Loading...
Report Matrix of Operation Detail OUTPUTS I FAA Sprinkler Horn Door All HVAC HVAC C.S. C.S. C.S. N 1 MATRIX Display& Bell Strobe Holder Dampers Unit Alarm Supvisry Trouble Sounder Activate Activate Release* Close Shutdown Signal Signal Signal P Water Flow X X X X X X U Pull Station X X X X X Smoke Detector X X X X X Duct Detector X X N/A X Valve Tamper X X FACP Trouble** X X * Door Holders release by floor(zone) ** System Trouble conditions: - Disabled circuit/broken wire/ground fault - Missing device -AC power fail/low battery - Phone line fail/comm fail Matrix of Operation Detail - Elevator Recall (additional to above) OUTPUTS Relay Relay Relay MATRIX Recall Elev Recall Elev Fire Hat N to Alt Main Light P i Smoke-1st Floor Lobby X _ - U . Smoke-2nd Floor Lobby X • Smoke-3rd Floor Lobby X Smoke-4th Floor Lobby X Smoke-Elevator Mech Rm X X • Alarm Points List Detail CID: Alarm Company Customer System Information Stanley Security Pacific Parkway Panel: SK5808 503-968-3300 (Office) 12909 SW 68th Parkway(Bldg B) Radio: AES 7788F 877-899-0001 (Monitoring) Portland,OR 97223 RJ31X#1: Installer: Lance&Steve Cross St: 72nd Ave RJ31X#2: 1st Floor Zone SLC CS I 5K I Device Zone Location 1 001 5001 Smoke Detector _ 1st Floor Elevator Lobby 4 5002 Smoke Detector 1st Floor West Corridor 1 S003 Smoke Detector 1st Floor East Corridor 1 5004 Smoke Detector 1st Floor South Corridor 1 S005 Smoke Detector 1st Floor South Corridor 1 S006 Smoke Detector 1st Floor South Corridor 3 S007 Smoke Detector 1st Floor North Corridor 3 S008 Smoke Detector 1st Floor North Corridor 3 S009 Smoke Detector 1st Floor North Corridor 2 5010 Smoke Detector 1st Floor FACP Room 4 5011 Smoke Detector 1st Floor Suite#150 1 5012 Smoke Detector 1st Floor Suite#100 S013 5014 5015 S016 4 S017 Duct Smoke 1st Floor Mens Room 4 5018 Duct Smoke 1st Floor Behind Mens Room 2 S019 Duct Smoke 1st Floor Behind Elevators 1 201 M001 Riser Flow 1st Floor South Stairs - 1 M002 Riser Tamper 1st Floor South Stairs 1 M003 Valve Tamper 1st Floor Suite#140 Storage Room 1 M004 Valve Tamper 1st Floor Suite#100 1st Office - 3 M005 Valve Tamper 1st Floor North Stairs 2 M006 Pull Station 1st Floor FACP Room M007 M008 M009 1 M010 SK-RELAY: Door Holders South Hall(2) 1st Floor Electrical Room 4 M011 SK-RELAY: Door Holder Stairs(1) 1st Floor Above ceiling behind door holder M012 M013 M014 M015 M016 M017 Reserved:Duct Relay M018 Reserved:Duct Relay _ M019 Reserved:Duct Relay RLY#1 Panel Relay#1 1st Floor FACP (Trips 24VDC Relay-All Building Dampers) OUT#4 Panel Aux#4 1st Floor FACP(24VDC-Door Holder North Corridor) Alarm Points List Detail CID: Alarm Company Customer System Information Stanley Security Pacific Parkway Panel: SK5808 503-968-3300 (Office) 12909 SW 68th Parkway(Bldg B) Radio: AES 7788F 877-899-0001 (Monitoring) _Portland,OR 97223 RJ31X#1: Installer: Lance&Steve Cross St: 72nd Ave RJ31X#2: 2nd Floor Zone SLC I CS I SK !Device Zone Location 1 S020 Smoke Detector 2nd Floor Elevator Lobby 1 5021 Smoke Detector 2nd Floor Corridor 1 5022 Smoke Detector 2nd Floor Corridor 1 5023 Smoke Detector 2nd Floor Corridor 5024 — - — 5025 5026 1 5027 Duct Smoke 2nd Floor Mens Room 1 5028 Duct Smoke 2nd Floor Behind Mens Room 1 S029 Duct Smoke 2nd Floor Behind Mens Elevators 1 M020 Riser Flow 2nd Floor South Stairs 1 M021 Riser Tamper 2nd Floor South Stairs 1 M022 SK-RELAY: Door Holders(3) 2nd Floor 2nd Floor Electrical Room M023 M024 M025 M026 M027 Reserved:Duct Relay M028 Reserved:Duct Relay M029 Reserved:Duct Relay Alarm Points List Detail CID: Alarm Company Customer System Information Stanley Security Pacific Parkway Panel: SK5808 503-968-3300 (Office) 12909 SW 68th Parkway(Bldg B) Radio: AES 7788F 877-899-0001 (Monitoring) Portland,OR 97223 RJ31X#1: . Installer: Lance&Steve Cross St: 72nd Ave RJ31X#2: 3rd Floor Zone SLC I CS I SK I Device Zone I Location 5 5030 Smoke Detector 3rd Floor Elevator Lobby 5 5031 Smoke Detector 3rd Floor ;Corridor 5 S032 Smoke Detector 3rd Floor Corridor 5 S033 Smoke Detector 3rd Floor _Corridor 5 S034 Smoke Detector 3rd Floor Corridor 5 5035 Smoke Detector 3rd Floor Corridor S036 5 S037 Duct Smoke 3rd Floor Mens Room 5 S038 Duct Smoke 3rd Floor Behind Mens Room 5 S039 Duct Smoke 3rd Floor Behind Elevators 5 M030 Riser Flow 3rd Floor South Stairwell 5 M031 Riser Tamper 3rd Floor South Stairwell 5 M032 SK RELAY: Door Holders(3) 3rd Floor Above Elevator Lobby Double Doors M033 M034 M035 M036 M037 Reserved:Duct Relay M038 Reserved:Duct Relay M039 Reserved:Duct Relay Alarm Points List Detail CID: Alarm Company _ Customer System Information Stanley Security Pacific Parkway Panel: SK5808 503-968-3300 (Office) 12909 SW 68th Parkway(Bldg B) Radio: AES 7788F 877-899-0001 (Monitoring) Portland,OR 97223 RJ31X#1: Installer: Lance&Steve Cross St: 72nd Ave RJ31X#2: 4th Floor Zone SLC I CS I SK Device )Zone Location 5 S040 Smoke Detector '4th Floor Elevator Lobby 5 S041 Smoke Detector 4th Floor Corridor 5 S042 Smoke Detector 4th Floor Corridor 5 S043 Smoke Detector 4th Floor Corridor 5 S044 Smoke Detector 4th Floor Corridor 5 S045 Smoke Detector 4th Floor Corridor S046 5 S047 Duct Smoke 4th Floor Mens Room 5 S048 Duct Smoke 4th Floor Behind Mens Room 5 S049 Duct Smoke 4th Floor Behind Elevators 5 M040 Riser Flow 4th Floor South Stairwell 5 M041 Riser Tamper 4th Floor South Stairwell 5 M042 SK-RELAY-Door Holders(3) 4th Floor Above Elevator Lobby Double Doors M043 M044 _ M045 M046 M047 Reserved:Duct Relay M048 Reserved:Duct Relay M049 Reserved:Duct Relay • Alarm Points List Detail CID: Alarm Company Customer System Information Stanley Security Pacific Parkway Panel: SK5808 503-968-3300 (Office) 12909 SW 68th Parkway(Bldg B) Radio: AES 7788F 877-899-0001 (Monitoring) Portland,OR 97223 RJ31X#1: Installer: Lance&Steve Cross St: 72nd Ave RJ31X#2: 5th Floor Zone SLC CS SK Device Zone Location 5 S050 Smoke Detector 5th Floor Elevator Machine Room S051 S052 S053 5054 S055 S056 S057 5058 5059 5 M050 SK-RELAY: Elevator Recall to Alt 5th Floor Elevator Machine Room 5 M051 SK-RELAY: Elevator Recall to Main 5th Floor Elevator Machine Room 5 M052 SK-RELAY: Elevator Fire Hat 5th Floor Elevator Machine Room 5 M053 SK-RELAY: Alarm Output to Radio 5th Floor Mechanical Room 5 _ M054 SK-RELAY: Trouble Output to Radio 5th Floor Mechanical Room_ 5 M055 5K-RELAY: Supvervisory Out to Radio 5th Floor Mechanical Room 5 M056 Radio Fault 5th Floor Mechanical Room M057 M058 M059 - Global Project Values: S I LENT I Project Name: Pacific Parkway Standby Hours: 24 SS KNIGHT Project ID: Alarm Mins: 5 Prepared By:Lance Sundberg Derating Factor: 1.2 5808 Calculations Date:3/27/2014 Voltage Drop Warning Version 12.30.10 Threshold%: 10 Panel ID: 5808 Model:5808 Add.Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: Volts: 24 VDC Max Panel Current: 6.0 Amps Ckt.# Circuit Name qty Current Draw Wre AWG Ohms Per Length(ft) Actual Volts @ %Drop Standby Alarm &Type 1000 Ft. One-Way Ohms EOL 5808 5808 CTRL Panel 1 0.170 0.325 / SK Photo,Photo-T 22 0.006 0.006 i SK Ion 0.000 0.000 SK Heat,Heat-HT 0.000 0.000 i/ SK Heat ROR 0.000 0.000 % SK Beam,Beam-T 0.000 0.000 / SK _ 'Duct 12 0.003 0.003 SK Acclimate 0.000 0.000 j SK Control 0.000 0.000 SK Relaymon 0.000 0.000 / SK Control-6 0.000 0.000 SK Monitor,Minimon 1 0.000 0.000 SK Monitor-2 4 0.003 0.003 / SK Monitor-10 0.000 0.000 SK Pull-SA,Pull-DA 1 0.000 0.000 SK Relay 9 0.002 0.002 SK Relay-6 0.000 0.000 SK Zone 0.000 0.000 SK Zone-6 0.000 0.000 SK Isolator Module 0.000 0.000 SSB224BI _Isolator Base 0.000 0.000 B200SR Sounder Base 0.000 0.000 SSB224RB Relay Base 0.000 0.000 SSRTS151 Magnetic Remote Test 0.000 0.000 \ SSRTS151KEY Key Activated Test 0.000 0.000 ‘ SSRA100Z Remote LED 0.000 0.000 5860 LCD Remote Annunc 1 0.020 0.025 5824 Serial/Parallel Module 0.000 0.000 5496 ,Power Expander 0.000 0.000 5895XL Power Expander 0.000 0.000 5865-4 LED Annunciator(4G) 0.000 0.000 5865-3 LED Annunciator(3G) 0.000 0.000 5880 LED Driver Module 0.000 0.000 5883 Relay Module 0.000 0.000 #18 Solid 6.39 200 2.56 20.40 0.00% NAC#1 Notification Appl Circuit 0.000 0.000 #18 Solid 6.39 200 2.56 20.25 0.75% NAC#2 Notification Appl Circuit 0.000 0.060 #14 Solid 2.52 0.00 20.40 0.00% NAC#3 Notification Appl Circuit 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% NAC#4 Notification Appl Circuit 0.000 0.000 Total Alarm Current(Amps) Total Standby Current(Amps) 0.205 0.425 Alarm Time In Minutes/60 (5 Mins) Standby Time In Hours 24 0.083 Total Alarm AH Required Total Standby AH Required 4.925 0.035 Command Shortcuts Total Combined AH Required 4.96 Multiply By The Derating Factor 1.20 Configure Circuits Print Page Minimum Battery AmpHours Required 5.95 SILENT Circuit Configuration . Project Information Project Name: Pacific Parkway Project ID: 0 Prepared By: Lance Sundberg Date: 3/27/2014 Ckt. Number: NAC#1 Panel ID: 5808 Ckt. Name: Notification Appl Circuit Use: Notification Appi Circuit V Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 1 SK 5495 Panel Trigger 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 _ 0.000 Ckt. Number: NAC#2 Panel ID: 5808 Ckt. Name: Notification Appl Circuit Use: Notification Appi Circuit _ .• ,, Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 1 Potter 24VDC Bell 0.000 0.060 0.000 0.060 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.060 Ckt. Number: NAC#3 Panel ID: 5808 Ckt. Name: Notification Appl Circuit Use: Notification Appi Circuit V Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number: NAC#4 Panel ID: 5808 Ckt. Name: Notification Appl Circuit Use:' Notification Appl Circuit ■ Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 _ 0.000 • RECEIVED FACP Riser Detail ((( ))) APR 2 2 2014 --> 120 VAC Power by electrician CITY OF TIGARD —II, 14-2 FPLR cable for Horns/Strobes Addressable Devices SLC 5 .► 18-4 FPLR cable for SLC devices (Elevator Mech Room) A BUILDING DIVISION _ _ _ _► 18-4 FPLR cable for controls,relays Radio etwo rk Hi.----- Cat 3 cable or higher for telco lines&data • — Low AC IAI 5th Floor(Roof top) 120 vac 4.1 QI Horn/Strobes-4th Floor SK-5495 4.2 SLC 5 ■DI Horn/Strobes-4th Floor Addressable Devices a NAC4 4.3 or gig Horn/Strobes-Down 4.4 Horn/Strobes-Down 4th Floor 120 vac 3.1 Horn/Strobes-Suite#350 NW SK-5495 3.2 ► 31 Horn/Strobes-Suite#350 South Addressable Devices SLC 5 NAC3 3.3 3.4 ► 3rd Floor Addressable Devices 41 SLC 1 2nd Floor 120 VAC, k 2.1 OI Horn/Strobes-West SK-5495 .;; 2.2 ®1 Horn/Strobes-Suites:#250,#270,#290 NAC2 2.3 ■09 Horn/Strobes-Suite#140 2.4 ► 120 VAC 1.3 SK-5495'' 1.1 ma, Horn/Strobes- NAC 1 1.2 a Horn/Strobes- 1.4 gA Horn/Strobes- Addressable Devices West SLC 4 _— NAC1 Booster Trigger 120 VAC 0.1 Addressable Devices North d SLC 3 0'2 Sprinkler Bell Addressable Devices FACP Rm d SLC 2 SK-5808 Addressable Devices South d SLC FACP 0.3 0.4 ► RLY 1 ►ik 24VDC Relay for 120 VAC Dampers Telco __ Line ° 1 '►�R� t RLY2 ► Telco_ __ Line 2 Fti ABU`; 5860 nunciator 1st Floor INTELLIKNIGHT ACCESSORY 4 Model SK-Relay Intelligent Relay Module To Next Device 4 If Any Wiring to Terminals 3–9 is Not Power + • Limited,the CB500 Barrier is Required.The CB500 Includes a Non-Power Limited Label, n n Which Must Be Placed Over the Power Limited O c O ,� Terminal Information on the Name Plate Label. Relay Common 2 PI• t•. •:II—�JI Normally Closed 2 EI • �•1' I : Normally Open 2 E ;' = ,: – From Compatible FACP Relay Common 1 EC:)• .'�1 •[ ] + or Previous Device Normally Closed 1 E • •, a.• ... 0 R Normally Open 1 Module Does Not Supervise V O 0 0 Controlled Circuits v U U Wiring the SK-Relav Module Specifications End-of-Line Resistance: not used Physical Standby Current: 300 pA max @ 24 VDC (one Height:4.65" communication every 5 sec with LED enabled) Width: 4.25" LED Current: 5.5 mA(with LED latched on) Depth: 1.1" SLC Loop Resistance: 4052 max. Shipping Weight: 6.3 oz(196 g) Relay Contact Ratings 3.0A @ 30 VDC resistive Electrical Operating Voltage: 15–32 VDC 0.9A @ 110 VDC resistive Current Draw: 6.5 mA max (LED on) 0.9A @ 125 VAC resistive Operating Current: 0.5A @ 125 VAC inductive (PF = .35) 230 pA(LED flashing)direct poll 0.7A @ 75 VAC inductive(PF= .35) 255 pA(LED flashing)group poll SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA Is KNIGHT to keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350127 Rev C subject to change without notice. For more information,contact Silent ©2011 Honeywell International Inc. by Honeywell Knight 12 Clintonville Road,Northford,CT 06472-1610 Phone: (800)328- 0103, Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SILENT SK-Relay KNIGHT by Honeywell Intelligent Relay Module The SK-Relay Module is intended for use in intelligent, two-wire systems where the individual address of each module is selected using the built in rotary switches. For more information about the Intelliknight system, or to locate you nearest source, please call 800-328-0103. Description The SK-Relay is an addressable relay module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Relay allows a Silent Knight FACP to switch discrete contacts by code command. The relay contains two isolated `', sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the notification appliance circuit. The SK-Relay ontacts can be used for virtually any normally Y Y Y Y open or normally closed application. Each SK-Relay is programmed with a unique signaling line circuit(SLC) loop address. When an event occurs that controls the SK-Relay, the SK-Relay relay is triggered by the FACP. Installation Features The SK-Relay mounts directly into a 4" square • Two sets of Form C contacts electrical box. The box must have a minimum • Rotary address switches for fast installation depth of 2-1/8".A surface mount electrical box • Contacts are rated for a variety of amps (see Specifications) (System Sensor®PN SMB500) is available from Silent Knight • Panel controlled status LED that flashes green in normal state and is solid red in alarm Compatibility • Relay programming is completely flexible—can be mapped to The SK-Relay is compatible with the following zone conditions IntelliKnight FACP's: 5820XL • Polling LED visible through the cover plate 5808 5700 • Attractive ivory cover plate 5600 (Rev 2.0 or higher) • SEMS screws for easy wiring • UL Listed INTELLIKNIGHT ACCESSORY o- SK-Minimon Intelligent Monitor Module Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable monitor modules Silent Knight SK-Minimon. