product.Always make sure to properly Nomenclature and Material: "hold back"the valve and each component being installed to the valve to prevent Part: Material: over tightening or stressing of the valve body. It is also necessary to make sure Nut Steel all components are in proper alignment in the assembly where the ball valve is Handle Steel Stem Gland Brass* present. Improper alignment of attached components may create stress on the Stem Packing PTFE valve leading to valve failure. Use a suitable thread sealant such as PTFE tape or Stem Brass* PipeFit Thread Sealant Paste with PTFE. Never use tape and paste together. Body Forged Brass" Ball Disc Pack PTFE We do not recommend the use of anaerobic sealants with this product. The Ball Disc Chrome Plated materials used in this sealant type are highly caustic and may cause failure of the Brass or synthetic components present in this product. Forged Brass" End Plug Forged Brass* "UUULC Listed 2R97 Part No.: Size: Take-Out: 06-838-00 1/4" IPS 111/16" DO NOT USE MORE THAN ONE SEALANT TYPE PER THREADED 06-840-00 '/z" 23/46" 06-842-00 3/4" 24'8" CONNECTION. DO NOT OVER TIGHTEN THREADS. OVER TIGHTENING WILL 06-844-00 1" 2'/e" CAUSE LEAKS IN THIS AND OTHER THREADED COMPONENTS. 06-845-00 11/4" 3%16" 06-846-00 11/2" 313/16" 06-848-00 2" 4418" "Full port valves have slightly larger"take out"dimensions than standard port valves. You may need to adjust trim components accordingly. 'Contains lead.Not for use in water systems intended for human 3198 LIONSHEAD AVE consumption. CARLSBAD, CA 92010 TEL+1 760 599-1168 +1 800 344-1822 FAX+1 800 344-3775 ©2012 Fire Protection Products,Inc. C® LISTED USTED APPROVED 11111 V +. • . Three-way Brass Valve 44 r� • '/a" IPS UUULC Listed* 300 psi F P P 1® Description ; ; , The 1/4" IPS three-way female threaded valve is used to facilitate the installation • ■ of sprinkler system pressure gauges.The valve provides for one inlet and • two outlets.This design allows for replacement of the system gauge without , shutting down the water supply to the sprinkler system.This design also allows Authorities' Having Jurisdiction to test system pressure with an additional V gauge through the second outlet. (The second outlet is normally plugged during installation with a'/4" IPS lu i e P�P plug.) Installation Specifications Installation of the three-way valve can be accomplished with normal field installation tools. Make sure the valve is installed according to the flow indication Materials: Seat-Brass arrow that has been cast into the valve body.The most common installation Body-Brass allows for a'/4" IPS nipple between the valve and the water supply being Handwheel-Iron measured. This assures there will be ad-equate spacing for the sprinkler system Sizes: gauge from the riser. Use either PTFE Pipe Thread Sealing Tape or a suitable pipe 1/4"IPS thread sealant such as PipeFit®Thread Sealant Paste with PTFE when installing the valve. Working Pressure: 400 WOG DO NOT OVERTIGHTEN THREADS.OVERTIGHTENING MAY CAUSE VALVE FAILURE. *UUULC Listed 2R97 3198 LONSHEAD AVE TEL+S11 800 344-1822 2 FAX+1 800 344-3775 ©2012 Fire Protection Products,Inc. (L g �� LISTED LISTED IT n U • V TrimFit® Butterfly Valves I A - F P P 1• Description TrimFit® Model BFT(Threaded Butterfly Valve) and Model BFG (Grooved Butterfly Valve) close slowly to prevent water hammer. The butterfly valves are designed to be installed % IP' in any orientation and monitored to signal if the valve is opened or closed. They are r both UL Listed and FM Approved for use in a fire