fEGEIVED ti.icci APR 2 7 2015 Worldwide www.tyco-fire.com Fire Protection CITY OF TIGARD Contacts Products BUILDING DIVISION Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers • Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers • if 'm" 1 I -..--.0*- Description described herein must be installed and maintained in compliance with this doc- The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable Upright(TY313)and Pendent(TY323) standards of the National Fire Protec- S Sprinklers described in this data sheet in,P tion Association,in addition fo the stan are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair sprinklers designed for use in light or the performance of these devices. :_ ..2i \ r" ordinary hazard,commercial occupan- .-- The owner is responsible for maintain- ---_-�_ ties such as banks,hotels, and shop- P ping malls. ing their fire protection system and ` Y— t devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble,is intended for use in areas with a any questions. it finished ceiling.This recessed pendent sprinkler uses one of the following: Sprinkler - • A two-piece Style 15 Recessed p Escutcheon with recessed adjust- Identification "1 . j'� ment up to 5/8 inch (15,9 mm)from /, the flush pendent position. Number (SIN) � ` • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT � ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT . r_T; the flush pendent position. The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of Series Approvals 175°F(79°C) 200°F(93°C) TY-FRB Sprinklers are described in UL and C-UL Listed Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved 286°F(141 C) kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler:Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi(12.1 bar) Frame Bronze 250 psi(17.2 bar)' Button Brass/Copper The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psitt2(80,6 LPM/bar112) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* — .%7E7•c ribA /// /–P1"11% \ -- / • " 5 .1 7/16 . I �_ ` R 4 NOMINAL 2" } ( I ��I IR MAKE-IN tit (50,8 mm) I ..S1 t 2 F:At�` 2" 1-3/8" (50,8 mm) (34,9 mm) I lir 3 WRENCH G l / j FLATS 1/2"NPT** DEFLECTOR* — 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE �. Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, ,....107.°WRENCH RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached,the Sprinklers must be installed in accor- END"A°) fluid expands sufficiently to shatter the dance with this section. glass bulb, allowing the sprinkler to General Instructions activate and water to flow. FIGURE 2 Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally,a small air bub- WRENCH Criteria ble should be present. The diameter of the air bubble is approximately 1/16 ;EC:SS The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) Sprinklers are intended for fire protec- temperature ratings. tion systems designed in accordance with the standard installation rules rec- ognized by the applicable Listing or should be obtained by applying a t Approval agency(such as, UL Listing min- imum to maximum torque of 7 to 14 is based on the requirements of NFPA ft.-Ibs. (9,5 to 19,0 Nm). Higher levels fir" 13, and FM Approval is based on the of torque can distort the sprinkler Inlet with cons PUSH WRENCH requirements of FM's Loss Prevention of the spri�nkler.t leakage or impairment IN TO ENSURE Data Sheets).Only the Style 15 or Style ENGAGEMENT 20 Recessed Escutcheon is to be used Do not attempt to compensate for WITH SPRINKLER for recessed pendent installations. insufficient adjustment in the Escutch- WRENCHING AREA eon Plate by under-or over-tightening FIGURE 3 the sprinkler. Re-adjust the position of - the sprinkler fitting to suit. W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP172 Page 3 of 4 Step 3. Tighten the sprinkler into the 2-7/8"DIA. sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1, apply the W-Type 6 2-1/4"DIA. Sprinkler Wrench to the wrench flats. FACE OF — (57,2 mm) — Torque sprinklers 7 to 14 ft.