Report
SUBMITTAL TRANSMITTAL TO SUBCONTRACTOR BU I L D S 11308 SW 68th Parkway Tigard,OR 97223 Submittal T: 503.547 0859 No 24 Date 4/17/2013 F: Project Comcast Tech Ops West To Cosco Fire Protection 11800 NE 95th Street,#240 Vancouver,WA 98682 Attention Kevin Friesen Phone 360.883.6383 Fax 360.883.6390 The following submittals are transmitted for your use Please review and note any additional information or corrections that are required COPIES SECTION DESCRIPTION DATE SUB DATE BACK STATUS SUBMITTED TO SUB 210000 SPRINKLER SYSTEM 1 210000 01 First Floor Sprinkler Plan 4/8/2013 4/17/2013 APR 1 210000.02 Second Floor Sprinkler Plan 4/8/2013 4/17/2013 APR 1 210000.03 Sprinkler Material 8 Accessories 4/8/2013 4/17/2013 APR 1 210000.04 Hydrolic Calculations 4/8/2013 4/17/2013 APR DEFINITION OF STATUS APR Submittal is APPROVED AS NOTED,please proceed with fabrication and notify us of your lead time REJ Submittal is REJECTED,please revise and resubmit REMARKS DESIGN-BUILD SUBCONTRACTOR IS RESPONSIBLE FOR CODE COMPLIANCE.VERIFY HEADS LOCATIONS INFIELD FOR NEW AND EXISTING MEP. APPROVED AS NOTED. Signed Vishnu Jhaveri, LEED AP PS 20\3—COO 5co File: Cosco Fire Protection c` r � �w y • Submittal File: 210000-24 `�`r v `� 1! Job No: PC12682 RECB V ED APR 3 0 2013 CITUL NVSION BUILDD GD Submittal Review This review is only for general conformance with the design concept and the information given in the Construction Documents. Corrections or comments made on the shop drawings during this review do not relieve the contractor from compliance with the requirements of the plans and specifications. Approval of a specific item shall not include approval of an assembly of which the item is a component. The contractor is responsible for: dimensions to be confirmed and correlated at the jobsite; means, methods, techniques, sequences, and procedures of construction; coordination of the Work with that of all other trades and performing all Work in a safe and satisfactory manner. Review does not authorize changes to the contract documents ❑ Approved ❑ Not Subject to Review ❑ Approved As Noted ❑ No Action Required ❑ Revise& Resubmit ❑ Rejected • Reviewed For Design Intent Only Project No: 12018 Sub. #: 24 Review By: RG Date: 04-17-13 Gromatzky Dupree & Associates RECEIve im Alm% APR 342013 CITY OF TIGARD BUILDING DIVISION . Fire Protection by Computer Design Cosco Fire Protection 11800 NE 95th Street suite#240 Vancouver, Washington 98682 360-883-6383 Job Name : Comcast TOC Building : FS-2 Location : 11308 SW 68th Parkway, Tigard, OR 97223 System : 1 Contract : 24PD5111 Data File : PD5111 2nd Floor E.C. Heads Remote 1.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Cosco Fire Protection Page 1 Comcast TOC Date 3/11/13 HYDRAULIC CALCULATIONS for Project name: Comcast TOC Location: 11308 SW 68th Parkway, Tigard, OR 97223 Drawing no: FS-2 Date: 3.11.13 Design Remote area number: 1 Remote area location: Open Office 223 Occupancy classification: Light Hazard Density: .10- Gpm/SqFt Area of application: 948-SqFt Coverage per sprinkler: 256- SqFt Type of sprinklers calculated: Viking VK534 EC Pendent 11.2 K-Fact. No. of sprinklers calculated: 6 In-rack demand: -GPM Hose streams: - GPM Total water required(including hose streams): 198.38-GPM @ 67.780 - Psi Type of system: Wet Volume of dry or preaction system: N/A- Gal Water supply information Date: 5/4/1999 Location: Atlanta and SW 68th Ave. Source: Tualatin Valley Water District Name of contractor: Cosco Fire Protection Address: 11800 NE 95th St., Suite 240, Vancouver, WA Phone number: 360.883.6383 Name of designer: Ken Molinari Authority having jurisdiction: City of Tigard Notes: (Include peaking information or gridded systems here.) Note: 30 feet added to each drop for equivalent length for friction loss of the Flex drop Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) • • Cosco Fire Protection Page 2 Comcast TOC Date 3/11/13 City Water Supply: Demand: C1 -Static Pressure : 88 D1 - Elevation : 11.261 C2- Residual Pressure: 70 D2-System Flow : 198.378 C2- Residual Flow : 1800 D2- System Pressure : 73.570 Hose(Adj City ) Hose( Demand ) : 100 D3- System Demand : 298.378 Safety Margin : 13.782 150 • 140 130 P 120 R 110 E 100 S 90 0-- C1 80 S o--o D2 - C2 U 70 — - R 60 E 50 40 30 20 10 ° D1 200 400 600 800 1000 1200 1400 1600 1800 FLOW( NA1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Cosco Fire Protection Page 3 Comcast TOC Date 3/11/13 Fitting Legend Abbrev. Name 1/2 3/4 1 1% 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24 B BFV 0 0 5 5 5 5 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90*Ell 2 2 2 3 4 5 4.3 5 8 7 8.5 10 13 17 20 35 40 45 50 61 T Tee 3 4 5 6 8 10 10.3 13 17 17 21 25 33 42 50 71 81 91 101 121 Ue* UG 90*Ell 8 12 17.3 21.3 23.9 Uf* UG 45*Ell 5.3 9.3 12 14.6 18.6 I Ug* UG Gate Va 2.7 4 5.3 6.7 8 Ut* UG Tee 26.6 39.9 46.6 66.5 79.8 Zab Ames 2000SE Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 Pressure/ Flow Summary - STANDARD Cosco Fire Protection Page 4 - Comcast TOC Date 3/11/13 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. 91 26.0 11.2 8.76 na 33.15 0.1 256 7.2 92 26.0 11.2 9.2 na 33.97 0.1 256 7.2 93 26.0 11.2 12.49 na 39.59 0.1 256 7.2 94 26.0 11.2 7.2 na 30.05 0.1 256 7.2 95 26.0 11.2 7.57 na 30.81 0.1 256 7.2 96 26.0 11.2 7.57 na 30.81 0.1 256 7.2 81 31.167 19.44 na 82 31.167 20.49 na 83 31.167 28.21 na 72 31.167 33.78 na 84 31.167 15.74 na 85 31.167 16.61 na 86 31.167 30.35 na 71 31.167 34.56 na 62 26.917 37.13 na 61 26.917 37.54 na 60 26.917 48.37 na 55 26.917 55.68 na 50 26.917 56.05 na 45 14.25 61.79 na 40 3.0 66.99 na BOR 3.0 67.78 na SM1 3.0 72.08 na SCR 0.0 73.57 na 100.0 The maximum velocity is 19.66 and it occurs in the pipe between nodes 85 and 86 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Cosco Fire Protection Page 5 Comcast TOC Date 3/11/13 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 91 33.15 1.049 1T 5.0 34.000 8.759 K Factor= 11.20 to 120.0 0.0 5.000 -2.238 81 33.15 0.3314 0.0 39.000 12_.923 Vel = 12.31 0.0 33.15 19.444 K Factor= 7.52 92 33.97 1.049 1T 5.0 34.000 9.202 K Factor= 11.20 to 120.0 0.0 5.000 -2.238 82 33.97 0.3488 0.0 39.000 13.526 Vel= 12.61 0.0 33.97 20.490 K Factor= 7.50 93 39.59 1.049 1T 5.0 34.000 12.494 K Factor= 11.20 to 120.0 0.0 5.000 -2.238 83 39.59 0.4602 0.0 39.000 17.949 Vel = 14.70 0.0 39.59 28.205 K Factor= 7.45 94 30.05 1.049 1T 5.0 34.000 7.200 K Factor=11.20 to 120.0 0.0 5.000 -2.238 84 30.05 0.2764 0.0 39.000 10.780 Vel= 11.16 . 0.0 30.05 15.742 K Factor= 7.57 95 30.81 1.049 1T 5.0 34.000 7.566 K Factor= 11.20 to 120.0 0.0 5.000 -2.238 85 30.81 0.2894 0.0 39.000 11.287 Vel = 11.44 0.0 30.81 16.615 K Factor= 7.56 96 30.81 1.049 1T 5.0 34.000 7.566 K Factor= 11.20 to 120.0 0.0 5.000 -2.238 85 30.81 0.2894 0.0 39.000 11.287 Vel = 11.44 0.0 30.81 16.615 K Factor= 7.56 81 33.15 1.38 0.0 12.000 19.444 to 120.0 0.0 0.0 0.0 82 33.15 0.0872 0.0 12.000 1.046 Vel= 7.11 82 33.97 1.38 0.0 24.000 20.490 to 120.0 0.0 0.0 0.0 83 67.12 0.3215 0.0 24.000 7.715 Vel= 14.40 83 39.59 1.61 1T 8.0 7.583 28.205 to 120.0 0.0 8.000 0.0 72 106.71 0.3578 0.0 15.583 5.575 Vel = 16.82 72 0.0 2.067 1T 10.0 4.250 33.780 to 120.0 0.0 10.000 1.841 6.2 106.71 0.1060 0.0 14.250 1.510 Vel = 10.20 0.0 106.71 37.131 K Factor= 17.51 84 30.05 1.38 0.0 12.000 15.742 to 120.0 0.0 0.0 0.0 85 30.05 0.0728 0.0 12.000 0.873 V el = 6.45 85 61.62 1.38 0.0 24.000 16.615 to 120.0 0.0 0.0 0.0 86 91.67 0.5722 0.0 24.000 13.732 Vel = 19.66 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • Final Calculations - Hazen-Williams Cosco Fire Protection Page 6 . Comcast TOC Date 3/11/13 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 86 0.0 1.61 1T 8.0 7.583 30.347 to 120.0 0.0 8.000 0.0 71 91.67 0.2701 0.0 15.583 4.209 Vel= 14.45 71 0.0 2.067 1T 10.0 4.250 34.556 to 120.0 0.0 10.000 1.841 61 91.67 0.0800 0.0 14.250 1.140 Vel= 8.76 0.0 91.67 37.537 K Factor= 14.96 62 106.71 2.635 0.0 12.500 37.131 to 120.0 0.0 0.0 0.0 61 106.71 0.0325 0.0 12.500 0.406 Vel= 6.28 61 91.67 2.635 1T 14.14 91.750 37.537 to 120.0 0.0 14.140 0.0 60 198.38 0.1023 0.0 105.890 10.831 Vel= 11.67 60 0.0 3.26 1E 6.72 177.333 48.368 to 120.0 1T 17.471 24.191 0.0 55 198.38 0.0363 0.0 201.524 7.311 Vel= 7.63 55 0.0 4.26 1T 22.384 6.250 55.679 to 120.0 1E 9.217 31.601 0.0 50 198.38 0.0099 _ 0.0 37.851 0.373 Vel= 4.47 . 50 0.0 4.26 1E 9.217 15.917 56.052 to 120.0 0.0 9.217 5.486 45 198.38 0.0099 0.0 25.134 0.248 Vel= 4.47 45 0.0 4.26 1E 9.217 24.500 61.786 to 120.0 0.0 9.217 4.872 40 198.38 0.0098 0.0 33.717 0.332 Vel= 4.47 40 0.0 4.26 1E 9.217 10.250 66.990 to 120.0 2T 44.768 69.785 0.0 BOR 198.38 0.0099 1B 15.8 80.035 0.790 Vel = 4.47 BOR 0.0 6.357 1T 31.433 10.000 67.780 to 120.0 1 E 12.573 44.006 4.224 *Fixed loss=4.224 SM1 198.38 0.0014 1Zab 0.0 54.006 0.075 Vel= 2.01 SM1 0.0 8.27 4Ue 69.2 475.000 72.079 to 140.0 1 Uf 12.0 179.700 1.299 SCR 198.38 0.0003 2Ut 93.2 654.700 0.192 Vel= 1.18 1Ug 5.3 100.00 Qa= 100.00 298.38 73.570 K Factor= 34.79 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 ii-A- _ _ _ Fire Protection by Computer Design Cosco Fire Protection 11800 NE 95th Street suite#240 Vancouver, Washington 98682 360-883-6383 Job Name : Comcast TOC Building : FS-2 Location : 11308 SW 68th Parkway, Tigard, OR 97223 System : 2 Contract : 24PD5111 Data File : PD5111 2nd Floor E.C. Heads Remote 2.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Cosco Fire Protection Page 1 Comcast TOC Date 3/11/13 HYDRAULIC CALCULATIONS for Project name: Comcast TOC Location: 11308 SW 68th Parkway, Tigard, OR 97223 Drawing no: FS-2 Date: 4.5.13 Design Remote area number: 2 Remote area location: Open Office 269 Occupancy classification: Light Hazard Density: .10- Gpm/SqFt Area of application: 1 181 -SgFt Coverage per sprinkler: 256- SqFt Type of sprinklers calculated: Viking VK 534 EC Pendent 11.2 K-Fact. No. of sprinklers calculated: 5 In-rack demand: - GPM Hose streams: - GPM Total water required(including hose streams): 180.36-GPM @ 62.812 - Psi Type of system: Wet Volume of dry or preaction system: N/A- Gal Water supply information Date: 5/4/1999 Location: Atlanta and SW 68th Ave. Source: Tualatin Valley Water District Name of contractor: Cosco Fire Protection Address: 11800 NE 95th St., Suite 240, Vancouver, WA Phone number: 360.883.6383 Name of designer: Ken Molinari Authority having jurisdiction: City of Tigard Notes: (Include peaking information or gridded systems here.) Note: 30 feet added to each head for equivalent friction loss of the Flex drop Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • Water Supply Curve (C) Cosco Fire Protection Page 2 Comcast TOC Date 3/11/13 City Water Supply: Demand: C1 - Static Pressure : 88 D1 - Elevation : 11.261 C2- Residual Pressure: 70 D2- System Flow : 180.362 C2- Residual Flow : 1800 D2 -System Pressure : 68.775 Hose(Adj City ) Hose( Demand ) : 100 D3- System Demand : 280.362 Safety Margin : 18.648 150 140 130 p120 R 110 E 100 S90 a— C1 - S 80 - - D2 C2 U 70 —o — R 60 E 50 40 30 20 10 ° D1 _ . . . 