sprinkler system. Features 4.The tamper switch features two Specifications • UL Listed for Fire Protection Use switches: Switch-1 has dual leads on Rated to 300 PSI (UL File Number EX 16319.) the terminals.This switch is used for Switch rated: 10 Amps/115 connection of the supervisory circuit of a VAC-60Hz • FM Approved for Fire Protection 0.5Amps/28 VDC Use listed fire alarm control panel. Indoor/Outdoor Use • Threaded or Grooved Switch-2 has a single lead.This switch is used for connection of auxiliary Materials • Tamper Switch assemblies for equipment. Body: Bronze ASTM 584 indoor or outdoor use 5. All the unused wires need to be 6 • Quarter-Turn valve with slow closing capped with lead nuts and tucked into a Disc:Disc:S S304 and opening mechanism prevents junction box. Handwheel:ASTM A216 WCB water hammer Seat:ASTM D2000 Viton 6.All connections need to be reviewed Indicator: Powder Metal and approved by the appropriate Housing/Cover: Forged Brass jurisdictional authorities. JIS C3771 (Ref.ASTM C37700) 7.A No. 14 green wire is fixed inside the switch housing. It is provided as a Available Sizes Installation ground for the housing. TrimFit®Model BFT(Threaded) 1. The valve can be installed in any 8. The valves are intended for use with 06-500-00 1" orientation in a piping system with ANSI 836.10 Schedule 40 and/or 06-502-00 1 1/4" 06-504-00 1 Y2" standard ASME 81.20.1 NPT or Schedule 80 pipes, sizes 1", 1-/4", 1-1", 06-506-00 2" standard roll or cut grooved pipe. 2" and 2-1". 06-508-00 2 1/2" 2. When threading to pipe, apply PipeFit®or equivalent thread sealant TrimFit®Model BFG(Grooved) or tape. 06-526-00 2" 3. Use a wrench to cramp on the 06-528-00 2 Y2" hexagon end of the valve. 3198 LIONSHEAD AVE NOTE:ALL REPLACEMENT PARTS CA LSB7D, CA9-2010 MUST BE OBTAINED FROM THE +1 800 34a 1e22 MANUFACTURER TO ASSURE PROPER FAX+1 800 344-3775 OPERATION OF THE VALVE,AND TO MAINTAIN APPROVAL OF THE DEVICE. 0 ®2013 Fire Protection Products,Inc.FPPF. LISTED APPIIIT fl) ITfrII. II . It . • TrimFit® Butterfly Valves 1 41 1 FPPI' Wiring Diagram SWITCH SHOWN IN POSITION WITH VALVE FULLY OPEN SWITCH 1 : DUAL LEADS SOLDERED TO SWITCH TABS BLACK SUPERVISORY TO NEXT INDICATOR CIRCUIT OF A LISTED FIRE ALARM NC �'• END-OF-LINE RESISTOR CONTROL PANEL WHITE • COMMON NO RED SWITCH 2 : SINGLE LEADS SOLDERED TO SWITCH TABS ORANGE AUXILIARY EQUIPMENT NC 0. VOLTAGE BLUE Green wire is provided as ground for the switch housing. SOURCE COMMON Switch rating:10.1Amps-125/250VAC-60Hz NO Actual switch application rating: YELLOW 10 Amps/115 VAC-60Hz 0.5 Amps/28 VDC SUPERVISORY TAMPER SWITCH (FOR INDOOR/OUTDOOR USE) I/2'ELECTRICAL Pi CONDUIT El •m 3 x O z A 0 L 7 -T 0 701.T , rn�v N 1 II: 1- Z ` F -y1 1^T /^1 n I C Ic), O bi LUL LISTED JUNCTION BOX Installation must comply with NFPA 13 and NFPA 72. Cap unused leads with wire nuts and tuck into a junction box(not provided). 11 11 11. ' ' . , V 0 TrimFit® Butterfly Valves a. 1 . , FPPI® Dimensions Model BFT (Threaded) I— 4.65" I _._ E. 1::::1-- 1, ifrieepp. ' -- f BUTTEKFLS �� VALVE SAmi ��� �_ -1 4 PEA'' H Rtle F P P I (1. . 1 ' 1 SIZE 1 . 300 CWP ` M I. A SIZE 1 ", 11/4", 11/2", 2", 21/2" SIZE 1 " 1 1/4 " 1 1/2 " 2 " 21/2 A 2.13" 2.63" 2.87" 3.25" 4.49" H 4.94" 5.13" 5.59" 6.13" 6.58" L 1.56" 1.94" 2.19" 2.76" 3.41" M 1.75" 2.17" 2.37" 3.11" 3.78" • Packing Gland with Adjustable Glands shall be accessible for tightening stem seals without the disassembly of the valve or operator. 1► 11 11 ' • I 1 TrimFit® Butterfly Valves FPPIa Dimensions Model BFG (Grooved) 1-4.65" 1 o — • —I — L 1 7 lV r _ l� [ /\/� p p .,.