Loading...
Report r ' RECEIVED DN-7101:A•Al-110 • FireWarden-100-2(E) JUL 14 2014 N OTI F 1 E R® Intelligent Addressable FACP '8 9 CITY OF TIGA • with Built-In Comtr,7unciator BUILDING DIVISION by Honeywell Addressable General The Notifier FireWarden-100-2 (NFW2-100) is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter)all on one circuit board. This com- pact intelligent addressable control panel has an extensive list of powerful features. The SLC (Signaling Line Circuit) of the FireWarden-100-2 operates using a Rapid Group Polling communication protocol • technology that polls multiple devices simultaneously for a quicker device response time.This patented technology allows a fully-loaded panel with up to 198 devices to report an inci- dent and activate the notification circuits in under 10 seconds. With this improved polling, devices can be wired on standard twisted,unshielded wire up to a distance of 10,000 feet. (Con- sult the wire table on page 3 for specific installation instruc- tions.) The FireWarden-100-2's quick-remove chassis protects the electronics during construction. The backbox can be installed allowing field wiring to be pulled. When construction is com- pleted, the electronics can be quickly installed with just two bolts. Available accessories include LED,graphic and LCD annunci- ators,and reverse polarity/city box transmitter. o The panel is programmed through the FACP's keypad or via a standard PS-2 computer keyboard, which can be plugged directly into the printed circuit board. This permits easy typing of address labels and other programming information. • System alarm verification selection per detector point. • NOTE:Unless otherwise specified,the terms FireWarden-100-2 is PAS (Positive Alarm Sequence) and presignal delay per used in this document to refer to both the FireWarden-100-2 and point(NFPA 72 compliant). the FireWarden-100-2E FACPs(Fire Alarm Control Panels). NOTE:Only detectors may participate in PAS. Features SLC LOOP: • SLC can be configured for NFPA Style 4,6,or 7 operation. • Listed to UL standard 864,9th edition. • SLC supports up to 198 addressable devices per loop (99 • On-board DACT. detectors and 99 monitor,control,or relay modules). • Four Style Y (Class B) or two Class A (Style Z) NAC cir- • SLC loop maximum length 10,000 ft. (3,000 m.). cults. See wire table on page 3. • Selectable strobe synchronization for System Sensor, Wheelock,and Gentex devices. NOTIFICATION APPLIANCE CIRCUITS(NACS): • Remote Acknowledge, Silence,Reset and Drill via address- • Four onboard NACs with additional NAC capability using able monitor modules. output control modules(NC-100). • Up to 32 annunciators or remote annunciators via EIA- • Silence Inhibit and Auto Silence timer options. 485. • Continuous, March Time, Temporal or California code for • EIA-232 printer/PC interface (variable baud rate) on main main circuit board NACs with two-stage capability. circuit board. • Selectable strobe synchronization per NAC. • Integral 80-character LCD display with backlighting. • 2.5 amps maximum per each NAC circuit. • Real-time clock/calendar with automatic daylight savings NOTE: Maximum or total 24VDC system power shared between control. all NAC circuits and auxiliary power outputs is 3.6 amps. (System • Detector sensitivity test capability(NFPA 72 compliant). power increases to 6.6 amps with optional XRM-24 transformer) • History file with 1,000-event capacity. PROGRAMMING AND SOFTWARE: • • Maintenance alert warns when smoke detector dust accu- • Autoprogram(learn mode)reduces installation time. mutation is excessive. • Custom English labels(per point)may be manually entered • Automatic device type-code verification. or selected from an internal library file. • One person audible or silent walk test with walk-test log and • Two programmable Form-C relay outputs. printout. • 99 software zones. • Point trouble identification. • Continuous fire protection during online programming at the • Waterflow(nonsilenceable)selection per monitor point. front panel. DN-7101:A•09/21/07—Page 1 of 4 • Program Check automatically catches common errors not LDM Graphic Series: Lamp Driver Module series for use linked to any zone or input point. with custom graphic annunciators. FDU-80(Liquid Crystal Display)point annunciator: User interface 80-character, backlit LCD-type fire annunciators capable of LED INDICATORS displaying English-language text. AC POWER(green) NOTE:For more information on Compatible Annunciators for use • (9 ) with the FireWarden-100-2, see the following data sheets (docu- • FIRE ALARM(red) ment numbers)ACM-8R(DN-3558),ACS/ACM Series(DN-0524), • SUPERVISORY(yellow) LDM Series(DN-0551),FDU-80(DN-6820). • ALARM SILENCED(yellow) COMPATIBLE ADDRESSABLE DEVICES • SYSTEM TROUBLE (yellow) All feature a polling LED and rotary switches for addressing. • MAINTENANCE/PRESIGNAL(yellow) NI-100: Addressable low-profile ionization smoke detector. • DISABLED(yellow) NP-100: Addressable low-profile photoelectric smoke detector. • BATTERY FAULT(yellow) • GROUND FAULT(yellow) NP-100T: Addressable low-profile photoelectric smoke detec- tor with thermal sensor. KEYPAD CONTROLS NH-100: Fast-response, low-profile heat detector. • ACKNOWLEDGE/STEP NH-100R: Fast-response, low-profile heat detector with rate- • ALARM SILENCE of-rise option. • DRILL ND-100: Photoelectric low-flow duct smoke detector. • SYSTEM RESET(lamp test) ND-100R: Photoelectric low-flow duct smoke detector with • 16-key alpha-numeric pad(similar to