Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE -
The TYCO Series TY-FRB Sprinklers --'=`
Description described herein must be installed and =-
maintained in compliance with this doc-
The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable
Upright(TY313)and Pendent(TY323) standards of the National Fire Protec-
Sprinklers described in this data sheet tion Association,in addition to the stan- `t'
are quick response,standard coverage, dards of any other authorities having
decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair ,` `'.44. ( �_
sprinklers designed for use in light or the performance of these devices. -._ :'.. , -
ordinary hazard,commercial occupan- The owner is responsible for maintain . –
cies such as banks, hotels, and shop- P ;.__- , _ _
ping malls. ing their fire protection system and
devices in proper operating condition.
The recessed version of the Series TY- The installing contractor or sprinkler
FRB Pendent Sprinkler,where applica- manufacturer should be contacted with
ble,is intended for use in areas with a any questions.
finished ceiling.This recessed pendent `
sprinkler uses one of the following: ."C..
• A two-piece Style 15 Recessed Sprinkler =' —
Escutcheon with recessed adjust- Identification (��'
ment up to 5/8 inch (15,9 mm)from /. '� �
the flush pendent position. Number (SIN) .y '"-
. • A two-piece Style 20 Recessed '�
Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT 't•3'
ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT °„
the flush pendent position.
The adjustment provided by the Technical
Recessed Escutcheon reduces the Temperature Rating
accuracy to which the fixed pipe drops Data 135°F(57°C)
to the sprinklers must be cut. 155°F(68°C)
Intermediate level versions of Series Approvals 175°F(79°C)
UL and C-UL Listed 200°F(93 °C)
TY-FRB Sprinklers are described in FM,LPCB,and VdS Approved
286°F(141°C)
Technical Data Sheet TFP357. Sprin- pP
kler guards and shields are described CE Certified Finishes
in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler:Refer to Table A
and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated,
tant Sprinklers. Chrome Plated,or Brass Plated
Maximum Working Pressure Physical Characteristics
175 psi(12.1 bar) Frame Bronze
250 psi(17.2 bar)` Button Brass/Copper
The maximum working pressure of 250 psi Sealing Assembly Stainless
IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON
Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass
Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze
WARNING"that provides cautions K=5.6 GPM/psi"2(80,6 LPM/bar112) Deflector Bronze
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4 FEBRUARY 2014 TFP172
TFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
• 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression
STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
6*6 -
1:iTidE` /'r'i-r -s_
5 ,.f 7/16" Y R—,_.- __•• _-- /
(11,1 mm) , �c
4 NOMINAL ril 2" ) ( 1
MAKE-IN (50,8 mm) �,■
2 P. ` 9, 2" 1-3/8" 17 R 3 W Tr (50,8 mm) �, (34,9 mm) I vir
` WRENCH
y FLATS
1/2'NPT** DEFLECTOR* -- 2-7/8"(73,0 mm)DIA. —
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
�, Operation Installation
WRENCH RECESS
The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor,
expands when exposed to heat.When Upright(TY313)and Pendent(TY323)
(USE ONLY the rated temperature is reached,the Sprinklers must be installed in accor-
END^A") fluid expands sufficiently to shatter the dance with this section.
......1/fr4s-P.
glass bulb, allowing the sprinkler to
activate and water to flow. General Instructions
FIGURE 2 Do not install any bulb-type sprinkler if
W-TYPE 6 the bulb is cracked or there is a loss
SPRINKLER WRENCH Design of liquid from the bulb.With the sprin-
kler held horizontally,a small air bub-
• WRENCH Criteria ble should be present. The diameter
of the air bubble is approximately 1/16
;ECI.E.SS The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and
Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C)
Spr inklers are intended for fire protec- temperature ratings.
it
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or by applying Approval agency(such as, UL Listing min-
imum to maximum torque of 7 to 14
`r is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels
�.., 13, and FM Approval is based on the of torque can distort the sprinkler Inlet
requirements of FM's Loss Prevention with consequent leakage or impairment
PUSH WRENCH Data Sheets).Only the Style 15 or Style of the sprinkler.
IN TO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for
ENGAGEMENT P com P
WITH SPRINKLER for recessed pendent installations. insufficient adjustment in the Escutch-
WRENCHING AREA eon Plate by under-or over-tightening
the sprinkler. Re-adjust the position of
FIGURE 3 the sprinkler fitting to suit.
W-TYPE 7 RECESSED
" SPRINKLER WRENCH Upright and Pendent Sprinklers
•
The Series TY-FRB Upright and Pen-
dent Sprinklers must be installed
• in accordance with the following
instructions.
Step 1.Install Pendent sprinklers in the
pendent position.Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
TFP172
Page 3 of 4
Step 3. Tighten the sprinkler into the 2-7/8"DIA.
sprinkler fitting using only the W-Type (73,0 mm)
6 Sprinkler Wrench(Figure 2).With ref-
erence to Figure 1, apply the W-Type 6 2-1/4'DIA.
Sprinkler Wrench to the wrench flats. FACE OF ~ (57,2 mm) —'
Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER
19,0 Nm). FITTING 5/8"(15,9 mm)
Recessed Pendent Sprinklers 1 \ - FLUSH
The Series TY-FRB Recessed Pendent —� 1 I
Sprinklers must be installed in accor- 3/±7.916•
. dance with the following instructions. (9,517,9 mm) '=% }
Step A.After installing the Style 15 or MOUNTING �_� 1/8" J I
Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm)
• kler threads, and with pipe-thread ----- —
sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8°(34,9 mm)
hand-tighten the sprinkler into the TY-FRB PLATE 3/4"(19,1 mm)
sprinkler fitting.
Step B.Tighten the sprinkler into the FIGURE 4
Step B. fitting using sprinkler
the in T e SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
g g y yp WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
7 Recessed Sprinkler Wrench (Figure RECESSED ESCUTCHEON
3).With reference to Figure 1,apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque 2-7/8'DIA.
—
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73.0 mm)
Nm). FACE OF
Step C.After ceiling installation and fin- SPRINKLER �_2-1/4°DIA.
fishing,slide on the Style 15 or Style 20 FITTING (57,2 mm)
Closure over the Series TY-FRB Sprin- 5/16±1/4" 1/2"(12,7 mm
kler and push the Closure over the (7,9±6,4 mm) ( mm)
Mounting Plate until its flange comes in + FLUSH
contact with the ceiling.
�1 ,� I
Care and I I " _ t
MOUNTING 1/8° J
Maintenance SURFACE -� (3,2 mm)
The TYCO Series TY-FRB,5.6 K-factor, ---' I
Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
Sprinklers must be maintained and ser- TY-FRB PLATE 7/8''(22,2 mm)
viced in accordance with this section. FIGURE 5
Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
work on the fire protection system RECESSED ESCUTCHEON
that it controls, obtain permission to
shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav-
systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing
and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer
affected by this action. have not operated, should be replaced regarding any questions.
Absence of the outer piece of an if they cannot be completely cleaned
p by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec-
escutcheon, which is used to cover
by brushing it with a soft bristle brush. ommended to be inspected, tested,
a clearance hole, can delay sprinkler y g and maintained by a qualified Inspec-
operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local
The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes.
klers are not used for hanging any after installation.Sprinklers damaged
objects and that the sprinklers are only by dropping, striking, wrench twist/
cleaned by means of gently dusting slippage,or the like,must be replaced.
with a feather duster;otherwise, non- Also, replace any sprinkler that has a
operation in the event of a fire or inad- cracked bulb or that has lost liquid from
vertent operation may result. its bulb.(Ref.Installation Section.)
