Specifications
+ SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 4 DATE: 4/28/2012 C: \HASS74\REUCKERRES . SDF JOB TITLE: Reucker Residence WATER SUPPLY DATA • SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ' D RECEIVED NODE PRESS . PRESS. @ PRESS. @ DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) APR 3 0 2012 8 60. 0 55 . 0 1150. 0 60 . 0 26. 6 46. 1 CITY OF TIGARD BUILDING DIVISION AGGREGATE FLOW ANALYSIS: .1-DS TOTAL FLOW AT SOURCE 26. 6 GPM LQ 2- 000608/�, � TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0 . 0 GPM 1 L of O sit,/ rl OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM r TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26. 6 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 -1 . 0 K= 4 . 90 7 . 0 13 . 0 2 -1 . 0 K= 4 . 90 7 . 7 13 . 6 3 -0 .5 - - - - 11 . 4 - - - 4 12 . 0 - - - - 24 . 7 - - - 5 -2 . 0 - - - - 33. 4 - - - 6 -4 . 0 - - - - 34 . 6 - - - 7 -4 . 0 - - - - 38 . 6 - - - 8 0 . 0 SOURCE 46. 1 26. 6 • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 4/28/2012 C: \HASS74\REUCKERRES . SDF JOB TITLE: Reucker Residence PIPE DATA PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL(FPS) HW (C) (FT) SUM. • NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -13. 0 1 . 101 PL 15 . 00 PF 0 . 7 1 -1 . 0 4 . 9 7. 0 13. 0 4 . 4 150 FTG 2E PE 0 . 0 2 -1 . 0 4 . 9 7. 7 13. 6 0 . 031 TL 22 . 65 PV Pipe: 2 -26. 6 1 . 101 PL 11 . 00 PF 3 . 9 2 -1 . 0 4 . 9 7 . 7 13. 6 8 . 9 150 FTG E2T PE -0. 2 3 -0 . 5 0 . 0 11. 4 0. 0 0 . 115 TL 33 . 95 PV Pipe: 3 -26. 6 1 . 101 PL 77 . 00 PF 18 . 7 3 -0. 5 0 . 0 11. 4 0.0 8 . 9 150 FTG 5E7T PE -5 . 4 4 12 . 0 0. 0 24. 7 0. 0 0. 115 TL 163 . 06 PV Pipe: 4 -26. 6 1 . 101 PL 15 . 00 PF 2 . 6 4 12 . 0 0. 0 24. 7 0.0 8 . 9 150 FTG 2E PE 6. 1 5 -2 . 0 0 . 0 33. 4 0. 0 0. 115 TL 22. 65 PV Pipe: 5 -26. 6 1 . 080 PL 2 . 00 PF 0. 4 5 -2 . 0 0 . 0 33. 4 0. 0 9 . 3 120 FTG ---- PE 0 . 9 6 -4 . 0 0 . 0 34 . 6 0.0 0. 191 TL 2 . 00 PV Pipe: 6 FIXED PRESSURE LOSS DEVICE 7 -4 . 0 0 . 0 38 . 6 0.0 4 . 0 psi, 26. 5 gpm 6 -4 . 0 0 . 0 34 . 6 0.0 Pipe: 7 -26. 6 1 . 101 PL 80. 00 PF 9. 2 7 -4 . 0 0. 0 38 . 6 0. 0 9. 0 150 FTG ---- PE -1. 7 8 0. 0 SRCE 46. 1 (N/A) 0. 115 TL 80. 00 PV NOTES: (1) Calculations were performed by the HASS 7 . 4 computer program under license no. 5010113212 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0. 011 gpm and a maximum imbalance at any node of 0. 077 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 9. 3 ft/sec at pipe 5 . (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD. PIP SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 4/28/2012 C: \HASS74\REUCKERRES . SDF JOB TITLE: Reucker Residence PAGE: * MATERIAL: S40 HWC: 120 • Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee • 1 .080 2 . 30 5 .76 2. 30 5 . 76 6. 91 1 . 15 11 . 52 11 . 52 5 . 76 1 .101 2 . 53 6.33 2 . 53 6.33 7 . 59 1 . 27 12 . 66 12 . 66 6.33 • o• > CO H WATER SUPPLY ANALYSIS t� y .. 80.0 _ Static: 60. 00 psi Resid: 55.00 psi Flow: 1150.0 gpm y ,A r LEGEND - N 70.0 __ 1 Available pressure • ° 60.00 psi @ 26. 6 gpm m N 2 , . Required pressure 10 46.09 psi @ 26. 6 gpm x G A 60. 01 . o to U 0.) ro G a H E m z 50.0 m• N P 2 x R m �C E to S 40.0 _ S 3 U x �C R w E 30. 0 — o r H ( n P 20.0 — z i n r .. k m xi--1 > C 10. 0 C 4, 0. 0 C n x z tl ro to w • ,c M m d -14 .7 1 I I I 1 I F I 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) 04/25/2012 11:29 5036848840 COT_PW PAGE 01/04 7ecVe - City of Tigard t 73125 SW Hall Blvd. .!. Tigard, O,R 97223 o Phone: 503-639-4271 TIGARD FAX TRANSMITTAL Date April 25,2012 Numbcr uI pages including cover sheet L To: DWy2s.t Fire From: Aaron Beattie Co: Co: City o d Fax#: 503-684-9657 Fax#: Ph#: SUBJECT: Fire flow report for 14998 Augusta Terr MESSAGE: This fire flow is .from 2006. There have been a lot of piping improvements in the area since this test was performed if the fate flows from this test are not high enough for, your needs I would suggest performing another fire flow. • tijcti Fire Suppression & B la ui/ ding Products rapid response® Technical Services 800-381-9312 +1-401-781-8220 HOME FIRE SPRINKLER SYSTEM www.tyco-fire.com Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General The Series LFII Residential Flat-Plate Concealed Pendent Sprinkler has a 4.9 Description (60,5)K-factor that provides the required residential flow rates at reduced pres- The TYCO RAPID RESPONSE Series sures,enabling smaller pipe sizes and .11,7.r.;." LFII Residential Flat-Plate Concealed water supply requirements. i Pendent Sprinklers(TY2524)are decora- This sprinkler has been designed with ',- tive,fast response,fusible solder sprin- heat sensitivity and water distribution ,:;,.. klers designed for use in residential oc- characteristics proven to help in the con- 4-- .;v' cupancies such as homes,apartments, trol of residential fires and to improve dormitories,and hotels. the chance for occupants to escape or The Cover Plate/Retainer Assembly con- be evacuated. 41„ b . ceals the sprinkler operating compo- ,.. '�`"� + '~ .�.,-'x The Series LFII Residential Flat-Plate -..rib » nents above the ceiling.The flat profile Concealed Pendent Sprinklers are of the Cover Plate provides the optimum shipped with a Disposable Protective - aesthetically appealing sprinkler design. Cap.The Protective Cap protects the Additionally,the concealed design of the sprinkler during ceiling installation or Series LFII Residential Flat-Plate Con- finish.After ceiling installation is corn- Technical cealed Pendent Sprinklers provides 1/2 ' inch(12,8 mm)vertical adjustment.This plete, the Protective Cap is removed adjustment provides a measure of flex- and the Cover Plate/Retainer Assem- Data a ju when provides si a bly is installed. Removing the Protec- t' cutting pipe drops. tive Cap is required for proper sprinkler Approvals The Series LFII Residential Flat-Plate performance. UL and C-UL Listed Concealed Pendent Sprinklers are in- NSF-61 Certified tended for use in the following systems: NOTICE The Series LFII Residential Flat-Plate •per NFPA 13D, wet pipe residential The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are only sprinkler systems for one- and two- Concealed Pendent Sprinklers(TY2524) listed with the Series LFII Concealed family dwellings and mobile homes; described herein must be installed and Cover Plates having a factory-applied •per NFPA 13R, wet pipe residential maintained in compliance with this doc- finish. sprinkler systems for pipe oc- ument and with the applicable standards cupnklers up to and including four of the National Fire Protection Associa Maximum Working Pressure stories in height;and tion,in