200 400 600 800 1000 1200 1400 1600 1800 FLOW( N ^ 1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Cosco Fire Protection Page 3 Comcast TOC Date 3/11/13 Fitting Legend Abbrev. Name 1/2 1/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24 B BFV 0 0 5 5 5 5 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90*Ell 2 2 2 3 4 5 4.3 5 8 7 8.5 10 13 17 20 35 40 45 50 61 T Tee 3 4 5 6 8 10 10.3 13 17 17 21 25 33 42 50 71 81 91 101 121 Ue* UG 90*Ell 8 12 17.3 21.3 23.9 Uf* UG 45*Ell 5.3 9.3 12 14.6 18.6 Ug* UG Gate Va 2.7 4 5.3 6.7 8 Ut* UG Tee 26.6 39.9 46.6 66.5 79.8 Zab Ames 2000SE Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • Pressure/ Flow Summary - STANDARD Cosco Fire Protection Page 4 • Comcast TOC Date 3/11/13 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual _ Req. 171 26.0 11.2 7.2 na 30.05 0.1 256 7.2 172 26.0 11.2 8.66 na 32.97 0.1 256 7.2 173 26.0 11.2 10.81 na 36.83 0.1 256 7.2 174 26.0 11.2 12,47 na 39.54 0.1 256 7.2 175 26.0 11.2 13.38 na 40.97 0.1 256 7.2 161 31.167 16.62 na 162 31.167 20.26 na 163 31.167 25.55 na 164 31.167 38.84 na 159 31.167 42.24 na 165 31.167 29.59 na 166 31.167 31.83 na 167 31.167 40.76 na 158 31.167 43.04 na 155 26.917 45.42 na 154 26.917 45.78 na 150 26.917 50.51 na 50 26.917 51.3 na 45 14.25 57.0 na 40 3.0 62.15 na BOR 3.0 62.81 na SM1 3.0 67.32 na SCR 0.0 68.78 na 100.0 The maximum velocity is 21.42 and it occurs in the pipe between nodes 163 and 164 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams • Cosco Fire Protection Page 5 Comcast TOC Date 3/11/13 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 171 30.05 1.049 1E 2.0 35.167 7.200 K Factor= 11.20 to 120.0 1T 5.0 7.000 -2.238 161 30.05 0.2764 0.0 42.167 11.656 Vel = 11.16 0.0 30.05 16.618 K Factor= 7.37 172 32.97 1.049 1E 2.0 35.167 8.664 K Factor= 11.20 to 120.0 1T 5.0 7.000 -2.238 162 32.97 0.3280 0.0 42.167 13.831 Vel= 12.24 0.0 32.97 20.257 K Factor= 7.33 173 36.83 1.049 1E 2.0 35.167 10.811 K Factor=11.20 to 120.0 1T 5.0 7.000 -2.238 163 36.83 0.4026 0.0 42.167 16.977 Vel= 13.67 0.0 36.83 25.550 K Factor= 7.29 174 39.54 1.049 1E 2.0 35.167 12.466 K Factor=11.20 to 120.0 1T 5.0 7.000 -2.238 1.65 39.54 0.4592 0.0 42.167 19.365 Vel= 14.68 0.0 39.54 29.593 K Factor= 7.27 175 40.97 1.049 1E 2.0 35.167 13.384 K Factor= 11.20 - to 120.0 1T 5.0 7.000 -2.238 166 40.97 0.4905 0.0 42.167 20.682 Vel= 15.21 0.0 40.97 31.828 K Factor= 7.26 161 30.05 1.049 0.0 13.167 16.618 to 120.0 0.0 0.0 0.0 162 30.05 0.2764 0.0 13.167 3.639 Vel= 11.16 162 32.97 1.38 0.0 18.500 20.257 to 120.0 0.0 0.0 0.0 163 63.02 0.2861 0.0 18.500 5.293 Vel= 13.52 163 36.82 1.38 0.0 19.833 25.550 to 120.0 0.0 0.0 0.0 164 99.84 0.6701 0.0 19.833 13.291 Vel= 21.42 164 0.0 1.61 1T 8.0 2.750 38.841 to 120.0 0.0 8.000 0.0 159 99.84 0.3164 0.0 10.750 3.401 Vel= 15.73 159 0.0 2.067 1T 10.0 4.250 42.242 to 120.0 0.0 10.000 1.841 15.5 99.84 0.0937 0.0 14.250 1.335 Vel= 9.55 0.0 99.84 45.418 K Factor= 14.81 165 39.54 1.38 0.0 18.500 29.593 to 120.0 0.0 0.0 0.0 166 39.54 0.1208 0.0 18.500 2.235 Vel= 8.48 166 40.98 1.38 0.0 19.833 31.828 to 120.0 0.0 0.0 0.0 - 167 80.52 0.4501 0.0 19.833 8.927 Vel= 17.27 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • . Final Calculations - Hazen-Williams Cosco Fire Protection Page 6 . Comcast TOC Date 3/11/13 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 167 0.0 1.61 1T 8.0 2.750 40.755 to 120.0 0.0 8.000 0.0 158 80.52 0.2125 0.0 10.750 2.284 Vel = 12.69 158 0.0 2.067 1T 10.0 4.250 43.039 to 120.0 0.0 10.000 1.841 154 80.52 0.0629 0.0 14.250 0.897 Vel= 7.70 0.0 80.52 45.777 K Factor= 11.90 155 99.84 2.635 0.0 12.500 45.418 to 120.0 0.0 0.0 0.0 154 99.84 0.0287 0.0 12.500 0.359 Vel= 5.87 154 80.52 2.635 0.0 55.167 45.777 to 120.0 0.0 0.0 0.0 150 180.36 0.0858 0.0 55.167 4.731 Vel = 10.61 150 0.0 3.26 1E 6.72 2.000 50.508 to 120.0 1T 17.471 24.191 0.0 50 180.36 0.0304 0.0 26.191 0.797 Vel= 6.93 50 0.0 4.26 1E 9.217 15.917 51.305 to 120.0 0.0 9.217 5.486 45 180.36 0.0083 0.0 25.134 0.208 Vel = 4.06 . 45 0.0 4.26 1E 9.217 24.500 56.999 to 120.0 0.0 9.217 4.872 40 180.36 0.0083 0.0 33.717 0.279 Vel = 4.06 40 0.0 4.26 1E 9.217 10.250 62.150 to 120.0 2T 44.768 69.785 0.0 BOR 180.36 0.0083 1B 15.8 80.035 0.662 Vel = 4.06 BOR 0.0 6.357 1T 31.433 10.000 62.812 to 120.0 1E 12.573 44.006 4.440 *Fixed loss=4.44 SM1 180.36 0.0012 1Zab 0.0 54.006 0.063 Vel= 1.82 SM1 0.0 8.27 4Ue 69.2 475.000 67.315 to 140.0 1 Uf 12.0 179.700 1.299 SCR 180.36 0.0002 2Ut 93.2 654.700 0.161 Vel = 1.08 1 Ug 5.3 100.00 Qa= 100.00 280.36 68.775 K Factor= 33.81 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 / ! . . Fire Protection by Computer Design Cosco Fire Protection 11800 NE 95th Street suite#240 Vancouver, Washington 98682 360-883-6383 Job Name : Comcast TOC Building : FS-1 Location : 11308 SW 68th Parkway,Tigard, OR 97223 System : 3 Contract : 24PD5111 Data File : PD5111 1st Floor Ord. Gp. 2 Reduced Area Remote 3.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • Cosco Fire Protection Page 1 Comcast TOC Date 3/11/13 HYDRAULIC CALCULATIONS for Project name: Comcast TOC Location: 11308 SW 68th Parkway, Tigard, OR 97223 Drawing no: FS-1 Date: 4.4.13 Design Remote area number: 3 Remote area location: Warehouse 101 Occupancy classification: O.H. Gp. 2 Density: .20-Gpm/SqFt Area of application: 1020-SqFt Coverage per sprinkler: 112-SqFt Type of sprinklers calculated: Viking VK300 QR Upright No. of sprinklers calculated: 9 In-rack demand: -GPM Hose streams: -GPM Total water required(including hose streams): 221.51 -GPM @ 54.696 - Psi Type of system: Wet Volume of dry or preaction system: N/A- Gal Water supply information Date: 5/4/1999 • Location: Atlanta and SW 68th Ave. Source: Tualatin Valley Water District Name of contractor: Cosco Fire Protection Address: 11800 NE 95th St., Suite 240, Vancouver, WA Phone number: 360.883.6383 Name of designer: Ken Molinari Authority having jurisdiction: City of Tigard Notes:(Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) Cosco Fire Protection Page 2 Comcast TOC Date 3/11/13 City Water Supply: Demand: C1 - Static Pressure : 88 D1 - Elevation : 5.883 C2- Residual Pressure: 70 D2-System Flow : 221.508 C2- Residual Flow : 1800 D2-System Pressure : 60.259 Hose(Adj City ) Hose( Demand ) : 250 D3-System Demand : 471.508 Safety Margin : 26.231 150 140 130 P 120 R 110 E 100 S90 Cl S 80 _ - C2 U 70 - D2 R 60 ? 0 E 50 D3 40 30 20 10 • 200 400 600 800 1000 1200 1400 1600 1800 FLOW( NA1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Cosco Fire Protection Page 3 Comcast TOC Date 3/11/13 Fitting Legend Abbrev. Name 1/2 % 1 1% 11/2 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24 B BFV 0 0 5 5 5 5 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90*Ell 2 2 2 3 4 5 4.3 5 8 7 8.5 10 13 17 20 35 40 45 50 61 T Tee 3 4 5 6 8 10 10.3 13 17 17 21 25 33 42 50 71 81 91 101 121 Ue* UG 90*Ell 8 12 17.3 21.3 23.9 Uf' UG 45*Ell 5.3 9.3 12 14.6 18.6 Ug* UG Gate Va 2.7 4 5.3 6.7 8 Ut* UG Tee 26.6 39.9 46.6 66.5 79.8 Zab Ames 2000SE Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 Pressure/ Flow Summary - STANDARD Cosco Fire Protection Page 4 • Comcast TOC Date 3/11/13 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. 81 13.583 5.6 16.1 na 22.47 0.2 112.333 7.0 82 13.583 5.6 16.48 na 22.74 0.2 112.333 7.0 83 13.583 5.6 17.9 na 23.69 0.2 112.333 7.0 84 13.583 5.6 21.38 na 25.89 0.2 112.333 7.0 88 13.583 5.6 22.06 na 26.3 0.2 112.333 7.0 85 13.583 5.6 16.62 na 22.83 0.2 112.333 7.0 86 13.583 5.6 17.02 na 23.1 0.2 112.333 7.0 87 13.583 5.6 18.48 na 24.07 0.2 112.333 7.0 89 13.583 5.6 29.51 na 30.42 0.2 112.333 7.0 75 11.0 23.01 na 74 11.0 23.71 na 73 11.0 31.5 na 65 11.0 28.24 na 64 11.0 29.09 na 63 11.0 32.14 na 62 11.0 48.76 na 40 3.0 53.73 na BOR 3.0 54.7 na SM1 3.0 58.72 na SCR 0.0 60.26 na 250.0 The maximum velocity is 20.66 and it occurs in the pipe between nodes 74 and 64 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Cosco Fire Protection Page 5 Comcast TOC Date 3/11/13 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv """`•'" Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 81 22.47 1.38 0.0 9.167 16.095 K Factor= 5.60 to 120.0 0.0 0.0 0.0 82 22.47 0.0424 0.0 9.167 0.389 Vel= 4.82 82 22.73 1.38 0.0 9.167 16.484 K Factor= 5.60 to 120.0 0.0 0.0 0.0 83 45.2 0.1547 0.0 9.167 1.418 Vel= 9.70 83 23.70 1.38 1T 6.0 5.833 17.902 K Factor=5.60 to 120.0 0.0 6.000 1.119 75 68.9 0.3374 0.0 11.833 3.992 Vel = 14.78 0.0 68.90 23.013 K Factor= 14.36 84 25.89 1.38 1T 6.0 3.333 21.380 K Factor=5.60 to 120.0 0.0 6.000 1.119 7.5 25.89 0.0551 0.0 9.333 0.514 Vel= 5.55 0.0 25.89 23.013 K Factor= 5.40 88 26.30 1.38 1T 6.0 3.333 22.057 K Factor=5.60 to 120.0 0.0 6.000 1.119 74 26.3 0.0568 0.0 9.333 0.530 Vel= 5.64 0.0 26.30 23.706 K Factor= 5.40 . 85 22.83 1.38 0.0 9.167 16.615 K Factor= 5.60 to 120.0 0.0 0.0 0.0 86 22.83 0.0437 0.0 9.167 0.401 Vel= 4.90 86 23.10 1.38 0.0 9.167 17.016 K Factor=5.60 to 120.0 0.0 0.0 0.0 87 45.93 0.1593 0.0 9.167 1.460 Vel= 9.85 87 24.07 1.38 1T 6.0 5.833 18.476 K Factor=5.60 to 120.0 0.0 6.000 1.119 74 70.0 0.3474 0.0 11.833 4.111 Vel = 15.02 0.0 70.00 23.706 K Factor= 14.38 89 30.42 1.38 1T 6.0 5.833 29.506 K Factor=5.60 to 120.0 0.0 6.000 1.119 73 30.42 0.0743 0.0 11.833 0.879 Vel= 6.53 0.0 30.42 31.504 K Factor= 5.42 75 94.79 1.38 1T 6.0 2.583 23.013 to 120.0 0.0 6.000 0.0 65 94.79 0.6089 0.0 8.583 5.226 Vel= 20.33 0.0 94.79 28.239 K Factor= 17.84 74 96.30 1.38 1T 6.0 2.583 23.706 to 120.0 0.0 6.000 0.0 64 96.3 0.6268 0.0 8.583 5.380 Vel= 20.66 0.0 96.30 29.086 K Factor= 17.86 - 73 30.42 1.38 1T 6.0 2.583 31.504 to 120.0 0.0 6.000 0.0 63 30.42 0.0743 0.0 8.583 0.638 Vel= 6.53 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Cosco Fire Protection Page 6 Comcast TOC Date 3/11/13 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 0.0 30.42 32.142 K Factor= 5.37 65 94.79 2.157 0.0 12.250 28.239 to 120.0 0.0 0.0 0.0 64 94.79 0.0691 0.0 12.250 0.847 Vel = 8.32 64 96.30 2.157 0.0 12.083 29.086 to 120.0 0.0 0.0 0.0 63 191.09 0.2529 0.0 12.083 3.056 Vel = 16.78 63 30.42 2.157 2E 12.307 37.667 32.142 to 120.0 0.0 12.307 0.0 62 221.51 0.3325 0.0 49.974 16.616 Vel= 19.45 62 0.0 4.26 2E 18.434 106.083 48.758 to 120.0 0.0 18.434 3.465 40 221.51 0.0121 0.0 124.517 1.505 Vel= 4.99 40 0.0 4.26 1E 9.217 10.250 53.728 to 120.0 2T 44.768 69.785 0.0 BOR 221.51 0.0121 1B 15.8 80.035 0.968 Vel = 4.99 BOR 0.0 6.357 1T 31.433 10.000 54.696 to 120.0 1E 12.573 44.006 3.936 *Fixed loss=3.936 SM1 221.51 0.0017 1Zab 0.0 54.006 0.093 Vel= 2.24 . SM1 0.0 8.27 4Ue 69.2 475.000 58.725 to 140.0 1 Uf 12.0 179.700 1.299 SCR 221.51 0.0004 2Ut 93.2 654.700 0.235 Vel= 1.32 1Ug 5.3 250.00 Qa= 250.00 471.51 60.259 K Factor= 60.74 Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 IMMAMMV _ Fire Protection by Computer Design Cosco Fire Protection 11800 NE 95th Street suite#240 Vancouver, Washington 98682 360-883-6383 Job Name : Comcast TOC Building : FS-1 Location : 11308 SW 68th Parkway, Tigard, OR 97223 System : 4 Contract : 24PD5111 Data File : PD5111 1st Floor Ord. Gp. 2 Reduced Area Remote 4.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • Cosco Fire Protection Page 1 • Comcast TOC Date 3/11/13 HYDRAULIC CALCULATIONS for Project name: Comcast TOC Location: 11308 SW 68th Parkway, Tigard, OR 97223 Drawing no: FS-1 Date: 4.4.13 Design Remote area number: 4 Remote area location: Warehouse 101 Occupancy classification: O.H. Gp. 2 Density: .20-Gpm/SqFt Area of application: 1034-SqFt Coverage per sprinkler: 108-SqFt Type of sprinklers calculated: Viking VK300 OR Upright No. of sprinklers calculated: 11 In-rack demand: - GPM Hose streams: - GPM Total water required(including hose streams): 255.71 -GPM @ 46.506- Psi Type of system: Wet Volume of dry or preaction system: N/A-Gal Water supply information Date: 5/4/1999 Location: Atlanta and SW 68th Ave. Source: Tualatin Valley Water District Name of contractor: Cosco Fire Protection Address: 11800 NE 95th St., Suite 240, Vancouver, WA Phone number: 360.883.6383 Name of designer: Ken Molinari Authority having jurisdiction: City of Tigard Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) • Cosco Fire Protection Page 2 Comcast TOC Date 3/11/13 City Water Supply: Demand: C1 -Static Pressure : 88 D1 - Elevation : 5.885 C2- Residual Pressure: 70 D2-System Flow : 255.714 C2 - Residual Flow : 1800 D2- System Pressure : 51.762 Hose(Adj City ) Hose( Demand ) : 250 D3-System Demand : 505.714 Safety Margin : 34.519 150 140 130 P 120 R 110 E 100 ' S90 4-- C1 s 80 C2 U 70 O R 60 D2 E 50 _ o 40 Q3 30 20 10 41 - . . 