Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications
PS20ILI - 00020 HYDRAULIC CALCULATIONS 154 �Z 1,-urn VTR for RECEIVED Job Information Project Name:Arlington Heights#94 FEB - 3 2014 m Contract No. :C13 4581 City: Tigard, OR 97223 CITYOFTIGARD Project Location: 15492 SW Sumerview Dr Date:2/3/2014 BUILDING DIVISION Contractor Information Name of Contractor: Wyatt Fire Protection Address: 9095 SW Burnham Dr City: Tigard, OR 97223 f Phone Number: (503)684-2928 E-mail:a.payne @wyattfire.com Name of Designer: Ashley Payne Authority Having Jurisdiction: City of Portland Design Remote Area Name BR 2 and Closet Remote Area Location Occupancy Classification Residential_NewCommodityl Density(gpm/ft2) 0.04 Area of Application (ft2) 648 Coverage per Sprinkler(ft2) 324 Number of Calculated Sprinklers 2 In-Rack Demand(gpm) 0 Special Heads Hose Streams(gpm) 0 Total Water Required(incl. Hose Streams)(gpm) 26.4 Required Pressure at Source(psi) 48.8 Type of System Wet Volume- Entire System (gal) 2.4 gal Water Supply Information Date Location Source Notes 1 File:C:\Users\Ashley\Documents\Projects\Arlington\94\Arlington 94 Calcs.tyc3 Date 2/3/2014 Copyright©2002-2012 Tyco Fire Protection Products Page 1 Job :Arlington Heigftts#94 Node Labels: Node Feference Pipe Labels: Off Diagram for Design Area : BR 2 and Closet n39 n38 h3 h4 n34 .40401111n37 n33 2 32 srcl File:C:\Users\Ashley\Documents\Projects\Arlington1941Arlington 94 Calcs.tyc3 Date 2/3/2014 Copyright©2002-2012 To Fire Protection Products Page 2 Job:Arlington Heights#94 Hydraulic Analysis for : BR 2 and Closet Calculation Info Calculation Mode Demand Hydraulic Model Hazen-Williams Fluid Name Water @ 60F (15.6C) Fluid Weight, (Ib/ft3) N/A for Hazen-Williams calculation. Fluid Dynamic Viscosity, (Ib•s/ft2) N/A for Hazen-Williams calculation. • Water Supply Parameters Supply 1 : srcl Flow(gpm) Pressure(psi) 0 118 1230 54 Hoses Inside Hose Flow/Standpipe Demand(gpm) Outside Hose Flow(gpm) Additional Outside Hose Flow(gpm) Other(custom defined) Hose Flow(gpm) Total Hose Flow(gpm) Sprinklers Ovehead Sprinkler Flow(gpm) 26.4 InRack Sprinkler Flow(gpm) 0 Other(custom defined)Sprinkler Flow(gpm) 0 Total Sprinkler Flow(gpm) 26.4 Other Required Margin of Safety(psi) 0 Base of Riser -Pressure(psi) 48.8 Base of Riser -Flow(gpm) 26.4 Demand w/o System Pump(s) N/A File:C:\Users\Ashley\Documents\Projects\Arlington\941Arlington 94 Calcs.tyc3 Date 2/3/2014 Copyright©2002-2012 Tyco Fire Protection Products Page 3 . ` Job:Arlington Heights#94 Hydraulic Analysis for : BR 2 and Closet f Supply f System Demand 150 140 _ --- - — - 120 L` — - — -__ 110 ---- -- — _ - -Y ; ___.._ 100 -- i ( __' Q90 -_ f L_ ter. , _- -- C) 80 NMI __.- ----' mrt� H- ---- 6 ∎∎a D2 �:on . - + 47.099 50 - --. , limmi s.., .. = --1— • 40 -- ��.n NI , 111•111111E1 . . -, . I = ����2• D1 � ■ --. • —. -- 1 _ _ N- 0 ism N====s∎∎∎∎A∎∎∎∎∎∎■•• •■•■∎1 0 400 500 600 700 800 900 1000 1100 1200 1300 Flow, gpm File:C:\Users\Ashley\Documents\Projects\Arlington\94\Arlington 94 Calcs.tyc3 Date 2/3/2014 Copyright©2002-2012 Tyco Fire Protection Products Page 4 Job :Arlington Heights#94 Hydraulic Analysis for : BR 2 and Closet Graph Labels Label Description Values Flow (gpm) Pressure (psi) • S1 Supply point#1 -Static 0 118 '') S2 Supply point#2-Residual 1230 54 D1 Elevation Pressure 0 7.4 D2 System Demand 26.4 48.8 r Curve Intersections & Safety Margins Intersection Safety Margin Curve Name -_ __ Pressure (psi) Flow (gpm) Pressure (psi) @ Flow (gpm) Supply 117.9 44.9 69.2 26.4 Open Heads Required _ Head Ref. Head Type Coverage K-Factor Density Flow Pressure Density Flow Pressure (ft2) (gpm/Psi'/2) (gpm/ft2) (gpm) (psi) (gpm/ft2) (gpm) (Psi) h3 Overhead 324 4.9 0.04 17 7 0.041 13.4 7.5 Sprinkler h4 Overhead 324 4.9 0.04 17 7 0.04 13 7 Sprinkler n a File:C:\Users\Ashley\Documents\Projects\Arlington1941Arlington 94 Calcs.tyc3 Date 2/3/2014 Copyright©2002-2012 Tyco Fire Protection Products Page 5 Job :Arlington Heights#94 Hydraulic Calculations/Fluid Delivery Time Analysis Node Data Node# Type K-Fact. Discharge Coverage Tot. Pres. Req. Pres. Elev Hgroup Open/Closed Overdischarge Density Elev. Pres. Req. Discharge gpm/psis/z gpm ft2 psi psi ft gpm gpm/ft2 psi gpm n2 Node 43.1 4 NODE -1.3 ` n32 Node 44 3 NODE -0.9 srcl Supply 48.8 -26 4 1 SUPPLY 0 n33 Node 38.5 9 NODE -3.5 n34 Node 31 9 NODE -3.5 n35 Node 25.7 9 NODE -3.5 n37 Node 23 9 NODE -3.5 n38 Node 14.5 18 NODE -7.4 n39 Node 12.3 18 NODE -7.4 n40 Node 8.6 18 NODE -7.4 n41 Node 7.7 18 NODE -7.4 h3 Overhead Sprinkler 4.9 13.4 324 7.5 7 18 HEAD Open -3.6 0.041 -7.4 17 h4 Overhead Sprinkler 4.9 13 324 7 7 18 HEAD Open -4 0.04 -7.4 17 J1 File:C:\Users\Ashley\Documents\Projects\Arlington\94\Arlington 94 Calcs.tyc3 Date 2/3/2014 Copyright©2002-2012 Tyco Fire Protection Products Page 6 Job name:Arlington Heights#94 Sheet number: PIPE INFORMATION Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt) Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES T frict (Pf) . (ft) (gpm/psil/2) (gpm) (M) (ft) (ft) (psi) (psi) ..' h4 18 4.9 13 .75 1x(BM.90)=4 3.5 150 7 n41 18 13 0.874 4 0.0939 0 7.5 0.7 .4. n41 18 0 .75 lx(BM.Tee-Run)=1 7.75 150 7.7 n40 18 13 0.874 1 0.0939 0 8.75 0.8 _1, n40 18 13.4 .75 lx(BM.90)=4 6.75 150 8.6 n39 18 26.4 0.874 4 0.3497 0 _ 10.75 3.8 n39 18 0 .75 lx(BM.90)=4 2.25 150 12.3 n38 18 26.4 0.874 4 0.3497 0 6.25 2.2 n38 18 0 .75 lx(BM.90)=4 9 150 14.5 n37 9 26.4 0.874 4 0.3497 3.9 13 4.5 n37 9 0 .75 lx(BM.Tee-Br)=3 4.75 150 23 n35 9 26.4 0.874 3 0.3497 0 7.75 2.7 n35 9 0 .75 lx(BM.90)=4 11.33 150 25.7 n34 9 26.4 0.874 4 0.3497 0 15.33 5.4 n34 9 0 .75 lx(BM.90)=4 17.33 150 31 n33 9 26.4 0.874 4 0.3497 0 21.33 7.5 n33 9 0 .75 lx(coupling)=2.01 5 150 38.5 n2 4 26.4 0.874 2.01 0.3497 2.2 7.01 2.5 n2 4 0 1 lx(coupling)=1 1 120 43.1 n32 3 26.4 1.049 1 0.2174 0.4 2 0.4 n32 3 0 1 2 0 44 Ames 200B 1" srcl 1 26.4 0 0 1.958 0.9 2 3.9 h3 18 4.9 13.4 .75 lx(BM.Tee-Br)=3 7.5 150 7.5 n40 18 13.4 0.874 3 0.0998 0 10.5 1 * Discharge shown for flowing nodes only ©2006 National Fire Protection Association Page 7 RECEIVED ttico FEB - 3 2014 CITYOFTIGARD Worldwide Contacts www.tyco-fire.com Rapid Response Series LFII Residential 4.9 K-factor Concealed Pendent Sprinklers, Flat Plate Wet Pipe and Dry Pipe Systems General The Series LFII Residential Concealed . Pendent Sprinklers(TY3596)has been Description designed with heat sensitivity and wa- ter distribution characteristics proven Adak The TYCO RAPID RESPONSE Se- to help in the control of residential fires ries LFII Residential 4.9 K-factor Con- and to improve the chance for occu- cealed Pendent Sprinklers (TY3596) pants to escape or be evacuated. � j are decorative, fast response, fus- able solder sprinklers designed for use The Series LFII Residential Concealed f in residential occupancies such as Pendent Sprinklers (TY3596) are �__ homes, apartments, dormitories, and shipped with a Disposable Protective f hotels. Cap. The Protective Cap is temporar- , . T'�� ily removed for installation, and then The cover plate assembly conceals it can be replaced to help protect the the sprinkler operating components sprinkler while the ceiling is being in- above the ceiling.The flat profile of the stalled or finished. The tip of the Pro- cover plate provides the optimum aes- tective Cap can also be used to mark thetically appealing sprinkler design. the center of the ceiling hole into plas- NOTICE In addition, the concealed design of ter