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight FACPs. The device shall be capable of Styles A and B supervised wiring to the load device. The SK-Minimon shall be installed inside a single gang junction box directly behind the monitored unit. .1 IN OUT 4. '�!i , = ADDRESS 0 1 12 ' TH •3 cree-1:1 Compatible FACP 11 -i I 4 :y 4 1 5 '3 7 $ LOOP 0 0 7 9 TENS ONES - a 4. - 7 a -‹a F 4 o _O O O a i ° I -r- - Other Devices Wiring the SK-Minimon SILENT This document is not intended to be used for installation purposes.We MADE IN AMERICA KNIGHT try to keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All FORM#350133 Rev C specifications are subject to change without notice. For more information, ©2011 Honeywell International Inc by Honeywell contact Silent Knight 12 Clintonville Road, Northford,CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SILENT SK-Minimon KNIGHT by Honeywell Intelligent Mini Monitor Module The SK-Minimon addressable mini monitor modules for use with Silent Knight IntelliKnight fire alarm control panels (FACP). The SK-Minimon is designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103. Description The SK-Minimon is an addressable monitor modules for use with the IntelliKnight fire alarm control panels (FACPs). The SK-Minimon acts as an interface to contact devices, such as waterflow switches and pull stations. t` The SK-Minimon supports Class B �.r+ supervised wiring to the load ` device. Conventional 4-wire smoke �—• . detectors can be monitored for alarm and trouble conditions The SK-Minimon can be mounted in a single gang junction box directly behind the monitored device. Its small size and light SK-Minimon weight allow it to be installed without rigid mounting Specifications Compatibility requirements. The SK-Minimon is compatible with Electrical the following IntelliKnight Systems: Features Standby Current: 400 uA max @ g g y • Single contact monitor 24 VDC with comm. 5820XL • SK-Minimon support for Class B Voltage Range: 15 32 VDC 5808 (Style B) contact monitor wiring End of Line Resistance: 47 k Ohms 5700 5600 (Rev 2.0 or higher) • Small and lightweight size allows Physical SK-FFT for flexible mounting options Dimensions: • Rotary address switches for fast 2.75" W x 1.3" H x 0.5" D installation Weight: 1.2 oz (37 Approvals ( g) pprovals • UL listed Environmental UL approved Operating Temperature: CSFM 32°F — 120°F (0°C—49°C) FM Approved Humidity: 10% —93% non-condensing INTELLIKNIGHT FIRE ALARM CONTROL PANEL a Ittakita SILENT IntelliKnight® 5808 �j KNIGHT APR 2 2 2014 Single Loop Addressable cs�,, � Fire Alarm Control System by Honeywell y Bull The The vemence of an addressable fire alarm control panel in a cost-effective easy to use package. IntelliKnight Model 5808 is a 127 point class leading single loop addressable fire alarm control/communicator system. 5808 provides you with the revolutionary value and performance of addressable sensing technology combined with exclusive, built-in digital communication, distributed intelligent power, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-328-0103. Description The basic 5808 system can be enhanced by adding modules such as 5860 remote annunciator, 5824 serial/parallel printer interface module (for printing system reports), and 5496 intelligent power module. 5808 supports ::, Hochiki or SK protocol devices. 5808 also features a powerful built-in dual line fire communicator that allows for reporting of all system activity to a remote monitoring • location. . Features • Built-in support for up to 99 SK detectors and 99 SK modules. • Built in support for 127 Hochiki SD devices. � ,•; • Up to 125 zones and 125 output groups. • Uses standard wire—no shielded or twisted pair required • Built-in digital communicator. Model 5808 • Central station reporting by point or by zone • Programmable date setting for Daylight Saving • Supports Class B (Style 4) and Class A(Style 6 or 7) Time configuration for SLC. • Plex-2 door option combines a dead front • Distributed, intelligent power. cabinet door with a clear window, limiting • Drift compensation. access to the panel while providing single • 13 pre-programmed output cadences, (including ANSI- button operation of the reset and silence functions. 3.41), and 4 programmable outputs. • Notification circuits can be configured as 2 Class A(Style Integrated dead front panel protects operator Z) or 4 Class B (Style Y), or auxiliary power for resettable, from exposure to electrical components. constant, or door holder power. • The FACP enclosure features a Plexiglass® • Built-in annunciator with 80-character LCD display. viewing window to protect annunciator. • RS-485 bus provides communication to system accessories. • Acknowledge function allows operator to keep • Built-in RS-232 and USB interface for programming via a track of event status. PC. Installation • Upload or download programming, event history, or The 5800 can be surface or flush mounted. detector status via remote or direct connection. • Improvements in SKSS deliver five times faster Compatibility upload/downloads. The 5808 SLC supports multiple device types of the • Built-in synchronization for appliances from AMSECO, same protocol: Gentex®, Faraday, System Sensor®, and Wheelock®. • SK(System Sensor) • One Form C trouble relay rated at 2.5A at 27.4 VDC and • Hochiki SD two Form C programmable relays rated at 2.5A at 27.4 VDC. You cannot mix SD and SK devices on a FACP. INTELLIKNIGHT FIRE ALARM CONTROL PANEL -4.0--, . :-_IIIIIIIIII ' or__ ---s ill . . _Jr .... 11--.. F l fit .: a .�.+an> a....r ....+. ... W �+em.w,i,».a.wa.a,.l . . a...a... 1.