addition to the standards of any 175 psi(12,1 bar) authorities having jurisdiction. Failure Discharge Coefficient •per NFPA 13, wet pipe sprinkler sys- to do so may impair the performance 'rz si K=4.9 GPM/ tems for the residential portions of of these devices. p (70,6 LPM/bar any occupancy. Owners are responsible for maintaining Temperature Rating their fire protection system and devices Sprinkler: 160°F(71°C) in proper operating condition. The in- Cover Plate: 139°F(59°C) IMPORTANT stalling contractor or sprinkler manu- Vertical Adjustment Always refer to Technical Data facturer should be contacted with any 1/2 inch (12,7 mm) Sheet TFP700 for the "INSTALLER questions. WARNING" that provides cautions Finishes with respect to handling and instal- Model/Sprinkler Refer to the Ordering Procedure lation of sprinkler systems and com- section. ponents. Improper handling and in- Identification Ph si stallation can permanently damage y cal Characteristics a sprinkler system or its components Number (SIN) • Cover Plate/Retainer Assembly: • and cause the sprinkler to fail to Cover Plate Copper operate in a fire situation or cause it TY2524 Ejection Spring . . . . Stainless Steel to operate prematurely. Retainer Brass Page 1 of 6 OCTOBER 2010 TFP443 TFP443 Page 2 of 6 f ■ Horizontal Ceiling Sloped Ceiling Sloped Ceiling 1 Minimum Flow(b)and Minimum Flow(b)and Minimum Flowabiand n. Residual Pressure Residual Pressure Residual Pressure ■ Maximum Maximum (Maximum 2-inch rise (Greater than 2-inch rise (Greater than 4-inch rise Coverage Spacing for 12-inch run) up to maximum 4-inch up to maximum 8-inch rise for 12-inch run) rise for 12-inch run) 160°F(71°C) 160°F(71°C) 160°F(71°C) Sprinkler Sprinkler Sprinkler 12'x 12' 12' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (3,7 m x 3,7 m) (3,7 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 14'x 14' 14' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,3 m x 4,3 m) (4,3 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 16'x 16' 16' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,9 m x 4,9 m) (4,9 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 18'x 18' 18' 17 GPM(64,3 LPM) 22 GPM(83,3 LPM) 22 GPM(83,3 LPM) (5,5 m x 5,5 m) (5,5 m) 12.0 psi(0,83 bar) 20.2 psi(1,39 bar) 20.2 psi(1,39 bar) 20'x 20' 20' 20 GPM(75,7 LPM) 24 GPM(90,8 LPM) 24 GPM(90,8 LPM) (6,1 m x 6,1 m) (6,1 m) 16.7 psi(1,15 bar) 24.0 psi(1,65 bar) 24.0 psi(1,65 bar) (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b)The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details. TABLE A SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS • Sprinkler/Support Cup Assembly: Design For systems designed to NFPA 13, the Body Brass number of design sprinklers is to be - . . .. . :..::. Bronze Cap BronzCr/ter/a the four most hydraulically demanding Saddle Brass sprinklers.The minimum required dis- Sealing Assembly Beryllium The TYCO RAPID RESPONSE Series charge from each of the four sprinklers Nickel w/Teflon' LFII Residential Flat-Plate Concealed is to be the greater of the following: Soldered Link Halves Nickel Pendent Sprinklers Lever Bronze (TY2524) are UL •flow rates given in Table A for NFPA Compression Screw Bras s e C-UL Listed for installation in ac- 13D and 13R as a function of tern- Deflector Bronze cordance with the following criteria. perature rating and the maximum al- Guide Pin Housing Bronze towable coverage area Guide Pins Bronze NOTICE • minimum discharge of 0.1 GPM/ Support Cup Steel When conditions exist that are outside sq. ft. over the "design area" corn- the scope of the provided criteria, re- prised of the four most hydraulically fer to the Residential Sprinkler Design demanding sprinklers for actual cov- operation Guide TFP490 for the manufacturer's erage areas protected by the four recommendations that may be accept- sprinklers When exposed to heat from a fire,the able to the Authority Having Jurisdiction. Cover Plate,which is normally soldered Obstruction To Water Distribution to the Retainer at three points,falls away The Series LFll Residential Flat-Plate Locate sprinklers in accordance with the to expose the Sprinkler/Support Cup As- Concealed Pendent Sprinklers must obstruction rules of NFPA for residential sembly.At this point,the Deflector,sup- not be used in applications where the sprinklers as well as obstruction criteria ported by the Guide Pins, drops down air pressure above the ceiling is greater described within TYCO technical data to its operated position. than that below. Down drafts through sheet TFP490. the Support Cup can delay sprinkler op- The Solder Link Element of the Sprinkler/ eration in a fire situation. Support Cup Assembly is comprised of Operational Sensitivity two link halves that are soldered togeth- System Type Install sprinklers relative to the ceiling er with a thin layer of solder. When the Only wet pipe systems may be utilized. mounting surface as shown in Figure 3. rated temperature is reached,the sol- Sprinkler Spacing der melts and the two link halves sepa- Hydraulic Design P pacin Table A rate, allowing the sprinkler to activate provides the minimum required The minimum spacing between sprin- and flow water. sprinkler flow rate for systems designed klers is 8 feet(2,4 m). • to NFPA 13D or NFPA 13R as a function The maximum spacing between sprin- of temperature rating and the maximum klers cannot exceed the length of the allowable coverage areas.The sprinkler coverage area(Table A)being hydrau- flow rate is the minimum required dis- lically calculated;for example, a maxi- charge from each of the total number of mum of 12 feet for a 12 ft.x 12 ft. coy- 1 Registered trademark of Dupont "design sprinklers"as specified in NFPA erage area or 20 feet for a 20 ft.x 20 ft. 13D or NFPA 13R. coverage area. • TFP443 Page 3 of 6 BODY P SEALING (1/2 NPT) /! ASSEMBLY CAP r In.' 1Lw� SPRINKLER �-►"/��!�■���� � j WRENCHING SADDLE 1 ;� �,?