Report • • • q-.A9S 2013oota ttjco Fire Suppression & Buildin g Products Technical Services 800-381-93121+1-401-781-8220 www.tyco-fire.com Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General NOTICE The Series DS-1 Dry-Type Sprinklers Description described herein must be installed 4114 and maintained in compliance with this TYCO Series DS-1 Dry-Type Sprinklers, document,as well as with the applica- 5.6K Pendent, Upright, and Horizontal ble standards of the National Fire Sidewall,Quick Response(3 mm Bulb) Protection Association, in addition to a and Standard Coverage, are decora- the standards of any Authorities Having tive glass bulb automatic sprinklers de- Jurisdiction.Failure to do so may impair signed for commercial use. Dry-Type the performance of these devices. Sprinklers are typically used where: Owners are responsible for maintaining • pendent sprinklers are required on their fire protection system and devices dry pipe systems that are exposed to in proper operating condition. The in- freezing temperatures;for example, stalling contractor or sprinkler manu- sprinkler drops from unheated por- facturer should be contacted with any tions of buildings. questions. •sprinklers and/or a portion of the con- The Series DS-1 Dry-Type Sprinklers necting piping are exposed to freezing must only be installed in fittings that f temperatures; for example,sprinkler meet the requirements of the Design drops from wet systems into freezers, Criteria section. ►, sprinkler sprigs from wet systems into unheated attics, or horizontal piping Model/Sprinkler extensions through a wall to protect an p unheated areas such as loading docks, Identification overhangs,and building exteriors. •sprinklers are used on systems that are Numbers (SINS) seasonally drained to avoid freezing; for example,vacation areas. 3/4-Inch NPT: / TY3935- Pendent TY3735- Horizontal Sidewall 1-Inch NPT: TY3235- Pendent TY3135- Upright TY3335 -Horizontal Sidewall IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING"that provides cautions with respect to handling and in- stallation of sprinkler systems and components.Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 MAY 2011 TFP510 r TFP51O Page 2 of 10 3/4-Inch NPT TY3935 Pendent TY3935 Pendent TY3735 Horizontal Sidewall with Top of Deflector-to-Ceiling with Standard with Standard Escutcheon Distance of 4 to 12 inches Recessed Escutcheon (Figure 3) (100 to 300 mm) (Figure 4) with Deep Escutcheon with Standard Escutcheon (Figure 5) (Figure 8) without Escutcheon with Deep Escutcheon (Figure 6) (Figure 9) without Escutcheon (Figure 10) Finish Temperature Bulb - - - Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester 135°F(57°C) Orange 155°F(68°C) Red 175°F(79°C) Yellow 1,2 1,2 1°,2* 200°F(93°C) Green 286°F(141°C) Blue N/A Notes 1. Listed by Underwriters Laboratories,Inc.(maximum order length of 48 inches) 2. Listed by Underwriters Laboratories for use in Canada(maximum order length of 48 inches) • Light and Ordinary Hazard Occupancies Only N/A-Not Available TABLE A SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS — LABORATORY LISTINGS AND APPROVALS — 1-Inch NPT TY3235 Pendent TY3235 Pendent TY3335 Horizontal Sidewall with Top of Deflector-to-Ceiling with Standard with Standard Escutcheon Distance of 4 to 12 inches Recessed Escutcheon (Figure 3) (100 to 300 mm) (Figure 4) with Deep Escutcheon (Figure 5) with Standard Escutcheon (Figure 8) without Escutcheon (Figure 6) with Deep Escutcheon TY3135 Upright (Figure 9) without Escutcheon without Escutcheon (Figure 7) (Figure 10) Finish Temperature Bulb - Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester 135°F(57°C) Orange 155`F(68°C) Red 1,2.3.4 1,2,4 175°F(79°C) Yellow 1,2,3,4 1,2,4 1*,2*,3**,4 1*,2*,4 200°F(93°C) Green 286°F(141°C) Blue N/A Notes: 1. Listed by Underwriters Laboratories,Inc.