- ...aw a... w-i: " 5496• E 4 INE4 ven.5808 Specifications for automatic, manual,waterflow, sprinkler Miscellaneous Accessories Electrical supervisory(DACT non-coded)signalling 5660 Silent Knight Software Suite services. Primary AC: 120 VRMS at 50/60 Hz, UL Listed PC-base software for FACP 2.75A CSFM 7165-0559:0142; programming. Upload and view panel Total Accessory Load: 6A @ 27.4 MEA 429-92-E Vol. XIV account information, event history, and VDC detector status. Notification Power: 6A© 27.4 VDC, S-BUS Accessories power-limited 5670 Silent Knight Software Suite p 58601R Remote Fire Annunciator End-user facility management software Standby Current: 170 mA Features the same 80 character backlit allows viewing of detector status and Alarm Current: 325 mA LCD display keypad and firefighter's key event history via modem or direct Notification &Auxiliary Circuits: switch as the 5808. 5860 is gray and connection. 3A @ 27.4 VDC per circuit,power- 5860R is red. limited Plex-2 Door 5496 Intelligent Power Module Dead front cabinet door with clear Battery Charging Capacity: 7.0-35 A 6 amp notification power expander that window to limit access to the FACP. AH provides four additional power-limited Battery Size: 18 AH max. allowed in notification appliance circuit outputs. RBB FACP. Larger capacity batteries can Remote Battery Box Accessory be housed in an RBB accessory 5880 LED/I0 Module Cabinet. Use if backup batteries are cabinet Features 40 LED outputs, 8 normally open too large to fit into FACP cabinet. dry contact inputs and one piezo output. Dimensions: Physical Flush Mount Dimensions: 5865-3 and 5865-4 16"W x 10" H x 6" D(406 mm W x 254 14.5"W x 24.75" H x 3.5" D Remote LED Annunciator mm H x 152 mm D) Features 30 programmable LED(15 red (36.8 W x 62.9 H x 8.73 D cm) and 15 yellow)outputs and a piezo Hochiki and SK Devices Overall Dimensions: sounder.The 5865-4 adds a silence and See the specification sheets listed 16"W x 26.4" H x 4.65" D reset switch to the package. below for a complete listing of the (40.6 W x 67 H x 11.8 D cm) Hochiki and SK devices. Weight: 28 lbs. (12.8 kg) 5824 Serial/Parallel Printer 53624 Hochiki SD Devices data Interface Module sheet Color: Red Provides one parallel and one RS-232 Telephone Requirements: serial port for connecting a printer to 5808. 53623 SK Device Protocol Devices FCC Part 15 and Part 68 approved Use to print a real-time log of system data sheet Type of Jack: RJ31X(two required) events,detector status reports, and event Approvals history. NFPA 13, NFPA 15, NFPA 16, NFPA 5883 Relay Board 70, &NFPA 72: Central Station; Features 10 general purpose Form C Remote Signalling; Local Protective relays. Used with 5880 module. IntelliKnight&JumpStart are Registered Signalling Systems;Auxiliary Trademarks of Silent Knight Flexput is a Protected Premises Unit; &Water Trademark of Silent Knight Deluge Releasing Service. Suitable . SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA ft keep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are 350386 Rev. H subject to change without notice. For more information,contact Silent Knight ©2011 Honeywell International Inc. by Honeywell 12 Clintonville Road,Northford, CT 06472-1610. Phone:(800)328-0103, Fax: (203)484-7118.www.silentknight.com -Ps 2°1,4- 01301 1 FIRE SYSTEM ACCESSORY 0 SILENT Model 5495 4%ilk Distributed Power Module KNIGHT talk‘ST �G, In an emergency, by Honeywell you need maximum power The 5495 Distributed Power Module by Silent Knight is the most powerful and cost-effective power supply available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensore,Gentex®,AMSECO®, Wheelock and Faraday—what you need to drive power- hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies.And,ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost-effective notification power supply available, you need the 5495. Call Silent Knight today for more information at 1-800-328-0103. Model 5495 to non-essential high-current Distributed Power Module accessories like magnetic door holders The 5495 is a 6 amp notification power Built-in synchronization for expander that provides its own AC appliances from System power connection, battery charging Sensor®,Gentex®,AMSECO®, circuit, and backup battery for use with Wheelock and Faraday fire and security controls such as the Silent Knight Model 5208 Fire Control • Stand alone operation /Communicator.The 5495 is the cost- • Lightweight design adds to ease of effective solution for owerin P 9 installation and reduces shipping notification appliances required by the costs Americans with Disabilities Act(ADA). • Operates with most polarized, UL . The 5495 has built-in ANSI cadence Listed notification devices pattern, which can upgrade older • control panels that lack cadence ANSI Cadence pattern output capability. capability built-in r rn iPr..a:,n Features Connection to Local Fire Control • UL Listed for 6 amps of notification The 5495 may be connected to a local Model 5495 fire control which utilizes Class A or power Class B type notification circuits Distributed Power Module • Power supply's advanced switch operating between 9 and 32 VDC.The mode design reduces damaging control panel's notification circuit is Approvals heat and manages power up to 50% connected to one of the inputs on the • UL Listed more efficiently than other systems 5495. The control panel's notification • MEA 429-92-E Vol XII • Dip switches allow for easy circuit end-of-line resistor is also • CSFM 7300-0559:123 reconfiguration connected across two terminals on the NFPA 72 •• 24 VDC filtered output voltage 5495, which provides supervision • Four power-limited notification between the 5495 and the fire control outputs; 2 Class A or 4 Class B, or 1 panel. Polarized audible and/or visual Class A and 2 Class B notification devices are then connected • Additional continuous auxiliary to the 5495 signal circuits using the Connect new fire panel to output 4.7kfl end-of-line resistors provided. above existing equipment Since the 5495 draws very little power • 3 amps per output circuit from the control, it is possible to • 2 inputs; 2 Class B or 2 Class A connect one 5495 to each notification • Ground fault detector/indicator circuit on the control panel and still • Independent trouble relay provide full supervision of the • AC loss delay option shuts off power notification circuits all the way back to the control panel. FIRE SYSTEM ACCESSORY Model 5495 Distributed Power Module Model 5495 Block Diagram Signal Circuit Output Signal 1 ---- Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power Input Module 5495 Signal 3 (Optional) Signal 4 120 VAC — Aux. Power _ I Trouble Output Local Fire Control (Alternative to notification circuit trouble.) Supervision Current: Input The 5495 supervises