200 400 600 800 1000 1200 1400 1600 1800 FLOW( N ^ 1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Cosco Fire Protection Page 3 Comcast TOC Date 3/11/13 Fitting Legend Abbrev. Name 1/2 ' 1 1% 11/2 2 21/2 3 3'/2 4 5 6 8 10 12 14 16 18 20 24 B BFV 0 0 5 5 5 5 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90•Ell 2 2 2 3 4 5 4.3 5 8 7 8.5 10 13 17 20 35 40 45 50 61 T Tee 3 4 5 6 8 10 10.3 13 17 17 21 25 33 42 50 71 81 91 101 121 Ue• UG 90'Ell 8 12 17.3 21.3 23.9 Uf• UG45•Ell 5.3 9.3 12 14.6 18.6 Ug• UG Gate Va 2.7 4 5.3 6.7 8 Ut* UG Tee 26.6 39.9 46.6 66.5 79.8 Zab Ames 2000SE Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 • • • Pressure/ Flow Summary - STANDARD Cosco Fire Protection Page 4 ' Comcast TOC Date 3/11/13 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. 101 13.588 5.6 16.87 na 23.0 0.2 101 7.0 102 13.588 5.6 15.79 na 22.25 0.2 108 7.0 103 13.588 5.6 15.54 na 22.07 0.2 108 7.0 104 13.588 5.6 15.55 na 22.08 0.2 108 7.0 105 13.588 5.6 16.0 na 22.4 0.2 108 7.0 106 13.588 5.6 17.44 na 23.39 0.2 108 7.0 107 13.588 5.6 18.38 na 24.01 0.2 108 7.0 108 13.588 5.6 17.71 na 23.56 0.2 108 7.0 109 13.588 5.6 17.64 na 23.52 0.2 108 7.0 142 13.588 27.96 na 117 13.588 19.61 na 118 13.588 18.9 na 119 13.588 18.83 na 110 13.588 5.6 18.98 na 24.4 0.2 122 7.0 111 13.588 5.6 19.96 na 25.02 0.2 122 7.0 132 13.588 27.28 na 152 13.588 31.13 na 232 13.588 28.87 na 242 13.588 29.27 na 252 13.588 31.51 na 131 11.0 30.92 na 141 11.0 31.11 na 151 11.0 32.25 na 231 11.0 30.92 na 241 11.0 31.14 na 251 11.0 32.64 na 160 11.0 34.71 na 51 11.0 36.11 na 50 11.0 40.75 na ' 40 3.0 45.24 na BOR 3.0 46.51 na SM1 3.0 50.16 na SCR 0.0 51.76 na 250.0 The maximum velocity is 15.28 and it occurs in the pipe between nodes 106 and 232 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Cosco Fire Protection Page 5 Comcast TOC Date 3/11/13 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 101 -40.94 1.38 0.0 8.417 16.874 K Factor= 5.60 to 120.0 0.0 0.0 0.0 102 -40.94 -0.1288 0.0 8.417 -1.084 Vel = 8.78 102 22.25 1.38 0.0 8.417 15.790 K Factor=5.60 to 120.0 0.0 0.0 0.0 103 -18.69 -0.0302 0.0 8.417 -0.254 Vel= 4.01 103 22.08 1.38 0.0 8.417 15.536 K Factor=5.60 to 120.0 0.0 0.0 0.0 104 3.39 0.0012 0.0 8.417 0.010 Vel= 0.73 104 22.08 1.38 0.0 8.417 15.546 K Factor= 5.60 to 120.0 0.0 0.0 0.0 105 25.47 0.0536 0.0 8.417 0.451 Vel= 5.46 105 22.39 1.38 0.0 8.417 15.997 K Factor=5.60 to 120.0 0.0 0.0 0.0 106 47.86 0.1719 0.0 8.417 1.447 Vel= 10.27 106 23.39 1.38 1T 6.0 25.833 17.444 K Factor=5.60 to 120.0 0.0 6.000 0.0 232 71.25 0.3590 0.0 31.833 11.429 Vel= 15.28 • 0.0 71.25 28.873 K Factor= 13.26 107 24.01 1.049 1T 5.0 1.750 18.383 K Factor= 5.60 . to 120.0 0.0 5.000 0.0 117 24.01 0.1825 0.0 6.750 1.232 Vel= 8.91 0.0 _ 24.01 19.615 K Factor= 5.42 108 23.56 1.049 1T 5.0 1.750 17.708 K Factor=5.60 to 120.0 0.0 5.000 0.0 118 23.56 0.1761 0.0 6.750 1.189 Vel= 8.75 0.0 23.56 18.897 K Factor= 5.42 109 23.52 1.049 1T 5.0 1.750 17.643 K Factor=5.60 to 120.0 0.0 5.000 0.0 119 23.52 0.1757 0.0 6.750 1.186 Vel= 8.73 0.0 23.52 18.829 K Factor= 5.42 142 -56.76 1.38 1T 6.0 29.417 27.963 to 120.0 0.0 6.000 0.0 117 -56.76 -0.2357 0.0 35.417 -8.348 Vel= 12.18 117 24.01 1.38 0.0 8.417 19.615 to 120.0 0.0 0.0 0.0 118 -32.75 -0.0853 0.0 8.417 -0.718 Vel= 7.02 118 23.57 1.38 0.0 8.417 18.897 to 120.0 0.0 0.0 0.0 119 -9.18 -0.0081 0.0 8.417 -0.068 Vel = 1.97 119 23.52 1.38 0.0 8.417 18.829 to 120.0 0.0 0.0 0.0 110 14.34 0.0185 0.0 8.417 0.156 Vel = 3.08 . 110 24.40 1.38 0.0 8.417 18.985 K Factor= 5.60 to 120.0 0.0 0.0 0.0 111 38.74 0.1163 0.0 8.417 0.979 Vel = 8.31 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 . Final Calculations - Hazen-Williams Cosco Fire Protection Page 6 • Comcast TOC Date 3/11/13 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Of Pf/Ft Eqv. Ln. Total Pf Pn 111 25.02 1.38 1T 6.0 25.833 19.964 K Factor= 5.60 to 120.0 0.0 6.000 0.0 242 63.76 0.2923 0.0 31.833 9.305 Vel = 13.68 0.0 63.76 29.269 K Factor= 11.79 132 -63.94 1.38 1T 6.0 29.417 27.281 to 120.0 0.0 6.000 0.0 101 -63.94 -0.2938 0.0 35.417 -10.407 Vel= 13.72 0.0 -63.94 16.874 K Factor=-15.57 152 5.78 1.38 2T 12.0 90.917 31.133 to 120.0 2E 6.0 18.000 0.0 252 5.78 0.0034 0.0 108.917 0.375 Vel = 1.24 0.0 5.78 31.508 K Factor= 1.03 132 63.94 1.38 1T 6.0 2.583 27.281 to 120.0 0.0 6.000 1.121 • 131 63.94 0.2938 0.0 8.583 2.522 Vel= 13.72 0.0 63.94 30.924 K Factor= 11.50 • 142 56.76 1.38 1T 6.0 2.583 27.963 to 120.0 0.0 6.000 1.121 141 56.76 0.2357 0.0 8.583 2.023 Vel= 12.18 0.0 56.76 31.107 K Factor= 10.18 152 -5.78 1.38 0.0 2.583 31.133 to 120.0 0.0 0.0 1.121 151 -5.78 -0.0035 0.0 2.583 -0.009 Vel= 1.24 0.0 -5.78 32.245 K Factor= -1.02 232 71.25 1.38 0.0 2.583 28.873 to 120.0 0.0 0.0 1.121 231 71.25 0.3593 0.0 2.583 0.928 Vel= 15.28 0.0 71.25 30.922 K Factor= 12.81 242 63.76 1.38 0.0 2.583 29.269 to 120.0 0.0 0.0 1.121 241 63.76 0.2923 0.0 2.583 0.755 Vel= 13.68 0.0 63.76 31.145 K Factor= 11.42 252 5.78 1.38 0.0 2.583 31.508 to 120.0 0.0 0.0 1.121 251 5.78 0.0035 0.0 2.583 0.009 Vel= 1.24 0.0 5.78 32.638 K Factor= 1.01 131 63.94 2.635 0.0 14.500 30.924 • to 120.0 0.0 0.0 0.0 141 63.94 0.0126 0.0 14.500 0.183 Vel= 3.76 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams , Cosco Fire Protection Page 7 Comcast TOC Date 3/11/13 • Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 141 56.76 2.635 0.0 27.900 31.107 to 120.0 0.0 0.0 0.0 151 120.7 0.0408 0.0 27.900 1.138 Vel= 7.10 151 -5.78 2.635 0.0 66.083 32.245 to 120.0 0.0 0.0 0.0 160 114.92 0.0373 0.0 66.083 2.462 Vel= 6.76 0.0 114.92 34.707 K Factor= 19.51 231 71.25 2.635 0.0 14.500 30.922 to 120.0 0.0 0.0 0.0 241 71.25 0.0154 0.0 14.500 0.223 Vel = 4.19 241 63.76 2.635 0.0 29.750 31.145 to 120.0 0.0 0.0 0.0 251 135.01 0.0502 0.0 29.750 1.493 Vel = 7.94 251 5.78 2.635 0.0 64.083 32.638 to 120.0 0.0 0.0 0.0 51 140.79 0.0542 0.0 64.083 3.476 Vel = 8.28 0.0 140.79 36.114 K Factor= 23.43 160 114.92 3.26 1T 17.471 89.000 34.707 to 120.0 0.0 17.471 0.0 51 114.92 0.0132 0.0 106.471 1.407 Vel = 4.42 51 140.79 3.26 1T 17.471 62.500 36.114 to 120.0 0.0 17.471 0.0 50 255.71 0.0580 0.0 79.971 4.640 Vel= 9.83 50 0.0 4.26 1T 22.384 33.417 40.754 to 120.0 1E 9.217 31.601 3.465 40 255.71 0.0158 0.0 65.018 1.025 Vel= 5.76 40 0.0 4.26 1E 9.217 10.250 45.244 to 120.0 2T 44.768 69.785 0.0 BOR 255.71 0.0158 1B 15.8 80.035 1.262 Vel = 5.76 BOR 0.0 6.357 1T 31.433 10.000 46.506 to 120.0 1E 12.573 44.006 3.528 *Fixed loss=3.528 SM1 255.71 0.0023 1Zab 0.0 54.006 0.122 Vel= 2.58 SM1 0.0 8.27 4Ue 69.2 475.000 50.156 to 140.0 1 Uf 12.0 179.700 1.299 SCR 255.71 0.0005 2Ut 93.2 654.700 0.307 Vel= 1.53 1Ug 5.3 250.00 Qa= 250.00 505.71 51.762 K Factor= 70.29 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 FlexHead ommercial fire sprinkler connections ' r r- ■r -. — '64. ii. ti - , .......1 . Ink Viiimow ; .- . . ' . .- ' . s' ''''' l'-,, vi. `, ^ / _ Si F ' . ,rr i , • ■ ! • : 1 L.ai' li (A1 L .sue r * A �� gc. .. &'. b't. si klt -�. :r ,Irik . . . r I • , ,, . \ .. e 'joi0000000:1011600000000t . IP: # 6 .,,„, , .__ mi, ., . _ \ 0 ,,,,s„: Your connection to INDUSTRIES The pioneers in flexible fire protection higher prod 'vity. nd Lon - costs. 7 :pt(kvilr'' Ric c®us I.pCB snta,�arrnnnc APPROVED LISTED S N.Y.C. MEA #261-99-E CA: OPA-0672 Friction Loss Data and Specifications FlexHead Outlet Hose Maximum Maximum Maximum Maximum Rated Maximum • Model p (orifice) Assembly Number of Equivalent Ambient Pressure K-factor Size Length 90-Degree Length of Temperature in(cm) ft(m) Bends Schedule 40, Rating (3 in. Nominal 1 in. F(C) H-Series 1/1 Bending Diameter Pipe,ft psi (kPa)/psi (kPa) Radius) FM _ UL t/1 2024, 2024H 1/2(1.27) 2(0.6) 3 3.5, 11 11 300 0(148 0) 175(1205)/300(2068) 5.62 2036, 2036H 1/2(1.27) 3(0.9) 3 4.8, 19 16 300°(148°) 175(1205)/300(2068) 5.62 0 2048,2048H 1/2(1.27) 4(1.2) 4 6.8,21 24_ 300 0(148 0) 175(1205)/300(2068) 5.62 2060,2060H 1/2(1.27) 5(1.5) 4 8.5,24 29 300 0(148 0) 175(1205)/300(2068) 5.62 J __- _ 2072,2072H 1/2(1.27) 6(1.8) 4 8.9,27.5 35 300°(148°) 175(1205)/300(2068) 5.62 2024 75, 2024H 75 3/4(1.90) 2(0.6) 3 7.8,15.3 12 300°(148°) 175(1205)1300(2068) 14.0 Z 2036 75,2036H 75 3/4(1.90) 3(0.9) 3 8.1,22.3 18 300°(148°) 175(1205)/300(2068) 14.0 2048 75,2048H 75 3/4(1.90) 4(1.2) 4 17.9,32.1 23 300 0(148 0) 175(1205)/300(2068) 14.0 0 2060 75,2060H 75 3/4(1.90) 5(1.5) 4 19.9,35.4 29 300°(148°) 175(1205)/300(2068) 14.0 _ 2072 75, 2072H 75 3/4(1.90) 6(1.8) 4 24.3,42.9 32 300°(148°) 175(1205)/300(2068) 14.0 2024E, 2024HE 1/2(1.27) 2(0.6) 3 5.5, 13 19 300°(148°) 175(1205)/300(2068) 5.62 2036E, 2036HE 1/2(1.27) 3(0.9) 3 6.8,21 23 300°(148°) 175(1205)/300(2068) 5.62 1.") 2048E, 2048HE 1/2(1.27) 4(1.2) 4 8.8,23 27 300°(148°) 175(1205)/300(2068) 5.62 o-■i 2060E, 2060HE 1/2(1.27) 5(1.5) 4 10.5,26 32 300 0(148 0) 175(1205)/300(2068) 5.62 2072E,2072HE 1/2(1.27) 6(1.8) 4 10.9,29.5 35 300°(148°) 175(1205)/300(2068) 5.62 Q' 2024E 75, 2024HE 75 3/4(1.90) 2(0.6) 3 9.8, 17.3 18 300 0(148 0) 175(1205)/300(2068) 14.0 " 2036E 75,2036HE 75 3/4(1.90) 3(0.9) 3 10.1,24.3 23 300°(148°) 175(1205)/300(2068) 14.0 2048E 75, 2048HE 75 3/4(1.90) 4(1.2) 4 19.9,34.1 23 3000(148 0) 175(1205)1300(2068)_ 14.0 2060E 75, 2060HE 75 3/4(1.90) 5(1.5) 4 21.9,37.4 29 300 0(148 0) 175(1205)/300(2068) 14.0 2072E 75, 2072HE 75 3/4(1.90) 6(1.8) 4 26.3,44.9 32 300°(148°) 175(1205)/300(2068) 14.0 Model Numbers: The"H" designates high pressure unit rated to 300 psig and the "E" designates elbow style unit. FlexHead products are intended for use in hydraulically designed wet, pre-action, deluge or dry pipe sprinkler connections per NFPA 13, 13R, and 13D guidelines. The hydraulic loss of the FlexHead connector needs to be included in the hydraulic design calculations the same as a valve or fitting.Each FlexHead sprinkler drop has a 3"minimum bend radius per UL guidelines, and a 7"minimum bend radius per FM guidelines. * Equivalent lengths are shown with maximum number of 90 degree bends at the minimum bend-radius. Different values were obtained by FM and UL due to the differences in minimum bend radius, testing protocol and calculation methods. Please see individual testing standards for more information relative to friction loss (Equivalent Length of Pipe). Pressure surges aren't a risk for FlexHead connection systems. Our fully braid .,. stainless steel hose is rated to /' ' ' 300 psi. 