Sprinklers which are found to be leak- The owner is responsible for the
ing or exhibiting visible signs of corro- inspection,testing,and maintenance of
sion must be replaced. their fire protection system and devices
in compliance with this document,as
Automatic sprinklers must never be well as with the applicable standards
• painted, plated, coated, or other- of the National Fire Protection Associa-
wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the
TFP172
Page 4 of 4
P/N* 77 - XXX - X - XXX
SPRINKLER TEMPERATURE
FINISH RATINGS
SIN 1 NATURAL BRASS 135 135°F(57°C)
370 5.6K UPRIGHT(1/2"NPT) TY313 g PURE WHITE(RAL9010°° 155 155°F(68°C)
POLYESTER
371 5.6K PENDENT(1/2"NPT) TY323 q SIGNAL WHITE(RAL9003)
POLYESTER 175 175°F(79°C)
•Use suffix"1°for ISO 7-1 connection: 9 CHROME PLATED 200 200°F(93°C)
for example.77-370-4-175-I
"Eastern Hemisphere sales only 286 286°F(141°C)
TABLE A
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Limited Ordering
Warranty Procedure
For warranty terms and conditions,visit Contact your local distributor for avail-
www.tyco-fire.com. ability.When placing an order,indicate
the full product name and Part Num-
ber(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify:Series TY-FRB Upright or Pen-
dent(specify)Sprinkler,SIN (specify),
K=5.6,Quick Response,(specify)tem-
perature rating, (specify) finish, P/N
(specify,refer to Table A).
Recessed Escutcheon
Specify:Style 15 Recessed Escutcheon
with(specify')finish,P/N(specify')
Specify: Style 20 Recessed Escutch-
eon with(specify)finish,P/N(specify*)
Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
Copyright®2014 Tyco Fire Products,LP. All rights reserved. tgco
TEFLON is trademark of The DuPont Corporation.
Fire Protection Products
tL,CO Worldwide
www.tyco-fire.com
Fire Protection Contacts
Products
Series DS-1 Dry-Type Sprinklers
5.6K Pendent, Upright, and Horizontal Sidewall
Quick Response, Standard Coverage
General The owner is responsible for maintain-
ing their fire protection system and
Description devices in proper operating condi-
tion. Contact the installing contrac-
TYCO Series DS-1 Dry Type Sprinklers, tor or product manufacturer with any
5.6K Pendent, Upright, and Horizontal questions.
Sidewall,Quick Response(3 mm bulb) The Series DS-1 Dry-Type Sprinklers
and Standard Coverage are decora- must only be installed in fittings that
five glass bulb automatic sprinklers meet the requirements of the Design ii
designed for commercial use. Dry-type Criteria section.
sprinklers are typically used where:
• pendent sprinklers are required on dry Sprinkler
pipe systems that are exposed to freez- ,
ing temperatures(e.g.,sprinkler drops Identification
from unheated portions of buildings) ■■ I ,
• sprinklers and/or a portion of the con- Numbers (SINs)
necting piping are exposed to freezing
temperatures; for example, sprinkler 3/4 Inch NPT:
drops from wet systems into freezers, TY3935-Pendent ,
• sprinkler sprigs from wet systems into TY3735 Horizontal Sidewall
unheated attics, or horizontal piping 1 Inch NPT:
extensions through a wall to protect an TY3235-Pendent
unheated areas such as loading docks, TY3135 -Upright
overhangs,and building exteriors TY3335-Horizontal Sidewall
• sprinklers are used on systems that Technical
are seasonally drained to avoid freez-
ing(e.g.,vacation areas) Data -
NOTICE
Approvals
The Series DS-1 Dry-Type Sprinklers UL and C-UL Listed
described herein must be installed FM Approved
and maintained in compliance with this NYC Approved under MEA 352-01-E
document, as well as with the applica-
ble standards of the National Fire Previous New York City Approval
Protection Association (NFPA), in ad- and MEA certification numbers ap- Maximum Working Pressure
dition to the standards of any authori- ply to product as shown in this data 175 psi(12,1 bar)
ties having jurisdiction.Failure to do so sheet. In accordance with Section
may impair the performance of these BC 3502 of the Construction Code, Inlet Thread Connections
devices. current NYC Approvals for use in the 3/4 Inch NPT
City of New York apply to all products 1 Inch NPT or ISO 7-R 1
that contain UL or FM Approvals and
Listings; therefore, not all products Discharge Coefficient
currently Approved for use in the City K=5.6 gpm/psil'2
IMPORTANT of New York will carry an actual MEA (80,6 Ipm/bar1i2)
Always refer to Technical Data Certification number.
Temperature Ratings
Refer to Tables A and B.
Sheet TFP700 for the "INSTALLER Refer to Tables A and B.
WARNING"that provides cautions
with respect to handling and in- Finishes
stallation of sprinkler systems and Sprinkler: Natural Brass, Chrome
components. Improper handling and Plated,or Signal White
installation can permanently dam Escutcheon: Signal White, Chrome
age a sprinkler system or its compo Plated,or Brass Plated
vents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 SEPTEMBER 2014 TFP51O
TFP51O
Page 2 of 10
,_ ` Physical Characteristics
PLUG WITH g``1t., INLET Inlet Copper
ASSEMBLY
Plug Copper
i3 � 1111 YOKE Yoke Stainless Steel
I� Casing Galvanized Carbon Steel
�lIMI P 9
PLUG + INLET Insert Bronze
SPRING !--'�MI+ Bulb Seat Stainless Steel
.�:. BAND
��1 Bulb Glass
1■1 ti Compression Screw Bronze
WATER SPRING Deflector Bronze
TUBE AN CASING Frame Bronze
16 Guide Tube Stainless Steel
Water Tube Stainless Steel
GUIDE 11M L INSERT Spring Stainless Steel
TUBE b—�� Plug Spring* Stainless Steel
�rrr��;;;I` f�% BULB Sealing Assembly . . Beryllium Nickel
FRAME tot ii l SEAT w/TEFLON
Escutcheon Carbon Steel
�i'G� •For 3/4 inch NPT only
I, ``�i1 3 mm BULB
VENT HOLE II I I Operation
COMPRESSION When the TYCO Series DS-1 Dry-Type
DEFLECTOR kiirP4__ SCREW Sprinklers,5.6K Pendent,Upright,and
Horizontal Sidewall,Quick Response(3
FIGURE 1 mm bulb)and Standard Coverage are
SERIES DS-1,3/4 INCH NPT,DRY-TYPE SPRINKLER in service,water is prevented from en-
ASSEMBLY tering the assembly by the Plug with
Sealing Assembly in the Inlet of the
PLUG WITH �' 0 INLET Sprinkler.See Figures 1 and 2.
r .E The glass bulb contains a fluid that ex-
SEALING �W �.
AS EMB i panels when exposed to heat.When the
' i YOKE rated temperature is reached,the fluid
1 expands sufficiently to shatter the glass
SPRING .4 •■�� Bulb,and the Bulb Seat is released.
�`I� INLET The compressed Spring is then able
+ 1 BAND to expand and push the Water Tube as
WATER im•mi i well as the Guide Tube outward.This
action simultaneously pulls inward on
TUBE ; ` 1 CASING the Yoke, withdrawing the Plug with
k ' Sealing Assembly from the Inlet and
allowing the sprinkler to activate and
GUIDE k'� % INSERT flow water.