-Ibs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm)+ Recessed Pendent Sprinklers 1 ;, ; FLUSH The Series TY-FRB Recessed Pendent 3/8±5/16' I ' Sprinklers must be installed in accor- (9,5±7,9 mm) = r % + } dance with the following instructions. f / • t Step A.After installing the Style 15 or MOUNTING 1/8' i I Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread ---- — 1 sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE sprinkler fitting. 3/4"(19,1 mm) FIGURE 4 Step B.Tighten the sprinkler into the SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) sprinkler fitting using only the W-Type WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 7 Recessed Sprinkler Wrench(Figure RECESSED ESCUTCHEON 3).With reference to Figure 1,apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8"DIA. __ sprinklers 7 to 14 ft.-Ibs. (9,5 to 19,0 (73.0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER 2-1/4"DIA. — fishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- 5/16±1/4" kler and push the Closure over the (7,9±6,4 mm) 1/2"(12,7 mm) Mounting Plate until its flange comes in - FLUSH contact with the ceiling. _ 1 1 . ,T } Care and t mmor MOUNTING i 1/8" Maintenance SURFACE - (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, --� I Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8'(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. if they cannot be completely cleaned Absence of the outer piece of an by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec- escutcheon, which is used to cover by brushing it with a soft bristle brush. ommended to be inspected, tested, a clearance hole, can delay sprinkler and maintained by a qualified Inspec- operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. • klers are not used for hanging any after installation.Sprinklers damaged objects and that the sprinklers are only by dropping, striking, wrench twist/ cleaned by means of gently dusting slippage,or the like,must be replaced. with a feather duster;otherwise,non- Also, replace any sprinkler that has a operation in the event of a fire or inad- cracked bulb or that has lost liquid from vertent operation may result. its bulb.(Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corm- inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document,as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion(e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) PURE WHITE(RAL9010)" 370 5.6K UPRIGHT(1/2"NPT) TY313 3 POLYESTER 155 155°F(68°C) 371 5.6K PENDENT(1/2"NPT) TY323 q SIGNAL WHITE(RAL9003) POLYESTER 175 175,E(79°C) •Use suffix"I"for ISO 7-1 connection: 9 CHROME PLATED 200 200°F(93°C) for example.77470-4-175-I Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order,indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent(specify)Sprinkler, SIN (specify), K=5.6,Quick Response,(specify)tem- perature rating, (specify) finish, P/N (specify,refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify')finish, P/N(specify`) Specify:Style 20 Recessed Escutch- eon with(specify`)finish, P/N(specify') Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 l Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. tyco TEFLON is trademark of The DuPont Corporation. Fire PtotecOon Products Dyna-Thread® - M-COAT® Submittal Data Sheet C) Full Line Sch-40 Replacement Dyna-Thread—M-COAT Specifications Dyna-Thread'—M-Coat" sprinkler pipe represents an engineering NPs Nominal I.D. Wt. Wt.(1120 Filled) CRR CRR y advancement for the sprinkler pipe industry.It combines the safety In;mm In;mm Lbs/Ft kg/m Lbs/Ft;kg/m Unthreaded Threaded and longevity of traditional Sch-40 pipe with quality and superior 1" 1.080 1.330 1.75 11.39 1.00 hydraulic advantages. 