•R�. n rr..� 1 BUTTERFLY ` ��V.aLVE 1-T-1 t g '. 9' '11-4_ BFG P 1:—.) ' — — FPPI' J SIZE 300 CWP P I 0 _i_____.! A SIZE: 2", 21/2" SIZE 2" 21/2 " A 4.09" 4.49" H 6.07" 6.58" P 0.63" 0.63" O 0.31" 0.31" M 2.25" 2.72" L 2.37" 2.87" • Grooved ends to AWWA C606 for steel pipe. • Packing Gland with Adjustable Glands shall be accessible for tightening stem seals without the disassembly of the valve or operator. 111111 I ' IT VSR P POT TER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD . UL,CUL and CSFM Listed,FM Approved,LPCBApproved,For CE Marked(EN12259-5)/VdS Approved model use VSR-EU Service Pressure: 450 PSI(31 BAR)-UL Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)-UL Maximum Surge: 18 FPS(5.5 m/s) Contact Ratings: Two sets of SPDT(Form C) 10.0 Amps at I25/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min.at 24VDC 1cb.. j Conduit Entrances: Two knockouts provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: • NEMA 4/1P54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. IlAWARNING • Temperature Range:40°F-120°F,(4.5°C-49°C)-UL �- • Non-corrosive sleeve factory installed in saddle. • Installation must be performed by qualified personnel and in Service Use: accordance with all national and local codes and ordinances. Automatic Sprinkler NFPA-13 - • Shock hazard.Disconnect power source before servicing.Serious One or two family dwelling NFPA-13D injury or death could result. Residential occupancy up to four stories NFPA-13R • Risk of explosion.Not for use in hazardous locations.Serious National Fire Alarm Code NFPA-72 injury or death could result. Optional: Cover Tamper Switch Kit,Stock No.0090148 General Information Drain the system and drill a hole in the pipe using a hole saw in a slow The Model VSR is a vane type waterflow switch for use on wet speed drill.(see Fig. 1) sprinkler systems. It is UL Listed and FM Approved for use on steel Clean the inside pipe of all growth or other material for a distance equal pipe;schedules 10 through 40,sizes 2"thru 8"(50 mm thru 200 mm). to the pipe diameter on either side of the hole. LPC approved sizes are 2"thru 8"(50 mm thru 200 mm). See Ordering Roll the vane so that it may be inserted into the hole;do not bend or Information chart. crease it. Insert the vane so that the arrow on the saddle points in the The VSR may also be used as a sectional waterflow detector on direction of the waterflow. Install the saddle strap and tighten nuts large systems. alternately to required torque. (see Fig. 1).The vane must not rub the The VSR contains two single pole,double throw,snap action switches inside of the pipe or bind in any way. and an adjustable,instantly recycling pneumatic retard. The switches Specifications subject to change without notice. are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period Ordering Information of time necessary to overcome the selected retard period. Nominal Pipe Size Model Part Number Enclosure 2" DN50 VSR-2 1144402 The VSR switches and retard device are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant 2 1/2" DN65 VSR-2 1/2 1144425 screws which require a special key for removal. A field installable 3" DN80 VSR-3 1144403 cover tamper switch is available as an option which may be used 3 1/2" - VSR-3 1/2 1144435 to indicate unauthorized removal of the cover. See bulletin number 4" DN100 VSR-4 1144404 5401103 for installation instructions of this switch. 