telephone keypad) relay option. • 4 cursor keys NMM-100: Addressable Monitor Module for one zone of nor- • ENTER mally-open dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of- Ordering Options line resistor. Module may be configured for either a Style B (Class B)or Style D(Class A)IDC. NFW2-100(E): 198-point addressable Fire Alarm Control NDM-100: Dual Monitor Module. Same as NMM-100 except it Panel, one SLC loop. Includes 80-character LCD display, sin- provides two Style B(Class B)only IDCs. gle printed circuit board mounted on chassis,and cabinet. NFW2-100R: Same as NFW2-100,exept in a red backbox. NMM-100P: Miniature version of NMM-100. Excludes LED and Style D option. Connects with wire pigtails. May mount in 4XTM Reverse Polarity Transmitter Module: Provides device backbox. supervised output for local energy municipal box transmitter, NZM-100: Similar to NMM-100,but may monitor up to 20 con- alarm,and trouble. ventional two-wire detectors. Requires resettable 24 VDC DP-9692B: Optional dress panel for FireWarden-100-2. power. Consult factory for compatible smoke detectors. TR-CE-B: Trim Ring for semi-flush mounting. NC-100: Addressable Control Module for one Style Y/Z BB-26: Battery backbox, holds up to two 26 AH batteries and (Class B/A) zone of supervised polarized Notification Appli- CHG-75. ances. Mounts directly to a 4.0" (10.16 cm.) electrical box. Notification Appliance Circuit option requires external 24 VDC NFS-LBB: Battery box, houses two 55 AH batteries. to power notification appliances. CHG-75: Battery charger for lead-acid batteries with a rating NC-100R: Addressable relay module containing two isolated of 25 to 75 AH. sets of Form-C contacts, which operate as a DPDT switch. CHG-120: Remote battery charging system for lead-acid bat- Mounts directly to a 4.0"(10.16 cm.)box, surface mount using teries with a rating of 55 to 120 AH. Requires additional NFS- the SMB500. LBB for mounting. NOT BG12LX: Addressable manual pull station with interface NOTE: CHG-120 or CHG-75 required for batteries larger than module mounted inside. 18AH. N100-ISO: Fault Isolator Module. BAT Series: Batteries,see data sheet DN-6933. SMB500: Used to mount all modules except the NMM-100P. XRM-24(E): Optional transformer. Increases system power to NZM-100-6Six-zone interface module. Mount one or two 6.6 amps. Use XRM-24E with FireWarden-100-2E. modules in a BB-2F cabinet (optional). Mount up to six mod- PRT/PK-CABLE: Cable printer/personal computer interface ules on a CHS-6 chassis in a BB-6F. cable. NOTE:For more information on Compatible Addressable Devices PRN-6: UL listed compatible event printer. Uses tractor-fed for use with the FireWarden-100-2, see the following data sheets paper. (document numbers): N100-ISO (DN-6994), NP-100/NP-100T (DN-6995), NI-100(DN-6996), NH-100/NH-100R(DN-6997), ND- COMPATIBLE ANNUNCIATORS 100/ND-100R (DN-7006), NMM-100/NMM-100P/NDM-100/NZM- ACM-SR: Relay module provides 8 Form-C 5.0 amp relays. 100(DN-6999), NC-100/NC-100R(DN-7000), NOT-BG12LX(DN- ACM-8R: and NZM-100-6(DN-60150). ACM Annunciator Series: LED-type fire annunciators capa- ble of providing up to 99 software zones of annunciation.Avail- able in increments of 16 or 32 points to meet a variety of applications. Page 2 of 4—DN-7101:A•09/21/07 r Wiring Requirements While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference. Wire size should be no smaller than 18 AWG (0.78 mm2) and no larger than 12 AWG (3.1 mm2). The wire size depends on the length of the SLC circuit. Use the table below to determine the specific wiring requirements for the SLC. SLC Wire Distance in Feet Wire Size Wire Type Requirements (m) Non-Plenum(FPLR): Genesis 4315, Belden 5020UL Twisted-pair,unshielded 10,000 feet(3,048 m) 12 AWG(3.31 mm2) Plenum(FPLP): Genesis 4515,Belden 6020UL Non-Plenum(FPLR): Twisted-pair,unshielded 8,000 feet(2,438 m) Genesis 4313,Belden 5120UL P ( ) 14 AWG(2.08 mm2) Plenum(FPLP): Genesis 4513,Belden 6120UL Non-Plenum(FPLR): Genesis 4311,Belden 5220UL Twisted-pair,unshielded 4,875 feet(1,486 m) 16 AWG(1.31 mm2) Plenum(FPLP): Genesis 4511,Belden 6220UL Non-Plenum(FPLR): Genesis 4306,Belden 5320UL Twisted-pair,unshielded 3,225 feet(983 m) 18 AWG(0.821 mm2) -Plenum(FPLP): Genesis 4506,Belden 6320UL FireWarden-100-2 Wire Requirements DN-7101:A•09/21/07—Page 3 of 4 SYSTEM SPECIFICATIONS System Capacity 16.65" (42.29 cm.) wide x 5.20" (13.34 cm.) deep. Trim Ring Intelligent Signalling Line Circuits 1 (TR-CE-B): 22.00"(55.88 cm.) high x 19.65"(49.91 cm.)wide. •• Addressable device capacity 198 Shipping Specifications • Programmable software zones 99 Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00"(50.80 cm.) • Annunciators 32 high x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. Electrical Specifications Temperature and Humidity Ranges AC Power: FireWarden-100-2: 120 VAC, 60 Hz, 3.0 amps. This system meets NFPA requirements for operation at 0 - Fire Warden-100-2(E): 240 VAC, 50 Hz, 1.5 amps. Wire size: 49°C/32 - 120°F and at a relative humidity 93% ± 2% RH minimum 14 AWG (2.00 mm2)with 600 V insulation. (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the Battery: Two 12 V 18AH lead-acid batteries. Battery charger useful life of the system's standby batteries and the electronic capacity: 7 - 18 AH. FireWarden-100-2 cabinet holds maxi- components may be adversely affected by extreme tempera- mum of two 18 AH batteries. ture ranges and humidity. Therefore, it is recommended that Communication Loop: Supervised and