a variety of Standby 75 mA voltage range: 9 - 32 VDC functions including: Alarm 205 mA Battery charging • Low AC power Auxiliary capacity: 35.0 AH • Low battery condition power circuit: 1 Ambient temp.: 32° to 120° F • Earth ground fault Notification (0° to 49° C) • Auxiliary output power limit circuits: 4 Mechanical condition Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or configuration: 2 Class A(Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40.64 cm H x output (1 Class A& 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights the 5495 creates a trouble condition on the host control signal Amps per AC power on : Green circuits to which it is connected. the output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow 5495 still maintains the ability to be Notification Ground fault: Yellow activated by the host control. In circuit output: 20.4 to 27.3 VDC Y Aux trouble: Yellow addition, the 5495 provides a Form @ 3.0 amps each, C trouble relay output as an 4.7 lc() EOL Output troubles (1-4): Yellow alternative to using the notification resistor required Ordering Information circuit trouble. on each Class B 5495 Distributed Power Module circuit Electrical Specification No. of inputs 2 AC input: 120 VAC at 2 amps Input Output: 24 VDC at 6 amps configuration: 2 Class B or 2 Class A SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA KNIGHT keep our product information up-to-date and accurate.We cannot cover all NI specific applications or anticipate all requirements.All specifications are FORM#350395 Rev D subject to change without notice. For more information,contact Silent Knight ©2010 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford,CT 06472-7161 Phone: (800)328-0103, Fax:(203)484-7118.www.silentknight.com I 7788F/774 4 F Series =►AE lInteiiNet CORPORATION For Alarm Monitoring Wireless Fire Alarm ommunicators for Features —All models • UL Listed commercial fire alarm appli- AES-In IliNet cations. • Meets NFPA 72 requirements • Direct reporting to AES receiver across IntelliNet wireless mesh net- work • Each Subscriber acts as transmit- 41 0, , ■,.,,�. ter/receiver/repeater kg ;y'r fi%.t_ • Simple and fast activation on network ,, 6•d . .,.1 E..,- •• t • On board status LEDs for easy set up i K'i+Fa s'; r, • 8 programmable zone inputs—7788F • -, • 4 programmable zone inputs and 4 ...mum, :r reverse polarity inputs—7744F • Easy programming via AES handheld 4 i programmer or PC • Rugged metal housing ideal for any commercial fire alarm application rus' Models 7788F/7744F-ULP with 0 IntelliPro Fire also includes Model 7788F • IntelliPro Fire transmits full alarm data udTEO ..----- -_ from virtually any fire alarm panel dig- ital communicator Advanced Wireless Alarm Monitoring • Alarm format support for Contact ID, The AES-IntelliNet mesh radio network offers unmatched reliability and Pulse, or Bosch Modem Ile or Modem speed in delivering wireless alarm signals to a central station without third IIla2 party fees or reliance on networks owned by companies outside the security • Easy installation in AES subscriber and fire alarm industry. AES-7788F/7744F Series Smart Subscriber • Operates in applications with or with- Transceivers provide the wireless communication link between the fire out a phone line alarm panel and the central station receiver. The 7788F/7744F Series is ideal for most commercial fire alarm applications. Each 7788F/7744F Series Subscriber is housed in a full sized, red, locked, steel cabinet and supports Now! ......_.. — .. a range of alarm panel inputs including EOL fire, EOL supervised, and - direct voltage from the panel (non-fire applications). Y�.—. --•' 11'i t ` r'r Supervised Operation II,C AES Smart Subscribers offer fully supervised operation that includes moni- ' - � iii x ,,� toring of operating power(both primary AC power and battery backup)and -. 'r . 9r 'l the connection to the radio network. Each Subscriber"checks in" with the AES central station receiver at least once every 24 hours. The supervision Wireless mesh networking is an innovative technology adopted by check in time can be set for as often as once per minute and, because the many industries with applications central station owns the wireless network, there is no additional cost for air that need to communicate data over time to transmit supervisory signals. a large geographic area with a high level of reliability at a low total cost Full Data Reporting from Alarm Panel Digital Dialer of ownership. i Models 7788F-ULP and 7744F-ULP come equipped with an IntelliPro Fire The advanced design and 2 way Full Data Module (AES-7794)which enables reporting of full alarm data communications capability provides easy installation, expansion, and captured from the fire alarm panel's digital communicator. IntelliPro Fire management when compared to alte supports most alarm communication formats including Contact ID, Pulse, as native communication methods, both well as Bosch Modem Ile and Modem ll1a2. wired and wireless. • I . 7788F/7744F Series 4 SAES IntelliNet CORPORATION For Alarm Monitoring Technical Specifications How to Order 7788F/7744F Series Subscribers Model Description Dimensions Antenna Cut/Communication 7744E 4 Zone Fire Alarm • 13.25°H x 8.5"W x 4.3"D Trouble Output Subscriber with (34cm H x 21.5cm W x 11cm D) • Form C relay; fail secure; rated for 24 4 reverse polarity inputs Weight VDC 1A resistive • Approx. 7 pounds(3.2 kilograms), Reset Button 7744F-ULP 7744F Fire Alarm excludes battery. • Located on main circuit board. Subscriber with IntelliPro Radio Frequency Operating Temperature Fire full data module • Standard Frequency Range: • 0°to 50' C(32°to 122°F) 7788F 8 Zone Fire Alarm 450-470MHz(others available) Storage Temperature Subscriber • Output Power-2 Watts • -10°to 60° C(14°to 140°F) (others available) 7788F-ULP 7788F Fire Alarm Relative Humidity Subscriber with IntelliPro Antenna • 0 to 85% RHC, Non Condensing Fire full data module • Included 2.5 db tamper resistant antenna mounts on enclosure AES-7794 IntelliPro Fire • Multiple remote antenna options Input 1 Output Connections available • RJ11 connection to AES subscriber for Optional Accessories Power Input module data and power 7041E Subscriber Handheld • 16.5VAC, 40VA(transformer not • RJ11 connector for Handheld Programmer included) Programmer/PC programming Backup Battery • RJ31X Telco connections-T and R 7794 IntelliPro Fire Full Data • Will charge 12V battery up to 7.5 AH. both in and out via terminal strip and Module Requires 12VDC 7.5 AH battery for RJ45 UL 864. • Alarm Panel digital communicator CusT2 =Alarm Signal Inputs (subscriber) T and R both in and out via terminal BAs n• 7788F—8 