(maximum order length 4. Approved by the City of New York under MEA 352-01-E of 48 inches) 5. The Upright Sprinkler without an Escutcheon(TY3135)is avail- 2. Listed by Underwriters Laboratories for use in Canada(maxi- able in 1-Inch NPT only mum order length of 48 inches) Light and Ordinary Hazard Occupancies Only 3. Approved by Factory Mutual Research Corporation(maximum Light Hazard Occupancies Only order length of 48 inches) N/A-Not Available TABLE B 1-INCH NPT AND ISO 7-R1,SERIES DS-1 QUICK RESPONSE,STANDARD COVERAGE DRY-TYPE SPRINKLERS — LABORATORY LISTINGS AND APPROVALS — v TFP51O Page 3 of 10 Technical PLUG WITH r i INLET Data SEALING I is.wit ASSEMBLY ill It YOKE Approvals UL and C-UL Listed ;'I�I&, FM Approved PLUG iy, INLET NYC Approved under MEA 352-01-E SPRING t' tj BAND Previous New York City Approval �4 and MEA certification numbers ap- WATER i SPRING ply to product as shown in this data , , sheet. In accordance with Section ■ TUBE C ; CASING BC 3502 of the Construction Code, ; ' current NYC Approvals for use in the City of New York apply to all products GUIDE d�_ INSERT that contain UL or FM Approvals and TUBE 1 ' ; Listings; therefore, not all products $� currently Approved for use in the City It o� BULB of New York will carry an actual MEA FRAME ��� Certification number. 3 mm BULB Refer to Tables A and B. VENT HOLE till Maximum Working Pressure COMPRESSION 175 psi(12,1 bar) DEFLECTOR .r SCREW Inlet Thread Connections 3/4-Inch NPT 1-Inch NPT or ISO 7-R1 FIGURE 1 Discharge Coefficient SERIES DS-1, 3/4-INCH NPT,DRY-TYPE SPRINKLER K=5.6 GPM/psi1/2 — ASSEMBLY— (80,6 LPM/bar1/2) Temperature Ratings Refer to Tables A and B. Finishes PLUG WITH al INLET Sprinkler: Natural Brass, Chrome SEALING 41 Plated,White Polyester ASSEMBLY j '�' f Escutcheon: White Coated, Chrome i r YOKE Plated, Brass Plated SPRING .Physical Characteristics E INLET Inlet Copper 4 �∎� Z BAND Plug Copper WATER 4 i Yoke Stainless Steel TUBE i CASING Casing Galvanized Carbon Steel t ,iii Insert Bronze Bulb Seat Stainless Steel GUIDE 11�� % INSERT Bulb Glass TUBE ;I�►`!� Compression Screw Bronze �; Deflector Bronze 4 `■ BULB Frame Bronze FRAME iiif' h SEAT Guide Tube Stainless Steel Water Tube Stainless Steel Spring Stainless Steel 3 mm BULB VENT HOLE ■� Plug Spring` Stainless Steel rll Sealing Assembly Beryllium -, COMPRESSION Nickel w/Teflon" DEFLECTOR .� SCREW Escutcheon Carbon Steel For 3/4-Inch NPT only "Registered trademark of DuPont FIGURE 2 SERIES DS-1, 1-INCH NPT AND ISO 7-R1 DRY-TYPE SPRINKLER — ASSEMBLY— TFP510 Page 4 of 10 SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING (REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION) FACE OF FACE OF FACE OF SPRINKLER SPRINKLER SPRINKLER FITTING - FITTING FITTING \ L_ _ _J \ \\ L- ORDER LENGTHS: ORDER LENGTHS: ORDER LENGTHS: 3-1/2" DIA. 2-3/4"to 48" 1-3/4"DIA. 3-3/4"to 48" 1/2"to 46" x(88,9 mm)y (69,9 to 1219,2 mm) (44,5 mm) (95,3 to 1219,2 mm) (1 N71/4116,4 mm) ) 2-1/2"DIA. IN 1/4"(6,4 mm) IN 