power-limited. this system and its peripherals be installed in an environment with a normal room temperature of 15-27°C/60-80°F. Notification Appliance Circuits: Each terminal block pro- vides connections for two Style Y (Class B) or one Style Z NFPA Standards (Class A) for a total of four Style Y (Class B) or two Style Z (Class A) NACs. Maximum signaling current per circuit: 2.5 The FireWarden-100-2 complies with the following NFPA 72 amps. End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 Fire Alarm Systems requirements: UL listed)for Style Y (Class B) NAC. Refer to panel documen- -LOCAL (Automatic, Manual, Waterflow and Sprinkler tation and Notifier Device Compatibility Document for listed Supervisory). compatible devices. -AUXILIARY(Automatic, Manual and Waterflow) (requires Two Programmable Relays and One Fixed Trouble Relay: 4XTM). Contact rating:2.0 amps @ 30 VDC (resistive),0.5 amps @ 30 -REMOTE STATION (Automatic, Manual and Waterflow) VAC (resistive). Form-C relays. (Where a DACT is not accepted, the alarm, trouble and Special Application Power(24 VDC Nominal): Jumper supervisory relays may be connected to UL 864 listed selectable (JP4)for conversion to resettable power output. Up transmitters. For reverse polarity signaling of alarm and to 0.5 amps total DC current available from each output. trouble,4XTM is required.) Power-limited. -PROPRIETARY(Automatic,Manual and Waterflow). Four-Wire Resettable Special Application Smoke Detector -CENTRAL STATION (Automatic, Manual and Waterflow, Power(24 VDC nominal): Up to 0.5 amps for powering four- and Sprinkler Supervised). wire smoke detectors. Power-limited. Refer to Notifier Device -AUTO DETECTOR SELF TEST Compatibility Document for listed compatible devices. Remote Sync Output: Remote power supply synchronization Agency Listings and Approvals output. Nominal special application power:24 VDC. Maximum current:40 mA. End-of-Line Resistor:4.7K ohm.Output linked The listings and approvals below apply to the basic FireWar- to NAC 1 control. Supervised and power-limited. den-100-2 control panel. In some cases, certain modules may not be listed by certain approval agencies,or listing may be in Telephone Interface: Requires dedicated business tele- process.Consult factory for latest listing status. phone number with a minimum of 7 volts DC.Obtain dedicated phone line directly from your local phone company. Do not use UL: S635 shared phone lines or PBX(digital)type phone line extensions. • FM approved • CSFM: 7165-0028:235 Cabinet Specifications • MEA: 120-06-E,Volume 2 Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.12" (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x FireWarden® and Notifter® are registered trademarks of Honeywell International Inc.Microsoft®and Windows®are registered trademarks of the Microsoft Corporation. 02007 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. II ! I I 1 We try to keep our product information up-to-date and accurate. c F t F r F We cannot cover all specific applications or anticipate all requirements. • rt MEM II IMIIM111111 All specifications are subject to change without notice. ISSLITY SYSTEMS Made in the U S A For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—DN-7101:A•09/21/07 DN-7001:D•A1-380 NOT-BG 12LX N 4T 1 F 1 E R Addressable Manual Pull Station by Honeywell Intelligent/Addressable Devices General The Notifier NOT-BG12LX is a state-of-the-art, dual-action FIRE (i.e., requires two motions to activate the station) pull station that includes an addressable interface for FireWarden series intelligent control panels,and the NSP-25 panel. Because the NOT-BG12LX is addressable,the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. PUSH IN Features PULL DOWN • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word"ACTIVATED" appears to clearly indicate the station has been operated. ti • Captive screw terminals wire-ready for easy connection to NOT%F%ER SLC loop(accepts up to 12 AWG/3.25 mm2 wire). 1 • Can be surface mounted (with SB-10 or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- gang.double-gang,or 4"(10.16 cm)square electrical box. • Smooth dual-action design. The NOT-BG12LX • Meets ADAAG controls and operating mechanisms guide- Addressable Manual Pull Station lines (Section 4.1.3[13]): meets ADA requirement for 5 lb. maximum activation force. • Highly visible. The BG12TR is usually needed for semi-flush mounting with 4" • Attractive shape and textured finish. (10.16 cm)or double-gang boxes(not with single-gang boxes). • Key reset. Operation • Includes Braille text on station handle. • Optional trim ring(BG12TR). Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word"ACTI- • Meets UL 38. Standard for Manually Actuated Signaling VATED" (in bright yellow) appears at the top of the handle. Boxes. while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the Construction key and pull the door open.This action resets the handle:clos- Shell, door, and handle are molded of durable polycarbonate mg the door automatically resets the switch. material with a textured finish. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual Specifications switch.Two rotary decimal switches allow address settings (1 —99 on NFW2-100/NFW2-100C, 1 —50 for NFW-50/NFW- • Shipping Weight:9.6 oz. (272.15 g) 50C). • Normal operating voltage: 24 VDC. • Maximum SLC loop voltage: 28.0 VDC. Architectural/Engineering • Maximum SLC standby current: 375 NA. Specifications • Maximum SLC alarm current: 5 mA. Manual Fire Alarm Stations shall be non-coded. with a key- • Temperature Range:32°F to 120°F(0°C to 49°C) operated reset lock in order that they may be tested, and so • Relative Humidity: 10%to 93%(noncondensing) designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key.An operated sta- • For use indoors in a dry location tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of Installation red-colored polycarbonate material with clearly visible operat- The NOT-BG12LX will mount semi-flush into a single gang. ing instructions provided on the cover. The word FIRE shall double-gang.or standard 4"(10.16 cm)square electrical outlet appear on the front of the stations in white letters. 1.00 inches box, or will surface mount to the model SB-10 or SB-I/O sur- (2.54 cm) or larger. Stations shall be suitable for surface face backbox. If the NOT-BG12LX is being semi flush mounting on matching backbox SB-10 or SB-I/O;or semi-flush mounted. then the optional trim ring (BG12TR) may be used. mounting on a standard single gang. double gang, or 4"(10.16 cm) square electrical box, and shall be installed DN-7001:D•4/13/2012—Page 1 of 2 within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel,send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information NOT-BG12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian applications.) SB-10: Surface backbox;metal. SB-I/O:Surface backbox; plastic. BG12TR: Optional trim ring. 17021: Keys,set of two. Agency Listings and Approvals In some cases. certain modules or applications may not be listed by certain approval agencies. or listing may be in pro- cess.Consult factory for latest listing status. • UL/ULC Listed: S692 (listed for Canadian and non-Cana- dian applications). • MEA:67-02-E Vol. IV. • CSFM:7150-0028:0199. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6.632,108. NOTIFIER®is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. ISO 9001 We try to keep our product information up-to-date and accurate. C E RT t F E CI. We cannot cover all specific applications or anticipate all requirements. BEINFEIIINC i IIMIF#CTIIINC All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161.FAX:(203)484-7118. www.notifier.com Page 2 of 2—DN-7001:D•4/13/2012 DN-6995:C•Al-320 NP-100(A) Series N OTI F 1 E R® Addressable Photoelectric Detectors • for the FireWarden Series by Honeywell Addressable General The NP-100(A), NP-100T(A) and NP-100R(A) addressable, low-profile plug-in photoelectric detectors use a state-of-the- - art photoelectric sensing chamber with communications to provide open area protection and are used exclusively with NOTIFIER's FireWarden Series (FireWarden-100-2 and Fire- Warden-50) and Spartan (NSP-25) Addressable Fire Alarm Control Panels (FACPs). The NP-100T(A) adds thermal sen- / sors that will alarm at a fixed temperature of 135°F (57°C). Since these detectors are addressable, they will help emer- gency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage.Two LEDs on each sensor light to provide a local,visible sensor indication.Remote LED annunciator capa- bility is available as an optional accessory, PN RA100Z(A). The NP-100R(A)is a remote test capable detector for use with NP-100(A) in B210LP(A) Base DNR(A)/DNRW duct smoke detector housings. Features Applications SLC loop Use photoelectric detectors in life-safety applications to pro- • Two-wire loop connection. vide a broad range of fire-sensing capability, especially where • Unit uses base for wiring. smoldering fires are anticipated. Ionization detectors are often Addressing better than photoelectric detectors at sensing fast, flaming fires. • Addressable by device. • Rotary,decimal addressing:01 -99 with FireWarden-100-2 Construction and NSP-25,and 01 -50 with FireWarden 50. These detectors are constructed of off-white fire resistant plas- . Architecture tic. NP-100(A) series plug-in, low-profile smoke detectors are • Unique single-source, dual-chamber design to respond designed to commercial standards and offer an attractive quickly and dependably to a broad range of fires. appearance. • Sleek,low-profile design. • Integral communications and built-in type identification. Installation • Built-in tamper-resistant feature. NP-100(A)series plug-in detectors use a detachable mounting • Removable cover and insect-resistant screen for simple base to simplify installation,service and maintenance. field cleaning. Mount base(all base types)on an electrical backbox which is Operation at least 1.5"(3.81 cm)deep.For a chart of compatible junction boxes,see DN-60054. • Withstands air velocities up to 4,000 feet-per-minute(20 m/ sec.)without triggering a false alarm. NOTE:Because of the inherent supervision provided by the SLC • Factory preset at 1.5% nominal sensitivity for panel alarm loop, end-of-line resistors are not required. Wiring `T--taps" or threshold reset. branches are permitted for Style 4 (Class B) wiring. NP-100R(A) mounts in a DNR(A)/DNRW duct detector housing. • Visible LED"blinks"when the unit is addressed (communi- cating with the fire panel)and latches on in alarm. Operation Mechanicals Each NP-100(A) series detector uses one of 99 possible • Sealed against back pressure. addresses on the FireWarden-100-2 and NSP-25,or one of 50 • Direct surface mounting or electrical box mounting. possible addresses on the FireWarden-50 Signaling Line Cir- • Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cult (SLC). It responds to regular polls from the system and cm)octagonal box,or 4.0" (10.16 