`` Al I AREA 1E mir1 1 l■ `r� SUPPORT ` ; ,I, ; COMPRESSION CUP WITH \ % Olt� SCREW ROLL FORMED � THREADS 1 1� _ WRENCH �1 LEVER L`, ,; „ RECESS GUIDE I __ PIN - � 1 i i SOLDER LINK �j -�.: I ELEMENT 1 GUIDE PIN 1 HOUSING I f I Mr t �__�-- I DEFLECTOR �- (OPERATED PUSH WRENCH DEFLECTOR 1 1 r z_____ ---_. I POSITION) IN TO ENSURE I SPRINKLER/SUPPORT CUP I ENGAGEMENT ASSEMBLY WITH SPRINKLER 1 I WRENCHING AREA THREAD INTO I RETAINER SUPPORT CUP UNTIL MOUNTING ) WITH THREAD SURFACE MOUNTING J 1 DIMPLES FIGURE FLUSH WITH j EJECTION W-TYPE 18 _CEILING- SPRINKLER WRENCH SPRING SOWER COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE FIGURE 1 FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) ASSEMBLY 2-1/2'DIA. SPRINKLER- (63,5 mm) 1/2•(12,7 mm) FACE OF SUPPORT CUP 1/2' THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING OPERATED/ SPRINKLER �IIF 1 E 6 1/8'GAP ER 5(3,2 mm) . . ,,, ..,_ _ .....11 COVER- SPRINKLER- f 4 7/8'(22,2 mm) RETAINER SUPPORT CUP SURFACE J MOUNTING 1-1/8'(28,6 mm) ASSEMBLY ASSEMBLY '-���mm)3/16' - 3-3/16"DIA. DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 PROTECTIVE CAP AND ACTIVATED DEFLECTOR • INSTALLATION DIMENSIONS TFP443 Page 4 of 6 Installation 6. Screw on the Cover Plate/Retainer Replace sprinklers that: Assembly until its flange contacts The TYCO RAPID RESPONSE Series the ceiling. • were damaged by dropping,striking, • LFII Residential Flat Plate Concealed wrench twisting, wrench slippage, or Pendent Sprinklers must be installed Do not continue e/R ai to screw ly the the like. in accordance with the following Cover Plate/Retainer Assembly such • 9 that it lifts a ceiling panel out of its •were modified or over-heated. instructions. normal position. • are leaking or exhibiting visible signs NOTICE If the Cover Plate/Retainer Assembly of corrosion. cannot be engaged with the Mounting Responsibility lies with owners for the Damage to the Solder Link Element dur- Cup or the Cover Plate/Retainer As- inspection,testing, and maintenance of ing installation can be avoided by han- sembly cannot be engaged sufficiently their fire protection system and devices dling the sprinkler by the Support Cup to contact the ceiling,the Sprinkler in compliance with this document, as only,-that is, do not apply pressure to the Fitting must be repositioned. Solder Link Element(Figure 1). well as with the applicable standards of the National Fire Protection Association Obtain a leak-tight 1/2 inch NPT sprinkler Care and (for example, NFPA 25), in addition to joint by applying a minimum-to-maxi- the standards of any other authorities mum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Maintenance having jurisdiction. Contact the install- Nm).Higher levels of torque can distort ing contractor or sprinkler manufacturer the sprinkler inlet with consequent leak- The TYCO RAPID RESPONSE Series regarding any questions. age or impairment of the sprinkler. LFII Residential Flat-Plate Concealed Automatic sprinkler systems are Pendent Sprinkler (TY2524) must be tec- Do not attempt to compensate for in- ommended to be inspected, tested, sufficient adjustment in the Cover Plate/ maintained and serviced in accordance and d maintained by a qualified Inspec- Retainer Assembly by under-or over- with the following instructions, tion Service in accordance with local tightening the sprinkler. Re-adjust the requirements and/or national codes. position of the sprinkler fitting to suit. NOTICE 1. Install pendent sprinklers in the Before closing a fire protection system pendent position, with the center- main control valve for maintenance work line of the sprinkler perpendicular on the fire protection system that it con- to the mounting surface. trols,obtain permission to shut down the affected fire protection system from the • 2. Remove the Protective Cap. proper authorities and notify all person- 3. With pipe-thread sealant applied ne/who may be affected by this action. to the pipe threads, and using-the When properly installed,there is a-nomi-----------— W-Type 18 Wrench shown in Figure nal 1/8 inch(3,2 mm)air gap between - 2, install and tighten the Sprinkler/ the lip of the Cover Plate and the ceil- Support Cup Assembly into the fit- ing,as shown in Figure 3.This air gap ting. The W-Type 18 Wrench ac- is necessary for proper operation of the cepts a 1/2 inch ratchet drive. sprinkler by allowing heat flow from a 4. Replace the Protective Cap by fire to pass below and above the Cover pushing it upwards until it bottoms Plate to help assure appropriate release out against the Support Cup. The of the Cover Plate in a fire situation.If the Protective Cap helps prevent dam- ceiling needs repainting after sprinkler age to the Deflector and Guide installation, exercise care to ensure that Pins during ceiling installation and/ the new paint does NOT seal off any of or during application of the finish the air gap. Failure to do so may impair coating of the ceiling. sprinkler operation. Absence of a Cover Plate can delay the NOTICE sprinkler operation in a fire situation. As long as the protective Cap re- Do not pull the Cover Plate relative to mains in place, the system is con- the Enclosure.Separation may result. sidered"Out Of Service" Exercise care to avoid damage to sprin- 5. After the ceiling has been corn- • klers before, during, and after installa- pleted with the 2-1/2 inch (63 mm) tion.Never paint, plate,coat, or other- diameter clearance hole and in wise alter automatic sprinklers after they preparation for installing the Cover leave the factory. Plate/Retainer Assembly, remove Never repaint factory-painted Cover and discard the Protective Cap, Plates.When necessary, replace cover and verify that the Deflector moves plates with factory-painted units. Non- up and down freely. factory applied paint can adversely de- if the Sprinkler has been damaged lay or prevent sprinkler operation in the and the Deflector does not move up event of a fire. and down freely, replace the entire • Sprinkler assembly.Do not attempt to modify or repair a damaged sprinkler. TFP443 Page 5 of 6 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression & Building Products ability.When placing an order, indicate (TFSBP)are warranted solely to the orig- the full product description and Part inal Buyer for ten(10)years against de- Number(P/N). fects in material and workmanship when paid for and properly installed and main- Sprinkler/Support Cup Assembly tained under normal use and service. Specify: Series LFII Residential Flat- This warranty will expire ten (10)years Plate Concealed Pendent Sprinkler from date of shipment by TFSBP. No (TY2524), K=4.9,without Cover Plate/ warranty is given for products or com Retainer Assembly,P/N 51-114-1-160. ponents manufactured by companies Cover Plate/Retainer Assembly not affiliated by ownership with TFSBP Specify:Cover Plate/Retainer Assem- or for products and components which bly with finish (below) for the Series have been subject to misuse, improper LFII Residential Flat-Plate Concealed installation,corrosion,or which have not Pendent Sprinkler(TY2524),K=4.9, P/N been installed,maintained, modified or (below): repaired in accordance with applicable Standards of the National Fire Protection Chrome P/N 56-201-9-135 Association,and/or the standards of any Custom P/N 56-201-X-135 other Authorities Having Jurisdiction. Off White Materials