25 27.4 2.0 2.60 — — 11/4" 1.408 1.870 2.54 9.50 1.00 ® Comparison to Schedule 40 32 35.8 2.8 3.78 — — 1'h" 1.639 2.290 3.22 9.14 1.00 Dyna-Thread"'—M-Coate inside diameter is up to 3.6%larger than Sch-40 40 41.6 3.4 4.79 — — giving it superior hydraulics.Also,when used in combination with Dyna- 2" 2.104 3.050 4.57 8.41 1.00 Flow—M-Coat pipe,down sizing often occurs.Dyna-Thread is fully listed and 50 53.4 4.5 6.80 — — approved UL,ULC,and FM for fire sprinkler applications.The life expectancy of Dyna-Thread—M-Coat and Sch-40 are equal based on the calculated wall 0 c® thicknesses per UL.The consistent quality of steel used to make Dyna-Thread— ..,.o.t• M-Coat facilitates smooth threading and lower maintenance costs.The exterior of Dyna-Thread—M-Coat is protected by a clean,durable mill coating for O American Made extended shelf life and easy paint application.With its increased strength Manufactured at one of 3 U.S.Facilities and is available and lighter weight,Dyna-Thread—M-Coat reduces installation fatigue and through distributors in the USA,Canada,Mexico,and is ideal for retio-fit applications.Corrosion Resistance Ratio(CRR) is a UL Latin America. (Underwriters Laboratory)term for the estimated life expectancy of a pipe joint. This is based on the calculated wall thickness at the base of the first exposed U Specifications & Approvals thread,assumed to be the weakest point of the pipe length.Dyna-Thread— M-Coat and Sch-40 have the same calculated wall thicknesses at this point Dyna-Thread—M-Coat pipe is manufactured to meet:ASTM A and are both assigned the same CRR of 1.00. 135,Type E Grade A,and is in compliance with NFPA-13.All sizes of Dyna-Thread—M-Coat are rated at 300 psi working O Comparison to L.W.T. Pipe pressure.Dyna-Thread—M-Coat is UL and ULC Listed for wet, More wall thickness at the thread(CRR=1.00)gives Dyna-Thread—M-Coat dry and pre action sprinkler systems and FM Approved for better life expectancy than lightwall threadable pipe joints.Dyna-Thread— use in wet systems.Dyna Thread—M-Coat is approved for all M-Coat is approved for standard hanger spacing(15 ft.O.C.),can be used as threaded couplings and welded outlets and is suitable for all earthquake sway bracing,and is safe to use as drops.Dyna-Thread—M-Coat roll grooved,and plain end fittings.(See listing information). is safer to weld on than many zinc coated lightwall threadable pipe products. Dyna-Thread—M-Coat is more widely accepted than lightwall threadable where Sch-40 is specified. Project: Sprinkler Contractor: Date: Engineer: Specification Reference: System Type: Locations: Comments: eN4 1 allied Customer Service: (800)882-5543 Fax: (800)659-7730 www.alliedtube-sprinkler.com `o • 16100 S Lathrop Ave • 11350 Norcom Rd. • 2525 N 27th Ave. TUBE&CONDUIT* Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009 """°A.Vfe 02013 Atkore International,Inc.All Rights Reserved.STP-S3-4M-1301 .$CI Ductile Iron Fittings-Class 300 UL/FM I QUALITY PLUS C ® US APPROVED Fig. 35E 3- 90° Elbow LISTED A Size Part Number A Packing Weight '�'� in in Inner Master lb ' \ 1/2 35E 3004 1 1 100 200 0.2 t\'',• i 3/4 35E 3006 1.31 70 140 0.3 1.11i A 1 35E 3010 1 :,,J 40 00 0.5 =1 1-1/4 35E 3012 1 75 25 50 0.8 1-1/2 35E 3014 1_ )4 18 36 1.1 2 35E 3020 2 25 10 20 1.8 2-1/2 35E 3024 2 7' 8 32 Fig. 35RE3- 90°Reducing Elbow B Size Part Number A B Packing Weight , \ _ in in in Inner Master lb "r ��� 3/4 x 1/2 35RE3006004 1 20 1.22 80 160 0 3 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 - I" 1 x 3/4 35RF3010006 1 -23 1.45 50 100 0.4 � A 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 ' 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0 6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0"6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0"8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 