cm)square electrical box reports its type and status. (using a plaster ring—included). The addressable photoelectric sensor in the NP-100(A)series Other system features has a unique unipolar chamberthat responds quickly and uni- formly to a broad range of smoke conditions. It can withstand • Fully coated circuit boards and superior RF/transient pro- wind gusts up to 4,000 feet-per-minute (20 m/sec.) without tection. sending an alarm level signal. Because of its unipolar cham- • 94-VO plastic flammability rating. ber, the NP-100(A) series is approximately two times more • Low standby current. responsive than most photoelectric sensors. This makes it a Options more stable detector. • Remote LED output connection, PN RA100Z(A). DN-6995:C•12/07/2011—Page 1 of 2 Detector Sensitivity Test NP-100RA: Same as NP-100R with ULC Listing for use with a DNRA duct detector housing; B210LPA base included. Each detector can have its sensitivity tested (required per NFPA 72.Chapter 14 on Inspection. Testing and Maintenance) INTELLIGENT BASES when installed/connected to a FireWarden-100-2 or FireWar- NOTE:"A"suffix indicates ULC Listed model. • den-50 addressable fire alarm control panel.The results of the sensitivity test can be printed off the Fire Warden-100-2 or Fire- NOTE:For details about intelligent bases and their mounting, see Warden-50 for record keeping. DN-60054. B210LP(A): Plug-in detector base (included); standard U.S. Specification flanged low-profile mounting base. Voltage range: 15-32 VDC(peak). B210LPBP: Bulk pack of B210LP; package contains 10. Standby current: 300 pA @ 24 VDC. B501(A): Standard European flangeless mounting base. LED current: 6.5 mA @ 24 VDC(latched"ON"). B501 BP: Bulk pack of B501: package contains 10. Air velocity:4,000 ft./min. (20 m/sec.)maximum. B200SR(A): Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Size:2.1"(5.33 cm) high; base determines diameter. Replaces B501 BH series bases in retrofit applications. -B210LP(A):6.1"(15.5 cm)diameter. B224RB(A): Plug-in System Sensor relay base. Screw termi- -B501(A): 4.1"(10.4 cm)diameter. nals: up to 14 AWG(2.0 mm2).Relay type:Form-C.Rating:2.0 -B200SR(A):6.875"(17.46 cm)diameter. A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ -B224RB(A):6.2"(15.748 cm)diameter. 30 VDC inductive. Weight:3.6 oz. (102 g). B224B1(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases (see DN-6994). Operating temperature range: for NP-100(A):0°C to 49`C ACCESSORIES (32'F to 120'F): for NP-100T(A):0°C to 38°C(32°F to 100°F). NP-100R(A):installed in a DNR(A)/DNRW-20°C to 70`C(-4°F F110: Retrofit flange to convert B210LP(A) to match the to 158`F). B71OLP(A) profile, or to convert older high-profile bases to Temperature: 0 C-49°C(32°F-120°F). low-profile. Relative humidity: 10%-93%,non-condensing. F110BP: Bulk pack of F110; package contains 15. F210: Replacement flange for B210LP(A)base. Listings RA100Z(A): Remote LED annunciator.3-32 VDC. Mounts to Listings and approvals below apply to the NP-100(A). NP- a U.S. single-gang electrical box. For use with B501(A) and 100T(A), and NP-100R(A) detectors. In some cases. certain B210LP(A)bases only. modules may not be listed by certain approval agencies, or SMB600:Surface mounting kit listing may be in process. Consult factory for latest listing sta M02 04-OO:Test magnet. tus. - • UL Listed: S1115. M02-09-00:Test magnet with telescoping handle. • ULC Listed: S911. XR2B: Detector removal tool. Allows installation and/or removal of detector heads from bases in high ceiling applica- • CSFM:7272-0028:0231. tions. • MEA:243-02-E Vol.2. XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 • Maryland State Fire Marshal: permit 2173. m) sections. • FM approved. T55-127-010: Detector removal tool without pole. Product Line Information BCK-200B: Black detector covers for use with NP-100(A)only; box of 10. NOTE:"A"suffix indicates ULC Listed model. WCK-200B: White detector covers for use with NP-100(A) NP-100: Adressable photoelectric detector: B210LP base only:box of 10. included. NP-100A: Sames as NP-100 with ULC Listing: B210LPA base included. NP-100T: Same as NP-100 but with thermal element; B210LP base included. NP-100TA: Same as NP-100T with ULC Listing; B210LPA base included. NP-100R: Remote test capable addressable photoelectric NOTIFIER® and FireWarden® are registered trademarks of Honeywell detector for use with a DNRA/DNRW duct detector housing: International Inc. ©2011. All rights reserved. Unauthorized use of this document is strictly B210LP base included. prohibited. This document is not intended to be used for installation purposes. 'SO 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. 91CINESIINC&MANIFICTIRINC All specifications are subject to change without notice. MMMLITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161.FAX:(203)484-7118. www.notifier.com Page 2 of 2-DN-6995:C•12/07/2011 dn-60383:A2 NC-100R(A) NOTI FI ER' Relay Module for • FireWarden Series Panels by Honeywell Addressable General The NC-1 00R(A) Addressable Relay Module provides NOTI- FIER's FireWarden Series intelligent control panels with two isolated sets of Form-C dry-contact outputs for activating a - variety of auxiliary devices, such as fans. dampers.door hold- ers, control equipment, etc. Addressability allows the dry con- If • , tact to be activated. either manually or through panel - programming,on a select basis. Features • '"`°""' �" • Built-in type identification automatically identifies these -- - devices to the control panel. "`°' Wd-,.