5" - VSR-5 1144405 Installation: See Fig. 1 These devices may be mounted on horizontal or vertical pipe. On 6" DNI50 VSR-6 _ 1144406 horizontal pipe they should be installed on the top side of the pipe 8" DN200 VSR-8 1144408 • where they will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24"(60 cm)of a valve or drain. Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161 •Phone: 800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5401146-REV H PAGE 1 OF 3 12/07 - VSR P POTTER VANE TYPE WATERFLOW . The Symbol of Protection ALARM SWITCH WITH RETARD Fig. 1 COVER TAMPER"S D" Fig.2 Switch Terminal Connections Til MEN DELAY I AN Pt ADILMILD I ROT All,IRF /1�� = Clamping Plate Terminal RETARD AM CI F." KNIMH �1 ,r. FIRM �I�1� OD ror1EAYEfOYEROif F011 POI MIM EU T.M1T 1•' ERTBN°ED.ERtl.VE0= D+R.I r� )',r 1 TIGHTEN .DMER Q RoM� \I ALTERNATELY `` Qy. :ll'*�.I� O 2.mm.2mm MAX �,I011` IMO DNS°ONLY Y4./ USE(2)5180162 ADAPTERS AS SHOWN.ABOVE ��}? DWN Ali] MORONI ON SADDLE ARROW AWARNING v." of wanxtww ' insulated section of a single conductor/' Y should not be looped around the teinal and ROLL PADDLE serve as two separate connections. The wire must OPPOSITE DIRECTION Or WATERnow be severed,thereby providing supervision of the 0R&TIONOP connection in the event that the wire become MATERPLOw dislodged from under the terminal. Failure to �` sever the wire may render the device inoperable risking severe property damage and loss of life. I.__ DWG 011..11. (Flowing water activates device in one direction only.) Installation Requirements —, A CAUTION Model Nominal Pipe Size Nominal Pipe O.D. Hole Size U-Bob Nuts Torque Waterflow switches that are monitoring wet pipe inch nun inch Dun inch mm ft-lb n-rn sprinkler systems should not be used as the sole VSR-2 2 DN50 2.375 603 initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches VSR-2 12 2 12 2.875 73.0 1.25+.125/-.062 33.0±2.0 used for this application may result in unintended VSR-2 1R 2 1/2 DN65 3.000 76.1 discharges caused by surges,trapped air,or short retard times. VSR-3 3 DN80 3.500 88.9 VSR-312 312 4.000 101.6 20 27 VSR-4 4 DN100 4.500 114.3 2.00±.125 50.8±2.0 VSR-5 5 5.563 141.3 VSR-6 6 DNI50 6.625 168.3 VSR-8 8 DN200 8.625 219.1 Fig.3 Typical Electrical Connections Fig.4 Fig.5 1 �, NEGATIVE Break out thin section of cover when wiring both To remove knockouts:Place screwdriver at DC OR H switches from one conduit entrance. inside edge of knockouts,not in the center. AC 1111 _ _ UCA 1 O SHOT 4C +( ' 1:611 Ilri l2 -' '..*, Mit"n ON FlRE PANEL Illid Notes: 4;40o�l\i I. The Model V SR has two switches,one can be used �..'��')� to erase a central station,proprietary or remote ` � �S_ op pop arY �,,_0 / signaling unit,while the other contact is used to `!`•'D j 41 / �� �I is that the electrical entry must be sealed to -,�� . exclude moisture. ‘111■%%\.„104111r11., 3. For supervised circuits see "Switch Terminal Connections"drawing and caution note(Fig.2). \�� "' `S PRINTED IN USA MFG.#5401146-REV H PAGE 2 OF 3 12/07 VSR P POTTER VANE TYPE WATERFLOW • The Symbol of Protection ALARM SWITCH WITH RETARD Compatible Pipe Note:For copper or plastic pipe use Model Nominal Pipe Nominal Pipe Pipe Wall Thickness Model VSR-CF. Size O.D. Schedule 10(UL) Schedule 40(UL) BS-1387(LPC) DN(VDS) inch mm inch mm inch nun inch mm inch nun inch mm VSR-2 2 DN50 2.375 60.3 0.109 2.77 0.154 3.91 0.142 ;.6 0.091 2.3 VSR-2 1/2 212 2.875 73.0 0.120 3.05 0.203 5.16 VSR-2 1/2 DN65 3.000 76.1 0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 88.9 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 VSR-3 1/2 312 4.000 101.6 0.120 3.05 0.226 5.74 VSR-4 4 DN100 4.500 