found by TFSBP to be defec- P/N 56-201-0-135 tive shall be either repaired or replaced, Pure White' at TFSBP's sole option.TFSBP neither (RAL 9010) P/N 56-201-3-135 assumes, nor authorizes any person to Signal White— assume for it, any other obligation in (RAL 9003) P/N 56-201-4-135 connection with the sale of products or Standard White(Grey White) parts of products.TFSBP shall not be (RAL9002) P/N 56-201-5-135 responsible for sprinkler system design errors or inaccurate or incomplete in- ' Easuery Hemisphere shes only. supplied by Buyer or Buyer's " Previously known as Bright White. . representatives. Note: All Custom Cover Plates are - painted using Sherwin Williams Interior In no event shall TFSBP be liable,in con- Latex Paint. Contact TYCO Customer tract,tort,strict liability or under any oth- Service with any questions related to er legal theory, for incidental, indirect, custom orders. special or consequential damages,in- cluding but not limited to labor charg- Sprinkler Wrench es, regardless of whether TFSBP was Specify W-Type 18 Sprinkler Wrench, informed about the possibility of such P/N 56-000-1-265. damages,and in no event shall TFSBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,express or implied,including warranties of mer- chantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on fail- ure of or defect in products,materials or components,whether the claim is made in contract,tort,strict liability or any oth- er legal theory. This warranty will apply to the full extent permitted by law.The invalidity,in whole or part, of any portion of this warranty will not affect the remainder. • DynamiThread 0 . Full. Line Seh-4O Replacement Dyjia-Thread• offers the life expectancy of Sch40 with superior hydraulics and greater value. Dyne-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages. • Comparison to Schedule 40 '- Caiparisnts to !.W fi;Pikes • Dyna-Thread's inside diameter 15 up • With its increased strength and lighter - More wall thickness at the thread to 3.6%large"than Sch-40 giving it weight,Dyna-Thread reduces (CRR-1.00)gives D Thread aup�or hydraulics.And,when used installation fatigue and Is ideal for better life expectancy combination with Dyna-Flow pipe, Pr ay than lightwall down sizing o8cn occurs, retie-frtapplications. threadable pipe joints. Corrosion Resistance Ratio (CRR)is a • Unlike]ightwall threadable pipe, - Dyna-Thread is fully listed and UL(Underwriters Labors approved by UL,ULC,and FM for Laboratory)of term for waning, ad Eras no thread gauge the estimated life expectancy of a pipe warning, fire sprinkler applications. joint.This is based on the caloulated •• The life expectancy of Dyna-Thread wall thiolcnass at the base of the first DYna "�is approved for and Soli 1l0 arc equal based on the exposed thread,assumed to be the standard hanger spacing(15 ft • calculated wall thicknesses per UL. weEtke8t Pow of the pipe length.1)3/1111- 0,C,),can be used as earthquake Thread and Sch-40 have the same sway bracing, and is safe to use as • The consistent quality of steel used to calculated wall thicknesses at this point GPs' make Dyna-Thread facilitates smooth and are bath assigned the same CRR of threading and lower maintenance 1,00. Dyna-Thread is safes to weld on, costs, • Dyna-Thread is more widely • The exterior of Dyna-Thread is The internal surface of all black Allied accepted than lightwall threadable protected by a clean,durable mill Tube&Conduit Fire Sprinkler pipe Y'b Soh-40 is specified. coating for extended shelf life and products up to 4.5000"in diameter is easy paint application. coated with our new Anvbacterial Formula, ABF .In scientific laboratory— - -- --- — -- - • test,ABS proved to have superior Specifications-& Approvals resistance to microbial colonization of till 4ii›- 41) pipe walls,thereby delaying or possibly Super 40713yna-Thread pipe is preventing the onset of manufactured to meet:ASTM A-135, Listed Approved Listed Microbiologioal)y Influenced corrosion Grade A and is in compliance with (MIC)when the First Sprinkler System NFPA-13.A11 sizes of Super$p/Dyzta- is first installed. Thread are rated at 300 psi working pressure.Super 40/Dyna-Thread is UL . - - Specifications and Ltt C Listed for wet,dry deluge and• N1' Nemfnal I,Q, Wt. WI,(K2D Flllstl) Per/ W41 IPt(Zi') Wf!!ilt(24') WVLIIt 25' pm-action sprinkler systems and FM In;mm la;mm Lbs'-Kam Lbs •Kc,/m Lilr Lbs•Kg L f Approved for use in wet systems.Super 0 n&'Kg as;Kg 40/Dyna-Thread can be"hot-dip" 1' 1.080 1.93D 1,75 70 1955 2234 2327 galvanized to moot FM requirement for 25 274 2.0 2.60 70 887 7013 705: dry systems, Super 40/Dyna-Thread is 1W 1,408 1,870 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 358 2.8 3,78 51 808 1038 iG8 welded outlets and is suitable fix all 1.639 2.290 3.22 44 2115 2418 251. 1W rill-grooved,and plain cad flttin . 40 41.6 3,4 4,79 44 959 7097 114' (Sec listing information). 2" 2.104 3.080 4,57 30 1921 2195 2287 50 53.4 4.5 a80 30 871 996 103 rtiCa/Row Ccmrrol o f Ile�r 15100 S. Lathrop • Harvey, IL 50425 Customer Service: [ (J 11,350 Noncom Rd. •Philadelphia, PA 19154 (B00)882-5543 TuaE a ooNOUir 2525 N,27 th Ave, •Phoenix,AZ 85009 Fax 708-339-1608 S3-3 Submittal Data Sheet Dynes-Threade Sump Here Full Line Sch-40 Replacement Dyne-T1ncad sprinkler pine represeate an engineering advanecment for the sprinkler pipe industry.It combines the eatery and longrviry of traditional Sch-40 pipe with quality and s pc or hydraulic advantages, Comparison to Schedule 40 Duna-Thrrada inside diem=is up to 3.6%large than Sch-40 giving it superior trydraufies.Also,whm used in combination with Dyna-Flaw — pipe, down sung often occurs.Dyna-Thread is fully listed and approved UL, ULC -�:° _ and FM for fire sprinkler epplinadone.The life expectancy of Dyna•Thread and Sch-40 ....... • . - are equal based am the calculated wall dockncsses per �'y _ - W`;�_� 4,•?.;.,..--..:.,....,.-; p UL.The consistent quality of :•• �•- ;:. �'. . , _• steel used to make Dyna-Thread faeiliteeel smooth threading and ':``' - 7:::',i' - ` '• -.`"' awes 1nelIltt$IInCC :_t ?--. r € coal. The exterior ofl3yna-Thread is protected by a clean,durable mill eoadag :� k"" f+�~ ed shelf life end 'for �•°may• .�._ � ': cxtrnd easy paint application.With its increased strength and lighter •"1 -•' c- .:i; : weight,Dyne-Thread reduces installation fatigre and is ideal for retro-fit applications. ,Vf•"`: {: %��i '"-. : � .4fr Corrosion Resistance Ratio(CRR)is a UL(Undaawritera Laboratory)term for the 34 , /.�_,.:. '-" «z "%-- "•i""` estimated life ppeetaany of a pips joint.This is based the calculated wall '.