TUBE ;y�';
TFP51O
Page 3 of 10
3/4 Inch NPT
TY3935 Pendent TY3935 Pendent TY3735 Horizontal Sidewall
with Top of Deflector-to-Ceiling
with Standard with Standard Escutcheon Distance of 4 to 12 inches
Recessed Escutcheon (Figure 3) (100 to 300 mm)
(Figure 4)
with Deep Escutcheon with Standard Escutcheon
(Figure 5) (Figure 8)
without Escutcheon with Deep Escutcheon
(Figure 6) (Figure 9)
without Escutcheon
(Figure 10)
Finish
Temperature Bulb - -
Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
135°F(57°C) Orange
155°F(68°C) Red
175'F(79°C) Yellow 1,2 1,2 1* 2*
200T(93'C) Green
286°F(141°C) Blue
Notes:
• Light and Ordinary Hazard occupancies only
1. Listed by Underwriters Laboratories,Inc.(maximum order length of 48 inches)
2. Listed by Underwriters Laboratories for use in Canada(maximum order length of 48 inches)
TABLE A
3/4 INCH NPT SERIES DS-1 QUICK RESPONSE,STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
1 Inch NPT(and ISO 7-R 1)
TY3235 Pendent TY3235 Pendent TY3335 Horizontal Sidewall
with Top of Deflector-to-Ceiling
with Standard with Standard Escutcheon Distance of 4 to 12 inches
Recessed Escutcheon (Figure 3) (100 to 300 mm)
(Figure 4) with Deep Escutcheon
(Figure 5) with Standard Escutcheon
(Figure 8)
without Escutcheon
(Figure 6) with Deep Escutcheon
(Figure 9)
TY3135 Upright
without Escutcheons without Escutcheon
(Figure 7) (Figure 10)
Finish
Temperature Bulb
Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
135°F(57°C) Orange
155'F(68'C) Red
1,2,3,4 1,2,4
175'F(79°C) Yellow 1,2,3,4 1,2,4 1*,2*,3**,4 1*,2*,4
200`F(93`C) Green
286'F(141'C) Blue 1,2,4
Notes:
Light and Ordinary Hazard occupancies only
•• Light Hazard occupancies only
1. Listed by Underwriters Laboratories,Inc.(maximum order length of 48 inches)
2. Listed by Underwriters Laboratories for use in Canada(maximum order length of 48 inches)
3. Approved by Factory Mutual Research Corporation(maximum order length of 48 inches)
4. Approved by the City of New York under MEA 352-01-E
5. The Upright Sprinkler without an Escutcheon(TY3135)is available in 1 inch NPT only
N/A—Not Available
TABLE B
1 INCH NPT(AND ISO 7-R 1)SERIES DS-1 QUICK RESPONSE,STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP510
Page 4 of 10
SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING
(REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN
CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION)
FACE OF FACE OF FACE OF
SPRINKLER SPRINKLER SPRINKLER
FITTING - FITTING FITTING
+ I \ L. f \ ,
ORDER LENGTHS: ORDER LENGTHS: ORDER LENGTHS: 3-1/2"DIA.
2-3/4"to 48' 1-3/4"DIA. 3-3/4"to 48° 1/2"to 46" (88,9 mm)
(69,9 to 1219,2 mm) (44,5 mm) ! (95,3 to 1219,2 mm) (12.7 to 1168,4 mm) 2-11/2"DIA.
IN 1/4"(6,4 mm) IN 1/4"(6,4 mm) 2-1/4"DIA. IN 1/4"(6.4 mm) F(63,5 mm)
INCREMENTS I INCREMENTS (57,2 mm) INCREMENTS�Y/'. FACE OF 1_ /ii• • '
I . CEILING .
FACE OF ■ FACE OF
CEILING ri'� i Iill1 = CEILING I lir
1■0 I ■.f 4-1/4"±1/8
"
II
I
(108,0±3,2 mm) -
2-3/16 ±1/8' 3"DIA. 1-3/8"±1/8" 2-7/8"DIA. 1 I 1 1
(55,6±3,2 mm)
(76.2 mm) (34,9±3,2 mm) (73,0 mm) ,
■
FIGURE 4
FIGURE 3 PENDENT TY3235 AND TY3935 FIGURE 5
PENDENT TY3235 AND TY3935 WITH STANDARD RECESSED PENDENT TY3235 AND TY3935
WITH STANDARD ESCUTCHEON ESCUTCHEON WITH DEEP ESCUTCHEON
SPRINKLER FITTING /
(REFER TO DESIGN TOP OF
CRITERIA SECTION) DEFLECTOR
FACE OF
SPRINKLER
FITTING
\ _J ORDER LENGTHS:
I 5"to 48"
(127,0 to 1219,2 mm)
ORDER LENGTHS: IN 1/4'(6,4 mm)
5"to 48" INCREMENTS
(127,0 to 1219,2 mm)
IN 1/4"(6.4 mm)
INCREMENTS FACE OF
SPRINKLER
FITTING
MINIMUM \
1-3/4'(44,5 mm) /(
DEFLECTOR /
TO CEILING SPRINKLER FITTING
' (REFER TO DESIGN
CRITERIA SECTION)
FIGURE 7
FIGURE 6 UPRIGHT TY3135
PENDENT TY3235 AND TY3935 WITHOUT ESCUTCHEON
WITHOUT ESCUTCHEON 1 INCH NPT ONLY
TFP510
• Page 5 of 10
ORDER LENGTHS: Design
2-3/4"to 48"(69,9 to 1219,2 mm)
IN 1/4"(6,4 mm)INCREMENTS Criteria
1 2-3/8"t 1/8"
(60.3±3,2 mm) The TYCO Series DS-1 Dry- e
FACE OF FACE OF
SPRINKLER MOUNTING Sprinklers,5.6K Pendent,Upright,an,and
FITTING SURFACE Horizontal Sidewall,Quick Response(3
mm bulb)and Standard Coverage are
I intended for use in fire sprinkler sys-
,��. ` t ems designed in accordance wi h the
'�11II�III�`IIII libir. } (3" DIA. ) standard installation rules reco nized
1 I` (76,2 mm by the applicable Listing or Approval
T---7I 3.5' agency; for example, UL Listing is
SPRINKLER FITTING 1-3/4"D . based on NFPA 13 requirements.
• (REFER TO DESIGN (44,5 mm) CENTERLINE 5/16" Sprinkler Fittings
CRITERIA SECTION) OF WATERWAY (7,9 mm) Install the 3/4 or 1 inch NPT Series
FIGURE 8 DS-1 Dry Type Sprinklers in the 3/4 or
TY3335 AND TY3735 HORIZONAL SIDEWALL 1 inch NPT outlet or run of the follow-
TY3335 fittings:
WITH STANDARD ESCUTCHEON
•malleable or ductile iron threaded tee
fittings that meet the dimensional re-
ORDER LENGTHS: quirements of ANSI B16.3(Class 150)
1/2"to 45-3/4"(12,7 to 1162,1 mm)
IN 1/4"(6,4 mm)INCREMENTS •cast iron threaded tee fittings that
i 4-1/4'±1/8" meet the dimensional requirements
2-1/2"DIA. FACE OF (108.0±3,2 mm) of ANSI B16.4(Class 125)
FACE OF (63,5 mm) MOUNTING Do not install the DS-1 Sprinklers into
SPRINKLER I �, SURFACE an elbow fittings.The Inlet of the sprin-
kler can contact the interior of the el-
•--1 I bow, potentially damaging the Inlet
„ '� lioniI' 1 1 3-1/2"DIA. seal.
'III'I'IIIi �' J } (88,9 mm) The unused outlet of the threaded tee is
p■ 3.5' ! plugged as shown in Figure 13.
SPRINKLER FITTING You can also install the Series DS-1
(REFER TO DESIGN CENTERLINE 5/16" Dry-Type Sprinklers in the 3/4 or 1 inch
CRITERIA SECTION) OF WATERWAY (7,9 mm) NPT outlet of a GRINNELL Figure 730
Mechanical Tee.However,the use of
FIGURE 9 the Figure 730 Tee for this arrangement
TY3335 AND TY3735 HORIZONAL SIDEWALL is limited to wet pipe systems.
WITH DEEP ESCUTCHEON The configuration shown in Figure 12
is only applicable for wet pipe systems
ORDER LENGTHS: where the sprinkler fitting and water-
5-1/2"to 48"(139,7 to 1219,2 mm) filled pipe above the sprinkler fitting are
IN 1/4"(6,4 mm)INCREMENTS MINIMUM not subject to freezing and where the
2-1/4"(57,2 mm) length of the Dry Type Sprinkler has the
FACE OF - -DEFLECTOR TO minimum exposure length depicted in
—SPRINKLER MOUNTING Figure 11.Refer to the Exposure Length
FITTING SURFACE section.
For wet pipe system installations of
the 1 inch NPT Series DS-1 Dry Type
Sprinklers connected to CPVC piping,
111111111:I`I } 1 use only the following TYCO CPVC. 17 3.5' 5/16" fittings:
SPRINKLER FITTING (7,9 mm) • 1"x1" NPT Female Adapter(P/N 80145)
(REFER TO DESIGN CENTERLINE • 1"x 1'x 1"NPT Sprinkler Head Adapter
CRITERIA SECTION) OF WATERWAY Tee(P/N 80249)
FIGURE 10 For wet pipe system installations of the
TY3335 AND TY3735 HORIZONAL SIDEWALL the 3/4 inch NPT Series DS-1 Sprinklers
WITHOUT ESCUTCHEON connected to CPVC piping, use in the
• 3/4" x 3/4" NPT Female Adapter(P/N
80142).