board, ceiling tiles, etc. by gently the Series LFII Residential Concealed pushing the ceiling product against The Series LFII Residential Con- Pendent Sprinklers (TY3596) provides the Protective Cap. When the ceiling cealed Pendent Sprinklers (TY3596) 1/2 inch (12,7 mm) vertical adjustment. installation is complete the Protective described herein must be installed This adjustment provides a measure of Cap is removed and the Cover Plate and maintained in compliance with flexibility when cutting fixed sprinkler Assembly installed. this document and with the applica- drops. ble standards of the National Fire Pro- The Series LFII Residential Concealed Dry Pipe System Application tection Association, in addition to the Sprinklers are intended for use in the The Series LFII Residential Concealed standards of any authorities having ju- Sprinklers scenarios:rintended Pendent Sprinklers offers a laboratory risdiction. Failure to do so may impair approved option for designing dry pipe the performance of these devices. • wet and dry pipe residential sprin- residential sprinkler systems,whereas, The owner is responsible for maintain- kler systems for one- and two-tam- most residential sprinklers are labora ing their fire protection system and de ily dwellings and mobile homes per tory approved for wet systems only. vices in proper operating condition. NFPA 13D Through extensive testing, it has been The installing contractor or sprinkler • wet and dry pipe residential sprin- determined that the number of design manufacturer should be contacted kler systems for residential occu- sprinklers (hydraulic design area) for with any questions. pancies up to and including four the Series LFII Residential Concealed stories in height per NFPA 13R Pendent Sprinklers (TY3596) need not Sprinkler be increased over the number of de- • wet and dry pipe sprinkler systems sign sprinklers (hydraulic design area) Identification for the residential portions of any as specified for wet pipe sprinkler sys- occupancy per NFPA 13 tems, as is accustomed for density/ area sprinkler systems designed per Number NFPA 13. TY3596 Consequently,the Series LFII Residen- tial Concealed Pendent Sprinklers of- IMPORTANT fer the features of non-water filled pipe Always refer to Technical Data in addition to not having to increase Sheet TFP700 for the "INSTALLER the number of design sprinklers (hy- WARNING" that provides cautions draulic design area) for systems de- with respect to handling and instal- signed to NFPA 13, 13D, or 13R. Non- lation of sprinkler systems and corn- water filled pipe will permit options for i ponents. Improper handling and in- areas sensitive to freezing. stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 APRIL 2013 TFP442 TFP442 Page 2 of 6 BODY ; Q SEALING WRENCH (1/2"NPT) '` ASSEMBLY RECESS CAP ►t �, `l� ��/'",s,, .z,' e \ \ SPRINKLER ) I^ _____ •OM WRENCHING • SADDLE � % =1 1 —� 1 4 — -N PUSH WRENCH SUPPORT {� COMPRESSION IN TO ENSURE CUP WITH lj 1 I I SCREW ENGAGEMENT ROLL FORMED i g WITH SPRINKLER ' THREADS ) 1 WRENCHING AREA A LEVER .A I FIGURE 2 GUIDE I IM. I W-TYPE 18 PIN •■•■•• •�_•,• SPRINKLER WRENCH SOLDER LINK ELEMENT GUIDE PIN HOUSING DEFLECTOR C 1 --�_tu (OPERATED DEFLECTOR - l r POSITION) SPRINKLER/SUPPORT CUP ASSEMBLY THREAD INTO I I RETAINER SUPPORT I i WITH THREAD CUP UNTIL J I DIMPLES MOUNTING \ O 0 I SURFACE IS FLUSH WITH CEILING EJECTION SPRING —/J =�A SOLDER-- COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER(TY3596) 2-1/2"DIA. SPRINKLER- (63,5 mm) y 1/2'(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING J OPERATED —.� SPRINKLER 1.------- .‘ , iil ------1.......!....■ 11 COVER 1-7/8"t1/4" PLATE - (47,6 mm RETAINER - I 1/8"GAP ±6,4 mm) '1 l►( Aiiii�� (3,2 mm) 1 ~� �� is „ I ` 1 i_- } 1 7/8"(22,2 mm) I COVER- SPRINKLER- MOUNTING RETAINER SUPPORT CUP 1-1/8"(28,6 mm) ASSEMBLY ASSEMBLY 3/16" SURFACE \ ,I•∎-,I. 1 (4,8 mm) _ 3-3/16"DIA. DISPOSABLE DEFLECTOR IN - (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION - FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER(TY3596) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR TFP442 Page 3 of 6 Technical Design Criteria Dry Pipe System Water Delivery g When using the Series LFII Residen- - Data The TYCO RAPID RESPONSE Series tial Concealed Pendent Sprinklers LFII Residential Concealed Pendent (TY3596)in dry pipe sprinkler systems, Approvals: Sprinklers (TY3596) are UL and C-UL the time for water delivery must not ex- UL and C-UL Listed. NYC Approved Listed for installation in accordance ceed 15 seconds for the most remote under MEA 44-03-E-2 NSF Certified to NSF/ANSI 61 with this section, operating sprinkler. The TYCO RAPID RESPONSE Series Note: When conditions exist that are Obstruction to Water Distribution The TYCO RAP Concealed RESPO Pendent outside the scope of the provided cri- Sprinklers are to be located in accor- feria, refer to the Residential Sprinkler dance with the obstruction rules of • Sprinklers are only listed with the Se- Design Guide TFP490 for the menu- NFPA 13D, 13R, and 13 as applicable ries LFII Concealed Cover Plates hav- facturer's recommendations that may for residential sprinklers as well as with ing a factory applied finish. be acceptable to the authority having the obstruction criteria described with- Maximum Working Pressure: jurisdiction. in the Technical Data Sheet TFP490. 175 psi (12,1 bar) Discharge Coefficient: System Types Operational Sensitivity. The sprin- Discharge GPM/psi'2(70,6 LPM/bar12} Per the UL Listing, wet pipe and dry klers are to be installed relative to the pipe systems may be utilized. Per the ceiling mounting surface as shown in Temperature Rating: C-UL Listing, only wet pipe systems Figure 3. 160°F(71°C)Sprinkler with may be utilized. Sprinkler Spacing. The minimum 139°F(59°C)Cover Plate Refer to Technical Data Sheet TFP485 spacing between sprinklers is 8 feet Vertical Adjustment: about the use of residential sprinklers (2,4 m). The maximum spacing be- 1/2 inch(12,7 mm) in residential dry pipe systems. tween sprinklers cannot exceed the Finishes: length of the coverage area(Ref.Table Refer to Ordering Procedure section Ceiling Types A or B) being hydraulically calculated Smooth flat horizontal, or beamed, or (e.g., maximum 12 feet for a 12 ft.x 12 Physical Characteristics: sloped, in accordance with the 2013 ft.coverage area,or 20 feet for a 20 ft. Body Brass Edition of NFPA 13D, 13R, or 13 as x 20 ft.coverage area). Cap Bronze applicable. Saddle Brass The Series LFII must not be used in Sealing Assembly Beryllium Hydraulic Design applications where the air pressure Nickel w/TEFLON (NFPA 13D and 13R) above the ceiling is greater than that Soldered Link Halves Nickel For systems designed to NFPA 13D below. Down drafts through the Sup- Lever Bronze or NFPA 13R, the minimum required port Cup could delay sprinkler opera- Compression Screw Brass sprinkler flow rates are given in Ta- tion in a fire situation. Deflector Copper or Brass bles A and B as a function of tem- Guide Pin Housing Bronze perature rating and the maximum Guide Pins Stainless Steel allowable coverage areas. The sprin- or Bronze kler flow rate is the minimum re- Support Cup Steel quired discharge from each of the Cover Plate Copper total number of"design sprinklers" as Retainer Brass specified in NFPA 13D or NFPA 13R. Cover Plate Ejection Spring The number of "design sprinklers" Stainless Steel specified in NFPA 13D and 13R