`: `? ,1:, y 7::: 4-•,;:. at estimated base life the ecta 08 ,�, thickness ;y`•.::l::l;1Y`s. -..-+' - ''�a.-n; --:-'Y ♦s cxp ed dread,assumed to be the weakest paint of the pipe >: _.•= :�%:, .; -a length.Dyna-Thread and Sch-40 have the same calculated wall x.:. ""`" t' t:•; 's: :% °s<^ thlcln.-sees at this point and are both ass ed the tame rt'{• ,', — .'-1•.;•. �'' 13•: +al-'"*. ..r � CRR of I.00. ".��s::�:4 � � .y�`�"�: .sdr:y Comparison to L.W.T.Pipe More well thickness at the thread(CRR=1.00)gives ""..• rr rt. .,1 r'yt• Dyne.-Thread better life empectancy than lightwall thresdable pipe joint Unlike ~:' `: -i' `" ` I lightwell threadahic D l '•= y'': " :- pipe Yna-Thread no thread gauge warning.Dyne-Thread is Rx'1 �°�•' . �. :=" "� t�.( approved for standard hangar spacing(15 ft.4.C.),can be uacd as earthquake sway ] d':�` e'. bracing,and is cafe to use as drops.Dyaa-Thread la safer to weld on than "'""°`'t,"' ,. • many Vic- Wit"` sv .E:.;,.,,,.... coated light-wall thrnadnble pipe products.Dyne-Thread is more widely accepted them }:°b ,',ski �.;; . ..,'c!.:5 i:," ,. lightwall threadable where Soh-40 is specified, ,:41: ::;;'::;"'!" Specifications&Approvals Super 40/ • • Dyne-Thread pipe is manufactured to Specifications • meet:ASTM A 135,Grade A and is in NPS Nomloal I.A. WI M.(N20 Filled) Pas/ WWII(21') WV1.ilt(24') WWII(26' compliance with NFPA-I3.All sizes of h mm hr mm IhvIt.Kann Lbe.eFY Wm Let Lk,'Kg Lbs;Kg Lb':K. Super 40/Dyna-Thread are rated at 300 1' 1,08D 1.330 1.75 70 1955 2234 232 psi working pressures. Sups;40/Dyne- 25 27.4 2.0 260 70 887 1013 105. Thread is UL end ULC Listed for wet, __ _ we 1,408 — --1.873-- 2.54 51 2002----2288 233 dry and pro-action sprinkler systems and 32 35.8 2.8 3,7E 51 908 1038 108 FM Approved for use in wct systems, Super 40/Dyna-Thread can be"hot-dip" 1W 1,639 2.290 3,22 44 2115 2418 251'. galvanized to arrest FM requirement for 40 41.6 14 4.79 44 959 1097 11- dry systems. Super 40/Dyna-Thread is 2' 2,104 3.050 4,57 30 1821 2196 228 approved for all threaded couplings and 50 53.4 4,5 6.90 30 871 696 103 welded=dots and is suitable for all roll- gmoved,and plain-end fittings. (See American Tubc and Pipe was acquired by Allied Tube and Cond tit on February 1, listing information). 1997.The engineered lightwall and standard wall family of products although they Tho internal surface of all black Fits have dm$errsrt names are the same in all respects with regard to strength,weight, bundle count,listings anti approvals.Far example, shall be coated with Allied Tube& Dyrra-Flow and Super Flo arc the same product as 4M) 4.. 4/1) Conduit Antibacterial Formula"A.BF" are Dyne Thread and Super 40.XL is manufeotnred with Exterior galvanized coating.13LT is manufactured with Black leoque coating Lusted Approved Listed Project. tipainkler Contractor: Dame: Engineer: Specification Reference. Systern T pa: Locations: Commaanta: S3-4 , . tqC01 F/o w Tyco Fire Control Products BlazeMaster FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale, Pennsylvania 19446 www.tyco-fire.com TECHNICAL SERVICES TEL: (800) 381-9312 • F.ix: (800) 791-5500 E-MAIL: techsenr@tycofp.com 7a-4FitaVZSE" ";.:'4,-4;itallaTZ,..***15- 14tM:50: 01.)1.L,.:"� i A� ..„.,..:.tsi✓ a:., •. mar w: Iii:.: :'''':I. 1k f No. 19-1.5 TD915 4-1.1.20 9/2001 14L m.�s,m�..w.. . . Introduction Tyco Fire Products (TFP) BlazeMaster.CPVC pipe and the same time,they provide superior heat resistance and fittings are designed exclusively for use in wet pipe strength as compared to traditional CPVC and PVC piping automatic fire sprinkler systems. They are made from a materials used in the plumbing trade. Various adapters are specially developed thermoplastic compound composed of available to connect CPVC pipe to metallic piping.All female post chlorinated polyvinyl chloride (CPVC) resin and state of pipe thread adapters have brass inserts for durability. the art additives. TFP BlazeMaster'CPVC products are Grooved adapters connect directly to grooved end valves easier to install than traditional steel pipe systems, and at and metallic pipe, with flexible grooved end couplings. Technical Data Sizes: '/4'-3" Manufacture Source: U.S.A. Maximum Working Pressure: 175 psi Material: Approvals: UL, FM, CUL, NSF, Dade County, LPCB, Pipe: ASTM F442, SDR 13.5 MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and Note: See current TFP BlazeMaster Installation Instructions and ASTM F439 (Sch. 80) Technical Manual,for exact listing/approval information Color: Orange Pipe Nom.Pipe Size Avg. 0.D.Inches Avg. I.D. Inches Wt. Lbs./Ft. Wt.IIzO filled Pipe Lbs./Ft. Ft.of Pipe per Lift Wt.per Lift Lbs. 3/4" 1.050 0.874 0.17 0.43 7875 1413 1.315 1.101 0.26 0.67 5040 1320 1.660 1.394 0.42 1.07 2835 1191 1'/2" 1.900 1.598 0.55 1.40 2205 1136 2" 2.375 2.003 0.86 2.20 1260 1063 2 '/2" 2.875 2.423 1.26 3.22 IIMEME 1531 3" 3.500 2.952 1.87 4.79 720 1344 Fittings To T/O' T/O MR 45° Elbow 11111V\ T/O -Reducing 2 90° Elbow �`1 90°Elbow :'. T/d T/O . gin li I 1 1 i Part No. Size Sch. I/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt. 80050 '/." 40 '/6" 0.08 lb. No. Size Sch. 1 2 Ib. 80025 '/" 40 8/+e" 0.09 Ib. 80051 1" 40 3/6" 0.11 lb. 80032 1"x'/." 40 "/,6" "/,a" 0.16 80026 1" 40 '/+" 0.14 lb. 80052 1'/." 40 3/4 0.20 lb. 80027 1'/4" 40 '/6" 0.21 lb. 80053 1'/2" 80 '/+6" 0.31 lb. 80028 1'/2" 80 1'/,6" 0.40 lb. 80054 2" 80 '/." 0.56 lb. 80029 2" 80 1'/4" 0.79 lb. 80055 2'/2" 80 3/." 0.89 lb. 80030 2'/z" 80 1'/z" 1.14 lb. 80056 3" 80 1" 1.19 lb. 80031 3" 80 113/18" 1.82 lb. 1 1 r/o I i 1 T/O' Tee T/° Reducing a _ Cross ���� Cross 11114 -� T/O f 1 T/0 # -I, T/0° I T/O s T/0' I T/O' T/0 I/O Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt. 80000 3/4" 40 5/6" 0.11 lb. No. Size Sch. 1 I 2 lb. 80009 '/." 