„•...., • Internal circuitry and relay powered directly by two-wire """'° SLC loop. ; • Integral LED "blinks" green each time a communication is received from the control panel and turns on in steady when • activated. ik • • l • High noise immunity(EMF/RFI). • Wide viewing angle of LED. • SEMS screws with clamping plates for wiring ease. NC-100R(A) • Direct Decade entry of address: 01 -99 with the FireWar- den-100-2(C)and 01 -50 with the FireWarden-50(C). Applications The NC-100R(A) may be programmed to operate dry contacts Specifications for door holders,Air Handling Unit shutdown,etc.,and to reset Normal operating voltage: 15 to 32 VDC. four-wire smoke detector power. Maximum SLC current draw: 6.5 mA(LED). Construction Average operating current: 230 pA direct poll (CLIP mode). • The face plate is made of off-white heat-resistant plastic. 255 pA group poll with LED flashing. • Controls include two rotary switches for direct-dial entry of EOL resistance: not used. address setting. Temperature range: 32°F to 120°F(0°C to 49°C). • The NC-100R(A) provides two Form-C dry contacts that Humidity range: 10%to 93%non-condensing. switch together. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x Operation 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125"(5.398 mm)deep box. Each NC-100R(A)uses one of the addresses on a SLC loop.It responds to regular polls from the control panel and reports its Relay Contact Ratings type and status. The LED blinks with each poll received. On command, it activates its internal relay. Maximum Current Load Description Application Voltage Rating switches set a unique address for each module. The g g address may be set before or after mounting. The built-in Resistive Non-Coded 30 VDC 3.0 A TYPE CODE (not settable)will identify the module to the con- trol panel. Resistive Coded 30 VDC 2.0 A Resistive Non-Coded 110 VDC 0.9 A Resistive Non-Coded 125 VAC 0.9 A Inductive(L/R=5ms) Coded 30 VDC 0.5 A Inductive(L/R=2ms) Coded 30 VDC 1.0 A Inductive(PF=0.35) Non-Coded 125 VAC 0.5 A dn-60383:A2•06/17/10—Page 1 of 2 Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. • UUULC Listed: S635. • CSFM approved:file 7300-0028:230. • FM approved. • MEA approved:file 72-01-E,Vol.2. Product Line Information NC-100R: Intelligent addressable relay module. NC-100RA: Intelligent addressable relay module, ULC listed model. SMB500:Optional surface-mount backbox. NOTE: For installation instructions, see document 156-2593-001 and refer to the SLC Wiring Manual, document 52304. NOTIFIER®is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. ISO9001 We try to keep our product information up-to-date and accurate. E a 1 i F E o We cannot cover all specific applications or anticipate all requirements. 6 1 MAI >Mfli All specifications are subject to change without notice. IIALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—dn-60383:A2•06/17/10 DN-6990:A•A1-351 NMM-100-10(A) N OT I F I E R Ten-Input Monitor Module by Honeywell Addressable Devices General •••• •••• •••- The NMM-100-10 ten-input monitor module is an interface between a FireWarden series control panel and normally - open contact devices in intelligent alarm systems such as , «•`�I``® �� pull stations, security contacts, or flow switches. The first address on the NMM-100-10 is set from 01 to 90 :: • • �:o • • ®' 6 6 at and the remaining modules are automatically assigned to the e next nine higher addresses. Provisions are included for dis `� •P*'•�•�•�4 * • abling a maximum of two t o unused addresses. :,`. ir'°' ar :i. •. The supervised state (normal, open. or short) of the moni- '}ii:•:. ;; • 111i • tored device is sent back to the panel. A common SLC input • • is used for all modules,and the initiating device loops share a _ � ' common supervisory supply and ground — otherwise each 'a;'° =1 • '' monitor operates independently from the others. �i"iiF'"°::, Each NMM-100-10 module has panel-controlled green LED ' • •E'" 2 indicators. The panel can cause the LEDs to blink, latch on, ::_ `. _• ::• or latch off. •,�.. fFlF:;: i#lE: ;r'Rp :. c.ii ...:aiF:, NOTE:Unless otherwise specified, the term NMM-100-10 is used in this data sheet to refer to both the NMM-100-10 and the NMM- 100-10A(ULC-listed version). Features Mounting options: • Listed to UL Standard 864, 9th edition. –CHS-6 chassis: Up to 6 modules. • Ten addressable Class B or five addressable Class A initi- –BB-25 cabinet: Up to 6 modules. ating device circuits. –BB-XP cabinet:One or two modules. • Removable 12 AWG (3.31 mm2) to 18 AWG (0.821 mm2) Wire gauge: 12 AWG (3.31 mm2)to 18 AWG (0.821 mm2). plug-in terminal blocks. Power-limited circuits must employ type FPL, FPLR, or • Status indicators for each point. FPLP cable as required by Article 760 of the NEC. • Unused addresses may be disabled. NMM-100-10 supports both Class B and Class A wiring; • Rotary address switches. remove shunt for Class A operation. • Class A or Class B operation. Maximum SLC wiring resistance: 40 or 50 ohms, panel • Flexible mounting options. dependent. • Mounting hardware included. Maximum IDC wiring resistance: 1500 ohms. Specifications Maximum IDC voltage: 10.2 VDC. Standby current: 3.5 mA (SLC current draw with all Maximum IDC current:240 NA. addresses used: if some addresses are disabled, the standby current decreases). Agency Listings and Approvals Alarm current:55 mA(assumes all ten LEDs solid ON). The listings and approvals below apply to the NMM-100- 10(A)Ten-Input Monitor Module. In some cases, certain mod- Temperature range: 32°F to 120°F (0°C to 49°C) for UL ules or applications may not be listed by certain approval applications;–10°C to+55°C for EN54 applications. agencies, or listing may be in process. Consult factory for lat- Humidity: 10% to 85% noncondensing for UL applications: est listing status. 