'r/�� ;, ' r ` Let FlexHead make your connection today. �� , 4 L 6 Engineers Contractors Owners i .; - - - Stainless steel quality Lower installation costs Shorter time to occupan tw- ig at black iron costs More productive installers Lower reconfigurati°' • y -1 I Fast-track construction No punch list items Cost effective c•. /4,1,l'ir �I�. _ ' Their Simplified project Highest quality available compliance industrial grade management Lower total co - f-IL construction is More flexible scheduling of owners ' �' Cost-effective code l-. all-welded, with compliance Competitive advantage 1-0.7' ��l- p for your company -�� no 0 rings. Seismically qualified oil'I -�,- r Connect sprinkler heads to sub-mains at least four times faster. FlexHead systems connect sprinkler heads to sprinkler sub-mains in about a quarter of the time it takes to install hard pipe. Add in the fact that less-skilled people can do the work, and you're looking at significant productivity gains. Expect even greater savings in retrofits, where Want pinpoint locations? No problem. FlexHead installs six to seven times faster than The design makes it easy to accurately locate hard pipe. sprinkler heads every time. If the spec calls for Everything about FlexHead says "fast installation." center-of-tile placement, you can do it with ease. You don't need to install bracing or hangers. There's In fact, you get center-of-tile placement every no on-site assembly. Every sprinkler connection is a install whether the spec calls for it or not. It takes finished, pre-constructed assembly, from the 1" pipe one more headache out of specifying and bidding. connector to the sprinkler head outlet. Accommodate floor plan changes. You pay a little more for FlexHead connections Need to relocate sprinkler heads? No problem. With compared to black iron armovers. But their labor its built-in flexibility it's much easier to move heads savings far exceed the materials premium. to a new location to accommodate new layouts or Installation is simple uses of the space. It doesn't matter whether the sprinkler head is Retrofits in less time. semi-recessed, full pendant or fully concealed, it's a Need to comply to code in unsprinklered buildings? snap to attach to a FlexHead connection system. In contrast to costly and labor-intensive hard-pipe Q Attach the bracket to t-bar ceiling grid. retrofits, FlexHead connections install in minutes in O Connect the FlexHead sprinkler drop to even the most restrictive spaces. the submain. Shorten your time to occupancy. 0 Secure sprinkler drop to the bracket. Faster installation times help get end-users into - That's it! No more wasted hours spent hard-piping. No their spaces more quickly—and get installers on more frustration over changes to blueprints. No more their next projects faster. FlexHead connections lost time fixing leaks and other problems common to virtually eliminate punch list items commonly hard-pipe armovers. found with hard-pipe armovers. Each connection is ready to install right out of the box. It comes complete with a mounting bracket— Green Benefits compatible with any suspended or Sheetrock ceiling Millions of gallons of water are drained from system—and a one-piece, leak-tested FlexHead sprinkler piping every year. FlexHead products sprinkler drop. help minimize hydrostatic testing and eliminate the need to drain down the system when relocating sprinkler heads. Three steps to faster installations. 00, NMI Attach bracket to t-bar ceiling grid. Connect FlexHead sprinkler drop to submain. Secure FlexHead sprinkler drop to bracket. Connection also compatible with Sheetrock ceilings ..n Nom+/./ MINILINIM .4,4,4 \ f _ \ ,. 1 ! a is Elbow style unit used in confined space Adjustable Bracket Design: for use with T-bar applications. grid, metal stud and Chicago grid applications. FM approved and UL listed Fully guaranteed All FlexHead sprinkler connections are Factory FlexHead has always maintained a commitment to Mutual Approved and Underwriters Laboratories quality. We pressure- and leak-test every FlexHead listed for suspended or sheetrock ceiling connection at our FM- and UL-audited factory. Burst installations. Tests include hydrostatic pressure, pressures exceed 3,000 pounds. Every product is vibration, friction loss, fatigue, head deployment, covered by our comprehensive limited warranty. corrosion and water hammer. Choose the length you need Our commercial connections also conform to these FlexHead connections are available in 2', 3', 4', 5' and industry standards: 6' hose lengths, and easily fit any sprinkler head on • Approved for use in suspended ceilings the market Outlets can accommodate both 1/2" and 3/4" with light, medium, and heavy-load grids sprinkler heads. (ASTM C-635 and C-636) Call, write or visit our website • They're the only flexible sprinkler connection FlexHead Industries offers everything you need to qualified for use in Seismic Design Categories specify, bid and install higher quality fire protection. C, D, E and F Let us make your connection today. Get in touch via • International Building Code (IBC) compliant the method that suits you best: without needing an unsightly oversized ring, • E-mail salesl @flexhead.com with questions and sleeve or adaptor where the ceiling meets the requests. sprinkler head • Call toll-free 800-829-6975 to speak to a • Compatible with BlazeMaster fire sprinkler representative. systems • Visit www.ftexhead.com for data sheets and • Meets all NFPA 13 guidelines and is demonstrations. specifically referenced in the 2007 edition New construction comparison Retrofit comparison al O v O v v v O O O J�//�/�✓„/� O I S S S / S S S FlexHeads 1 Hard-Pipe �i / i/ s FlexHeads ry tv rl rii 1 Haiti-ripe During a typical installation, a minimum of 4 , During a typical installation, a minimum of 6 - FlexHeads can be installed in the the same time FlexHeads can be installed in the the same time it takes to do 1 hard-pipe. takes to do 1 hard pipe. FlexHead metal stud detail 0 1111}}««««}}►}},,,,, FlexHead sprinkler connections }}}} .7,11111111111}1Fe.. 11111111114 4f 4}141{Illlllllh, """""0104 11, 1111114} are not just for high end 1�uluf►}, Sprinkler a11IIJ►■ '11,,;4;,};, installations. Their advantages branchline #4}14, ■"""' }}}111 make them cost-effective for . FlexHead •n}}}#1 r._ Sprinkler Drop I HII#i I#{111► every commercial job. (AU 304 stainless }}}#H I � �g� ,. ( 0111104 i steel including }4}##1} ''g fittings) }I'll} U Metal stud Adjustable hub 111 mounting bracket 1 Metal stud 1 It far `P • Sheetrock ceiling Sprinkler head (not included) FlexHead suspended cell ng detail }}1111,,##i11,,,, 0 .•144#Illllllfflllllfl#H1 141,11111114}411111104 011110411 011101}}}46 0446" .1 0 11+1+111' Sprinkler 111041114' .1111011• branchline 11111141 Milli, FlexHead 1111111 1111111• Sprinkler Drop • 1'm.'., (All 304 stainless }111441 $14�41f� steel including 1HIM fittings) Ceiling grid mounting bracket /Adjustable hub - Suspend• '= t-bar grid Q Ceiling tile Sprinkler head (not included) •a• ~ ...wr Each FM approved, UL listed, LPCB certified unit is ready-to-install, pressure- and leak-tested, and comes complete with a flexible stainless steel hose and mounting bracket with adjustable hub. FlexHead commercial fire sprinkler connections Your security is our business. FlexHead Industries was founded in 1992 to help engineers, builders and owners increase the safety of their buildings. Our patented sprinkler connection technologies show ir that it's possible to comply with codes cost-effectively. We're proud to help reduce the risks of property damage and illt loss of life in a wide variety of buildings, domestically and world-wide. '- Y FlexHead manufactures sprinkler connections for — . * 1 y1' all types of applications 1 including: / A -i_ ......_ • _ Commercial Exhaust ducts Institutions • Government • Aerospace • Concrete penetrations • Hospitals • Automotive for sidewall and • Offices • Biotechnology pendant applications Seismically • Restaurants • Electronics • Correctional centers qualified. • Retail • Forest products/ • Mental health facilities FlexHead connections allow • Schools paper pulp for independent movement . • Laboratories between sub-mains and Cleanrooms ceilings. They're the only • Biotechnology • Petrochemical flexible sprinkler connection • Electronics • Pharmaceuticals to be qualified for use in • High-end commercial • Restaurants Seismic Design Categories ceilings • Semiconductors C, D, E and F. • Pharmaceuticals • Steel manufacturers • Semiconductors FLExHEAD INDUSTRIES FBC1' c(:). ,_ _ The pioneers in flexible fire protection way ooranw APPROVED LISTED U.S.and international patents pending: #6,123,154, #6,119,784, 56 Lowland Street #6,752,218, #7,032,680, #6,488,097. Holliston, Massachusetts 01746 The FlexHead name and logo are trademarks of FlexHead Industries. toll-free 800-829-6975 FBC' System Compatible indicates that this product has been tested,and is monitored on an ongoing basis,to assure its chemical compatibility with (508) 893-9596 FlowGuard Gold's, BlazeMaster° and Corzan"pipe fittings. FBC", FlowGuard fax (508) 893-6020 Gold`, BlazeMaster" and Corzan` are licensed trademarks of The Lubrizol Corporation. info @flexhead.com USGBC and LEED are registered trademarks of the U.S.Green Building Council. www.flexhead.com 5M/SDP/04-10 RECEIVED APR 3 0 2013 . . . •• . . , COSCO CITY OF DINGDVIARD Fire Protection FIRE PROTECTION SYSTEMS EQUIPMENT SUBMITTAL BROCHURE FOR: COMCAST TOC WEST 11308 SW 68th PARKWAY TIGARD, OR 97223 COSCO PROJECT NUMBER 24PD5111 CONTRACT WITH: LEASE CRUTCHER LEWIS 550 SW 12th AVE. PORTLAND, OR 97205 August 7, 2012 Sprinkler 41a NII<ING® MICROFAST°AND TECHNICAL DATA MicrofastHP° QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Microfast® and MicrofastHP® Quick Response Pendent Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several differ- ent finishes and temperature ratings and K-Factors to meet design require- ments. The special Polyester and Polytetrafluoroethylene (PTFE) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmos- pheres and are cULus listed as corrosion resistant as indicated in the Approval P Chart. (Note: FM Global has no approval classification for PTFE and Polyester !! coatings as corrosion resistant.) 2. LISTINGS AND APPROVALS �� �s cULus Listed: Category VNIV • FM Approved: Classes 2001, 2002, 2015, and 2017 '~ NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E,Volume 16 ABS Certified: Certificate 04-HS407984C-PDA vds] VdS Approved: Certificates G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021 PCB LPC Approved: Ref. Nos. 096e/03 and 096e/04 (E CE Certified: Standard EN 12259-1, EC-certificates of conformity 0786-CPD-40130, 0786-CPD-40170 and 0786-CPD- 40279, 0832-CPD-2001, and 0832-CPD-2003 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on page 41d for cULus Listing requirements and refer to Approval Chart 2 and Design Criteria on page 41f for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at (0.5 bar) up to 250 psi (17 bar)for high-pressure systems. High-pres- http:Nwww.vikinggroupinc.com. sure (HP) sprinklers can be identified by locating "250" stamped on The Web site may include a more recent the deflector.All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page. maximum 175 psi(12 bar)wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65 °F(-55°C) Overall Length: Refer to the Approval Charts *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06662B and 12282. Brass UNS-C84400 for all other sprinklers. Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 06662B, 06666B, and 06765B. Copper UNS- C19500 for Sprinkler 12282. Phosphor Bronze UNS-C51000,Copper UNS-C19500 or Brass UNS-C26000 for Sprinkler 067208. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Form No. F_081296 Replaces page 41a-f, dated July 12, 2012. (Revised approval charts) Sprinkler 41 b August 7, 2012 N11(ING® MICROFAST°AND TECHNICAL DATA MicrofastHP° QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Ordering Information: (Also refer to the current Viking price list.) Order Microfast®and MicrofastHP®Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass =A, Chrome-Enloy®= F, White Polyester= M-/W, Black Polyester= M-/B, and Black PTFE = N Temperature Suffix: 135°F(57 °C)=A, 155°F (68 °C) = B, 175°F(79°C)= D, 200 °F (93°C) = E, and 286 °F (141 °C) = G For example, sprinkler VK302 with a 1/2"thread, Brass finish and a 155 °F(68°C)temperature rating = Part No. 06662BAB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for Recessed Pendent Sprinklers Part No. 16036W/B*(available since 2011) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool°° Part No. 15915 (available since 2010.) *A'A"ratchet is required(not available from Viking). "Allows use from the floor by attaching a length of 1"diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. Sprinkler Cabinets: A Six-head capacity: Part No 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Wrench Refer to NFPA 25 for Inspection, Testing and Maintenance require- Flats ments. �- Protective 1 �9111�® I Sprinkler 7. AVAILABILITY �' The Viking Microfast®and MicrofastHP®Quick Response Pendent fop Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. (11°..%■,, 10896 m� Figure 1: Standard Sprinkler Wrench 10896W/B August 7, 2012 Sprinkler 41c MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature' Ordinary 135 °F(57 °C) 100 °F (38 °C) Orange Ordinary 155 °F(68 °C) 100°F(38°C) Red Intermediate 175 °F(79 °C) 150 °F(65 °C) Yellow Intermediate 200 °F(93 °C) 150 °F(65 °C) Green High 286 °F(141 °C) 225 °F(107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy5, White Polyester, Black Polyester, and Black PTFE Corrosion-Resistant Coatings':White Polyester, Black Polyester, and Black PTFE Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and PTFE coatings. 1 I 1 1 t t l IltU_ LJ �I li 115asniL t= Sprinkler Wrench ��Y - I I 16036W/B*x for installing recessed A pendent sprinklers I Carefully slide the �� wrench sideways **A 1/2' ratchet is required II I around the protective (not available from Viking). II cap, ensuring engage- r, rnent with the sprinkler wrench flats. Figure 2: Wrench 16036W/B for Recessed Pendent Sprinklers Sprinkler 41d August 7, 2012 MICROFAST°AND TECHNICAL DATA MicrofastHP° QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) ---Temperature KEY Microfast5'and MicrofastHP Quick Response Pendent Sprinklers +_ Finish A Maximum 175 PSI(12 bar)WWP xf Escutcheon(if applicable) Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No.' NPT BSP U.S. metric2 Inches mm cULus4 NYC5 VdS LPCB (E 0 Standard Orifice 06662B VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 Al X, B1Y AIX, B1Y -- -- -- C2X,E2Y14 18021 VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A1X,B1Y AIX, B1Y A2 A2X,B2Y C2X,E2Y 1 C2X,E2Y'° Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 ' A1X,B1Y AI X, B1Y A2 A2X C211 -- 06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 AIX, B1Y A1X, B1Y A2 -- A21' -- Small Orifice' 06718B9 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 AI X, B1Y A1X,B1Y -- -- -- -- 06720B9 VK331 1/2" 15 mm 4.2 57 2-1/4" 58 A1X, B1 Y AIX, B1Y -- -- -- -- 06932B VK331 -- 10 mm 4.2 57 2-3/8" 60 -- -- A2 -- G3'3 -- Maximum 250 PSI(17 bar)WWP Standard Orifice Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No' NPT BSP U.S. metric2 Inches mm cULus4 NYC10 VdS LPCB E 0 12282 VK317 1/2" 15 mm 5.6 80.6 2-1/4" 58 A1X, B1Y A1X -- -- -- -- Maximum 250 PSI(17 bar)WWP Small Orifice' 1229010 VK342 1/2" 15 mm 2.8 40.3 2-3/16" 56 AI X,B1Y A1X -- -- -- -- Approved Temperature Ratings A-135°F(57°C),155°F(68'C),175°F(79°C),200°F(93°C), Approved Finishes Approved Escutcheons and 286°F(141 °C) 1 - Brass, Chrome-Enloy' White X - Standard surface-mounted escutcheon or B- 135°F(57°C), 155°F(68°C), 175°F(79°C), and 200°F (93°C) Polyesters , Black Polyesters the Viking Microfast` Model F-1 Adjustable C- 155°F(68°C), 175°F(79°C),200°F(93°C),and 286°F and Black PTFE6 Escutcheon (141 °C) 2 - Brass, Chrome-Enloy®, White Y - Standard surface-mounted escutcheon or D- 135°F(57°C), 155°F(68°C), 175°F(79°C),and 286°F Polyester,and Black Polyester the Viking Microfast°' Model F-1 Adjustable (141 °C) 3 Brass and Chrome-Enloy' Escutcheon or recessed with the Viking E- 155°F(68°C), 175°F(79°C),and 200°F(93°C) Micromatic' Model E-1 or E-2 Recessed F- 155°F(68°C), 175°F(79°C), and 286°F(141 °C) Escutcheon G-155°F(68°C) Footnotes ' Base part number is shown. For complete part number,refer to Viking's current price schedule. Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. °Listed by Underwriters Laboratories Inc.for use in the U.S. and Canada. 'Accepted for use,City of New York Board of Standards and Appeals, Calendar Number 219-76-SA. 'cULus Listed as corrosion resistant. Other colors are available on request with the same Listings and Approvals as the standard colors. 'Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. 9 The sprinkler orifice is bushed. 10Accepted for use,City of New York Department of Buildings,MEA Number 89-92-E,Vol. 16. 11(E Certified,Standard EN 12259-1, EC-certificates of conformity 0832-CPD-2001 and 0832-CPD-2003. 12(E Certified,Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40279. 13(E Certified,Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40130 and 0786-CPD-40170. 10 0 MED Certified, Standard EN 12259-1, EC-certificates of conformity 0832-MED-1003 and 0832-MED-1008. August 7, 2012 Sprinkler 41e VIKING® MICROFAST°AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com DESIGN CRITERIA - UL (Also refer to Approval Chart 1 on page 41d) cULus Listing Reauirements: Microfast'and MicrofastHP' Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies (exception small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Ceiling Opening Size: 2-5/16' (58.7 mm) minimum 2-1/8' 2-1/2' (63.5 mm) maximum (54 mm) 1/2' (15 nn) I■EN���■ NPT �\ i�T r . - 1 I � \�ri I� \1 2-1/4' 1-3/4' �� (44.5 mm) 2' 1-1/2' (38.1 mm) 1-5/8' <58 mm) / (50.8 mm) Ilr-Ili Minimum (41 mm) , Maximum i AP J______ Installed with a . ems Pendent Sprinkler standard 1/8' surface- 06662B (VK302) mounted escutcheon. Installed with a Microfast Model F-1 Adjustable Escutcheon Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon 2-1/8' 1 Ceiling Opening Size: _ 2-1/8' (54 mm) 2-5/16' (58.7 mm) minimum (54 mm) 2-1/2' (63.5 mm) maximum (bmiwl iii —�11 �1�m\1 '—: . � 1� I 1s�,1 \1 1-3/4' `l, 1-1/8' (28.6 rim) ��� Minimum 2' 1-1/Mi (28.6 mm) (44.5 mm) y Minimum Maximum - --- 1 (50.8 mm) A i Maximum .--- -- � 1 Installed with a Micromatic Model E-1 Recessed Escutcheon Installed with a thread on Model E-2 Recessed Escutcheon I Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons 1 Sprinkler 41f August 7, 2012 NIKING® MICROFAST°AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) Temperature KEY Microfase Quick Response Pendent Sprinklers Finish Maximum 175 PSI(12 bar)WWP A#Xf Escutcheon(it applicable) Sprinkler SIN Thread Size Nominal K-Factor Overall Length FM Approvals' Base Part No.' NPT BSP U.S. metric' Inches mm (Refer also to Design Criteria below.) Standard Orifice 06662B VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A2X, B2Y 18021 VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A2X, B2Y Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 A1X, B1Y 06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 Al X, B1Y Small Orifice' 06718B' VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 A1X Approved Escutcheons Approved Temperature Ratings Approved Finishes X-Standard surface-mounted escutcheon or the Viking A-135°F(57°C), 155°F(68°C), 175°F(79°C), 1 -Brass and Chrome-Enloy' Microfast' Model F-1 Adjustable Escutcheon 200°F(93°C),and 286°F(141 °C) 2_grass,Chrome-Enloy White Polyesters, Y - Standard surface-mounted escutcheon or the B- 135°F(57°C), 155°F(68°C),175°F(79°C), Viking Microfast"Model F-1 Adjustable Escutcheon and 200°F(93°C) and Black Polyester' ( ) or recessed with the Viking Micromatic Model E-1 or E-2 Recessed Escutcheon Footnotes ' Base part number is shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. 'FM Approved as quick response control mode standard spray Non-storage sprinklers.For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 6 The sprinkler orifice is bushed. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Aooroval Reauirements; The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-storage standard spray pendent sprinklers as indicated in the FM Approval Guidet. For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheets 2-0 and 8-9).FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements, hydraulic design,ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. tSprinklers VK302 and VK352 are also FM Approved as quick response Rack Storage standard spray pendent sprinklers. Refer to technical data page 131a-e for Intermediate Level In-Rack Sprinklers. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances,and standards, whenever applicable. Form No, F_081296 Replaces page 41a-f, dated July 12, 2012. (Revised approval charts) • January 27, 2012 Sprinkler 83a \ILIUM® STANDARD/QUICK RESPONSE TECHNICAL DATA EXTENDED COVERAGE LIGHT AND ORDINARY HAZARD ELO SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking EC/QREC Light and Ordinary Hazard Extra-Large Orifice Sprinklers VK532 and VK534 are thermosensitive spray sprinklers available in several different °° s finishes and temperature ratings to meet varying design requirements.The extra- large orifice produces the flows required to meet Light and Ordinary Hazard den- = sity requirements at lower pressures than standard orifice or large orifice sprin- klers. The glass bulb operating element and special deflector characteristics meet the challenges of quick response extended coverage standards. Upright Sprinkler VK532 is cULus Listed as standard and quick response and FM Approved as quick response. Pendent Sprinkler VK534 is cULus Listed as standard and quick response. The special Polyester and Teflon®coatings can be used in decorative applications where colors are desired. 2. LISTINGS AND APPROVALS c ut U5 cULus Listed: Category VNIV FM, FM Approved: Class 2022 NYC Approved: MEA 89-92-E, Volume 9 Refer to Approval Chart 1 and Design Criteria on pages 83d-e for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 83f for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1993. Minimum Operating Pressure: Refer to the Approval Charts. Maximum Working Pressure: 175 psi (12 Bar). Factory tested hydrostatically to 500 psi (34.5 bar). Factory tested hydrostatically to 500 psi(34.5 bar). Thread size: 3/4" (20 mm) NPT Nominal K-Factor: 11.2 U.S. (161.3 metrict) t Metric K-factor measurement shown is in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to-65°F(-55°C) Overall Length: Part No. 08687: 2-5/16(59 mm), Part No. 08340: 2-3/8" (61 mm) Viking Technical Data may be found on Material Standards: The Viking Corporation's Web site at Sprinkler Frame: Brass UNS-C84400 http://www.vikinggroupinc.com. Deflector: Brass UNS-C26000 for Sprinkler 08340. Copper UNS-C19500 The Web site may include a more recent for Sprinkler 08687 edition of this Technical Data Page. Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Teflon®Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon®Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order EC/OREC Light and Ordinary Hazard Extra-Large Orifice Sprinklers VK532 and VK534 by first adding the appropriate suf- fix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass=A, Chrome-Enloy®= F, White Polyester= M-/W, Black Polyester=M-/B, and Black Teflon®= N Temperature Suffix: 135°F(57°C)=A, 155°F(68°C) = B, 175°F(79 °C)= D, 200°F(93°C)= E, and 286°F(141 °C) =G For example, sprinkler VK532 with a Brass finish and a 155 °F (68°C)temperature rating = Part No. 08687AB Available Finishes And Temperature Ratings: Refer to Table 1. Form No. F051393 Replaces page 83a-f, dated May 14, 2010. (Updated FM Approval Design Criteria to include HC-3.) Sprinkler 83b January 27, 2012 STANDARD/QUICK RESPONSE TECHNICAL DATA EXTENDED COVERAGE LIGHT AND ORDINARY HAZARD ELO SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Accessories: (Also refer to the"Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 05118CW/B (available since 1981) B. Wrench for recessed pendent sprinkler Part No. 11663W/B**(available since 2001) **A%"ratchet is required(not available from Viking). Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinklers VK532 and VK534 are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Protective � 1-1/2" i 1\ Sprinkler :38 mm) Wrench O Shield Flat AElVE AFTER /•/--_`-``>• • INSEMUEIEN 11 VIK/INC III ' �` ^ II • 2-5/16" r (59 mm) \III 1lli if IIII/ 3/4 (20 mm) NPT Figure 1: Figure 2: Standard Sprinkler Wrench 05118CW/B Upright Sprinkler VK532 January 27, 2012 Sprinkler 83c VIKING® STANDARD/QUICK RESPONSE TECHNICAL DATA EXTENDED COVERAGE LIGHT AND ORDINARY HAZARD ELO SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services:877-384-5464 Fax: 269-818-1680 Email:techsvcs @vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature' Ordinary 135°F(57 °C) 100°F(38 °C) Orange Ordinary 155°F(68°C) 100°F(38°C) Red Intermediate 175°F(79°C) 150°F(65°C) Yellow Intermediate 200°F(93°C) 150°F(65°C) Green High 286°F(141 °C) 225°F(107°C) Blue Sprinkler Finishes: Brass, Chrome-Enloy®,White Polyester', Black Polyester', and Black Teflon®3 Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only.Note that the spring is exposed on sprinklers with Polyester and Teflon®coatings. For Teflon°coated open sprinklers only,the waterway is coated. ■ I I _ I 1 ° '.�. /ail_ ,►� 1lI i \ :) Sprinkler Wrench .© II` 11663\4/Bow must be �._ used for installing - -° recessed Sprinkler VK534 °- w*A 1/2' ratchet is Step 1: Carefully slide required. (not avail— the wrench sideways able from Viking). i around the deflector l I and protective shield. = Step 2: Carefully press 1 (Note the orientation of the wrench upward and the shield in the wrench.) turn slightly to ensure engagement with the sprinkler wrench flats. Figure 3: Wrench 11663W/B for Recessed Pendent Sprinkler VK534 • Sprinkler 83d January 27, 2012 Nina INGIt STANDARD/QUICK RESPONSE TECHNICAL DATA EXTENDED COVERAGE LIGHT AND ORDINARY HAZARD ELO SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs @vikingcorp.com Sprinkler NPT Thread Size Nominal K-Factor Maximum Water Overall Length Base SIN Working Pressure Part Number' Inches mm U.S. metric2 9 Inches mm 08687 Upright VK532 3/4 20 11.2 161.3 2-5/16 59 175 psi(12 Bar) 08340 Pendent VK534 3/4 20 11.2 161.3 2-3/8 61 Approval Chart 1 (UL) r--- Temperature KEY Finish EC/QREC Light and Ordinary Hazard ELO Sprinklers AIX4-Escutcheon(if applicable) Listings and Approvals' Max.Sprinkler Maximum Minimum Water Supply Requirements' (Refer also to Design Criteria on page 83e.) Spacing Area per - ' (L x W) Sprinkler Light Hazard Ordinary Hazard Group I Ordinary Hazard Group II Pendent VK534 Upright VK532 Flow!Pressure Flow!Pressure Flow!Pressure cULus4 NYC' cULus4 NYC' Standard Response 16 ft.x 16 ft. 256 ft2 38 gpm @ 11.5 psi 51 gpm @ 20.7 psi CIX, ClX, Cl Cl --(4.9 m x 4.9 m) (23.8 m2) (143.9 Umin @ .79 Bar) (193.1 Umin @ 1.43 Bar) DIY WY 18 ft.x 18 ft. 324 ft2 49 gpm @ 19.1 psi 65 gpm @ 33.7 psi C1X, C1X, (5.5 m x 5.5 m) (30.1 m2) (185.5 Umin @ 1.32 Bar) (246.1 Umin @ 2.32 Bar) DIY D1Y Cl Cl 20 ft.x 20 ft. 400 ft2 60 gpm @ 28.7 psi 80 gpm @ 51.0 psi C1X, C1X, Cl Cl --(6.1 m x 6.1 m) (37.2 m2) (227.1 L/min @ 1.98 Bar) (302.8 Umin @ 3.52 Bar) 1 DIY DIY Quick Response • 12 ft.x 12 ft. 144 ft2 30 gpm @ 7.2 psi 39 gpm @ 12.1 psi --(3.7 m x 3.7 m) (13.4 m2) (113.6 L/min @.50 Bar) (147.7 Umin©.84 Bar) E1Y El See Footnote 6 14 ft.x 14 ft. 196 ft2 30 gpm @ 7.2 psi 39 gpm @ 12.1 psi El Y El See Footnote 6 --(4.3 m x 4.3 m) (18.2 m2) (113.6 L/min @ .50 Bar) (147.7 Umin @.84 Bar) 16 ft.x 16 ft. 256 ft2 30 gpm @ 7.2 psi (4.9 m x 4.9 m) (23.8 m2) (113.6 Umin @ .50 Bar) B1 Y 61 See Footnote 6. 18 ft.x 18 ft. 324 ft2 33 gpm @ 8.7 psi (5.5 m x 5.5 m) (30.1 m2) (124.9 L/min @.60 Bar) B1 Y B1 See Footnote 6 20 ft.x 20 ft. 400 ft2 40 gpm @ 12.8 psi (6.1 m x 6.1 m) (37.2 m2) (151.4 L/min @.88 Bar) A1Y Al See Footnote 6 Approved Temperature Ratings A-135°F(57°C)and 175°F(79°C) Approved Escutcheons B- 135 °F (57 °C), 155 °F(68 °C), and 175°F Approved Finishes (79°C) pp X - Standard surface-mounted escutcheons or the Micro- C 155°F(68°C),175°F(79°C),200°F(93°C), 1 - Brass, Chrome-Enloy", White Poly- fast'Model F-1 Adjustable Escutcheon and 286°F(141 °C) ester, Black Polyester, and Black Y-Standard surface-mounted escutcheons or the Microfast" D 155 °F(68°C), 175°F(79°C),and 200°F Teflon' Model F-1 Adjustable Escutcheon, or recessed with the (93°C) Micromatic'Model E-1 or E-2 Recessed Escutcheon E- 155°F(68°C) Footnotes 'Part number shown is the base part number. For complete part number,refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This chart shows listings and approvals available at time of printing. Check with the manufacturer for any additional approvals. a cULus Listed for use in the U.S.and Canada. 'Accepted for use,City of New York Department of Buildings,MEA 89-92-E Vol.9. 6 Meets New York City requirements,effective July 1,2008. 'To determine"Minimum Water Supply Requirement"for areas of coverage where length and width of actual sprinkler spacing are not equal, select the"Maximum Sprinkler Spacing"from the chart that is equal to or greater than the larger of the actual spacing (length or width)dimensions used Example:When using 10'-6"x 13'-0"sprinkler spacing, provide the"Minimum Water Supply Requirement"listed in the chart for 14'-0"x 14'-0"spac- . ing. For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" in the appropriate hazard group for the next larger area listed. The distance from sprinklers to walls shall not exceed one-half the"Maximum Sprinkler Spacing"listed for the"Minimum Water Supply Requirement"used. . January 27, 2012 Sprinkler 83e NIKIING. STANDARD/QUICK RESPONSE TECHNICAL DATA EXTENDED COVERAGE LIGHT AND ORDINARY HAZARD ELO SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com DESIGN CRITERIA- UL (Also refer to Approval Chart 1.) cULus Listing Requirements: EC-ELO Upright Sprinkler VK532 and Pendent Sprinkler VK534 are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for extended coverage upright and pendent spray sprinklers as indicated below: • The minimum water supplies and maximum areas of coverage shown in Approval Chart 1 are designed to provide the following design densities: 0.10 gpm/ft2(4.1 mm/min)for Light Hazard densities;0.15 gpm/ft2(6.1 mm/min)for Ordinary-Hazard Group I densities;0.2 gpm/ft.2(8.1 mm/min) for Ordinary-Hazard Group II densities. • The sprinkler installation rules contained in NFPA 13 for extended coverage upright and pendent spray sprinklers must be followed. • Viking EC-ELO Upright and Pendent Sprinklers are cULus Listed for use in unobstructed construction,and noncombustible obstructed construction consisting of solid steel and/or concrete beams as defined in the latest edition of NFPA 13. • Ceiling slope not to exceed 2/12(9.5°). Also.Viking ECOH-ELO Upright Sprinkler VK532 and Pendent Sorinkter VK534 are specifically cULus Listed for Ordinary Hazard Occupancies; • For non-combustible obstructed construction within trusses or bar joists having non-combustible web members greater than 1"(25.4 mm)when applying the 4 times obstruction criteria rule as defined in NFPA 13 under"Obstructions to Sprinkler Discharge Pattern Development". • For installation under concrete tees when installed as follows: 1.The stems of the concrete tee construction must be spaced between 3 ft(0.9 m)and 7 ft-6 in(2.3 m)on center.The depth of the concrete tees must not exceed 30 in(762 mm).The maximum permitted concrete tee length is 32 ft(9.8 m).However,where the concrete tee length exceeds 32 ft(9.8 m), non-combustible baffles,equal in height to the depth of the tees,can be installed so that the space between the tees does not exceed 32 ft(9.8 m). 2.The sprinkler deflector is to be located in a horizontal plane at or above 1"(25.4 mm)below the bottom of the concrete tee stems. 3.When the sprinkler deflector is located higher than a horizontal plane 1"(25.4 mm)beneath the bottom of the concrete tee stems,the obstruc- tion to sprinkler discharge criteria requirements of NFPA 13 for extended coverage upright sprinklers applies. IMPORTANT: Always refer to Bulletin Form No. F_091699 -Care and Handling of Sprinklers. Also refer to pages EC1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Ceiling Opening Size 2-5/16' (58.7 mm) minimum 3/4' 2-1/2' (63.5 mm) maximum (20 mm) 2-1/8' NPT (54 mm) ��_� IF--- 1 I 6 �` �IIErd=�illl 2 3/8'( I 1-3/4' IE riuNtn111�1-11/16' I Ip' (60 mm) I I (44.5 mm) \ HI/I t (42.9 mm) 1,1 _r A.1 J 1-1/2' (38.1 mm) ��� � i 2' (50,8 mm) Minimum } Maximum *A 1 1_1/2, Installed with a standard 1/8' (38.1 mm) (3.1 mm) surface-mounted escutcheon Pendent Sprinkler Installed with a Microfast 08340 (VK534) Model F-1 Adjustable Escutcheon Figure 4: Sprinkler VK534 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon • Sprinkler 83f January 27, 2012 C STANDARD/QUICK RESPONSE TECHNICAL DATA EXTENDED COVERAGE LIGHT AND ORDINARY HAZARD ELO SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) tune KEY Response Extended Coverage ELO Upright S rinkler VK532 Finish For HC-1,HC-2,and HC-3 Occupancies A1X.--Escutcheon(if applicable) Maximum 175 PSI(12 Bar)WWP Maximum Sprinkler Maximum Area Refer to Design Criteria below. FM Approval' Spacing(L x W2) per Sprinkler Upright Sprinkler VK532 NOTE: FM installation guidelines may differ 16 ft.x 16 ft.(4.9 m x 4.9 m) 256 ft2(23.8 m2) from cULus and/or NFPA criteria. Refer to the Al 18 ft.x 18 ft.(5.5 m x 5.5 m) 324 ft2(30.1 m2) latest applicable FM Loss Prevention Al 20 ft.x 20 ft.(6.1 m x 6.1 m) 400 ft2(37.2 m2) Data Sheets(including 2-0 and 3-26). Al Approved Temperature Ratings Approved Finishes A- 155'F(68'C), 175°F(79°C),200°F(93°C),and 286°F(141 °C) 1 -Brass,Chrome-Enloy`, White Polyester, and Black Polyester Footnotes 'This chart shows the FM Approvals available at time of printing.Check with the manufacturer for any additional approvals. To determine"Minimum Water Supply Requirement"for areas of coverage where length and width of actual sprinkler spacing are not equal, select the "Maximum Sprinkler Spacing"from the chart that is equal to or greater than the larger of the actual spacing(length or width)dimensions used Example: When using 10'-6"x 13'-0"sprinkler spacing,provide the"Minimum Water Supply Requirement"listed in the chart for 14'-0"x 14'-0"spacing.For areas of coverage smaller than shown,use the"Minimum Water Supply Requirement"in the appropriate hazard group for the next larger area listed.The distance from sprinklers to walls shall not exceed one-half the"Maximum Sprinkler Spacing"listed for the"Minimum Water Supply Requirement"used DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Anoroval Reauirements: Sprinkler VK532 is FM Approved as a quick response Non-Storage extended coverage upright sprinkler as indicated in the FM Approval Guide for use in occupancy hazard classifications HC-1, HC-2.and HC-3. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheets 2-0 and 3-26). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page EC1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances,and standards, whenever applicable. Ceiling Opening Size: 2-1/8' 2-1/8' 2-5/16' <58.7 rim) minimum (54 mm) (54 MM) 2-1/2' (63.5 rim) maximum uNin,111 1 i l ' rirTiiiNin-. 1-1/8' 1-3/4' r�r 1-1/8• (28,6 mm) (51 2 mm) \I111%,. JI (28.6 mm) Minimum (44.5 mm) Minimum Maximum .... Maximum 1y Installed with a Micromatic Installed with a Model E-2 Model E-1 Recessed Escutcheon Thread-on Recessed Escutcheon Figure 5: Sprinkler VK534 Dimensions with the Model E-1 and E-2 Recessed Escutcheons Form No. F_051393 Replaces page 83a-f, dated May 14, 2010. (Updated FM Approval Design Criteria to include HC-3.) July 12, 2012 Sprinkler 51a • NII(ING® MICROFAST°AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional *mom- (Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several different finishes, temperature ratings, and K-Factors to meet • design requirements. The special Polyester and Polytetrafluoroethylene (PTFE) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive at- mospheres and are cULus listed as corrosion resistant as indicated in Approval ! - I Chart 1. (Note: FM Global has no approval classification for PTFE and Polyester • coatings as corrosion resistant.) 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approved: Classes 2002 and 2020 — NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E,Volume 16 ABS Certified: Certificate 04-HS407984B-PDA VdS Approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020 LPC Approved: Ref. No. 096e/03, TE30401, and TE30872 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, 0786-CPD-40171, and 0786-CPD-40278 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on pages 51c-d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 51e for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar)' Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi (0.5 The Viking Corporation's Web site at bar) up to 250 psi (17 bar) for high-pressure systems. High-pressure http://www.vikinggroupinc.com. (HP) sprinklers can be identified by locating "250" stamped on the The Web site may include a more recent deflector.All other Part Nos. not mentioned above are rated to a maxi- edition of this Technical Data Page. mum 175 psi (12 bar)wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65°F (-55°C) Overall Length: Refer to the Approval Charts *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 12978, 06766B, 07060, and 12281. Brass UNS-C84400 for all other sprinklers. Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 12978, 06764B, and 12281. Copper UNS-C19500 for Sprinklers 06665B, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Form No F_080488 Replaces page 51a-e, dated August 4, 2011. (Revised main image and VK300 part number, removed brand name and replaced with PTFE) Sprinkler 51b July 12, 2012 Ki NG® MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order Microfast®and MicrofastHP®Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass=A, Chrome-Enloy® = F, White Polyester= M-/W, Black Polyester= M-/B, and Black PTFE = N Temperature Suffix(°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK300 with a 1/2"thread, Brass finish and a 155°F/68 °C temperature rating = Part No. 12978AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrench: Standard Wrench: Part No 10896W/B (available since 2000) Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B. Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast®and MicrofastHP®Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature' Ordinary 135 °F (57 °C) 100°F(38 °C) Orange Ordinary 155°F(68 °C) 100°F (38 °C) Red Intermediate 175°F(79 °C) 150°F(65°C) Yellow Intermediate 200°F (93 °C) 150°F(65°C) Green High 286 °F(141 °C) 225°F(107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloe, White Polyester, Black Polyester, and Black PTFE Corrosion-Resistant Coatings°: White Polyester, Black Polyester. and Black PTFE Footnotes 'The sprinkler temperature rating is stamped on the deflector. Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e.These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment.For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only Note that the spring is exposed on sprinklers with Polyester and PTFE coatings. • • July 12, 2012 Sprinkler 51c lI(IFSIG ® MICROFAST®AND TECHNICAL DATA MicrofastHP° QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) Temperature KEY Microfast°°and MicrofastHP'Quick Response i*c Finish Upright and Conventional Sprinklers A1Xt Escutcheon(if applicable) Maximum 175 PSI(12 bar)WWP Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals' SIN (Refer also to Design Criteria on page 51d.) Number' NPT BSP U.S. metric' Inches mm cULus° NYC° VdS LPCB (E 0 Upright-Standard Orifice 12978 VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 Al See Footnote 7 -- -- __ __ 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- -- A2 A2 B2t2 8215 Conventional-Standard Orifice 06766B VK310 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- A2 82i2 B215 Upright-Large Orifice 06665B VK350 3/4" -- 8.0 115.2 2-5/16 59 Al Al A2 A2 B2i2 -- 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 Al Al A2 A2 8212 -- 06764B VK350 1/2" 15 mm 8.0 115.2 2-5/16 59 Al Al A2 -- A213 -- Conventional-Large Orifice 06768B VK354 3/4" 20 mm 8.0 115.2 2-5/16 59 _ Al A2 -- A2 13212 -- Upright-Small Orifice" 06717B1' VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Al -- -- -- -- • 06719811 VK327 1/2" 15 mm 4.2 57 2-3/16 56 Al Al -- -- -- -- . 06931 B11 VK327 -- 10 mm 4.2 57 2-3/16 56 -- -- A2 -- C314 -- Maximum 250 PSI(17 bar)WWP Upright-Standard Orifice Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals' SIN (Refer also to Design Criteria on page 51d.) Number' NPT BSP U.S. metric2 Inches mm cULus° NYC' VdS LPCB (E 0 12281 VK315 1/2" 15 mm 5.6 80.6 2-3/16 56 Al Al -- -- -- -- Upright-Small Orifice1' 1228611 VK340 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Al -- -- -- -- Approved Temperature Ratings Approved Finishes A- 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 1 -Brass,Chrome Enloy®,White Polyester 55, Black Polyesters', 286°F(141°C) and Black PTFE B- 155°F(68°C), 175°F(79°C), 200°F(93°C), and 286°F(141°C) 2 - Brass, Chrome Enloy®, White PolyesterS5, and Black Polyester'h C 155°F (68°C) 3- Brass and Chrome-Enloy® Footnotes 'Base part number is shown.For complete part number,refer to Viking's current price schedule. 'Metric K-factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. 'Listed by Underwnters Laboratories Inc.for use in the U.S.and Canada. scULus Listed as corrosion resistant. 8 Other colors are available on request with the same Listings and Approvals as the standard colors. 'Meets New York City requirements,effective July 1,2008. 8 Accepted for use,City of New York Board of Standards and Appeals,Calendar Number 219-76-SA. °Accepted for use,City of New York Department of Buildings,MEA 89-92-E,Vol. 16. 10 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems only. Exception:4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized "The sprinkler orifice is bushed. '2 (E Certified,Standard EN 12259-1,EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. " (E Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40278. " ((Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40131. 15 tJ MED Certified,Standard EN 12259-1,EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. Sprinkler 51d July 12, 2012 NIKING8 MICROFAST'�AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com DESIGN CRITERIA-U4 (Also refer to Approval Chart 1 on page 510) cULus Listing Requirements: Microfast and MicrofastHP Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers,or old style(conventional)sprinklers. • Designed for use in Light and Ordinary Hazard occupancies (exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to the installation guidelines for old style(conventional)sprinklers. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. °rotective Sprinkler • Cap 10896 Figure 1: Standard Sprinkler Wrench 10896W/B July 12, 2012 Sprinkler 51e • MICROFAST�AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) Temperature KEY � Microfasr" Quick Response Upright Sprinklers MX 4-Escutcheon 14 applicable) Maximum 175 PSI(12 bar)WWP Base Part ' SIN Thread Size Nominal K-Factor Overall Length FM Approvals' Number' NPT BSP U.S. metric' ` Inches mm (Refer also to Design Criteria below.) Standard Orifice 12978 VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A2 Large Orifice 06665B VK350 3/4" -- 8.0 115.2 2-5/16 59 A2 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2 06764B VK350 1/2" 15 mm 8.0 115.2 2-5/16 59 A2 Small Orifice' 0671786 VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Approved Finishes Approved Temperature Ratings 1 - Brass and Chrome-Enloy® A- 135 °F(57°C), 155°F(68°C), 175°F(79°C), 200°F(93 °C), and 286°F(141°C) 2 - Brass, Chrome-Enloy®, White Polyesters, and Black Polyesters Footnotes 'Base part number is shown. For complete part number,refer to Viking's current price schedule. • 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the FM Approvals available at the time of printing.Check with the manufacturer for any additional approvals. °FM Approved as quick response Non-Storage pendent sprinklers. For specific application and installation requirements, reference the latest appli- cable FM Loss Prevention Data Sheets(including Data Sheet 2-0). 'Other colors are available on request with the same Approvals as the standard colors. 6 The sprinkler orifice is bushed. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Aooroval Reauirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-Storage upright sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements,hydraulic design,ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations,and also with the provisions of governmental codes, ordinances,and standards, whenever applicable. • THIS PAGE INTENTIONALLY LEFT BLANK Form No F_080488 Replaces page 51a-e, dated August 4, 2011. (Revised main image and VK300 part number, removed brand name and replaced with PTFE) State P45 ipe & Supply, Inc. THIS INFORMATION PROVIDED IS BASED ON ASTM GUIDELINES FOR WELDED PIPE SPECIFICATIONS AND ASTM REQUIREMENTS. ACTUAL PIPE AND MATERIAL TEST REPORTS PROVIDED WOULD MEET OR EXCEED THESE GUIDELINES. TEST REPORTS WOULD PROVIDE SPECIFIC AND ACTUAL DETAILS CONCERNING THE MECHANICAL AND CHEMICAL PROPERTIES OF THE ACTUAL PIPE,AS WELL AS ADDITIONAL TESTS RESULTS REQUIRED BY ASTM. SCHEDULE 40 Black and Galvanized Steel ERW Pipe Pipe Size Test Pressure Nominal O.D. I.D. Weight!Foot psi 1" 1.315 1.049 1.680 700 1-1/4" 1.660 1.380 2.270 1200 1-1/2" 1.900 1.610 2.720 1200 2" 2.375 2.067 3.660 2300 2-1/2" 2.875 2.469 5.800 2500 3" 3.500 3.068 7.580 2220 4" 4.500 4.026 10.800 1900 5" 5.563 5.047 14.630 1670 6" 6.625 6.065 18.990 1520 8" 8.625 7.981 28.580 1340 COMPOSITION AND PROPERTIES Chemical and mechanical properties requirements are as prescribed by applicable ASTM standards edition January 2006. Chemical Requirements,Percent(Product) C Mn P S Other _ Specification Grade max max max max ASTM A53 A 0.250 0.950 0.05 0.045 - 1 Residual elements max'Cu-0.40,Ni-0.40,Cr-0.40,Mo-0.15 and V-08. These live elements combined shall not exceed 1%. Mechanical Properties-Tensile Requirements Stren th-psi. Yield Tensile Specification Grade Min Max Min Max ASTM A53 A 30,000 - 48,000 - NOTE_ Elongation requirements vary with nominal area of test specimen and specified minimum tensile strength of the steel grade. 