40 9/,6" 0.13 lb. 80001 1" 40 3/4' 0.19 lb. 80015 1"x 3/4" 40 "/,6" "/,6" 0.28 80010 1" 40 t5/16" 0.23 lb. 80002 11/4" 40 7/6" 0.26 lb. 80011 1'/4" 40 5/16" 0.34 lb. 80003 1'h" 80 1" 0.51 lb. 80012 172" 80 1'/,6" 0.67 lb. - 80004 2" 80 13/6" 0.90 lb. 80013 2" 80 13/6" 1.00 lb. 80005 2'/2" 80 1'/,6' 1.59 lb. 80014 2'/2" 80 19/16" 1.91 lb. 80006 3" 80 11'/,6" 2.41 lb. 80008 3" 80 1'3/18" 2.89 lb. gym..". -{�T/O I/O 1 T/O I fl I , . Coupling _. _ _ �. Cap _ > Reducer _ ii _._ _ tsmsciss-As Bushing • Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt. 80200 1"x'/4" 40 '/,6" 0.04 lb. 80075 '/4" 40 /a" 0.07.lb 80100 '/" 40 5/ " 0.04 Ib. 80201 1'/4"x'/4" 40 '/,6" 0.11 lb. 80076 1" 40 '/e" 0.11 lb. 80101 1" 40 '/e" 0.06 lb. 80202 1'/4"x 1" 40 5/,6" 0.12 lb. 80077 1'/4" 40 '/,6" 0.12 lb. 80102 11/4" 40 '/2" 0.10 lb. 80203 11/2"x'/4" 80 5/e" 0.16 lb. 80078 1'/2" 80 3/,6" 0.25 lb. 80103 1'/2" 80 5/6" 0.20 lb. 80204 172"x 1" 80 '/2" 0.14 lb. 80079 2" 80 '/,6" 0.38 lb. 80104 2" 80 5/e" 0.31 lb. 80080 2'/2" 80 '/16" 0.67 lb. 80205 1'/z"x 1'/4" 80 '/e" 0.17 lb. 80105 21/2" 80 '/e" 0.58 lb. 80206 2"x'/4" 80 '/4" 0.27 lb. 80081 3" 80 '/,6" 0.91 lb. 80106 3" 80 1" 0.88 lb. 80207 2"x 1" 80 "/16" 0.26 Ib. 80208 2"x 1'/4" 80 9116" 0.24 lb. I I no 80209 2"x 1'/2" 80 '/,e" 0.19 lb. Grooved 80215 2'/2"x 1" 80 1151,6" 0.42 lb. Coupling _ __ _ pipe 0.D. 80214 2'/2"x 1'/4" 80 1'/4" 0.45 lb. Adapter -1 80213 272"x 1'/2" 80 15/6" 0.46 lb. 80211 2'12"x 2" 80 19/,6" 0.29 lb. Part No. Size Sch. T/O Wt. Pipe OD 80210 3"x 2" 80 2'/16" 0.72 lb. 80160 1'/+"x 174" Grooved 40 2 5/,6" 0.78 lb. 11/4"(1.660") 80212 3"x 2'/2" 80 115/,6" 0.47 lb. 80161 1'/2"x 1'/2" Grooved 80 2 5/16" 0.95 lb. 1'/2"(1.900") 80162 2"x 2" Grooved 80 2 5/,6" 1.42 lb. 2" (2.375") i 80163 2'/2"x 2'/2" Grooved 80 2 5/16" 2.28 lb. 2'/2"(2.875") �►-- 80164 3"x 3" Grooved 80 21/4" 3.00 lb. 3"(3.500") Reducing :NI T 80168 3" x 76.1 mm Grooved 80 2'/4" 2.72 lb. 76.1 mm (3.000") Tee tiw , rro' Tro4 T/O Part - - - - - - _ - T/O Wt. No. Size Sch. 1 2 3 lb. Female :Till 80132 3/4"x 3/4"x 1" 40 '/4" '/4" 5/i" 0.14 Adapter � 80133 1"x'/4"X'/4" 40 '/2" "lie" 3/4" 0.14 80134 1"x'/4"x 1" 40 5/6" 3/4" 3/4" 0.17 Part No. Size Sch. T/O Wt. 80260 1"x 1"x'/4" 40 '/4" '/4" "/,6" 0.16 80142 '/."x'/4"NPT 40 6/i" 0.41 lb. 80135 1'/."x 1"x'/." 40 '/,6" '/4" 'S/,6" 0.21 80145 1"x 1" NPT 40 '/4" 0.63 lb. 80136 1'/4"x 1"X 1" 40 "/,e" '/4" 5/,6" 0.22 80146 1'/4"x 1'/4" NPT 40 '/e" 1.03 lb. 80137 1'/."x 1"x 1'/4" 40 "/6" 15/,6" "/,6" 0.26 80147 11/2"x 11/2" NPT 80 1" 1.42 lb. 80261 1'/ X 11/4"X'/4" 40 5/e" 5/e" '/6" 0.23 80148 2"x 2" NPT 80 1'/8° 2.66 lb. 80262 V/4" X 1'/4"x 1" 40 3/4" 3/4' '/a" 0.26 80138 174"X 11/4"X 1 72" 80 1" 1" 1" 0.43 rro 80140 1'/2"x 11/4"x'/4" 80 '/2" 5/6" 1" 0.36 4., 80141 11/2"x 174"X 1" 80 '/2" 5/1" 1'/e" 0.38 Male _____ ___^_ 80263 11/2"x 172"x 3/4" 80 9/16" 9/16" 1" 0.36 Adapter .� r-� 80264 172"X 11/2"x 1" 80 9/,e" 9/,e" 1" 0.38 80275 1'/2"X 1'/2"X 11/4" 80 '/e" 7/8" 1" 0.45 Part No. Size Sch. T/O Wt. _ 80265 2"x 2"x'/4" 80 3/4" '/4" 1'/6" 0.61 80157 '/." x'/4" NPT 40 15/,6" 0.33 lb. 80266 2"x 2"x 1" 80 '/9" '/i" 1'/e" 0.66 80158 1" x 1" NPT 40 1'/e" 0.56 lb. 80274 2"x 2"x 174" 80 1" 1" 1'/e" 0.74 80267 2"x 2"x 172" 80 11/6" 1'/e" 1'/e" 0.78 1rT/O 80271 21/2"x 2'/z"X 1" 80 1"/,e" 117,8"" 19/,6" 1.43 80272 21/2"x 21/2"x 174" 80 1"/1e" 1"/,e" 1 9/16" 1.46 Reducing _____ _ 80273 21/2"x 272"x 1'/2" 80 1"/,6" 1 11/,6"4 19/1e" 1.48 Coupling 80276 272"x 2'/2"x 2" 80 1"/,e" 1"/,e" 19/,6" 1.50 ,..._-, 80270 3"x 3"x 11/2" 80 4 1 3/4" 1'/4" 1"/16" 2.28 Part No. Size Sch. T/0 Wt. 80268 3"x 3"x 2" 80 1'/4" 13/4" 1'/4" 2.25 80220 _ 1"x 3/4" 40 - '/e" 0.08 lb. 80269 3"x 3"x 2'/2" 80 13/4" 1'/4" 115/,6" 2.44 K) T/O TO . Sprinkler Head Adapter I _ Sprinkler Head Adapter _ with Brass Threaded Insert �=I�� with Brass Threaded Insert !1� Part No. Size I Sch. T/O i Wt. 1 Part No. Size 1 Sch.i T/0 I Wt. 80175E 3/4"X'/2" NPT 80 '/+e" 0.20 lb. 80175W 3/4"x '/2" NPT 40 '/16" 0.19 lb. 80176E 1"x 1/2" NPT 80 '/,e" 0.22 lb. 80176W 1"x 'h" NPT 40 7h6" 0.18 lb. 80177WL 3/4"X '/2"NPT 40 9/16" 0.16 lb. 80179 1 x 3/4" NPT 40 3/4" 0.43 lb. Tio' 1 T/0 --•- y Back-to-Back Cross Sprinkler Head Adapter F�: with Brass Threaded Insert 011110 1: . (Spigot) _ T with Brass Threaded Insert I T/O' I T/O' Part No. Size Sch.I T/O 1 Wt. Part T/O Wt. 80177L 3/4"x 1/2" NPT 40 '/2" 0.16 lb. No. Size Sch. 1 2 lb. 80178 1"x '/2"NPT 40 1/2" 0.20 lb. 80462 1"x 1"x '/2"NPT x '/2" NPT 40 5/s" 1'/e" 0.46 80463 1"x 1"x '/2"NPT x 1/2" NPT 40 5/8" 16/16" 0.47 ion T/O' Sprinkler Head Adapter °°"— >; 90° Elbow 1 = T/O •max: �,'., + with Brass Threaded Insert " u�� T/0 Back-to-Back Tee I MCC: ` r with Brass Threaded Insert I -I ,--tr` t T/o' T/O' Part I/O 1 Wt. i I Part Size Sch. T_/O Wt. Size Sch. No. 1 2 Ib. No. 1 2 lb. . 80199 3/4"X '/2" NPT 40 5/e" 15/,6" 0.20 80459 1"x '/z"NPT x '/2"NPT 40 "/16" 15/ie" 0.48 80189 1"x '/2" NPT 40 77/16" 13/,6" 0.26 80460 1"x '/2"NPT x '/2"NPT 40 "/16" 11/4" 0.46 Part T/O Wt. No. Size Sch. 1 2 3 lb. 80250 3/4"x 3/4"X '/2"NPT 40 5/e" s/e" 1" 0.22 1 80251 1"x 1"x '/2"NPT 40 "/,e" "/,e" 13/he" 0.29 1111P- --e f 80249 1"X 1"X 1"NPT 40 t5/,e" 15/,e" 1'/,e" 0.73 Sprinkler Head Adapter .,`v "`` T/Q' 80256 1'/4"x 1"x'/2"NPT 40 '/te" 9h6" 1'/e" 0.30 Tee -"~'-"— ,---------1* 80252 1'/4" x 1'/4"x '/2"NPT 40 '/,e" '/,e" 1'/e" 0.31 with Brass Threaded Insert 'r 80257 1'/2" x 11/4"x '/2"NPT 80 9/,e" 5/e" 17/16" 0.43 To. I Y I I nd 80254 1'/2" x 1'/2"X '/2" NPT 80 9/,e" 9/,e" 17/,6" 0.46 80258 2"x 1'/2"X 1/2"NPT 80 '/2" 5/e" 15/e" 0.56 80253 2" x 2"X1/2"NPT 80 '/2" '/2" 15/e" 0.62 Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten(10)years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten(10)years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse,improper installation,corrosion,or which have not been installed.maintained,modified or repaired in accordance with applicable Standards of the National Fire Protection Association(NFPA),and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced.at Tyco Fire Products sole option. Tyco Fire Products neither assumes,nor authorizes any person to assume for it.any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE,IN CONTRACT,TORT,STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY,FOR INCIDENTAL.INDIRECT.SPECIAL OR CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT LIMITED TO LABOR CHARGES,REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES. AND IN NO EVENT SHALL TYCO FIRE PRODUCT'S LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. .4 • THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED.INCLUDING ' WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, tgCO/Flow Control/Tyco Fire Products - POTTER uLc ci® vs R..D ® VANE TYPE WATERFLOW APPROVED SWITCH WITH RETARD Potter electric Signal Company 2081 Craig Rd., / St. Louis, MO 63146 / (800)325-3936 / (314)878-4321 SERVICE PRESSURE UP TO 450 PSI CHARACTERISTICS FOR 2" TO 8" PIPE SIZES 250 PSI FOR 10" PIPE SIZE U.L. LISTED AND F.M. APPROVED MINIMUM FLOW RATE FOR ALARM-10 GPM DIMENSIONS & WEIGHTS: See Fig. 2 ENCLOSURE: Cast Aluminum Finished: Red Enamel CONTACT RATINGS: Two sets of S.P.D.T. (Form C) 15.00 Amp. @ 125/250V. AC 0.50 Amp. @ 125V. DC 0.25 Amp. @ 250V. DC • 2.50 Amp. @ 0-30V. DC • Resistive ENVIRONMENTAL LIMITATIONS: 40°F/120°F 4.5°C/49°C General Purpose for Indoor Use ` CAUTION: This device is not intended for a applications outdoors or in explosive environments. { : 1 SIZES AVAILABLE: U.L. - For Schedule 40 Pipe: 2" thru 10" • - For Schedule 30 Pipe: 8" _ _ 'F.M.