114.3 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 VSR-5 5 5.563 141.3 0.134 3.40 0.258 6.55 VSR-6 6 DNI50 6.625 168.3 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5 Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction(manufacturer recommends quarterly or more frequently). If provided,the inspector's test valve,that is usually located at the end of the most remote branch line,should always be used for test purposes.If there are no provisions for testing the operation of the flow detection device on the system,application of the VSR is not recommended or advisable. A minimum flow of 10 GPM(38 LPM)is required to activate this device. Maintenance Inspect detectors monthly for leaks. If leaks are found,replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable.In the unlikely event that either component does not perform properly,please order replacement retard switch assembly stock#1029055.There is no maintenance required,only periodic testing and inspection. Removal • To prevent accidental water damage,all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector,then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers,roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • Lift detector clear of pipe. Important Notice Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Mounting Dimensions 89,0 mm (3.50") GROUND SCREWS 141,2 mm __• • n �i■1�� SO mm(5.56') II___IIII___II �• ■ -•--••U4lOLT NUT (�I RIM U-BOLT WASHER .,j_`•• +11333.4 mm fa-: 1 ' ' (+5-1/4") It PLASTIC PADDLE U-BOLT NOMINAL PIPE DIA.+445 mm(+1-3/4)FOR DN50-01965(2-2-12") NOMINAL PIPE DR.+54.0 mm(+2-I,5)FOR DN80.DN200(3-8") UWCo 1146-6 PRINTED IN USA MFG.#5401146-REV H PAGE 3 OF 3 12/07 . 1 P POTTER BELLS PBA-AC & PBD-DC The Symbol of Protection UL Listed, FM Approved Sizes Available:6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC 12VDC(10.2 to 15.6)Polarized ®Ponrn 24VDC(20.4 to 31.2)Polarized tiMy Service Use: Fire Alarm n2- 0.--7„ rim E." General Signaling p_ tip). Burglar Alarm Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: 4 No. 18 AWG stranded wires 6" BELL SHOWN Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox These vibrating type bells are designed for use as fire, burglar or general signaling devices. They have low power con- sumption and high decibel ratings. The unit mounts on a standard 4" (101mm) square electrical box for indoor use or on a model BBK-1 weatherproof backbox for outdoor applications. Weatherproof backbox model BBK-1, Stock No. 1500001. ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION: SIZE CURRENT TYPICAL dB MINIMUM dB INCHES VOLTAGE MODEL NO. STOCK NO. AT 10 FT. AT 10 FT. (mm) (MAX.) (3m)(2) (3m)(1) 6(150) 12VDC PBD126 1706012 12A 85 76 8(200) 12VDC PBD128 1708012 .12A 90 76 10(250) 12VDC P601210 1710012 .12A 92 76 6(150) 24VDC PBD246 1706024 .06A 87 76 8(200) 24VDC PBD248 1708024 .06A 91 79 10(250) 24VDC PBD2410 1710024 .06A 94 79 6(150) 24VAC PBA246 1806024 .17A 91 76 8(200) 24VAC PBA248 1808024 .17A 94 76 10(250) 24VAC PBA2410 1810024 .17A 94 76 6(150) 120VAC PBA1206 1806120 .05A 92 82 8(200) 120VAC PBA1208 1808120 .05A 99 82 10(250) 120VAC PBA12010 1810120 .05A 99 85 Notes: - - 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. Potter Electric Signal Company•2081 Craig Road,St.Louis,MO.63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT #8850001-REV Q PAGE 1 OF 2 MFG #5400776-12/01 u. I - BELLS PPOTTER PBA-AC & PBD-DC e The Symbol of Protection DIMENSIONS INCHES(mm) FIG. 1 BELLS FIG.2 WEATHERPROOF BACKBOX BOX HAS ONE THREADED 