for wet pipe systems is to be applied when Operation designing dry pipe systems. When exposed to heat from a fire, the Hydraulic Design Cover Plate, which is normally sol- (NFPA 13) dered to the Support Cup at three For systems designed to NFPA 13,the points,falls away to expose the Sprin- number of design sprinklers is to be kler Assembly. At this point the De- the four most hydraulically demanding flector supported by the Arms drops sprinklers.The minimum required dis- down to its operated position.The fus- charge from each of the four sprinklers ible link of the Sprinkler Assembly is is to be the greater of the following: comprised of two link halves that are soldered together with a thin layer of • The flow rates given in Tables A solder. When the rated temperature is and B as a function of temperature reached,the solder melts and the two rating and the maximum allowable link halves separate allowing the sprin- coverage area. kler to activate and flow water. • A minimum discharge of 0.1 gpm/ ft2 over the"design area"comprised of the four most hydraulically demanding sprinklers for actual ,l coverage areas protected by the four sprinklers. The number of "design sprinklers" specified in NFPA 13 for wet pipe sys- tems is to be applied when designing dry pipe systems. TFP442 Page 4 of 6 WET PIPE SYSTEM Minimum Flow and Residual Pressuret•°I Maximum Maximum • Coverage Spacing Ordinary Temp.Rating Area( p 160°F(71°C) Minimum Ft.x Ft. Ft' Deflector to Installation Spacing (m x m) (m) Flow Pressure Ceiling Type Ft. GPM PSI (m) (L/min) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 13 7.0 inches (4,3 x 4,3) (4,3) (49,2) (0,48) Beamed 16 x 16 16 13 7,0 Ceilings per 8 (4,9 x 4,9) (4,9) (49,2) (0,48) NFPA 13D or Concealed (2,4) 13R,or 13. Installed in 18 x 18 18 17 12.0 beam (5,5 x 5,5) (5,5) (64,3) (0,83) 7/8 to 1-1/8 inches below 20 x 20 20 20 16.7 bottom of (6,1 x 6,1) (6,1) (75,7) (1,15) beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow In accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY3596) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Minimum Flow and Residual Pressure tb,°t Maximum Maximum Coverage Ordinary Temp.Rating Areal Spat' 160°F(71°C) Minimum Ft.x Ft. . Deflector to Installation Spacing (m x m) Ceiling Type Ft. GPM PSI (m) (L/min) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 14 8.2 inches (4,3 x 4,3) (4,3) (53,0) (0,57) Beamed 16 x 16 16 15 9.4 Ceilings per 8 (4,9 x 4,9) (4,9) (56,8) (0,65) NFPA 13D or Concealed (2,4) 13R,or 13. Installed in 18 x 18 18 18 13.5 beam (5,5 x 5,5) (5,5) (68,1) (0,93) 7/8 to 1-1/8 inches below 20 x 20 20 21 18.4 bottom of (6,1 x 6,1) (6,1) (79,5) (1,27) beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. g TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT-PLATE CONCEALED PENDENT(TY3596) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP442 Page 5 of 6 Installation Step 6. Screw on the Cover Plate As- Care must be exercised to avoid dam- sembly until its flange comes in con- age -before, during, and after installa- The TYCO RAPID RESPONSE Series tact with the ceiling. tion. Sprinklers damaged by dropping, LFII Residential Concealed Pendent Do not continue to screw on the Cover striking, wrench twist/slippage. or the • Sprinklers (TY3596) must be installed Plate Assembly such that it lifts a ceil- like, must be replaced. in accordance with this section. ing panel out of its normal position. If the Cover Plate Assembly cannot The owner is responsible for the in General Instructions spection, testing, and maintenance of Damage to the fusible Link Assembly be engaged with the Mounting Cup their fire protection system and devic- during installation can be avoided by or the Cover Plate Assembly cannot es in compliance with this document, handling the sprinkler by the support be engaged sufficiently to contact the as well as with the applicable Stan- • cup only(i.e., do not apply pressure to ceiling, the Sprinkler Fitting must be dards of the National Fire Protection the fusible Link Assembly). Association(e.g., NFPA 25), in addition Y)• repositioned. to the standards of any other authori- A 1/2 inch NPT sprinkler joint should ties having jurisdiction. The installing be obtained with a minimum to maxi- Care and contractor or sprinkler manufacturer mum torque of 7 to 14 ft.-lbs. (9,5 to should be contacted relative to any 19,0 Nm). Higher levels of torque may Maintenance questions. distort the sprinkler inlet with conse- quent leakage or impairment of the The TYCO RAPID RESPONSE Se- The owner must assure that the sprin- sprinkler. ries LFII Residential Concealed Pen- klers are not used for hanging any ob- Do not attempt to compensate for in- dent Sprinklers (TY3596) must jects and that the sprinklers are only sufficient adjustment in the Cover be maintained and serviced in cleaned by means of gently dusting accordance with this section. with a feather duster; otherwise, non- Plate/Retainer Assembly by under-or operation in the event of a fire or inad- over-tightening the Sprinkler. Readjust Before closing a fire protection system vertent operation may result. the position of the sprinkler fitting to main control valve for maintenance suit. work on the fire protection system Automatic sprinkler systems should be Step 1. The sprinkler must only be in- which it controls, permission to shut inspected,tested,and maintained by a stalled in the pendent position and down the affected fire protection sys- qualified Inspection Service in accor- tern must be obtained from the prop- dance with local requirements and/or with the centerline of the sprinkler per er authorities and all personnel who national codes. pendicular to the mounting surface. may be affected by this action must be Step 2. Remove the Protective Cap. notified. Step 3. With pipe thread sealant ap- Absence of a Cover Plate may de- plied to the pipe threads,and using the lay the sprinkler operation in a fire W-Type 18 Wrench shown in Figure 2, situation. install and tighten the Sprinkler/Sup- When properly installed, there is a port Cup Assembly into the fitting.The nominal 1/8 inch (3,2 mm) air gap be - W-Type 18 Wrench will accept a 1/2 tween the lip of the Cover Plate and inch ratchet drive. the ceiling, as shown in Figure 3. This Step 4. Replace the Protective Cap by air gap is necessary for proper op- pushing it upwards until it bottoms out eration of the sprinkler by allowing against the Support Cup. The Protec- heat flow from a fire to pass below tive Cap helps prevent damage to the and above the Cover Plate to help as- Deflector and Guide Pins during ceil- sure appropriate release of the Cover ing installation and/or during applica- Plate in a fire situation. If the ceiling is tion of the finish coating of the ceil- to be repainted after the installation of ing. It may also be used to locate the the Sprinkler, care must be exercised center of the clearance hole by gen- to ensure that the new paint does not tly pushing the ceiling material against seal off any of the air gap. the center point of the Cap. Factory painted Cover Plates must Note: As long as the protective Cap not be repainted. They should be re- remains in place,the system is consid- placed, if necessary, by factory paint- ered to be"Out Of Service". ed units. Non-factory applied paint Step 5. After the ceiling has been may adversely delay or prevent sprin- completed with the 2-1/2 inch (63 mm) kler