TFP51O
. Page 6 of 10
• RUN
FACE OF TO WET SIDE OUTLET
SPRINKLER SYSTEM OUTLET O _ PLUGGED IT
FITTING PLUGGED -1 r"'SPRINKLER
�
HEATED EXPOSURE HEATED TO DRY (SEE DESIGN
AREA LENGTH AREA SYSTEM CRITERIA
(SEE DESIGN SECTION)
DSB-2 CRITERIA D3B-2 SPRINKLER AREA
INTENDED SECTION) INTENDED FITTING SUBJECT DSB-2
FOR FREEZER FOR FREEZER (SEE DESIGN TO INTENDED
STRUCTURES STRUCTURES CFUTERIA FREEZING FOR FREEZER
SECTION) STRUCTURES
ra
di 7777 7777
FIGURE 12 FIGURE 13
FIGURE 11 SPRINKLER FITTING SPRINKLER FITTING
EXPOSURE LENGTH HEATED AREA UNHEATED AREA
STRAP TIES 1-3/4"DIA.
_ (ENDS ON (44,5 mm)
OPPOSING CLEARANCE INSULATED
SIDES OF HOLE FREEZER WRENCH
BOOT) ADHESIVE STRUCTURE RECESS
DSB-2 BOOT
'
�
'0
DSB-2 ••�ADHESIVE BOOT % %
• A 1-3/4"DIA. \ i WRENCH 4
(44,5 mm) II
11111: FLAT CLEARANCE v
v HOLE i� ��
INSULATED �i �i
PUSH WRENCH
FREEZER IN TO ENSURE
'LI' STRUCTURE ENGAGEMENT
STRAP TIES
■ DS-1 WITH SPRINKLER
DS-1 (ENDS ON SHOWN WITH WRENCHING AREA
�III� SHOWN WITH OPPOSING STANDARD
STANDARD SIDES OF FIGURE 16
ESCUTCHEON BOOT) ESCUTCHEON W-TYPE 7
SPRINKLER WRENCH
FIGURE 14 FIGURE 15
MODEL DSB-2 SPRINKLER MODEL DSB-2 SPRINKLER
BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES
DS-1 DRY SPRINKLER DS-1 DRY SPRINKLER
TFP51O
Page 7 of 10
Clearance Space
Temperatures for Heated Areal In accordance with Section 8.4.9.2 of
the 2010 edition of NFPA 13,when con-
Ambient Temperature 40°F 50°F 60°F necting an area subject to freezing and
Exposed to (4°C) (10°C) (16°C) an area containing a wet pipe sprinkler
Discharge End of Sprinkler Minimum Exposed Barrel Length2, system,the clearance space around the
Inches sprinkler barrel of Dry Type Sprinklers
(mm) must be sealed.Due to temperature dif-
40°F ferences between two areas,the poten-
40°F 0 0 0 tial for the formation of condensation in
•
the sprinkler and subsequent ice build-
30°F up is increased.If this condensation is
(-1°C) 0 0 0 not controlled, ice build-up can occur
that might damage the dry-type sprin-
20°F 4 0 0 kler and/or prevent proper operation in
(-7°C) (100) a fire situation.
10°F 8 1 Use of the Model DSB-2 Dry Sprinkler
0
(-12°C) (200) (25)(-12°C) described in Technical Data
Sheet TFP591 and shown in Figures 14
0°F 12 3 0 and 15,can provide the recommended
(-18°C) (305) (75) seal.
-10°F 14 4 1 Installation
(-23°C) (355) (100) (25)
-20°F 14 6 3 The TYCO Series DS-1 Dry-Type
(-29°C) (355) (150) (75) Sprinklers,5.6K Pendent,Upright,and
Horizontal Sidewall,Quick Response
-30°F 16 8 4 (3 mm bulb) and Standard Coverage
(-34°C) (405) (200) (100) must be installed in accordance with
this section.
-40`F 18 8 4 General Instructions
(-40°C) (455) (200) (100) The Series DS-1 Dry Type Sprinklers
-50°F 20 10 6 must only be installed in fittings that
(-46°C) (510) (255) (150) meet the requirements of the Design
Criteria section. Refer to the Design
-60°F 20 10 6 Criteria section for other important re-
(-51°C) (510) (255) (150) quirements regarding piping design and
sealing of the clearance space around
Notes: the Sprinkler Casing.
1. For protected area temperatures that occur between vakies fsted above,use the next
cooler temperature. Do not install any bulb-type sprinkler
2. These lengths are inclusive of wind velocities up to 30 mph 118.6 kph).
if the bulb is cracked or there is a loss
TABLE C of liquid from the bulb.With the sprin-
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS kler held horizontally,a small air bubble
MINIMUM RECOMMENDED LENGTHS should be present.The diameter of the
air bubble is approximately 1/16 inch
For dry pipe system installations, use Drainage (1,6 mm)for the 135°F(57°C)rating to
only the side outlet of maximum 2-1/2- In accordance with the minimum 1/8 inch(3,2 mm)for the 286°F(141°C)
inch reducing tee when locating the requirements of the National Fire rating.
Series DS-1 Sprinklers directly below Protection Association for dry pipe
the branch line.Otherwise,use the con- sprinkler systems, branch,cross,and •A leak-tight 3/4 inch NPT sprinkler
figuration shown in Figure 13 to assure feed-main piping connected to Dry joint should be obtained by applying
complete water drainage from above Sprinklers and subject to freezing tern-
a minimum-to-maximum torque of 10
• the Series DS-1 Dry Type Sprinklers peratures must be pitched for proper to 20 ft.-lbs.(13,4 to 26,8 Nm).
and the branch line. Failure to do so drainage. •A leak-tight 1 inch NPT sprinkler joint
may result in pipe freezing and water should be obtained by applying a
•
damage. Exposure Length minimum-to-maximum torque of 20
When using Dry Sprinklers in wet pipe to 30 ft.-Ibs.(26,8 to 40,2 Nm).
NOTICE sprinkler systems to protect areas sub- Higher levels of torque can distort the
Do not install the Series DS-1 Dry-Type C tot determine a sprinkler's appropriate sprinkler Inlet with consequent leakage
Sprinkler into any other type fitting exposed barrel length to prevent water or impairment of the sprinkler.
without first consulting the Technical from freezing in the connecting pipes Do not attempt to compensate for
• Services Department.Failure to use the due to conduction.The exposed bar- insufficient adjustment in an
appropriate fitting may result in one of rel length measurement must be taken Escutcheon Plate by under or over-
the following: from the face of the sprinkler fitting to tightening the sprinkler.Re-adjust the
•failure of the sprinkler to operate prop- the surface of the structure or insula- position of the sprinkler fitting to suit.
erly due to formation of ice over the tion that is exposed to the heated area.
inlet Plug or binding of the Inlet Plug Refer to Figure 11 for an example.