112"CONDUIT ENTRANCE o 10" _11_ O 3 3113- 5' (250) 5 3/4` — (86) (127)ift 8` I (146) (2 ) 6' I I (15D) I l� I I _`ter_ I Li— 33/_. �I 5/8-�(86) (41) 4 1/4` 2 11/16" (68) DWG. /776-1 (108) OWG. 1776-2 FIG.3 WIRING (REAR VIEW) D.C. BELLS (OBSERVE POLARITY) A.C, BELLS RED (IN) AggiElihs. REO(OUT) RIME (IN) Adiabh. WHITE (OUT) FROM CONTROL PANEL � TO NEXT BELL FROM CONTROL PANEL �/OR �' OR END-DF-LINE DR oll PRECEDING BELL RESISTOR PRECEDING BELL BLACK (IN) _ ' BLACK(OUT) BLACK (IN) _�' BLACK(OUT) MIEN ELECTRICAL SUPERVISION IS REODIREO USE IN MO OUT LEADS AS SHOWN. WHEN ELECTRON-SUPERWSLON W REOUREO USE M MO OUT LEADS AS SHOWN. NOTES: NOTES: 1. OBSERVE POLARITY TO RING D.C. BELLS. I, WHEN USING A.C. BELLS. TERMINATE EACH EXTRA WIRE SEPARATELY 2. RED WIRES POSITWE (r) AFTER LAST BELL. 3. BLACK WIRES NEGATIVE (-) 2, ENO-OF-UNE RESISTOR IS NOT REQUIRED ON hC. BELLS. DWG. #776-3 INSTALLATION 1. The bell should be mounted a minimum of 8 ft. (2,4m)from the floor or as close to the ceiling as possible. 2. Removethe gong. . 3. Connect wiring(see Fig. 3). 4. Mount bell mechanism to backbox(bell mechanism must be mounted with the striker pointing down). 5. Reinstall the gong(be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 6. Test all bells for proper operation and observe that they can be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). PRINTED IN USA MKT.#8850001-REV Q PAGE 2 OF 2 MFG.#5400776-12/01 r a Sprinkler Gauge 1 44 ��,v FPP1• Description _________ FPPI pressure gauges feature an impact and corrosion resistant case made from ,% , NN ABS (plastic). Features phosphor bronze bourdon tube movement with white , ,ti , , enameled brass dial face with large numbers for easy reading. Dual scale to 300 i �� PSI/2000Kpa. UUULc Listed and FM Approved. 445 ' '4,I s . F e Applications Standard Features Specifications • Fire sprinkler systems Design • Suitable for all media that will not EN 837-1 &ASME B40.100 Bourdon Tube Material:copper alloy C-type obstruct the pressure system or Sizes attack copper alloy parts 4" (100 mm) Pressure Connection Accuracy class Material:copper alloy '/a" NPT lower mount(LM) Special Features ±3%'3% of span • UL-listed (UL-393), United States (ASME B40.100 Grade B) Movement and Canada Ranges Copper alloy • Factory Mutual (FM) approved 0/80 psi, retard to 250 psi (air) Dial • Reliable and economical 0/300 psi (air, water,air/water) White aluminum with stop pin; Working Pressure black and red lettering Steady: 34 of full scale value Pointer Fluctuating: 3/3 of full scale value Black aluminum Short time:full scale value Operating Temperature Case Black polycarbonate Ambient: -40°F to 140°F (-40°C to 60°C) Window Media: 140°F(+60°C) maximum Snap-in clear polycarbonate Temperature Error Additional error when temperature changes from reference temperature of 68°F(20°C) +0.4% for every 18°F (10°C)rising or falling. Percentage of span. 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL+1 800 344-1822 FAX+1 800 344-3775 NM ©2012 Fire Protection Products,Inc. , ' ® c® MAUI DI A. LISTED LISTED APPROVED w $ Spare Sprinkler Head Storage Cabinet FPPI® Description Fire Protection Products, Inc. Spare Sprinkler Head Cabinets are designed to allow for spare sprinkler head storage as required by NFPA guidelines. The Spare Sprinkler Head Cabinets are available in six configurations.Three head, six head, six head ESFR, twelve head, twenty-four head and thirty-six head. All six styles are manufactured with "knockouts"to accommodate the most common size sprinklers.The shelf is located