1/4"(6,4 mm) 2-1/4"DIA. (6,4 (63,5 mm) INCREMENTS �_ INCREMENTS (57,2 mm) INCREMENTS I---�I 1 ,3-..e:..1 __ FACE OF I % • CEILING FACE OF 11111 lir FACE OF . I ji M_ CEILING CEILING 11'1 1 lip' • 4-1/4"±1/8" 1 ii# ) - (108,0±3,2 mm) I 3"DIA. 2-7/8" DIA. I 11'1 2-3/16" ±1/8" 1-3/8"±1/8" fl (55,6±3,2 mm) _(76,2 mm) (34,9±3,2 mm) (73,0 mm) ��� FIGURE 4 FIGURE 3 PENDENT TY3235 AND TY3935 FIGURE 5 PENDENT TY3235 AND TY3935 WITH STANDARD RECESSED PENDENT TY3235 AND TY3935 WITH STANDARD ESCUTCHEON ESCUTCHEON WITH DEEP ESCUTCHEON SPRINKLER FITTING I i - (REFER TO DESIGN TOP OF CRITERIA SECTION) DEFLECTOR FACE OF SPRINKLER FITTING \ L ORDER LENGTHS: 1 5"to 48" (127,0 to 1219,2 mm) ORDER LENGTHS: IN 1/4"(6,4 mm) 5"to 48" INCREMENTS (127,0 to 1219,2 mm) IN 1/4"(6,4 mm) INCREMENTS FACE OF SPRINKLER 1 FITTING r MINIMUM 1 \ 1-3/4"(44,5 mm) /� — DEFLECTOR TO CEILING SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) FIGURE 7 FIGURE 6 UPRIGHT WITHOUT ESCUTCHEON PENDENT TY3235 AND TY3935 TY3135 WITHOUT ESCUTCHEON — 1-INCH NPT ONLY— , TFP510 Page 5 of 10 ORDER LENGTHS: Operation 2-3/4" 1/to 48"mm)INCREMENTS to REME TS mm) When the TYCO Series DS-1 Dry-Type IN 1/4"(6,4 mm)INCREMENTS Y- YPe ` 4" ±1/8" Sprinkler is in service, water is prevent- _ '-(101,6±3,2 mm) ed from entering the assembly by the FACE OF FACE OF 1-3/4"DIA. Plug with Sealing Assembly in the Inlet —SPRINKLER MOUNTING (44,5 mm) of the Sprinkler. See Figures 1 and 2. FITTING SURFACE \� f The glass Bulb contains a fluid that ex- v\ pands when exposed to heat.When the �_ 3" DIA. rated temperature is reached, the fluid } (76,2 mm) expands sufficiently to shatter the glass "`I 3.5' I Bulb, and the Bulb Seat is released. The compressed Spring is then able SPRINKLER FITTING to expand and push the Water Tube as (REFER TO DESIGN CENTERLINE 5/16" well CRITERIA SECTION) OF WATERWAY (7,9 mm) the Guide Tube outward.simultaneously pulls lls This inward.inw on the Yoke, withdrawing the Plug with FIGURE8 Sealing Assembly from the Inlet and TY3335 AND TY3735 HORIZONAL SIDEWALL allowing the sprinkler to activate and WITH STANDARD ESCUTCHEON flow water. Design ORDER LENGTHS: FACE OF Criteria 1/2"to 45-3/4"(12,7 to 1162,1 mm) MOUNTING IN 1/4"(6,4 mm)INCREMENTS SURFACE I -_ 4-13/16"±1/8" The TYCO Series DS-1 Sprinklers are - (122,2 t 3,2 mm) intended for use in fire sprinkler sys- FACE OF 2-1/2"DIA' tems designed in accordance with the (63,5 mm) standard installation rules recognized SPRINKLER by the applicable Listing or Approval FITTING agency; for example, UL Listing is based on NFPA 13 requirements.`�� •�■` � � 3-1/2" DIA. I �rJ } (88,9 mm) Sprinkler Fittings■ 3.5° I Install the 3/4 or 1-Inch NPT Series SPRINKLER FITTING \� + DS-1 Dry-Type Sprinklers in the 3/4 or follow- (REFER TO DESIGN \ 1-Inch NPT outlet or run of the follow- CENTERLINE 5/16" ing fittings: CRITERIA SECTION) OF WATERWAY (7,9 mm) • malleable or ductile iron threaded tee fittings that meet the dimensional re- FIGURE 9 quirements of ANSI B16.3(Class 150) TY3335 AND TY3735 HORIZONAL SIDEWALL • cast iron threaded tee fittings that WITH DEEP ESCUTCHEON meet the dimensional requirements of ANSI B16.4(Class 125). Do not install the DS-1 Sprinklers into ORDER LENGTHS: an elbow fittings.The Inlet of the sprin- 5-1/2"to 48"(139,7 to 1219,2 mm) kler can contact the interior of the el- IN 1/4"(6,4 mm)INCREMENTS MINIMUM bow, potentially damaging the Inlet 2-1/4'(57,2 