•insufficient engagement of the Inlet
pipe threads with consequent leakage
TFP510
. Page 8 of 10
• Step 1. Install pendent sprinklers only Absence of the outer piece of an es- Ordering
in the pendent position, and install up- cutcheon, which is used to cover a
right sprinklers only in the upright posi- clearance hole, can delay the time to Procedure
tion.The deflector of a pendent or up- sprinkler operation in a fire situation.
right sprinkler must be parallel to the A Vent Hole is provided in the Bulb Contact your local distributor for avail-
ceiling. Seat(Ref. Figures 1 and 2)to indicate ability.When placing an order, indicate
Install horizontal sidewall sprinklers in if the Dry-Type Sprinkler is remaining the full product name and Part Number
the horizontal position with their cen- dry.Evidence of leakage from the Vent (P/N).
terline of waterway perpendicular to Hole indicates potential leakage past DS-1 Dry-Type Sprinklers
the back wall and parallel to the ceil- the Inlet seal and the need to remove When ordering TYCO Series DS-1
ing.Ensure the word"TOP"on the De- the sprinkler to determine the cause of Dry-Type Sprinklers, 5.6K Pendent,
flector faces the ceiling. leakage(e.g., an improper installation Upright,and Horizontal Sidewall,Quick
Step 2. With a non-hardening pipe- or an ice plug). Close the fire protec- Response(3 mm bulb)and Standard
• thread sealant such as TEFLON tape tion system control valve and drain the Coverage, specify the following
applied to the Inlet threads, hand-tight system before removing the sprinkler, information:
en the sprinkler into the sprinkler fitting. Sprinklers which are found to be leak- •SIN:
Step 3.Wrench-tighten the sprinkler ing or exhibiting visible signs of corro Pendent—TY3935 or TY3235
using either: Sion must be replaced. Sidewall—TY3735 or TY3335
• a pipe wrench on the Inlet Band or the Automatic sprinklers must never be Upright—TY3135
Casing(Ref. Figures 1 and 2) painted, plated, coated, or other- • 5.6 K-factor
wise altered after leaving the factory.
• the W-Type 7 Sprinkler Wrench on the Modified sprinklers must be replaced. • Deflector Style:
Wrench Flat(Ref.Figure 16) Sprinklers that have been exposed to Upright,Pendent,or Horizontal Sidewall
Apply the Wrench Recess of the corrosive products of combustion, but •Quick Response,Standard Coverage,
W-Type 7 Sprinkler Wrench to the have not operated,should be replaced Dry-Type Sprinkler
Wrench Flat. if they cannot be completely cleaned
by wiping the sprinkler with a cloth or •Order Length:
Note: If sprinkler removal becomes by brushing it with a soft bristle brush. Dry-Type Sprinklers are furnished based
necessary, remove the sprinkler us- upon Order Length as measured per
ing the same wrenching method not- Care must be exercised to avoid dam- Figures 3 through 10.After taking the
ed above. Sprinkler removal is easier age to the sprinklers before,during, and measurement,round it to the nearest
• when a non-hardening sealant was after installation.Sprinklers damaged 1/4 inch increment.
used and torque guidelines were fol by dropping, striking, wrench twist/
slippage,or the like,must be replaced. •• Inlet Connections:
lowed.After removal,inspect the sprin- Also, replace any sprinkler that has a 3/4 Inch NPT, 1 Inch NPT,or ISO 7-R 1
kler for damage. p y p
cracked bulb or that has lost liquid from •Temperature Rating
Step 4. After installing the ceiling or its bulb.(Ref. Installation Section.)
wall and applying a ceiling finish, slide • Sprinkler Finish
on the outer piece of the escutcheon The owner is responsible for the in • Escutcheon Style and Finish, as
until it comes in contact with the cell spection,testing, and maintenance of applicable y
ing or wall. Do not lift the ceiling panel their fire protection system and devices
out of its normal position. in compliance with this document, as • Part Number(P/N)from Table D
well as with the applicable standards of The Upright Sprinkler without an
When using the Deep Escutcheon, the National Fire Protection Association p
hold the outer piece in contact with (e.g., NFPA 25), in addition to the Stan Escutcheon (TY3135) is available in
the mounting surface(ceiling or wall). 1 Inch NPT only.
9 ( 9 ) dards of any other authorities having
Then rotate the inner piece approxi- jurisdiction.Contact the installing con- Part Numbers are for 3/4 inch and
mately 1/4 turn with respect to the out- tractor or product manufacturer with 1 inch NPT standard order sprin-
er piece,to hold the Deep Escutcheon any questions. klers. Orders for all other sprinkler
firmly together. Automatic sprinkler systems are recom-
mended to be inspected,tested, and by a complete description. Refer to
Care and maintained by a qualified Inspection the Price List for a complete listing of
Service in accordance with local re Part Numbers.
Maintenance quirements and/or national codes. Sprinkler Wrench
The TYCO Series DS-1 Dry Type P ecify: W 4Y001 Sprinkler Wrench,
. Sprinklers, 5,6K Pendent. Upright,and Limited N
Horizontal Sidewall,Quick Response(3 Sprinkler Boot
mm bulb)and Standard Coverage must Warranty Specify: Model DSB-2 Dry Sprinkler
be maintained and serviced in accor- Boot, P/N 63-000-0-002
dance with this section. For warranty terms and conditions, This Part Number includes one (1)
Before closing a fire protection system visit www.tyco-fire.com. Boot,two(2)Strap Ties,and 1/3 oz.of
. main control valve for maintenance Adhesive (a sufficient quantity for in-
work on the fire protection system that stalling one boot).
it controls, obtain permission to shut
down the affected fire protection sys-
, tems from the proper authorities and
notify all personnel who may be affect-
ed by this action.
TFP51O
Page 9 of 10
P/N* 60 - XXX - X - XXX
SIN SPRINKLER ESCUTCHEON
FINISH FINISH1
01 Pendent with Standard TY3935 SIGNAL WHITE
• Escutcheon(3/4"NPT) (Figure 3) 0 CHROME PLATED (RAL9003)
02 Pendent with Deep TY3935 SIGNAL WHITE
•
Escutcheon(3/4"NPT) (Figure 5) 1 NATURAL BRASS (RAL9003)
03 Pendent with Standard Recessed TY3935 2 NATURAL BRASS BRASS PLATED
Escutcheon(3/4"NPT) (Figure 4)
SIGNAL WHITE SIGNAL WHITE
04 Pendent without TY3935 4 (RAL9003) (RAL9003)
Escutcheon(3/4"NPT) (Figure 6)
I 9 CHROME PLATED CHROME PLATED
05 Sidewall with Standard TY3735
Escutcheon(3/4"NPT) (Figure 8)
06 Sidewall with Deep TY3735 TEMPERATURE SAMPLE
Escutcheon(3/4"NPT) (Figure 9) RATINGS ORDER
- LENGTHS2
07 Sidewall without TY3735 0 135°F(57°C)
Escutcheon(3/4"NPT) (Figure 10) 055 5.50"
I 1 155`F(68°C)
082 8.25"
Pendent with Standard TY3235 2 175°F(79°C)
36 Escutcheon(1"NPT) (Figure 3) 180 18.00"
3 200°F(93°C)
Pendent with Deep TY3235 187 18.75"
33 Escutcheon(1"NPT) (Figure 5) 4 286°F(141°C)
372 37.25"
37 Pendent with Standard Recessed TY3235 480 48.00"
Escutcheon(1'NPT) (Figure 4)
32 Pendent without TY3235
Escutcheon(1'NPT) (Figure 6)
INotes:
Use Prefix'r for ISO 7-R 1 Connection(e.g..1-60-010-4-055).
Sidewall with Standard TY3335 1. Escutcheon Finish applies to sprinklers provided with escutcheons.