35RE3020004 1.60 1.97 18 30 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 D 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1 5 U 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 C 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 _ 2 5 T I Fig. 35F 3- 45° Elbow ESize Part Number A Packing Weight A in in Inner Master lb t�, 1/2 35F 3004 0.88 150 300 02 3/4 35F 3006 0.98 80 160 0.3 1 35F 3010 1.13 40 80 0 5 1-1/4 35F 3012 1.29 25 50 07 Ilk 1-1/2 35F 3014 1.44 20 40 1.0 � 2 35F 3020 1.69 10 20 1.6 ^ 2-1/2 35F 3024 1.95 - 8 2 7 a. Fig. 35T 3- Tee Size Part Number A Packing Weight in in Inner Master lb � IN IA 2 35T 3004 1.13 0.0 160 0 3 3/4 35T 3006 1.31 30 �b 60 0.5 �� �� 1 35T 3010 1.50 56 0.7 �,...�. 1-1/4 35T 3012 1.75 10 20 1.1 1-1/2 351 3014 1.94 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 111 SNII"I'H-COOPER INTERNATIONAL" • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 1 uctile Iron ittings- lass I I $ I UUALfI I PWS C ® US APPROvrn A Fig. 35CP3 -Straight Coupling with Ribs LISTED la ] ,elorv' Size Part Number A Packing Weight in in Inner Master lb 1/2 35CP3004 1.38 200 400 0.1 3/4 35CP3006 1.63 100 200 0.2 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35CP3014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling 111 Pros Size Part Number A Packing Weight in in 1 69 80 er Master n lb A 1 x 1/2 1 x 3/4 35RC3010004 160 0 3 35RC3010006 1.69 60 120 0.4 0.6 _fl - 1-1/4 x 3/4 35RC3012006 2.06 In40 80 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B in in Inner Master lb 1 x 1/2 35HB3010004 1.06 180 360 0.2 1 x 3/4 35HB3010006 1.06 180 360 0.1 ii I i I A 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 I i - 1-1/2 x 1 35HB3014010 1.25 75 150 0.4 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 0 2 x 1 35HB3020010 1.38 40 80 0.6 y,. U 2 x 1-1/4 35H83020012 1.38 40 80 0.6 C 2 x 1-1/2 35H83020014 1.38 40 80 6.6 T I Fig. 35SP3 -Square Head Plug E Size Part Number A Packing Weight in in Inner Master lb 1/2 35SP3004 0.94 600 1200 007 - 3/4 35SP3006 1.12 350 700 0.1 ® IA 1 35SP3010 1.25 200 400 1-1/4 35SP3012 1.37 100 200 0 3 1-1/2 35SP3014 1.44 80 160 0 4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat A Size A Packing Weight Part Number Imam in in Inner Master lb 1 35U 3010 2.19 20 40 1.0 -__ _ ___ 1-1/4 35U 3012 2.50 15 30 1.2 ill 7--, 1-1/2 35U 3014 2.62 10 20 1.7 .I..-- 2 35U 3020 3.12 6 12 2.4 113 SNII'I'H-COOPER IN'I'ERNAI'IONAL® • 'POLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Pipe Hangers Fig.200 - ""Trimline"" Adjustable Band Hanger (B-Line Fig.B317ONF) ®TOLCO Fig.200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig. B317ONFF) c Ul us Fig.200C - "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) LISTED Fig. 200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig, 200 - 1/2" (15mm)thru 8" (200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications �r Function: For fire sprinkler and other general piping purposes. Knurled - swivel nut design permits hanger adjustment after installation. Features: : __ • (1/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe _ (.`:" types and protect CPVC plastic pipe from abrasion. Captured design �� keeps adjusting nut from separating with hanger.Hanger is easily Q1 B �. 