to allow for the storage of a typical sprinkler head wrench. Each cabinet is finished with a red enamel finish. Each spare head cabinet comes with a hinged door which remains closed to protect the spare sprinklers from the elements and features two holes on the back panel to allow for attachment to most surfaces utilizing the appropriate fasteners. Not intended for exposed or harsh environments. Installation Specifications Select the correct Spare Sprinkler Head Cabinet in accordance with the Automatic Sprinkler Systems Handbook. As per the 1989 Edition the correct Material: Painted Plain Steel number of spare sprinkler is as follows: Finish: 0-300 sprinklers, not less than 6; 300-1000, not less than 12; 1000 or more, Red enamel not less than 24. Stock of spare sprinklers shall include all types and ratings Styles: installed.* 3 Spare sprinklers,Y2 or Y4 6 Spare sprinklers,1 or 3/4 6 Spare, ESFR,1/2, 3/4 or 1" Once the correct Spare Sprinkler Head Cabinet has been selected, installation 12 Spare sprinklers 1/2 or V4 is accomplished by inserting the correct fastener in each of the two holes inside 24 Spare sprinklers the cabinet, securing the cabinet securely to the wall.The insert the correct 36 Spare sprinklers number and type of sprinklers in accordance with the "handbook". `Final determination is subject to approval by the AHJ. 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL+1 760 599-1168 +1 800 344-1822 FAX+1 800 344-3775 ©2012 Fire Protection Products,Inc. 1111 11 ' ' I a Identification Signs •r. ► 444 F P P Description Manufactured from .020" white coated aluminum.All sign types are screen printed with a fade resistant red ink. Each sign is shipped with a clear protective plastic coating which can be re- moved at time of installation. Each sign type meets or exceeds NFPA13 requirements. All signs (except 7" round) are drilled in four corners to allow for easy installation. All signs (except T�_ 7" round) may be installed with sign chain or with any fastener that is suitable for the material s-a"cpRUV that the sign is being attached. The 7" round bell signs are center drilled to allow for installation at-,_ �F directly to the bell gong assembly. Type "A" 9" x 7" Control valve signs are drilled with the same .^Y` #714,p, •4qRM four hole pattern as Type "B" 6" x 2" signs to allow for attachment of Type "B" to Type"A". ,— � s Installation Specifications Installation of aluminum signs is accomplished by several methods. The most common installation procedure is to use #16 Single Jack chain to hang the Material: .020" aluminum with sign on the area being identified. Since all of the above mentioned signs are removable plastic coating predrilled at all four corners, the last link of the chain can be opened and hooked • through the top holes on the signs and hung on the appropriate valve or piping. Sizes: 9 P 9 9 6"x2" The signs may also be fastened to a flat surface with fasteners appropriate to 4"x 6" the base material. (The 9" x 7" Fire Alarm Bell sign must be drilled with a 3/8" hole 5"x 7" if it is to be attached directly to the bell gong.) 9"x 7" 12"x 10" 8.5" x11" 7" Round See current catalog for a full listing of all available signs. 