operation in the event of a fire. diameter clearance hole and in prep- Do not pull the Cover Plate relative to aration for installing the Cover Plate the Enclosure.Separation may result. Assembly, remove and discard the Sprinklers which are found to be leak- Protective Cap, and verify that the De- ing or exhibiting visible signs of corro- flector moves up and down freely. sion must be replaced. If the Sprinkler has been damaged and Automatic sprinklers must never be the Deflector does not move up and painted, plated, coated, or otherwise down freely, replace the entire Sprin altered after leaving the factory. Modi- kler assembly.Do not attempt to modi- fied or over heated sprinklers must be fy or repair a damaged sprinkler. replaced. TFP442 Page 6 of 6 Ordering Procedure ~ When placing an order, indicate the full product name. Contact your local distributor for availability. Sprinkler Assembly: Series LFII (TY3596), K=4.9, Resi- dential Concealed Pendent Sprin- kler without Cover Plate Assembly, P/N 51-112-1-160 Cover Plate Assembly: Cover Plate Assembly having a(spec- ify) finish for the Series LFII (TY3596), K=4.9, Residential Concealed Pendent Sprinkler,P/N(specify) Ivory(RAL1015) P/N 56-202-0-135 Beige(RAL1001) P/N 56-202-2-135 Pure White(b)(RAL9010) P/N 56-202-3-135 Signal White(a)(RAL9003) P/N 56-202-4-135 Grey White(RAL9002) P/N 56-202-5-135 Brown(RAL8028) P/N 56-202-6-135 Black(RAL9005) P/N 56-202-7-135 Brushed Brass P/N 56-202-8-135 Brushed Chrome P/N 56-202-9-135 Custom Paint P/N 56-202-X-135 (a)Previously known as Bright White. (b)Eastern Hemisphere sales only. Note:All Custom Cover Plates are painted us- ing Sherwin Williams Interior Latex Paint.Contact TYCO Customer Service with any questions re- lated to custom orders. Sprinkler Wrench: Specify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 GLOBAL HEADQUARTERS1 1400 Pennbrook Parkway,Lansdale,PA 19446 1 Telephone+1-215-362-0700 Copyright®2012 Tyco Fire Products,LP. All rights reserved. NCO TEFLON is trademark of The DuPont Corporation. tqccs I Fire & Building Aer Products rapid response HOME FIRE SPRINKLER SYSTEM Technical Services:Tel:(800)381-9312/Fax: (800)791-5500 BlazeMaster ® CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Technical Description Data Tyco Fire& Building Products (TFBP) Sizes BlazeMaster CPVC Pipe and Fittings 3/4"to 3" • are designed exclusively for use in wet ,' pipe automatic fire sprinkler systems. 175 plum Working Pressure They are made from a specially devel- 71A • oped thermoplastic compound corn- Approvals posed of post chlorinated polyvinyl UL, FM, CUL, NSF, Dade County, — 14 p. chloride(CPVC)resin and state of the LPCB,MEA,and the City of Los Ange- art additives. TFBP BlazeMaster les. (Refer to IH-1900, Rev. 0, Janu- CPVC products are easier to install ary 2005 "Installation Instruction & 41#11:". • than traditional steel pipe systems, Technical Handbook" for exact list- and at the same time,provide superior ing/approval information.) heat resistance and strength as corn- Manufacture Source pared to traditional CPVC and PVC U.S.A. piping materials used in the plumbing trade. Various adapters are available Material to connect CPVC pipe to metallic pip- Pipe:ASTM F442,SDR 13.5 ing. All female pipe thread adapters have brass inserts for durability. • Fittings: ASTM F438 (Sch. 40) and Grooved adapters connect directly to ASTM F439(Sch.80),ASTM F1970 grooved end valves and metallic pipe, Color with flexible grooved end couplings. Orange WARNING Tyco Fire&Building Products(TFBP) BlazeMaster CPVC Pipe and Fittings described herein must be installed and maintained in compliance with this document,as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. BlazeMasters is a registered trademark of Noveon IP Holding Corp. Page 1 of 6 JANUARY, 2006 TFP1915 Page 2 of 6 TFP1915 WATER NOMINAL AVERAGE AVERAGE WEIGHT FT.OF PIPE WEIGHT PER LIFT • SIZE O.D. I.D. lbs./ft. FILLED WEIGHT lbs./ft. PER LIFT lbs. 3/4" 1.050" 0.874" 0.18 0.44 7875 1339 1" 1.315" 1.101' 0.26 0.67 5040 1320 1-1/4' 1.660" 1.394" 0.42 1.08 2835 1191 1-1/2" 1.900" 1.598" 0.54 1.41 2205 1213 2" 2.375" 2.003" 0.84 2.20 1260 1084 2-1/2" 2.875" 2.423" 1.26 3.26 1215 1531 3" 3.500" 2.952" 1.87 4.83 720 1344 FIGURE 1—PIPE DIMENSIONS Installation Care and Tyco Fire and Building Products Maintenance (TFBP) BlazeMaster CPVC Pipe and Fittings are to be installed in accord- The owner is responsible for the fin- ance with IH-1900, Rev. 0, January spection,testing, and maintenance of 2005'Installation Instruction&Techni- their fire protection system and de- cal Handbook". vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. NOTES Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls,permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service,notify the proper authorities and advise those responsible for moni- toring proprietary and/or central sta- tion alarms. TFP1915 Page 3 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT TYPE NUMBER (T/O) (lb.) 0 TEE 80000 3/4" 5/8" 40 0.11 T/0 80001 1" 11/16" 40 0.19 /„j 80002 1-1/4" 7/8" 40 0.26 -ii. 80003 1-1/2" 1-1116" 80 0.51 MM.. 80004 2" 1-3/8" 80 0.90 80005 2-1/2" 1-9/16" 80 1.59 T/0 .1. 1!0 80006 3" 1-13/16" 80 2.41 X x Y x Z X Y Z 80132 3/4"x 3/4"x 1" 3/4' 3/4" 5/8" 40 0.14 80133 1"x 3/4"x 3/4" 9116" 9/16" 3/4" 40 0.14 80134 1"x 3/4"x 1" 3/4" 11/16" 3/4" 40 0.17 80260 1"x 1"x 3/4" 5/8" 5/8" 13/16" 40 0.16 80135 1-114"x 1"x 3/4" 5/8" 5/8" 15/16" 40 0.21 80136 1-1/4"x 1"x 1" 3/4" 3/4" 15/16" 40 0.22 80137 1-1/4"x 1"x 1-1/4" 15/16" 15/16" 7/8" 40 0.26 REDUCING TEE 80261 1-1/4"x 1-1/4'x 3/4" 5/8" 5/8" 7/8" 40 0.23 80262 1-1/4'x 1-1/4"x 1" 3/4" 3/4" 7/8" 40 0.26 Z 80138 1-1/4"x 1-1/4"x 1-1/2" 1" 1" 1" 80 0.43 BEMs T/0 80140 1-1n"x 1-1/4"x3/4" 9/16' 9/16" 1" 80 0.36 ��i 80141 1-112"x 1-1/4"x l" 9116" 9/16" 1-1/16" 80 0.38 .��1. 80263 1-1/2"x 1-1n"x3/4" 9/16" 9/16" 1" 80 0.36 X..•-Y 80264 1-1/2"x 1-1/2"x 1" 9/16" 9/16" 1-1/16" 80 0.38 �����I'�" 80275 1-1/2'x 1-1/2"x 1-1/4" 7/8" 7/8" 1" 80 0.45 TIO •• T/O 80265 2"x 2'x 3/4" 3/4" 3/4" 1-3/8" 80 0.61 80266 2"x 2"x 1" 7/8" 7/8" 1-3/8" 80 0.66 80274 2"x 2"x 1-1/4" 1-1/16" 1-1/16" 1-3/8" 80 0.74 80267 2"x 2"x 1-1/2" 1-1/8" 1-1/8" 1-3/8" 80 0.78 80271 2-1/2"x 2-1/2"x 1" 1-9/16" 1-9/16" 1-9/16" 80 1.43 80272 2-1/2"x 2-1/2"x 1-1/4" 1-9/16" 1-9/16" 1-9/16" 80 1.46 80273 2-1/2"x 2-1/2"x 1-1/2" 1-9/16" 1-9/16" 1-9/16" 80 1.48 80276 2-1/2"x 2-1/2"x 2" 1-9/16" 1-9/16" 1-9/16' 80 1.50 80270 3"x 3"x 1-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.28 80268 3"x 3"x 2" 1-13/16" 1-13/16" 1-3/4" 80 2.25 80269 3"x 3"x 2-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.44 CROSS&REDUCING CROSS 80009 3/4" 9(16" 40 0.13 80010 1' 11/16" 40 0.23 Mt T/0 80011 1-114" 15/16" 40 0.34 .AO MI 80012 1-1/2" 1-1/16" 80 0.67 -EM.. 80013 2" 1-5/16" 80 1.00 ■r 1v=== 80014 2-1/2" 1-9/16" 80 1.91 I.,il T/0 80008 3" 1-13/16" 80 2.89 T/0 ■■ T/0 80015 1"x 1"x 3/4"x 3/4" 7/8" 40 0.28 80025 3/4" 5/8" 40 0.09 90°ELBOW& 80026 1" 3/4" 40 0.14 REDUCING ELBOW 80027 1-114" 7/8" 40 0.21 X 80028 1-1/2" 1-1/16" 80 0.40 I.,/ T/0 80029 2" 1-5/16" 80 0.79 1. . 