individually programmable strip and RJ45 �� � zones • Trouble output: Form C relay detects if • 7744F-4 individually programmable Subscriber is off the network zones and 4 reverse polarity inputs Alarm Formats UL Standards • Support for Contact ID and Pulse • UL 864 Edition 9—Standard for formats as well as Modem Ile and Control Units and Accessories for Fire Modem IIla2 converted to CID Alarm Systems Size • UL 365—Standard for Police Station • 2.8 x 5.0 inches(7.1cm x 12.7cm) Connected Burglar Alarm Units and Power Requirements Systems • 12 VDC nominal-primary and backup • UL 1681 —Standard for Central power provided by the AES Station Burglar Alarm Units 7788F/7744F or other Subscriber AES-IntelliNet"is the industry leader in delivering high quality wireless mesh networks to the fire and security industry in commercial,corporate,government,and educational applications with its broad line of products and advanced network management tools.Users of AES-IntelliNet networks have gained significant revenue,communications,and cost advantages while meeting the high stan- dards of reliability required for the fire and security industry.AES-IntelliNet alarm monitoring systems are deployed at hundreds of thousands of locations in over 150 countries. 47AESIIntelli et CORPORATION For Alarm Monitoring For more information Call 800-AES-NETS(800-237-6387) AES Corporation 1 285 Newbury Street Peabody, MA 01960 USA Copynght 2011 AES Corporation AES-IntelliNet is a registered trademark Tel. +1 978-535-7310 I Fax+1 978-535-7313 I Email info @aes-intellinet.com of AES Corporation Web www.aes-intellinet.com 7788F-7744F/9/7/11R3 INTELLIKNIGHT ACCESSORY SILENT SK-Pull-SA and SK-Pull-DA KNIGHT by Honeywell Intelligent Pull Stations The SK-Pull-SA and SK-Pull-DA are a single action or dual action addressable fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SK-Pull-DA and SK-Pull-SA provide a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Pull-SA is a single action pull station requiring only FIRE . one motion to activate the station. The SK-Pull-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Silent Knight I ♦ DOWN Intelliknight series fire alarm control panels (FACPs). Features • Installer can open station without causing an alarm condition L ©h\hI • Dual-color LED is visible through handle of station blinks .11 0 green to indicate normal operation and remains steady red in an alarm condition SK-Pull-SA • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks FIRE • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms I PUSH IN guidelines (Section 4.1.3[13]) PULLDOWN� • Meets ADA requirement for 5 lbs maximum pull force to active • Shell, door, and handle molded from durable LEXAN® :w' '^ • Reliable analog communications for trouble-free operation • Braille text on station handle SK-Pull-DA • Handle latches in down position and the word Activated Compatibility appears, clearly indicating the station has been pulled The SK-Pull-SA and SK-Pull-DA are compatible • Rotary address switches for fast installation with the following IntelliKnight FACP's: 5600 • UL Listed, including UL 38, Standard of Manually Actuated 5700 Signaling System 5808 5820XL INTELLIKNIGHT ACCESSORY Model SK-Pull-DA and SK-Pull-SA Intelligent Pull Stations Engineering Specifications The contractor shall furnish and install where indicated on the plans,Addressable Pull Stations, Silent Knight model SK-Pull-SA single action pull station or SK-Pull-DA, dual action pull station. SK-Pull-DA or SK-Pull-SA meet the ADAAG controls and operating mechanisms guidelines, and the ADA requirements for a 5 lb. maximum pull force to activate the pull station. Class A StC � .? OUT Class B C°mpattbte FACP ( 91 : L n 1 1,rll 3 i ® et s s e I t 1 Cons A = -.. Mist II MIAs:w - to Wiring SK-Pull-SA&SK-Pull-DA Pull Stations Specifications Electrical Physical Operating Voltage: 15-32 VDC Height: 5.5"(14 cm) Average Operating Current(LED flashing): 300 pA Width:4"(10.2 cm) Wire Gauge: Up to 12 AWG (3.1 mm2) Depth: 5.4 oz. (3.7 cm) Environmental Housing Material: LEXAN polycarbonate resin Operating Temperature 32°— 120°F(0°C—49°C) Bi-Colored LED: Humidity: 10%—93%non-condensing Blinking Green: Normal Steady Red:Alarm Accessories Switch: Single pole, single throw(SPST)normally open (N/O) BG-TR Optional trim ring. switch which closes upon activation of the pull station SB-I/O Surface backbox SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA 10 to keep our product information up-to-date and accurate.We cannot cover KNIGHT all specific applications or anticipate all requirements.All specifications are FORM#350135 Rev B subject to change without notice.For more information,contact Silent Knight 12 Clintonville Road,Northford,CT 06472-1610 ©2012 Honeywell International Inc. by Honeywell Phone:(800)328-0103,Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY t SK-Photo ,,, and i. �,, SK-Photo-T 1 �a. -� Intelligent Photoelectric Smoke Sensors ■3 owl �,,,, - ru► :, rr l The SK-Photo is a photoelectric smoke detector and the SK-Photo-T is a photoelectric smoke detector with thermal. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with Silent Knight IntelliKnight Fire Alarm Control Panels (FACPs). For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103 or in Connecticut, call (203)484-7161. Description • Plug-in mounting provides ease of SK-Photo and SK-Photo-T are plug-in installation type smoke sensors that combine a • Tamper-proof feature available on +. photoelectric sensing chamber with mounting bases addressable analog communications. • Listed for use in duct applications 3R" Point ID capability allows each detector's address to be set with rotary • Rotary address switches for fast .1 address switches, providing exact installation - detector locations for selective • UL Listed _ maintenance when chamber • FM Approved contamination reaches unacceptable levels. Specifications ,, f . SK-Photo and SK-Photo-T have a Physical unique optical sensing chamber that is Height: 2.0"(5.0 cm) engineered to sense smoke produced by a wide range of combustion Diameter:4.1"(10.4 cm) sources. In the SK-Photo-T,dual Shipping Weight: 5.2 oz. (147 g) SK-Photo (Base included) electronic thermistors add 135°F(57°C) Electrical Compatibility thermal technology to maximize Operating Voltage: 15-32 VDC detection. Standby Current: The SK-Photo and SK-Photo-T are compatible with the following Features 300 pA @ 24 VDC Maximum IntelliKnight FACPs: • Sleek, low-profile design Alarm Current: 6.5 mA @ 24 VDC max 5700 • Base included (with LED on) 5808 Environmental 5820XL • Reliable analog communications for Operating Temperature trouble-free operation p g P