-- For Schedule 40 Pipe:2" thru 6" For Schedule 30 Pipe: 8" and 10" f z SERVICE USE: ~ 'ti, S b t ' Automatic Sprinkler NFPA-13 -� ��� �a One or Two Family Dwelling NFPA-13D ' Central Station NFPA-71 Local NFPA-72A • Auxiliary NFPA-72B Remote Station NFPA-72C Proprietary NFPA-72D U.S. Pat. Nos. 3,912,247 OPTIONAL: Cover Tamper Switch •,osz,s» Order Stk. No. 5420220 The Model VSR-D is a vane type waterflow switch for The flow condition must exist for a period of time necessary use on wet sprinkler systems. It is UL Listed for use on to overcome the selected retard period. steel pipe;schedule 40 sizes 2"thru 10"and schedule 30 size B" and has FM approvals for schedule 40 steel ENCLOSURE:The unit is enclosed in a general purpose, pipe in sizes 2" thru 6" and schedule 30 pipe in sizes indoor use cast aluminum housing. The cover is held in 8" and 10 1'. place with two tamper resistant screws which require a spe- cial key for removal.A field installable cover tamper switch The unit may also be used as a sectional waterflow is available as an option which may be used to indicate detector on large systems. unauthorized removal of the cover. See Bulletin 751 for installation instructions of this switch. The unit contains two single pole, double throw, snap RETARD ADJUSTMENT: The unit has an adjustable action switches and an adjustable pneumatic retard. pneumatic retard to prevent false alarms due to water . The switches are actuated when a flow of 10 gallons surges.The retard is adjustable from 0 to approximately 75 per minute or more occurs downstream of the device. seconds. 2-88 CAT. #A010 PAGE 1 _.7. _: , ..: - VSRaD +- -" - -. ...r••�..-d'ti" .!4tkt+. -•n• A- ..a. ,-rii-'�`vraa* -.'.b�,3r'ra•[i i -. Potter Electric Signal Company 2081 Craig Rd., / P.O.. Box 28480 / St. Louis, MO 63146 / FAX: 314 878 7264 VSR-D INSTALLATION FACTORY ADJUSTED FIG. 1 SENSITIVITY SPRING. DO NOT ADJUST RETARD ADJUSTMENT TO CHANGE TIME TURN KNOB I' (EITHER DIRECTION)FOR .1 DESIRED TIME DELAY. 1,11. TIGHTEN NUTS USE THE MINIMUM AMOUNT i ALTERNATELY TO OF RETARD NECESSARY TO CW� - EVENTUAL PREVENT FALSE ALARMS. -.�` -I 50 FT.-LBS. A EQ SETTING IS USUALLY OF TORQUE. ADEQUATE FOR THIS. �� { I MOUNT ON PIPE SO ARROW ON SADDLE NNINNb. Lk POINTS IN DIRECTION OF WATERFLOW, • . %�/ ROLL PADDLE IN TO INSTALL= 1 OPPOSITE DIRECTION FOR DRILL AND 2 V SIZES OF WATER FLOW. DRILL 1 I/4-HO LE. ' FOR ALL OTHER SIZES DRILL 2'.HOLE d 4iI ' °v- I APPROX. RETARD SETTING UN SECS 0 A E C D E I , I�, Y 0 10-25 20-40 35-55 50-70 10-10 i OPTIONAL: COMM Tamper SirN Ch Order Stk. No. 5420220 01,1111111.DIRECTIDN OF WATERFLCW ./1� a DWG.5400710-305 SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL CAUTION: ")•,,, AN UNINSULATED SECTION OF A SINGLE CONDUCTOR IS NOT PERMIT i TED TO BE LOOPED AROUND THE TERMINAL AND SERVE AS TWO SEPARATE CONNECTIONS.THE WIRE MUST BE SEVERED TO SERVE INCoiyllNG AS TWO SEPARATE CONNECTIONS,THEREBY PROVIDING SUPERVI- � � SION OF THE CONNECTION IN THE EVENT THAT THE WIRE BECOMES DISLODGED FROM UNDER TERMINAL. OUTG pING`-- DWG. 5400710-31 . ._ z a INSTALLATION INSTRUCTIONS: These devices may Clean the inside of the pipe of all growth or other mate- be mounted in a horizontal or vertical pipe. On horizon- rial for a distance equal to the pipe diameter on either tal pipe they should be installed on the top side of the side of the hole. pipe where they will be accessible.The units should not Roll the vane so that it may be inserted into the hole; do be installed within 6 inches of a fitting which chances the not bend or crease it. insert the vane so that the arrow direction of the water-flow or within 24 inches of a valve on the saddle points in the direction of the waterflow. or drain. Install the saddle strap and tighten nuts alternately to an Drain the system and drill a hole in the pipe using a cir- eventual 50 FT.-LBS. of torque. See Fig. 1 above. cular saw in a slow speed drill.The 2" and 21/2" devices The vane must not rub the inside of the pipe or bind in require a 11/4" hole; all other sizes require a 2" hole. any way. TESTING The frequency of testing for the model VSR-D and its associated protective monitoring system should be in accordance with applicable NFPA Standards and/or the authority having jurisdiction,but under no circumstances less than bi-monthly. CAT.#A010 PAGE 2 VIIMIENUI • TESTANDRAI DR A I .,A !ash `�, ) f," F4 zA,- d r Mk�e1 .7�1'f�d kS hy�( ��p„� r ,firs AN' u r�wY tm Syp. s ' A�Mj ,t.v. _ f kk�'�� •:e ' : h d ,i " A jog!d'Y_eren A S f:Nt;t ID 1? TESTAE- :{ ' I " ,y � AC.F.AV;C0 Stith Okor ILL ,t ON '4'` - 4 { • �j! �t,:r a�a T• • The AGF Manufacturing Co., Inc. Model 1000 has been designed to provide both the Test Function and the Express Drain Function in a multi story installation. • Complies with all requirements of NFPA-13, and NFPA-13R • Complies with all requirements of NFPA-13D (HOUSING) • Positive Shut Off • Single Locking Handle • Tapped 1/z" for Pressure Gauge • Tamper Resistant Orifice permanently installed • Available with all required Orifices • Orifice size noted on Indicator Plate ■ Lightweight and compact (11/4" weighs 5 lbs.) • 300 PSI Rating • Fused, tempered, tamper resistant Sight Glasses . Ag0 MODEL 1000 300 PSI <> TESTANDITI:::.?.-- 3/4 ,1 . 1 1, 1 1/4 " 1 1/2 2 " 'A'NOT FM APPROVED PLAN VIEW FRONT VIEW 4 j O FROM 0 BRANCH GAUGE OUTLET 14 PROVIDED I I= li TO DRAIN . Iii OFF 1 , = ✓• _I illi~gO� STREET EL --- off) 1 I..O FRONT VIEW/HORIZONTAL INSTALLATION STREET EL TO DRAIN OR PIPE E l j I 111111. _- _y TO DRAIN F IIIIFOR RIGHT HAND/STRAIGHT INSTALLATION TO DRAIN . ` E II■ 4 APPROVALS • UL and ULC Listed : i (0 • FM Approved except 3/4" U • NYC BD. of S&A CAL. NO. 720-87-SM • CA. State Fire Marshall ORIFICE SIZE PROVIDED-3/s—7/16'-'-• T/2—' 17/32'-'•5/8**.