80030 2-1/2" 1-9/16" 80 1.14 MIN= 80031 3" 1-13/16" 80 1.82 941,111M Y XxY X Y - -T/0 80032 1"x 3/4" 11/16" 13/16" 40 0.16 FIGURE 2-FITTING DIMENSIONS(Part 1 of 4) Page 4 of 6 TFP1915 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT TYPE NUMBER (-1/0) (lb.) • 45°ELBOW 80050 314" 3/8" 40 0.08 i T/O- - 80051 1" 3/8" 40 0.11 �� 80052 1-1/4" 3/4" 40 0.20 �r_ 80053 1-1/2" 1/2" 80 0.31 �'��: 80054 2" 3/4" 80 0.56 T/O ♦S �ii1� 80055 2-1/2" 13/16" 80 0.89 80056 3" 1" 80 1.19 80075 3/4" 1/8" 40 0.07 COUPLING& 80076 1" 1/8" 40 0.11 REDUCING COUPLING 80077 1-1/4" 3/16" 40 0.12 80078 1-1/2" 3/16" 80 0.25 2" 3/16" 80 0.38 I ii80079 80080 2-1/2" 1/4" 80 0.67 80081 3" 3/16" 80 0.91 -T/O _ 80220 1"x 314" 1/8" 40 0.08 80200 1"x 3/4" 7/16" 40 0.04 80201 1-1/4"x 3/4" 1/2" 40 0.11 80202 1-1/4"x 1" 5/16" 40 0.12 80203 1-1/2"x 3/4" 5/8" 80 0.16 80204 1-1/2"x 1" 1/2" 80 0.14 REDUCER BUSHING 80205 1-1/2"x 1-1/4" 3/8" 80 0.17 80206 2"x 3/4" 13/16" 80 0.27 ' 80207 2"x 1" 11/16" 80 0.26 80208 2"x 1-1/4" 9/16" 80 0.24 80209 2"x 1-1/2" 7/16" 80 0.19 T,O 80215 2-1/2"x 1" 15/16" 80 0.42 80214 2-1/2"x 1-1/4" 13/16" 80 0.45 80213 2-1/2"x 1-1/2" 11/16" 80 0.46 80211 2-1/2"x 2" 5/8" 80 0.29 80210 3"x 2" 3/4" 80 0.72 80212 3"x2-1/2" 1/2" 80 0.47 CAP 80100 3/4" 5/16" 40 0.04 80101 1" 3/8" 40 0.06 .9,• 80102 1-1/4" 7/16" 40 0.10 le) 80103 1-1/2" 11/16" 80 0.20 _- 80104 2" 5/8" 80 0.31 T/O- - 80105 2-1/2' 7/8" 80 0.58 80106 3" 1" 80 0.88 GROOVED T/O PIPE O.D. COUPLING ADAPTER 80160 1-1/4"x 1-1/4"Groove 2-5/16" 1-1/4"(1.660") 40 0.78 v1/4, , I■ 80161 1-1/2"x 1-1/2"Groove 2-5/16" 1-1/2"(1.900") 80 0.95 1.42 PIPE 80162 2"x 2'Groove 2-5/16" 2"(2.375") 80 O.D. 80163 2-1/2"x 2-112"Groove 2-5/16" 2-1/2"(2.875") 80 2.28 morar...909N- 80164 3"x 3"Groove 2-1/4" 3"(3.500") 80 3.00 -T/O-I 80169 2-1/2"x 76,1 mm Groove 2-5/16" 76,1 mm(3.000") 80 2.28 FIGURE 2-FITTING DIMENSIONS(Part 2 of 4) TFP1915 Page 5 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT TYPE NUMBER (T/O) (lb.) SPRINKLER HEAD 11 ADAPTER _ 80175E 3/4"x 1/2"NPT 7116" 80 0.20 � " 80176E 1"x 1/2"NPT 7116" 80 0.22 U 80175WL 3/4"x 1/2"NPT 7/16" 40 0.16 —44i 80179 1"x 3f4"NPT 13/16" 40 0.43 . — T/0 SPRINKLER HEAD ADAPTER „,,t", 80175W 3/4"x 112"NPT 1/2" 40 0.19 Y 80176W 1'x 1/2"NPT 1/2" 40 0.18 — T/O SPRINKLER HEAD ADAPTER(SPIGOT) 80177L 314"x 1/2"NPT 1/2" 40 0.16 MIUUU 80178 1"x 1/2"NPT 9/16" 40 0.20 TilX:• 80180 1"x 3/4"NPT 7/8" 40 0.40 -I T/O FEMALE ADAPTER Arampurxf \\\\ 80142 3/4"x3/4"NPT 13/16" 40 0.41 80145 1'x 1"NPT 7/8" 40 0.63 80146 1-1/4"x 1-114"NPT 1-1/8" 40 1.03 80147 1-1/2"x 1-1/2"NPT 1-3/8" 80 1.42 80148 2"x 2"NPT 1-11/16" 80 2.66 — —T/O MALE ADAPTER 80157 3/4"x3!4'NPT 1-5/16" 40 0.33 80158 1'x 1"NPT 1-3/8" 40 0.56 iii �i.3 —T/O-I XxYxZ X Y Z SPRINKLER HEAD 80250 3/4"x 3/4"x 1/2"NPT 9/16" 9/16" 1" 40 0.22 ADAPTER TEE Z 80251 1"x 1"x 1/2"NPT 11/16" 11/16" 1-3/16" 40 0.29 ;_• , T/O 80249 1"x 1"x 1"NPT 15/16" 15/16" 1-9/16" 40 0.73 1`� ��) I 80256 1-1/4"x 1"x 1/2"NPT 7/16" 9/16" 1-5/16' 40 0.30 =- 11 ..- 80252 1-1/4"x 1-1/4"x 1/2"NPT 7/16" 7/16" 1-5116' 40 0.31 X _MI—Y 80257 1-1/2"x 1-1/4"x 1/2"NPT 1/2" 11/16" 1-7/16" 80 0.43 ...........40........• 80254 1-1/2"x 1-1/2"x 1/2"NPT 1/2" 1/2" 1-7/16" 80 0.46 T/O •• T/0 80258 2"x 1-1/2"x 1/2"NPT 1/2" 5/8" 1-11/16" 80 0.56 80253 2"x 2'x 1/2'NPT 1/2" 1/2" 1-11/16" 80 0.62 I FIGURE 2—FITTING DIMENSIONS(Part 3 of 4) Page 6 of 6 TFP1915 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT • TYPE NUMBER (T/O) (lb.) 1 BACK-TO-BACK TEE X x Y x 2 X Y,2 X ii T/O Y••=0,2 ''" 80459 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.48 111111= IMMIIIIII 80460 1"x 1/2"NPT x 1/2"NPT 5/8" 1-3/16" 40 0.46 T/O TIO BACK-TO-BACK CROSS X x Y x Z x W X,Y Z W X 111 T/O Z I ' �IIIII IIIII " ��iniI III w 80462 1 x 1 x 1/2 NPT x 1/2"NPT 5/8" 1-3/16" 40 0.46 •-%.9 .�'— 80463 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.47 I/O T/0 T/O SPRINKLER HEAD X x Y X Y ADAPTER 90°ELBOW Y 't I/O r� l 80199 3/4"x 1/2"NPT 9/16" 1" 40 0.20 80198 1"x 1/2"NPT 3/4" 1-1/4" 40 0.26 0.• _X 80196 1'x 3/4'NPT 1-1/16" 1-7/16" 40 0.26 4r`�■•■ T/O FIGURE 2—FITTING DIMENSIONS(Part 4 of 4) by TFBP to be defective shall be either of merchantability and fitness for a par- Limited repaired or replaced, at TFBP's sole ticular purpose. Warranty option. TFBP neither assumes, nor This limited warranty sets forth the ex- authorizes any person to assume for it, clusive remedy for claims based on any other obligation in connection with failure of or defect in products, materi- Products manufactured by Tyco Fire& the sale of products or parts of prod- als or components, whether the claim Building Products (TFBP) are war- ucts.TFBP shall not be responsible for ranted solely to the original Buyer for sprinkler system design errors or inac- is made in contract, tort, strict liability ten(10)years against defects in mate- curate or incomplete information sup- or any other legal theory. rial and workmanship when paid for plied by Buyer or Buyer's repre- This warranty will apply to the full ex- and properly installed and maintained sentatives. tent permitted by law.The invalidity,in under normal use and service. This whole or part, of any portion of this warranty will expire ten (10) years In no event shall TFBP be liable, in warranty will not affect the remainder. from date of shipment by TFBP. No contract, tort, strict liability or under warranty is given for products or corn- any other legal theory, for incidental, ponents manufactured by companies indirect,special or consequential dam- not affiliated by ownership with TFBP ages,including but not limited to labor or for products and components which charges, regardless of whether TFBP 0 have been subject to misuse,improper installation, corrosion, or which have was informed about the possibility of such damages, and in no event shall not been installed, maintained, modi- TFBP's liability exceed an amount fled or repaired in accordance with ap- equal to the sales price. plicable Standards of the National Fire The foregoing warranty is made in lieu Protection Association, and/or the of any and all other warranties. ex- standards of any other Authorities . - . '1111 '-. .. ..1. -. '- Having Jurisdiction. Materials found TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 ® TOLCS www.tolco.com Il„,,, NIBCO Revision 5/24/2001 Fig. 27 & 27A ®E®k • "Stand-Off" Hanger/Restrainer for CPVC Plastic Pipe � ., Size Range— 3/4" and 1" CPVC Plastic Pipe*. =' Material —Carbon Steel, Pre-Galvanized L. Function—Designed to be used as a hanger/restrainer**for CPVC piping : . where the"stand-off"design will ease installation by eliminating the need for �. wood blocking. r �� =� " . Features: �. - • Flared edge design protects CPVC from any rough or abrasive surfaces. i .. • Snap-in retainers hold pipe firmly in place during installation. • The"Stand-Off"design eliminates the need for wood block extension. Fig. 27 • Can be installed on horizontal or vertical piping regardless of mounting surface orientation. • Attaches easily to wood structure with two hex head self-threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16" sockets, v eliminating impact tool damage to pipe. i 0 Approvals—Underwriters'Laboratories Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. Meets and exceeds the Fig. 27A requirements of NFPA 13, 13R and 13D. • -`' ., Important Note**—When installed in slot opening on Fig.27, Fig.27A provides additional stability and satisfies the UL vertical restraint requirement where needed. Order By— Fig. 27: By figure number and CPVC pipe size i Fig.27A: By figure number and CPVC pipe size US and International Patent application in process. 