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL+1 760 599-1168 +1 800 344-1822 FAX+1 800 344-3775 ©2012 Fire Protection Products,Inc. TT ,1 ' ' I t A. 4 2-pc Adjustable Sprinkler Escutcheons FPP1' Description The 2-pc adjustable sprinkler escutcheon(canopy)has been designed to provide an aesthetically pleasing concealment of the sprinkler piping servicing the individual sprinkler head. The standard sprinkler escutcheon (canopy) has a full 2" of field adjustment, making it possible to accommodate minor irregularities in ceiling to sprinkler head location.This assures complete concealment of the ceiling penetration allowing only the sprinkler to be exposed. Flush and Semi-flush skirts feature an adjustment range of 0-11/4". Skirt are manufactured with two raised reliefs allowing for increased friction between the two parts when installed.This sprinkler escutcheon (canopy) is available in two standard thread sizes and four standard finishes. Special threads and finishes are available. Installation Specifications Proper installation of the sprinkler escutcheon can be accomplished with tools ordinarily found on the job site.The installer must make sure that the reducing Type: 2-pc Adjustable w/weep hole _ coupling on the drop nipple does not exceed 2"outside diameter. The face of the coupling must extend at least 1.85" but not more than 2.85" past the finished Standard threads: ' ceiling if the standard skirt is used.Turn the escutcheon cup onto the sprinkler '/2"or 34" IPS threads then install the sprinkler into the reducing coupling using the manufacturers Material: sprinkler installation instructions.After the finished ceiling is installed, push the skirt .020"cold rolled steel over the cup so that it is flush against the ceiling. Upon system activation, leaks Standard finishes: can be detected by observing accumulation of moisture at the"weep" hole. Chrome Brass White Off White CUP&STANDARD SKIRT Depth: Min.2" 0- Max.3" ■ i Base coverage: 31/2" FLUSH/SEMI-FLUSH SKIRTS Profile: (distance from base material) Flush 0.085"(flat) Semi-flush 0.345"(angled) Depth: Min.0" 3198 LIDNSHEAD AVE * Max. 11/a" ` CARLSBAD, CA 92010 TEL+1 760 599-1168 Base coverage: - - +1 800 344-1822 33/4" FAX+1 800 344-3775 ©2012 Fire Protection Products,Inc. tlIt11 Ii . IV Recessed Canopy Coverage Plate F P P Description Recessed Canopy Coverage Extensions provider increased coverage of the recessed canopy flange against the ceiling or wall material where it is installed. The primary purpose is to allow for increased distance between the finished surface of the building interior and the recessed sprinkler assembly.AHJs within certain earthquake zones require a minimum of 1" space between the sprinkler or sprinkler drop and the material it penetrates. Can also be used to provide coverage for oversized holes cut in finish material from previous sprinkler placements. Fits most existing recess sprinkler canopies and is compatible with all FPPI Recessed Canopys. Installation Specifications No tools are required for installation of the Recessed Canopy Coverage Extension. Simply slide the recessed escutcheon skirt through the ID of the Material: .020" Cold Rolled Steel coverage extension then install or re-install the recessed escutcheon skirt on to the retainer. Press the recessed skirt firmly into place against the interior surface Standard finishes: ' the sprinkler penetrates without causing the interior surface to be moved or Chrome White lifted by the recessed skirt/coverage extension. Follow sprinkler manufacturers instructions regarding the installation of sprinklers in recessed applications. May Coverage: be used either horizontally or vertically. 5"x 115/,s" ID Item Numbers: 01-491 5"Coverage Chrome 01-493 5"Coverage White 3198 LIONSHEAD AVE TER+1760 599-1168 +1 800 344-1822 • FAX+1 800 344-3775 ©2012 Fire Protection Products,Inc. 11 11 TV. • I .