mm) seal. FACE OF --DEFLECTOR TO The unused outlet of the threaded tee is —SPRINKLER MOUNTING plugged as shown in Figure 13. FITTING SURFACE You can also install the Series DS-1 Dry-Type Sprinklers in the 3/4 or 1-Inch ` ) NPT outlet of a GRINNELL Figure 730 'IIiIII�illlll'jI Mechanical Tee. However,the use of the Figure 730 Tee for this arrangement _ 5/16" is limited to wet pipe systems. SPRINKLER FITTING (7,9 mm) The configuration shown in Figure 12 (REFER TO DESIGN CENTERLINE is only applicable for wet pipe systems CRITERIA SECTION) OF WATERWAY where the sprinkler fitting and water- filled pipe above the sprinkler fitting are not subject to freezing and where the FIGURE 10 TY3335 AND TY3735 HORIZONAL SIDEWALL minimum of the Dry-Type length has in minimum exposure length depicted in WITHOUT ESCUTCHEON Figure 11. Refer to the Exposure Length section. TFP510 Page 6 of 10 For wet pipe system installations of NOTICE exposed barrel length to prevent water the 1-Inch NPT Series DS-1 Dry-Type Do not install the Series DS-1 Dry-Type from freezing in the connecting pipes Sprinklers connected to CPVC piping, Sprinkler into any other type fitting due to conduction. The exposed bar- use only the following TYCO CPVC without first consulting the Technical rel length measurement must be taken fittings: Services Department. Failure to use the from the face of the sprinkler fitting to • 1"x 1"NPT Female Adapter(P/N 80145) appropriate fitting may result in one of the surface of the structure or insula- tion that is exposed to the heated area. • 1"x 1" x 1"NPT Sprinkler Head Adapter Refer to Figure 11 for an example. Tee(P/N 80249). •Failure of the sprinkler to operate prop- erly due to formation of ice over the Clearance Space For wet pipe system installations of inlet Plug or binding of the Inlet Plug. In accordance with Section 8.4.9.2 the the 3/4-Inch NPT Series DS-1 of the 2010 edition of NFPA 13, when Sprinklers connected to CPVC pip- •Insufficient engagement of the Inlet ing, use in the 3/4" x 3/4" NPT Female pipe threads with consequent leakage. connecting an area subject to freez Adapter(P/N 80142). ing and an area containing a wet pipe Drainage sprinkler system, the clearance space For dry pipe system installations, use In accordance with the minimum around the sprinkler barrel of Dry-Type only the side outlet of maximum 2-1/2- requirements of the National Fire Sprinklers must be sealed.Due to tern- inch reducing tee when locating the Protection Association for dry pipe perature differences between two ar- Series DS-1 Sprinklers directly below sprinkler systems, branch,cross, and eas, the potential for the formation of the branch line.Otherwise,use the con- feed-main piping connected to Dry condensation in the sprinkler and sub- figuration shown in Figure 13 to assure Sprinklers and subject to freezing tern- sequent ice build-up is increased. If complete water drainage from above peratures must be pitched for proper this condensation is not controlled,ice the Series DS-1 Dry-Type Sprinklers drainage. build-up can occur that might damage and the branch line. Failure to do so the dry-type sprinkler and/or prevent may result in pipe freezing and water Exposure Length proper operation in a fire situation. damage. When using Dry Sprinklers in wet pipe Use of the Model DSB-2 Dry Sprinkler sprinkler systems to protect areas sub- Boot,described in technical data sheet