34 Escutcheon(1"NPT) (Figure 8) 2. Dry-Type Sprinklers are furnished based upon"Order Length"as measured
per Figures 3 through 10,as applicable,and for each individual sprinkler
where it is to be installed.After the measurement is taken,round it to the
43 Sidewall with Deep TY3335 nearest 1.'4 inch increment.
Escutcheon(1"NPT) (Figure 9)
44 Sidewall without TY3335
Escutcheon(1"NPT) (Figure 10)
. I
38 Upright without TY3135
Escutcheon(1'NPT) (Figure 7)
TABLE D
SERIES DS-1 DRY-TYPE SPRINKLERS
PART NUMBER SELECTION
TFP51 O
Page 10 of 10
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
Copyright®2014 Tyco Fire Products,LP. All rights reserved. tgco
TEFLON Is trademark of the DuPont Corporation. Fire Protection Products
Dyna-Thread® - M-COAT®
Submittal Data Sheet
• ® Full Line Sch-40 Replacement Dyna-Thread—M-COAT Specifications
Dyna-Threadh'—M-Coat' sprinkler pipe represents an engineering NPs Nominal I.D. Wt. Wt.(H20 Filled) ERR CRR
▪ advancement for the sprinkler pipe industry.It combines the safety In;mm In;mm Lbs/Ft;kg/m Lbs/Ft;kg/m Unthreaded Threaded
and longevity of traditional Sch-40 pipe with quality and superior 1" 1.080 1.330 1.75 11.39 1.00
hydraulic advantages. 25 27.4 2.0 2.60 —
1'/a" 1.408 1.870 2.54 9.50 1.00
® Comparison to Schedule 40 32 35.8 2.8 3.78 — —
1'/" 1.639 2.290 3.22 9.14 1.00
Dyna-Thread``—M-Coat` inside diameter is up to 3.6%larger than Sch-40 40 41.6 3.4 4.79 — —
giving it superior hydraulics.Also,when used in combination with Dyna- 2" 2.104 3.050 4.57 8.41 1.00
Flow—M-Coat pipe,down sizing often occurs.Dyna-Thread is fully listed and 50 53.4 4.5 6.80 — —
approved UL, ULC,and FM for fire sprinkler applications.The life expectancy
of Dyna-Thread—M-Coat and Sch-40 are equal based on the calculated wall ® c® 4011,-
thicknesses per UL.The consistent quality of steel used to make Dyna-Thread—
APPROVED
M-Coat facilitates smooth threading and lower maintenance costs.The exterior
of Dyna-Thread—M-Coat is protected by a clean,durable mill coating for O American Made
extended shelf life and easy paint application.With its increased strength Manufactured at one of 3 U.S.Facilities and is available
and lighter weight,Dyna-Thread—M-Coat reduces installation fatigue and through distributors in the USA,Canada,Mexico,and
is ideal for retio-fit applications.Corrosion Resistance Ratio(CRR)is a UL Latin America.
- (Underwriters Laboratory)term for the estimated life expectancy of a pipe joint.
This is based on the calculated wall thickness at the base of the first exposed Specifications & Approvals
• thread,assumed to be the weakest point of the pipe length.Dyna-Thread—
M-Coat and Sch-40 have the same calculated wall thicknesses at this point Dyna-Thread—M-Coat pipe is manufactured to meet:ASTM A
and are both assigned the same CRR of 1.00. 135,Type E Grade A,and is in compliance with NFPA-13.All
sizes of Dyna-Thread—M-Coat are rated at 300 psi working
O Comparison to L.W.T. Pipe pressure.Dyna-Thread—M-Coat is UL and ULC Listed for wet,
More wall thickness at the thread(CRR=1.00)gives Dyna-Thread—M-Coat dry and pre action sprinkler systems and FM Approved for
better life expectancy than lightwall threadable pipe joints.Dyna-Thread— use in wet systems.Dyna Thread—M-Coat is approved for all
M-Coat is approved for standard hanger spacing(15 ft.0.C.),can be used as threaded couplings and welded outlets and is suitable for all
earthquake sway bracing,and is safe to use as drops.Dyna-Thread—M-Coat roll grooved,and plain end fittings.(See listing information).
is safer to weld on than many zinc coated lightwall threadable pipe products.
Dyna-Thread—M-Coat is more widely accepted than lightwall threadable
where Sch-40 is specified.
Project: Sprinkler Contractor: Date:
Engineer: Specification Reference: System Type:
Locations: Comments:
9. Customer Service:(800)882-5543 Fax:(800)659-7730 www.alliedtube-sprinkler.com
allied • 16100 5 Lathrop Ave • 11350 Norcom Rd. • 2525 N 27th Ave.
TUBE&CONDUIT' Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009
...'.''F atkore
- ,, 02013 Atkore International,Inc.All Rights Reserved.STP-53-4M-1301
Ductile Iron Fittings - Class 300 UL/FM
, SO -I UUA.L!T?PLUS
•
C ® US FM
APPROVED
LISTED
A Fig. 35E 3-90° Elbow
A Size Part Number A Packing Weight
�''-"'� in in Inner Master lb
,� 1/2 35E 3004 3 200 0.2
'" ' 1 3/4 35E 3006 1.31 70 140 0.3
A 1 35E 3010 1.50 ') 80 0.5
'fRU - 1-1/4 35E 3012 1.75 25 50 0.8
1-1/2 35E 3014 1.94 18 36 1.1
2 35E 3020 2.25 10 20 1.8
2-1/2 35E 3024 2.70 -1 8 3.2
Fig. 35RE3- 90°Reducing Elbow
B Size A B Packing Weight
fil ( in Part Number in in Inner Master lb
3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3
I1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4
1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4
1E1111 A 1-114 x 1/2 35RE3012004 1.34 1.53 35 70 0.5
1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6
1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7
1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6
1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7
1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0 8
1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0
2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0
2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0
• 2 x 1 35RE3020010 1.73 2.02 16 32 1.2
2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3
D 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5
U 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2
C 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5
T
1 Fig. 35F 3-45°Elbow
ESize Part Number A Packing Weight
'`A in in Inner Master lb
�, 1/2 35F 3004 0.88 150 300 0.2
3/4 35F 3006 0.98 80 160 0.3
ri 1 35F 3010 1 13 40 80 0.5
1-1/4 35F 3012 1.29 25 50 0.7
1-1/2 35F 3014 1.44 20 40 0
i�� IA 2 35F 3020 1.69 10 20 1.6
2-1/2 35F 3024 1.95 4 8 _
Fig. 35T 3- Tee
Size Part Number A Packing Weight
in in Inner Master lb
l-ES 1/2 35T 3004 1.13 80 160 0.3
A In
I 3/4 351 3006 1.31 30 60
50 0.5
�I 1 35T 3010 1.50 25 0.7
1-1/4 35T 3012 1.75 10 20 1.1
A �I� /a 1-1/2 35T 3014 1.94 1/ 20 1.5
2 35T 3020 2.25 6 12 2.4
2-1/2 35T 3024 2.70 4 8 4.3
111 SMITH-COOPER IN'I'ERNA'I'IONAL" • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.sminccooper.com
r.=
.> .. Ductile Iron Fittings - Class 300 UL/FM
I QUAt!TY .ds-
c ® us
A PPROVC'r?
A
Fig. 3503 -Straight Coupling with Ribs LISTED
Size Part Number A Packing Weight
in in Inner Master lb
1/2 35CP3004 200 2.00 0.1
3/4 35CP3006 163 100 200 0.2
1 35CP3010 1.75 60 120 0.4
1-1/4 35CP3012 2.00 35 70 0.5
1-1/2 35CP301-1 2.19 25 50 0.7
2 35CP3020 2.62 15 30 1.2
2-1/2 35CP3024 3.00 9 18 2.2
Fig. 35RC3 -Hex Reducing Coupling
III pa-mq
Size Part Number A Packing Weight
i in lb
A 1 x 1/2 35RC3010004 t69 80 160 0.3
1 x 3/4 35RC3010006 1.69 60 120 0.4
0.6
_--_ 1-1/4 x 3/4 35RC3012006 2.06 40 Inner Master 50
2 x 1 (not hex) 35RC3020010 2 81 20 40 1.0
Fig. 35HB3 -Hex Bushing
Size Part Number A Packing Weight
B in in Inner Master lb
1 x 1/2 35HB3010004 1.013 180 360 0.2
Ii I ^A 1 x 3/4 35HB3010006 1.06 180 360 0.1
1-1/4 x 1 35HB3012010 19 90 80 0.2
1-1/2 x 1 35HB3014010 1.25 75 150 0.4
1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3
D 2 x 1 35HB3020010 1.38 40 80 0.6
U 2 x 1-1/4 35HB3020012 1 38 40 20 0.6
C 2 x 1-1/2 35HB3020014 1.38 40 80 0.6
T
Fig. 35SP3 -Square Head Plug
E Size A Packing Weight
in Part Number in Inner Master lb
1/2 35SP3004 0 94 600 1200 0 07
' L1111 A 3/4 35SP3006 1.12 350 700 0.1
1 35SP3010 25 200 400 0.1
1-1/4 35SP3012 1.37 100 200 0.3
1-1/2 35SP3014 1.44 80 160 0.4
2 35SP3020 1.50 45 90 0.6
Fig. 35U 3- Union with Brass Seat
A Size A Packing Weight
Part Number
in in Inner Master lb
Mil oa 1 35U 3010 2.19 20 40 1.0
1-1/4 35U 3012 2.50 15 30 1.2
1-1/2 35U 3014 2.62 20 1.7
2 35U 3020 3.12 6 12 2.4
a 110
•
113 SMITH-COOPER INTERNATIONAL® • 'POLL FREE 1-800-766-0076 • FAX (323)890-4456 • www.smithcooper.com
Pipe Hangers
Fig. 200 - "Trimline" Adjustable Band Hanger (B-Line Fig.B317ONF) ®TOLCO
Fig. 200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig. B317ONFF) c Ous
Fig.200C - "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) us>reu
Fig.200S - "Trim line" Adjustable Band Hanger with Non-Captured Nut
Size Range:
Fig. 200 - 1/2" (15mm)thru 8" (200mm)pipe
Material: Steel, Pre-Galvanized to G90 specifications
Function: For fire sprinkler and other general piping purposes. Knurled
swivel nut design permits hanger adjustment after installation. 'II Features: ,� :_
• • (1/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe �' '
types and protect CPVC plastic pipe from abrasion.Captured design
keeps adjusting nut from separating with hanger.Hanger is easily B
e�
installed around pipe. = A
For hanger with non-captured nut order Fig.200S. r
• (21/2" (65mm)thru 8" (2oomm))Spring tension on nut holds it securely in ii!7--,„:4"P'llii°4.'