9615 S. Norwalk Blvd.,Santa Fe Springs,CA 90670 •(562)695-5555 •FAX: (562)692-1054 •www.stateplpe.com State Pipe &Supply, Inc. THIS INFORMATION PROVIDED IS BASED ON ASTM GUIDELINES FOR WELDED PIPE SPECIFICATIONS AND ASTM REQUIREMENTS. ACTUAL PIPE AND MATERIAL TEST REPORTS PROVIDED WOULD MEET OR EXCEED THESE GUIDELINES. TEST REPORTS WOULD PROVIDE SPECIFIC AND ACTUAL DETAILS CONCERNING THE MECHANICAL AND CHEMICAL PROPERTIES OF THE ACTUAL PIPE,AS WELL AS ADDITIONAL TESTS RESULTS REQUIRED BY ASTM. SCHEDULE 10**Black and Galvanized Steel ERW Pipe Pipe Size Test Pressure Nominal O.D. I.D. Weight/Foot psi 1" 1.315 1.097 1.410 700 1-1/4" 1.660 1.442 1.810 1200 1-1/2" 1.900 1.682 2.090 1200 2" 2.375 2.157 2.640 2300 2-1/2" 2.875 2.635 3.530 2500 3" 3.500 3.260 4.340 1290 4" 4.500 4.260 5.620 1000 5" 5.563 5 295 7.780 1010 6" 6.625 6.357 9.300 1020 8.625 8.249 16.960 780 • '*8"wall thickness is 0.188, not SCH10 or 0.148"wall thickness. COMPOSITION AND PROPERTIES Chemical and mechanical properties requirements are as prescribed by applicable ASTM standards edition January 2006. Chemical Requirements,Percent(Product) C Mn P S Other Specification Grade max max max max ASTM A53 A 0.250 0.950 0.05 0.045 - 1 Residual elements max:Cu-0.40.Ni-0.40.Cr-0.40.Mo-0 15 and V-.08. These live elements combined shall not exceed 1% Mechanical Properties-Tensile Requirements Stren th-psi. Yield Tensile Specification Grade Min Max Min Max ASTM A53 A _ 30,000 - 48,000 - NOTE: Elongation requirements vary with nominal area of test specimen and specified minimum tensile strength of the steel grade 9615 S. Norwalk Blvd.,Santa Fe Springs,CA 90670 •(562)695-5555 •FAX: (562)692-1054 •www.statepipe.com • IPS CARBON STEEL PIPE-HOLE CUT PRODUCTS • FireLock® Outlet-T 0 <> ® vds LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 • The Style 922 Outlet-T provides a convenient method of incorporating V,3,and 1715,20 and 25mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and other outlet products.Available for 11 through 76.1 mm/32 to 76.1 mm piping systems,Style 922 outlets are UL/ULC Listed,LPCB and FM Approved for branch connections and VdS Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UUFM rated up to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard,lightwall,Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing:Ductile iron conforming to ASTM A-536,grade 65-45-12.Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Gasket: • Grade"E"EPDM-Type A (Violet color code).FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Gasket System. Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: • Orange enamel(North America,Latin America,Asia Pacific) • Red enamel(Europe) JOB/OWNER CONTRACTOR ENGINEER System No. __ Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctaulIi G� REV_G 10.52_1 • IPS CARBON STEEL PIPE-HOLE CUT PRODUCTS 10.52 FireLock® Outlet-T STYLE 922 DIMENSIONS Approx. Dimensions-inches/r■illimeters Weight Each Run X Branch +0.061.1.5 - Y Z I FPT; I T• Y _.-. w,. V. X $ 1 . 1.30 1.83 1.10 3.87 2.56 .0 V � \W1 32 15 _ 30.2 33.0 46.5 27.9 98.3 65A 0.45 • / ` ' 34 135. 1.28 1.83 1.10 3.87 2.56 1.1 ` l l 20 30.2 32.5 46.5 27.9 98.3 65.0 050 r.,��r VV ,:I 1 1 V. 1 52 2.18 1.10 3.87 2.56 1.2 �� 1 V I 25 30.2 38.6 55.4 27.9 98.3 650 054 _ 11/2 V2 111. 1.42 1.95 1.22 4.08 2.56 1.2 40 X 15 30.2 36.1 49.5 31.0 103.6 65.0 0.54 14 135. 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 495 31.0 103.6 65.0 0.54 1 115. 1.64 2.30 1.22 4.08 2.56 1.3 25 _ 30.2 41.7 58.4 31.0 103.6 650 0.59 2 h 19. 1.66 2.19 1.46 4.60 2.56 1.3 50 X 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 3/4 131. 1.64 2.19 1.46 4.60 2.56 1.4 20 30.2 41.7 55.6 37.1 116.8 65.0 0.64 1 1 v. 1.88 2.54 1.46 4.60 2.56 1.5 25 30.2 47.8 645 37.1 116.8 65.0 0.68 21 Y2 111. 1.91 2.44 1.71 5.40 2.56 1.6 65 X 15 30.2 48.5 62A 43.4 137.2 65.0 0.73 94 1 R. 1.89 2.44 1.11 5.40 2.56 1.6 20 30.2 48.0 62.0 43.4 1372 65.0 0.73 1 135. 2.13 2.79 1.71 5.40 2.56 1.6 25 302 54.1 70.9 43.4 1372 65.0 0.73 76.11T1rn X 16 1'F. 1.91 2.44 1.71 5.50 2.56 1.6 15 302 48.5 62,0 43.4 139.7 65.0 0.73 54 1 M. 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 62.0 43.4 139.7 65.0 0.73 1 151. 2.13 2.79 1.71 5.50 2.56 1.7 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional) male pipe threads only.Use of male threaded products with special features,such as probes,dry pen- dent sprinklers,etc,should be verified as suitable for use with this Victaulic product.Failure to verify , suitability in advance may result in assembly problems or leakage. 'Center of run to engaged pipe end for NPT threads(dimensions are approximate). www.victaulic.com • VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICta'lUI1C� 10.52_2 REV_G • • IPS CARBON STEEL PIPE-HOLE CUT PRODUCTS 10.52 FireLock® Outlet-T STYLE 922 PERFORMANCE Equivalent Length of 1 inch Schedule 40 Steel Pipe(per UL Run Size x Outlet Size 213,Section 16)(C=120)•,FT .e....'u"„"."i..,9!l�ir+•+ersglu ,.+..s. '��7!'.w"_."rst'.°'6 Inches/mm Feet/meters 116 x 1 32 25 1%z x 1 40 25 2 x 1 8.5 50 25 2.6 21/2 X 1 8.5 65 25 2.6 76.1 mm X 1 8.5 25 2.6 •Hazen-Williams coefficient of friction is 120 www.victaulic.com 6 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 209 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jataUllse REV_G 10.52_3 FireLock® Outlet-T STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing.Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 10.52 3355 REV G UPDATED 12/2009 C'.t.aUll1C VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.O 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10.52 Pipe Hangers Fig. 200 - "Trimline" Adjustable Band Hanger (Cooper B-Line Fig.B317ONF) ®TOLCO Fig. 200F - "Trimline" Adjustable Band Hanger with Felt Lining (Cooper B-Line Fig. B317ONFF) Fig. 200C - "Trimline" Adjustable Band Hanger with Plastic Coated (Cooper B-Line Fig. B317ONFC) LISTED Fig. 200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig.200 - 1/2"(15mm)thru 8"(200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications ,. Function: For fire sprinkler and other general piping purposes. Knurled -- swivel nut design permits hanger adjustment after installation. u Features: • (1/2" (15mm)thru 2"(50mm)) Flared edges ease installation for all pipe ,' �:` types and protect CPVC plastic pipe from abrasion.Captured design `J keeps adjusting nut from separating with hanger. Hanger is easily a B installed around pipe. For hanger with non-captured nut order Fig. 200S. ' (- f; ,▪ (21/2" (65mm)thru 8"(200mm))Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. � Approvals: Underwriters Laboratories listed (1/2"(1 5mm)thru 8" (200mm)) --='' Fig.200-Vz.200-3/a in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (FM)(3/4"(20mm)thru 8"(20omm Fig.200-1 zee 2 Fig.zoa z�/z to zoo 8 rY 9 9 PP ( )( ( ) )) Conforms to Federal Specifications WW-H-171 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, ,,y, Type 10. Maximum Temperature: 650°F(343'C) Finish: Pre-Galvanized. Stainless Steel materials will be supplied with(2)hex nuts O ) in place of a knurl nut. "'31 Order By: Figure number and pipe size 4 1 is Designed to meet or exceed requirements of FM DS 2-0. )s.. ; • n w Rs.200 Fig.200C Rg.200F Pipe Size Rod Size A B Approx.Wt./100 Part No. in. (mm) in. (nun) in. (nun) lbs. (kg) tit, 200-1/2 t/2" (15) 3/8"-16 31/8" (79.4) 25/8" (66.7) 11 (5.0)- 200-3/4 3/4" (20) 3/8"-16 31/8" (79.4) 21/2" (63.5) 11 (5.0) 200-1 1" (25) 3/8"-16 33/8" (85.7) 25/8" (66.7) 12 (5.5) ,_ 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8" (73.0) 13 (5.9) r 200-11/2 11/2" (40) 3/e"-16 37/e" (98.4) 27/B" (73.0) 14 (6.4) ' 200-2 2" (50) 3/e"-16 41/2" (114.3) 3" (/6.3) 15 (6.9) 200-21/2 21/2" (65) 3/e"-16 55/8" (142.9) 41/8" (104.7) 27 (12.3) 200-3 3" (75) 3/B"-16 5718" (149.1) 4" (101.6) 29 (13.3) Fig.2008 200-31/2 31/2" (90) 3/8"-16 73/e" (187.3) 51/4" (133.3) 34 (15.6) 200-4 4" (100) 318"-16 73/8" (187.3) 5" (1271) 35 (16.0) 200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" (158.7) 66 (30.2) 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 20 . / COOPER B-Line Pipe Hangers • ®TOLCO' Fig. 200M - "Trimline" Adjustable Band Hanger for Metric Rod O Size Range: C US Fig.200 - 1/2"(15mm)thru 8"(200mm)pipe LMTEO Material: Steel,Pre-Galvanized to G90 specifications Function: For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. _ � Features: `� • (1/2"(15mm)thru 2"(5omm))Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion.Captured design keeps adjusting nut from separating with hanger. Hanger is easily o 40 installed around pipe. r ® • (21/2"(65mm)thru 8"(2oomm))Spring tension on nut holds it securely in hanger before installation.Adjusting nut is easily removed. , B Approvals: Underwriters Laboratories listed(1/2"(15mm)thru 8"(2013mm)) N.200-1 to 200-2 in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and A ' Factory Mutual Engineering Approved(3/4"(20mm)thru 8"(20omm)). - Conforms to Federal Specifications WW-H-171 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, Type 10. Y/ Flo.200-1/z.200-3I4 Maximum Temperature: 650°F(343°C) pg.200-2+h to 200-8 Finish: Pre-Galvanized.Stainless Steel materials will be supplied with(2)hex nuts in place of a knurl nut. Order By: Figure number and pipe size AL Designed to meet or exceed requirements of FM DS 2-0. �1►- Pipe Size Rod Size A B Approx.Wt./100 Part No. in. (mm) in, (mm) in. (mm) lbs. (kg) 200M8-1/2 1/2" (15) M8 31/8" (79.4) 25/8" (66.7) 11 (5.0) 200M10-1/2 1/2" (15) M10 31/8" (79.4) 25/8" (66.7) 11 (5.0) 200M8-3/4 3/4" (20) M8 31/8" (79.4) 21/2" (63.5) 11 (5.0) 200M10-3/4 3/4" (20) M10 31/8" (79.4) 21/2" (63.5) 11 (5.0) 200M8-1 1" (25) M8 33/8" (85.7) 25/8" (66.7) 12 (5.5) 200M10-1 1" (25) M10 33/8" (85.7) 25/8" (66.7) 12 (5.5) 200M8-11/4 11/4" (32) M8 33/4" (94.0) 27/8" (73.0) 13 (5.9) 200M10-11/4 11/4" (32) M10 33/4" (94.0) 27/e" (73.0) 13 (5.9) 200M8-11/2 11/2" (40) M8 37/8" (98.4) 2'/e" (73.0) 14 (6.4) 200M10-11/2 11/2" (40) M10 37/8" (98.4) 27/8" (73.0) 14 (6.4) 200M8-2 2" (50) M8 41/2" (114.3) 3" (76.3) 15 (6.9) 200M10-2 2" (50) M10 41/2" (114.3) 3" (76.3) 15 (6.9) 200M-21/2 21/2" (65) M10 55/8" (142.9) 41/8" (104.7) 27 (12.3) 200M-3 3" (75) M10 57/6" (149.1) 4" (101.6) 29 (13.3) 200M-31/2 31/2" (90) M10 73/8" (187.3) 51/4" (133.3) 34 (15.6) 200M-4 4" (100) M10 73/8" (187.3) 5" (127.0) 35 (16.0) 200M-S 5" (125) M12 91/8" (231.8) 61/4" (158.7) 66 (30.2) 20051$ 6" (150) M12 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200M-8 8" (200) M12 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. COOPER- BB-Line