ject to freezing temperatures, use Table TFP591 and shown in Figures 14 and C to determine a sprinkler's appropriate 15,can provide the recommended seal. Temperatures for Heated Area(al Ambient Temperature Exposed to Discharge End of 40°F(4°C) 50°F(10°C) 60°F(16°C) Sprinkler Minimum Exposed Barrel Length, Inches(mm)(b) 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes: (a)For protected area temperatures that occur between values listed above, use the next cooler temperature. (b)These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE C EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS — MINIMUM RECOMMENDED LENGTHS — v TFP51 O Page 7 of 10 RUN FACE OF TO WET SIDE Fa-PLUGGED OUTLET SPRINKLER SYSTEM OUTLET _ FITTING PLUGGED -1 r'''SPRINKLER e---)HEATED S FITTING HEATED TO DRY EXPOSURE AREA SYSTEM (SEE DESIGN AREA LENGTH CRITERIA (SEE DESIGN SECTION) DSB-2 CRITERIA DBB-2 SPRINKLER AREA INTENDED SECTION) INTENDED FITTING SUBJECT DSB-2 FOR FREEZER FOR FREEZER (SEE DESIGN TO INTENDED STRUCTURES STRUCTURES CRITERIA FREEZING FOR FREEZER SECTION) STRUCTURES rd iv I vii rill 7777 7777 0 wo, 4. ......c. . .,...: FIGURE 12 FIGURE 13 FIGURE 11 SPRINKLER FITTING SPRINKLER FITTING — EXPOSURE LENGTH — — HEATED AREA — — UNHEATED AREA — STRAP TIES 1-3/4"DIA. (44,5 mm) (ENDS ON CLEARANCE OPPOSING HOLE INSULATED SIDES OF FREEZER BOOT) ADHESIVE STRUCTURE DSB-2 BOOT DSB-2\t- o ✓ i ADHESIVE BOOT �% 1-3/4" DIA. , (44,5 mm) it 1I I CLEARANCE 0 HOLE i� ,i INSULATED 1�'�� FREEZER ■, = STRUCTURE STRAP TIES ■ (ENDS ON DS-1 DS-1 SHOWN WITH ,IlOPPOSING � SHOWN WITH SIDES OF STANDARD STANDARD BOOT) ESCUTCHEON ESCUTCHEON FIGURE 14 FIGURE 15 MODEL DSB-2 SPRINKLER MODEL DSB-2 SPRINKLER BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES DS-1 DRY SPRINKLER DS-1 DRY SPRINKLER . TFP510 Page 8 of 10 Installation 3. Wrench-tighten the sprinkler using Exercise care to avoid damage before, either: during, and after installation. Never The TYCO Series DS-1 Dry-Type • a pipe wrench on the Inlet Band or paint, plate, coat, or otherwise alter Sprinklers must be installed in accor- the Casing (Figures 1 and 2) automatic sprinklers after they leave dance with the following instructions. the factory. • the W-Type 7 Sprinkler Wrench on the Wrench Flat(Figure 16). Never repaint factory-painted Cover NOTICE Plates.When necessary, replace cover The Series DS-1 Dry Type Sprinkler Apply the Wrench Recess of the plates with factory-painted units. Non- must only be installed in fittings that W-Type 7 Sprinkler Wrench to the factory applied paint can adversely de- meet the requirements of the Design Wrench Flat. lay or prevent sprinkler operation in the Criteria section. Refer to the Design Note:If sprinkler removal becomes event of a fire. Criteria section for other important re- necessary, remove the sprinkler Replace sprinklers that: quirements regarding piping design using the same wrenching meth- and sealing of the clearance space od noted above. Sprinkler remov wrench twisting,wrench slippage, or around the Sprinkler Casing. al is easier when a non-hardening the like. Do not install any bulb type sprinkler sealant was used and torque guide if the bulb is cracked or there is a loss lines were followed. After removal, • were modified or over-heated. of liquid from the bulb.With the sprin- inspect the sprinkler for damage. • have cracked bulbs or have lost liquid kler held horizontally,a small air bubble 4. After installing the ceiling or wall and from the bulbs. Refer to the Installation should be present.The diameter of the applying a celing finish, slide on the Section in this data sheet. air bubble is approximately 1/16 inch outer piece of the Escutcheon until • are leaking or exhibiting visible signs (1,6 mm)for the 135°F(57°C)rating to it comes in contact with the ceiling of corrosion. 