hanger before installation.Adjusting nut is easily removed. `
Approvals: Underwriters Laboratories listed(1/2" (15mm)thru 8" (200mm)) Fg.200 V2-20014
in the USA(UL)and Canada (cUL)for steel and CPVC plastic pipe and tig.zao_t to 200-2 F zog x,hto 200-11
Factory Mutual Engineering Approved(FM) (3/4" (2omm)thru 8" (2oomml). g'
Conforms to Federal Specifications WW-H-171 E&A-A-1 192A, Type 10
and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, ,,,M
Type 10.
Maximum Temperature: 650"F(343"c) ,,
Finish: Pre-Galvanized. Stainless Steel • -
materials will be supplied with (2) hex nuts 1 * '
in place of a knurl nut, ""
Order By Figure number and pipe size ;',-
.
Designed to meet or exceed requirements of .`x
FM DS 2-0.
4. ' : ^ .•
Fig.200 ''''':-
.--
Fig.200C Fig.200F
Pipe Size Rod Size A B Approx.Wt./100 , ,
Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) ""74,-."----, ,
200-1/2 I/2" (15) 3/8"-16 31/8' (79.4) 25/8 (66.7) 11 (5.0)
200-3/4 3/4" (20) 3/8"-16 31/8" (79.4) 21/2" (63.5) 11 (5.0)
200-1 1" (25) 3/8"-16 33/8" (85.7) 25/8- (66.7) 12 (5.5)
. 200-11/4 11/4" (32) 3/8"-16 33/4" (94.01 27/8" (73.0) 13 (5.9)
200-11/2 11/2" (40) 3/s"-16 37/s" (98.4) 21/8" (73.0) 14 (6.4)
200-2 2" (50) 3/8.-16 41/2" (114.3) 3" (76.3) 15 (6.9) .
200-21/2 21/2" (65) 3/8"-16 55/8" (142.9) 41/8" (104.7) 27 (12.3)
3" (75) 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S
200-31/2 31/2" (90) 3/8"-16 73/8" (187.3) 51/4" (133.3) 34 (15.6)
200-4 4" (100) 3/8"-16 73/8° (187.3) 5" (127.0) 35 (16.0)
200-5 5" (125) W-13 91/8" (231.8) 61/4" (158.7) 66 (30.2)
200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4)
200-8 8' (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.31
All dimensions in charts and on drawings ate in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line
Fire Protection Solutions 21
by E:T•N
Threaded Accessories
B3205 - Threaded Rod (right-hand threads - both ends) (Toico Fig.103) '
B3205L - Threaded Rod (right& left hand threads) TL f.---
Size Range: 3/8"-16 thru 3"-4 rod ,„--- `Leoytb ? ' '
Material: Steel ,.---'
Function: Recommended for use as a hanger support in hanger assemblies. ‘. ...---..---..TL ��:
Rod is threaded on both ends with right hand threads of the length shown.Also ,--0∎' A
available with left and right hand threads-specify Fig. B3205L when ordering. '' Thread Size
Maximum Temperature: 750`F(399°C)
Finish: Plain.Contact B-Line for alternative finishes and materials.
Order By: Part number,rod size, length and finish
Standard Design Load
Thread Size Thread length TL 650°F(343°C) 750°F(399°C)
Part No. A in. (mm) Lbs. (kN) Lbs. (kN)
B3205-3/8 x'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54)
B3205-1/z x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70)
B3205-5/8 x'L' 5/6"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52)
B3205-3/4 x'L' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25)
B3205-7/8 x'L' 7/6"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60)
B3205-1 x'L' 1"-8 4" (101.6) 5900 (2624) 4620 (20.55)
83205-11/8 x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93)
B3205-11/4 x'L' 11/4"-7 5" (127.0) 9500 (4225) 7440 (33.09)
B3205-11/2 x'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07)
B3205-13/4 x'L' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79)
• B3205-2 x'L' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29)
• B3205-21/4 x'L' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51)
83205-21/2x'L' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64)
83205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08)
B3205-3 x'L' 3"-4 12" (304.81 60100 (267.32) 47066 (209.35)
ATR -All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig.100) �����,
Fig. 99- All Threaded Rod Cut To Length _=
3 t CJ ,o
Size Range: /e" 16 thru 1 /2" 6 rod in 120"(3.05m)lengths or cut to length i ' ���`' �C1�1
Material: Steel r4 t 1i--' »
Maximum Temperature: 750°F(399°C) ` ' " .a 0
Finish: Plain.Contact B-Line for alternative finishes and materials. R as m
. Order By: Part number,rod diameter and finish
- Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft.
ATR Fig.99 Per Inch Lbs. (IN Lbs. (kg)
ATR 1/4"x 120 99-1/4"x length 20 240 (1.07) 12 (5.44)
ATR 3/a"x 120 99-3/a"x length 16 730 (324) 29 (13.15)
ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04)
ATR 5/8"x 120 99-5/8"x length 11 2160 (9.60) 89 (40.37)
. ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79)
ATR 71a"x 120 99-7/8"x length 9 4480 (19.93) 170 (77,11)
ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06)
All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in milimeters unless otherwise specified.
B-Li
Pipe Hangers&Supports 236 Rev sed4.8/2014
ne
by EA•N
VERTICAL MOUNT SAMMYS
SAMMYS® for Wood Installs VERTICALLY into the bottom of wood structures easily and quickly!
O .
Not tens than Wood Flooring
0 2'natural inal width Product Features
( )
•No pre-drilling required.
0 . Not man •Quick to install using the Sammy
a nominal Nut Driver with an 18V cordless
)
wood Jost drilVdriver.
I W Itrickdeptneshs4tidlie2
f vertical member) _ - -. _//
� •Saves time from traditional
ooub a sneehock methods.
121 ,
For vertical use- Ceiing
inst�lmmnteroflnwerrace. •Reduces installation cost.
Minimum 2'embedment mro base
me eva for aFPA 13 compliance, Composite l Truss •Made in the U.5 A.