10%to 93%noncondensing for EN54 applications. • UL Listed: S635 Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm) • ULC Listed:S635(NMM-100-10A) wide x 1.25" (31.75 mm)deep. • CSFM approved:7300-0028:256 Shipping weight:0.76 lb.(0.345 kg)including packaging. • FM approved DN-6990:A•06/10/2009—Page 1 of 2 Product Line Information NMM-100-10:Ten-input monitor module. NMM-100-10A:Same as above with ULC Listing. BB-XP: Optional cabinet for one or two modules. Dimen- sions, DOOR:9.234" (23.454 cm)wide(9.484" [24.089 cm] including hinges), x 12.218" (31.0337 cm) high, x 0.672" (1.7068 cm) deep; BACKBOX:9.0" (22.860 cm)wide(9.25" [23.495 cm] including hinges), x 12.0" (30.480 cm) high x 2.75" (6.985 cm); CHASSIS(installed):7.150" (18.161 cm) wide overall x 7.312" (18.5725 cm) high interior overall x 2.156"(5.4762 cm)deep overall. BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis (below). Dimensions, DOOR:24.0" (60.96 cm) wide x 12.632" (32.0852 cm) high, x 1.25" (3.175 cm) deep,hinged at bottom; BACKBOX:24.0"(60.96 cm)wide x 12.550"(31.877 cm)high x 5.218"(13.2537 cm)deep. CHS-6:Chassis,mounts up to six modules in BB-25. FlashSean®, NOTIFIER®, FireWarden®. and system Sensor® are registered trademarks of Honeywell International Inc. Microsoft® and Windows®are registered trademarks of the Microsoft Corporation. ©2009 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I I 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C F R T F 1 F 171 We cannot cover all specific applications or anticipate all requirements. MEM I Mal= All specifications are subject to change without notice. SSSIITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—DN-6990:A•06/10/2009 SYSTEM SENSOR F ' -_' F I ( I Indoor Selectable- E -r41 E Output Horns, Strobes, and !f , /fp---; Horn Strobes fort R Wall Applications • SpectrAlert®Advance audible visible notification products SPECTFNert are rich with features guaranteed to cut installation times 14 v c N c E and maximize profits. Features The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns,strobes,and horn strobes in the industry. • Plug-in design with minimal intrusion into the back box With white and red plastic housings,wall and ceiling mounting • Tamper-resistant construction options,and plain and FIRE-printed devices,SpectrAlert Advance • • Automatic selection of 12-or 24-volt operation at can meet virtually any application requirement. 15 and 15/75 candela Like the entire SpectrAlert Advance product line,wall-mount horns, • Field-selectable candela settings on wall units: 15, 15/75, strobes,and horn strobes include a variety of features that increase 30,75,95, 110, 115, 135, 150, 177,and 185 their application versatility while simplifying installation.All devices • Horn rated at 88+dBA at 16 volts feature plug-in designs with minimal intrusion into the back box, • Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. • Universal mounting plate for wall units • Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction device installation damage,SpectrAlert Advance utilizes a universal mounting plate • Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring,so installers can test wiring • Compatible with MDL3 sync module continuity before the device is installed. • Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with three volume selections. Agency Listings SIGNALING (T1 0) 0 MEP( approved 771125-1 25-1653186 does) 653.188(h(inaor n strobestrobs. 54011(chimes.horn strobes,horns) 3023572 MEA452-05-E chime strobes) 55512(strobes) 7135-1653.189(horns.chimes) • SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuit'°Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110,115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR' Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.3"D(142 mm L x 119 mm W x 33 mm D) Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS) 5.7"L x 4.8"W x 0.35"D(145 mm L x 122 mm W x 9 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. P. UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) • 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Tones and Sound Output Data Horn and Horn Strobe Output(dBA) 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 75 75 80 80 86 86 96 96 3 Temporal Low 71 71 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 73 74 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 74 75 81 81 88 85 96 92 tSettings 7,8,and 9 are not available on 2-wire horn strobes. SpectrAlert Advance Dimensions 4.7" 2.5'=-► 9L=1..."11.:==C3C:3=1.6MM. :311 I II 5.6" i.