41416 ' ' - - *For other sizes, consult factory. Fig.27 and Fig.27/27A have also been tested by UL mounted on 3/8" -_ composite wood web material (such as TJI Series/Trus Joist MacMillan) Fig. 27/Fig. 27A without the use of back-up wood blocking. When using Fig.27 and 27A in combination on 3/8"web to satisfy the UL requirement for vertical restraint, FIG.27 install two reinforcing speed nuts (Fig.27B). Fig.27B is UL Listed only when WJFIG 27A used with TOLCOrm products. FIG 278 FIG.27 y W/FIG.27A i e I . I --1 41 1k .J 1 1 ill ,- FIG.27 - F1G 27 i 3 - FIG.27 FIG27 W'FIG 27A 1 FIG.27 , MIL. t, Typical Applications 1111 Main Office/Manufacturing Facility•1375 Sampson Ave.•Corona,CA 92919•Phi 909.737.5599•Fax: 909.737 0330 Customer Service•800.786.5266 www.tolco.com I Dyna-Thread® - M-COAT® Submittal Data Sheet 1) • O Full Line Sch-40 Replacement Dyna-Thread—M-COAT Specifications Dyna-Thread'"'-M-Coat' sprinkler pipe represents an engineering NPs Nominal I.D. Wt. Wt.(H20 Filled) CRR CRR - advancement for the sprinkler pipe industry.It combines the safety In;mm In;mm Lbs/Ft kg/m Lbs/Ft;kg/m Unthreaded Threaded and longevity of traditional Sch-40 pipe with quality and superior 1" 1.080 1.330 1.75 11.39 1.00 — - hydraulic advantages. 25 27.4 2.0 2.60 11/4" 1.408 1.870 2.54 9.50 1.00 O Comparison to Schedule 40 32 35.8 2.8 3.78 — — 1'h" 1.639 2.290 3.22 9.14 1.00 Dyna-Thread'-M-Coat'inside diameter is up to 3.6%larger than Sch-40 40 41.6 3.4 4.79 — - giving it superior hydraulics.Also,when used in combination with Dyna- 2° 2.104 3.050 4.57 8.41 1.00 Flow-M-Coat pipe,down sizing often occurs.Dyna-Thread is fully listed and 50 53.4 4.5 6.80 - - approved UL,ULC,and FM for fire sprinkler applications.The life expectancy of Dyna-Thread-M-Coat and Sch-40 are equal based on the calculated wall 0 c® 41:■ thicknesses per UL.The consistent quality of steel used to make Dyna-Thread- APPROVED M-Coat facilitates smooth threading and lower maintenance costs.The exterior of Dyna-Thread-M-Coat is protected by a clean,durable mill coating for O American Made extended shelf life and easy paint application.With its increased strength Manufactured at one of 3 U.S.Facilities and is available and lighter weight, Dyna-Thread-M-Coat reduces installation fatigue and through distributors in the USA,Canada,Mexico,and is ideal for retro-fit applications.Corrosion Resistance Ratio(CRR)is a UL Latin America. (Underwriters Laboratory)term for the estimated life expectancy of a pipe joint. This is based on the calculated wall thickness at the base of the first exposed ®Specifications & Approvals thread,assumed to be the weakest point of the pipe length.Dyna-Thread- M-Coat and Sch-40 have the same calculated wall thicknesses at this point Dyna-Thread-M-Coat pipe is manufactured to meet:ASTM A and are both assigned the same CRR of 1.00. 135,Type E Grade A,and is in compliance with NFPA-13.All sizes of Dyna-Thread-M-Coat are rated at 300 psi working ® Comparison to L.W.T. Pipe pressure.Dyna-Thread-M-Coat is UL and ULC Listed for wet, More wall thickness at the thread(CRR=1.00)gives Dyna-Thread-M-Coat dry and pre action sprinkler systems and FM Approved for better life expectancy than lightwall threadable pipe joints.Dyna-Thread- use in wet systems.Dyna Thread-M Coatis approved for all M-Coat is approved for standard hanger spacing(15 ft.O.C.),can be used as threaded couplings and welded outlets and is suitable for all earthquake sway bracing,and is safe to use as drops.Dyna-Thread-M-Coat roll grooved,and plain end fittings.(See listing information). is safer to weld on than many zinc coated lightwall threadable pipe products. Dyna-Thread-M-Coat is more widely accepted than lightwall threadable where Sch-40 is specified. Project: Sprinkler Contractor: Date: Engineer: Specification Reference: System Type: Locations: Comments: ^`allied Customer Service:(800)882-5543 Fax:(800)659-7730 www.alliedtube-sprinkler.corn l ) • 16100 S Lathrop Ave • 11350 Norcom Rd. • 2525 N 27th Ave. TUBE&//CONDUIT• Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009 --15P!, 02013 Atkore International,Inc.All Rights Reserved.STP-S3-4M-1301 Model 1000 0 A T TESTAN D RAI N. , F Sectional Floor Control Test and Drain Valve c L us �P® 3/411 1" 1h/41 11/211 2" r- -= WP TEST 3 ' 1!2 Ice ` k !a --. ./ PUS ` o 1 TESTANDRAIN` MOM 110G '• f C ' 1wa CN i DRAIN FITTING-SPOIAL ma O @T® LIB t „ s p AGF MIS lee..Malvern.M. "` ' ' f - "' 1,i,r F .. SIZE 1-1/4"IN MODEL f •The AGF Manufacturing Inc. Model 1000 TESTANDRAIN' MODEL 1000— FRONT VIEW,VERTICAL INSTALLATION provides both the test function and the express drain function for a wet fire sprinkler system. •The Model 1000 complies with the requirements of 1 FROM BRANCH NFPA-13, NFPA-13R, and NFPA-13D. il•The Model 1000 TESTANDRAIN®is a compact single SYST�ACCESS PORT handle ball valve which includes a tamper resistant test MN orifice and integral tamper resistant sight glasses, and is 300 PSI rated. I• " •'' •Available in a full range of sizes from 3/4"to 2" NPT and r It®' BSPT, with all specifiable orifice sizes 3/9" (2.8K), 'As" (4.2K), STREET EL cam 1h" (5.6K), 17/32" (8.0K), 5/s" (11.2K, ELO), 3/a' (14.0K, ESFR), cam and K25 as required by NFPA 13,2007 Edition(see reverse). 1MM1 •The orifice size is noted on the indicator plate and the valve • features a tapped and plugged port for system access. STREET E/.I%I�'f TO DRAIN •A locking kit is available and can be ordered with the valve OR PIPE 1 I to provide vandal resistance or prevent unintentional alarm 'z activation. TO DRAIN j • Repair kits including (1) adapter gasket, (1)ball, (2)valve i seats, (1)stem packing, and(1)stem washer are available for all TESTANDRAIN®valves.Valve and orifice size must RIGHT HAND/STRAIGHT INSTALLATION be specified when ordering. Reliability, Versatility, Code Compatibility TESTANDRAIN is a registered trademark of AOF Manufacturing Inc. CS1000 10/09 Model 1000 I AcL us F TESTAN D RAI N. APPROVIM 300 PSI Bronze Ball Valve MODEL 1000 - PLAN VIEW FRONT VIEW - HORIZONTAL INSTALL . A r Ems! O • NMI 1/2"NPT SYSTEM I • U� ACCESS PORT \/ . TO DRAIN TO DRN � ` ~ N IJ • PIC mil 1 LITa J G - 1 -- 1- -- .' . 1 DIMENSIONS MATERIALS Orifice Size Available:3/8",7A6", 1/°,77/32", ELO(5/8")*, ESFR(3/4")*,&K25** Handle:Steel Stem:Rod Brass SIZE A B C D E F G H Ball: C.P.Brass 'A" 51/16" 11/2" 23/46" 35/2" 33/8" 113/16" 43/46" 63" Body: Bronze (128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) Valve Seat: Impregnated Teflon® 51/16" 11/2" 23/16" 35/8" 34" 113/46" 43/46" 61/8" Handle Plate:Steel 1 ' (128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) Handle Stop:Steel 11/4" 506" 111A6" 29/16" 41/4" 3316" 113/46" 536" 51/2" APPROVALS (163 mm) (43 mm) (65 mm) (108 mm) (83 mm) (51 mm) (141 mm) (192 mm) UL and ULC Listed (EX4019) 11h.. 67A6" 113/46" 31/4" 51/16" 37%" 25/6" 81/4" 107/8" FM Approved (163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm) NYC-BSA No.720-87-SM 67/16" 113/46" 31/4" 51/16" 31/2" 25/2" 81/4" 107/8" 2" (163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm) f^,Rf Available on 11/4"to 2" size units only `"'' ""Available on 11/2" and 2"size units only `, THE MODEL 1000 PROVIDES ALL OF THE FOLLOWING... MADE IN U.S.A. From the 2007 Edition of NFPA 13 Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system. Chapter 8.16.2.4.2 Drain connections,interior sectional or floor control valve(s)-shall be provided with a drain &8.16.2.4.3 connection having a minimum size as shown in Table 8.16.2.4.2. Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the drain. Chapter A.8.17.4.2 (Wet Pipe System)test connection is permitted to terminate into a drain capable of accepting full flow... using an approved sight test connection containing a smooth bore corrosion-resistant orifice giving a flow equivalent to one sprinkler... Chapter 8.17.4.2.2 The test connection valve shall be readily accessible. Chapter 8.17.4.2.4 shall be permitted to be installed in any location...downstream of the waterflow alarm. Chapter 8.17.4.3.1 (Dry Pipe System)a trip test connection not less than 1" in diameter,terminating in a smooth bore corrosion-resistant orifice,to provide a flow equivalent to one sprinkler... Chapter 8.17.4.3.2 The trip test connection...with a shutoff valve and plug not less than 1",at least one of which shall be brass. USA Patent # 4741361 and Other Patents Pending I AGF Manufacturing Inc. Job Name: ° C 100 Quaker Lane,Malvern,PA 19355 Phone:610-240-4900 Architect: FFax:610-240-4906 Engineer: www.testandrain.com Contractor: P POTTER FOR SMALL PIPE VSR-S VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD UL,ULC,CSFM Listed and NYMEAAccepted Service Pressure: Up to 300 PSI(20,7 BAR) Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)UL Maximum Surge: 18 FPS(5,5 m/s) Enclosure: Die-cast,red enamel finish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT(Form C) " 10.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Resistive 10mAmps min.at 24 VDC Conduit Entrances:Two openings provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed plastic,copper and schedule 40 iron pipe. Fits pipe sizes-1"(25mm), 1 1/4"(32mm),1 1/2"(38mm) and 2"(50mm) Stock No. 1144440 Note:12 paddles are fiuntished with each unit,one for each pipe size of threaded and sweat TEE,one for 1"(25mm)CPVC, one for 1"(25mm)CPVC(Central),one for 1"threaded Nibco wA G CPVC,and one for 1 1/2"(38mm)threaded(Japan). R(V.N Environmental Specifications: •mE � tit •NEMA-4/1'54 Rated enclosure suitable for indoor or outdoor Installation must be perfomed by qualified personnel and in use with factory installed gasket and die-cast housing when used accordance with all national and local codes and ordinances. with appropriate conduit fitting. Shock hazard. Disconnect power source before servicing. • Temperature range:40°F to 120°F,(4,5°C to 49°C)UL Serious injury or death could result. Service Use: Risk of explosion. Not for use in hazardous locations. Serious Automatic Sprinkler NFPA-13 injury or death could result. One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional:Cover Tamper Switch Kit,Stock No.0090148 (See Fig.7 for terminations) Replaceable Components:Retard/Switch Assembly,stock no.1029030 The Model VSR-S is a vane type waterflow switch for use on wet Installation sprinkler systems that use 1"(25mm),11/4"(32mm),11/2"(38mm)or 2" These devices may be mounted in horizontal or vertical pipe. On (50mm)pipe size.The unit may also be used as a sectional waterflow horizontal pipe they should be installed on the top side of the pipe where detector on large systems. they will be accessible.The units should not be installed within 6"(15cm) The unit contains two single pole double throw snap action switches and of a valve,drain or fitting which changes the direction of the waterflow. an adjustable, instantly recycling pneumatic retard.The switches are Select the proper paddle for the pipe size and type of TEE used see Fig. actuated when a flow of 10 gallons per minute(38 LPM)or more occurs 1 for instructions on changing paddle.The unit has a 1"NPT bushing downstream of the device.The flow condition must exist for a period of for threading into a non-corrosive TEE.See Fig.2 for proper TEE size, time necessary to overcome the selected retard period. type and installation.Use no more than three wraps of teflon tape. Enclosure Screw the device into the TEE fitting as shown in Fig.2.Care must be The VSR-S switches and retard device are enclosed in a general purpose, taken to properly orient the device for the direction of waterflow. die-cast housing.The cover is held in place with two tamper resistant The vane must not rub the inside of the TEE or bind in any way.The screws which require a special key for removal.A field installable cover stem should move freely when operated by hand. tamper switch is available as an option which may be used to indicate The device can also be used in copper or plastic pipe installations with unauthorized removal of the cover. See bulletin number 5401103 for the proper adapters so that the specified TEE fitting may be installed installation instructions of this switch. on the pipe run. Note:Do not leave cover off for an extended period of time. f Potter Electric Signal Company,LLC•2081 Craig Road.St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1 833•www.pottersignaLwm PRINTED IN USA MFG.#5401206-REV G PAGE 1 OF 3 12/08 FOR SMALL PIPE V SR—S p PoriER VANE TYPE WATERFLOW 9 The Symbol of Protection ALARM SWITCH WITH RETARD 1 Fig.1 Fig.2 Retard Adjustment DO NOT LEAVE COI.ER OFF FOR EXTENDED PERIOD OFTIME ry 4341 A The time delay is factory set at 30±10 seconds. ro�TA*�SWITCH aunt,Am" The delay can be adjusted by rotating the retard -� -. J � adjustment knob from 0 to the max setting(60- \./y�'t*!� I l D°TR/ I 90 seconds).The time delay should be set at the �,�I t°I! P. ilk,' 1 011.•».,3 minimum required to prevent false alarms. " J \ '',�/�1 ' Screw the device into the tee fitting as shown. <.r. w I�`,�'i,-��� Care must be taken to properly orient the s_ " DItECTIOD'OF 1 I 11•'•w./�"... WATER FLOW MOUNT w \',rl1r` device for the direction of waterflow.On sweat ARROW ON BcsTlnac rotNTS �,. = � tees,no threaded bushings,inserts,or adapters / W DIRE TR)N OF � WArEAFLJw ;` are permitted,unless they comply with the _ dimensions listed in the chart below. DWG.Al-31 THREADED u Important-The depth to the inside bottom of FITTING ON ' the tee should have the following dimensions: " AWARNING F11OT S ALL a RUN OF THE TIE ii� approximate Depth Regmrement MAYBE ^� There are 12 paddle furnished with each unit THREADED OP \ .1 Tee Sire Threaded Sweat CPVC SWEAT PIPE One for each size of threaded,sweat or plastic I'x I'x I" 2 1/16' 13/4' 2 7/16' ( TEE as described in Fig 2.These paddles have DIRECTION OF , WATERFLOW ,,, I 1 V-x 1 U4-x I' 2 1/16' 2 7/16- WA raised lettering that shows the pipe size and type Vi' ' awe.Reaea 112'x 1 1/r x 1' 211n6• 2 1/4' N A ofTEE that they are to be used with.The proper 2"x 2'x 1" 3 3/16' 2 3/4" N paddlemustbeused.Thepaddlemustbepiuyei ly Shown with optional Cover Tamper Switch Kit. attached(see drawing)and the screw that holds the paddle must be securely tightened. Do not use more than three , -_ _ • wraps of teflon tape. Fig.3 Switch Terminal Connections Clamping Plate Terminal Fig.7 Cover Tamper Switch Wiring (Shown with cover in place) '" ! WARNING \;- An uninsulated section of a single conductor should not be looped � around the terminal and serve as two separate connections.The wire CI osoce D.a„e,., must be severed,thereby providing supervision of the connection in C N.O. N.C. the event that the wire become dislodged from under the terminal. ( T) (RED) (ELK) Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. DWG,8310018-2 Fig.4 Typical Electrical Connections Fig.5 Fig.6 To remove knockouts: Breakout thinsection ofcoverwhen wiring NEGLADCJA Place screwdriver at edge of both switches from one conduit entrance. _ � .