�' Consult buss manufacturer for
O .� recommended installation point
f x•
O — �''---' i •Prednikng may be required for GST
—�. Z„� 25380.Tod available on page II
IS Approvals Rod Part Model Screw Ultimate UL Test FM Test Box Case
PP Size Number Descriptions Pullort(lbs) Load(Ibs) Load(Ibs) Qty Qt
1/4' 8002957 GST 100 1/4 x 1' 210 (7716'OSB) 25 125
670 (3/4'Ply)
1/4' 8003957 GST 200 1/4 x 2" 1760 (Fir) 25 125
' 1/4" 8004957 GST 300 1/4 x 3' 2060(Fir) 25 125
3/8" 8006957 GST.75 1/4 x 3/4' 564(3/4"Ply) 25 125
3/8" 8007957 GST 10 1/4 x 1" 210(7/16'OSB) 300 25 125
670(3/4'Ply) —
? 3/8" 8008957 GST 20 1/4 x 2' 1760 (Fir) 850 1475 25 125
i< Q' 3/8" 8068925 GST 20-SS 1/4x2' 1760(Fir) 850 25 125
3/8" 8009925 GST 25-380 3/8 x 2-112" 2113 (Fir) 1500 25 125
d 4 3/8" 8010957 GST 30 1/4 x 3" 2060 (Fir) 1500 1475 25 125 #14 Black
Nut Driver
3/8" 8069925 GST 30-SS 1/4 x 3" 2060 (Fir) 25 125 Part#8113910
ElleaL 3/8' 8011925 GST 40 1/4x 4' 2180(Fir) 25 125 ii
3/8" 8012925 GST 60 1/4 x 6" 2230(Fir) 25 125 —
1/2° 8013925 GST 2 1/4 x 2" 1760(Fir) 25 125
1/2" 8014925 GST 2.5-380 3/8 x 2-1/2" 2113 (Fir) 25 125
y. 1/2" 8015925 GST 3 1/4x 3° 2275 (Fir) 25 125 —
.- — 1/2" 8016925 GST 4 1/4 x 4" 2180 (Fir) 25 125
O 1/2" 8017925 GST 6 1/4 x 6" 2230(Fir) 25 125 _ #14 SW Red
Nut Driver
Part 4 8114910
SAMMY Swivel Head' for Wood Installs VERTICALLY and swivels up to 17°in wood structure
Product Features
•Eliminates distortion of threaded rod. •Saves time from traditional methods,
.-' •Accommodates up to 3''/_"x 12 pitch roof. •Reduces installation cost-
•Allows 17°deflection from vertical. •Made in the U.SA.
Approvals Rod Part Model Screw Ultimate UL Test FM Test Kin Box Case
ii: Size Number Descriptions Pullout(lbs) Load(Ms) Load Ike) Thickness Qty Qty
`2' 'C' 318" 8139957 SH-GST 20 1/4 x T 1257(Fir) 1050 1475 25 125 125
' Q•Q 318" 8141957 SH-GST 30 114 x 3' 1720(Fir) 1500 1475 25 125
#14 Black
Nut Driver
SPECIAL NUT DRIVER S(STEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into Part#8113910
contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations.
1/44,itii
For the most up to date information,visit wwwsammysuperscrew.com 4 ,' 11"t U)
�loc" vTZ
• 0 0
RECEIVED
+6'-B•MIN. +8'-0•AFF
. •B HOOD •• - ---- - --—_
B GAP BD lr - __—"..— .--_- -_—, - MAR
• DISHWASHING Y B8 GAP BD • - Le - "_". ._. __ 11�yy'',, - lJe ) MAR 2015
ti�
III -8' F.F. • - — .
_ ;�7__'__■�I■=�_____�I�_! 7 y e 04 FIXTURE ` -- , , ' = CITY OF TIGARD----;+9•-6•AFF IMi—'L:Ai�7 ° 1■�lii�El.LAM ® ����I►A �I'.. •a;...• ' ■��i ell L- _�__ -__ ��,.- _1� _'I i - BUILDING DIVISION
'B/CLNG TILE — 1--_ -AFF ENE 1 ,�■\i�I w ,• '~..; '.Y.'.' DIN NG C � ��--_ `` �,�.� 'c�
,•8/HEAD R
I ! !! ! s :■ { �, ® :, _ \ —,. �_--c. 0
4;; ' /}gai ■ ■■ JII1ic: r. it TENANT E tt ® ,+Ph • ■■N ,w_ — � m ma m :>.'` > .I��w��'I +e-o A� =�T TENANT - y • 2
400 tr
O r. el-W�Si 1 EXISTING W -
F• `•.:,.. SINGLE STORY STORY �SyiN `j TENANT it EXISTING TRASH
:•,..--,...' I- O �. WOOD FRAME. SLAB cT�N ,\ - ROOM
//////// // � ///// ® /�//��//�//. ON GRADE BUILDING. �"
+g•_g• % - .`.'J.;::•::°•:,.:-•'; ::::';••••'"
.. .. SHELL UNDER QU4 ' /
,+8 HEADER t= ;Y .�7 2' -.... •�_ ti.. SEPARATE PERMIT. RF
.I., "i/ 2..•••.�'n'i" .�. �. •'. 11■I Ro \.. , EXISTING PARKING
w/Ss.C.G. ,. . r _ .E 1I II q,
ORD -•• GO
ti'
toE�
■r■
ff•] d
;'iY
b, e V
�I j1
B/GYP BD • '•s, - �, F..'i`•��_� ';r ..xa••�«: '-r•°,' ...?.:.:;.,1:.; :.."'`::''''.:: +1a' 0• CFF 1! ��,si▪.. jl .I;�'S `.. ,,.S. ,,q K� :r' c.,%•{` I B/GYP ED
�� Y KEY PLA\
�, :'`''�: NOT TO SCALE NOTES
• ° " All piping to be Dyna-Thread w/screwed ductile iron fittings.
® — ?• ' ` All heads cut in from branch lines.
CooLER Lull t■ I rte. on •>t iiii O' `O' `O' All hangers to be per NFPA 13 requirements.
I„I :,..!:•:.::.-.;.' +•• a 8 DINING B All armovers greater than 2'-0' shall be provided with hangers.
�� s: ,....,..'.t....:' Q 0 �•P7 Meets design requirements of NFPA 13 2013 edition.
' ilhEfEN TO DECK
O I! ¶ ' t ��1 All public areas(dining) will be light hazard occupancy.
ABOVE COOLER FAN ••„” LJ� .�
■. .:'ep':';,,^} All back of house areas(prep St storage) will be ordinary hazard group 1 occupancy.
6'-0' } .t I ' 1.._: Max sprinkler spacing to be 225 (Light Hazard) or 130 sq. ft. (Ordinary Hazard) per head.
KITCHEN�TORAGE '• 'r: i'
+9'-6•AFF ■�___ 'tl• 't 4004 O �' O �' ho41
-
�e7 cLHC TILE ��� I
II\IAmi 11as117 , �w,.-EA : ) 0 • ��� sAMMYS FOR WOOD
0 V ,IVr7f�lV ,i,:: .. - ----i---
� ;e• a.
—, — It
_. r{ 3/8• ALL THREAD R00
i
A — - o � REI PRaF4-
k S
= E. . 1-6•A.F.F. DI N A +12'-0•APT • `, �NGINEF.' s�O2
IiDA• e A3 NXTORE Ell B cLNC TILE • SEASONAL PATIO TOLCO 200 TRIMLINE ADJUSTABLE BAND HANGER �' .T 9
+B/GY AFF� L��.}.J ,� 12089 P,,E,�
L '11
0. 0:
470REGON
PARTIAL REFLECTED CEILING PLAN HA\GER DETAIL EXPIRES. 12/31;2016
1/8"=1'-0" NOT TO SCALE
0' 4' 8' 16'
REVISIONS SPRINKLER SYMBOLS FIT:PROTECTION PLAN
DATE DLSDwnLN eA Fil^•;tiKWAPi9_:r::P)E_I:I�i,:�i: 7P'igiewcri:Eee IIv./mCY.'.nE�., 41 NOODLES + CO.
Tyco TY323 SSP-OR cT/6i 155 1/2 t/2 5.6 22[0].
- TYCO TY323 SS'- dl/tT 200 1/2• 1/Y S6 , W YAT T 10218 SW WASHINGTON SQUARE ROAD PERMIT CO.
CONTRACT NO. C15-336
- `l ile( TYCa TY3636 SsP'RDRY a 155 yr 7/+ 5.6 I FIRE PROTECTION, INC. TIGARD, OREGON 97233 DRAWN BY APae
_ 9095 S.W.Burnham SCALE
2/ MAR 2015
- Tigard,OR 97223
(503)684-2928 ROBERTSON ec OLSON CONSTRUCTION,4600 NW CAMAS MEADOWS DR, CAMAS, WA 98607 FP 1 OF 1