1 installed around pipe. = A For hanger with non-captured nut order Fig, 200S. i, • (21/2" (65mm)thru 8" (20omm))Spring tension on nut holds it securely in • }. \___ hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed(1/2" (15mm)thru 8" (200mm)) -- -' Fig.200-1/2.2003/4 in the USA(UL)and Canada (cUL)for steel and CPVC plastic pipe and Fig.200-1 to 200-2 Fg.200,21/zto 200-8 Factory Mutual Engineering Approved(FM) (3/4" (20mm)thru 8" (200rnm)). Conforms to Federal Specifications WW-H-1 71 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, ,,u. Type 10. Maximum Temperature: 650°F(3431C) yew it Finish: Pre-Galvanized.Stainless Steel s.q �y 4 materials will be supplied with (2)hex nuts { in place of a knurl nut. Order By: Figure number and pipe size Designed to meet or exceed requirements of FM DS 2-0. i Fig.200 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) 200 1/2 i/2" (15) 3/8"-16 31/8" (79.4) 25/8" (66.7) 11 (5.0) r1'' j 200-3/4 3/4" (20) 3/8"-16 31/8" (79.4) 21/2" 163.5) 11 (5.0) 200-1 1" (25) 3/8"-16 33/8" (85.7) 25/8" (66.7) 12 (5.5) 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8 (73.0) 13 (5.9) 200-11/2 11/2" (40) 3/8"-16 37/8" (98.4) 27/s" (73.0) 14 (6.4) 200-2 2" (50) 3/8.-16 41/2' (114.3) 3" (76.3) 15 (6.9) 200-21/2 21/2" (65) 3/8"-16 55/8" (142.9) 41/8" (104.7) 27 (12.3) 200-3 3" (75) 3/8"-16 57/8" (149,1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2" (90) 3/8"-16 73/8" (187.3) 51/4" (133.3) 34 (15.6) 200-4 4" (100) 3/8"-16 73/8" (187.3) 5" (127.0) 35 (16.0) 200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" (158.7) 66 (30.2) 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on dia ings are in inches.Dimensions shown in paientheses are in millimeteis unless otherwise specified. B-Line Fire Protection Solutions 21 by F:Z•N Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig.103) B3205L - Threaded Rod (right& left hand threads) -TL r .‘ Size Range: 3/s" 16 thru 3" 4 rod Specify Length 111 Material: Steel r, Function: Recommended for use as a hanger support in hanger assemblies. ✓ tt 4\� 1 Rod is threaded on both ends with right hand threads of the length shown.Also ° --' \\ A available with left and right hand threads-specify Fig. B3205L when ordering. Thread Sin Maximum Temperature: 750°F(399°C) Finish: Plain.Contact B-Line for alternative finishes and materials. Order By: Part number,rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) 83205-3/8 x'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-1/2 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) 83205-5/8 x'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) 83205-3/4 x'L' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) B3205-7/8 x 1' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) B3205-1 x'L' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) B3205-11/8 x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) B3205-11/4 x'L' 11/4"-7 5" (127.0) 9500 (4225) 7440 (33.09) B3205-1112 x'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) 83205-13/4 x'L' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79) B3205-2 x'L' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29) 83205-21/4x'L' 21/4"_41/2 9" (228.6) 32300 (143.67) 25295 (112.51) B3205-21/2 x'L' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) 83205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L' 3"-4 12" (304.8) 60100 (267.32)-1 47066 (209.35) ATR - All Threaded Rod 120" (3.05m) Lengths (TOLCo Fig.loo) o Fig. 99- All Threaded Rod Cut To Length � ' ,, N\ Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length y,,;,w1� Material: Steel �j��'F N vd Maximum Temperature: 750°F(399°C) -oo `o -ova Plain.Contact B-Line for alternative finishes and materials. F. m Order By: Part number,rod diameter and finish a Part No.-Size x Length Threads Recommended Load Approx.WtJ100 Ft. ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"x 120 99-1/4"x length _ 20 240 (1.07) 12 (5.44) ATR 3/s"x 120 99-3/8"x length 16 730 (324) 29 (13.15) ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) ATR 518"x 120 99-5/8"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) ATR 7/s"x 120 99-7/8"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line Pipe Hangers&Supports 236 Revsed4.28/2014 by EA•N VERTICAL MOUNT SAMMYS`" SAMMYS® for Wood Installs VERTICALLY into the bottom of wood structures easily and quickly! Not bas than 2'nonral width Mai Fkad� Product Features (tom► •No pre-drilling required. a Na •Quick to install using the Sammy "� Nut Driver with an 18V cordless thickness(2-1/71( a drill/driver.maximewcworfwirbarzwzrrim;ow ) -i"'�°� •Saves time from traditional Double Sbeelrod' methods. For verbal use- Caring install in center of lower face. I •Reduces installation cost. Minimum 2'embedment:nto base material for NFFA 13 mmpllance. Composite!Truss •Made in the U.SA. I Consul truss manufacturer for i ' recommended installation point. i - 'Pre-dn'6ng may be required for GST -.,t i —_-- =� - 25380.Tod avadabie e"page 10. ^..��1. T t-- II *im Rod Part Screw Itimate UL Test FM Test Box Case Approvals Size Number Model Descriptions ' Putout(Ibs) Load(Ibs) Load(lbs) Qty Qty 1/4' 8002957 GST 100 114 x 1' 210(7/16"OSB) 25 125 0 670 (314'Ply) 1'4' 8003957 GST 200 114 x 2" 1760 (Fir) 25 125 1/4" 8004957 GST 300 114 x 3' 2060(Fir) 25 125 0 3'8' 8006957 GST.75 1/4 x 3/4" 564 (3/4"Pty) 25 125 Q 318' 8007957 GST 10 1!4 x 1' 210(7/16"OSB) 300 25 125 670 (3/4'Ply) - ii IF %"-`� 3'8" 8008957 GST 20 1/4x 2' 1760 (Fir) 850 1475 25 125 3/8` 8068925 GST 20-SS 1/4x2' 1760(Fir) 850 25 125 3/8° 8009925 GST 25-380 3/8 x 2-1/2" 2113 (Fir) 1500 25 125 4-' 3/8" 8010957 GST 30 1/4 x 3" 2060(Fir) 1500 1475 25 125 #14 Black Nut Driver 3/8" 8069925 GST 30-SS 1/4 x 3" 2060 (Fir) 25 125 Part#8113910 IISN . 3/8" 8011925 GST 40 114 x 4" 2180(Fir) 25 125 3/8` 8012925 GST 60 114x 6' 2230(Fir) 25 125 1/2' 8013925 GST 2 114 x 2' 1760(Fir) 25 125 1/2' 8014925 GST 25-380 3/8 x 2-1/2' 2113 (Fir) 25 125 0 1/2' 8015925 GST 3 114 x 3' 2275(Fir) 25 125 1/2" 8016925 GST 4 1/4 x 4" 2180 (Fir) 25 125 — iii 1/2' 8017925 GST6 1/4x6' 2230(Fir) 25 125 _ #14SWRei Nut Driver . 0 Part#8114910 SAMMY Swivel Head'for Wood Installs VERTICALLY and swivels up to 17° in wood structure - - ---1 Product Features I •Elminates distortion of threaded rod. •Saves time from traditional methods. j •Accommodates up to 3'1/ x 12 pitch roof. •Reduces installation cost. II •Allows 17°deflection from vertical. •Made in the U.S.A. IH, 44 Rod Part Screw Ultimate UL Test FM Test Min Box Case Approvals Model Size Number Descriptions Pullout(Ibs) Load(Ibs) Load(Ibs) Thickness Qty Qty <' 3/8' 8139957 SF1 GST 20 1/4x2" 1257(Fir) 1050 1475 25 125 125 - '. 3/8" 8141957 SH-GST 30 1/4 x 3" 1720(Fir) 1500 1475 25 125 #14 Black Nut Driver SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into Part#8113910 contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations, For the most up to date information,visit www.sammysuperscrew.com 4 e N°;S,n,° ONInj,n8 T aaVO,1 jr),u,o 2'-0" 0 0 3•-s- — CIoz- 0 Z 8d b' - _ d 2-6- ' O , � Y i 5.-5" i' r ii iii SAMMYS FOR WOOD 16'-4' AT ROOF 3/8" ALL THREAD ROD In TOLCO 200 TRIMLINE ADJUSTABLE BAND HANGER AT CEILING --1 i 10: 1 a N I N 3'-8' HANGER DETAIL NOT TO SCALE X • la'-to- X N N N S f S PARTIAL REFLECTED CEILI \G PLA\ 1/4"=1'-0" 0' 2' 4' 8' NOTES REVISIONS SPRINKLER SYMBOLS GERBER CMM ROOM All piping to be Dyna-Thread w/screwed ductile iron fittings. Dim a nar UT li.:v, lLic :i:.;b ir�m:E:1i,'ay[::Ial!iGLy:IGtMp:;ltii All hangers to be per NFPA 13 requirements. 0 .'-' 7YCa fl723 s'—rss Ch/Ch 155 I/2' 1/Y SB 2 _ 9 P ew D0S11C �, W YAT T 14200 SW 72ND AVE PERMIT NO. All armovers greater than 2'-0' shall be provided with hangers. CONTRACT NO. TGir�7 Max sprinkler spacing to be 130 sq. ft. per head. FIRE PROTECTION, INC. DRAWN BY A.Payne PORTLAND, OREGON 97224 All heads cut in from branch lines. 9095 S.W.Burnham SCALE 1114 = 1-0"' Meets design requirements of NFPA 13 2013 edition. Tigard,OR 97223 DATE 24 APR 2015 All of work area will be ordinary hazard group 1 occupancy. (503)684-2928 GERBER BLADES 14200 SW 72ND AVE, PORTLAND, OR 97224 FP 1 OF 1