1/8 inch(3,2 mm)for the 286°F(141°C) or wall. Do not lift the ceiling panel rating. out of its normal position. Responsibility lies with owners for the • Obtain a leak-tight 3/4-Inch NPT sprin- When using the Deep Escutcheon, their fire r testing,and maintenance s kler joint by applying a minimum-to- hold the outer piece in contact with their fire protection system and devices maximum torque of 10 to 20 ft. lbs. the mounting surface (ceiling or in compliance the with this document,standards of (13,4 to 26,8 Nm). wall). Then rotate the inner piece well as with tFe applicabo standaiati of approximately 1/4 turn with respect the National Fire Protection Association • Obtain a leak-tight 1-Inch NPT sprin- to the outer piece,to hold the Deep (for example, NFPA 25), in addition to kler joint by applying a minimum-to- the standards of any other Authorities maximum torque of 20 to 30 ft. lbs. Escutcheon firmly together. Having Jurisdiction.The installing con- (26,8 to 40,2 Nm). tractor or sprinkler manufacturer should Higher levels of torque can distort the Care and be contacted relative to any questions. sprinkler Inlet with consequent leakage Maintenance Automatic sprinkler systems are recom- or impairment of the sprinkler. mended to be inspected, tested, and Do not attempt to compensate for The TYCO Series DS-1 Dry Type maintained by a qualified Inspection insufficient adjustment in an Sprinklers must be maintained and ser- Service in accordance and/or at o al c local re Escutcheon Plate by under or over- viced in accordance with the following quirements and/or national codes. tightening the Sprinkler. Re-adjust the instructions. position of the sprinkler fitting to suit. 1. Install pendent sprinklers only in the NOTICE pendent position, and install upright Before closing a fire protection system WRENCH sprinklers only in the upright posi- main control valve for maintenance RECESS tion. The deflector of a pendent or work on the fire protection system that 't✓-� upright sprinkler must be parallel to it controls, obtain permission to shut i/ , the ceiling. down the affected fire protection sys- Install horizontal sidewall sprin- tems from the proper authorities and WRENCH klers in the horizontal position with notify all personnel who may be affect- FLAT O their centerline of waterway perpen ed by this action. v dicular to the back wall and paral- Absence of the outer piece of an es- lel `� to the ceiling. Ensure the word cutcheon, which is used to cover a "TOP" on the Deflector faces the clearance hole, can delay the time to PUSH WRENCH ceiling. sprinkler operation in a fire situation. IN TO ENSURE ENGAGEMENT 2. With a non-hardening pipe-thread A Vent Hole is provided in the Bulb Seat WITH SPRINKLER sealant such as Teflon1 tape applied (Figures 1 and 2)to indicate if the Dry- WRENCHING AREA to the Inlet threads,hand-tighten the Type Sprinkler is remaining dry. Evi- sprinkler into the sprinkler fitting. dence of leakage from the Vent Hole in- FIGURE 16 dicates potential leakage past the Inlet W-TYPE 7 SPRINKLER WRENCH seal and the need to remove the sprin- kler to determine the cause of leakage; for example, an improper installation or an ice plug. Close the fire protec- tion system control valve and drain the system before removing the sprinkler. 