SK-Photo and SK-Photo-T are SK-Photo: 32°— 120°F (0°C—49°C) compatible with the following detector • Age resistant polymer housing bases: SK-Photo-T: 32°— 100°F(0°C—38°C) • Dual electronic thermistor design on Humidity: 10%—93% non-condensing B210LP (included)6" base the SK-Photo-T B501 2 wire base • Superior EMI resistance for reliability Other Ratings B501BHT-2 Temporal base SK-Photo-T Thermal: Fixed B224RB Relay base • Simple field cleaning for code temperature set point 135°F(57°C) B224B1 Isolator base compliance Velocity: 0—4000 fpm(0—20 m/sec) B501 BH-2 Sounder base • Variety of mounting options to meet SK-Photo Insect Screen Hole Size: any application 0.016"(0.41 mm)nominal • Dual LED indicators for 360°visibility SILENT • Detector transmits signal to indicate ti KNIGHT maintenance is required • Optional remote LED annunciator by Honeywell (System Sensor®PN RA100Z) INTELLIKNIGHT ACCESSORY _ Model SK-Photo and SK-Photo-T Intelligent Photoelectric Smoke 2 Sensors Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent photoelectric smoke sensors Silent Knight SK-Photo or SK-Photo-T with thermal. The combination detector head, and twist-lock base, shall be UL listed and compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with SK-Photo or SK-Photo-T. Base shall be the appropriate twist-lock base part number B210LP (included). The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SK-Photo shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. SIX- 1N OUT co-npstibk"'ACP I.;_. * _ i I I RAICOZ 1Opbor.a1) i ., I ��� 1,,.. ,i i ANNA 11, 1 7111\ i r 16-Ii ii s Or i ‘mil j ■ I I ; e 1, . , , , ..,.,..._.........,...,.....,....,. . .,. ......,.,,,, , , ,, , ,, , , ,,...,.... ,....,..........,.......,.......,..,.....,.... VOW.SK4Ws D.do orMou'+ting Masts SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA glit NI KNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject FORM#350118 Rev A, to change without notice.For more information,contact Silent Knight 12 ©2009 Honeywell International Inc. by Honeywea Clintonville Road, Northford,CT 06472-1610 Phone:(800)328-0103, Fax: (203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY 146 SILENT SK-DUCT KNIGHT Intelligent Air Duct Smoke Detector by Honeywell Detect smoke in air handling systems and air handling equipment with Silent Knight's addressable duct smoke detector The SK-Duct Intelligent air duct smoke detector is used with SK-PhotoR (included) for detecting smoke and products of combustion present in air moving through an HVAC air handling system. When smoke is detected in a duct, the unit communicates the condition to the IntelliKnight control panel. The panel, in turn, depending on programming and wiring, turns off fans, blowers, and other devices. The duct housing allows for mounting of SK-Relay addressable relay module. Now there's even more power and flexibility available to the IntelliKnight family of products! Description The Model SK-Duct Air Duct Smoke Detector utilizes photoelectric technology for the detection of smoke. It provides early detection of smoke and products of combustion present in air moving through HVAC ducts in Commercial and Industrial applications. The SK-Duct is in a heavy duty gray steel back box with a • clear cover. It features a pivoting housing that fits both square and rectangular footprints capable of mounting to a round or rectangular duct. It installs quickly and easily. SK-DUCT The unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4000 feet per minute, Specifications temperatures of-4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing). Physical (Rectangular): 14.38 in (37 cm) Length; Features 5in (12.7 cm) Width; 2.5 in (6.6 cm) Depth • Versatile mounting options: square or rectangular (Square): 7.75 in (19.7cm) Length; configuration 9 in (22.9cm) Width; 2.5 in (6.35cm) Depth • New Cover tamper signal Weight: 1.61b (0.73kg) • LED alarm indication and communication on sensor Environmental head Operating Temperature: -4°F — 158°F • Detects and limits the spread of smoke (-20°C— 70°C) • Rugged steel back box with clear plastic cover Humidity: 0%—95% (non-condensing) • Easy to clean Air Velocity • Large terminal connection screws 100 to 4000 fUmin (0.5—20.3 m/sec.) • Transparent cover for convenient visual inspection • Patented sampling tube installs from front or back of the Electrical (using SK-Photo or SK-Photon) detector with no tools required Operating Voltage: 15-32 VDC • Available space within housing to accommodate Standby Current: 300 pA @ 24 VDC max. mounting of relay module Alarm Current: 6.5 mA @ 24 VDC max • UL listed (with LED on) INTELLIKNIGHT ACCESSORY Model SK-DUCT Air Duct Smoke Detector Engineering Specifications The air duct smoke detector shall be a SK-Duct photoelectric duct smoke detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS151KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12-18AWG wiring. The unit housing shall be capable of mounting a relay module. Ordering Information SK-Duct Intelligent non-relay duct smoke detector M02-04-00 Test Magnet SK-Photo Addressable Photo Detector P48-21-00 Replacement End Cap for Metal SK-PhotoR Addressable Photo Detector with remote test Sampling Tube capability(included with SK-Duct) APA151 Remote annunciator with piezo alarm SK-Relay Addressable Relay Module, must be added if relay function is required, (fits in housing) Important Notes: Accessoriest •The use of either RTS151 or RTS151KEY requires the DST1 Metal Sampling Tube Duct Width up to 1' installation of an accessory coil, DCOIL, sold separately. DST1.5 Metal Sampling Tube Duct Widths 1'-2' Please refer to the SK-Duct installation instructions for DST3 Metal Sampling Tube Duct Widths 2'—4' more information DST5 Metal Sampling Tube Duct Widths 4'—8' •The RTS151/RTS151KEY test coil circuit requires an DST10 Metal Sampling Tube Duct Widths 8'— 12' external 24VDC power supply which must be UL listed. DH4000E-1 Weatherproof Enclosure ETX Metal Exhaust Tube Duct width 1' Accessory Current Loads at 24 VDC RA100Z Remote LED Annunciator DCOIL Duct accessory coil, required if using with Device Standby Alarm SK-Photo and not SK-PhotoR (included)with RA100Z OmA 12mA Max. SK-Duct RTS151 Magnetic Remote Test station RTS151 OmA 12mA Max. RTS151KEY Key-Activated Remote Test station RTS151KEY 12mA 12mA Max. SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA 41k14, to keep our product information up-to-date and accurate.We cannot cover KNIGHT all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent FORM#350122 Rev D Knight 12 Clintonville Road, Northford,CT 06472-1610 ©2010 Honeywell International Inc. by Honeywell Phone: (800)328-0103, Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY 10SILENT SK-Monitor-2 1 KNIGHT by Honeywell Intelligent Dual Monitor Module The SK-Monitor-2 module is capable of monitoring two separate Class B circuits simultaneously, making it ideal for waterflow tamper switch and flow switch monitoring. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor-2 is an addressable monitor module with two initiating circuits for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Monitor-2 acts as an interface to contact devices, such as waterflow switches and pull stations The SK-Monitor-2 supports Class B supervised " wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. SK-Monitor-2 Installation Features SK-Monitor-2 mounts directly into a 4" • Monitor two circuits, with unique addresses, square electrical box. The box must have simultaneously a minimum depth of 2-1/8". A surface • Support for Class B wiring mount electrical box (System Sensor® • Fully supervised part number SMB5O0) is available from • Panel controlled status LED that flashes green Silent Knight. in normal state and is solid red in alarm Compatibility • Attractive ivory cover plate The SK-Monitor-2 is compatible with the • Rotary address switches for fast installation following IntelliKnight FACP's: • SEMS screws for easy wiring 5700 • UL Listed 5808 5820XL INTELLIKNIGHT ACCESSORY . Model SK-Monitor-2 Intelligent Dual Monitor Module • To Next Device f• n n , iis a O 0 • O " an tO 0, F-•.) 0 -0-) Compatible FACP U U Two initiating Device Circuits NFPA Style 8 Power Limited 230 pA Max•12 VDC Max SLC n n OUT IN 0 I I w j Ilbi• OW .e • ME I I .%^-..le...• •• • 4 0i° 0 -b1 u u Wiring 8K-Monitor-2 Modules Specifications End-of-Line Resistance:47K 0 Physical Max IDC wiring resistance: 1,5000 Height:4.5" H x 4"W x 1.25" D SLC Line Loop Resistance:400 max. Shipping Weight:6.3 oz(196 g) Environmental Electrical Operating Temperature: 32°F—120°F(0°C—49°C) Operating Voltage: 15—32 VDC Humidity: 10%—93% non-condensing Current Draw(LED on): 6.4 mA max Accessories Operating Current(LED flashing):750 pA SMB500 4"Square Surface Mount Electrical Box This document is not intended to be used for installation purposes.We try MADE IN AMERICA gr SILENT NI to keep our product information up-to-date and accurate.We cannot cover KNIGHall specific applications or anticipate all requirements.All specifications are subject to change without notice.For more information,contact Silent FORM#350124 Rev B Knight 12 Clintonville Road,Northford,CT 06472-1610 ©2009 Honeywell International Inc. by Honeywell Phone:(800)328-0103,Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SILENT SK-Monitor KNIGHT by Honeywell Intelligent Monitor Module The SK-Monitor module provides an interface to contact devices, such as security contacts, waterflow switches, or pull stations. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor is an addressable monitor module for use with Silent Knight IntelliKnight . series fire alarm control panels (FACPs). The SK- µ" Monitor is intended for use in intelligent, two-wire systems, where individual address of each module is selected using the built-in rotary 5;•1 switches. The SK-Monitor supports Class A supervised or Class B supervised wiring to the load device. "*► ' Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. Features _ _ • Single contact monitor • Support for Class A and Class B wiring • Fully supervised • Panel controlled status LED that flashes green SK-Monitor in normal state and is solid red in alarm • Attractive ivory cover plate • Rotary address switches for fast installation The SK-ibility The SK-Monitor is compatible with the • SEMS screws for easy wiring following IntelliKnight FACP's: • UL Listed 5700 5808 Installation 5820XL The SK-Monitor mounts directly into a 4" square electrical box. The box must have a minimum depth of 2-1/8". A surface mount electrical box (System Sensor® PN SMB500) is available from Silent Knight. INTELLIKNIGHT ACCESSORY o- Model SK-Monitor Intelligent Monitor Module To Next Device + n n [do ll e O ,�J Class B espo `* e Me _'' ry 1 I;f Xx.:. 4 I DIG e s From Compatible Silent Knight ■I s 5 + FACP or Previous Device Initiating Device Circuit NFPA Style B V O e 0 f'�, Power Limited 230µA Max a 12 VDC Max (� U U Class A Wiring: To Next Device +f Class B Wiring:I Any Number of UL Listed Contact Closure n n Devices May Be Used Do Not Mix Fire Alarm U ^ O e O initiating Devices.Supervisory.or Security Devices on the Same Nodule. Cu M A i - From Compatible Silent Knight•s ® t - + FACP or Previous Device i EOL Reetslor Is Internal (l li O O at Terminals S&t V U U Wirina SK-Monitor Modules Specifications 5.5 mA(with LED latched on) Physical LED Current: 5.5 mA(with LED latched on)End-of-Line Height:4.5" (11.4 cm) Resistance: 47K CI Width: 4" (10.2 cm) Initiating Device Circuit Wiring Resistance: 1,500 52 max Depth: 1.25" (3 cm) SLC Loop Resistance: 40 n max. Shipping Weight: 6.3 oz(196 g) Environmental Electrical Operating Temperature: 32°F— 120°F (0°C—49°C) Operating Voltage: 15—32 VDC Humidity: 10%—93% non-condensing Current Draw(LED on): 5.0 mA max Operating Current (LED flashing): 375 pA Ordering Information SK-Monitor Monitoring Module Standby Current: 400 pA max @ 24 VDC (one communication every 5 sec with Accessories 47K EOL) SMB500 4" Square Surface Mount Electrical 550 pA max @ 24 VDC (one communication every 5 sec with Box EOL<1K) This document is not intended to be used for installation purposes.We try MADE IN AMERICA SILENT to keep our product information up-to-date and accurate.We cannot cover it KNIGHT all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent FORM#350131 Rev B2 Knight 12 Clintonville Road, Northford,CT 06472-1610 ©2010 Honeywell International Inc. by Honeywell Phone:(800)328-0103, Fax: (203)484-7118. www.silentknight.com Matrix of Operation Detail I FAA Sprinkler Horn Door All HVAC HVAC C.S. C.S. C.S. N MATRIX Display& Bell Strobe Holder Dampers Unit Alarm Supvisry Trouble Sounder Activate Activate Release* Close Shutdown Signal Signal Signal P Water Flow X X X X X X U Pull Station X X X X X T Smoke Detector X X X X X S Duct Detector X X N/A X Valve Tamper X X FACP Trouble** X X * Door Holders release by floor(zone) ** System Trouble conditions: - Disabled circuit/broken wire/ground fault - -Missing device -AC power fail/low battery _ -Phone line fail/comm fail Matrix of Operation Detail - Elevator Recall [additional to above) - r. Relay Relay Relay N * MATRIX Recall Elev Recall Elev Fire Hat to Alt Main Light P Smoke-1st Floor Lobby X U ; Smoke-2nd Floor Lobby X ------ T Smoke 3rd Floor Lobby X ------ s Smoke-4th Floor Lobby X ------ • Smoke-Elevator Mech Rm X X -----