-.'3/4** DIMENSIONS—INCHES MATERIAL LIST SIZE A B C D E F G H PART MATERIAL 3/4 5'/16 13/4 23/8 4'/8 33/6 13/4 49/16 65/16 HANDLE STEEL STEM ROD BRASS C.P. BRONZE 1 5'/16 13/4 23/8 4'/e 33/e 13/4 49/16 65/16 BALL 1 '/4 57A6 13/4 2'/e 45/8 35/16 115/16 51/2 77/16 BODY BRONZE VALVE SEAT GLASS INPREGNATED TEFLON 1 '/2 67/16 13/4 311/16 57/16 31/2 23/s 8'/i6 10'/i6 INDICATOR PLATE STEEL 2 6'/16 13/4 3"A6 57/16 3'/2 23/e 81/16 10'/16 HANDLE LOCK SPRING STEEL SIGHT GLASS (2) FUSED TEMPERED GLASS ** Available on 174"to 2"size units only. • AGF MFG. CO. JOB NAME: _ ( Box 4437, 150 Mt. Bethel Rd. Warren, N.J. 07059-0437 ARCHITECT: MADE IN U.S.4 Telephone (908) 604-6471 ENGINEER: Fax (908) 604-6501 CONTRACTOR: 1000 8/94 IOLCO INCORPORATED CORONA, CA (909)737-5599 0 C 0 Fig. 27 & 27A "Stand-Off" Hanger/Restrainer for CPVC Plastic Pipe Size Range—3/4" & 1" CPVC Plastic Pipe*. - Material— Carbon Steel, Pre-Galvanized. Function—Designed to be used as a hanger/restrainer**for CPVC piping where the "stand-off' design will ease installation by eliminating the need for \\ wood blocking. Features: '' • Flared edge design protects CPVC from any rough or abrasive surfaces. It� • Snap-in retainers hold pipe firmly in place during installation. • The "Stand-Off' design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting Fig. 27 surface orientation. • Attaches easily to wood structure with 2 hex head self-threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16" sockets, o eliminating impact tool damage to pipe Approvals- Underwriters Laboratories Listed in the U.S. (UL) and Canada j o ,-- (cUL) to support automatic fire sprinkler systems. Meets and exceeds the ( ` ';requirements of NFPA 13, 13R, and 13D. Fig. 27A 'v **Important Note—When installed in slot opening on Fig. 27, Fig. 27A . \ provides additional stability and satisfies the UL vertical restraint requirement ' where needed. Order By—Fig. 27: By figure number and CPVC pipe size. - \`\ Fig. 27A: By figure number and CPVC pipe size. ) 114�U.S. and International Patent application in process. It � ' *for other sizes consult factory. Fig. 27 and Fig. 27/27A have also been tested by U.L. mounted on 3/8" Fig. 27/ Fig. 27A composite wood web material (such as TJI Series/Trus Joist MacMillan) Combination without the use of back up wood blocking. When using Fig.27 & 27A in combination on 3/8"web to satisfy the UL requirement for vertical restraint, FIG.27 install 2 reinforcing speed nuts (Fig. 27B). Fig. 27B is UL Listed only when w/FIG.27A used with Tolco products. ■_■', FIG.27B � FIG.27 1 Fibm W/FIG.27A MO I ill . I il FIG.27 FIG.27 rill! OM= FIG.27 FIG.27 W/FIG.27A F1G.27 —;II IL —V . - Ii1V., millIMENImmanagsg . (0 Typical Applications 01 • ES-A-2000B A Series 2000B A M E S Double Check Valve Assemblies FIRE&WATERWORKS° Sizes: .1/2" —2" (15 -60mm) .-- it Features --. ', -� : = • Ease of maintenance with only one cover 2°20008 HC • Top entry (50mm) • Replaceable seats and seat discs :-. ,, al• Modular construction • Compact design •; '/z"-2" (15-.50mm)Cast bronze ` body construction /�"2000B • :Top mounted ball valve test cocks (20rnlm).; .': *.;Low pressure drop. • No special tools required Series 2000B Double Check Valve Assemblies shall be installed at referenced cross-con- • %"-1° (15-25 mm)have nections to prevent the backflow of polluted water into the potable water supply.Only tee handles - those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation, frequency of Available Models testing or other installation requirements. Suffix: These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are B=_Quarter_..turn.ball valves____ approved_by_the_Foundation_for Cross_Connection_Control_and_Hydraulic aesearch at the LBV- less ball valves University of Southern California ° LH- locking handle ball valves(open position) Specifications SH- stainless steel ball valve handles A Double Check Valve Assembly shall be installed at each noted location.The assembly HC- 21/2"inlet/outlet fire hydrant fitting shall consist of two positive seating check modules with captured springs and rubber seat (2' valve) discs.The check module seats and seat discs shall be replaceable.Service of all internal Prefix: components shall be through a single access cover secured with stainless steel bolts.The U- union connections assembly shall also include two resilient seated isolation valves and four top mounted, re- silient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Pressure — Temperature Hydraulic Research at the University of Southern California.Assembly shall be an Ames Temperature Range:33°F-140°F Company Series 200013 (5°C-60°C) Approvals Maximum Working Pressure: 175psi t ASSE,IAPMO,CSA,UPC (12 bars) • Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Standards • Model LBV is not listed. ASSE Std. 1015,AWWA Std. C510 u UL Classified(LBV models only)3/4"-2° (19-50mm) c IAPMO PS31,CSA B64.5 * Horizontal and vertical"flow up"approval on all sizes. @ S P® �o Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative • Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Dimensions - Weights A 7 i IINIM"_ 1 P# 11._...�i■ ®�� I F H _I. --- 41 G Suffix HC-Fire Hydrant Fittings dimension"A"=231/2"(594mm) 6 Size(DN) A B C F Dimensions H I Weight Model in, mm in. mm in. mm in. mm in. mm in. mm in, mm in. mm Ibs, kgs. 20008 h 15 10 254 46/a 117 2'/�a 62 5 127 33/e 85 25/6 59 2'ha 52 4.5 2 2000B M3 3/ 20 11'%6 282 4 102 3'%6 79 6'16 157 3%6 87 2% 54 1544 33 5 2.3 20008 1 25 13'/ 337 5'/ 130 4 102 711 191 3% 85 1"1a 43 1"1a 43 12 5.4 20008 1% 32 16% 416 5 127 35As 84 91/2 241 5 127 3 76 2 50 15 6.8 20008 11/2 40 163/ 425 4'/ 124 3'h 89 93/+ 248 513/6 148 3'%6 79 2"16 68 15.86 7.2 20008 2 50 191/2 495 6'/ 159 4 102 13%6 340 6'/6 156 37/16 87 2"16 68 25.75 11.7 Strainer sold separately Capacities bars psi 11/4"(32mm) As compiled from documented Foundation for Cross-Connection Control 1 14 and Hydraulic Research at the University of Southern California lab tests. a .8 12 ea 'Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) J •5 8 .4 6 liii bars 8 12 1/2"(15mm) * ai .3 4 N ca • .7 10 a .1 2 • .4 6 0 0 E- 1_2- - eP 0 10 1 5 3 2 340 3.0 0- 60 70 80 90 100 110 120 pm w 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm za..,' a. 0 0 15 -._ - fps .,Mb.,:l1' • AP 0 2 4 6 8 10 12 gpm 4.6 mps 0 7.6 15.2 22.8 30.4 38 45.6 fpm Flow Rate 5 7.5 10 fps bars psi 11/ "(40mm) * 1.5 2.3 3.0 mps rn .8 12 bars psi %"(20mm) Flow Rate co 3 .7 10 1 N 1.5 22 i .5 86 L'12 .96 14 m .3 4 •■�..�� �.. m .69 10 a .1 2 a .41 6 Apo 10 20 30 40 58 6D 70 80 90 100 11D 120 gpm .14 2 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.5 10 15 fps AP 0 5 10 15 20 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps II 19 38 57 76 95 114 133 152 171 190 Ipm Flow Rate 7.5 15 2.3 4.6 mpps .8 12 bars 2"(50mm) w bars psi 1"(25mm) * Flow Rate y y 1.1 16 0 .7 10 0 .8 12 -r .5 6 8 y .7 10 m .4 6 ��f .5 8 m .3 4 m .4 6 �� aNi .1 2 .3 4 _ 0 0 D. .1 2 - 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 Ipm 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm AP 1.5 2.3 3.0 19 38 57 76 95 114 133 152 171 190 209 2281pm 5 7.5 3.0 4 15 fps 5 7.5 10 15 .6 mps 1.5 2.3 3.0 4.5 fps Flow Rate mps Flow Rate IMPORTANT Inqinrities for local uire installation with govern requirements.g autho A M E S ISO 9001 I l` A Division of Watts Industries FIRE&WATERWORKS www.amesfirewater.com CERTIFIED �.�- ___ • 875 National Drive • Suite #107 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 ES-A-20008 0313 ©Ames Co.2003 Printed in U.S.A.