1 Registered trademark of DuPont TFP510 Page 9 of 10 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression & Building Products ability. When placing an order, indicate (TFSBP) are warranted solely to the the full product name and Part Number original Buyer for ten(10)years against (P/N). defects in material and workman- ship when paid for and properly in- Dry-Type Sprinklers stalled and maintained under normal Specify this dry-type sprinkler as use and service.This warranty will ex- follows: pire ten (10) years from date of ship- ment by TFSBP. No warranty is given • Model/SIN from Page 1 for products or components manu- •Quick Response,Standard Coverage, factured by companies not affiliated Dry-Type Sprinkler by ownership with TFSBP or for prod- ucts and components which have • Deflector Style been subject to misuse,improper in- •5.6 K-Factor stallation, corrosion, or which have •Order Length not been installed, maintained, modi Dry- YPe$P T nnklersare furnished based fied or repaired in accordance with ap- plicable Standards of the National Fire upon Order Length as measured per Protection Association,and/or the stan Figures 3 through 10.After taking the Bards of any other Authorities Having measurement,round it to the nearest Jurisdiction.Materials found by TFSBP 1/4 inch increment. to be defective shall be either repaired • Inlet Connections or replaced, at TFSBP's sole option. 3/4-Inch NPT,1-Inch NPT,or ISO 7-R1 TFSBP neither assumes,nor authorizes •Temperature Rating any person to assume for it,any other obligation in connection with the sale of •Sprinkler Finish products or parts of products.TFSBP • Escutcheon Style and Finish, as shall not be responsible for sprinkler applicable system design errors or inaccurate or incomplete information supplied by • Part Number(P/N)from Table C Buyer or Buyer's representatives. The Upright Sprinkler without an In no event shall TFSBP be liable, in Escutcheon (TY3135) is available in contract, tort, strict liability or under 1-Inch NPT only. any other legal theory,for incidental, Part Numbers are for 3/4-Inch and indirect,special or consequential dam- 1-Inch NPT standard order sprin- ages,including but not limited to labor klers. Orders for all other sprinkler charges,regardless of whether TFSBP assemblies must be accompanied was informed about the possibility of by a complete description. Refer to such damages, and in no event shall the Price List for a complete listing of TFSBP's liability exceed an amount Part Numbers. equal to the sales price. The foregoing warranty is made in lieu Sprinkler Wrench of any and all other warranties.express Specify:W-Type 7 Sprinkler Wrench, or implied.including warranties of mer- P/N 56-850-4-001. chantability and fitness for a particular purpose. Sprinkler Boot This limited warranty sets forth the ex- Specify: Model DSB-2 Dry Sprinkler Boot,P/N 63-000-0-002. clusive remedy for claims based on fail- ure of or defect in products,materials This Part Number includes one Boot, or components, whether the claim is two Strap Ties,and 1/3 oz.of Adhesive. made in contract,tort,strict liability