—.'a - +: knockouts,not in the center. �_� - POT AC DC OR HOT _.a it I•._ �U_ -1 1 Il�la• ll .' / 4 I • • IN `. . ?- it- wATERFLOw ZONE ON r,...... 411111. 1 \011k.� a ®`— .+; FIRE PANEL • Notes: /� / -40117-/ 1. The Model VSR S has two switches,one can be used to operate a `�� + central station,proprietary or remote signaling unit,while the other ��® { is used to operate a local audible or visual annunciator. 2. For supervised circuits see"Switch Terminal Connections"drawing 4 ..pA r and caution note(Fig.3). PRINTED IN USA MFG.#5401206-REV G PAGE 2 OF 3 12/08 P P O' fER FOR SMALL PIPE VSR-S VANE TYPE WATERFLOW 0 The Symbol of Protection ALARM SWITCH WITH RETARD Testing Removal The frequency of inspection and testing for the Model VSR-S and its • To prevent accidental water damage,all control valves should iassociated protective monitoring system should be in accordance with be shut tight and the system completely drained before waterflow applicable NFPA Codes and Standards and/or the authority having detectors are removed or replaced. jurisdiction(manufacturer recommends quarterly or more frequently.) • Turn off electrical power to the detector,then disconnect wiring. Aninspector'stestvalve(usuallylocatedattheendofthemostremotebranch • Use a wrench on the flats of the bushing.Turn the switch line)should always be used for test purposes.If there are no provisions for counterclockwise to disengage the pipe threads. testing the operation of the flow detection device on the system,application • Gently lift with your fingers,roll the vane so it will fit through the of the VSR-S is not recommended or advisable. bole while continuing to lift the waterflow detector. A minimum flow of 10 gpm(38 Lpm)is required to activate this device. • Lift detector clear of pipe. NOTICE Please advise the person responsible for testing of the A CAUTION fire protection system that this system must be tested in accordance with the testing instructions. Waterflow switches that are monitoring wet pipe sprinkler systems Maintenance shall not be used as the sole initiating device to discharge AFFF, Inspect detectors monthly for leaks. If leaks are found, replace the deluge,or chemical suppression systems.Waterflow switches used detector.The VSR-S waterflow switch should provide years of trouble- for this application may result in unintended discharges caused free service.The retard and switch assembly are easily field replaceable. by surges,trapped air,or short retard times. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock#1029030.There is no maintenance required,only periodic testing and inspection. Mounting Dimensions 3.50" - 5.56" GROUND SCREWS (89.0 mm) (141.2 mm) A 0 2.00" f 4P:!U'•� (50.8 mm)) IL II ��, f ._1, L. i i_,i I I e _il 234 WI (59.4 mm) alai 4.89" j 0;,'' v - — (52.3 mm) i • *TM!hi . U. atm II „... .1., i .r. 0 1"-111/2NPT NI DWG4 1206-5 • I PRINTED IN USA MFG.#5401206-REV G PAGE 3 OF 3 12/08 ES-A-2000B Series 2000B A M E s Double Check Valve Assemblies FIRE&WATERWORKS Sizes: 1/2" -2" (15-50mm) ; Features • Ease of maintenance with only one • cover 2"2000B HC • Top entry (50mm) • • Replaceable seats and seat discs — �. • Modular construction • Compact design - • '/z'—2" (15—50mm)Cast bronze body construction • Top mounted ball valve test cocks a/4"2000B • Low pressure drop (gym) • No special tools required Series 2000B Double Check Valve Assemblies shall be installed at referenced cross- • '/z"—1" (15—25 mm)have connections to prevent the backflow of polluted water into the potable water supply. tee handles Only those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation,frequency Available Models of testing or other installation requirements. Suffix: These valves meet the requirements of ASSE Std. 1015 and AWWA Std.C510 and are B- Quarter turn ball valves approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. LBV- less ball valves SH- stainless steel ball valve handles Specifications HC 21/2" inlet/outlet fire hydrant fitting A Double Check Valve Assembly shall be installed at each noted location.The assembly (2"valve) shall consist of two positive seating check modules with captured springs and rubber seat discs.The check module seats and seat discs shall be replaceable.Service of all internal components shall be through a single access cover secured with stainless steel bolts. Pressure — Temperature The assembly shall also include two resilient seated isolation valves and four top mounted, Temperature Range:33`F—140°F resilient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 (0.5°C—60°C) and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.Assembly shall be an Ames Maximum Working Pressure: 175psi Company Series 2000B. (12.1 bar) Approvals 4�pSSIp4 Standards 0 AW ® eke WA Std.C510,IAPMO PS31 5E c C ® US us 1015 864.5 1/4"-2" (LBV Models Only) Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. LBV models not listed. Horizontal and vertical"flow up"approval on all sizes. Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Dimensions -Weights • A �, M es w le '-4_ ., 117_ 0 �_ 0 w -�� F 1 Suffix HC - Fire Hydrant Fittings dimension "A"=231/2"(594mm) 4--H <--I--► • G SIZE(ON) DIMENSIONS WEIGHT . A B C F G H I in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. • ' 15 10 254 4% 117 2'/As 62 5 127 33/4 85 2%6 59 21,6 52 4.5 2 1/4 20 111/8 282 4 102 3% 79 63/4r, 157 37A6 87 21/6 54 1'/6 33 5 2.3 1 25 131/4 337 5'% 130 4 102 71/2 191 33/4 85 111/6 43 111/16 43 12 5.4 11/4 32 16% 416 5 127 35/ee 84 97: 241 5 127 3 76 2 50 15 6.8 1'/z 40 16% 425 4% 124 31/2 89 93/4 248 5'3/46 148 3% 79 21/,6 68 15.86 7.2 2 50 191/2 495 61/4 159 4 102 131/6 340 61' 156 3'/16 87 2"/A6 68 25.75 11.7 Strainer sold separately Capacities kPa psi A 11/4" (32mm) As compiled from documented Foundation for Cross-Connection Control 96 14 and Hydraulic Research at the University of Southern California lab tests. w 83 12 ATypical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) o 69 10 1/2" (15mm) d 41 6 kPa psi . A N 83 12 a 28 4 O 69 10 a 14 2 0 55 8 0 0 a 28 4 "` AP 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm a i 14 2 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm Cr. 0 0 5 7.5 10 15 fps 0 2 4 6 8 10 12 gpm 1.5 2.3 3.0 4.6 mps AP 0 7.6 15.2 22.8 30.4 38 45.6 Ipm Flow Rate 5 7.5 10 fps 1.5 2.3 3.0 mps kPa psi 11/2" (40mm) Flow Rate 83 12 4 kPa psi 3/4" (20mm) N 69 10 0 152 22 - 0 55 8 J 41 6 124 18 ?28 4 2 96 14 N 14 2 7 i 69 10 0 0 0 N a APO 10 20 30 40 50 60 70 80 90 100 110 120 gpm a 41 6 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 14 2 ."---- 5 7.5 10 15 fps 0 5 10 15 28 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps AP 0 19 38 57 76 95 114 133 152 171 190 Ipm Flow Rate 7.5 15 fps 2.3 4.6 mps kPa psi 2" (50mm) Flow Rate 0 83 12 d kPa psi 1" p 69 10 N 110 16 A 1 (25mm) 55 8 J 83 12 - 41 6 y 69 10 y 28 4 - _ 8 • 55 8 N 41 6 � 14 2 d 28 4 a 0 0 El 14 2 - - 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 Ipm 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm 5 7.5 10 15 fps AP 0 19 38 57 76 95 114 133 152 171 190 209 228 1pm 1.5 2.3 3.0 4.6 mps 5 7.5 10 15 fps Flow Rate 1.5 2.3 3.0 4.6 mps 1 A Flow Rate A M E S \7 • 9001-2008 FIRE&WATERWORKS www.amesfirewater.com LMBf E RT I F I E D • A Watts Water Technologies Company USA: Backflow- Tel:(916)928-0123•Fax:(916)928-9333 Control Valves- Tel:(713)943-0688•Fax:(=13)944-9445 Canada: Tel.(905)332-4090•Fax:(905)332-7068 ES-A-20008 1322 ©2013 Ames Fire&Waterworks