� Wall-mount horn strobes SpectrAlert Advance Ordering Information Model Description Model Description • Wall Horn Strobes Wall Strobes(cont.) P2R 2-Wire Horn Strobe,Standard cd,Red SRH Strobe,High cd,Red P2R-P 2-Wire Horn Strobe,Standard cd,Red,Plain SRH-P Strobe,High cd,Red,Plain P2R-SP 2-Wire Horn Strobe,Standard cd,Red,"FUEGO" SRH-SP Strobe,High cd,Red,"FUEGO" P2RH 2-Wire Horn Strobe,High cd,Red SW Strobe,Standard cd,White P2RH-P 2-Wire Horn Strobe,High cd,Red,Plain SW-P Strobe,Standard cd,White,Plain P2W 2-Wire Horn Strobe,Standard cd,White SWH Strobe,High cd,White P2W-P 2-Wire Horn Strobe,Standard cd,White,Plain SWH-P Strobe,High cd,White,P lain _ P2WH 2-Wire Horn Strobe,High cd,White Horns P2WH-P 2-Wire Horn Strobe,High cd,White,Plain HR Horn,Red P4R 4-Wire Horn Strobe,Standard cd,Red HW Horn,White P4R-P 4-Wire Horn Strobe,Standard cd,Red,Plain Accessories P4RH 4-Wire Horn Strobe,High cd,Red TR-HS Trim Ring,Wall,Red P4W 4-Wire Horn Strobe,Standard cd,White SBBR Indoor Surface Mount Back Box,Red Wall Strobes SBBW Indoor Surface Mount Back Box,White SR Strobe,Standard cd,Red SR-P Strobe,Standard cd,Red,Plain SR-SP Strobe,Standard cd,Red,"FUEGO" Notes: All-P models have a plain housing(no"FIRE"marking on cover) All-SP models have"FUEGO"marking on cover - "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings. "High cd"refers to strobes that include 135,150,177,and 185 candela settings. 1 SYSTEM 3825 Ohio Avenue•St.Charles,IL 60174 02014 System Sensor. Phone:800-SENSOR2•Fax:630-377-6495 Product specihcffians subject to change without notice.VisA systemsenso.com SEAISOR y to current product information,'including the latest version of this data sheet. \Y\Y 'v www.s stemsensor.com AVDS10201•1/14 SYSTEM SENSOR • .+ S tt Indoor Selectable- Output Strobes and Horn Strobes for Ceiling Applications t y ' „ SpectrAlert®Advance audible visible notification products are rich with features guaranteed to cut installation times SPECTRAlert and maximize profits. A N c clinawaY Features The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns,strobes,and horn strobes in the industry. • Plug-in design with minimal intrusion into the back box With white and red plastic housings,wall and ceiling mounting • Tamper-resistant construction options,and plain and FIRE-printed devices,SpectrAlert Advance • • Automatic selection of 12-or 24-volt operation at 15 and can meet virtually any application requirement. 15/75 candela Like the entire SpectrAlert Advance product line,ceiling-mount • Field-selectable candela settings on ceiling units: 15,15/75,30, 75,95, 110, 115, 135, 150, 177,and 185 strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation.All devices • Horn rated at 88+dBA at 16 volts feature plug-in designs with minimal intrusion into the back box, • Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. • Universal mounting plate for ceiling units • Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction device installation damage,SpectrAlert Advance utilizes a universal mounting plate • Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring,so installers can test wiring • Compatible with MDL sync module continuity before the device is installed. • Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with three volume selections. Agency Listings SIGNALING 0 ® MEA LISTED approved 7000r s 7125.1653.188 125-16531866(in(horn strobes.strobe) S4011 i-i -._:..,rn strobes,horns) 3023572 .._-,a_: chime strobes) S5512(strobes) 7135-1653189(horns,chimes) r SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double- gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17B-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance products,when used with the Sync•Circuit'°Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95,110, 115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21B-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR' Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high) Ceiling-Mount Back Box Skirt Dimensions(BBSC-2,BBSCW-2) 7.1-diameter x 2.2"high(180 mm diameter x 57 mm high) Ceiling-Mount Trim Ring Dimensions(sold as a 5 pack)(TRC-HS, 6.9"diameter x 0.35-high(175 mm diameter x 9 mm high) TRCW-HS) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS00501 pm UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) • 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High 135 NA NA 228 207 Candela Range 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 . Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Strobe Tones and Sound Output Data Horn Strobe Output(dBA) 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 75 75 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 • 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 75 75 81 81 88 85 96 92 /Settings 7,8,and 9 are not available on 2-wire horn strobes. AVD500501 r SpectrAlert Advance Dimensions 7.1" 14-2.251 6.8" / \ Dia. II09.1% Dia. ppa ° Q c '1, ;1;1.1 2 J / ; C 1. I ) en�n O \ C . Ceiling-mount horn strobes Ceiling back box skirt SpectrAlert Advance Ordering Information Model Description Model Description Ceiling Horn Strobes Ceiling Strobes PC2R* 2-Wire Horn Strobe,Standard cd,Red SCR Strobe,Standard cd,Red PC2RH 2-Wire Horn Strobe,High cd,Red SCRH Strobe,High cd,Red PC2W*t 2-Wire Horn Strobe,Standard cd,White SCW* Strobe,Standard cd,White PC2WH" 2-Wire Horn Strobe,High cd,White SCWH Strobe,High cd,White PC4R 4-Wire Horn Strobe,Standard cd,Red Accessories PC4RH 4-Wire Horn Strobe,High cd,Red BBSC-2 Back Box Skirt,Ceiling,Red PC4W 4-Wire Horn Strobe,Standard cd,White Back Box Skirt,Ceiling,White TRC-HS Trim Ring,Ceiling,Red TRCW- Trim Ring,Ceiling,White HS Notes: •Add"-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2R-P. t Add"-SP"to model number for"FUEGO"marking on cover,e.g.,P2R-SP. - t"Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185 candela settings. ®2012 System Sensor. • SYSTEM 3825 Ohio Avenue•St.Charles,IL 60174 Product specn�cations sut ect to change wmnut notice.Visa systemsensorcorn �_ SENSOR Phone:800-SENSOR2•Fax:630-377-6495 r«current product tm«motion.nctwng the latest vers.on a this data sheet. AVDS00501•3/12