or The quantity of adhesive is sufficient for any other legal theory. installing one Boot. This warranty will apply to the full ex- tent permitted by law.The invalidity,in whole or part,of any portion of thiswar- ranty will not affect the remainder. TFP510 Page 10 of 10 P/N* 60 - XXX - X - XXX 11 1 1 SPRINKLER ESCUTCHEON MODEL/SIN i FINISH FINISH(1) 01 Pendent with Standard TY3935 1 NATURAL BRASS WHITE Escutcheon(3/4"NPT) (Figure 3) 4 WHITE POLYESTER WHITE 02 Pendent with Deep TY3935 Escutcheon(3/4"NPT) (Figure 5) 9 CHROME PLATED CHROME 03 Pendent with Standard Recessed TY3935 0 CHROME PLATED WHITE Escutcheon(3/4"NPT) (Figure 4) 2 NATURAL BRASS BRASS PLATED 04 Pendent without TY3935 Escutcheon(3/4"NPT) (Figure 6) I 05 Sidewall with Standard TY3735 Escutcheon(3/4"NPT) (Figure 8) 06 Sidewall with Deep TY3735 TEMPERATURE SAMPLE ORDER Escutcheon(3/4"NPT) (Figure 9) RATINGS(2) LENGTHS(3) 07 Sidewall without TY3735 0 135°F(57°C) Escutcheon(3/4"NPT) (Figure 10) 055 5.50" 1 155°F(68°C) 082 8.25" Pendent with Standard TY3235 2 175°F(79°C) 36 Escutcheon(1"NPT) (Figure 3) 180 18.00" 3 200°F(93°C) Pendent with Deep TY3235 187 18.75" 33 Escutcheon(1"NPT) (Figure 5) 4 286°F(141°C) 372 37.25" 37 Pendent with Standard Recessed TY3235 480 48.00" Escutcheon(1"NPT) (Figure 4) 32 Pendent without TY3235 Escutcheon(1"NPT) (Figure 6) I Notes ' Use Prefix "I" for ISO 7-R1 Connection; for example, 34 Sidewall with Standard TY3335 1-60-010-4-055. Escutcheon(1"NPT) (Figure 8) 1. Escutcheon Finish applies to sprinklers provided with escutcheons. 43 Sidewall with Deep TY3335 2. 286°F(141°C)temperature rating applies to non-recessed Escutcheon(1"NPT) (Figure 9) sprinkler assemblies. 3. Dry-Type Sprinklers are furnished based upon "Order as Sidewall without TY3335 Length"as measured per Figures 3 through 10,as appli- Escutcheon(1'NPT) (Figure 10) cable, and for each individual sprinkler where it is to be I installed.After the measurement is taken, round it to the nearest 1/4 inch increment. 38 Upright without TY3135 Escutcheon(1"NPT) (Figure 7) TABLE C SERIES DS-1 DRY-TYPE SPRINKLERS — PART NUMBER SELECTION— Copyright©2009,2011 Tyco Fire Suppression&Building Products.All rights reserved. r RECEIVED APR 162013 ' 1 CITYOFTIGARD I' _ -_- -- -- - -- - — B UILDING DIVISION 111 I1Z It2r,. rT N 2 ,. v aw cL,T AT NEW — 11 - l a'L 11 -101z 11 -'0 JI-!0 13-7„ 5.- ::;'Z o - tl�5i/t U ) 0� :, 4,<rEi<l^e .owe .. 'I-- till v\P au... � .:R . E.5. COOLER a© xz0 -o- cis. R) 1s'-aFREEZER ,(4 ,1&i �S /A1 C e-xi 1 I/V el 4")"1l-I `BY T' ft, ./ A-pplet X 301-0" AwA�Y. \n, r N ,a 1 1 14 lid /1L 'f; 2N ♦\ 11 - JD'2 \* If-lO1z \* 1/ -/� \• f1- lo * H: \ t \? :� ,�;: z 5-oz NE14 2x1 x2 Ts . / w 1"P4-04 (mil?4 2) E.S. i i ' -�Pe ill ,_ - ' , � 54 A I , A r CC 6 , ,„.-----__,........----) , UAi '?'v cX,4!` �• �- 9,2� ,_it w NakP 4- x2t !7T �- RENEVIlAL: DEC. 31, 20 Ptvl � 4 0k7a __ � GROUND FLOOR PLAN �,_�.,-,_-._. - i������°°`�;; � � _ CITY OF TIGARI3 � � �' _} 14a" = 1`-f�" Approved [ /a,4--R.7) 1 OR 97ZZ S Conditionally Approved [ ] i<5/1-7-71- 3le0 -4o94 -8DGQ See Letter to: Follow [ i Attayii ii1 [ Permit Number: r/691_..1_-.12t2€25:0 Address:! PG 70 SW MA)/ f8L yp. By: Miff Day,:: =_43-- CDA1 7?,4 e...74R C61414-12.2.441<C cc rwi PA J Y ;:�!`s•.. AII VA-JC 7 VV YAT T 9/20 �.� �oaP� 440i 14A- 9 Ec�6Z �'YA'��.DU .�., " FIRE PROTECTION, INC. f 9095 S.W. Burnham g Ti ard, OR 97223 OFFICE COPY (503) 684-2928